poweract active filter

46
PowerAct Operations Manual Rev 0.2 Page 1 | 46 Visit Powerside.com for the latest manual PowerAct Active Filter Operations Manual The information contained in this document is subject to change without notice. POWERSIDE MAKES NO WARRANTY OF ANY KIND WITH REGARD TO THIS MATERIAL, INCLUDING, BUT NOT LIMITED TO, THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR USE. Powerside shall not be liable for errors contained herein or for incidental or consequential damages in connection with the furnishing, performance, or use of this material. If you do not accept this limitation on liability, please return the product to Powerside prior to use. If you find information in this manual that is incorrect, misleading, or incomplete, we would appreciate your comments and suggestions. Powerside 7850 TransCanada Hwy 980 Atlantic Ave. Saint-Laurent, Quebec Alameda, CA 514-333-8393 510-522-4400 www.powerside.com

Upload: others

Post on 23-May-2022

10 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: PowerAct Active Filter

PowerAct Operations Manual Rev 0.2 P a g e 1 | 46

Visit Powerside.com for the latest manual

PowerAct Active Filter

Operations Manual

The information contained in this document is subject to change without notice. POWERSIDE MAKES NO WARRANTY OF ANY KIND WITH REGARD TO THIS MATERIAL, INCLUDING, BUT NOT LIMITED TO, THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR USE. Powerside shall not be liable for errors contained herein or for incidental or consequential damages in connection with the furnishing, performance, or use of this material. If you do not accept this limitation on liability, please return the product to Powerside prior to use. If you find information in this manual that is incorrect, misleading, or incomplete, we would appreciate your comments and suggestions.

Powerside 7850 TransCanada Hwy 980 Atlantic Ave. Saint-Laurent, Quebec Alameda, CA 514-333-8393 510-522-4400 www.powerside.com

Page 2: PowerAct Active Filter

PowerAct Operations Manual Rev 0.2 P a g e 2 | 46

Visit Powerside.com for the latest manual

Product Identification and Version

The product identification plate is in the cabinet door. Prior to installation and commissioning

verify the system configuration with site conditions.

The following product configuration are and covered by this operations manual:

PowerAct Active Filter

PowerAct: 3W, 480V or 600V/up to 4 x125 A modules

Vac Amps NEMA 3R NEMA 1/12

Customer P/N Engineering P/N Customer P/N Engineering P/N

480 125 PF5R025PL-3R PSAF-01255.1/0 B3R-

0 PSAF0125.5-01

PSAF-01255.1/0 B01-0

480 250 PF5R040PL-3R PSAF-02505.2/0 B3R-

0 PSAF0250.5-01

PSAF-02505.2/0 B01-0

480 375 PF5R050PL-3R PSAF-03755.3/0 B3R-

0 PSAF0375.5-01

PSAF-03755.3/0 B01-0

480 500 PF5R060PL-3R PSAF-05005.4/0 B3R-

0 PSAF0500.5-01

PSAF-05005.4/0 B01-0

600 125 PSAF0125.7-3R PSAF-01257.1/0 B3R-

0 PSAF0125.7-01

PSAF-01257.1/0 B01-0

600 250 PSAF0250.7-3R PSAF-02507.2/0 B3R-

0 PSAF0250.7-01

PSAF-02507.2/0 B01-0

600 375 PSAF0375.7-3R PSAF-03757.3/0 B3R-

0 PSAF0375.7-01

PSAF-03757.3/0 B01-0

600 500 PSAF0500.7-3R PSAF-05007.4/0 B3R-

0 PSAF0500.7-01

PSAF-05007.4/0 B01-0

Page 3: PowerAct Active Filter

PowerAct Operations Manual Rev 0.2 P a g e 3 | 46

Visit Powerside.com for the latest manual

Table of Contents

Contents

1 Information on this document .............................................................................................................................. 4

2 Safety Warnings & Instructions ........................................................................................................................... 5

3 Function description ............................................................................................................................................. 7

4 User Interfaces .................................................................................................................................................... 10

5 Operating the PowerAct Active Filter ................................................................................................................ 13

6 Commissioning and system start-up ................................................................................................................. 15

7 Display and Control Screen—Touch Panel (HMI) ........................................................................................... 16

7.1 Control modes ..................................................................................................................................................... 17

7.2 Reactive power Settings ..................................................................................................................................... 18

7.3 Load Balancing .................................................................................................................................................... 20

7.4 Harmonic compensation ..................................................................................................................................... 21

7.5 System Identification Algorithm (SIA) Harmonic Correction ........................................................................... 21

7.6 DC voltage regulation—DC link ......................................................................................................................... 25

8 Network configuration ........................................................................................................................................ 26

9 Information on complying with grid connection rules ..................................................................................... 27

APPENDIX A: Fieldbus States & Commands ............................................................................................................ 33

Page 4: PowerAct Active Filter

PowerAct Operations Manual Rev 0.2 P a g e 4 | 46

Visit Powerside.com for the latest manual

1 Information on this document

Information on this document

The text can include abbreviations. The first usage will be written out in full and the abbreviation will follow in

parentheses.

Terminology Abbreviation

Active filter ACF

IGBT Power Unit IPU

Measurement Unit MIO

Control Computer Unit CCU

Web User Interface WUI

Human Machine Interface (touch panel) (HMI)

System Identification Algorithm—grid analysis SIA

Per Unit—these are unitless dimensions, based on the system rated

value. Example: 1.1 pu voltage means grid rated voltage x 1.1.

pu

Scope of manual

This manual describes the user interface and the operating modes of the PowerAct Active Filter series.

The user manual describes how to use the installed software, such as for operation, basic configuration and

commissioning.

Page 5: PowerAct Active Filter

PowerAct Operations Manual Rev 0.2 P a g e 5 | 46

Visit Powerside.com for the latest manual

2 Safety Warnings and Instructions

IMPORTANT SAFETY INSTRUCTIONS

SAVE THESE INSTRUCTIONS

Please read the operating instructions prior to installation. The operating instructions explain how to operate

the product safely. The notes listed below warn of possible sources of danger and provide information on the

correct use of the active filter.

Priority must be given to the respectively applicable, recognized regulations of the technology, as well as the

accident prevention regulations and, if applicable, internal regulations in the most up-to-date version.

The system contains LETHAL VOLTAGES. All repairs and service should be performed by

AUTHORIZED PERSONNEL ONLY.

Death, serious injury, or fire hazard could result from improper connection or operation of this instrument.

Read and understand this manual before connecting the device.

This equipment may present an arc flash hazard. Personal Protection Equipment may be required. Refer

to NFPA70E for sections related to Standard for Electrical Safety in the Workplace.

This system contains energy storage devices (capacitors) that may present a shock hazard even with

primary power disconnected

Ensure that the current transformer’s secondary circuit is short-circuited (CT shorting block provided by

others) prior to working on current transformer circuits. Under no circumstances should the secondary

circuit of the CTs be operated in the open state as lethal voltages may be present.

The voltage of the DC link may be above 1000 V. Allow 60 minutes discharging time before work. Verify

voltage levels using appropriate instrument.

All local applicable standards and specifications, in addition to the generally recognized codes of practice,

must be observed.

If configured for remote communications an unintended/remote start may occur if input power is available.

Remove power if personal safety makes it essential to prevent an unintentional start.

All people who are involved in the setting up, commissioning, operation, maintenance or repair of the

device must be adequately professionally qualified and must read, and following, operating instructions

provided. If you are unsure TAKE NO ACTION without contacting qualified personnel.

DANGER

WARNING

Page 6: PowerAct Active Filter

PowerAct Operations Manual Rev 0.2 P a g e 6 | 46

Visit Powerside.com for the latest manual

Do not install or operation this system close to a gas or electric heat source

The operating environment should be maintained within the parameters stated in this manual

Keep surrounding uncluttered, clean, and free from excessive moisture and particulates. The device may only be used in accordance with its intended use. Unauthorized and improperly performed

work on the device and tampering with system-internal protection functions are prohibited!

Any persons who configure settings on the device, commission it or change its settings at a later date must

be sufficiently qualified, meaning that they have successfully completed a product-specific training

program.

NOTICE: These operating instructions have been created with great care; however, Powerside cannot

assume any liability for the freedom from errors of the operating instructions or for damage resulting from

the use of the manual. We will strive to fix any errors that we become aware of as quickly as possible.

Please refer to the Powerside web site for the latest version of this manual.

The PowerAct Active Filter is an electronic grid filter. Its role is to feed fundamental (50/60 Hz) and

harmonic currents to improve the voltage quality in electrical AC voltage grids.

It must only be possible for authorized persons to come into contact with, to access and to intervene in the

PowerAct Active Filter—i.e., the cabinet door is to be kept closed and locked. The key to the room/cabinet

may only be available to authorized persons.

The devices may only be operated with the cabinet doors closed.

The devices may only be operated if they have been installed correctly (see PowerAct Installation Manual).

Correct installation includes both the attachment and state of the cabinet, as well as the electrical

connection and electrical protection.

The PowerAct Active Filter may only be used for the function described in this document.

Interventions in the hardware and software are not permitted.

The PowerAct Active Filter is designed for the environmental conditions described in the installation

manual and may only be operated under these conditions.

CAUTION

INTENDED USE

Page 7: PowerAct Active Filter

PowerAct Operations Manual Rev 0.2 P a g e 7 | 46

Visit Powerside.com for the latest manual

3 Function description

This section provides an overview of the compensation settings of the PowerAct Active Filter. These settings can

be changed via the touch panel (HMI) or the Web User Interface (WUI). Details on this are provided in a later

section. Please refer to the Overview section in the PowerAct Installation Manual for an overview of the operating

principle.

Before the system can be used, it must be commissioned. This includes setting up the basic and operating

parameters of the system. Commissioning can either be performed via the touch panel or the WUI.

There are three (3) basic compensation modes

Reactive Power Compensation

Load Balancing

Harmonic Compensation

Reactive power compensation

The active filter can be configured for droop or dynamic reactive power compensation.

In static operation, a defined reactive power (Qref—Reactive Power Control) is generated similarly to a fixed

capacitor or choke.

In dynamic operation, the filter regulates its output power of the fundamental oscillation such that a defined power

factor (range) is maintained at the measurement point. The target range can be specified via an upper and lower

limit value of the active power factor (cosφ).

Note: All settings relate only to the fundamental (60Hz) and have no influence on the harmonics. Please note in

comparison measurements that the active power factor (cosφ) in distorted grids does not correspond to the power

factor (λ), because the active power factor (cosφ) does not contain a harmonic component by definition.

Load balancing (LB)

Load balancing is used to balance the asymmetrical current consumption of one or more loads at a network node

defined by the MIO measurement point. The function compensates for the difference of the fundamental

oscillation components of the three-phase currents with each other and thus produces a symmetrical grid load.

The regulation is configured separately for the negative sequence system (asymmetry caused by load between

two conductors) and zero sequence system (asymmetry caused by single-phase loads L against N, 4-wire

systems only):

Balancing ∆: Compensation level as a percentage [%] of the negative sequence system

Page 8: PowerAct Active Filter

PowerAct Operations Manual Rev 0.2 P a g e 8 | 46

Visit Powerside.com for the latest manual

Through this division into the symmetrical components, the symmetry is restored without any explicit

compensation of reactive power.

Functional notes:

The active and reactive components of the current will always be balanced with the same compensation

level

Prerequisites for zero sequence system compensation are the use of four-wire IPUs with N-connection and a

three-phase load/grid current measurement with the MIO.

Balancing the fundamental oscillation leads to an increased load on the DC link and can therefore lead to the

power limitation (derating) of the system with the message “Derating: DC voltage unbalanced”:

Variable per IPU Derating AC RMS

current 3W

Positive sequence system 125A

Negative sequence system 125A

Zero sequence system NA

Table 2: Derating limit values per IPU

The open/closed loop parameterization has the following effect on the behavior

Open loop: The currents are measured at the load and set at the IPU output

Closed loop: The currents are measured in the grid and regulated at the measurement point

Harmonic Compensation

The function SHC (Selective Harmonic Compensation) compensates for (“filters”) harmonics in the energy supply

grid.

For this, differentiated modes are distinguished for this which achieve both optimized current-based and

optimized voltage-based results for different requirements and grid conditions.

The following modes are available separately and can be individually configured for each harmonic

(3rd to 51st order):

1. Switched off No output

2. To zero Regulates the current output at the system connection point to zero

3. Compensation I Reduces the harmonic current measured at the connection point of the MIO by the

set compensation level (0 ...100%)—with current measurement.

Compensation U Reduces the

harmonic voltage measured at the connection point of the MIO by the set

compensation level (0 ...100%)—without current measurement.

Page 9: PowerAct Active Filter

PowerAct Operations Manual Rev 0.2 P a g e 9 | 46

Visit Powerside.com for the latest manual

4. 5. U Limit/I-Ctrl Limits the harmonic voltage measured at the connection point of the MIO to the set

maximum value taking the set maximum compensation level (0 … 100% based on

current) into consideration—with current measurement.

U Limit/U-Ctrl Limits the

harmonic voltage measured at the connection point of the MIO to the set maximum

value taking the set maximum compensation level (0 … 100% based on voltage)

into consideration—without current measurement

voltage-based compensation modes.

Modes 4 and 6 do not need an external current transformer. They function exclusively based on the measured

line voltage.

In these modes, the compensation level relates to the reduction of the voltage based on the SIA grid analysis.

0% corresponds to the operating mode “to zero” (no output current at this frequency)

100% regulates to the line voltage only and reduces this to the desired value 0.

NOTICE: It is strongly recommended that modes 4 and 6 NOT BE USED with manual SIA!

NOTICE: The tolerance in terms of the compensation level in these modes can be up to +/-30%. It is therefore

recommended that full compensation (100%) or the combination with Limit U be used as the setting.

Current-Based Compensation Modes

In modes 3 and 5, the compensation level is based on the current. Here, the compensation level describes the

ratio of system output current to grid current at the MIO connection point:

0% corresponds to the operating mode “to zero” (no output current at this frequency)

100% only regulates the grid current and reduces this to the desired value 0.

Limiting compensation modes

In modes 5 and 6, the compensation is only active if the configured voltage limit values are exceeded at the MIO

connection point. The system only supplies enough output necessary to comply with these limits.

In all modes, the compensation level applies in the same way for the positive, negative and zero sequence

systems, and is only specified once per harmonic. Compensation of the zero sequence system is only relevant

for 4-wire systems. The selective regulators for all odd-numbered harmonics of the ordinal numbers 3rd to 51st

operate parallel to each other without functional limitations in a system configuration (up to max. 4x IPUs and 1x

MIO).

With the SIA function (System Identification Algorithm), the system performs an automated grid scan to

determine the frequency response.

Page 10: PowerAct Active Filter

PowerAct Operations Manual Rev 0.2 P a g e 10 | 46

Visit Powerside.com for the latest manual

4 User Interfaces

There are four different user interfaces:

1. Human Machine Interface (HMI) via touch panel or Web User Interface (WMI)

2. Fieldbus interface (to a superordinate control technology system)

3. Digital inputs and outputs

4. SD card (offline system configuration via the manipulation of text files)—NOTICE: ONLY TO BE USED BY

AUTHORIZED SERVICE PERSONNEL!

Human Machine Interface (HMI)

The touch panel and WUI (Web User Interface) layouts are as effectively identical. The WUI (Java

applet) includes additional functions for data management on the SD card

touch panel.

The system can be configured, commissioned and operated via the touch panel in the front door. It can be used

to easily set parameters, check operating states, and display the measured data and system state during

operation. The touch panel can be used for entering commands and for menu navigation.

Touching the screen in the designated areas will call up, for example, the operating mode, the menu items or

measured values:

Figure 4.1: HMI home screen

Page 11: PowerAct Active Filter

PowerAct Operations Manual Rev 0.2 P a g e 11 | 46

Visit Powerside.com for the latest manual

Number Meaning

1 Device state with current parameter set

2 Message area for warnings and errors

3 Measured values—tap to see further details

4 Date and time

5 Language selection

6 Return to the home screen

7 Menu

8 Stop

9 Pause

10 Start

Table 4.1: Home screen legend

(HMI) home screen

Overview of the most important device functions and operating parameters

An equivalent circuit is displayed in the center

Four info boxes display the following measurement points:

Load (displayed: Irms; THDi; Q; P)

Grid (displayed: Irms; THDi; Q; P)

Busbar (displayed: U, THDu, f)

ACF (displayed: Irms; THDi; Q; Utilization)

Tapping on the info boxes will take you directly to the respective screens with the complete measurement data.

Display Header

Left: State display: (Run, Stop, Eco, Idle, Error) and skipping to the selection menu for the

current parameter set

Center: Pending messages and errors, and skipping to the message list

Right: Company logo and HMI-screenshot function to inserted SD card (in the touch panel)

The parameter set currently in use is displayed.

Tapping the display brings up a new window in which the parameter set can be changed.

Display Footer

Start, Stop, Pause, can be selected here and can be changed from any menu

Date and time

Currently selected language

Home screen button

Menu button

Page 12: PowerAct Active Filter

PowerAct Operations Manual Rev 0.2 P a g e 12 | 46

Visit Powerside.com for the latest manual

WUI — Web User Interface

As an alternative, the system can be operated graphically via a PC. To do so, the respective device

is to be connected to the TCP/IP interface of the control computer and the Java applet called up. The

tabs in the interface also provide access to the SD card contents with copy function to the connected

PC. A site-specific IP address can be assigned at the touch panel.

Anybus Fieldbus Interface

The control computer (CCU) has an integrated Anybus interface. Any approved plug-in modules from the

manufacturer HMS can provide native communications using the Modbus and BACnet protocols.

SD Card

The control computer comes equipped with an SD card. In addition to the programs for operating the system, this

memory card also contains all configured parameters. These can be edited offline via a text editor, e.g., to set the

system configuration parameters (hardware configuration) or to configure general basic settings, e.g., to preset

the parameter sets. Card can be inserted or removed only when the system is deactivated. All parameter settings

via touch panel or Java applet are also stored on the SD card (online).

NOTICE: Parameter changes which are made directly in the text files of the SD card are not checked for

plausibility. Incorrect changes can lead to malfunctions or even to irreversible hardware damage—therefore,

changes may only be made by authorized personnel. The manufacturer’s warranty will become void in the event

of unauthorized manipulation of data on the SD card.

The SD cards approved for use is SanDisk, 16 GB, HC, class 4

Page 13: PowerAct Active Filter

PowerAct Operations Manual Rev 0.2 P a g e 13 | 46

Visit Powerside.com for the latest manual

5 Operating the PowerAct Active Filter

Once the system has been switched via the switch S1 and it has booted up, it can be started and

stopped via the user interface:

The following internal system states are issued via the user interface Java/touch panel:

Name (No.) Description

INIT System boot-up phase

All system parameters are loaded

IDLE Parameter entry complete

PRECHARGE The pre-charging unit is charging the DC link voltage

STOP-PRECHARGE Pre-charging process interrupted

RUN The system is operating in compensation mode

ERROR Issue of an error message Stops PWM pulsing

Stops compensation mode

PAUSE Compensation of the grid-side current to “zero”

DERATING Output power choking

Table 5.1: System states

Manual start and stop

The control commands are created in local access mode via the Play/Stop/Pause buttons on the HMI

or, in remote access mode, via fieldbus.

Table 5.2: Function buttons and meaning

Page 14: PowerAct Active Filter

PowerAct Operations Manual Rev 0.2 P a g e 14 | 46

Visit Powerside.com for the latest manual

Control command Control command set via Target status

Start command • HMI Play button

• Digital inputs (MIOs)

• Via auto-restart or

• auto-start command

• Fieldbus

STATE_RUN

Stop command • HMI Stop button

• Stop command from

the MIO digital input

• Via auto-restart or

auto-start command

• Via induced warm start

• Fieldbus

STATE_IDLE

Pause command • HMI Pause button

• Digital inputs (MIOs)

• Fieldbus (no active PWM)

STATE_PAUSE

Error ACK command • HMI Error ACK button

• Digital inputs (MIOs)

• Via auto-restart

• Fieldbus

If the error is

successfully reset, the

following target state is

set: STATE_IDLE

Table 5.3: system states

Custom alarm messages and warnings

The system contains both hardware and software that continuously monitor the operating states and trigger

alarms or warnings that put the system in a safe, stopped error state or that issue messages to the HMI. Using

the programmable internal digital inputs or outputs, the user can implement remote monitoring.

Acknowledging Alarm Messages

Pending alarms are reported at the HMI. Alarms may be acknowledged. If the cause of an alarm remains a new

alarm is triggered. If an alarm forced the system to standby all alarms must be acknowledged before the system

will allow a restart. It is strongly recommended that the cause of the error be identified before acknowledging an

alarm in order to prevent damage in the system or the installation.

Java application (WUI)

The PowerAct Active Filter can be configured and monitored remotely via Ethernet from a PC web browser with a

valid and current Java installation. System IP address can be assigned and viewed at the touch panel (HMI).

Web version displays the same screen views as those appearing on the touch panel. Note that touch panel

access will be denied if while Java app is active.

Page 15: PowerAct Active Filter

PowerAct Operations Manual Rev 0.2 P a g e 15 | 46

Visit Powerside.com for the latest manual

6 Commissioning and system start-up

Refer to PowerAct Active Filter Installation Manual.

Review and update the system operating parameters set at the factory

Page 16: PowerAct Active Filter

PowerAct Operations Manual Rev 0.2 P a g e 16 | 46

Visit Powerside.com for the latest manual

7 Display and Control Screen—Touch Panel (HMI)

(HMI) Home screen

The button for switching to the home screen is in the footer. The values displayed are

Grid data

Load data

Voltage values

System values

Tapping on the info boxes calls up the respective measurements screen directly.

(HMI) Maintenance > Security > User-Password

The user can log out via this screen. If the user does not log out manually, the system will automatically

log the user out after an admin-configurable delay.

The user PIN can also be re-entered here. The default PIN is 0000.

(HMI) Maintenance > Security > Administrator-Password

The administrator can log out via this screen. If the administrator does not log out manually, the system

will automatically log the administrator out after a configurable delay.

Three setting options are available in the Administrator menu item:

Changing the administrator PIN, default setting is 4321

Automatic user logout parameter field: minimum time: 1 min., maximum time: 30 min.

Password protection selection field: Activation/deactivation of the request for PIN

(HMI) Logger > Error Messages

If an error is triggered or in the event of warning statuses, a text message is displayed in the header of

the HMI. The header will be highlighted in red. The messages remain for as long as the status is

present.

Column: Date

Column: Time

Column: Error

Column: Source

Column: Error message See Table: Errors

System settings and Configuration

Defines the hardware-specific characteristics. Due to the basic nature of these settings, the system must be

RESTARTED after any changes. (Exception: Operator mode)

(HMI) System > Grid

• Nominal voltage: e.g., 480 V Nominal frequency: 50 Hz/60 Hz

• Grid configuration: IT/TN

• Control topology: Closed loop/open loop

Page 17: PowerAct Active Filter

PowerAct Operations Manual Rev 0.2 P a g e 17 | 46

Visit Powerside.com for the latest manual

• Level THDv for shutdown: e.g., starting from 20% Telecontrol frequency in Hz

(HMI) System > DSC Port Configuration:

Enter the number of modules (IPUs) and the number of connected measurement modules (MIOs).

One CCU (controller) can operate and connect

• up to 4 connected IPUs

• as well as up to 2 MIOs at the same time.

(HMI) System > Operator Mode

Select between

• Local access => operation via HMI/touch screen. No commands via Modbus are accepted

• Remote access => operation via PLC. No commands from the HMI (touch screen/Java) are

accepted.

7.1 Control modes

There are three control modes available which can be operated in parallel:

(HMI) Control > Basic Setting > Mode > Parameter Set.

The following are available as the control basic settings:

• Reactive power control

• Balancing

• Harmonic compensation

For each control function, a mode, a priority, a dynamic and a rate of change can be selected via the HMI.

The settings are only valid for the respective parameter set (there are eight parameter sets). You can switch

between the parameter sets via the HMI (tapping at top left).

Control Modes Priority

If more than one control mode is active, the system may reach its power limit before control targets have been

reached. If all active control modes have the same priority, these will all be derated in the same way if the power

limit is reached. Control modes can be assigned priorities (1 – 4) with the control mode with the highest priority

derated last. The difference between the priorities of two control modes may not be greater than 1.

Dynamic

This describes the response speed of the system to changing grid states. The dynamic is configured in seconds

and specifies the time constant tau. In ideal conditions, the desired control value reaches 95% of its target value

within a period of 3x tau. Here, 0.1 s is recommended as the standard parameter value. An exception to this is the

dynamic of the reactive power voltage regulation. Here, unitless parameters are used.

For the dynamic, the rule is as fast as necessary, as large as possible. A high dynamic reduces the stability and

accuracy.

Page 18: PowerAct Active Filter

PowerAct Operations Manual Rev 0.2 P a g e 18 | 46

Visit Powerside.com for the latest manual

The dynamic for the voltage regulation is not specified in “seconds.” In the case of voltage regulation, the grid

impedance has an influence on the control dynamics. For this reason, the dynamic cannot be specified as a time

constant here.

The recommended dynamic for voltage regulation is unitless and is 0.001. Because the reactive power modes

Qref/Cos (phi)/Vref cannot work in parallel, there is only one dynamic parameter. If the reactive power control

mode is changed, it is necessary to check the dynamic parameter and to adjust it if required.

Change Rate

This is the rate of change when changing the desired value in pu/s. The standard parameter value is “0”—> the

change rate is disabled. This means that the system responds to a desired value change with the control dynamic.

Example: Parameter set to 1 pu/s: the system responds to a desired value change with a maximum rate of

increase of 1 pu/s.

7.2 Reactive power Settings

• Function for feeding in constant reactive power Qref

The Q function feeds in symmetrical reactive power at the connection point highly dynamically in accordance with

the desired value specification.

(HMI) Control > Control Q > Menu overview

All reactive power influences on the grid are done at the fundamental frequency (60 Hz)

The control variable is the imaginary part of the current (+/-90 °) in relation to the line voltage.

• cos (phi) (PFC control)

• Reactive power (Qref control—Q Reference)

• Voltage level (Vref control—V Reference)

(HMI) Control > Control Q > Qref

The Qref function regulates the symmetrical reactive power at the IPU AC connection in accordance with the

desired value specification, whereby this information is specified in kvar inductive (load sign convention).

The change rate for changing the desired value is configured in the basic settings.

• Function for dynamic reactive power compensation PFC Power Factor Correction

(HMI) Control > Control Q > PFC

The function PFC keeps the power factor at the measurement point (mean value over three phases) in a band

between two configurable limit values.

Page 19: PowerAct Active Filter

PowerAct Operations Manual Rev 0.2 P a g e 19 | 46

Visit Powerside.com for the latest manual

The limit values are stored on the SD card (negative sign for capacitive and positive sign for inductive

compensation). Eight different parameter sets are available for selection for the online configuration.

In order to enable the parallel operation of distributed systems, a droop is also specified.

Note on compliance with the limit values: The limit values are site-specific and adjusted according to the load

case. Here, it is not ensured that cos (phi) is permanently kept within this band under all circumstances. Instances

with very low active power, cos (phi) can temporarily leave the band.

Figure 7.1: Power Factor Correction operating principle

Function for dynamic voltage regulation Vref Voltage regulation Vref

(HMI) Control > Control Q > Vref.

Voltage reference control:

This function is used to maintain line voltage stability. It feeds in reactive power based on the line voltage in

accordance with the configurable VI characteristic curve.

Within the dead band between values 1 and 2, the voltage is not manipulated. If the line voltage leaves the dead

band, reactive power is fed in based on the slope (droop) of the VI characteristic curve that can be configured

separately for overvoltage and undervoltage.

Here, the system output current is regulated based on the line voltage.

The VI characteristic curve is configured using the following parameters:

Reference 1 voltage: Lower desired value of the voltage [in pu]

Reference 2 voltage: Upper desired value of the voltage [in pu]

Page 20: PowerAct Active Filter

PowerAct Operations Manual Rev 0.2 P a g e 20 | 46

Visit Powerside.com for the latest manual

Droop capacitive: VI characteristic curve increase below desired value 1

Droop inductive: VI characteristic curve increase above desired value 2

The droop is the result of the ratio dV/dI. It is to be adapted to individual grid conditions.

Note:

1.0 pu of the voltage V equates to the grid rated voltage

pu of the current I equates to the system rated current

Figure 7.2: Vref operating principle

NOTE: The dynamic for the voltage regulation is not specified in “seconds.” In the case of voltage regulation, the

grid impedance has an influence on the control dynamics. For this reason, the dynamic cannot be specified as a

time constant here. See Control => Basic Settings.

7.3 Load Balancing

(HMI) Control > Load Balancing

The balancing function compensates for the difference of the fundamental (60 Hz) component of the three-phase

currents producing a symmetrical grid load at the measurement point.

The regulation can be configured separately for negative sequence system compensation (systems with three-

and four-wire connection) and zero sequence system compensation (only systems with four-wire connection).

Page 21: PowerAct Active Filter

PowerAct Operations Manual Rev 0.2 P a g e 21 | 46

Visit Powerside.com for the latest manual

7.4 Harmonic compensation

The system compensates harmonics up to the 51st harmonic.

(HMI) Control > Harmonics > Harmonics

The following settings can be configured for each harmonic individually:

Mode: Off, To zero, Compensation I, Compensation U, Limit U/Control I, Limit U/Control U

I/ U Comp: Compensation level in [%]

I Limit: No function, created for future function

U Limit: Voltage limit value [%] Superordinate function call ups with a button on the right-hand side:

Copy: Copy all parameters in this screen for pasting into another parameter set

Paste: Paste all parameters copied from another parameter set

Reset: Reset to previous settings

(HMI) Control > Harmonics > Harm. Expert

Configuration of system-critical settings. Changes are only possible in the “Administrator” user level.

Padlock symbol: Click to change color red/green—blocks configuration changes for the “User” user level on

the “Harmonics” screen

Phase manual: Manual configuration of phase-correction values per harmonic

The manually configured phase angles are only used in the “Manual” setting

The phase angles determined by the SIA are only used in the “Automatic” mode

Phase Ext/Int: Display of the phase correction values determined automatically via the SIA at the MIO

measurement point (Ext) and system connection point (Int)

U trip: Voltage limit values that lead to the selective deactivation of the compensation per harmonic

Superordinate function call ups with a button on the right-hand side:

Trigger: Manual triggering of an SIA process for the automatic update of the phase correction angles

Manual: Use of the manually configured phase correction angles (see above)

Logger: Manual triggering of an error log entry on the SD card

Copy: Copy all parameters in this screen for pasting into another parameter set

Paste: Paste all parameters copied from another parameter set

Reset: Reset to previous settings

7.5 System Identification Algorithm (SIA) Harmonic Correction

The System Identification Algorithm (SIA) determines the grid-dependent harmonic corrections. To this end, the

transfer function to the measuring device is determined. The amplitude of the scanning signal can be configured.

For safety reasons, a limit value for the maximum permissible SIA voltage distortion is also configured in parallel

with the amplitude limit value.

Page 22: PowerAct Active Filter

PowerAct Operations Manual Rev 0.2 P a g e 22 | 46

Visit Powerside.com for the latest manual

Triggering the SIA

Automatic correction determination is triggered by:

1. The system being restarted (if the Boolean parameter DoSiaAfterBoot is set in the settings.txt file)

2. Manual triggering via button

3. External triggering via fieldbus interface

4. Automatic triggering in the event of resonance detection (violation of the limit value HarmonicDistortion level

UTrip for a harmonic)

The number of times the SIA is triggered in a time interval is monitored. This time interval can be configured.

Both manual SIA trigger commands and automatic control triggers are counted. If the permissible number of SIA

triggers per time interval is exceeded, retriggering the SIA is not permitted. The counter is automatically reset

once the time interval elapses or via a manual acknowledgment.

Persistent storage of data collected by SIA

The data collected by the SIA is stored permanently on the SD card and is also available after a restart of the

system.

Visualization of the SIA results

(HMI) Measurements > Overview > Harmonics Settings

Displays the correction angle for each harmonic as numerical values

(HMI) Measurements > Charts > Bode Diagram

Graphical visualization in a Bode diagram.

Figure 7.4: Bode Diagram

Page 23: PowerAct Active Filter

PowerAct Operations Manual Rev 0.2 P a g e 23 | 46

Visit Powerside.com for the latest manual

(HMI) Measurements > Harmonics > Expert

Mode:

Mode of the harmonic compensation.

“ACF to zero”: Output of the ACF is compensated for.

“Compensation”: MIO measurement point is compensated.

“ULimit”: The ACF only begins compensation once the harmonic limit value ULimit has been exceeded.

Phase correction: manual

Correction angle for the controller to adjust the specific frequency to a phase offset between the measuring signal

and the output of the filter (step response of the grid) caused by mains impedance.

Phase iExt/iInt:

Phase correction angle of the internal system model [in °]. Only the automatically determined values are

displayed.

UTrip:

Monitoring limit value of the individual harmonic voltage distortions.

Trigger:

Manual triggering of the SIA for correction angle determination.

NOTE: The commissioning engineer must be aware that with manual triggering the SIA, the harmonic

compensation mode must also be set to “automatic” to ensure that the determined values are also used by the

regulator. If the harmonics compensation mode is set to manual, the manually specified phase correction angles

will be used.

Resonance Monitoring

(HMI) Control > Harmonic Expert

The line voltage level of all harmonics up to the 51st harmonic are continuously monitored to detect and prevent

the excitation of resonances in the grid. The limit values for triggering automatic resonance suppression can be

adapted to the local conditions manually.

The default values are based on EN50160 and are set to 2% above the permissible limit values in accordance

with this standard:

Page 24: PowerAct Active Filter

PowerAct Operations Manual Rev 0.2 P a g e 24 | 46

Visit Powerside.com for the latest manual

Harmonic Default value

for UTrip in % Harmonic

Default value

for UTrip in %

3 7 29 3.1

5 8 31 3.1

7 7 33 2.2

9 3.5 35 2.8

11 5.5 37 2.8

13 5 39 2.2

15 2.4 41 2.7

17 4 43 2.7

19 3.8 45 2.2

21 2.3 47 2.6

23 3.4 49 2.6

25 3.3 51 2.6

27 2.2

Table7.1: Default parameter values for harmonics monitoring

NOTE: When setting the UTrip and ULimit parameters on the HMI, it must be ensured that the UTrip parameter

values are always higher than the ULimit parameter values.

Automated reaction of the harmonic control to a resonance

If a resonance is detected, the System Identification Algorithm is automatically started if the phase correction is

set to “Automatic.” If this sequence exceeds the maximum permissible number of triggers the harmonic causing

the triggering is deactivated.

Automatic warning with the message, “Suspect.”

The resonance monitoring system includes the function of automatically disabling individual harmonics after

several error events. After a single resonance detection, a warning is first issued to the HMI by marking the

corresponding harmonics as “suspect” (yellow exclamation point) but compensation will not be disabled.

Automatic blocking with the message “Critical”

If a resonance event occurs several times in succession, the status of the harmonics is changed from “suspect”

to “critical” (red exclamation point) and compensation will be disabled.

The status “critical” is reset by deactivating the affected harmonics (status to “deactivated”) or by restarting the

system. The access level is visualized via a “padlock symbol” to the right of the harmonics on the screens. After

restarting the system, all harmonic control warnings and disabling actions are reset.

The “critical” status is reset via a mode change of the respective harmonics to “deactivated” and then resetting to

“to zero,” “Compensation,” or “ULimit.”

Page 25: PowerAct Active Filter

PowerAct Operations Manual Rev 0.2 P a g e 25 | 46

Visit Powerside.com for the latest manual

Manual blocking

When setting the parameters for harmonic compensation, the administrator can specify access rights, and

therefore disable access to setting the parameters of individual harmonics for the “user” user level. See figure

“Harmonics” and “Harmonics Expert.” When logged in as an administrator, harmonics disabled for the user are

displayed in red, and harmonics accessible to the user are highlighted in green.

7.6 DC voltage regulation—DC link

Configuration and operation:

DC voltage regulation can be operated in 4 control modes:

0: = Disable

1: = Constant value regulation

2: = Variable regulation with specification of a maximum limit value (This function is only available for the 3W

configuration).

3: = Manual desired value set by the user

The parameter can be set on the SD card or via fieldbus interface.

Control Mode 0: Disable

The DC link voltage is not regulated.

Control Mode 1: Constant value regulation of the DC link voltage.

Depending on the set grid rated voltage, the DC link voltage is calculated automatically in the system.

The system regulates the DC link voltage to the following nominal values without an adjustment regulator:

Grid rated voltage [V] DC rated voltage [V] maxdcvoltage_V value range

<440 800 600 V - 1350 V

[440 528] 950 950 V - 1350 V

>528 1300 1300 V - 1350 V

Table 7.2: DC link desired value dependent on the grid rated voltage

In this mode, the DC voltage can no longer be influenced via parameterization.

Control Mode 2: Dynamic DC link voltage adjustment

Variable regulation with specification of a maximum limit value (This function is only available for the 3W

configuration).

If the following requirements are met:

Page 26: PowerAct Active Filter

PowerAct Operations Manual Rev 0.2 P a g e 26 | 46

Visit Powerside.com for the latest manual

Reduction of losses

High compensation current in level and frequency

Operation at high peak grid voltage

The level of the DC link voltage can be adjusted variably.

Behavior: If the set UDC Max of the DC link voltage is reached, the system power is derated. Derating is signaled

via a message. There are no error messages or a shutdown.

In the event of incorrect parameterization of maxDcVoltageInVolt outside of the limits: 800 V - 1,350 V, a warning

message is issued on the HMI.

In the event of incorrect parameterization of maxDcVoltageInVolt within the limits: 800 V - 1,350 V, e.g.,

maxDcVoltageInVolt is below the rated-voltage dependent MinDC voltage, an automatic adjustment of the limit

value is carried out internally without a warning message being issued on the HMI.

• Control Mode 3: Desired value regulation

As the target variable, the desired value is specified in V on the SD card (or via the fieldbus interface).

Parameterization

The following parameters are located in the parameter sets and are used to set the DC link regulation:

generalSettings. autoFunction. dcVoltageControlMode

generalSettings. autoFunction. setpointInVolt

NOTE: When using a DC/DC actuator on the DC link, the DC voltage regulation function of the AC/DC converter

is also to be disabled.

8 Network configuration

Fieldbus configuration

(HMI) System > Interface > Network

The standard settings for the network are preset. The TCP/IP settings can be changed here.

(HMI) System > Interfaces > Serial (CCU)

The standard settings for the interfaces are already preset.

This is intended for internal communication.

If the RS485 parameters are changed on the CCU, the settings must also be configured on the touch screen to

ensure correct functioning. If the transmission paths are long or the electrical noise levels high on the

communication line between CCU and HMI, it is possible to achieve increased communication stability through

Page 27: PowerAct Active Filter

PowerAct Operations Manual Rev 0.2 P a g e 27 | 46

Visit Powerside.com for the latest manual

reconfiguration, e.g., by reducing the communication speed.

9 Information on complying with grid connection rules

FRT function

The FRT function is deactivated in the default parameter configuration, and switches to the error state if an

under- or overvoltage is present.

Monitoring and protection system

The system has an integrated monitoring and protection system. It contains both hardware and software

functions that continuously monitor the operating status and trigger alarms or warnings that, where necessary,

put the system in a safe stop state and that issue messages to the HMI. By combining the programmable internal

inputs or outputs, the user can implement remote monitoring. In the event of an alarm, the alarm output is

activated. The pending errors can be read off and acknowledged via the fieldbus or HMI.

Protection—External Monitoring

Physical variables such as voltages, currents and temperatures are monitored within the system. The limit values

are listed in the corresponding document. In addition, software monitoring functions are implemented, such as

watchdogs, runtime checks and communication checks.

Protection—System response to errors

The response of the system to the triggering of a protection function is divided into three cases:

1. Information for the user:

The device does not respond because the event is not safe relevant, rather is merely information for the

user. This includes information and warnings.

2. Derating:

A physical variable reaches the first limit value => the output power is reduced. A message is issued

simultaneously whenever the output power is reduced. Furthermore, the derating factor is displayed on the

home screen in place of the utilization.

Example: IGBT temperature too high => the system derates the output power, bringing the entire system to

a thermally uncritical and stable operating point.

3. Disconnection:

If derating was not successful, or if safety-relevant limit values have been violated, the device disconnects

immediately. A trip occurs and an error message is issued.

IPU Redundancy

If just one IPU is affected due to an error, only this unit disconnects if the redundancy mode is active. Otherwise

the entire system switches to the error state.

Page 28: PowerAct Active Filter

PowerAct Operations Manual Rev 0.2 P a g e 28 | 46

Visit Powerside.com for the latest manual

Protection Derating (reduced output)

The derating function protects the system against damage by reducing its output.

Variable (per IPU) Sampling period Behavior 3W

RMS AC current positive sequence system

(overcurrent of 1.4x the rated current permitted for

1 second)

100ms Integral 125A

RMS Fundamental (60 Hz) current positive

sequence system

100ms Integral 125A

RMS Fundamental (60 Hz) current negative

sequence system

100ms Integral 125A

RMS Fundamental (60 Hz) current zero sequence

system

100ms Integral NA

Peak current IGBT 12.5ms / 10,240Hz Integral/graduated 275 / 325A

Over temperature IGBT 1s Proportional—integral 80°C

Under temperature IGBT 1s State-dependent -

Over temperature of the choke on the grid side 1s Proportional—integral 145°C

Under temperature of the choke on the module

side

1s Proportional—integral 145°C

Over temperature air interior IGBT 1s Proportional—integral 69°C

Difference between DC voltages high-side

/ low-side

12.5ms/10,240Hz Integral/graduated 125 / 150V

Peak DC voltages 25ms / 10,240Hz Integral/graduated 700 / 725V

Modulation index 12.5 ms/10,240 Hz Integral/graduated 0.95/1.5

Table 9.1: Overview of derating limit values

In the case of fundamental frequency (50/60 Hz) processes, the system power is reduced directly by reducing

the current limit. The harmonics are reduced indirectly by reducing the measured load. The individual limit values

from which derating begins are hardware-dependent.

Protection—Disconnection/trip and Information

In the event of a violation of a system-critical parameter in the software or firmware, or in system-critical software

statuses, e.g., breakdown of communication to an IPU, a trip occurs:

• The system stops the function, the main contactor is opened

• The system switches to the error state. The error is displayed on the HMI and recorded in the error list.

• Errors and warnings are also transmitted via fieldbus

The error messages are displayed on the HMI in two ways:

Page 29: PowerAct Active Filter

PowerAct Operations Manual Rev 0.2 P a g e 29 | 46

Visit Powerside.com for the latest manual

1. Error code

2. Text message

The error code is issued as an 8-digit code on the HMI:

Meaning Main number Module ID Block Error number Type

Meaning 07 0 0 : 0 d 01

Table 9.2: Error coding

Main number Origin

0x20 IPU3L125

0x21 IPU4L70

0x30 MIO3VBE

0x10 MIO3V4C

0x11 MIO6C

0x90 Control ACF

0x91 Control SVC

0x06 COM

0x07 Anybus

0x08 Software HMI, all errors that occur on the

touch screen, Java application or other HMI

0x09 Software SHARC, errors on the SHARC

0x02 Software Blackfin, errors on the Blackfin that

are not handled under 0x08.

Table 9.3: Breakdown of the main error number

Block Description

0x00 NONE — no specific block available

0x01 AIX

0x02 MCU

0x04 EXT1

0x08 EXT2

Table 9.4: Breakdown of the block error number

Type Description

0x00 Error still exists (internal for Anybus)

Page 30: PowerAct Active Filter

PowerAct Operations Manual Rev 0.2 P a g e 30 | 46

Visit Powerside.com for the latest manual

0x01 Arrived

0x02 Gone (acknowledged by the user)

0x03 Gone (acknowledged by system)

0x04 Warning

0x08 Information

0x0c Debug message

Table 9.5: Breakdown of the type error number

Pre-heating function for IPUs with output derating to zero

In order to preheat the IGBTs at temperatures below the minimum value, an automated function is implemented

in such cases that first put the IGBTs into operation without current output (100% derating). This state is

maintained until the minimum temperature at the IGBTs is reached. A corresponding message is shown on the

display:

Protection—Error Handling

After the occurrence of an error event, an ERR.bin error record is written to the SD card and an entry is also

made in the ERROR.txt file on the SD card. In the case of fieldbus connection, the error ID is also specified.

Depending on how the auto functions have been configured; further handling is performed in the system:

1. No handling

Waiting for user action

2. Auto-restart

After the error state disappears, the error is automatically acknowledged, and the system restarts after a

defined time. The number of permitted auto-restarts can be set in the file Settings.txt, see below

3. Auto-configuration.

The resonance handling activates a function which, after error triggering, performs a reconfiguration of the

phase angles of the harmonic compensation via SIA.

4. Disabling

Ultimately, a function can also be disabled

Protection—Manual acknowledgment of alarm messages

Pending alarms are displayed on the HMI (header, center). They can be called up and acknowledged by tapping

this area.

If the cause of the alarm remains after acknowledgment, a new alarm is triggered. All alarms must be

acknowledged before operation is possible again. Via fieldbus, acknowledgment is performed via the

Acknowledge bit (only rising edges are evaluated).

NOTE: It is strongly recommended that the causes of the error are identified before they are acknowledged in

Page 31: PowerAct Active Filter

PowerAct Operations Manual Rev 0.2 P a g e 31 | 46

Visit Powerside.com for the latest manual

order to avoid damage in the system or the surrounding installation.

Protection—Access rights

The operating concept grants the following access rights:

Protection level Access right

1. Firmware Development (Internal), Technology Partners

2. Software Development (internal)

3. SD card Development (internal), experts (Service, OEM)

4. HMI administrator/Service Experts (Service, OEM), trained specialists (external)

5. HMI user Operators (e.g., electricians without specific knowledge)

6. HMI no login No access rights, display only

Table 9.6: Access hierarchy

Protection—HMI

Access to the system is protected by a three-stage access level:

User level Rights and obligations

Administrator (Service) • Can view settings and measured values. • Can also configure settings that • may impair the safety/function of the system. • Can access the file system on the SD card

remotely via Java applet.

User • Can view settings and measured values. • Can configure settings that are not • reserved for Service.

Display • Can only view settings and measured values.

• Cannot configure any additional settings.

Table 9.7: User level and assigned rights

The security settings are saved on the SD card under “/CONFIGS/Security.txt.” If this file is deleted, the PIN will

be reset to 0000 (or 4321 for Service). Furthermore, the control check is disabled, i.e., anyone can change

settings immediately. The PIN entry for users is red, the PIN entry for administrators (Service) is blue:

Page 32: PowerAct Active Filter

PowerAct Operations Manual Rev 0.2 P a g e 32 | 46

Visit Powerside.com for the latest manual

Figure 9.8: Administrator login mask

Figure 9.9: User login mask

Page 33: PowerAct Active Filter

PowerAct Operations Manual Rev 0.2 P a g e 33 | 46

Visit Powerside.com for the latest manual

APPENDIX A: Fieldbus States and Commands

The following states are issued via the fieldbus interface:

State name Number Description

STATE_OFFLINE 0 //no communication

STATE_INIT 1 //Initialization/Booting in progress

STATE_IDLE 2 //System waiting for Instructions, main contactor open, IGBTs not

working

STATE_GO_IDLE 4 //System changing to STATE_IDLE

STATE_ERROR 8 //System in error state

STATE_PAUSE 9 //System pause, MAIN contactor closed, IGBTs are switching

STATE_SYNC_TO_V 10 //System is synchronized to grid

STATE_BLACKSTART 11 //System is black starting

STATE_COMPENSATOR 12 //System is in grid parallel mode

STATE_ISLANDING 13 //System in island mode

STATE_SIA 14 //System is analyzing grid

STATE_FRT 15 //Fault Ride Through

Control mode meaning/SD card

parameters Active power (P-

Control)

Description Data

type

Unit Min Max Default PackedID ParamID

ActivePowerControl

::

General::MODE_I

0: = DISABLE, 1: =

ACTIVE_POWER_ CONTROL,

2:= ACTIVE_POWER_LIMITER

Float No unit 0 2 0 2 0

Reactive power (Q-Control) Description Data type Unit Min Max Default PackedID ParamID

ReactivePowerControl::

General::MODE_I

0: = DISABLE, 1: =

REACTIVE_POWER_

CONTROL, 2: =

POWER_FACTOR_

CORRECTION, 3: =

VOLTAGE_CONTROL

Float No unit 0 3 0 3 0

Current balancing Description Data

type

Unit Min Max Default PackedID ParamID

Page 34: PowerAct Active Filter

PowerAct Operations Manual Rev 0.2 P a g e 34 | 46

Visit Powerside.com for the latest manual

LoadBalancingControl:: MODE_I 0: = DISABLE, 1: =

Delta balancing, 2: = Star balancing

Float No unit 0 3 0 4 0

Harmonic compensation

(harmonics)

Description Data

type

Unit Min Max Default PackedID ParamID

HarmonicControlGeneral::

MODE_I

0: = DISABLE, 1: = DELTA, 2: =

STAR, 3: = DELTA_STAR

Float No unit 0 3 0 6 0

SD card parameters–Charge Rate

- Regulation basic settings

Description Data type Unit Min Max Default PackedID ParamID

For the regulation of the individual functions, a time constant can be set. This enables project-specific interactions with other systems combined with dynamic

requirements to be taken into account. The change rate of the reference values is another setting option. This means that in the event of a reference value jump,

the slew rate is limited internally. A value of zero deactivates the limitation.

HarmonicControlGener al::

BANDWIDTH_F

Time constant tau Float sec 1.00 100,00

0

100 6 2

HarmonicControlGener al::

PRIO_I

0: = IMPORTANT,

3: = UNIMPORTANT

Int No unit 0.00 3.00 0.00 6 1

HarmonicControlGener al::

MODE_I

0: = DISABLE, 1: = DELTA, 2: =

STAR, 3: = DELTA_STAR

Int No unit 0.00 3.00 0.00 6 0

LoadBalancingControl::

CHANGE_RATE_F

Change rate in the event of

desired value change

Float pu/s 0.00 10.00 0.00 4 3

LoadBalancingControl::

TIME_CONSTANT_F

Time constant tau Float sec 0.00 1.00 0.10 4 2

LoadBalancingControl:: PRIO_I 0: = IMPORTANT, 3:

= UNIMPORTANT

Int No unit 0.00 3.00 0.00 4 1

LoadBalancingControl:: MODE_I 0: = DISABLE, 1: = Delta

balancing, 2: =

Balancing

Int No unit 0.00 3.00 0.00 4 0

ReactivePowerControl::

General::

Change rate in the event of

desired value change

Float pu/s 0.00 10.00 0.00 3 3

CHANGE_RATE_F

ReactivePowerControl:: General:: TIME_CONSTANT_F

Time constant tau Float sec 0.00 1.00 0.10 3 2

Page 35: PowerAct Active Filter

PowerAct Operations Manual Rev 0.2 P a g e 35 | 46

Visit Powerside.com for the latest manual

ReactivePowerControl:: General::

PRIO_I

0: = IMPORTANT, 3:

= UNIMPORTANT

Int No unit 0.00 3.00 0.00 3 1

ReactivePowerControl:: General::

MODE_I

0: = DISABLE, 1: =

REACTIVE_POWER_CONTRO L,

2: =

POWER_FACTOR_CORRECTI

ON, 3: =

VOLTAGE_CONTROL

Int No unit 0.00 3.00 0.00 3 0

ActivePowerControl:: General::

TIME_CONSTANT_F

Time constant tau Float sec 0.00 1.00 0.10 2 2

ActivePowerControl:: General::

CHANGE_RATE_F

Change rate in the event of

desired value change

Float pu/s 0.00 10.00 0.00 2 3

ActivePowerControl: General::

PRIO_I

0: = IMPORTANT, 3:

= UNIMPORTANT

Int No unit 0.00 3.00 0.00 2 1

ActivePowerControl:: General::

MODE_I

0: = DISABLE, 1: =

ACTIVE_POWER_CONTROL,

2:= ACTIVE_POWER_LIMITER

Int No unit 0.00 2.00 0.00 2 0

SD card parameters—Plimit active

power function

Description Data type Unit Min Max Default PackedID ParamI D

ActivePowerControl::

ActivePowerLimiter:

:LIMIT_TWO_F

Active power limit value of the

Plimit function

Float pu - 1.00 1.00 0.00 2 22

ActivePowerControl::

ActivePowerLimiter::

LIMIT_ONE_F

Active power limit value of the

Plimit function

Float pu - 1.00 1.00 0.00 2 21

ActivePowerControl::

ActivePowerControl::

SETPOINT_F

Desired value specification of

the active power control

Float pu - 1.00 1.00 0.00 2 8

ActivePowerControl::

General::

TIME_CONSTANT_ F

Time constant tau Float sec 0.00 1.00 0.10 2 2

ActivePowerControl::

General::CHANGE_RATE_F

Change rate in the event of

desired value change

Float pu/s 0.00 10 0.00 2 3

ActivePowerControl::

General::PRIO_I

0: = IMPORTANT, 3: =

UNIMPORTANT

Float No unit 0.00 3.00 0.00 2 1

ActivePowerControl::

General::MODE_I

0: = DISABLE, 1: =

ACTIVE_POWER_CONTR OL,

2:= ACTIVE_POWER_LIMITER

Float No unit 0.00 2.00 0.00 2 0

Page 36: PowerAct Active Filter

PowerAct Operations Manual Rev 0.2 P a g e 36 | 46

Visit Powerside.com for the latest manual

Active power characteristic

curves—Parameters

Meaning HMI Fieldbus SD card

(Parameter set x)

Min …

Max

Default

Pref Active power reference value at nominal

conditions

pu [Snominal]

Yes Yes pControl. pRef.

setPoint

-1 ..1 0

P(f) droop main

(lower, upper)

Active power droop depending on the

grid frequency below and above the

dead band

pu [Snominal/fnominal]

No Yes No - 0

P(f) dead band

(lower, upper)

Lower and upper end of the dead

band

pu [base: Snominal]

No Yes No - 0

P(f) max_charge Maximum charging power resulting

from a grid frequency deviation

pu [base: Snominal]

No Yes No

P(f)

max_discharge

Maximum discharging power resulting

from a grid frequency deviation

pu [base: Snominal]

No Yes No

P(U) droop

(lower, upper)

Active power droop depending on the

line voltage below and above the dead

band pu [base: Snominal/Unominal]

No Yes No - 0

P(U) dead band

(lower, upper)

Lower and upper end of the dead

band

pu [

base: Snominal]

No Yes No - 0

P(U) max_charge Maximum charging power resulting

from a line voltage deviation

pu [base: Snominal]

No Yes No - 0

P(U)

max_discharge

Maximum discharging power resulting

from a line voltage deviation

pu [base: Snominal]

No Yes No - 0

Power Factor Correction—

Parameters

File Description Access

via HMI

Access via

fieldbus

Data

type

Unit Min Max Default Packed

ID

fieldbus

Param ID

fieldbus

ReactivePowerControl::

PowerFactorCorrection :: DROOP_F

Parameter

set

Configurable control

deviation when using

independent parallel

regulation units

Yes Yes Float No unit - 10 10 0 3 22

Page 37: PowerAct Active Filter

PowerAct Operations Manual Rev 0.2 P a g e 37 | 46

Visit Powerside.com for the latest manual

ReactivePowerControl::

PowerFactorCorrection :: POWER_FACTOR_T

WO_F

Parameter

set

Limit value two for

cos (phi) regulation

Yes Yes Float No unit -1 1 1 3 21

ReactivePowerControl::

PowerFactorCorrection :: POWER_FACTOR_O

NE_F

Parameter

set

Limit value one for

cos (phi) regulation

Yes Yes Float No unit -1 1 1 3 20

Voltage regulation Vref—

Parameters Meaning Type Unit Min Max Default PackedID ParamID

ReactivePowerControl::

VoltageControl::

DROOP_TWO_F

Voltage regulation U/I droop Float pu 0.10 10.00 1.00 3 26

ReactivePowerControl::

VoltageControl::

DROOP_ONE_F

Voltage regulation U/I droop Float pu 0.10 10.00 1.00 3 25

ReactivePowerControl::

VoltageControl::

SETPOINT_TWO_F

Voltage regulation dead band

point 2 Float pu 0.90 1.10 1.00 3 24

ReactivePowerControl::

VoltageControl::

SETPOINT_ONE_F

Voltage regulation dead band

point 1 Float pu 0.90 1.10 1.00 3 23

Load balancing—Parameters Description Data type Unit Min Max Default PackedID ParamID

LoadBalancingControl::

COMPENSATION_LEVEL_STAR_F

Compensation level, star

balancing Float % 0.00 100 100 4 7

LoadBalancingControl::

COMPENSATION_LEVEL_DELTA_

F

Compensation level, delta

balancing Float % 0.00 100 100 4 6

LoadBalancingControl::

CHANGE_RATE_F

Change rate in the event of

desired value change Float pu/s 0.00 10 0.00 4 3

LoadBalancingControl::

TIME_CONSTANT_F Time constant tau Float sec 0.00 1 0.10 4 2

LoadBalancingControl::PRIO_I

0: =

IMPORTANT, 3: = UNIMPORTANT

Float No unit 0.00 3 0.00 4 1

LoadBalancingControl::

MODE_I

0: = DISABLE

1: = Delta balancing

(negative sequence

system) 2: = Star

balancing (zero sequence

system)

3: = Star and delta balancing

Float No unit 0.00 3 0.00 4 0

Page 38: PowerAct Active Filter

PowerAct Operations Manual Rev 0.2 P a g e 38 | 46

Visit Powerside.com for the latest manual

Harmonic compensation—

Parameters

Description Data type Unit Min Max Default Packet ID Param ID

SelectiveHarmonicControl

<harmonic order>.

MODE_I

0: = DISABLE_CONTROL

1: = TO_ZERO_CONTROL (comp. of

the inherent distortion)

2: =

CURRENT_COMPENSATION_CONT

ROL (compensation current at the MIO

measurement point)

3: =

VOLTAGE_COMPENSATION_CONT

ROL (compensation voltage at the MIO

measurement point)

4: =

CURRENT_COMPENSATION_VOLTAG

E_L

IMIT_CONTROL (mode 2 with U

limit) 5: =

VOLTAGE_COMPENSATION_V

OLTAGE_LIMIT_CONTROL

(mode 3 with U limit)

Int No

unit

0.0

0

5.0

0

0.00 24 0

SelectiveHarmonicControl

<harmonic order>.

access

Access restriction for the HMI Flo at No

unit

0.0

0

1.0

0

1.00

SelectiveHarmonicControl

<harmonic order>.

MANUAL_PHASE_CORRE

C TION_F

Manually configurable correction angle Flo at Degrees - 36

1

36

1

0.00 24 5

SelectiveHarmonicControl

<harmonic order>.

VOLTAGE_BLOCK_LIMIT_F

Individual switch-off threshold

of the controller

Flo at % 0.0 0

10 0

0.00 24 4

SelectiveHarmonicControl

<harmonic order>.

COMPENSATION_LEVEL_F

Compensation level for modes 2

and 3 0% => no compensation

100% => full compensation

Flo at % 0.0

0

10

0

100 24 1

SelectiveHarmonicControl

<harmonic order>.

CURRENT_COMPENSATI

O N_LIMIT_F

Placeholder for future function Flo at 24 2

SelectiveHarmonicControl

<harmonic order>.

VOLTAGE_COMPENSATI

O N_LIMIT_F

Limit value of the voltage distortion for

modes 4 and 5 (U limit)

Floa t % 0.0

0

10

0

100 24 3

Page 39: PowerAct Active Filter

PowerAct Operations Manual Rev 0.2 P a g e 39 | 46

Visit Powerside.com for the latest manual

SIA parameters Meaning Unit HMI Fieldbu

s

SD card

file

SD card

(name)

Min … Max Default

maxActorCurrent The parameter iMax specifies the

maximum current amplitude of

the generator signal in pu

(measured at the system rated

current).

pu No No INITCTR L.txt

frequencyResp

onse.

maxActorCurre nt

0.1 - 1 0.1

maxLineVoltage The parameter vMax specifies

the maximum permissible voltage

distortion as a percentage based

on the rated voltage while the

SIA algorithm is being executed.

If the voltage is distorted up to

the configured value by the

generator signal, the current

amplitude will no longer be

increased.

% No No INITCTR

L.txt

frequencyResp

onse.

maxLineVoltag e

0-0.05 0.01

actorCurrentAmplitudeCor

rection

<harmonic order>

Current amplitude response

determined by the SIA at the

connection point of the system

% Displa

y only

? FREQRE

SP

.txt

actorCurrentA

mplitudeCorrec

tion

1 e-6 -

1e6

actorCurrentPhaseCorrec

tion

<harmonic order>

Current phase response

determined by the SIA at the

connection point of the system

° Displa

y only

? FREQRE

SP

.txt

actorCurrentPh

aseCorrection

-361

to +361

lineCurrentAmplitudeCorr

ection

<harmonic order>

Current amplitude response

determined by the SIA at the MIO

measurement point

% Displa

y only

? FREQRE

SP

.txt

lineCurrentAmp

litudeCorrection

1 e-6 - 1e6

lineCurrentPhaseCorrectio

n

<harmonic order>

Current phase response

determined by the SIA at the MIO

measurement point

° Displa

y only

FREQRE

SP

.txt

lineCurrentPha

seCorrection

-361

to

+361

lineVoltageAmplitudeCorr

ection

<harmonic order>

Voltage phase response

determined by the SIA at the MIO

measurement point

% Displa

y only

FREQRE

SP

.txt

lineVoltageAmp

litudeCorrection

1 e-6 -

1e6

lineVoltagePhaseCorrectio

n

<harmonic order>

Voltage phase response

determined by the SIA at the MIO

measurement point

° Displa

y only

FREQRE

SP

.txt

lineVoltagePhase

Correction

-361

to

+361

Resonance

monitoring SD card

parameters

Meaning Unit HMI Fieldbus SD card

file

SD card (name) Min … Max

Default

VOLTAGE_BLOCK_LIMIT_F

Maximum permissible limit value of the respective harmonic if it is being compensated by the systems

% Yes No Parametersatz.txt

SelectiveHarmonic Control3. VOLTAGE_BLOCK_ LIMIT_F

0- 100

Page 40: PowerAct Active Filter

PowerAct Operations Manual Rev 0.2 P a g e 40 | 46

Visit Powerside.com for the latest manual

Reaction to resonance—

parameters

File Description Access via

HMI

Access

via

fieldbus

Data

type

Unit Min Max Def PackID ParaI

D

statemachine.

triggerSiaAfterBoot

Settings.

txt

True: System determines

the phase angle for

harmonics compensation

itself directly upon the first

goToRun.

No No Float No

unit

0.0

0

1.00 0.0

0

-2 -2

HarmonicStatemachine::

MIN_TIME_GAB_FOR_

SIA_

TRIGGER_I

Paramet

er set

Minimum time between two

SIA processes

No Yes Flea

t

sec 0.0

0

3600 30 1 11

HarmonicStatemachine::

MAX_NMB_SIA_TRIGG

ER_

TIME_INTERVALL_I

Paramet

er set

Time interval during which the

MAX_NMB_SIA_TRIGG

ER_I is permissible

No Yes Flea t

sec 0.0 0

3600 600 1 10

HarmonicStatemachine::

MAX_NMB_SIA_TRIGG

ER_I

Paramet

er set

Maximum permissible

number of SIA processes

within the defined time

interval

No Yes Flea

t

ST 0.0

0

20.0

0

5.0

0

1 9

HarmonicControlGeneral ::

AUTOPHASE_CORRECT

ION

_ ENABLED_I

Paramet

er set

Mode of the SIA: Auto or

Manual

No Yes Flea t

No

unit

0.0 0

1.00 0.0 0

6 3

netzkonfiguration.

teleControlFrequency

Settings.

txt

Ripple control frequency Yes No Float F 0.0

0

10 k 0 -2 -2

DC link DC voltage

regulation—parameters

Meaning Unit HMI Fieldbus SD card

(Parameter set

x)

SD card (name) Min… Max Default

Control Modus 0 := Disable

1 := Constant 2 := Variable 3 := Setpoint

No unit No Yes Parameter

set

ACDCConverterControl:: Group::

DC_VOLTAGE_CONTROL_MODE_I

0-4 1

Setpoint Desired

value can be

set by the

user

Volts No Yes Parameter

set

ACDCConverterControl::

Converter1::

DC_VOLTAGE_SET_POINT_F

800 V

Page 41: PowerAct Active Filter

PowerAct Operations Manual Rev 0.2 P a g e 41 | 46

Visit Powerside.com for the latest manual

Max DC Wert im

Modus Variable

Maximum DC

link voltage in

the “Variable”

mode

Volts No No InitCtrl.txt ipuControl. dcLinkControl.

levelControl. maxDcVoltageInVolt

800 V - 1,350 V

1,300 V

MIO configuration – SD

card parameters

Meaning HMI Fieldbus SD card (DSCPORTx) Min …

Max

Default

MIO n, Stromwandler N,

primär

Primary transformer ratio

current measurement N at MIO

n

Yes No mion. measurement.

stromwandlerN. primaer

1..1000 0

MIO n, Stromwandler N,

sekundär

Secondary transformer ratio

current measurement N

at MIO n

Yes No mion. measurement.

stromwandlerN. sekundaer

1/ 5 1

Gain Korrektur MIO n, current transformer gain

correction factor for input

No No mion. measurement.

stromwandlerN. gainxA

- 1000 - 1000

1

Offse Korrektur MIO n, current transformer

correction offset for current input

No No mion. measurement.

stromwandlerN. offsetxA

-1000 A - 1000A

0A

MIO n, Spannungswandler N,

primär

Primary transformer ratio

current measurement N at MIO

n

Yes No mion.

measurement.

SpannungswandlerN.

primaer

-100MV - 100MV

1000V

MIO n, Spannungswandler N,

sekundär

Secondary transformer ratio

voltage measurement N

at MIO n 0 -> 100 V/1 -> 1000 V

Yes No mion.

measurement.

SpannungswandlerN.

sekundaer

0 - 1 1

MIO n,

Spannungswandler

Gain Korrekturfaktor für

Volt Eingang

MIO n, current transformer gain correction factor for input

Yes No mion.

measurement.

SpannungswandlerN.

gainxV

-1000—

1000

1

MIO n,

Spannungswandler N

Korrektur-Offset für x

VoltEingang

MIO n, current transformer

correction offset for input

No No mion.

measurement.

SpannungswandlerN.

offsetxV

-1000 V

- 1000 V

0

MIO n,

Spannungswandler N

Phasenkorrektur für x

Volt und y Ampere

Phase correction current for

voltage transformer

No No mion.

measurement.

SpannungswandlerN.

phaseMeasurementErrorxVyA

-10 s -

10 s

0

Page 42: PowerAct Active Filter

PowerAct Operations Manual Rev 0.2 P a g e 42 | 46

Visit Powerside.com for the latest manual

Eingang

Steuerspannungs-

überwachung

0 Deactivated

1 Activated

No No mion.

measurement.

voltagecontrol

0-1 0

Temperaturmessung

(ext.)

0 Deactivated

1 Activated for KTY81 2

Activated for KTY85 3

Activated for PT100 4

Activated for PT1000

No No mion.

measurement.

temperature

0 - 4 0

Temperaturmessung

(ext)

Grenzen

No No mion. measurement.

extTempMin/Max

-100 °C - +250 °C

- 100

Aktion für

Digitaleingang N an

MIO n

0 Acknowledged 1 Start 2 Pause

3 Stop 4 Start/Stop 5 Start/Pause

6 Measurement switch 1 7 Measurement switch 2 8 to 15

Parameter set: 1 to 8 16 LCU pressure sensor 17

System release

Yes No mion. digital.

inputN. action

0-16 0

Triggerbedingung für

Digitaleingang N an MIO

n

0 Deactivated 1 Normal 2 Inverted

Yes No mion.

digital.

inputN.trigger

0-2 0

Aktion für 0 Deactivated Yes No mion. 0-16 0 Digitalausgang N an 1 Run digital.

MIO n 2 Pause outputN.

3 Error action

4 Warning

5 Derating

6 Mode PFC

7 Mode Qref

8 Mode Vref

9 FRT

10 OVRT

11 LVRT

12 MIO internal temp.

13 MIO ext temp.

14 Cooling

15 LCU pump control

16 LCU heating

Triggerbedingung für 0 Deactivated mion.

Page 43: PowerAct Active Filter

PowerAct Operations Manual Rev 0.2 P a g e 43 | 46

Visit Powerside.com for the latest manual

Digitalausgang N an 1 N/O contact digital. MIO n 2 N/C contact outputN.

trigger

SD card parameters—fieldbus. The

fieldbus interface is configured via the SD

card in the “Anybus.txt” file.

Description Access

via HMI

Access

via

fieldbus

Data

type

Unit Min Max Default

general. anybusenabled Activation of the fieldbus

communication; 0: = fieldbus

deactivated, 1:

= fieldbus activated

No No Int No unit 0 1 0

general. monitorConnectionState Fieldbus monitoring. If an

error is detected, the system

switches to STOP mode

No No Int No unit 0 1 1

general. monitorLifebit Monitoring of the fieldbus device

life bit. If the life bit is not

available, the system switches to

the STOP mode

No No Int No unit 0 1 0

profibus.dpv1. nodeid Definition of the node point of the

communication (address of the

fieldbus device in the Profibus

network)

No No Int No unit 0 125 10

modbus.rtu. nodeid Definition of the node point of the

communication (address of the

fieldbus device in the Modbus

network)

No No Int No unit 0 247 10

modbus.rtu. parity Use of a parity bit in the

communication protocol

No No Int No unit 0 3 0

modbus.rtu. baudrate Configuration of the

communication baud rate

No No Int No unit 0 8 4

modbus.rtu. rtuascii Selection between 8-bit RTU

(=0) and

7-bit ASCII (=1)

No No Int No unit 0 1 0

Page 44: PowerAct Active Filter

PowerAct Operations Manual Rev 0.2 P a g e 44 | 46

Visit Powerside.com for the latest manual

modbus.rtu. processtimeout Timeout in seconds, how long

after the last packet the

connection is to be considered

as still active.

No No Int Millisec

onds

0 1,00

0,00

0

10,000

modbus.tcp. ipaddress IP address of the fieldbus

device in the Modbus/TCP

network

No No Int No unit 10.0.0.3

modbus.tcp. subnetmask Subnet mask, specifies at

which bit position within the IP

address is to be used for

addressing the network or host

portion

No No Int No unit 255.255.

0.0

modbus.tcp. gateway Address of a gateway No No Int No unit 0.0.0.0

modbus.tcp. dhcpon Automatic IP address

assignment; on: = 1, off: = 0

No No Int No unit 1 0 1

modbus.tcp. duplexmode Duplex mode on: = 1/off : = 0 No No Int No unit 0 0 4

modbus.tcp. timeout TCP protocol timeout of the

internal connection

No No Int Second

s

0 1,000

,000

60

modbus.tcp. processtimeout Timeout in seconds, how long

after the last packet the

connection is to be considered

as still active.

No No Int Millisec

onds

0 1,000

,000

10,000

Error log entry configuration

Logger and Auto-restart parameters:

Meaning HMI Fieldbus SD card (Parameter set x) Min … Max

Default

Loggeraktivierung 1 Activated

0 Deactivated

No No system. logger. enabled - 0.1

Loggerauslösungsverzögerung [sec] No No system. logger. afterTrigger - 0.2

Loggerauflösung Time scaling: 1 = 10,240 Hz

No No system. logger. prescaler - 1

Derating Warnung True or false No No system. warning. derating - True

Page 45: PowerAct Active Filter

PowerAct Operations Manual Rev 0.2 P a g e 45 | 46

Visit Powerside.com for the latest manual

max_count_of_restarts Number of permitted

automatic restarts in a

fixed time period of

10 min.

No No netzkonfiguration.

max_count_of_resta

rts=0

0-7 0

DC/ DC actuator—regulation parameters Meaning HMI Fieldbus SD card

Settings.txt

Min …

Max

Default

netzkonfiguration. IPUredundancy [0 = disabled; 1 = enabled] No No Yes 0..1 0

Page 46: PowerAct Active Filter

PowerAct Operations Manual Rev 0.2 P a g e 46 | 46

Visit Powerside.com for the latest manual

Powerside 7850 TransCanada Hwy 980 Atlantic Ave. Saint-Laurent, Quebec Alameda, CA 514-333-8393 510-522-4400 www.powerside.com