HPM seriesDecentralized Parallel Modular Online UPS System
3:3 Phase
HPM3300 Series
3:3 Phase
HPM3300 Series
![Page 3: Power u ps hpm3300 presentation-r1](https://reader031.vdocuments.net/reader031/viewer/2022012406/55c9b4febb61eb201b8b474a/html5/thumbnails/3.jpg)
HPM3300-60K/100K
HPM3300-90/150K
HPM 3300-200K
HPM3300-60K/100K
HPM3300-90/150K
HPM 3300-200K
HPM3300-200K
HPM3300-250K
HPM3300-320K
HPM3300-200K
HPM3300-250K
HPM3300-320K10K/15K/20/25/30/40KVA Module
10K/15K/20/25/30/40KVA Module
3/3 system:
60K/100/200KVA (10/15/20k module)250KVA (25k module)90/150/300KVA (30k module)200/320/400/520KVA (40k module)
PF=0.9 and 1 are available
HPM3300-400K
HPM3300-520K
HPM3300-400K
HPM3300-520K
![Page 4: Power u ps hpm3300 presentation-r1](https://reader031.vdocuments.net/reader031/viewer/2022012406/55c9b4febb61eb201b8b474a/html5/thumbnails/4.jpg)
HPM 3/3 Module
Model Power Dimension Weight
HPM3310-RM 10KVA 443x580x131mm 3U 26.0 kg
HPM3315-RM 15KVA 443x580x131mm 3U 30.0 kg
HPM3320-RM 20KVA 443x580x131mm 3U 31.0 kg
HPM3325-RM 25KVA 443x580x131mm 3U 32.0 kg
HPM3330-RM 30KVA 443x580x131mm 3U 33.0 kg
HPM3340-RM 40KVA 443x580x131mm 3U 34.0 kg
![Page 5: Power u ps hpm3300 presentation-r1](https://reader031.vdocuments.net/reader031/viewer/2022012406/55c9b4febb61eb201b8b474a/html5/thumbnails/5.jpg)
HPM UPS Cabinet (3/3)
Model Application Dimension (W*D*H) mm Net Weight
HPM3300-60K max. (3+1) x 10/15/20KVA Modules 600x840x1400 145 kg
HPM3300-100K max. 5 x 10/15/20KVA Modules 600x840x1400 170 kg
HPM3300-200K max. 10 x 10/15/20KVA Modules 600x1100x2000 270 kg
HPM3300-250K max. 10 x 25KVA modules 600x1100x2000 290 kg
HPM 3300-90k max. (3+1) x 30KVA Modules 600x840x1400 149 kg
HPM 3300-150K max. 5 x 30KVA Modules 600x840x1400 152 kg
HPM 3300-300K max. 10 x 30KVA modules 600x1100x2000 310 kg
HPM3300-200K max. 5 x 40KVA Modules 600x860x1600 205 kg
HPM3300-320k max. 8 x 40KVA Modules 600x860x2000 310 kg
HPM3300-400/520k max. 8/13 x 40KVA Modules 1200x860x2000 450 kg
![Page 6: Power u ps hpm3300 presentation-r1](https://reader031.vdocuments.net/reader031/viewer/2022012406/55c9b4febb61eb201b8b474a/html5/thumbnails/6.jpg)
Operator Centres, Servers, Computer rooms
Telecom Switchgear & Infrastructures
Bank, Hospital, Healthcare Equipment
Security Systems, Emergency Lighting, Fire Protection
Airport Infrastructure
Processing Control Equipments
Operator Centres, Servers, Computer rooms
Telecom Switchgear & Infrastructures
Bank, Hospital, Healthcare Equipment
Security Systems, Emergency Lighting, Fire Protection
Airport Infrastructure
Processing Control Equipments
Mission critical & industrial applications
Mission critical & industrial applications
![Page 7: Power u ps hpm3300 presentation-r1](https://reader031.vdocuments.net/reader031/viewer/2022012406/55c9b4febb61eb201b8b474a/html5/thumbnails/7.jpg)
Fit into standard 19” Rack Cabinet
Decentralized Parallel Structure Concept
Compact in Size, only 3U Height
Modular N+X Parallel Redundancy
Parallel Operation up to 10 Units for each Rack
Invest as You Grow
High Power Density to 520KVA per Rack
Common Battery
Fit into standard 19” Rack Cabinet
Decentralized Parallel Structure Concept
Compact in Size, only 3U Height
Modular N+X Parallel Redundancy
Parallel Operation up to 10 Units for each Rack
Invest as You Grow
High Power Density to 520KVA per Rack
Common Battery
Main FeaturesMain Features
![Page 8: Power u ps hpm3300 presentation-r1](https://reader031.vdocuments.net/reader031/viewer/2022012406/55c9b4febb61eb201b8b474a/html5/thumbnails/8.jpg)
Wide input voltage: 208~478Vac (3/3)
Sinusoidal input current THDI <3%
High input power factor up to 1 (0,99)
High efficiency up to 95.5%
Output power factor up to 1
Plug-and-Play Hot Swappable Module
Remote EPO Function
Control Monitoring with Touch-screen LCD Graphic Display
Wide input voltage: 208~478Vac (3/3)
Sinusoidal input current THDI <3%
High input power factor up to 1 (0,99)
High efficiency up to 95.5%
Output power factor up to 1
Plug-and-Play Hot Swappable Module
Remote EPO Function
Control Monitoring with Touch-screen LCD Graphic Display
Main FeaturesMain Features
![Page 9: Power u ps hpm3300 presentation-r1](https://reader031.vdocuments.net/reader031/viewer/2022012406/55c9b4febb61eb201b8b474a/html5/thumbnails/9.jpg)
Superior MTBF (> 220,000 hrs) and MTTR ( < 30 min. )
Powerful Charger Built-in Module and UPS Cabinet
Matching Battery Module also Available
Megatec/Mod Bus Protocol
Versatile Communication Interface
Superior MTBF (> 220,000 hrs) and MTTR ( < 30 min. )
Powerful Charger Built-in Module and UPS Cabinet
Matching Battery Module also Available
Megatec/Mod Bus Protocol
Versatile Communication Interface
Main FeaturesMain Features
![Page 10: Power u ps hpm3300 presentation-r1](https://reader031.vdocuments.net/reader031/viewer/2022012406/55c9b4febb61eb201b8b474a/html5/thumbnails/10.jpg)
NO SPOF (Single Points of Failure)
Highest Availability 0.999998
Safe Swappable Modular Concept
NO SPOF (Single Points of Failure)
Highest Availability 0.999998
Safe Swappable Modular Concept
Decentralized Parallel Structure ConceptDecentralized Parallel Structure Concept
![Page 11: Power u ps hpm3300 presentation-r1](https://reader031.vdocuments.net/reader031/viewer/2022012406/55c9b4febb61eb201b8b474a/html5/thumbnails/11.jpg)
Single Line Module Diagram Single Line Module Diagram
EMI AC/DC Converter BUSDC/AC Inverter
Static Bypass
Battery
DC/DC Converter Charger
I/P O/PEMI
![Page 12: Power u ps hpm3300 presentation-r1](https://reader031.vdocuments.net/reader031/viewer/2022012406/55c9b4febb61eb201b8b474a/html5/thumbnails/12.jpg)
Only 3U Height
10KVA/15KVA/20KVA/25KVA/30KVA/40KVA Modules Available
Only 3U Height
10KVA/15KVA/20KVA/25KVA/30KVA/40KVA Modules Available
Compact in Size Compact in Size
![Page 13: Power u ps hpm3300 presentation-r1](https://reader031.vdocuments.net/reader031/viewer/2022012406/55c9b4febb61eb201b8b474a/html5/thumbnails/13.jpg)
Parallel up to 13 Modules
Load Sharing
More than 1 Module can be set at Redundancy
Parallel up to 13 Modules
Load Sharing
More than 1 Module can be set at Redundancy
Modular N + X Parallel RedundancyModular N + X Parallel Redundancy
H=1.4MH=1.4M
H=2.0MH=2.0MPay as you grow
Pay as you grow
![Page 14: Power u ps hpm3300 presentation-r1](https://reader031.vdocuments.net/reader031/viewer/2022012406/55c9b4febb61eb201b8b474a/html5/thumbnails/14.jpg)
H=1.4M/1.6M : up to 5 Modules
H=2.0M : up to 13 Modules
UPS Modules/Battery Modules
System Parallel Maximum: 4
H=1.4M/1.6M : up to 5 Modules
H=2.0M : up to 13 Modules
UPS Modules/Battery Modules
System Parallel Maximum: 4
Parallel up to 13 Units for Each RackParallel up to 13 Units for Each Rack
UPS Modules Battery Modules
![Page 15: Power u ps hpm3300 presentation-r1](https://reader031.vdocuments.net/reader031/viewer/2022012406/55c9b4febb61eb201b8b474a/html5/thumbnails/15.jpg)
Sizing What You Need Now
Pay as You Grow
Flexibility/Scalability for Future Expansion
Low Service Contracts
Sizing What You Need Now
Pay as You Grow
Flexibility/Scalability for Future Expansion
Low Service Contracts
Invest as You GrowInvest as You Grow
No over-sizing UPS &
Add power w/o increasing footprint
No over-sizing UPS &
Add power w/o increasing footprint
![Page 16: Power u ps hpm3300 presentation-r1](https://reader031.vdocuments.net/reader031/viewer/2022012406/55c9b4febb61eb201b8b474a/html5/thumbnails/16.jpg)
High Power Density High Power Density
Footprint Reduction, less Surface Costs
Easy to upgrade from 10KVA up to 520KVA per Rack
Footprint Reduction, less Surface Costs
Easy to upgrade from 10KVA up to 520KVA per Rack
![Page 17: Power u ps hpm3300 presentation-r1](https://reader031.vdocuments.net/reader031/viewer/2022012406/55c9b4febb61eb201b8b474a/html5/thumbnails/17.jpg)
HPM Cabinet DiagramHPM Cabinet Diagram
Monitor Module
LCD displayer Communication
UPS Module 13#
UPS Module 9#
UPS Module 2#
UPS Module 1#
Maintain Bypass
I/P O/P
Battery
BPS InductorBPS
Output Switch
![Page 18: Power u ps hpm3300 presentation-r1](https://reader031.vdocuments.net/reader031/viewer/2022012406/55c9b4febb61eb201b8b474a/html5/thumbnails/18.jpg)
High Input Power Factor up to 1High Input Power Factor up to 1
![Page 19: Power u ps hpm3300 presentation-r1](https://reader031.vdocuments.net/reader031/viewer/2022012406/55c9b4febb61eb201b8b474a/html5/thumbnails/19.jpg)
Low Input Current THDI <3% Low Input Current THDI <3%
![Page 20: Power u ps hpm3300 presentation-r1](https://reader031.vdocuments.net/reader031/viewer/2022012406/55c9b4febb61eb201b8b474a/html5/thumbnails/20.jpg)
High Efficiency up to 95.5% High Efficiency up to 95.5%
![Page 21: Power u ps hpm3300 presentation-r1](https://reader031.vdocuments.net/reader031/viewer/2022012406/55c9b4febb61eb201b8b474a/html5/thumbnails/21.jpg)
Plug-and-Play Hot Swappable ModulePlug-and-Play Hot Swappable Module High Power Density Reduced Footprint
Flexibility/Scalability
Lowest Service Cost
Lowest Installation Cost
![Page 22: Power u ps hpm3300 presentation-r1](https://reader031.vdocuments.net/reader031/viewer/2022012406/55c9b4febb61eb201b8b474a/html5/thumbnails/22.jpg)
Common Battery Common Battery
Several UPS Modules share one battery module
3/
![Page 23: Power u ps hpm3300 presentation-r1](https://reader031.vdocuments.net/reader031/viewer/2022012406/55c9b4febb61eb201b8b474a/html5/thumbnails/23.jpg)
Powerful Charger Powerful Charger Module: 10A (Max) Charge Current (A):
HPM3300-60/100k HPM3300-200/250k HPM3300-300/400K HPM3300-520K
Max. 30A Max. 60A Max. 100A Max. 130A
Max. Charging Current Settable
![Page 24: Power u ps hpm3300 presentation-r1](https://reader031.vdocuments.net/reader031/viewer/2022012406/55c9b4febb61eb201b8b474a/html5/thumbnails/24.jpg)
3-Stage Intelligent Charging Modes3-Stage Intelligent Charging Modes
Constant current
Constant voltage
Floating Charge
![Page 25: Power u ps hpm3300 presentation-r1](https://reader031.vdocuments.net/reader031/viewer/2022012406/55c9b4febb61eb201b8b474a/html5/thumbnails/25.jpg)
Battery Voltage Configurable Battery Voltage Configurable
3:3 phase
± 192Vdc/ ± 204Vdc/ ± 216Vdc/ ± 228Vdc/ ± 240Vdc Configurable
Decrease Initial Investment
Increase Competition
![Page 26: Power u ps hpm3300 presentation-r1](https://reader031.vdocuments.net/reader031/viewer/2022012406/55c9b4febb61eb201b8b474a/html5/thumbnails/26.jpg)
HPM-BF36100 or BF36120 36pcs of 100AH or 120AH
Matching battery Frame
![Page 27: Power u ps hpm3300 presentation-r1](https://reader031.vdocuments.net/reader031/viewer/2022012406/55c9b4febb61eb201b8b474a/html5/thumbnails/27.jpg)
Matching Battery Module Also Available Matching Battery Module Also Available Battery Module: for Max. 18pcs 7AH/9AH bat.
Simply plug into UPS System
Only 3U Height
![Page 28: Power u ps hpm3300 presentation-r1](https://reader031.vdocuments.net/reader031/viewer/2022012406/55c9b4febb61eb201b8b474a/html5/thumbnails/28.jpg)
Module LCD Display
Input Voltage/Frequency Output Voltage/Frequency Load Capacity, Battery Voltage/Current Charge Modes/Charger Status Internal/Ambient Temperature Module ID/Status Alarm Codes
![Page 29: Power u ps hpm3300 presentation-r1](https://reader031.vdocuments.net/reader031/viewer/2022012406/55c9b4febb61eb201b8b474a/html5/thumbnails/29.jpg)
Control Monitoring with Touch-screen LCDGraphic Display
Control Monitoring with Touch-screen LCDGraphic Display
![Page 30: Power u ps hpm3300 presentation-r1](https://reader031.vdocuments.net/reader031/viewer/2022012406/55c9b4febb61eb201b8b474a/html5/thumbnails/30.jpg)
Full-Screen status for Input, Output, Battery, Modules
ONLINE 30KVA 22-12-2008ID:01 08:30
◄Outp
utModu
leInput
BattStat
e►
APhase Voltage (v) 220Phase Current (A) 1Frequency (HZ) 50Active Power ( KW) 0.0Apparent Power (KVA) 0.0Load percent(%) 0Load crest factor 0.0
ONLINE 30KVA 22-12-2008ID:01 08:30
◄Outp
utModu
leInput
BattStat
e►
Module01 A B C Invert Voltage (V) 380 380
380 Invert Current (A) 220 220
220 Frequency (HZ) 50 Positive Bus Voltage (V) 400 Negative Bus Voltage (V) 400 Code 8000-8000 D800-8000 0000-0000 0000-0000
Back
ONLINE 30KVA 22-12-2008ID:01 08:30
◄Outp
utModul
eInpu
tBatt
State
►
Mains A B C Phase Voltage (V) 380 380
380 Phase Current (A) 220 220
220 Frequency (HZ) 50 Power Factor 0.97 0.97
0.97 Bypass Phase Voltage (V) 220 220
220 Frequency (HZ) 50
ONLINE 30KVA 22-12-2008ID:01 08:30
◄Outp
utModul
eInpu
tBat
tStat
e►
Positive Battery Voltage (V) 240.0Negative Battery Voltage (V) 240.0Positive Battery Current (A) 10.0Negative Battery Current (A) 10.0Battery State ChargeBattery Temperature (℃) 28Lasting (min) 90
![Page 31: Power u ps hpm3300 presentation-r1](https://reader031.vdocuments.net/reader031/viewer/2022012406/55c9b4febb61eb201b8b474a/html5/thumbnails/31.jpg)
Command
Battery Test
Buzzer Set
Default Set
Command
Battery Test
Buzzer Set
Default Set
ONLINE
30KVA 22-12-2008 ID:01 08:30
◄ Comma
ndSetting
Record
Version
►
Battery TestBuzzer Set MuteDefault Set
Self-Test Date Mode: Weekly ▲ Week: SAT Time: 18:36 ▼ Lasting: 60min
Ensure Cancel
LBS Group Setting
▼Master▲
Ensure Cancel
![Page 32: Power u ps hpm3300 presentation-r1](https://reader031.vdocuments.net/reader031/viewer/2022012406/55c9b4febb61eb201b8b474a/html5/thumbnails/32.jpg)
Setting
Language
System Parameters
Working Modes
Setting
Language
System Parameters
Working Modes
ONLINE 30KVA 22-12-2008 ID:01 08:30
◄Comman
d Setting Record
Version
►
Language Change Password Date Setting 2008-12-22 08:30:00 Back-Light Delay 10Min Contrast 20 Self-Test Date STA 18:36 FOR:60min Back Timing of ON/OFF ON:MON 08:48 OFF:SUN 17:25 Next
ONLINE 30KVA 22-12-2008ID:01 08:30
◄ Comman
dSettin
gRecor
dVersion ►
Work Mode Single LBS Group Setting Master System Voltage Level 220V System Frequency Level 50HZ Auto Turn-on Enable Bypass Frequency Range 2% Bypass Volt. Upper Limit 10% Back Bypass Volt. Lower Limit -30% O/P Volt Micro tuning 0% Next
![Page 33: Power u ps hpm3300 presentation-r1](https://reader031.vdocuments.net/reader031/viewer/2022012406/55c9b4febb61eb201b8b474a/html5/thumbnails/33.jpg)
Setting
Parallel ID
Battery Voltage/Capacity
Setting
Parallel ID
Battery Voltage/Capacity ONLINE 30KVA 22-12-2008 ID:01 08:30
◄ Comma
ndSettin
gRecor
dVersion ►
Parallel ID 01M/S hot standby Cyc. 6 MonUPS Output EnablePre-Alarm Time 14 MinFloat Volt Revise 0.001Parallel Amount 04Parallel Redundancy 01 Back
Next
ONLINE 30KVA 22-12-2008
ID:01 08:30
◄ Command Setting Record Version ►
Single Battery Volt. 12VBattery Number 20Battery Group 1Single Battery Capa. 100AHBoost Upper Limit Volt. 2.31Float Base Volt. 2.25Battery Protect Volt. 1.70Boost Charge Enable BackBoost Last Time 231 MinMax Charge Current 25A Next
![Page 34: Power u ps hpm3300 presentation-r1](https://reader031.vdocuments.net/reader031/viewer/2022012406/55c9b4febb61eb201b8b474a/html5/thumbnails/34.jpg)
Record All Events/Alarm Message Display Up to 49 events 50 alarm messages
ONLINE 30KVA 22-12-2008ID:01 08:30
◄ Command Setting Record Version ►
Single Battery Volt. 12VBattery Number 20Battery Group 1Single Battery Capa. 100AHBoost Upper Limit Volt. 2.31Float Base Volt. 2.25Battery Protect Volt. 1.70Boost Charge Enable BackBoost Last Time 231 MinMax Charge Current 25A Next
![Page 35: Power u ps hpm3300 presentation-r1](https://reader031.vdocuments.net/reader031/viewer/2022012406/55c9b4febb61eb201b8b474a/html5/thumbnails/35.jpg)
Hot Standby Mode
ONLINE 30KVA 22-12-2008
ID:01 08:30
◄ Command Setting Record Version ►
Parallel ID 01M/S hotstandby Cyc. 6 MUPS Output EnaPre-Alarm Time 14 Float Volt Revise 0.00Parallel Amount 04Parallel Redundancy 01 Back Next
M/S hot standby Cyc.
▼ 3 ▲
Ensure Cancel
![Page 36: Power u ps hpm3300 presentation-r1](https://reader031.vdocuments.net/reader031/viewer/2022012406/55c9b4febb61eb201b8b474a/html5/thumbnails/36.jpg)
Battery Setti
ng
ONLINE 30KVA 22-12-2008 ID:01 08:30
◄ Command Setting Record Version ►
Single Battery Volt. 12VBattery Number 20Battery Group 1Single Battery Capa. 100AHBoost Upper Limit Volt. 2.31Float Base Volt. 2.25Battery Protect Volt. 1.70Boost Charge Enable BackBoost Last Time 231 MinMax Charge Current 25A Next
ONLINE 30KVA 22-12-2008
ID:01 08:30 ◄ Command Setting Record Version ►
Single Battery Volt. 12VBattery Number 20Battery Group 1Single Battery Capa. 100AHBoost Upper Limit Volt. 2.31Float Base Volt. 2.25Battery Protect Volt. 1.70Boost Charge Enable BackBoost Last Time 231 MinMax Charge Current 25A Next
ONLINE30KVA 22-12-2008 ID:01 08:30
◄ Command Setting Record Version ►
Single Battery Capa.
1000
7 8 9Cancel
4 5 6 ←
1 2 3 →
. 0Ensure
Battery Number
▼ 20 ▲
Ensure Cancel
Battery Group
▼ 1 ▲
Ensure Cancel
![Page 37: Power u ps hpm3300 presentation-r1](https://reader031.vdocuments.net/reader031/viewer/2022012406/55c9b4febb61eb201b8b474a/html5/thumbnails/37.jpg)
Charging Current Setti
ngCharging
Current Setting
![Page 38: Power u ps hpm3300 presentation-r1](https://reader031.vdocuments.net/reader031/viewer/2022012406/55c9b4febb61eb201b8b474a/html5/thumbnails/38.jpg)
Independent Separate Bypass Independent Separate Bypass
Each Individual Modular has its own Bypass Switch
Maintenance bypass switch
![Page 39: Power u ps hpm3300 presentation-r1](https://reader031.vdocuments.net/reader031/viewer/2022012406/55c9b4febb61eb201b8b474a/html5/thumbnails/39.jpg)
Versatile Communication InterfacesVersatile Communication Interfaces RS485 Ports RS232 Port Mod Bus Port 2 x Intelligent slot (SNMP, relay option)
Network Management Card replacement
1 : Dry Contact Relay
2 : SNMP port
![Page 40: Power u ps hpm3300 presentation-r1](https://reader031.vdocuments.net/reader031/viewer/2022012406/55c9b4febb61eb201b8b474a/html5/thumbnails/40.jpg)
Versatile Communication InterfacesVersatile Communication Interfaces MEGAtec Protocol Supported SNMP Card
![Page 41: Power u ps hpm3300 presentation-r1](https://reader031.vdocuments.net/reader031/viewer/2022012406/55c9b4febb61eb201b8b474a/html5/thumbnails/41.jpg)
Versatile Communication InterfacesVersatile Communication Interfaces Dry Contact Relay
Pin Function
1
O/P
Utility Failure
2 /
3 Battery Low
4 On bypass
5 UPS Fault
6 Inverter On
7 UPS Alarm
8 Common
9I/P
+12V
10 0V
![Page 42: Power u ps hpm3300 presentation-r1](https://reader031.vdocuments.net/reader031/viewer/2022012406/55c9b4febb61eb201b8b474a/html5/thumbnails/42.jpg)
Cabinet Outlook --H=1.4M ( 5 Modules )Cabinet Outlook --H=1.4M ( 5 Modules )
Front View Front View Rear ViewRear View
![Page 43: Power u ps hpm3300 presentation-r1](https://reader031.vdocuments.net/reader031/viewer/2022012406/55c9b4febb61eb201b8b474a/html5/thumbnails/43.jpg)
Cabinet Outlook --H=1.6M ( 5 Modules )
![Page 44: Power u ps hpm3300 presentation-r1](https://reader031.vdocuments.net/reader031/viewer/2022012406/55c9b4febb61eb201b8b474a/html5/thumbnails/44.jpg)
Cabinet Outlook --H=2M ( 8 Modules )
![Page 45: Power u ps hpm3300 presentation-r1](https://reader031.vdocuments.net/reader031/viewer/2022012406/55c9b4febb61eb201b8b474a/html5/thumbnails/45.jpg)
Cabinet Outlook --H=2M ( 10 Modules )Cabinet Outlook --H=2M ( 10 Modules )
Front View Front View Rear ViewRear View
![Page 46: Power u ps hpm3300 presentation-r1](https://reader031.vdocuments.net/reader031/viewer/2022012406/55c9b4febb61eb201b8b474a/html5/thumbnails/46.jpg)
Cabinet Outlook --H=2M ( 10 Modules )
![Page 47: Power u ps hpm3300 presentation-r1](https://reader031.vdocuments.net/reader031/viewer/2022012406/55c9b4febb61eb201b8b474a/html5/thumbnails/47.jpg)
Cabinet Outlook --H=2M ( 13 Modules )
![Page 48: Power u ps hpm3300 presentation-r1](https://reader031.vdocuments.net/reader031/viewer/2022012406/55c9b4febb61eb201b8b474a/html5/thumbnails/48.jpg)
Module Outlook Module Outlook
Front ViewFront View Rear ViewRear View
10K/15K/20K/25k/30k
40k Front ViewFront View Rear ViewRear View
![Page 49: Power u ps hpm3300 presentation-r1](https://reader031.vdocuments.net/reader031/viewer/2022012406/55c9b4febb61eb201b8b474a/html5/thumbnails/49.jpg)
Product Specifications
![Page 50: Power u ps hpm3300 presentation-r1](https://reader031.vdocuments.net/reader031/viewer/2022012406/55c9b4febb61eb201b8b474a/html5/thumbnails/50.jpg)
Product Specifications
![Page 51: Power u ps hpm3300 presentation-r1](https://reader031.vdocuments.net/reader031/viewer/2022012406/55c9b4febb61eb201b8b474a/html5/thumbnails/51.jpg)
![Page 52: Power u ps hpm3300 presentation-r1](https://reader031.vdocuments.net/reader031/viewer/2022012406/55c9b4febb61eb201b8b474a/html5/thumbnails/52.jpg)
![Page 53: Power u ps hpm3300 presentation-r1](https://reader031.vdocuments.net/reader031/viewer/2022012406/55c9b4febb61eb201b8b474a/html5/thumbnails/53.jpg)
Special Models HPM-SA for Standard 19” Frame
can be used as a single unitModel HPM3315/HPM3320/HPM3325-SA
Capacity 15KVA/13.5KW, 20KVA/18KW, 25KVA/22.5KW
Input Voltage 208Vac~478Vac
Output Voltage 380/400/415Vac
Battery Voltage 384V/408V/432/480Vdc Settable
Parallel Quantity 4(default), 5~6 or 7~10 Settable(remove J31 & J31/J30)
Dimension(WxHxD) 443x131x580
Net Weight(w/o battery) 31.0
Model HPM-BR32007
Battery Type/Quantity HC1221W(12V/21W)/32pcs
Dimension 483x132x680mm
Net Weight(w/o battery) 76.0
![Page 54: Power u ps hpm3300 presentation-r1](https://reader031.vdocuments.net/reader031/viewer/2022012406/55c9b4febb61eb201b8b474a/html5/thumbnails/54.jpg)
Standard 19” Rack SolutionThe HPM3300-SA is designed to be the most versatile UPS on the market and provides the best technical & commercial solutions to meet individual power protection needs.
It fixes in various depths of standard
19” rack cabinet.