Page 1: Power factor correction and harmonic · PDF filePower factor correction and harmonic filtering How to choose the right power factor correction capacitor bank ? The recommended method

Catalogue

2007

Power factor correction and harmonic filtering

Propivar capacitors and MV banks

Page 2: Power factor correction and harmonic · PDF filePower factor correction and harmonic filtering How to choose the right power factor correction capacitor bank ? The recommended method

Power factor correction and harmonic filtering

Contents

Overview 2MV capacitor bank selection guide 2

Propivar capacitors 4Insulation level 7.2 kV (20/60)50/60 Hz 6Insulation level 12 kV (28/75)50/60 Hz 8Insulation level 17.5 kV (38/95)50/60 Hz 9Insulation level 24 kV (50/125)50/60 Hz 10Insulation level 36 kV (70/170)50/60 Hz 11

MV capacitor banks 12Fixed compensation 12

CP214 fixed capacitor bank 13Insulation level 7.2 kV (20/60) - 50/60 Hz 13Standard type (slightly polluted network) 13Insulation level 12 kV (28/75) - 50/60 Hz 14Standard type (slightly polluted network) 14

CP214 SAH fixed capacitor bank 15Insulation level 7.2 kV (20/60) - 50/60 Hz 15SAH type (highly polluted network) 15Insulation level 12 kV (28/75) - 50/60 Hz 16SAH type (highly polluted network) 16

CP227 fixed capacitor bank 17

Insulation level 7.2 kV (20/60) - 50/60 Hz 17Standard type (slightly polluted network) 17Insulation level 12 kV (28/75) - 50/60 Hz 18Standard type (slightly polluted network) 18Insulation level 17.5 kV (38/95) - 50/60 Hz 19Standard type (slightly polluted network) 19Insulation level 24 kV (50/125) - 50/60 Hz 20Standard type (slightly polluted network) 20Insulation level 36 kV (70/170) - 50/60 Hz 21Standard type (slightly polluted network) 21

MV capacitor banks 22Automatic compensation 22

CP253 automatic capacitor bank 23Insulation level 7.2 kV (20/60) - 50/60 Hz 23Standard type (slightly polluted network) 23Insulation level 12 kV (28/75) - 50/60 Hz 25Standard type (slightly polluted network) 25

CP253SAH automatic capacitor bank 26Insulation level 7.2 kV (20/60) - 50/60 Hz 26SAH type (highly polluted network) 26Insulation level 12 kV (28/75) - 50/60 Hz 28SAH type (highly polluted network) 28

CP254 automatic capacitor bank 29Insulation level 17.5 kV (38/95) - 50/60 Hz 29Standard type (slightly polluted network) 29Insulation level 24 kV (50/125) - 50/60 Hz 30Standard type (slightly polluted network) 30Insulation level 36 kV (70/170) - 50/60 Hz 31Standard type (slightly polluted network) 31

Page 3: Power factor correction and harmonic · PDF filePower factor correction and harmonic filtering How to choose the right power factor correction capacitor bank ? The recommended method

Power factor correction and harmonic filtering

How to choose the right power factor correction capacitor bank ?The recommended method consists of five successive steps

Step 1: basic data collection

Network characteristics:bvoltage U (V)bnetwork frequency f (50 or 60 Hz).

Characteristics of the installation:b insulation voltage U insulationb rated power of the transformer Sn (kVA)b transformer short circuit voltage Usc (%)bexisting capacitor bank (Qc (kvar), type of capacitor bank,…).

Operating conditions:benergy billsbmeasurements of power: P (kW) cos phi.

Step 2: calculation of the reactive power Qc (kvar)

DB

1096

43

The reactive power is determined either: b from the electricity bills, depending on the method of recording the consumption of kvar applied by the energy supplierb from the electrical data of the installation. The aim is:bnot to pay for the consumption of reactive energy and to ensure optimum use of the transformers, cables and control and protection switchgearb to satisfy the standards currently in force: compliance with a minimum cos phi, energy quality standards.

Step 3: choice of type of capacitor bank according to the harmonics

The presence of non-linear loads (variable speed drives, UPS, etc.) creates harmonic currents and voltages. The compensation equipment is chosen according to the value of these harmonics.

beither the installation has no harmonics and there is no risk of resonance

V Select a capacitor bank for a slightly polluted network (see selection table in step 5)

beither the installation has harmonics and/or there is a risk of resonance

V Select a capacitor bank for a highly polluted network (see selection table in step 5)

b in the absence of information about the installation and as a precautionary measure

V Select a capacitor bank for a highly polluted network (see selection table in step 5)

Harmonic filteringTo improve the quality of electrical power, Merlin Gerin provides a range of compensation and filtering solutions.

The HV or MV filters that absorb the harmonic currents in the electrical installation consist mainly of capacitors associated with filtering reactors. They are used to: bbring the percentage of distortion back to the acceptable values recommended by the energy distributors band also compensate for the reactive power.

Schneider Electric can undertake compensation and filtering analyses.

Overview 0 MV capacitor bank selection guide

Page 4: Power factor correction and harmonic · PDF filePower factor correction and harmonic filtering How to choose the right power factor correction capacitor bank ? The recommended method

Power factor correction and harmonic filtering

Step 4: choice of type of compensation

Global compensationThe type of compensation should be chosen by taking into account the calculated reactive power Qc (kvar) and the apparent power Sn (MVA) of the upstream transformer.

Qc/Sn < 15% the reactive power of the capacitor banks is constant and they are started up or shut down when a predetermined kvar value is reached. It is an “on/off” type of operation.

V Fixed compensation

Qc/Sn > 15% the customer specifies automatic startup or shutdown for the capacitor bank (controlled by Varlogic varmetric relay). The reactive power of the capacitor banks is split into “steps” with the possibility of starting or stopping more or fewer steps. The reactive power corresponds to the change in load requirements

V Automatic compensation

Motor compensation b if there is no risk of self-excitation V The capacitor bank will be connected in parallel with the motor

b if there is a risk of self-excitation. V But it is only possible to connect to the motor terminals, the capacitor bank will be connected to the busbar independently of the motor.

Step 5: selection table

The recommended choice is based on the network insulation voltage, network harmonic pollution level and on the type of compensation.

b if the power of the capacitor bank to be installed is less than 600 kvar

V A low voltage solution is recommended

b if the power of the capacitor bank to be installed u 600 kvar.

V See the following table.

Insulation level 7.2 kV 12 kV 17.5 kV 24 kV 36 kVSlightly polluted network Fixed CP��4

CP��7CP��4CP��7 CP��7 CP��7 CP��7

Auto CP�5� CP�5� CP�54 CP�54 CP�54Highly polluted network Fixed CP��4 SAH CP��4 SAH

Auto CP�5� SAH CP�5� SAH

CP��7 SAH and CP�54 SAH as a specific order.

Overview 0 MV capacitor bank selection guide (cont.)

Page 5: Power factor correction and harmonic · PDF filePower factor correction and harmonic filtering How to choose the right power factor correction capacitor bank ? The recommended method

4

Power factor correction and harmonic filtering

PresentationA Propivar medium voltage capacitor is a steel case or tank provided with resin insulators. The tank comprises an assembly of capacitor elements having a maximum permissible rated voltage of 2250 V. When connected in series-parallel groups, they provide high power units for elevated system voltages. There are two types of capacitors:bwith internal fuses (single-phase capacitor)bwithout internal fuses (three-phase or single-phase capacitor).Each capacitor is normally provided with discharge resistors to bring the residual voltage down to 75 V 10 minutes after the capacitor has been switched off. If requested, the capacitors can be supplied without discharge resistors.ConstructionThe Propivar capacitors are composed of elements which include:baluminium foil electrodesba dielectric liquid with no PCB or chlorine and a polypropylene film. Compliance with standardsThe Propivar capacitor complies with standard NF C 54-102 and with the following standards:b IEC 60871, 1 and 2bBS 1650bVDE 0560bC22-2 N° 190-M1985bNEMA CP1.Capacitors with internal fuses comply with the following standards: NF C 54-102, IEC 60871-4.Protection by internal fusePropivar capacitors can be supplied with internal protection: each element or unit capacitor is equipped with a fuse. In the event of a breakdown of an element, the element is disconnected and isolated. Breakdown of a unit capacity may occur:bwhen capacitor voltage is close to its maximum amplitude. In this case, it is the power stored in the capacitances of the parallel elements which guarantees a current sufficient to rupture the internal fuse (fig. 1)bwhen capacitor voltage is close to zero. This current ensures breaking of the internal fuse (fig. 2).Advantages of this protection type:b instantaneous disconnection of the short-circuiting elementb lifetime of the capacitorb reduction in material costs and maintenancebcontinuity of service is ensuredbpossiblity of programming site maintenance.

Main characteristicsThe exceptional life of Propivar capacitors is due to their temperature withstand, small temperature rise, chemical stability and overvoltage and overcurrent withstand.Temperature withstandThese capacitors can be put into service at low temperatures without any special precautions being taken.At higher ambient temperatures, the temperature rise is very low, so they can be operated without any risk of modifying the insulation characteristics of the dielectric.Chemical stabilityTransient overvoltages in circuits and partial discharge levels in tanks cause accelerated ageing of capacitors. The exceptional life of Propivar capacitors is closely connected with the intrinsic properties of the dielectric liquid:bvery high chemical stabilitybhigh absorption capacity for gases generated during partial dischargesbvery high dielectric strength.Overvoltage and overcurrent withstandThe capacitors can accept:ban overvoltage of 1.10 Un for 12 hours a dayba power frequency overvoltage of 1.15 Un for 30 minutes a dayba permanent overcurrent of 1.3 In. The withstand of capacitors is verified by:v1 000 cycles at an overvoltage level of 2.25 Un (cycle duration 1 s)vageing tests at 1.4 Un.

The Propivar capacitors are used to compensate reactive power on medium and high voltage networks.

0523

12

Single-phase Propivar capacitor.

The Propivar capacitors are used to compensate reactive power on medium and high voltage networks.

0523

12

Single-phase Propivar capacitor.

E14

591

Propivar capacitor with internal fuses, composed of 4 groups connected in series, each group comprising 12 elements connected in parallel.

E14

445A

Fig. 1

E14

445B

Fig. 2

E14

591

Propivar capacitor with internal fuses, composed of 4 groups connected in series, each group comprising 12 elements connected in parallel.

E14

445A

Fig. 1

E14

445B

Fig. 2

Propivar capacitors

Page 6: Power factor correction and harmonic · PDF filePower factor correction and harmonic filtering How to choose the right power factor correction capacitor bank ? The recommended method

5

Power factor correction and harmonic filtering

Insulating voltage of the Propivar capacitors in accordance with IEC 60871-1 and 2 standard in the majority of european and several other countries:Highest voltage for equipment Um

kV 7.2 12 17.5 24 36Insulation level

Rms kV, 50 Hz-1 mn 10 20 28 38 50 70Basic impulse level (BIL) kV, 1.2/50 µs

40 60 75 95 125 170

In accordance with NEMA CP1 standard based on current practice in some countries of North America and others:Highest voltage for equipment Um

kV 5.5 15.5 19.8 27.5 38Insulation level

Rms kV, 50 Hz-1 mn 13 24 30 36 50 70Basic impulse level (BIL) kV, 1.2/50 µs

45 75 95 125 150 200

Environmental protection / biodegradabilityPropivar capacitor contains a dielectric liquid with no PCB or chlorine.

Other characteristicsService frequency 50 Hz - (available in 60 Hz, please consult us)Temperature range -25 to +45 °C Average loss factor at 20 °C after stabilisation

0.16 W/kvar with internal fuses0.12 W/kvar without internal fuses

Maximum rated reactive power (1)

three phase capacitors 450 kvarsingle phase capacitors 600 kvar

Capacitance value tolerance -5, +15 %Capacitance variation DC/C -3.5 . 10-4/°CConnection to resin insulators for cables with a section y 50 mm2

Tank welded steel Thickness 1.5 mmColour Grey RAL 7038Anticorrosion treatment

Fixing system 2 perforated brackets for M10 screw

(1) Other reactive powers, on request.

Propivar capacitors0

Page 7: Power factor correction and harmonic · PDF filePower factor correction and harmonic filtering How to choose the right power factor correction capacitor bank ? The recommended method

Power factor correction and harmonic filtering

DB

1130

10

Three-phase Propivar capacitor.

Three phase capacitorsNetwork voltage (V) 4160 3300 3000 2400 Ref.Capacitor voltage (V) 4160 3300 3000 2400Dimensions (mm)(H x L x D / b / H2)

Weight(kg)

50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz

300 x 347 x 190 / 135 / 120 33 50 60 30 37.5 25 30 15 20 3658405R300 x 347 x 190 / 135 / 120 34 100 120 60 75 50 60 30 40 3658406R400 x 347 x 190 / 135 / 220 43 150 180 90 115 75 90 45 60 3658407R500 x 347 x 190 / 135 / 320 51 200 240 120 150 100 120 60 80 3658408R500 x 347 x 190 / 135 / 320 52 250 300 150 190 125 150 75 100 3658409R600 x 347 x 190 / 135 / 420 61 300 360 180 225 150 180 90 120 3658410R700 x 347 x 190 / 135 / 520 69 350 420 210 265 175 210 105 140 3658411R

Three phase capacitorsNetwork voltage (V) 6600 6300 6000 5500 Ref.Capacitor voltage (V) 6600 6300 6000 5500Dimensions (mm)(H x L x D / b / H2)

Weight(kg)

50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz

300 x 347 x 190 / 135 / 120 34 50 60 45 55 40 50 35 40 3658336R300 x 347 x 190 / 135 / 120 34 100 120 90 110 80 100 70 80 3658337R400 x 347 x 190 / 135 / 220 43 150 180 135 165 120 150 105 120 3658338R500 x 347 x 190 / 135 / 320 52 200 240 180 220 160 200 140 160 3658339R810 x 347 x 165 / 135 / 630 71 250 300 225 275 200 250 175 200 3658340R700 x 347 x 190 / 135 / 420 70 300 360 270 330 240 300 210 240 3658341R700 x 347 x 190 / 135 / 420 76 350 420 315 385 280 350 245 280 3658342R810 x 347 x 190 / 135 / 630 81 400 480 360 440 320 400 280 320 3658343R810 x 347 x 190 / 135 / 630 81 450 540 405 495 360 450 315 360 3658344R

OptionsDescription Ref.

Set of 3 clamps for delta connexion 73396904RSet of 3 clamps for star connexion 73396905R

DD

Propivar capacitorsInsulation level 7.2 kV (20/60) 50/60 Hz

Page 8: Power factor correction and harmonic · PDF filePower factor correction and harmonic filtering How to choose the right power factor correction capacitor bank ? The recommended method

7

Power factor correction and harmonic filtering

D

DB

1130

11

Single-phase Propivar capacitor.

Single phase capacitors with internal fusesNetwork voltage (V) 6600 6300 6000 5500 Ref.Capacitor voltage (V) 3810 3640 3460 3180Dimensions (mm)(H x L x D / b / H2)

Weight(kg)

50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz

400 x 347 x 165 / 233 / 220 39 100 120 90 110 80 95 - - 3658354R400 x 347 x 190 / 233 / 220 44 150 180 135 160 125 150 105 125 3658355R500 x 347 x 190 / 233 / 320 54 200 240 180 220 160 190 140 170 3658356R500 x 347 x 190 / 233 / 320 54 250 300 225 270 205 245 175 210 3658357R600 x 347 x 190 / 233 / 420 63 300 360 270 320 250 300 210 250 3658358R700 x 347 x 190 / 233 / 520 72 400 480 360 440 320 380 280 340 3658359R

Single phase capacitors without internal fusesNetwork voltage (V) 6600 6300 6000 5500 Ref.Capacitor voltage (V) 3810 3640 3460 3180Dimensions (mm)(H x L x D / b / H2)

Weight(kg)

50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz

300 x 347 x 190 / 233 / 120 35 100 120 90 110 80 95 70 85 3658375R300 x 347 x 190 / 233 / 120 35 150 180 135 160 125 150 105 125 3658376R400 x 347 x 190 / 233 / 220 44 200 240 180 220 160 190 140 170 3658377R400 x 347 x 190 / 233 / 220 44 250 300 225 270 205 245 175 210 3658378R500 x 347 x 190 / 233 / 320 53 300 360 270 320 250 300 210 250 3658379R600 x 347 x 190 / 233 / 420 62 400 480 360 440 320 380 280 340 3658380R

OptionsDescription Ref.

Set of 2 clamps for delta connexion 73396902RSet of 2 clamps for star connexion 73396903R

Propivar capacitorsInsulation level 7.2 kV (20/60) 50/60 Hz

Page 9: Power factor correction and harmonic · PDF filePower factor correction and harmonic filtering How to choose the right power factor correction capacitor bank ? The recommended method

Power factor correction and harmonic filtering

DB

1130

10

Three-phase Propivar capacitor.

Three phase capacitorsNetwork voltage (V) 12000 11000 10500 10000 Ref.Capacitor voltage (V) 12000 11000 10500 10000Dimensions (mm)(H x L x D / b / H2)

Weight(kg)

50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz

300 x 347 x 190 / 233 / 120 35 150 180 125 150 115 135 105 125 3658347R400 x 347 x 190 / 233 / 220 44 200 240 170 200 150 180 140 165 3658348R500 x 347 x 190 / 233 / 320 53 250 300 210 250 190 230 175 210 3658349R600 x 347 x 190 / 233 / 420 62 300 360 250 300 230 270 210 250 3658350R600 x 347 x 190 / 233 / 420 63 350 420 295 350 265 320 245 295 3658351R700 x 347 x 190 / 233 / 520 71 400 480 340 400 300 360 280 330 3658352R810 x 347 x 190 / 233 / 630 81 450 540 380 450 345 410 315 375 3658353R

OptionsDescription Ref.

Set of 3 clamps for delta connexion 73396904RSet of 3 clamps for star connexion 73396905R

DB

1130

11

Single-phase Propivar capacitor.

Single phase capacitors with internal fusesNetwork voltage (V) 11000 10500 10000 Ref.Capacitor voltage (V) 6350 6060 5770Dimensions (mm)(H x L x P / b / H2)

Weight(kg)

50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz

400 x 347 x 165 / 233 / 220 40 180 215 165 200 - - 3658360R500 x 347 x 180 / 233 / 320 51 240 290 220 260 200 240 3658361R600 x 347 x 180 / 233 / 420 60 300 360 275 330 250 300 3658362R700 x 347 x 190 / 233 / 520 71 360 430 330 400 300 360 3658363R810 x 347 x 190 / 233 / 630 82 480 580 440 520 400 480 3658364R1000 x 347 x 190 / 233 / 820 99 600 720 550 660 500 600 3658708R

Single phase capacitors without internal fusesNetwork voltage (V) 11000 10500 10000 Ref.Capacitor voltage (V) 6350 6060 5770Dimensions (mm)(H x L x P / b / H2)

Weight(kg)

50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz

300 x 347 x 190 / 233 / 120 35 120 145 110 130 100 120 3658381R300 x 347 x 190 / 233 / 120 35 180 215 165 200 150 180 3658382R400 x 347 x 190 / 233 / 220 43 240 290 220 260 200 240 3658383R500 x 347 x 190 / 233 / 320 52 300 360 275 330 250 300 3658384R600 x 347 x 190 / 233 / 420 61 360 430 330 400 300 360 3658385R700 x 347 x 190 / 233 / 520 70 480 580 440 520 400 480 3658386R900 x 347 x 190 / 233 / 720 83 600 720 550 660 500 600 3658709R

OptionsDescription Ref.

Set of 2 clamps for delta connexion 73396902RSet of 2 clamps for star connexion 73396903R

DD

DD

Propivar capacitorsInsulation level 12 kV (28/75) 50/60 Hz

Page 10: Power factor correction and harmonic · PDF filePower factor correction and harmonic filtering How to choose the right power factor correction capacitor bank ? The recommended method

Power factor correction and harmonic filtering

DB

1130

11

Single-phase Propivar capacitor.

Single phase capacitors with internal fusesNetwork voltage (V) 15000 13800 12000 Ref.Capacitor voltage (V) 8660 7970 6930Dimensions (mm)(H x L x D / b / H2)

Weight(kg)

50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz

400 x 347 x 165 / 282 / 420 56 200 240 170 200 - - 3658365R500 x 347 x 190 / 282 / 320 54 250 300 210 250 - - 3658366R600 x 347 x 190 / 282 / 420 63 300 360 250 300 - - 3658367R700 x 347 x 190 / 282 / 520 73 400 480 340 400 260 320 3658368R900 x 347 x 190 / 282 / 720 91 500 600 420 505 320 385 3658710R1000 x 347 x 190 / 282 / 820 100 600 720 510 610 385 460 3658711R

Single phase capacitors without internal fusesNetwork voltage (V) 15000 13800 12000 Ref.Capacitor voltage (V) 8660 7970 6930Dimensions (mm)(H x L x D / b / H2)

Weight(kg)

50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz

300 x 347 x 190 / 282 / 120 36 100 120 85 100 65 80 3658387R300 x 347 x 190 / 282 / 120 35 150 180 125 150 95 115 3658388R400 x 347 x 190 / 282 / 220 44 200 240 170 200 130 160 3658389R400 x 347 x 190 / 282 / 220 45 250 300 210 250 160 190 3658390R500 x 347 x 190 / 282 / 320 54 300 360 250 300 190 230 3658391R600 x 347 x 190 / 282 / 420 63 400 480 340 400 260 320 3658392R810 x 347 x 190 / 282 / 630 82 500 600 420 505 320 385 3658712R900 x 347 x 190 / 282 / 720 91 600 720 510 610 385 460 3658713R

OptionsDescription Ref.

Set of 2 clamps for delta connexion 73396902RSet of 2 clamps for star connexion 73396903R

DD

Propivar capacitorsInsulation level 17.5 kV (38/95) 50/60 Hz

Page 11: Power factor correction and harmonic · PDF filePower factor correction and harmonic filtering How to choose the right power factor correction capacitor bank ? The recommended method

�0

Power factor correction and harmonic filtering

DB

1130

11

Single-phase Propivar capacitor.

Single phase capacitors with internal fusesNetwork voltage (V) 22000 20000 Ref.Capacitor voltage (V) 12700 11550Dimensions (mm)(H x L x D / b / H2)

Weight(kg)

50 Hz 60 Hz 50 Hz 60 Hz

810 x 347 x 165 / 282 / 630 73 300 360 - - 3658369R810 x 347 x 165 / 282 / 630 73 360 430 300 360 3658370R810 x 347 x 190 / 282 / 630 83 480 580 400 480 3658371R1000 x 347 x 190 / 282 / 820 100 600 720 500 600 3658715R

Single phase capacitors without internal fusesNetwork voltage (V) 22000 20000 Ref.Capacitor voltage (V) 12700 11550Dimensions (mm)(H x L x D / b / H2)

Weight(kg)

50 Hz 60 Hz 50 Hz 60 Hz

300 x 347 x 190 / 282 / 120 36 120 145 100 120 3658393R400 x 347 x 190 / 282 / 220 44 180 215 150 180 3658394R400 x 347 x 190 / 282 / 220 45 240 290 200 240 3658395R500 x 347 x 190 / 282 / 320 53 300 360 250 300 3658396R600 x 347 x 190 / 282 / 420 62 360 430 300 360 3658397R700 x 347 x 190 / 282 / 520 71 480 580 400 480 3658398R900 x 347 x 190 / 282 / 720 88 600 720 500 600 3658716R

OptionsDescription Ref.

Set of 2 clamps for delta connexion 73396902RSet of 2 clamps for star connexion 73396903R

DD

Propivar capacitorsInsulation level 24 kV (50/125) 50/60 Hz

Page 12: Power factor correction and harmonic · PDF filePower factor correction and harmonic filtering How to choose the right power factor correction capacitor bank ? The recommended method

��

Power factor correction and harmonic filtering

DB

1130

11

Single-phase Propivar capacitor.

Single phase capacitors with internal fusesNetwork voltage (V) 33000 31500 30000 RefCapacitor voltage (V) 9530 9090 8660Dimensions (mm)(H x L x D / b / H2)

Weight(kg)

50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz

600 x 347 x 190 / 377 / 420 65 300 360 275 330 250 300 3658372R700 x 347 x 190 / 377 / 520 75 360 430 330 400 300 360 3658373R810 x 347 x 190 / 377 / 630 85 480 580 440 520 400 480 3658374R1000 x 347 x 190 / 377 / 820 100 600 720 550 660 500 600 3658706R

Single phase capacitors without internal fusesNetwork voltage (V) 33000 31500 30000 Ref.Capacitor voltage (V) 9530 9090 8660Dimensions (mm)(H x L x D / b / H2)

Weight(kg)

50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz

300 x 347 x 190 / 377 / 120 37 120 145 110 130 100 120 3658399R400 x 347 x 190 / 377 / 220 46 180 215 165 200 150 180 3658400R500 x 347 x 190 / 377 / 320 55 240 290 220 260 200 240 3658401R500 x 347 x 190 / 377 / 320 55 300 360 275 330 250 300 3658402R600 x 347 x 190 / 377 / 420 64 360 430 330 400 300 360 3658403R810 x 347 x 190 / 377 / 630 83 480 580 440 520 400 480 3658404R1000 x 347 x 190 / 377 / 820 100 600 720 550 660 500 600 3658707R

OptionsDescription Ref.

Set of 2 clamps for delta connexion 73396902RSet of 2 clamps for star connexion 73396903R

DD

Propivar capacitorsInsulation level 36 kV (70/170) 50/60 Hz

Page 13: Power factor correction and harmonic · PDF filePower factor correction and harmonic filtering How to choose the right power factor correction capacitor bank ? The recommended method

��

Power factor correction and harmonic filtering

Schneider Electric can supply all types of capacitor banks, whatever the:b complexity of the network in the presence or absence of harmonicsb demand for reactive power b nominal insulation voltages.

To make it easier to choose the right capacitor banks, they are supplied: b CP214 fixed capacitor banks b CP227 fixed capacitor banks.

DB

1096

58

CP214 and CP227 fixed capacitor banksFixed capacitor banks CP214 CP227

Rated voltage y �� kV y �� kVReactive power range y ��0 kvar y 57�0 kvarExample of application Individual motor

compensationGlobal installation compensation

CompositionProtection HBC fuse CT and relay unbalanceSwitching current limitation by: � reactors � reactorsConnection Delta Double star

Type of capacitor bankCP214 fixed capacitor bank

CP227 fixed capacitor bank

Insulation voltage:

Technical dataThe capacitor banks have the following common characteristics:benvironmentally compatible Propivar capacitors with no PCB or chlorine dielectric liquidbservice frequency: 50 Hz (available in 60 Hz, please consult us)bmaximum temperature: 45 °Cbaverage temperature over 24 hours: 35 °Cbinstallation altitude y 1000 mbIP23 cubicle mounted bincoming cables from below with power cables connected to the copper padsboptional: outdoor type, fuse blow indicator, fast discharge reactors, lockable door.

0597

70-5

6

DB

1096

59

MV capacitor banksFixed compensation

Page 14: Power factor correction and harmonic · PDF filePower factor correction and harmonic filtering How to choose the right power factor correction capacitor bank ? The recommended method

��

Power factor correction and harmonic filtering

DB

1130

12

CP214.

Network voltage (V) 4160 3300 3000 2400 Ref.Dimensions (mm)(L x D x H)

Weight(kg)

50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz

1180 x 905 x 1680 425 50 60 30 37.5 25 30 16.5 20 73380050R1180 x 905 x 1680 435 100 120 60 75 50 60 33 40 73380051R1180 x 905 x 1680 440 150 180 90 110 75 90 50 60 73380052R1180 x 905 x 1680 450 200 240 120 150 100 120 66 80 73380053R1180 x 905 x 1680 450 250 300 150 185 125 150 85 100 73380054R1180 x 905 x 1680 465 300 360 180 225 150 180 100 120 73380055R1180 x 905 x 1680 470 350 420 210 260 175 210 115 140 73380056R1180 x 905 x 1680 475 400 480 240 295 200 240 135 160 73380057R1180 x 905 x 1680 480 450 540 270 335 225 270 150 180 73380058R1180 x 905 x 1680 485 500 600 300 370 250 300 170 200 73380059R1180 x 905 x 1680 500 550 660 330 410 275 330 185 220 73380060R1180 x 905 x 1680 510 600 720 360 450 300 360 200 240 73380061R1180 x 905 x 1680 525 650 780 390 485 325 390 215 260 73380062R1180 x 905 x 1680 535 700 840 420 520 350 420 230 280 73380063R

DB

1088

05

Network voltage (V) 6600 6300 6000 5500 Ref.Dimensions (mm)(L x D x H)

Weight(kg)

50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz

1180 x 905 x 1680 425 50 60 45 55 40 50 35 40 73380000R1180 x 905 x 1680 435 100 120 90 110 80 100 70 80 73380001R1180 x 905 x 1680 440 150 180 135 165 120 150 105 120 73380002R1180 x 905 x 1680 450 200 240 180 220 160 200 140 160 73380003R1180 x 905 x 1680 455 250 300 225 275 200 250 175 200 73380004R1180 x 905 x 1680 465 300 360 270 330 240 300 210 240 73380005R1180 x 905 x 1680 470 350 420 315 385 280 350 245 280 73380006R1180 x 905 x 1680 475 400 480 360 440 320 400 280 320 73380007R1180 x 905 x 1680 480 450 540 405 495 360 450 315 360 73380008R1180 x 905 x 1680 485 500 600 450 550 400 500 350 400 73380009R1180 x 905 x 1680 500 550 660 495 605 440 550 385 440 73380010R1180 x 905 x 1680 510 600 720 540 660 480 600 420 480 73380011R1180 x 905 x 1680 525 650 780 585 715 520 650 455 520 73380012R1180 x 905 x 1680 535 700 840 630 770 560 700 490 560 73380013R1180 x 905 x 1680 540 750 900 675 825 600 750 525 600 73380014R1180 x 905 x 1680 545 800 960 720 880 640 800 560 640 73380015R1180 x 905 x 1680 550 850 1020 765 935 680 850 595 680 73380016R1180 x 905 x 1680 560 900 1080 810 990 720 900 630 720 73380017R

CP214 optionsDescription Ref.

Melted fuse indication device 73380021RQuick discharge coils: 7.2 - 12 kV (set of 2) 73380022RDoor with lock for indoor type enclosure 73380023ROutdoor type 73380020RDoor with lock for outdoor type enclosure 73380018RDouble roof for outdoor type enclosure 73380019R

CP214 fixed capacitor bankInsulation level 7.2 kV (20/60) - 50/60 HzStandard type (slightly polluted network)

Page 15: Power factor correction and harmonic · PDF filePower factor correction and harmonic filtering How to choose the right power factor correction capacitor bank ? The recommended method

�4

Power factor correction and harmonic filtering

D

DB

1130

12

CP214.

Network voltage (V) 12000 11000 10500 10000 Ref.Dimensions (mm)(L x D x H)

Weight(kg)

50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz

1180 x 905 x 1680 440 150 180 125 150 115 135 105 125 73380025R1180 x 905 x 1680 450 200 240 170 200 150 180 140 165 73380026R1180 x 905 x 1680 455 250 300 210 250 190 230 175 210 73380027R1180 x 905 x 1680 465 300 360 250 300 230 270 210 250 73380028R1180 x 905 x 1680 470 350 420 295 350 265 320 245 295 73380029R1180 x 905 x 1680 475 400 480 335 400 305 365 280 335 73380030R1180 x 905 x 1680 485 450 540 380 450 345 410 315 375 73380031R1180 x 905 x 1680 500 500 600 420 500 380 460 350 420 73380032R1180 x 905 x 1680 510 550 660 460 550 420 500 385 460 73380033R1180 x 905 x 1680 525 600 720 505 600 460 545 420 500 73380034R1180 x 905 x 1680 530 650 780 545 650 495 590 455 545 73380035R1180 x 905 x 1680 535 700 840 590 700 535 640 490 585 73380036R1180 x 905 x 1680 540 750 900 630 750 570 685 525 630 73380037R1180 x 905 x 1680 545 800 960 670 800 610 730 560 670 73380038R

DB

1088

05

1180 x 905 x 1680 550 850 1020 715 850 650 775 595 710 73380039R1180 x 905 x 1680 560 900 1080 760 900 690 820 630 750 73380040R

CP214 optionsDescription Ref.

Melted fuse indication device 73380021RQuick discharge coils: 7.2 - 12 kV (set of 2) 73380022RDoor with lock for indoor type enclosure 73380023ROutdoor type 73380020RDoor with lock for outdoor type enclosure 73380018RDouble roof for outdoor type enclosure 73380019R

CP214 fixed capacitor bankInsulation level 12 kV (28/75) - 50/60 HzStandard type (slightly polluted network)

Page 16: Power factor correction and harmonic · PDF filePower factor correction and harmonic filtering How to choose the right power factor correction capacitor bank ? The recommended method

�5

Power factor correction and harmonic filtering

DB

1130

13

CP214 SAH.

Network voltage (V) 4160 3300 3000 2400 Ref.Dimensions (mm)(L x D x H)

Weight(kg)

50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz

2000 x 1100 x 1900 425 55 65 35 40 30 30 20 20 73385150R2000 x 1100 x 1900 435 105 130 65 80 55 65 35 40 73385151R2000 x 1100 x 1900 440 160 195 100 120 85 100 55 65 73385152R2000 x 1100 x 1900 450 210 260 130 160 110 130 70 85 73385153R2000 x 1100 x 1900 450 265 325 165 200 140 165 90 105 73385154R2000 x 1100 x 1900 465 320 390 200 240 165 200 105 130 73385155R2000 x 1100 x 1900 470 370 455 230 280 195 230 120 150 73385156R2000 x 1100 x 1900 475 425 520 265 320 225 265 145 170 73385157R2000 x 1100 x 1900 480 480 585 300 360 250 300 160 195 73385158R2000 x 1100 x 1900 485 530 650 330 400 280 330 180 210 73385159R2000 x 1100 x 1900 500 585 715 365 440 305 365 195 235 73385160R2000 x 1100 x 1900 510 640 780 400 480 330 400 210 260 73385161R

DB

1130

09

2000 x 1100 x 1900 525 690 845 430 520 360 430 225 280 73385162R2000 x 1100 x 1900 535 740 910 460 560 390 460 240 300 73385163R

Network voltage (V) 6600 6300 6000 5500 Ref.Dimensions (mm)(L x D x H)

Weight(kg)

50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz

2000 x 1100 x 1900 465 52.5 65 47.5 57.5 42.5 52.5 37.5 42.5 73385100R2000 x 1100 x 1900 480 105 130 95 115 85 105 75 85 73385101R2000 x 1100 x 1900 490 160 190 145 175 130 160 110 130 73385102R2000 x 1100 x 1900 505 210 255 190 235 170 210 150 170 73385103R2000 x 1100 x 1900 515 265 320 240 290 210 265 185 210 73385104R2000 x 1100 x 1900 530 320 385 290 350 255 320 225 255 73385105R2000 x 1100 x 1900 540 375 445 335 410 300 375 260 300 73385106R2000 x 1100 x 1900 550 425 510 385 465 340 425 295 340 73385107R2000 x 1100 x 1900 565 480 575 435 525 385 480 335 385 73385108R2000 x 1100 x 1900 580 530 640 480 580 420 530 370 420 73385109R2000 x 1100 x 1900 600 585 705 530 640 465 585 410 465 73385110R2000 x 1100 x 1900 615 640 770 580 700 510 640 450 510 73385111R2000 x 1100 x 1900 630 695 830 625 760 555 695 485 555 73385112R2000 x 1100 x 1900 645 750 890 670 820 600 750 520 600 73385113R2000 x 1100 x 1900 660 800 955 720 875 640 800 555 640 73385114R2000 x 1100 x 1900 675 850 1020 770 930 680 850 590 680 73385115R2000 x 1100 x 1900 690 905 1085 820 990 725 905 630 725 73385116R2000 x 1100 x 1900 710 960 1150 870 1050 770 960 670 770 73385117R

CP214 SAH optionsDescription Ref.

Melted fuse indication device 73380021RQuick discharge coils: 7.2 - 12 kV (set of 2) 73380022RDoor with lock for indoor type enclosure 73385123ROutdoor type 73385120RDoor with lock for outdoor type enclosure 73385118RDouble roof for outdoor type enclosure 73385119R

CP214 SAH fixed capacitor bankInsulation level 7.2 kV (20/60) - 50/60 HzSAH type (highly polluted network)

Page 17: Power factor correction and harmonic · PDF filePower factor correction and harmonic filtering How to choose the right power factor correction capacitor bank ? The recommended method

��

Power factor correction and harmonic filtering

DB

1130

13

CP214 SAH.

Network voltage (V) 11000 10500 10000 Réf.Dimensions (mm)(L x D x H)

Weight(kg)

50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz

2000 x 1100 x 1900 490 135 160 125 150 110 125 73385125R2000 x 1100 x 1900 505 180 215 165 200 150 165 73385126R2000 x 1100 x 1900 515 225 270 205 250 185 210 73385127R2000 x 1100 x 1900 530 270 320 250 300 220 250 73385128R2000 x 1100 x 1900 540 315 375 285 350 260 295 73385129R2000 x 1100 x 1900 550 360 430 330 400 295 335 73385130R2000 x 1100 x 1900 565 405 485 370 450 335 375 73385131R2000 x 1100 x 1900 580 450 540 410 500 370 420 73385132R2000 x 1100 x 1900 600 495 590 455 550 405 460 73385133R2000 x 1100 x 1900 620 540 645 495 600 445 500 73385134R2000 x 1100 x 1900 640 585 695 535 650 480 545 73385135R2000 x 1100 x 1900 655 630 755 575 700 520 585 73385136R

DB

1130

09

2000 x 1100 x 1900 670 675 805 615 750 555 630 73385137R2000 x 1100 x 1900 690 720 860 660 800 590 670 73385138R2000 x 1100 x 1900 710 765 915 700 850 630 710 73385139R2000 x 1100 x 1900 730 810 970 740 900 670 750 73385140R

CP214 SAH optionsDescription Réf.

Melted fuse indication device 73380021RQuick discharge coils: 7.2 - 12 kV (set of 2) 73380022RDoor with lock for indoor type enclosure 73385123ROutdoor type 73385120RDoor with lock for outdoor type enclosure 73385118RDouble roof for outdoor type enclosure 73385119R

CP214 SAH fixed capacitor bankInsulation level 12 kV (28/75) - 50/60 HzSAH type (highly polluted network)

Page 18: Power factor correction and harmonic · PDF filePower factor correction and harmonic filtering How to choose the right power factor correction capacitor bank ? The recommended method

�7

Power factor correction and harmonic filtering

DB

1130

14

Network voltage (V) 6600 6300 6000 5500 Ref.Dimensions (mm)(L x D x H)

Weight(kg)

50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz

1400 x 1400 x 2000 500 1200 1440 1080 1320 960 1140 840 1020 73370002R1400 x 1400 x 2000 550 1500 1620 1350 1470 1230 1305 1050 1140 73370003R1400 x 1400 x 2000 600 1800 2160 1620 1920 1500 1800 1260 1500 73370004R

CP227.

CP227 optionsDescription Ref.

Unbalance protection relay (separately delivered) 73394251RQuick discharge coils: 7.2 - 12 kV (set of 2) 73394805RDoor with lock for indoor type enclosure 73370100ROutdoor type 73370101R

DB

1088

06

Door with lock for outdoor type enclosure 73370104R

CP227 fixed capacitor bankInsulation level 7.2 kV (20/60) - 50/60 HzStandard type (slightly polluted network)

Page 19: Power factor correction and harmonic · PDF filePower factor correction and harmonic filtering How to choose the right power factor correction capacitor bank ? The recommended method

��

Power factor correction and harmonic filtering

DB

1130

14

Network voltage (V) 11000 10500 10000 Ref.Dimensions (mm)(L x D x H)

Weight(kg)

50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz

1400 x 1400 x 2000 (1) 500 1440 1740 1320 1560 1200 1440 73370022R (1)

1400 x 1400 x 2000 (1) 550 1800 2160 1650 1980 1500 1800 73370023R (1)

1400 x 1400 x 2000 (1) 600 2160 2580 1980 2400 1800 2160 73370024R (1)

1900 x 1400 x 2000 (2) 650 2520 3030 2310 2760 2100 2520 73370025R (2)

1900 x 1400 x 2000 (2) 700 2880 3480 2640 3120 2400 2880 73370026R (2)

1900 x 1400 x 2000 (2) 750 3240 3870 2970 3600 2700 3240 73370027R (2)

(1) 6C: 6 capacitors.(2) 12C: 12 capacitors.

CP227.CP227 optionsDescription Ref.

Unbalance protection relay (separately delivered) 73394251RQuick discharge coils: 7.2 - 12 kV (set of 2) 73394805R

DB

1088

06

Door with lock for indoor type enclosure 73370100ROutdoor type CP227-6C 73370101ROutdoor type CP227-12C 73370102RDoor with lock for outdoor type enclosure 73370104R

CP227 fixed capacitor bankInsulation level 12 kV (28/75) - 50/60 HzStandard type (slightly polluted network)

Page 20: Power factor correction and harmonic · PDF filePower factor correction and harmonic filtering How to choose the right power factor correction capacitor bank ? The recommended method

��

Power factor correction and harmonic filtering

DB

1130

14

CP227.

Network voltage (V) 15000 13800 Ref.Dimensions (mm)(L x D x H)

Weight(kg)

50 Hz 60 Hz 50 Hz 60 Hz

1400 x 1400 x 2000 (1) 450 600 720 510 600 73370040R (1)

1400 x 1400 x 2000 (1) 500 900 1080 750 900 73370041R (1)

1400 x 1400 x 2000 (1) 550 1200 1440 1020 1200 73370042R (1)

1400 x 1400 x 2000 (1) 600 1500 1620 1260 1500 73370043R (1)

1400 x 1400 x 2000 (1) 650 1800 2160 1500 1800 73370044R (1)

1400 x 1400 x 2000 (1) 700 2100 2520 1770 2100 73370045R (1)

1400 x 1400 x 2000 (1) 750 2400 2880 2040 2400 73370046R (1)

1900 x 1400 x 2000 (2) 800 2700 3240 2250 2700 73370047R (2)

1900 x 1400 x 2000 (2) 850 3000 3600 2520 3000 73370048R (2)

1900 x 1400 x 2000 (2) 900 3300 3960 2790 3300 73370049R (2)

1900 x 1400 x 2000 (2) 950 3600 4320 3060 3600 73370050R (2)

1900 x 1400 x 2000 (2) 1050 4200 5040 3540 4200 73370051R (2)

(1) 6C: 6 capacitors.(2) 12C: 12 capacitors.

DB

1088

06 CP227 optionsDescription Ref.

Unbalance protection relay (separately delivered) 73394251RQuick discharge coils: 17.5 - 24 kV (set of 2) 73394806RDoor with lock for indoor type enclosure 73370100ROutdoor type CP227-6C 73370101ROutdoor type CP227-12C 73370102RDoor with lock for outdoor type enclosure 73370104R

CP227 fixed capacitor bankInsulation level 17.5 kV (38/95) - 50/60 HzStandard type (slightly polluted network)

Page 21: Power factor correction and harmonic · PDF filePower factor correction and harmonic filtering How to choose the right power factor correction capacitor bank ? The recommended method

�0

Power factor correction and harmonic filtering

DB

1130

14

CP227.

Network voltage (V) 22000 20000 Ref.Dimensions (mm)(L x D x H)

Weight(kg)

50 Hz 60 Hz 50 Hz 60 Hz

1400 x 1400 x 2000 (1) 500 720 870 600 720 73370060R (1)

1400 x 1400 x 2000 (1) 550 1080 1290 900 1080 73370061R (1)

1400 x 1400 x 2000 (1) 600 1440 1740 1200 1440 73370062R (1)

1400 x 1400 x 2000 (1) 700 1800 2160 1500 1800 73370063R (1)

1400 x 1400 x 2000 (1) 800 2160 2580 1800 2160 73370064R (1)

1400 x 1400 x 2000 (1) 850 2520 3030 2100 2520 73370065R (1)

1400 x 1400 x 2000 (1) 900 2880 3480 2400 2880 73370066R (1)

1900 x 1400 x 2000 (2) 1050 3240 3870 2700 3240 73370067R (2)

1900 x 1400 x 2000 (2) 1100 3600 4320 3000 3600 73370068R (2)

1900 x 1400 x 2000 (2) 1200 3960 4770 3300 3960 73370069R (2)

1900 x 1400 x 2000 (2) 1250 4320 5160 3600 4320 73370070R (2)

1900 x 1400 x 2000 (2) 1400 5040 5220 4200 5040 73370071R (2)

DB

1088

06

1900 x 1400 x 2000 (2) 1550 5760 6960 4800 5760 73370072R (2)

(1) 6C: 6 capacitors.(2) 12C: 12 capacitors.

CP227 optionsDescription Ref.

Unbalance protection relay (separately delivered) 73394251RQuick discharge coils: 17.5 - 24 kV (set of 2) 73394806RDoor with lock for indoor type enclosure 73370100ROutdoor type CP227-6C 73370101ROutdoor type CP227-12C 73370102RDoor with lock for outdoor type enclosure 73370104R

CP227 fixed capacitor bankInsulation level 24 kV (50/125) - 50/60 HzStandard type (slightly polluted network)

Page 22: Power factor correction and harmonic · PDF filePower factor correction and harmonic filtering How to choose the right power factor correction capacitor bank ? The recommended method

��

Power factor correction and harmonic filtering

DB

1130

14

Network voltage (V) 33000 31500 30000 Ref.Dimensions (mm)(L x D x H)

Weight(kg)

50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz

2500 x 2100 x 2000 700 1440 1740 1320 1560 1200 1440 73370080R2500 x 2100 x 2000 750 1800 2160 1650 1980 1500 1800 73370081R2500 x 2100 x 2000 850 2160 2580 1980 2400 1800 2160 73370082R2500 x 2100 x 2000 950 2880 3480 2640 3120 2400 2880 73370083R2500 x 2100 x 2000 1150 3600 4320 3300 3960 3000 3600 73370084R2500 x 2100 x 2000 1250 4320 5160 3960 4800 3600 4320 73370085R2500 x 2100 x 2000 1400 5040 6060 4620 5520 4200 5040 73370086R2500 x 2100 x 2000 1550 5760 6960 5280 6240 4800 5760 73370087R

CP227. CP227 options

DB

1088

06

Description Ref.Unbalance protection relay (separately delivered) 73394251RDoor with lock for indoor type enclosure 73370100ROutdoor type 73370103RDoor with lock for outdoor type enclosure 73370104R

CP227 fixed capacitor bankInsulation level 36 kV (70/170) - 50/60 HzStandard type (slightly polluted network)

Page 23: Power factor correction and harmonic · PDF filePower factor correction and harmonic filtering How to choose the right power factor correction capacitor bank ? The recommended method

22

Schneider Electric can supply all types of capacitor banks, whatever the:b complexity of the network in the presence or absence of harmonicsb demand for reactive power b nominal insulation voltages.

To make it easier to choose the right capacitor banks, they are supplied: b CP253 automatic capacitor banksb CP254 automatic capacitor banks.

CP253 and CP254 automatic capacitor banksType of capacitor bank CP253 CP254

Rated voltage y 12 kV y 36 kVReactive power range y 4500 kvar y 5760 kvarExample of application Global installation

compensationEnergy distribution substation compensation

CompositionProtection HBC fuse Unbalance CT and relaySwitching device Rollarc contactor SF1 circuit breakerSwitching current limitation via: 3 reactors 3 reactorsRegulation Varlogic varmetric controller Varlogic varmetric controllerConnection Delta Double star

Type of capacitor bankCP253 automatic capacitor bank

CP254 automatic capacitor bank

Insulation voltage:

Technical dataThe capacitor banks have the following common characteristics:benvironmentally compatible Propivar capacitors with no PCB or chlorine dielectric liquidbservice frequency: 50 Hz (available in 60 Hz, please consult us)bmaximum temperature: 40 °Cbaverage temperature over 24 hours: 35 °Cbinstallation altitude y 1000 mbIP23 cubicle mounted bincoming cables from below with power cables connected to the copper padsboptional: outdoor type, fuse blow indicator, fast discharge reactors, lockable door.

0581

56 DB

1096

60D

B10

9661

MV capacitor banksAutomatic compensation

Power factor correction and harmonic filtering

Page 24: Power factor correction and harmonic · PDF filePower factor correction and harmonic filtering How to choose the right power factor correction capacitor bank ? The recommended method

��

Power factor correction and harmonic filtering

L

DB

1130

15

CP253.

Network voltage (V) 4160 3300 3000 2400 Ref.Dimensions (mm)(L x D x H)

Weight(kg)

50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz

1 stage1500 x 1600 x 2000 350 50 60 30 37.5 25 30 16.5 20 73360300R1500 x 1600 x 2000 360 100 120 60 75 50 60 33 40 73360301R1500 x 1600 x 2000 370 150 180 90 110 75 90 50 60 73360302R1500 x 1600 x 2000 380 250 300 150 185 125 150 85 100 73360303R1500 x 1600 x 2000 390 300 360 180 225 150 180 100 120 73360304R1500 x 1600 x 2000 400 500 600 300 370 250 300 170 200 73360305R1500 x 1600 x 2000 420 600 720 360 450 300 360 200 240 73360306R2 stages2600 x 1600 x 2000 600 100 120 60 75 50 60 33 40 73360307R2600 x 1600 x 2000 610 150 180 90 112.5 75 90 49.5 60 73360308R

DB

1088

05

2600 x 1600 x 2000 620 200 240 120 150 100 120 66 80 73360309R2600 x 1600 x 2000 625 300 360 180 220 150 180 100 120 73360310R2600 x 1600 x 2000 650 450 540 270 335 225 270 150 180 73360311R2600 x 1600 x 2000 660 500 600 300 370 250 300 170 200 73360312R2600 x 1600 x 2000 680 600 720 360 450 300 360 200 240 73360313R2600 x 1600 x 2000 710 750 900 450 555 375 450 255 300 73360314R2600 x 1600 x 2000 740 900 1080 540 675 450 540 300 360 73360315R2600 x 1600 x 2000 760 1000 1200 600 740 500 600 340 400 73360316R2600 x 1600 x 2000 800 1200 1440 720 900 600 720 400 480 73360317R3 stages3700 x 1600 x 2000 1110 200 240 120 150 100 120 66 80 73360318R3700 x 1600 x 2000 1120 250 300 150 187.5 125 150 82.5 100 73360319R3700 x 1600 x 2000 1140 300 360 180 225 150 180 99 120 73360320R3700 x 1600 x 2000 1150 450 540 270 330 225 270 150 180 73360321R3700 x 1600 x 2000 1160 600 720 360 445 300 360 200 240 73360322R3700 x 1600 x 2000 1170 750 900 450 560 375 450 250 300 73360323R3700 x 1600 x 2000 1180 900 1080 540 675 450 540 300 360 73360324R3700 x 1600 x 2000 1200 1000 1200 600 740 500 600 340 400 73360325R3700 x 1600 x 2000 1210 1200 1440 720 900 600 720 400 480 73360326R3700 x 1600 x 2000 1220 1250 1500 750 925 625 750 425 500 73360327R3700 x 1600 x 2000 1230 1500 1800 900 1125 750 900 500 600 73360328R3700 x 1600 x 2000 1250 1800 2160 1080 1350 900 1080 600 720 73360329R4 stages4800 x 1600 x 2000 1400 350 420 210 262.5 175 210 115.5 140 73360330R4800 x 1600 x 2000 1410 400 480 240 300 200 240 132 160 73360331R4800 x 1600 x 2000 1520 1200 1440 720 900 600 720 400 480 73360332R4800 x 1600 x 2000 1640 1800 2160 1080 1350 900 1080 600 720 73360333R4800 x 1600 x 2000 1650 2000 2400 1200 1480 1000 1200 680 800 73360334R4800 x 1600 x 2000 1670 2100 2520 1260 1575 1050 1260 700 840 73360335R4800 x 1600 x 2000 1700 2400 2880 1440 1800 1200 1440 800 960 73360336R5 stages5900 x 1600 x 2000 2000 2500 3000 1500 1850 1250 1500 850 1000 73360337R5900 x 1600 x 2000 2100 3000 3600 1800 2250 1500 1800 1000 1200 73360338R

CP253 optionsDescription Ref.

Quick discharge coils: 7.2 - 12 kV (set of 2) n x 73380022RDoor with lock for indoor type enclosure n x 73360100ROutdoor type n x 73360101RDoor with lock for outdoor type enclosure n x 73360102RControl and protection box, for one (1) stage 73367111RLocal manual control switch, for one (1) stage 73367121RControl and protection box, for two (2) stages 73367112RLocal manual control switch, for two (2) stages 73367122RControl and protection box, for three (3) stages 73367113RLocal manual control switch, for three (3) stages 73367123RControl and protection box, for four (4) stages 73367114RLocal manual control switch, for four (4) stages 73367124RControl and protection box, for five (5) stages 73367115RLocal manual control switch, for five (5) stages 73367125R“n” is the quantity of steps required.

CP253 automatic capacitor bankInsulation level 7.2 kV (20/60) - 50/60 HzStandard type (slightly polluted network)

Page 25: Power factor correction and harmonic · PDF filePower factor correction and harmonic filtering How to choose the right power factor correction capacitor bank ? The recommended method

�4

Power factor correction and harmonic filtering

L

DB

1130

15

CP253.

Network voltage (V) 6600 6300 6000 5500 Ref.Dimensions (mm)(L x D x H)

Weight(kg)

50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz

1 stage1350 x 1350 x 2000 350 50 60 45 55 40 50 35 40 73360000R1350 x 1350 x 2000 360 100 120 90 110 80 100 70 80 73360001R1350 x 1350 x 2000 370 150 180 135 165 120 150 105 120 73360002R1350 x 1350 x 2000 380 250 300 225 275 200 250 175 200 73360003R1350 x 1350 x 2000 390 300 360 270 330 240 300 210 240 73360004R1350 x 1350 x 2000 400 500 600 450 550 400 500 350 400 73360005R1350 x 1350 x 2000 420 600 720 540 660 480 600 420 480 73360006R2 stages2050 x 1350 x 2000 600 100 120 90 110 80 100 70 80 73360007R2050 x 1350 x 2000 610 150 180 135 165 120 150 105 120 73360008R

DB

1088

05

2050 x 1350 x 2000 620 200 240 180 220 160 200 140 160 73360009R2050 x 1350 x 2000 625 300 360 270 330 240 300 210 240 73360010R2050 x 1350 x 2000 650 450 540 405 495 360 450 315 360 73360011R2050 x 1350 x 2000 660 500 600 450 550 400 500 350 400 73360012R2050 x 1350 x 2000 680 600 720 540 660 480 600 420 480 73360013R2050 x 1350 x 2000 710 750 900 675 825 600 750 525 600 73360014R2050 x 1350 x 2000 740 900 1080 810 990 720 900 630 720 73360015R2050 x 1350 x 2000 760 1000 1200 900 1100 800 1000 700 800 73360016R2050 x 1350 x 2000 800 1200 1440 1080 1320 960 1200 840 960 73360017R3 stages2950 x 1350 x 2000 1110 200 240 180 220 160 200 140 160 73360018R2950 x 1350 x 2000 1120 250 300 225 275 200 250 175 200 73360019R2950 x 1350 x 2000 1140 300 360 270 330 240 300 210 240 73360020R2950 x 1350 x 2000 1150 450 540 405 495 360 450 315 360 73360021R2950 x 1350 x 2000 1160 600 720 540 660 480 600 420 480 73360022R2950 x 1350 x 2000 1170 750 900 675 825 600 750 525 600 73360023R2950 x 1350 x 2000 1180 900 1080 810 990 720 900 630 720 73360024R2950 x 1350 x 2000 1200 1000 1200 900 1100 800 1000 700 800 73360025R2950 x 1350 x 2000 1210 1200 1440 1080 1320 960 1200 840 960 73360026R2950 x 1350 x 2000 1220 1250 1500 1125 1375 1000 1250 875 1000 73360027R2950 x 1350 x 2000 1230 1500 1800 1350 1650 1200 1500 1050 1200 73360028R2950 x 1350 x 2000 1250 1800 2160 1620 1980 1440 1800 1260 1440 73360029R4 stages3650 x 1350 x 2000 1400 350 420 315 385 280 350 245 280 73360030R3650 x 1350 x 2000 1410 400 480 360 440 320 400 280 320 73360031R3650 x 1350 x 2000 1520 1200 1440 1080 1320 960 1200 840 960 73360032R3650 x 1350 x 2000 1640 1800 2160 1620 1980 1440 1800 1260 1440 73360033R3650 x 1350 x 2000 1650 2000 2400 1800 2200 1600 2000 1400 1600 73360034R3650 x 1350 x 2000 1670 2100 2520 1890 2310 1680 2100 1470 1680 73360035R3650 x 1350 x 2000 1700 2400 2880 2160 2640 1920 2400 1680 1920 73360036R5 stages4600 x 1350 x 2000 2000 2500 3000 2250 2750 2000 2500 1750 2000 73360037R4600 x 1350 x 2000 2100 3000 3600 2700 3300 2400 3000 2100 2400 73360038R

CP253 optionsDescription Ref.

Quick discharge coils: 7.2 - 12 kV (set of 2) n x 73380022RDoor with lock for indoor type enclosure n x 73360100ROutdoor type n x 73360101RDoor with lock for outdoor type enclosure n x 73360102RControl and protection box, for one (1) stage 73367111RLocal manual control switch, for one (1) stage 73367121RControl and protection box, for two (2) stages 73367112RLocal manual control switch, for two (2) stages 73367122RControl and protection box, for three (3) stages 73367113RLocal manual control switch, for three (3) stages 73367123RControl and protection box, for four (4) stages 73367114RLocal manual control switch, for four (4) stages 73367124RControl and protection box, for five (5) stages 73367115RLocal manual control switch, for five (5) stages 73367125R“n” is the quantity of steps required.

CP253 automatic capacitor bankInsulation level 7.2 kV (20/60) - 50/60 HzStandard type (slightly polluted network)

Page 26: Power factor correction and harmonic · PDF filePower factor correction and harmonic filtering How to choose the right power factor correction capacitor bank ? The recommended method

�5

Power factor correction and harmonic filtering

L

DB

1130

15

CP253.

Network voltage (V) 12000 11000 10500 10000 Ref.Dimensions (mm)(L x D x H)

Weight(kg)

50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz

1 stage1350 x 1350 x 2000 430 150 180 125 150 115 135 105 125 73360050R1350 x 1350 x 2000 450 250 300 210 250 190 230 175 210 73360051R1350 x 1350 x 2000 460 300 360 250 300 230 270 210 250 73360052R1350 x 1350 x 2000 490 450 540 380 450 345 410 315 375 73360053R1350 x 1350 x 2000 500 500 600 420 500 380 460 350 420 73360054R1350 x 1350 x 2000 580 900 1080 760 900 690 820 630 750 73360055R2 stages2050 x 1350 x 2000 860 300 360 250 300 230 270 210 250 73360056R2050 x 1350 x 2000 890 450 540 375 450 345 405 315 375 73360057R

DB

1088

00

2050 x 1350 x 2000 900 500 600 420 500 380 460 350 420 73360058R2050 x 1350 x 2000 920 600 720 500 600 460 540 420 500 73360059R2050 x 1350 x 2000 950 750 900 630 750 570 690 525 630 73360060R2050 x 1350 x 2000 980 900 1080 760 900 690 820 630 750 73360061R2050 x 1350 x 2000 1000 1000 1200 840 1000 760 920 700 840 73360062R2050 x 1350 x 2000 1070 1350 1620 1140 1350 1035 1230 945 1125 73360063R2050 x 1350 x 2000 1160 1800 2160 1520 1800 1380 1640 1260 1500 73360064R3 stages2950 x 1350 x 2000 1320 600 720 500 600 460 540 420 500 73360065R2950 x 1350 x 2000 1350 750 900 625 750 575 675 525 625 73360066R2950 x 1350 x 2000 1380 900 1080 750 900 690 810 630 750 73360067R2950 x 1350 x 2000 1400 1000 1200 840 1000 760 920 700 840 73360068R2950 x 1350 x 2000 1450 1250 1500 1050 1250 950 1150 875 1050 73360069R2950 x 1350 x 2000 1470 1350 1620 1140 1350 1035 1230 945 1125 73360070R2950 x 1350 x 2000 1500 1500 1800 1260 1500 1140 1380 1050 1260 73360071R2950 x 1350 x 2000 1560 1800 2160 1520 1800 1380 1640 1260 1500 73360072R2950 x 1350 x 2000 1650 2250 2700 1900 2250 1725 2050 1575 1875 73360073R2950 x 1350 x 2000 1740 2700 3240 2280 2700 2070 2460 1890 2250 73360074R4 stages3650 x 1350 x 2000 1840 1200 1440 1000 1200 920 1080 840 1000 73360075R3650 x 1350 x 2000 1900 1500 1800 1260 1500 1140 1380 1050 1260 73360076R3650 x 1350 x 2000 1950 1750 2100 1470 1750 1330 1610 1225 1470 73360077R3650 x 1350 x 2000 2000 2000 2400 1680 2000 1520 1840 1400 1680 73360078R3650 x 1350 x 2000 2140 2700 3240 2280 2700 2070 2460 1890 2250 73360079R3650 x 1350 x 2000 2230 3150 3780 2660 3150 2415 2870 2205 2625 73360080R3650 x 1350 x 2000 2320 3600 4320 3040 3600 2760 3280 2520 3000 73360081R5 stages4600 x 1350 x 2000 2450 2250 2700 1890 2250 1710 2070 1575 1890 73360082R4600 x 1350 x 2000 2500 2500 3000 2100 2500 1900 2300 1750 2100 73360083R4600 x 1350 x 2000 2720 3600 4320 3040 3600 2760 3280 2520 3000 73360084R4600 x 1350 x 2000 2810 4050 4860 3420 4050 3105 3690 2835 3375 73360085R4600 x 1350 x 2000 2900 4500 5400 3800 4500 3450 4100 3150 3750 73360086R

CP253 optionsDescription Ref.

Quick discharge coils: 7.2 - 12 kV (set of 2) n x 73380022RDoor with lock for indoor type enclosure n x 73360100ROutdoor type n x 73360101RDoor with lock for outdoor type enclosure n x 73360102RControl and protection box, for one (1) stage 73367111RLocal manual control switch, for one (1) stage 73367121RControl and protection box, for two (2) stages 73367112RLocal manual control switch, for two (2) stages 73367122RControl and protection box, for three (3) stages 73367113RLocal manual control switch, for three (3) stages 73367123RControl and protection box, for four (4) stages 73367114RLocal manual control switch, for four (4) stages 73367124RControl and protection box, for five (5) stages 73367115RLocal manual control switch, for five (5) stages 73367125R“n” is the quantity of steps required.

CP253 automatic capacitor bankInsulation level 12 kV (28/75) - 50/60 HzStandard type (slightly polluted network)

Page 27: Power factor correction and harmonic · PDF filePower factor correction and harmonic filtering How to choose the right power factor correction capacitor bank ? The recommended method

��

Power factor correction and harmonic filtering

L

DB

1130

16

CP253 SAH.

Network voltage (V) 4160 3300 3000 2400 Ref.Dimensions (mm)(L x D x H)

Weight(kg)

50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz

1 stage1500 x 2400 x 2000 460 52.5 65 32.5 40 27.5 32.5 17.5 20 73360400R1500 x 2400 x 2000 470 105 130 65 80 55 65 35 40 73360401R1500 x 2400 x 2000 480 160 195 100 120 85 100 52.5 65 73360402R1500 x 2400 x 2000 500 265 325 165 200 140 165 90 105 73360403R1500 x 2400 x 2000 520 320 390 200 240 165 200 105 130 73360404R1500 x 2400 x 2000 550 530 650 330 400 280 330 180 210 73360405R1500 x 2400 x 2000 570 640 780 400 480 330 400 210 260 73360406R2 stages

DB

1088

07

2600 x 2400 x 2000 920 105 130 65 80 55 65 35 40 73360407R2600 x 2400 x 2000 930 160 195 100 120 85 97.5 55 60 73360408R2600 x 2400 x 2000 940 210 260 130 160 110 130 70 80 73360409R2600 x 2400 x 2000 960 320 390 200 240 170 200 105 130 73360410R2600 x 2400 x 2000 990 480 585 300 360 250 300 160 195 73360411R2600 x 2400 x 2000 1000 530 650 330 400 280 330 180 210 73360412R2600 x 2400 x 2000 1020 640 780 400 480 330 400 210 260 73360413R2600 x 2400 x 2000 1050 795 975 495 600 420 495 270 315 73360414R2600 x 2400 x 2000 1080 960 1170 600 720 495 600 315 390 73360415R2600 x 2400 x 2000 1100 1060 1300 660 800 560 660 360 420 73360416R2600 x 2400 x 2000 1140 1280 1560 800 960 660 800 420 520 73360417R3 stages3700 x 2400 x 2000 1390 210 260 130 160 110 130 70 80 73360418R3700 x 2400 x 2000 1400 265 325 165 200 140 162.5 90 100 73360419R3700 x 2400 x 2000 1410 315 390 195 240 165 195 105 120 73360420R3700 x 2400 x 2000 1440 480 585 300 360 255 300 160 195 73360421R3700 x 2400 x 2000 1450 640 780 400 480 340 400 210 260 73360422R3700 x 2400 x 2000 1470 800 975 500 600 425 500 265 325 73360423R3700 x 2400 x 2000 1500 960 1170 600 720 495 600 315 390 73360424R3700 x 2400 x 2000 1530 1060 1300 660 800 560 660 360 420 73360425R3700 x 2400 x 2000 1550 1280 1560 800 960 660 800 420 520 73360426R3700 x 2400 x 2000 1590 1325 1625 825 1000 700 825 450 525 73360427R3700 x 2400 x 2000 1600 1600 1950 1000 1200 825 1000 525 650 73360428R3700 x 2400 x 2000 1620 1920 2340 1200 1440 990 1200 630 780 73360429R4 stages4800 x 2400 x 2000 1850 370 455 230 280 195 228 125 140 73360430R4800 x 2400 x 2000 1860 420 520 260 320 220 260 140 160 73360431R4800 x 2400 x 2000 1870 1280 1560 800 960 660 800 420 520 73360432R4800 x 2400 x 2000 1880 1920 2340 1200 1440 990 1200 630 780 73360433R4800 x 2400 x 2000 2040 2120 2600 1320 1600 1120 1320 720 840 73360434R4800 x 2400 x 2000 2160 2240 2730 1400 1680 1155 1400 735 910 73360435R4800 x 2400 x 2000 2180 2560 3120 1600 1920 1320 1600 840 1040 73360436R5 stages5900 x 2400 x 2000 2750 2650 3250 1650 2000 1400 1650 900 1050 73360437R5900 x 2400 x 2000 2850 3200 3900 2000 2400 1650 2000 1050 1300 73360438R

CP253 SAH optionsDescription Ref.

Quick discharge coils: 7.2 - 12 kV (set of 2) n x 73380022RDoor with lock for indoor type enclosure n x 73360100ROutdoor type n x 73360101RDoor with lock for outdoor type enclosure n x 73360102RControl and protection box, for one (1) stage 73367111RLocal manual control switch, for one (1) stage 73367121RControl and protection box, for two (2) stages 73367112RLocal manual control switch, for two (2) stages 73367122RControl and protection box, for three (3) stages 73367113RLocal manual control switch, for three (3) stages 73367123RControl and protection box, for four (4) stages 73367114RLocal manual control switch, for four (4) stages 73367124RControl and protection box, for five (5) stages 73367115RLocal manual control switch, for five (5) stages 73367125R“n” is the quantity of steps required.

CP253SAH automatic capacitor bankInsulation level 7.2 kV (20/60) - 50/60 HzSAH type (highly polluted network)

Page 28: Power factor correction and harmonic · PDF filePower factor correction and harmonic filtering How to choose the right power factor correction capacitor bank ? The recommended method

�7

Power factor correction and harmonic filtering

L

DB

1130

16

CP253 SAH.

Network voltage (V) 6600 6300 6000 5500 Ref.Dimensions (mm)(L x D x H)

Weight(kg)

50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz

1 stage1400 x 2300 x 2000 460 52.5 65 47.5 57.5 42.5 52.5 37.5 42.5 73360200R1400 x 2300 x 2000 470 105 130 95 115 85 105 75 85 73360201R1400 x 2300 x 2000 480 160 190 145 175 130 160 110 130 73360202R1400 x 2300 x 2000 500 265 320 240 290 210 265 185 210 73360203R1400 x 2300 x 2000 520 320 385 290 350 255 320 225 255 73360204R1400 x 2300 x 2000 550 530 640 480 580 420 530 370 420 73360205R1400 x 2300 x 2000 570 640 770 580 700 510 640 450 510 73360206R2 stages2400 x 2300 x 2000 920 105 130 95 115 85 105 75 85 73360207R

DB

1088

05

2400 x 2300 x 2000 930 160 195 145 175 130 160 115 130 73360208R2400 x 2300 x 2000 940 210 260 190 230 170 210 150 170 73360209R2400 x 2300 x 2000 960 320 380 290 350 260 320 220 260 73360210R2400 x 2300 x 2000 990 480 575 435 525 385 480 335 385 73360211R2400 x 2300 x 2000 1000 530 640 480 580 420 530 370 420 73360212R2400 x 2300 x 2000 1020 640 770 580 700 510 640 450 510 73360213R2400 x 2300 x 2000 1050 795 960 720 870 630 795 555 630 73360214R2400 x 2300 x 2000 1080 960 1155 870 1050 765 960 675 765 73360215R2400 x 2300 x 2000 1100 1060 1280 960 1160 840 1060 740 840 73360216R2400 x 2300 x 2000 1140 1280 1540 1160 1400 1020 1280 900 1020 73360217R3 stages3400 x 2300 x 2000 1390 210 260 190 230 170 210 150 170 73360218R3400 x 2300 x 2000 1400 265 325 240 290 215 265 190 215 73360219R3400 x 2300 x 2000 1410 315 390 285 345 255 315 225 255 73360220R3400 x 2300 x 2000 1440 480 570 435 525 390 480 330 390 73360221R3400 x 2300 x 2000 1450 640 760 580 700 520 640 440 520 73360222R3400 x 2300 x 2000 1470 800 950 725 875 650 800 550 650 73360223R3400 x 2300 x 2000 1500 960 1155 870 1050 765 960 675 765 73360224R3400 x 2300 x 2000 1530 1060 1280 960 1160 840 1060 740 840 73360225R3400 x 2300 x 2000 1550 1280 1540 1160 1400 1020 1280 900 1020 73360226R3400 x 2300 x 2000 1590 1325 1600 1200 1450 1050 1325 925 1050 73360227R3400 x 2300 x 2000 1600 1600 1925 1450 1750 1275 1600 1125 1275 73360228R3400 x 2300 x 2000 1620 1920 2310 1740 2100 1530 1920 1350 1530 73360229R4 stages4400 x 2300 x 2000 1850 370 455 335 403 300 368 265 298 73360230R4400 x 2300 x 2000 1860 420 520 380 460 340 420 300 340 73360231R4400 x 2300 x 2000 1870 1280 1540 1160 1400 1020 1280 900 1020 73360232R4400 x 2300 x 2000 1880 1920 2310 1740 2100 1530 1920 1350 1530 73360233R4400 x 2300 x 2000 2040 2120 2560 1920 2320 1680 2120 1480 1680 73360234R4400 x 2300 x 2000 2160 2240 2695 2030 2450 1785 2240 1575 1785 73360235R4400 x 2300 x 2000 2180 2560 3080 2320 2800 2040 2560 1800 2040 73360236R5 stages5400 x 2300 x 2000 2750 2650 3200 2400 2900 2100 2650 1850 2100 73360237R5400 x 2300 x 2000 2850 3200 3850 2900 3500 2550 3200 2250 2550 73360238R

CP253 SAH optionsDescription Ref.

Quick discharge coils: 7.2 - 12 kV (set of 2) n x 73380022RDoor with lock for indoor type enclosure n x 73360100ROutdoor type n x 73360101RDoor with lock for outdoor type enclosure n x 73360102RControl and protection box, for one (1) stage 73367111RLocal manual control switch, for one (1) stage 73367121RControl and protection box, for two (2) stages 73367112RLocal manual control switch, for two (2) stages 73367122RControl and protection box, for three (3) stages 73367113RLocal manual control switch, for three (3) stages 73367123RControl and protection box, for four (4) stages 73367114RLocal manual control switch, for four (4) stages 73367124RControl and protection box, for five (5) stages 73367115RLocal manual control switch, for five (5) stages 73367125R“n” is the quantity of steps required.

CP253SAH automatic capacitor bankInsulation level 7.2 kV (20/60) - 50/60 HzSAH type (highly polluted network)

Page 29: Power factor correction and harmonic · PDF filePower factor correction and harmonic filtering How to choose the right power factor correction capacitor bank ? The recommended method

��

Power factor correction and harmonic filtering

L

DB

1130

16

CP253 SAH.

Network voltage (V) 11000 10500 10000 Ref.Dimensions (mm)(L x D x H)

Weight(kg)

50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz

1 stage1400 x 2300 x 2000 480 135 160 125 150 110 125 73360250R1400 x 2300 x 2000 500 225 270 205 250 185 210 73360251R1400 x 2300 x 2000 510 270 320 250 300 220 250 73360252R1400 x 2300 x 2000 540 405 485 370 450 335 375 73360253R1400 x 2300 x 2000 550 450 540 410 500 370 420 73360254R1400 x 2300 x 2000 630 810 970 740 900 670 750 73360255R2 stages2400 x 2300 x 2000 960 270 320 250 300 220 250 73360256R2400 x 2300 x 2000 990 405 480 375 450 330 375 73360257R

DB

1088

05

2400 x 2300 x 2000 1000 450 540 410 500 370 420 73360258R2400 x 2300 x 2000 1020 540 640 500 600 440 500 73360259R2400 x 2300 x 2000 1050 675 810 615 750 555 630 73360260R2400 x 2300 x 2000 1080 810 970 740 900 670 750 73360261R2400 x 2300 x 2000 1100 900 1080 820 1000 740 840 73360262R2400 x 2300 x 2000 1170 1215 1455 1110 1350 1005 1125 73360263R2400 x 2300 x 2000 1260 1620 1940 1480 1800 1340 1500 73360264R3 stages3400 x 2300 x 2000 1470 540 640 500 600 440 500 73360265R3400 x 2300 x 2000 1500 675 800 625 750 550 625 73360266R3400 x 2300 x 2000 1530 810 960 750 900 660 750 73360267R3400 x 2300 x 2000 1550 900 1080 820 1000 740 840 73360268R3400 x 2300 x 2000 1600 1125 1350 1025 1250 925 1050 73360269R3400 x 2300 x 2000 1620 1215 1455 1110 1350 1005 1125 73360270R3400 x 2300 x 2000 1650 1350 1620 1230 1500 1110 1260 73360271R3400 x 2300 x 2000 1710 1620 1940 1480 1800 1340 1500 73360272R3400 x 2300 x 2000 1800 2025 2425 1850 2250 1675 1875 73360273R3400 x 2300 x 2000 1890 2430 2910 2220 2700 2010 2250 73360274R4 stages4400 x 2300 x 2000 2040 1080 1280 1000 1200 880 1000 73360275R4400 x 2300 x 2000 2100 1350 1620 1230 1500 1110 1260 73360276R4400 x 2300 x 2000 2150 1575 1890 1435 1750 1295 1470 73360277R4400 x 2300 x 2000 2200 1800 2160 1640 2000 1480 1680 73360278R4400 x 2300 x 2000 2340 2430 2910 2220 2700 2010 2250 73360279R4400 x 2300 x 2000 2430 2835 3395 2590 3150 2345 2625 73360280R4400 x 2300 x 2000 2520 3240 3880 2960 3600 2680 3000 73360281R5 stages5400 x 2300 x 2000 2700 2025 2430 1845 2250 1665 1890 73360282R5400 x 2300 x 2000 2750 2250 2700 2050 2500 1850 2100 73360283R5400 x 2300 x 2000 2970 3240 3880 2960 3600 2680 3000 73360284R5400 x 2300 x 2000 3060 3645 4365 3330 4050 3015 3375 73360285R5400 x 2300 x 2000 3150 4050 4850 3700 4500 3350 3750 73360286R

CP253 SAH optionsDescription Ref.

Quick discharge coils: 7.2 - 12 kV (set of 2) n x 73380022RDoor with lock for indoor type enclosure n x 73360100ROutdoor type n x 73360101RDoor with lock for outdoor type enclosure n x 73360102RControl and protection box, for one (1) stage 73367111RLocal manual control switch, for one (1) stage 73367121RControl and protection box, for two (2) stages 73367112RLocal manual control switch, for two (2) stages 73367122RControl and protection box, for three (3) stages 73367113RLocal manual control switch, for three (3) stages 73367123RControl and protection box, for four (4) stages 73367114RLocal manual control switch, for four (4) stages 73367124RControl and protection box, for five (5) stages 73367115RLocal manual control switch, for five (5) stages 73367125R“n” is the quantity of steps required.

CP253SAH automatic capacitor bankInsulation level 12 kV (28/75) - 50/60 HzSAH type (highly polluted network)

Page 30: Power factor correction and harmonic · PDF filePower factor correction and harmonic filtering How to choose the right power factor correction capacitor bank ? The recommended method

��

Power factor correction and harmonic filtering

DB

1130

17

CP254.

Network voltage (V) 15000 13800 Ref.Dimensions (mm)(L x D x H)

Weight(kg)

50 Hz 60 Hz 50 Hz 60 Hz

2600 x 1400 x 2000 620 600 720 510 600 73365000R2600 x 1400 x 2000 680 900 1080 750 900 73365001R2600 x 1400 x 2000 740 1200 1440 1020 1200 73365002R2600 x 1400 x 2000 800 1500 1620 1260 1500 73365003R2600 x 1400 x 2000 860 1800 2160 1500 1800 73365004R2600 x 1400 x 2000 920 2100 2520 1770 2100 73365005R2600 x 1400 x 2000 980 2400 2880 2040 2400 73365006R2600 x 1400 x 2000 1040 2700 3240 2250 2700 73365007R2600 x 1400 x 2000 1100 3000 3600 2520 3000 73365008R2600 x 1400 x 2000 1160 3300 3960 2790 3300 73365009R2600 x 1400 x 2000 1220 3600 4320 3060 3600 73365010R

DB

1130

05

2600 x 1400 x 2000 1240 4200 5040 3540 4200 73365011R

CP254 optionsDescription Ref.

Unbalance protection relay (separately delivered) 73394251ROutdoor type 73365101RThree-pole grounding switch 73365110RQuick discharge coils: 17.5 - 24 kV (set of 2) 73394806RControl and protection box, for one (1) stage 73367111RLocal manual control switch, for one (1) stage 73367121RControl and protection box, for two (2) stages 73367112RLocal manual control switch, for two (2) stages 73367122RControl and protection box, for three (3) stages 73367113RLocal manual control switch, for three (3) stages 73367123RControl and protection box, for four (4) stages 73367114RLocal manual control switch, for four (4) stages 73367124RControl and protection box, for five (5) stages 73367115RLocal manual control switch, for five (5) stages 73367125R

CP254 automatic capacitor bankInsulation level 17.5 kV (38/95) - 50/60 HzStandard type (slightly polluted network)

Page 31: Power factor correction and harmonic · PDF filePower factor correction and harmonic filtering How to choose the right power factor correction capacitor bank ? The recommended method

�0

Power factor correction and harmonic filtering

DB

1130

17

CP254.

Network voltage (V) 22000 20000 Ref.Dimensions (mm)(L x D x H)

Weight(kg)

50 Hz 60 Hz 50 Hz 60 Hz

2600 x 1400 x 2000 650 720 870 600 720 73365020R2600 x 1400 x 2000 720 1080 1290 900 1080 73365021R2600 x 1400 x 2000 790 1440 1740 1200 1440 73365022R2600 x 1400 x 2000 860 1800 2160 1500 1800 73365023R2600 x 1400 x 2000 930 2160 2580 1800 2160 73365024R2600 x 1400 x 2000 1000 2520 3030 2100 2520 73365025R2600 x 1400 x 2000 1080 2880 3480 2400 2880 73365026R2600 x 1400 x 2000 1150 3240 3870 2700 3240 73365027R2600 x 1400 x 2000 1220 3600 4320 3000 3600 73365028R2600 x 1400 x 2000 1300 3960 4770 3300 3960 73365029R2600 x 1400 x 2000 1360 4320 5160 3600 4320 73365030R

DB

1130

05

2600 x 1400 x 2000 1500 5040 5220 4200 5040 73365031R2600 x 1400 x 2000 1650 5760 6960 4800 5760 73365032R

CP254 optionsDescription Ref.

Unbalance protection relay (separately delivered) 73394251ROutdoor type 73365101RThree-pole grounding switch 73365110RQuick discharge coils: 17.5 - 24 kV (set of 2) 73394806RControl and protection box, for one (1) stage 73367111RLocal manual control switch, for one (1) stage 73367121RControl and protection box, for two (2) stages 73367112RLocal manual control switch, for two (2) stages 73367122RControl and protection box, for three (3) stages 73367113RLocal manual control switch, for three (3) stages 73367123RControl and protection box, for four (4) stages 73367114RLocal manual control switch, for four (4) stages 73367124RControl and protection box, for five (5) stages 73367115RLocal manual control switch, for five (5) stages 73367125R

CP254 automatic capacitor bankInsulation level 24 kV (50/125) - 50/60 HzStandard type (slightly polluted network)

Page 32: Power factor correction and harmonic · PDF filePower factor correction and harmonic filtering How to choose the right power factor correction capacitor bank ? The recommended method

��

Power factor correction and harmonic filtering

DB

1130

17

CP254.

Network voltage (V) 33000 31500 30000 Ref.Dimensions (mm)(L x D x H)

Weight(kg)

50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz

3000 x 2800 x 2100 1000 1440 1740 1320 1560 1200 1440 73365040R3000 x 2800 x 2100 1100 1800 2160 1650 1980 1500 1800 73365041R3000 x 2800 x 2100 1200 2160 2580 1980 2400 1800 2160 73365042R3000 x 2800 x 2100 1300 2880 3480 2640 3120 2400 2880 73365043R3000 x 2800 x 2100 1450 3600 4320 3300 3960 3000 3600 73365044R3000 x 2800 x 2100 1550 4320 5160 3960 4800 3600 4320 73365045R3000 x 2800 x 2100 1700 5040 6060 4620 5520 4200 5040 73365046R3000 x 2800 x 2100 1850 5760 6960 5280 6240 4800 5760 73365047R

DB

1130

05

CP254 optionsDescription Ref.

Unbalance protection relay (separately delivered) 73394251ROutdoor type 73365101RThree-pole grounding switch 73365110RQuick discharge coils: 17.5 - 24 kV (set of 2) 73394806RControl and protection box, for one (1) stage 73367111RLocal manual control switch, for one (1) stage 73367121RControl and protection box, for two (2) stages 73367112RLocal manual control switch, for two (2) stages 73367122RControl and protection box, for three (3) stages 73367113RLocal manual control switch, for three (3) stages 73367123RControl and protection box, for four (4) stages 73367114RLocal manual control switch, for four (4) stages 73367124RControl and protection box, for five (5) stages 73367115RLocal manual control switch, for five (5) stages 73367125R

CP254 automatic capacitor bankInsulation level 36 kV (70/170) - 50/60 HzStandard type (slightly polluted network)

Page 33: Power factor correction and harmonic · PDF filePower factor correction and harmonic filtering How to choose the right power factor correction capacitor bank ? The recommended method

��

Notes

Page 34: Power factor correction and harmonic · PDF filePower factor correction and harmonic filtering How to choose the right power factor correction capacitor bank ? The recommended method

Schneider Electric Industries SASRectiphase399 rue de la Gare74370 Pringy (France)Tel.: (33) 04 50 66 95 00Fax: (33) 04 50 27 24 19

http://www.schneider-electric.comhttp://www.merlin-gerin.com

CFIED205098EN

As standards, specifications and designs develop from time to time, always ask for confirmation of the information given in this publication.

Printed on recycled paper.

Design: Schneider Electric - AmegPhoto: Schneider ElectricPrinted:

05-2007

AR

T960

085

© 2

007

Sch

neid

er E

lect

ric -

All

right

rese

rved