poweract active filter
TRANSCRIPT
PowerAct Operations Manual Rev 0.2 P a g e 1 | 46
Visit Powerside.com for the latest manual
PowerAct Active Filter
Operations Manual
The information contained in this document is subject to change without notice. POWERSIDE MAKES NO WARRANTY OF ANY KIND WITH REGARD TO THIS MATERIAL, INCLUDING, BUT NOT LIMITED TO, THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR USE. Powerside shall not be liable for errors contained herein or for incidental or consequential damages in connection with the furnishing, performance, or use of this material. If you do not accept this limitation on liability, please return the product to Powerside prior to use. If you find information in this manual that is incorrect, misleading, or incomplete, we would appreciate your comments and suggestions.
Powerside 7850 TransCanada Hwy 980 Atlantic Ave. Saint-Laurent, Quebec Alameda, CA 514-333-8393 510-522-4400 www.powerside.com
PowerAct Operations Manual Rev 0.2 P a g e 2 | 46
Visit Powerside.com for the latest manual
Product Identification and Version
The product identification plate is in the cabinet door. Prior to installation and commissioning
verify the system configuration with site conditions.
The following product configuration are and covered by this operations manual:
PowerAct Active Filter
PowerAct: 3W, 480V or 600V/up to 4 x125 A modules
Vac Amps NEMA 3R NEMA 1/12
Customer P/N Engineering P/N Customer P/N Engineering P/N
480 125 PF5R025PL-3R PSAF-01255.1/0 B3R-
0 PSAF0125.5-01
PSAF-01255.1/0 B01-0
480 250 PF5R040PL-3R PSAF-02505.2/0 B3R-
0 PSAF0250.5-01
PSAF-02505.2/0 B01-0
480 375 PF5R050PL-3R PSAF-03755.3/0 B3R-
0 PSAF0375.5-01
PSAF-03755.3/0 B01-0
480 500 PF5R060PL-3R PSAF-05005.4/0 B3R-
0 PSAF0500.5-01
PSAF-05005.4/0 B01-0
600 125 PSAF0125.7-3R PSAF-01257.1/0 B3R-
0 PSAF0125.7-01
PSAF-01257.1/0 B01-0
600 250 PSAF0250.7-3R PSAF-02507.2/0 B3R-
0 PSAF0250.7-01
PSAF-02507.2/0 B01-0
600 375 PSAF0375.7-3R PSAF-03757.3/0 B3R-
0 PSAF0375.7-01
PSAF-03757.3/0 B01-0
600 500 PSAF0500.7-3R PSAF-05007.4/0 B3R-
0 PSAF0500.7-01
PSAF-05007.4/0 B01-0
PowerAct Operations Manual Rev 0.2 P a g e 3 | 46
Visit Powerside.com for the latest manual
Table of Contents
Contents
1 Information on this document .............................................................................................................................. 4
2 Safety Warnings & Instructions ........................................................................................................................... 5
3 Function description ............................................................................................................................................. 7
4 User Interfaces .................................................................................................................................................... 10
5 Operating the PowerAct Active Filter ................................................................................................................ 13
6 Commissioning and system start-up ................................................................................................................. 15
7 Display and Control Screen—Touch Panel (HMI) ........................................................................................... 16
7.1 Control modes ..................................................................................................................................................... 17
7.2 Reactive power Settings ..................................................................................................................................... 18
7.3 Load Balancing .................................................................................................................................................... 20
7.4 Harmonic compensation ..................................................................................................................................... 21
7.5 System Identification Algorithm (SIA) Harmonic Correction ........................................................................... 21
7.6 DC voltage regulation—DC link ......................................................................................................................... 25
8 Network configuration ........................................................................................................................................ 26
9 Information on complying with grid connection rules ..................................................................................... 27
APPENDIX A: Fieldbus States & Commands ............................................................................................................ 33
PowerAct Operations Manual Rev 0.2 P a g e 4 | 46
Visit Powerside.com for the latest manual
1 Information on this document
Information on this document
The text can include abbreviations. The first usage will be written out in full and the abbreviation will follow in
parentheses.
Terminology Abbreviation
Active filter ACF
IGBT Power Unit IPU
Measurement Unit MIO
Control Computer Unit CCU
Web User Interface WUI
Human Machine Interface (touch panel) (HMI)
System Identification Algorithm—grid analysis SIA
Per Unit—these are unitless dimensions, based on the system rated
value. Example: 1.1 pu voltage means grid rated voltage x 1.1.
pu
Scope of manual
This manual describes the user interface and the operating modes of the PowerAct Active Filter series.
The user manual describes how to use the installed software, such as for operation, basic configuration and
commissioning.
PowerAct Operations Manual Rev 0.2 P a g e 5 | 46
Visit Powerside.com for the latest manual
2 Safety Warnings and Instructions
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
Please read the operating instructions prior to installation. The operating instructions explain how to operate
the product safely. The notes listed below warn of possible sources of danger and provide information on the
correct use of the active filter.
Priority must be given to the respectively applicable, recognized regulations of the technology, as well as the
accident prevention regulations and, if applicable, internal regulations in the most up-to-date version.
The system contains LETHAL VOLTAGES. All repairs and service should be performed by
AUTHORIZED PERSONNEL ONLY.
Death, serious injury, or fire hazard could result from improper connection or operation of this instrument.
Read and understand this manual before connecting the device.
This equipment may present an arc flash hazard. Personal Protection Equipment may be required. Refer
to NFPA70E for sections related to Standard for Electrical Safety in the Workplace.
This system contains energy storage devices (capacitors) that may present a shock hazard even with
primary power disconnected
Ensure that the current transformer’s secondary circuit is short-circuited (CT shorting block provided by
others) prior to working on current transformer circuits. Under no circumstances should the secondary
circuit of the CTs be operated in the open state as lethal voltages may be present.
The voltage of the DC link may be above 1000 V. Allow 60 minutes discharging time before work. Verify
voltage levels using appropriate instrument.
All local applicable standards and specifications, in addition to the generally recognized codes of practice,
must be observed.
If configured for remote communications an unintended/remote start may occur if input power is available.
Remove power if personal safety makes it essential to prevent an unintentional start.
All people who are involved in the setting up, commissioning, operation, maintenance or repair of the
device must be adequately professionally qualified and must read, and following, operating instructions
provided. If you are unsure TAKE NO ACTION without contacting qualified personnel.
DANGER
WARNING
PowerAct Operations Manual Rev 0.2 P a g e 6 | 46
Visit Powerside.com for the latest manual
Do not install or operation this system close to a gas or electric heat source
The operating environment should be maintained within the parameters stated in this manual
Keep surrounding uncluttered, clean, and free from excessive moisture and particulates. The device may only be used in accordance with its intended use. Unauthorized and improperly performed
work on the device and tampering with system-internal protection functions are prohibited!
Any persons who configure settings on the device, commission it or change its settings at a later date must
be sufficiently qualified, meaning that they have successfully completed a product-specific training
program.
NOTICE: These operating instructions have been created with great care; however, Powerside cannot
assume any liability for the freedom from errors of the operating instructions or for damage resulting from
the use of the manual. We will strive to fix any errors that we become aware of as quickly as possible.
Please refer to the Powerside web site for the latest version of this manual.
The PowerAct Active Filter is an electronic grid filter. Its role is to feed fundamental (50/60 Hz) and
harmonic currents to improve the voltage quality in electrical AC voltage grids.
It must only be possible for authorized persons to come into contact with, to access and to intervene in the
PowerAct Active Filter—i.e., the cabinet door is to be kept closed and locked. The key to the room/cabinet
may only be available to authorized persons.
The devices may only be operated with the cabinet doors closed.
The devices may only be operated if they have been installed correctly (see PowerAct Installation Manual).
Correct installation includes both the attachment and state of the cabinet, as well as the electrical
connection and electrical protection.
The PowerAct Active Filter may only be used for the function described in this document.
Interventions in the hardware and software are not permitted.
The PowerAct Active Filter is designed for the environmental conditions described in the installation
manual and may only be operated under these conditions.
CAUTION
INTENDED USE
PowerAct Operations Manual Rev 0.2 P a g e 7 | 46
Visit Powerside.com for the latest manual
3 Function description
This section provides an overview of the compensation settings of the PowerAct Active Filter. These settings can
be changed via the touch panel (HMI) or the Web User Interface (WUI). Details on this are provided in a later
section. Please refer to the Overview section in the PowerAct Installation Manual for an overview of the operating
principle.
Before the system can be used, it must be commissioned. This includes setting up the basic and operating
parameters of the system. Commissioning can either be performed via the touch panel or the WUI.
There are three (3) basic compensation modes
Reactive Power Compensation
Load Balancing
Harmonic Compensation
Reactive power compensation
The active filter can be configured for droop or dynamic reactive power compensation.
In static operation, a defined reactive power (Qref—Reactive Power Control) is generated similarly to a fixed
capacitor or choke.
In dynamic operation, the filter regulates its output power of the fundamental oscillation such that a defined power
factor (range) is maintained at the measurement point. The target range can be specified via an upper and lower
limit value of the active power factor (cosφ).
Note: All settings relate only to the fundamental (60Hz) and have no influence on the harmonics. Please note in
comparison measurements that the active power factor (cosφ) in distorted grids does not correspond to the power
factor (λ), because the active power factor (cosφ) does not contain a harmonic component by definition.
Load balancing (LB)
Load balancing is used to balance the asymmetrical current consumption of one or more loads at a network node
defined by the MIO measurement point. The function compensates for the difference of the fundamental
oscillation components of the three-phase currents with each other and thus produces a symmetrical grid load.
The regulation is configured separately for the negative sequence system (asymmetry caused by load between
two conductors) and zero sequence system (asymmetry caused by single-phase loads L against N, 4-wire
systems only):
Balancing ∆: Compensation level as a percentage [%] of the negative sequence system
PowerAct Operations Manual Rev 0.2 P a g e 8 | 46
Visit Powerside.com for the latest manual
Through this division into the symmetrical components, the symmetry is restored without any explicit
compensation of reactive power.
Functional notes:
The active and reactive components of the current will always be balanced with the same compensation
level
Prerequisites for zero sequence system compensation are the use of four-wire IPUs with N-connection and a
three-phase load/grid current measurement with the MIO.
Balancing the fundamental oscillation leads to an increased load on the DC link and can therefore lead to the
power limitation (derating) of the system with the message “Derating: DC voltage unbalanced”:
Variable per IPU Derating AC RMS
current 3W
Positive sequence system 125A
Negative sequence system 125A
Zero sequence system NA
Table 2: Derating limit values per IPU
The open/closed loop parameterization has the following effect on the behavior
Open loop: The currents are measured at the load and set at the IPU output
Closed loop: The currents are measured in the grid and regulated at the measurement point
Harmonic Compensation
The function SHC (Selective Harmonic Compensation) compensates for (“filters”) harmonics in the energy supply
grid.
For this, differentiated modes are distinguished for this which achieve both optimized current-based and
optimized voltage-based results for different requirements and grid conditions.
The following modes are available separately and can be individually configured for each harmonic
(3rd to 51st order):
1. Switched off No output
2. To zero Regulates the current output at the system connection point to zero
3. Compensation I Reduces the harmonic current measured at the connection point of the MIO by the
set compensation level (0 ...100%)—with current measurement.
Compensation U Reduces the
harmonic voltage measured at the connection point of the MIO by the set
compensation level (0 ...100%)—without current measurement.
PowerAct Operations Manual Rev 0.2 P a g e 9 | 46
Visit Powerside.com for the latest manual
4. 5. U Limit/I-Ctrl Limits the harmonic voltage measured at the connection point of the MIO to the set
maximum value taking the set maximum compensation level (0 … 100% based on
current) into consideration—with current measurement.
U Limit/U-Ctrl Limits the
harmonic voltage measured at the connection point of the MIO to the set maximum
value taking the set maximum compensation level (0 … 100% based on voltage)
into consideration—without current measurement
voltage-based compensation modes.
Modes 4 and 6 do not need an external current transformer. They function exclusively based on the measured
line voltage.
In these modes, the compensation level relates to the reduction of the voltage based on the SIA grid analysis.
0% corresponds to the operating mode “to zero” (no output current at this frequency)
100% regulates to the line voltage only and reduces this to the desired value 0.
NOTICE: It is strongly recommended that modes 4 and 6 NOT BE USED with manual SIA!
NOTICE: The tolerance in terms of the compensation level in these modes can be up to +/-30%. It is therefore
recommended that full compensation (100%) or the combination with Limit U be used as the setting.
Current-Based Compensation Modes
In modes 3 and 5, the compensation level is based on the current. Here, the compensation level describes the
ratio of system output current to grid current at the MIO connection point:
0% corresponds to the operating mode “to zero” (no output current at this frequency)
100% only regulates the grid current and reduces this to the desired value 0.
Limiting compensation modes
In modes 5 and 6, the compensation is only active if the configured voltage limit values are exceeded at the MIO
connection point. The system only supplies enough output necessary to comply with these limits.
In all modes, the compensation level applies in the same way for the positive, negative and zero sequence
systems, and is only specified once per harmonic. Compensation of the zero sequence system is only relevant
for 4-wire systems. The selective regulators for all odd-numbered harmonics of the ordinal numbers 3rd to 51st
operate parallel to each other without functional limitations in a system configuration (up to max. 4x IPUs and 1x
MIO).
With the SIA function (System Identification Algorithm), the system performs an automated grid scan to
determine the frequency response.
PowerAct Operations Manual Rev 0.2 P a g e 10 | 46
Visit Powerside.com for the latest manual
4 User Interfaces
There are four different user interfaces:
1. Human Machine Interface (HMI) via touch panel or Web User Interface (WMI)
2. Fieldbus interface (to a superordinate control technology system)
3. Digital inputs and outputs
4. SD card (offline system configuration via the manipulation of text files)—NOTICE: ONLY TO BE USED BY
AUTHORIZED SERVICE PERSONNEL!
Human Machine Interface (HMI)
The touch panel and WUI (Web User Interface) layouts are as effectively identical. The WUI (Java
applet) includes additional functions for data management on the SD card
touch panel.
The system can be configured, commissioned and operated via the touch panel in the front door. It can be used
to easily set parameters, check operating states, and display the measured data and system state during
operation. The touch panel can be used for entering commands and for menu navigation.
Touching the screen in the designated areas will call up, for example, the operating mode, the menu items or
measured values:
Figure 4.1: HMI home screen
PowerAct Operations Manual Rev 0.2 P a g e 11 | 46
Visit Powerside.com for the latest manual
Number Meaning
1 Device state with current parameter set
2 Message area for warnings and errors
3 Measured values—tap to see further details
4 Date and time
5 Language selection
6 Return to the home screen
7 Menu
8 Stop
9 Pause
10 Start
Table 4.1: Home screen legend
(HMI) home screen
Overview of the most important device functions and operating parameters
An equivalent circuit is displayed in the center
Four info boxes display the following measurement points:
Load (displayed: Irms; THDi; Q; P)
Grid (displayed: Irms; THDi; Q; P)
Busbar (displayed: U, THDu, f)
ACF (displayed: Irms; THDi; Q; Utilization)
Tapping on the info boxes will take you directly to the respective screens with the complete measurement data.
Display Header
Left: State display: (Run, Stop, Eco, Idle, Error) and skipping to the selection menu for the
current parameter set
Center: Pending messages and errors, and skipping to the message list
Right: Company logo and HMI-screenshot function to inserted SD card (in the touch panel)
The parameter set currently in use is displayed.
Tapping the display brings up a new window in which the parameter set can be changed.
Display Footer
Start, Stop, Pause, can be selected here and can be changed from any menu
Date and time
Currently selected language
Home screen button
Menu button
PowerAct Operations Manual Rev 0.2 P a g e 12 | 46
Visit Powerside.com for the latest manual
WUI — Web User Interface
As an alternative, the system can be operated graphically via a PC. To do so, the respective device
is to be connected to the TCP/IP interface of the control computer and the Java applet called up. The
tabs in the interface also provide access to the SD card contents with copy function to the connected
PC. A site-specific IP address can be assigned at the touch panel.
Anybus Fieldbus Interface
The control computer (CCU) has an integrated Anybus interface. Any approved plug-in modules from the
manufacturer HMS can provide native communications using the Modbus and BACnet protocols.
SD Card
The control computer comes equipped with an SD card. In addition to the programs for operating the system, this
memory card also contains all configured parameters. These can be edited offline via a text editor, e.g., to set the
system configuration parameters (hardware configuration) or to configure general basic settings, e.g., to preset
the parameter sets. Card can be inserted or removed only when the system is deactivated. All parameter settings
via touch panel or Java applet are also stored on the SD card (online).
NOTICE: Parameter changes which are made directly in the text files of the SD card are not checked for
plausibility. Incorrect changes can lead to malfunctions or even to irreversible hardware damage—therefore,
changes may only be made by authorized personnel. The manufacturer’s warranty will become void in the event
of unauthorized manipulation of data on the SD card.
The SD cards approved for use is SanDisk, 16 GB, HC, class 4
PowerAct Operations Manual Rev 0.2 P a g e 13 | 46
Visit Powerside.com for the latest manual
5 Operating the PowerAct Active Filter
Once the system has been switched via the switch S1 and it has booted up, it can be started and
stopped via the user interface:
The following internal system states are issued via the user interface Java/touch panel:
Name (No.) Description
INIT System boot-up phase
All system parameters are loaded
IDLE Parameter entry complete
PRECHARGE The pre-charging unit is charging the DC link voltage
STOP-PRECHARGE Pre-charging process interrupted
RUN The system is operating in compensation mode
ERROR Issue of an error message Stops PWM pulsing
Stops compensation mode
PAUSE Compensation of the grid-side current to “zero”
DERATING Output power choking
Table 5.1: System states
Manual start and stop
The control commands are created in local access mode via the Play/Stop/Pause buttons on the HMI
or, in remote access mode, via fieldbus.
Table 5.2: Function buttons and meaning
PowerAct Operations Manual Rev 0.2 P a g e 14 | 46
Visit Powerside.com for the latest manual
Control command Control command set via Target status
Start command • HMI Play button
• Digital inputs (MIOs)
• Via auto-restart or
• auto-start command
• Fieldbus
STATE_RUN
Stop command • HMI Stop button
• Stop command from
the MIO digital input
• Via auto-restart or
auto-start command
• Via induced warm start
• Fieldbus
STATE_IDLE
Pause command • HMI Pause button
• Digital inputs (MIOs)
• Fieldbus (no active PWM)
STATE_PAUSE
Error ACK command • HMI Error ACK button
• Digital inputs (MIOs)
• Via auto-restart
• Fieldbus
If the error is
successfully reset, the
following target state is
set: STATE_IDLE
Table 5.3: system states
Custom alarm messages and warnings
The system contains both hardware and software that continuously monitor the operating states and trigger
alarms or warnings that put the system in a safe, stopped error state or that issue messages to the HMI. Using
the programmable internal digital inputs or outputs, the user can implement remote monitoring.
Acknowledging Alarm Messages
Pending alarms are reported at the HMI. Alarms may be acknowledged. If the cause of an alarm remains a new
alarm is triggered. If an alarm forced the system to standby all alarms must be acknowledged before the system
will allow a restart. It is strongly recommended that the cause of the error be identified before acknowledging an
alarm in order to prevent damage in the system or the installation.
Java application (WUI)
The PowerAct Active Filter can be configured and monitored remotely via Ethernet from a PC web browser with a
valid and current Java installation. System IP address can be assigned and viewed at the touch panel (HMI).
Web version displays the same screen views as those appearing on the touch panel. Note that touch panel
access will be denied if while Java app is active.
PowerAct Operations Manual Rev 0.2 P a g e 15 | 46
Visit Powerside.com for the latest manual
6 Commissioning and system start-up
Refer to PowerAct Active Filter Installation Manual.
Review and update the system operating parameters set at the factory
PowerAct Operations Manual Rev 0.2 P a g e 16 | 46
Visit Powerside.com for the latest manual
7 Display and Control Screen—Touch Panel (HMI)
(HMI) Home screen
The button for switching to the home screen is in the footer. The values displayed are
Grid data
Load data
Voltage values
System values
Tapping on the info boxes calls up the respective measurements screen directly.
(HMI) Maintenance > Security > User-Password
The user can log out via this screen. If the user does not log out manually, the system will automatically
log the user out after an admin-configurable delay.
The user PIN can also be re-entered here. The default PIN is 0000.
(HMI) Maintenance > Security > Administrator-Password
The administrator can log out via this screen. If the administrator does not log out manually, the system
will automatically log the administrator out after a configurable delay.
Three setting options are available in the Administrator menu item:
Changing the administrator PIN, default setting is 4321
Automatic user logout parameter field: minimum time: 1 min., maximum time: 30 min.
Password protection selection field: Activation/deactivation of the request for PIN
(HMI) Logger > Error Messages
If an error is triggered or in the event of warning statuses, a text message is displayed in the header of
the HMI. The header will be highlighted in red. The messages remain for as long as the status is
present.
Column: Date
Column: Time
Column: Error
Column: Source
Column: Error message See Table: Errors
System settings and Configuration
Defines the hardware-specific characteristics. Due to the basic nature of these settings, the system must be
RESTARTED after any changes. (Exception: Operator mode)
(HMI) System > Grid
• Nominal voltage: e.g., 480 V Nominal frequency: 50 Hz/60 Hz
• Grid configuration: IT/TN
• Control topology: Closed loop/open loop
PowerAct Operations Manual Rev 0.2 P a g e 17 | 46
Visit Powerside.com for the latest manual
• Level THDv for shutdown: e.g., starting from 20% Telecontrol frequency in Hz
(HMI) System > DSC Port Configuration:
Enter the number of modules (IPUs) and the number of connected measurement modules (MIOs).
One CCU (controller) can operate and connect
• up to 4 connected IPUs
• as well as up to 2 MIOs at the same time.
(HMI) System > Operator Mode
Select between
• Local access => operation via HMI/touch screen. No commands via Modbus are accepted
• Remote access => operation via PLC. No commands from the HMI (touch screen/Java) are
accepted.
7.1 Control modes
There are three control modes available which can be operated in parallel:
(HMI) Control > Basic Setting > Mode > Parameter Set.
The following are available as the control basic settings:
• Reactive power control
• Balancing
• Harmonic compensation
For each control function, a mode, a priority, a dynamic and a rate of change can be selected via the HMI.
The settings are only valid for the respective parameter set (there are eight parameter sets). You can switch
between the parameter sets via the HMI (tapping at top left).
Control Modes Priority
If more than one control mode is active, the system may reach its power limit before control targets have been
reached. If all active control modes have the same priority, these will all be derated in the same way if the power
limit is reached. Control modes can be assigned priorities (1 – 4) with the control mode with the highest priority
derated last. The difference between the priorities of two control modes may not be greater than 1.
Dynamic
This describes the response speed of the system to changing grid states. The dynamic is configured in seconds
and specifies the time constant tau. In ideal conditions, the desired control value reaches 95% of its target value
within a period of 3x tau. Here, 0.1 s is recommended as the standard parameter value. An exception to this is the
dynamic of the reactive power voltage regulation. Here, unitless parameters are used.
For the dynamic, the rule is as fast as necessary, as large as possible. A high dynamic reduces the stability and
accuracy.
PowerAct Operations Manual Rev 0.2 P a g e 18 | 46
Visit Powerside.com for the latest manual
The dynamic for the voltage regulation is not specified in “seconds.” In the case of voltage regulation, the grid
impedance has an influence on the control dynamics. For this reason, the dynamic cannot be specified as a time
constant here.
The recommended dynamic for voltage regulation is unitless and is 0.001. Because the reactive power modes
Qref/Cos (phi)/Vref cannot work in parallel, there is only one dynamic parameter. If the reactive power control
mode is changed, it is necessary to check the dynamic parameter and to adjust it if required.
Change Rate
This is the rate of change when changing the desired value in pu/s. The standard parameter value is “0”—> the
change rate is disabled. This means that the system responds to a desired value change with the control dynamic.
Example: Parameter set to 1 pu/s: the system responds to a desired value change with a maximum rate of
increase of 1 pu/s.
7.2 Reactive power Settings
• Function for feeding in constant reactive power Qref
The Q function feeds in symmetrical reactive power at the connection point highly dynamically in accordance with
the desired value specification.
(HMI) Control > Control Q > Menu overview
All reactive power influences on the grid are done at the fundamental frequency (60 Hz)
The control variable is the imaginary part of the current (+/-90 °) in relation to the line voltage.
• cos (phi) (PFC control)
• Reactive power (Qref control—Q Reference)
• Voltage level (Vref control—V Reference)
(HMI) Control > Control Q > Qref
The Qref function regulates the symmetrical reactive power at the IPU AC connection in accordance with the
desired value specification, whereby this information is specified in kvar inductive (load sign convention).
The change rate for changing the desired value is configured in the basic settings.
• Function for dynamic reactive power compensation PFC Power Factor Correction
(HMI) Control > Control Q > PFC
The function PFC keeps the power factor at the measurement point (mean value over three phases) in a band
between two configurable limit values.
PowerAct Operations Manual Rev 0.2 P a g e 19 | 46
Visit Powerside.com for the latest manual
The limit values are stored on the SD card (negative sign for capacitive and positive sign for inductive
compensation). Eight different parameter sets are available for selection for the online configuration.
In order to enable the parallel operation of distributed systems, a droop is also specified.
Note on compliance with the limit values: The limit values are site-specific and adjusted according to the load
case. Here, it is not ensured that cos (phi) is permanently kept within this band under all circumstances. Instances
with very low active power, cos (phi) can temporarily leave the band.
Figure 7.1: Power Factor Correction operating principle
Function for dynamic voltage regulation Vref Voltage regulation Vref
(HMI) Control > Control Q > Vref.
Voltage reference control:
This function is used to maintain line voltage stability. It feeds in reactive power based on the line voltage in
accordance with the configurable VI characteristic curve.
Within the dead band between values 1 and 2, the voltage is not manipulated. If the line voltage leaves the dead
band, reactive power is fed in based on the slope (droop) of the VI characteristic curve that can be configured
separately for overvoltage and undervoltage.
Here, the system output current is regulated based on the line voltage.
The VI characteristic curve is configured using the following parameters:
Reference 1 voltage: Lower desired value of the voltage [in pu]
Reference 2 voltage: Upper desired value of the voltage [in pu]
PowerAct Operations Manual Rev 0.2 P a g e 20 | 46
Visit Powerside.com for the latest manual
Droop capacitive: VI characteristic curve increase below desired value 1
Droop inductive: VI characteristic curve increase above desired value 2
The droop is the result of the ratio dV/dI. It is to be adapted to individual grid conditions.
Note:
1.0 pu of the voltage V equates to the grid rated voltage
pu of the current I equates to the system rated current
Figure 7.2: Vref operating principle
NOTE: The dynamic for the voltage regulation is not specified in “seconds.” In the case of voltage regulation, the
grid impedance has an influence on the control dynamics. For this reason, the dynamic cannot be specified as a
time constant here. See Control => Basic Settings.
7.3 Load Balancing
(HMI) Control > Load Balancing
The balancing function compensates for the difference of the fundamental (60 Hz) component of the three-phase
currents producing a symmetrical grid load at the measurement point.
The regulation can be configured separately for negative sequence system compensation (systems with three-
and four-wire connection) and zero sequence system compensation (only systems with four-wire connection).
PowerAct Operations Manual Rev 0.2 P a g e 21 | 46
Visit Powerside.com for the latest manual
7.4 Harmonic compensation
The system compensates harmonics up to the 51st harmonic.
(HMI) Control > Harmonics > Harmonics
The following settings can be configured for each harmonic individually:
Mode: Off, To zero, Compensation I, Compensation U, Limit U/Control I, Limit U/Control U
I/ U Comp: Compensation level in [%]
I Limit: No function, created for future function
U Limit: Voltage limit value [%] Superordinate function call ups with a button on the right-hand side:
Copy: Copy all parameters in this screen for pasting into another parameter set
Paste: Paste all parameters copied from another parameter set
Reset: Reset to previous settings
(HMI) Control > Harmonics > Harm. Expert
Configuration of system-critical settings. Changes are only possible in the “Administrator” user level.
Padlock symbol: Click to change color red/green—blocks configuration changes for the “User” user level on
the “Harmonics” screen
Phase manual: Manual configuration of phase-correction values per harmonic
The manually configured phase angles are only used in the “Manual” setting
The phase angles determined by the SIA are only used in the “Automatic” mode
Phase Ext/Int: Display of the phase correction values determined automatically via the SIA at the MIO
measurement point (Ext) and system connection point (Int)
U trip: Voltage limit values that lead to the selective deactivation of the compensation per harmonic
Superordinate function call ups with a button on the right-hand side:
Trigger: Manual triggering of an SIA process for the automatic update of the phase correction angles
Manual: Use of the manually configured phase correction angles (see above)
Logger: Manual triggering of an error log entry on the SD card
Copy: Copy all parameters in this screen for pasting into another parameter set
Paste: Paste all parameters copied from another parameter set
Reset: Reset to previous settings
7.5 System Identification Algorithm (SIA) Harmonic Correction
The System Identification Algorithm (SIA) determines the grid-dependent harmonic corrections. To this end, the
transfer function to the measuring device is determined. The amplitude of the scanning signal can be configured.
For safety reasons, a limit value for the maximum permissible SIA voltage distortion is also configured in parallel
with the amplitude limit value.
PowerAct Operations Manual Rev 0.2 P a g e 22 | 46
Visit Powerside.com for the latest manual
Triggering the SIA
Automatic correction determination is triggered by:
1. The system being restarted (if the Boolean parameter DoSiaAfterBoot is set in the settings.txt file)
2. Manual triggering via button
3. External triggering via fieldbus interface
4. Automatic triggering in the event of resonance detection (violation of the limit value HarmonicDistortion level
UTrip for a harmonic)
The number of times the SIA is triggered in a time interval is monitored. This time interval can be configured.
Both manual SIA trigger commands and automatic control triggers are counted. If the permissible number of SIA
triggers per time interval is exceeded, retriggering the SIA is not permitted. The counter is automatically reset
once the time interval elapses or via a manual acknowledgment.
Persistent storage of data collected by SIA
The data collected by the SIA is stored permanently on the SD card and is also available after a restart of the
system.
Visualization of the SIA results
(HMI) Measurements > Overview > Harmonics Settings
Displays the correction angle for each harmonic as numerical values
(HMI) Measurements > Charts > Bode Diagram
Graphical visualization in a Bode diagram.
Figure 7.4: Bode Diagram
PowerAct Operations Manual Rev 0.2 P a g e 23 | 46
Visit Powerside.com for the latest manual
(HMI) Measurements > Harmonics > Expert
Mode:
Mode of the harmonic compensation.
“ACF to zero”: Output of the ACF is compensated for.
“Compensation”: MIO measurement point is compensated.
“ULimit”: The ACF only begins compensation once the harmonic limit value ULimit has been exceeded.
Phase correction: manual
Correction angle for the controller to adjust the specific frequency to a phase offset between the measuring signal
and the output of the filter (step response of the grid) caused by mains impedance.
Phase iExt/iInt:
Phase correction angle of the internal system model [in °]. Only the automatically determined values are
displayed.
UTrip:
Monitoring limit value of the individual harmonic voltage distortions.
Trigger:
Manual triggering of the SIA for correction angle determination.
NOTE: The commissioning engineer must be aware that with manual triggering the SIA, the harmonic
compensation mode must also be set to “automatic” to ensure that the determined values are also used by the
regulator. If the harmonics compensation mode is set to manual, the manually specified phase correction angles
will be used.
Resonance Monitoring
(HMI) Control > Harmonic Expert
The line voltage level of all harmonics up to the 51st harmonic are continuously monitored to detect and prevent
the excitation of resonances in the grid. The limit values for triggering automatic resonance suppression can be
adapted to the local conditions manually.
The default values are based on EN50160 and are set to 2% above the permissible limit values in accordance
with this standard:
PowerAct Operations Manual Rev 0.2 P a g e 24 | 46
Visit Powerside.com for the latest manual
Harmonic Default value
for UTrip in % Harmonic
Default value
for UTrip in %
3 7 29 3.1
5 8 31 3.1
7 7 33 2.2
9 3.5 35 2.8
11 5.5 37 2.8
13 5 39 2.2
15 2.4 41 2.7
17 4 43 2.7
19 3.8 45 2.2
21 2.3 47 2.6
23 3.4 49 2.6
25 3.3 51 2.6
27 2.2
Table7.1: Default parameter values for harmonics monitoring
NOTE: When setting the UTrip and ULimit parameters on the HMI, it must be ensured that the UTrip parameter
values are always higher than the ULimit parameter values.
Automated reaction of the harmonic control to a resonance
If a resonance is detected, the System Identification Algorithm is automatically started if the phase correction is
set to “Automatic.” If this sequence exceeds the maximum permissible number of triggers the harmonic causing
the triggering is deactivated.
Automatic warning with the message, “Suspect.”
The resonance monitoring system includes the function of automatically disabling individual harmonics after
several error events. After a single resonance detection, a warning is first issued to the HMI by marking the
corresponding harmonics as “suspect” (yellow exclamation point) but compensation will not be disabled.
Automatic blocking with the message “Critical”
If a resonance event occurs several times in succession, the status of the harmonics is changed from “suspect”
to “critical” (red exclamation point) and compensation will be disabled.
The status “critical” is reset by deactivating the affected harmonics (status to “deactivated”) or by restarting the
system. The access level is visualized via a “padlock symbol” to the right of the harmonics on the screens. After
restarting the system, all harmonic control warnings and disabling actions are reset.
The “critical” status is reset via a mode change of the respective harmonics to “deactivated” and then resetting to
“to zero,” “Compensation,” or “ULimit.”
PowerAct Operations Manual Rev 0.2 P a g e 25 | 46
Visit Powerside.com for the latest manual
Manual blocking
When setting the parameters for harmonic compensation, the administrator can specify access rights, and
therefore disable access to setting the parameters of individual harmonics for the “user” user level. See figure
“Harmonics” and “Harmonics Expert.” When logged in as an administrator, harmonics disabled for the user are
displayed in red, and harmonics accessible to the user are highlighted in green.
7.6 DC voltage regulation—DC link
Configuration and operation:
DC voltage regulation can be operated in 4 control modes:
0: = Disable
1: = Constant value regulation
2: = Variable regulation with specification of a maximum limit value (This function is only available for the 3W
configuration).
3: = Manual desired value set by the user
The parameter can be set on the SD card or via fieldbus interface.
Control Mode 0: Disable
The DC link voltage is not regulated.
Control Mode 1: Constant value regulation of the DC link voltage.
Depending on the set grid rated voltage, the DC link voltage is calculated automatically in the system.
The system regulates the DC link voltage to the following nominal values without an adjustment regulator:
Grid rated voltage [V] DC rated voltage [V] maxdcvoltage_V value range
<440 800 600 V - 1350 V
[440 528] 950 950 V - 1350 V
>528 1300 1300 V - 1350 V
Table 7.2: DC link desired value dependent on the grid rated voltage
In this mode, the DC voltage can no longer be influenced via parameterization.
Control Mode 2: Dynamic DC link voltage adjustment
Variable regulation with specification of a maximum limit value (This function is only available for the 3W
configuration).
If the following requirements are met:
PowerAct Operations Manual Rev 0.2 P a g e 26 | 46
Visit Powerside.com for the latest manual
Reduction of losses
High compensation current in level and frequency
Operation at high peak grid voltage
The level of the DC link voltage can be adjusted variably.
Behavior: If the set UDC Max of the DC link voltage is reached, the system power is derated. Derating is signaled
via a message. There are no error messages or a shutdown.
In the event of incorrect parameterization of maxDcVoltageInVolt outside of the limits: 800 V - 1,350 V, a warning
message is issued on the HMI.
In the event of incorrect parameterization of maxDcVoltageInVolt within the limits: 800 V - 1,350 V, e.g.,
maxDcVoltageInVolt is below the rated-voltage dependent MinDC voltage, an automatic adjustment of the limit
value is carried out internally without a warning message being issued on the HMI.
• Control Mode 3: Desired value regulation
As the target variable, the desired value is specified in V on the SD card (or via the fieldbus interface).
Parameterization
The following parameters are located in the parameter sets and are used to set the DC link regulation:
generalSettings. autoFunction. dcVoltageControlMode
generalSettings. autoFunction. setpointInVolt
NOTE: When using a DC/DC actuator on the DC link, the DC voltage regulation function of the AC/DC converter
is also to be disabled.
8 Network configuration
Fieldbus configuration
(HMI) System > Interface > Network
The standard settings for the network are preset. The TCP/IP settings can be changed here.
(HMI) System > Interfaces > Serial (CCU)
The standard settings for the interfaces are already preset.
This is intended for internal communication.
If the RS485 parameters are changed on the CCU, the settings must also be configured on the touch screen to
ensure correct functioning. If the transmission paths are long or the electrical noise levels high on the
communication line between CCU and HMI, it is possible to achieve increased communication stability through
PowerAct Operations Manual Rev 0.2 P a g e 27 | 46
Visit Powerside.com for the latest manual
reconfiguration, e.g., by reducing the communication speed.
9 Information on complying with grid connection rules
FRT function
The FRT function is deactivated in the default parameter configuration, and switches to the error state if an
under- or overvoltage is present.
Monitoring and protection system
The system has an integrated monitoring and protection system. It contains both hardware and software
functions that continuously monitor the operating status and trigger alarms or warnings that, where necessary,
put the system in a safe stop state and that issue messages to the HMI. By combining the programmable internal
inputs or outputs, the user can implement remote monitoring. In the event of an alarm, the alarm output is
activated. The pending errors can be read off and acknowledged via the fieldbus or HMI.
Protection—External Monitoring
Physical variables such as voltages, currents and temperatures are monitored within the system. The limit values
are listed in the corresponding document. In addition, software monitoring functions are implemented, such as
watchdogs, runtime checks and communication checks.
Protection—System response to errors
The response of the system to the triggering of a protection function is divided into three cases:
1. Information for the user:
The device does not respond because the event is not safe relevant, rather is merely information for the
user. This includes information and warnings.
2. Derating:
A physical variable reaches the first limit value => the output power is reduced. A message is issued
simultaneously whenever the output power is reduced. Furthermore, the derating factor is displayed on the
home screen in place of the utilization.
Example: IGBT temperature too high => the system derates the output power, bringing the entire system to
a thermally uncritical and stable operating point.
3. Disconnection:
If derating was not successful, or if safety-relevant limit values have been violated, the device disconnects
immediately. A trip occurs and an error message is issued.
IPU Redundancy
If just one IPU is affected due to an error, only this unit disconnects if the redundancy mode is active. Otherwise
the entire system switches to the error state.
PowerAct Operations Manual Rev 0.2 P a g e 28 | 46
Visit Powerside.com for the latest manual
Protection Derating (reduced output)
The derating function protects the system against damage by reducing its output.
Variable (per IPU) Sampling period Behavior 3W
RMS AC current positive sequence system
(overcurrent of 1.4x the rated current permitted for
1 second)
100ms Integral 125A
RMS Fundamental (60 Hz) current positive
sequence system
100ms Integral 125A
RMS Fundamental (60 Hz) current negative
sequence system
100ms Integral 125A
RMS Fundamental (60 Hz) current zero sequence
system
100ms Integral NA
Peak current IGBT 12.5ms / 10,240Hz Integral/graduated 275 / 325A
Over temperature IGBT 1s Proportional—integral 80°C
Under temperature IGBT 1s State-dependent -
Over temperature of the choke on the grid side 1s Proportional—integral 145°C
Under temperature of the choke on the module
side
1s Proportional—integral 145°C
Over temperature air interior IGBT 1s Proportional—integral 69°C
Difference between DC voltages high-side
/ low-side
12.5ms/10,240Hz Integral/graduated 125 / 150V
Peak DC voltages 25ms / 10,240Hz Integral/graduated 700 / 725V
Modulation index 12.5 ms/10,240 Hz Integral/graduated 0.95/1.5
Table 9.1: Overview of derating limit values
In the case of fundamental frequency (50/60 Hz) processes, the system power is reduced directly by reducing
the current limit. The harmonics are reduced indirectly by reducing the measured load. The individual limit values
from which derating begins are hardware-dependent.
Protection—Disconnection/trip and Information
In the event of a violation of a system-critical parameter in the software or firmware, or in system-critical software
statuses, e.g., breakdown of communication to an IPU, a trip occurs:
• The system stops the function, the main contactor is opened
• The system switches to the error state. The error is displayed on the HMI and recorded in the error list.
• Errors and warnings are also transmitted via fieldbus
The error messages are displayed on the HMI in two ways:
PowerAct Operations Manual Rev 0.2 P a g e 29 | 46
Visit Powerside.com for the latest manual
1. Error code
2. Text message
The error code is issued as an 8-digit code on the HMI:
Meaning Main number Module ID Block Error number Type
Meaning 07 0 0 : 0 d 01
Table 9.2: Error coding
Main number Origin
0x20 IPU3L125
0x21 IPU4L70
0x30 MIO3VBE
0x10 MIO3V4C
0x11 MIO6C
0x90 Control ACF
0x91 Control SVC
0x06 COM
0x07 Anybus
0x08 Software HMI, all errors that occur on the
touch screen, Java application or other HMI
0x09 Software SHARC, errors on the SHARC
0x02 Software Blackfin, errors on the Blackfin that
are not handled under 0x08.
Table 9.3: Breakdown of the main error number
Block Description
0x00 NONE — no specific block available
0x01 AIX
0x02 MCU
0x04 EXT1
0x08 EXT2
Table 9.4: Breakdown of the block error number
Type Description
0x00 Error still exists (internal for Anybus)
PowerAct Operations Manual Rev 0.2 P a g e 30 | 46
Visit Powerside.com for the latest manual
0x01 Arrived
0x02 Gone (acknowledged by the user)
0x03 Gone (acknowledged by system)
0x04 Warning
0x08 Information
0x0c Debug message
Table 9.5: Breakdown of the type error number
Pre-heating function for IPUs with output derating to zero
In order to preheat the IGBTs at temperatures below the minimum value, an automated function is implemented
in such cases that first put the IGBTs into operation without current output (100% derating). This state is
maintained until the minimum temperature at the IGBTs is reached. A corresponding message is shown on the
display:
Protection—Error Handling
After the occurrence of an error event, an ERR.bin error record is written to the SD card and an entry is also
made in the ERROR.txt file on the SD card. In the case of fieldbus connection, the error ID is also specified.
Depending on how the auto functions have been configured; further handling is performed in the system:
1. No handling
Waiting for user action
2. Auto-restart
After the error state disappears, the error is automatically acknowledged, and the system restarts after a
defined time. The number of permitted auto-restarts can be set in the file Settings.txt, see below
3. Auto-configuration.
The resonance handling activates a function which, after error triggering, performs a reconfiguration of the
phase angles of the harmonic compensation via SIA.
4. Disabling
Ultimately, a function can also be disabled
Protection—Manual acknowledgment of alarm messages
Pending alarms are displayed on the HMI (header, center). They can be called up and acknowledged by tapping
this area.
If the cause of the alarm remains after acknowledgment, a new alarm is triggered. All alarms must be
acknowledged before operation is possible again. Via fieldbus, acknowledgment is performed via the
Acknowledge bit (only rising edges are evaluated).
NOTE: It is strongly recommended that the causes of the error are identified before they are acknowledged in
PowerAct Operations Manual Rev 0.2 P a g e 31 | 46
Visit Powerside.com for the latest manual
order to avoid damage in the system or the surrounding installation.
Protection—Access rights
The operating concept grants the following access rights:
Protection level Access right
1. Firmware Development (Internal), Technology Partners
2. Software Development (internal)
3. SD card Development (internal), experts (Service, OEM)
4. HMI administrator/Service Experts (Service, OEM), trained specialists (external)
5. HMI user Operators (e.g., electricians without specific knowledge)
6. HMI no login No access rights, display only
Table 9.6: Access hierarchy
Protection—HMI
Access to the system is protected by a three-stage access level:
User level Rights and obligations
Administrator (Service) • Can view settings and measured values. • Can also configure settings that • may impair the safety/function of the system. • Can access the file system on the SD card
remotely via Java applet.
User • Can view settings and measured values. • Can configure settings that are not • reserved for Service.
Display • Can only view settings and measured values.
• Cannot configure any additional settings.
Table 9.7: User level and assigned rights
The security settings are saved on the SD card under “/CONFIGS/Security.txt.” If this file is deleted, the PIN will
be reset to 0000 (or 4321 for Service). Furthermore, the control check is disabled, i.e., anyone can change
settings immediately. The PIN entry for users is red, the PIN entry for administrators (Service) is blue:
PowerAct Operations Manual Rev 0.2 P a g e 32 | 46
Visit Powerside.com for the latest manual
Figure 9.8: Administrator login mask
Figure 9.9: User login mask
PowerAct Operations Manual Rev 0.2 P a g e 33 | 46
Visit Powerside.com for the latest manual
APPENDIX A: Fieldbus States and Commands
The following states are issued via the fieldbus interface:
State name Number Description
STATE_OFFLINE 0 //no communication
STATE_INIT 1 //Initialization/Booting in progress
STATE_IDLE 2 //System waiting for Instructions, main contactor open, IGBTs not
working
STATE_GO_IDLE 4 //System changing to STATE_IDLE
STATE_ERROR 8 //System in error state
STATE_PAUSE 9 //System pause, MAIN contactor closed, IGBTs are switching
STATE_SYNC_TO_V 10 //System is synchronized to grid
STATE_BLACKSTART 11 //System is black starting
STATE_COMPENSATOR 12 //System is in grid parallel mode
STATE_ISLANDING 13 //System in island mode
STATE_SIA 14 //System is analyzing grid
STATE_FRT 15 //Fault Ride Through
Control mode meaning/SD card
parameters Active power (P-
Control)
Description Data
type
Unit Min Max Default PackedID ParamID
ActivePowerControl
::
General::MODE_I
0: = DISABLE, 1: =
ACTIVE_POWER_ CONTROL,
2:= ACTIVE_POWER_LIMITER
Float No unit 0 2 0 2 0
Reactive power (Q-Control) Description Data type Unit Min Max Default PackedID ParamID
ReactivePowerControl::
General::MODE_I
0: = DISABLE, 1: =
REACTIVE_POWER_
CONTROL, 2: =
POWER_FACTOR_
CORRECTION, 3: =
VOLTAGE_CONTROL
Float No unit 0 3 0 3 0
Current balancing Description Data
type
Unit Min Max Default PackedID ParamID
PowerAct Operations Manual Rev 0.2 P a g e 34 | 46
Visit Powerside.com for the latest manual
LoadBalancingControl:: MODE_I 0: = DISABLE, 1: =
Delta balancing, 2: = Star balancing
Float No unit 0 3 0 4 0
Harmonic compensation
(harmonics)
Description Data
type
Unit Min Max Default PackedID ParamID
HarmonicControlGeneral::
MODE_I
0: = DISABLE, 1: = DELTA, 2: =
STAR, 3: = DELTA_STAR
Float No unit 0 3 0 6 0
SD card parameters–Charge Rate
- Regulation basic settings
Description Data type Unit Min Max Default PackedID ParamID
For the regulation of the individual functions, a time constant can be set. This enables project-specific interactions with other systems combined with dynamic
requirements to be taken into account. The change rate of the reference values is another setting option. This means that in the event of a reference value jump,
the slew rate is limited internally. A value of zero deactivates the limitation.
HarmonicControlGener al::
BANDWIDTH_F
Time constant tau Float sec 1.00 100,00
0
100 6 2
HarmonicControlGener al::
PRIO_I
0: = IMPORTANT,
3: = UNIMPORTANT
Int No unit 0.00 3.00 0.00 6 1
HarmonicControlGener al::
MODE_I
0: = DISABLE, 1: = DELTA, 2: =
STAR, 3: = DELTA_STAR
Int No unit 0.00 3.00 0.00 6 0
LoadBalancingControl::
CHANGE_RATE_F
Change rate in the event of
desired value change
Float pu/s 0.00 10.00 0.00 4 3
LoadBalancingControl::
TIME_CONSTANT_F
Time constant tau Float sec 0.00 1.00 0.10 4 2
LoadBalancingControl:: PRIO_I 0: = IMPORTANT, 3:
= UNIMPORTANT
Int No unit 0.00 3.00 0.00 4 1
LoadBalancingControl:: MODE_I 0: = DISABLE, 1: = Delta
balancing, 2: =
Balancing
Int No unit 0.00 3.00 0.00 4 0
ReactivePowerControl::
General::
Change rate in the event of
desired value change
Float pu/s 0.00 10.00 0.00 3 3
CHANGE_RATE_F
ReactivePowerControl:: General:: TIME_CONSTANT_F
Time constant tau Float sec 0.00 1.00 0.10 3 2
PowerAct Operations Manual Rev 0.2 P a g e 35 | 46
Visit Powerside.com for the latest manual
ReactivePowerControl:: General::
PRIO_I
0: = IMPORTANT, 3:
= UNIMPORTANT
Int No unit 0.00 3.00 0.00 3 1
ReactivePowerControl:: General::
MODE_I
0: = DISABLE, 1: =
REACTIVE_POWER_CONTRO L,
2: =
POWER_FACTOR_CORRECTI
ON, 3: =
VOLTAGE_CONTROL
Int No unit 0.00 3.00 0.00 3 0
ActivePowerControl:: General::
TIME_CONSTANT_F
Time constant tau Float sec 0.00 1.00 0.10 2 2
ActivePowerControl:: General::
CHANGE_RATE_F
Change rate in the event of
desired value change
Float pu/s 0.00 10.00 0.00 2 3
ActivePowerControl: General::
PRIO_I
0: = IMPORTANT, 3:
= UNIMPORTANT
Int No unit 0.00 3.00 0.00 2 1
ActivePowerControl:: General::
MODE_I
0: = DISABLE, 1: =
ACTIVE_POWER_CONTROL,
2:= ACTIVE_POWER_LIMITER
Int No unit 0.00 2.00 0.00 2 0
SD card parameters—Plimit active
power function
Description Data type Unit Min Max Default PackedID ParamI D
ActivePowerControl::
ActivePowerLimiter:
:LIMIT_TWO_F
Active power limit value of the
Plimit function
Float pu - 1.00 1.00 0.00 2 22
ActivePowerControl::
ActivePowerLimiter::
LIMIT_ONE_F
Active power limit value of the
Plimit function
Float pu - 1.00 1.00 0.00 2 21
ActivePowerControl::
ActivePowerControl::
SETPOINT_F
Desired value specification of
the active power control
Float pu - 1.00 1.00 0.00 2 8
ActivePowerControl::
General::
TIME_CONSTANT_ F
Time constant tau Float sec 0.00 1.00 0.10 2 2
ActivePowerControl::
General::CHANGE_RATE_F
Change rate in the event of
desired value change
Float pu/s 0.00 10 0.00 2 3
ActivePowerControl::
General::PRIO_I
0: = IMPORTANT, 3: =
UNIMPORTANT
Float No unit 0.00 3.00 0.00 2 1
ActivePowerControl::
General::MODE_I
0: = DISABLE, 1: =
ACTIVE_POWER_CONTR OL,
2:= ACTIVE_POWER_LIMITER
Float No unit 0.00 2.00 0.00 2 0
PowerAct Operations Manual Rev 0.2 P a g e 36 | 46
Visit Powerside.com for the latest manual
Active power characteristic
curves—Parameters
Meaning HMI Fieldbus SD card
(Parameter set x)
Min …
Max
Default
Pref Active power reference value at nominal
conditions
pu [Snominal]
Yes Yes pControl. pRef.
setPoint
-1 ..1 0
P(f) droop main
(lower, upper)
Active power droop depending on the
grid frequency below and above the
dead band
pu [Snominal/fnominal]
No Yes No - 0
P(f) dead band
(lower, upper)
Lower and upper end of the dead
band
pu [base: Snominal]
No Yes No - 0
P(f) max_charge Maximum charging power resulting
from a grid frequency deviation
pu [base: Snominal]
No Yes No
P(f)
max_discharge
Maximum discharging power resulting
from a grid frequency deviation
pu [base: Snominal]
No Yes No
P(U) droop
(lower, upper)
Active power droop depending on the
line voltage below and above the dead
band pu [base: Snominal/Unominal]
No Yes No - 0
P(U) dead band
(lower, upper)
Lower and upper end of the dead
band
pu [
base: Snominal]
No Yes No - 0
P(U) max_charge Maximum charging power resulting
from a line voltage deviation
pu [base: Snominal]
No Yes No - 0
P(U)
max_discharge
Maximum discharging power resulting
from a line voltage deviation
pu [base: Snominal]
No Yes No - 0
Power Factor Correction—
Parameters
File Description Access
via HMI
Access via
fieldbus
Data
type
Unit Min Max Default Packed
ID
fieldbus
Param ID
fieldbus
ReactivePowerControl::
PowerFactorCorrection :: DROOP_F
Parameter
set
Configurable control
deviation when using
independent parallel
regulation units
Yes Yes Float No unit - 10 10 0 3 22
PowerAct Operations Manual Rev 0.2 P a g e 37 | 46
Visit Powerside.com for the latest manual
ReactivePowerControl::
PowerFactorCorrection :: POWER_FACTOR_T
WO_F
Parameter
set
Limit value two for
cos (phi) regulation
Yes Yes Float No unit -1 1 1 3 21
ReactivePowerControl::
PowerFactorCorrection :: POWER_FACTOR_O
NE_F
Parameter
set
Limit value one for
cos (phi) regulation
Yes Yes Float No unit -1 1 1 3 20
Voltage regulation Vref—
Parameters Meaning Type Unit Min Max Default PackedID ParamID
ReactivePowerControl::
VoltageControl::
DROOP_TWO_F
Voltage regulation U/I droop Float pu 0.10 10.00 1.00 3 26
ReactivePowerControl::
VoltageControl::
DROOP_ONE_F
Voltage regulation U/I droop Float pu 0.10 10.00 1.00 3 25
ReactivePowerControl::
VoltageControl::
SETPOINT_TWO_F
Voltage regulation dead band
point 2 Float pu 0.90 1.10 1.00 3 24
ReactivePowerControl::
VoltageControl::
SETPOINT_ONE_F
Voltage regulation dead band
point 1 Float pu 0.90 1.10 1.00 3 23
Load balancing—Parameters Description Data type Unit Min Max Default PackedID ParamID
LoadBalancingControl::
COMPENSATION_LEVEL_STAR_F
Compensation level, star
balancing Float % 0.00 100 100 4 7
LoadBalancingControl::
COMPENSATION_LEVEL_DELTA_
F
Compensation level, delta
balancing Float % 0.00 100 100 4 6
LoadBalancingControl::
CHANGE_RATE_F
Change rate in the event of
desired value change Float pu/s 0.00 10 0.00 4 3
LoadBalancingControl::
TIME_CONSTANT_F Time constant tau Float sec 0.00 1 0.10 4 2
LoadBalancingControl::PRIO_I
0: =
IMPORTANT, 3: = UNIMPORTANT
Float No unit 0.00 3 0.00 4 1
LoadBalancingControl::
MODE_I
0: = DISABLE
1: = Delta balancing
(negative sequence
system) 2: = Star
balancing (zero sequence
system)
3: = Star and delta balancing
Float No unit 0.00 3 0.00 4 0
PowerAct Operations Manual Rev 0.2 P a g e 38 | 46
Visit Powerside.com for the latest manual
Harmonic compensation—
Parameters
Description Data type Unit Min Max Default Packet ID Param ID
SelectiveHarmonicControl
<harmonic order>.
MODE_I
0: = DISABLE_CONTROL
1: = TO_ZERO_CONTROL (comp. of
the inherent distortion)
2: =
CURRENT_COMPENSATION_CONT
ROL (compensation current at the MIO
measurement point)
3: =
VOLTAGE_COMPENSATION_CONT
ROL (compensation voltage at the MIO
measurement point)
4: =
CURRENT_COMPENSATION_VOLTAG
E_L
IMIT_CONTROL (mode 2 with U
limit) 5: =
VOLTAGE_COMPENSATION_V
OLTAGE_LIMIT_CONTROL
(mode 3 with U limit)
Int No
unit
0.0
0
5.0
0
0.00 24 0
SelectiveHarmonicControl
<harmonic order>.
access
Access restriction for the HMI Flo at No
unit
0.0
0
1.0
0
1.00
SelectiveHarmonicControl
<harmonic order>.
MANUAL_PHASE_CORRE
C TION_F
Manually configurable correction angle Flo at Degrees - 36
1
36
1
0.00 24 5
SelectiveHarmonicControl
<harmonic order>.
VOLTAGE_BLOCK_LIMIT_F
Individual switch-off threshold
of the controller
Flo at % 0.0 0
10 0
0.00 24 4
SelectiveHarmonicControl
<harmonic order>.
COMPENSATION_LEVEL_F
Compensation level for modes 2
and 3 0% => no compensation
100% => full compensation
Flo at % 0.0
0
10
0
100 24 1
SelectiveHarmonicControl
<harmonic order>.
CURRENT_COMPENSATI
O N_LIMIT_F
Placeholder for future function Flo at 24 2
SelectiveHarmonicControl
<harmonic order>.
VOLTAGE_COMPENSATI
O N_LIMIT_F
Limit value of the voltage distortion for
modes 4 and 5 (U limit)
Floa t % 0.0
0
10
0
100 24 3
PowerAct Operations Manual Rev 0.2 P a g e 39 | 46
Visit Powerside.com for the latest manual
SIA parameters Meaning Unit HMI Fieldbu
s
SD card
file
SD card
(name)
Min … Max Default
maxActorCurrent The parameter iMax specifies the
maximum current amplitude of
the generator signal in pu
(measured at the system rated
current).
pu No No INITCTR L.txt
frequencyResp
onse.
maxActorCurre nt
0.1 - 1 0.1
maxLineVoltage The parameter vMax specifies
the maximum permissible voltage
distortion as a percentage based
on the rated voltage while the
SIA algorithm is being executed.
If the voltage is distorted up to
the configured value by the
generator signal, the current
amplitude will no longer be
increased.
% No No INITCTR
L.txt
frequencyResp
onse.
maxLineVoltag e
0-0.05 0.01
actorCurrentAmplitudeCor
rection
<harmonic order>
Current amplitude response
determined by the SIA at the
connection point of the system
% Displa
y only
? FREQRE
SP
.txt
actorCurrentA
mplitudeCorrec
tion
1 e-6 -
1e6
actorCurrentPhaseCorrec
tion
<harmonic order>
Current phase response
determined by the SIA at the
connection point of the system
° Displa
y only
? FREQRE
SP
.txt
actorCurrentPh
aseCorrection
-361
to +361
lineCurrentAmplitudeCorr
ection
<harmonic order>
Current amplitude response
determined by the SIA at the MIO
measurement point
% Displa
y only
? FREQRE
SP
.txt
lineCurrentAmp
litudeCorrection
1 e-6 - 1e6
lineCurrentPhaseCorrectio
n
<harmonic order>
Current phase response
determined by the SIA at the MIO
measurement point
° Displa
y only
FREQRE
SP
.txt
lineCurrentPha
seCorrection
-361
to
+361
lineVoltageAmplitudeCorr
ection
<harmonic order>
Voltage phase response
determined by the SIA at the MIO
measurement point
% Displa
y only
FREQRE
SP
.txt
lineVoltageAmp
litudeCorrection
1 e-6 -
1e6
lineVoltagePhaseCorrectio
n
<harmonic order>
Voltage phase response
determined by the SIA at the MIO
measurement point
° Displa
y only
FREQRE
SP
.txt
lineVoltagePhase
Correction
-361
to
+361
Resonance
monitoring SD card
parameters
Meaning Unit HMI Fieldbus SD card
file
SD card (name) Min … Max
Default
VOLTAGE_BLOCK_LIMIT_F
Maximum permissible limit value of the respective harmonic if it is being compensated by the systems
% Yes No Parametersatz.txt
SelectiveHarmonic Control3. VOLTAGE_BLOCK_ LIMIT_F
0- 100
PowerAct Operations Manual Rev 0.2 P a g e 40 | 46
Visit Powerside.com for the latest manual
Reaction to resonance—
parameters
File Description Access via
HMI
Access
via
fieldbus
Data
type
Unit Min Max Def PackID ParaI
D
statemachine.
triggerSiaAfterBoot
Settings.
txt
True: System determines
the phase angle for
harmonics compensation
itself directly upon the first
goToRun.
No No Float No
unit
0.0
0
1.00 0.0
0
-2 -2
HarmonicStatemachine::
MIN_TIME_GAB_FOR_
SIA_
TRIGGER_I
Paramet
er set
Minimum time between two
SIA processes
No Yes Flea
t
sec 0.0
0
3600 30 1 11
HarmonicStatemachine::
MAX_NMB_SIA_TRIGG
ER_
TIME_INTERVALL_I
Paramet
er set
Time interval during which the
MAX_NMB_SIA_TRIGG
ER_I is permissible
No Yes Flea t
sec 0.0 0
3600 600 1 10
HarmonicStatemachine::
MAX_NMB_SIA_TRIGG
ER_I
Paramet
er set
Maximum permissible
number of SIA processes
within the defined time
interval
No Yes Flea
t
ST 0.0
0
20.0
0
5.0
0
1 9
HarmonicControlGeneral ::
AUTOPHASE_CORRECT
ION
_ ENABLED_I
Paramet
er set
Mode of the SIA: Auto or
Manual
No Yes Flea t
No
unit
0.0 0
1.00 0.0 0
6 3
netzkonfiguration.
teleControlFrequency
Settings.
txt
Ripple control frequency Yes No Float F 0.0
0
10 k 0 -2 -2
DC link DC voltage
regulation—parameters
Meaning Unit HMI Fieldbus SD card
(Parameter set
x)
SD card (name) Min… Max Default
Control Modus 0 := Disable
1 := Constant 2 := Variable 3 := Setpoint
No unit No Yes Parameter
set
ACDCConverterControl:: Group::
DC_VOLTAGE_CONTROL_MODE_I
0-4 1
Setpoint Desired
value can be
set by the
user
Volts No Yes Parameter
set
ACDCConverterControl::
Converter1::
DC_VOLTAGE_SET_POINT_F
800 V
PowerAct Operations Manual Rev 0.2 P a g e 41 | 46
Visit Powerside.com for the latest manual
Max DC Wert im
Modus Variable
Maximum DC
link voltage in
the “Variable”
mode
Volts No No InitCtrl.txt ipuControl. dcLinkControl.
levelControl. maxDcVoltageInVolt
800 V - 1,350 V
1,300 V
MIO configuration – SD
card parameters
Meaning HMI Fieldbus SD card (DSCPORTx) Min …
Max
Default
MIO n, Stromwandler N,
primär
Primary transformer ratio
current measurement N at MIO
n
Yes No mion. measurement.
stromwandlerN. primaer
1..1000 0
MIO n, Stromwandler N,
sekundär
Secondary transformer ratio
current measurement N
at MIO n
Yes No mion. measurement.
stromwandlerN. sekundaer
1/ 5 1
Gain Korrektur MIO n, current transformer gain
correction factor for input
No No mion. measurement.
stromwandlerN. gainxA
- 1000 - 1000
1
Offse Korrektur MIO n, current transformer
correction offset for current input
No No mion. measurement.
stromwandlerN. offsetxA
-1000 A - 1000A
0A
MIO n, Spannungswandler N,
primär
Primary transformer ratio
current measurement N at MIO
n
Yes No mion.
measurement.
SpannungswandlerN.
primaer
-100MV - 100MV
1000V
MIO n, Spannungswandler N,
sekundär
Secondary transformer ratio
voltage measurement N
at MIO n 0 -> 100 V/1 -> 1000 V
Yes No mion.
measurement.
SpannungswandlerN.
sekundaer
0 - 1 1
MIO n,
Spannungswandler
Gain Korrekturfaktor für
Volt Eingang
MIO n, current transformer gain correction factor for input
Yes No mion.
measurement.
SpannungswandlerN.
gainxV
-1000—
1000
1
MIO n,
Spannungswandler N
Korrektur-Offset für x
VoltEingang
MIO n, current transformer
correction offset for input
No No mion.
measurement.
SpannungswandlerN.
offsetxV
-1000 V
- 1000 V
0
MIO n,
Spannungswandler N
Phasenkorrektur für x
Volt und y Ampere
Phase correction current for
voltage transformer
No No mion.
measurement.
SpannungswandlerN.
phaseMeasurementErrorxVyA
-10 s -
10 s
0
PowerAct Operations Manual Rev 0.2 P a g e 42 | 46
Visit Powerside.com for the latest manual
Eingang
Steuerspannungs-
überwachung
0 Deactivated
1 Activated
No No mion.
measurement.
voltagecontrol
0-1 0
Temperaturmessung
(ext.)
0 Deactivated
1 Activated for KTY81 2
Activated for KTY85 3
Activated for PT100 4
Activated for PT1000
No No mion.
measurement.
temperature
0 - 4 0
Temperaturmessung
(ext)
Grenzen
No No mion. measurement.
extTempMin/Max
-100 °C - +250 °C
- 100
Aktion für
Digitaleingang N an
MIO n
0 Acknowledged 1 Start 2 Pause
3 Stop 4 Start/Stop 5 Start/Pause
6 Measurement switch 1 7 Measurement switch 2 8 to 15
Parameter set: 1 to 8 16 LCU pressure sensor 17
System release
Yes No mion. digital.
inputN. action
0-16 0
Triggerbedingung für
Digitaleingang N an MIO
n
0 Deactivated 1 Normal 2 Inverted
Yes No mion.
digital.
inputN.trigger
0-2 0
Aktion für 0 Deactivated Yes No mion. 0-16 0 Digitalausgang N an 1 Run digital.
MIO n 2 Pause outputN.
3 Error action
4 Warning
5 Derating
6 Mode PFC
7 Mode Qref
8 Mode Vref
9 FRT
10 OVRT
11 LVRT
12 MIO internal temp.
13 MIO ext temp.
14 Cooling
15 LCU pump control
16 LCU heating
Triggerbedingung für 0 Deactivated mion.
PowerAct Operations Manual Rev 0.2 P a g e 43 | 46
Visit Powerside.com for the latest manual
Digitalausgang N an 1 N/O contact digital. MIO n 2 N/C contact outputN.
trigger
SD card parameters—fieldbus. The
fieldbus interface is configured via the SD
card in the “Anybus.txt” file.
Description Access
via HMI
Access
via
fieldbus
Data
type
Unit Min Max Default
general. anybusenabled Activation of the fieldbus
communication; 0: = fieldbus
deactivated, 1:
= fieldbus activated
No No Int No unit 0 1 0
general. monitorConnectionState Fieldbus monitoring. If an
error is detected, the system
switches to STOP mode
No No Int No unit 0 1 1
general. monitorLifebit Monitoring of the fieldbus device
life bit. If the life bit is not
available, the system switches to
the STOP mode
No No Int No unit 0 1 0
profibus.dpv1. nodeid Definition of the node point of the
communication (address of the
fieldbus device in the Profibus
network)
No No Int No unit 0 125 10
modbus.rtu. nodeid Definition of the node point of the
communication (address of the
fieldbus device in the Modbus
network)
No No Int No unit 0 247 10
modbus.rtu. parity Use of a parity bit in the
communication protocol
No No Int No unit 0 3 0
modbus.rtu. baudrate Configuration of the
communication baud rate
No No Int No unit 0 8 4
modbus.rtu. rtuascii Selection between 8-bit RTU
(=0) and
7-bit ASCII (=1)
No No Int No unit 0 1 0
PowerAct Operations Manual Rev 0.2 P a g e 44 | 46
Visit Powerside.com for the latest manual
modbus.rtu. processtimeout Timeout in seconds, how long
after the last packet the
connection is to be considered
as still active.
No No Int Millisec
onds
0 1,00
0,00
0
10,000
modbus.tcp. ipaddress IP address of the fieldbus
device in the Modbus/TCP
network
No No Int No unit 10.0.0.3
modbus.tcp. subnetmask Subnet mask, specifies at
which bit position within the IP
address is to be used for
addressing the network or host
portion
No No Int No unit 255.255.
0.0
modbus.tcp. gateway Address of a gateway No No Int No unit 0.0.0.0
modbus.tcp. dhcpon Automatic IP address
assignment; on: = 1, off: = 0
No No Int No unit 1 0 1
modbus.tcp. duplexmode Duplex mode on: = 1/off : = 0 No No Int No unit 0 0 4
modbus.tcp. timeout TCP protocol timeout of the
internal connection
No No Int Second
s
0 1,000
,000
60
modbus.tcp. processtimeout Timeout in seconds, how long
after the last packet the
connection is to be considered
as still active.
No No Int Millisec
onds
0 1,000
,000
10,000
Error log entry configuration
Logger and Auto-restart parameters:
Meaning HMI Fieldbus SD card (Parameter set x) Min … Max
Default
Loggeraktivierung 1 Activated
0 Deactivated
No No system. logger. enabled - 0.1
Loggerauslösungsverzögerung [sec] No No system. logger. afterTrigger - 0.2
Loggerauflösung Time scaling: 1 = 10,240 Hz
No No system. logger. prescaler - 1
Derating Warnung True or false No No system. warning. derating - True
PowerAct Operations Manual Rev 0.2 P a g e 45 | 46
Visit Powerside.com for the latest manual
max_count_of_restarts Number of permitted
automatic restarts in a
fixed time period of
10 min.
No No netzkonfiguration.
max_count_of_resta
rts=0
0-7 0
DC/ DC actuator—regulation parameters Meaning HMI Fieldbus SD card
Settings.txt
Min …
Max
Default
netzkonfiguration. IPUredundancy [0 = disabled; 1 = enabled] No No Yes 0..1 0
PowerAct Operations Manual Rev 0.2 P a g e 46 | 46
Visit Powerside.com for the latest manual
Powerside 7850 TransCanada Hwy 980 Atlantic Ave. Saint-Laurent, Quebec Alameda, CA 514-333-8393 510-522-4400 www.powerside.com