preferred utilities manufacturing corp preferred utilities manufacturing corporation 31-35 south st....

33
Preferred Utilities Manufacturing Corp Preferred Utilities Manufacturing Corporation 31-35 South St. • Danbury • CT www.preferred-mfg.com Oxygen Trim Overview

Upload: jadyn-raff

Post on 31-Mar-2015

217 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: Preferred Utilities Manufacturing Corp Preferred Utilities Manufacturing Corporation 31-35 South St. Danbury CT  Oxygen Trim Overview

Preferred Utilities Manufacturing Corp

Preferred Utilities Manufacturing Corporation31-35 South St. • Danbury • CT

www.preferred-mfg.com

Oxygen Trim

Overview

Page 2: Preferred Utilities Manufacturing Corp Preferred Utilities Manufacturing Corporation 31-35 South St. Danbury CT  Oxygen Trim Overview

Overview

Introduction Combustion Experience ZP Oxygen Analyzer PCC-III Multiple Loop Controller Pricing Summary

Page 3: Preferred Utilities Manufacturing Corp Preferred Utilities Manufacturing Corporation 31-35 South St. Danbury CT  Oxygen Trim Overview

In-Situ Oxygen Probe

No separate analyzer, one less item to mount

Field replaceable probeOnly one conduit to stack.

Page 4: Preferred Utilities Manufacturing Corp Preferred Utilities Manufacturing Corporation 31-35 South St. Danbury CT  Oxygen Trim Overview

Proven Reliable Sensing element has been proven reliable in 100s

of installation over the last 10 years No Reference Air

The probe uses ambient air as a reference. Competitors use instrument air and run the risk of

element cracking due to water Automated, menu driven pushbutton

calibration. Fully automatic calibration package available.

In-Situ Oxygen Probe

Page 5: Preferred Utilities Manufacturing Corp Preferred Utilities Manufacturing Corporation 31-35 South St. Danbury CT  Oxygen Trim Overview

Thick cell Avoids premature cell failures

Ceramic heater provides reliable long life

Complete detailed diagnostics Automatic impedance checking

Alarms when time to recalibrate Alarms when reaching end of cell life

Optional fuel gas temperature element / T/C input

In-Situ Oxygen Probe

Page 6: Preferred Utilities Manufacturing Corp Preferred Utilities Manufacturing Corporation 31-35 South St. Danbury CT  Oxygen Trim Overview

Jackshaft Control with Air Trim

TE

Trim A ctuator

PCC - III

ACK

LOOP

AUTOMAN

AUTOMAN

DIS

REMLOC

ALARM

RUN

PV SP OUT

Boiler Master / Oxygen Trim

100A IR D A M P E R

D rum P ressure*

OIL

GAS

PT

TE

AE

STEAM

FEEDWATER

Jackshaft A ctuator

F lue G as Tem pera ture (O ptiona l)

F lue G as O xygen

A ir Tem pera ture (O ptiona l)

Notes:* H ot W ater Tem pera ture on H ot W ater G enera tor A pp lica tions

Coming Soon!

Page 7: Preferred Utilities Manufacturing Corp Preferred Utilities Manufacturing Corporation 31-35 South St. Danbury CT  Oxygen Trim Overview

Air Trim

Trim A ctuator

PCC - III

ACK

LOOP

AUTOMAN

AUTOMAN

DIS

REMLOC

ALARM

RUN

PV SP OUT

Boiler Master / Oxygen Trim

100A IR D A M P E R

OIL

GAS

AE

STEAM

FEEDWATER

F lue G as O xygen

Notes:* H ot W ater Tem pera ture on H ot W ater G enera tor A pp lica tions

ZT

FIRING RATE

Page 8: Preferred Utilities Manufacturing Corp Preferred Utilities Manufacturing Corporation 31-35 South St. Danbury CT  Oxygen Trim Overview

Fuel Trim

PCC - III

ACK

LOOP

AUTOMAN

AUTOMAN

DIS

REMLOC

ALARM

RUN

PV SP OUT

Boiler Master / Oxygen Trim

100A IR D A M P E R

OIL

GAS

AE

STEAM

FEEDWATER

Flue G as O xygen

Notes:* H ot W ater Tem pera ture on H ot W ater G enera tor A pp lica tions

IP

ZT

FIRING RATE**

Page 9: Preferred Utilities Manufacturing Corp Preferred Utilities Manufacturing Corporation 31-35 South St. Danbury CT  Oxygen Trim Overview

Combustion Experience

25 years of Combustion Control Experience…

Third Generation Digital Controller 2400 PCC II/III Controllers Installed

Exclusively in Combustion Control Applications 38 SCADA/Flex Projects 640 Rotary Cup Burner Projects

Page 10: Preferred Utilities Manufacturing Corp Preferred Utilities Manufacturing Corporation 31-35 South St. Danbury CT  Oxygen Trim Overview

Combustion Experience

JC Boiler Control & Monitoring Projects….

> 8000 Boilers

Numbers from 1998.… 324 Smoke Opacity Monitors 243 Flue Gas Temperature Monitors 226 Draft Indicators 212 Draft Controllers 91 Lead Lag Controllers

Page 11: Preferred Utilities Manufacturing Corp Preferred Utilities Manufacturing Corporation 31-35 South St. Danbury CT  Oxygen Trim Overview

Combustion Experience

PCC II/III Combustion Control Projects....

967 Boilers 624 Jackshaft Controlled Boilers 127 Parallel Positioning Controlled Boilers 103 Metering Controlled Boilers 351 Oxygen Trim Systems 13 EPA Compliant Opacity Monitors

Page 12: Preferred Utilities Manufacturing Corp Preferred Utilities Manufacturing Corporation 31-35 South St. Danbury CT  Oxygen Trim Overview

PCC-III Combustion Experience

Boiler Specific... Operator Friendly F(x) Characterizers with “Learn” Mode Built In Boiler Efficiency Constructed For Boiler Front Mounting 120 Vac Inputs for Direct BMS Interface Triac Outputs to Drive Electric Actuators Free Standard Combustion Blockware

There are many digital controller manufacturers, but NONE have Preferred’s in-depth and ongoing combustion control experience.

Page 13: Preferred Utilities Manufacturing Corp Preferred Utilities Manufacturing Corporation 31-35 South St. Danbury CT  Oxygen Trim Overview

Constructed For Boiler Front Mounting...

Weather Proof / Rain Proof Construction 7 3/4” Deep Case For Easy Mounting in Standard

Burner Panels 32 to 120 deg F rating for Continuous Operation Built-in Surge Suppressor, and 99-135 Vac

Input Power Rating for Industrial Applications

PCC-III - Construction

Page 14: Preferred Utilities Manufacturing Corp Preferred Utilities Manufacturing Corporation 31-35 South St. Danbury CT  Oxygen Trim Overview

English Used For Operation & Configuration...

Large Displays & Pushbuttons 16 character process variable

and alarm description messages 10 point first out alarm

annunciator Intuitive Bargraphs User Configurable Pushbuttons

PCC-III - Display

Page 15: Preferred Utilities Manufacturing Corp Preferred Utilities Manufacturing Corporation 31-35 South St. Danbury CT  Oxygen Trim Overview

Designed For Boilers... One PCC-III with integral I/O is capable of:

A Dual Fuel, Fully Metered with Oxygen Trim Control Scheme!

Standard 120 Vac Inputs, 8 Amp Relay Outputs for Easy BMS Interfacing

215 mA 24 Vdc Power Supply for Transmitters Triac Output Option Card for Electric Actuators Standard Optically Isolated RS485 Modbus

PCC-III - Input / Output

Page 16: Preferred Utilities Manufacturing Corp Preferred Utilities Manufacturing Corporation 31-35 South St. Danbury CT  Oxygen Trim Overview

18 Input / Outputs Standard! With Option Cards, Up to:

15 Analog Inputs 6 Analog Outputs 13 120 Vac Discrete Inputs

Partial List of Option Card Combinations:

PCC-III - Input / Output

I/O Expansion ExamplesPCC III Model

Number4-20 mA0-5 Vdc

AIN4-20 mAAOUT

120 VacDIN

8A(relay)ROUT

2A(triac pairs)

TOUT

200 mA(sinking)DOUT

TotalI/O

PCC-III- 0 0 0 0 5 2 5 2 0 4 18PCC-III- A A 0 0 15 2 5 2 0 4 28PCC-III- F F 0 0 11 6 5 2 0 4 28PCC-III- J J S 0 5 2 13 6 2 4 32PCC-III- G G S 0 9 2 5 2 5 4 27PCC-III- F G S 0 10 4 5 2 3 4 28PCC-III- A J 0 0 10 2 9 4 0 4 29PCC-III- F F 0 C 11 8 5 2 0 4 30PCC-III- G G S T 11 2 5 2 7 4 31

Page 17: Preferred Utilities Manufacturing Corp Preferred Utilities Manufacturing Corporation 31-35 South St. Danbury CT  Oxygen Trim Overview

Five (5) Discrete Inputs,120Vac, Opto-Isolated

Isolated RS 485;

Four (4) Discrete Outputs,24Vdc, 200mA;

Two (2) Analog Outputs,4 - 20mAdc, 750 Ohm;

Five (5) Analog Inputs,4 - 20mAdc, 1 - 5Vdc

120 VAC Power Input

Two (2) Relay Outputs,120 Vac 8 Amps. Max

One (1) Pair Triac Outputs, 2A,24 - 120Vac

Option Slot 3 BoardCPU Board

Option Slot 1

Option Slot 228

25

21

3456789101112

141516

13

1718192021222324

2627

4140

42434445464748495051

4140

42434445464748495051

1U

2U

3U

4U

5U

6U

7U

8U

1L

2L

3L

4L

5L

6L

7L

8L

33

Option Slot 3

3029

3132

CPU Board

PCC-IIIREAR VIEW "S” Board

PCC-III - Input / Output

120 Vac “L” & “N” Commons

Option Slot 1 and 2 Board (s)

Five (5) Analog Inputs,4 - 20mAdc, 1 - 5 Vdc

"A"Board

Three (3) Isolated Analog Inputs,4 - 20mAdc, 1 - 5 Vdc

"B"Board

Three (3) Analog Inputs4 - 20mAdc, 1 - 5 Vdc

Two (2) Analog Outputs,4 - 20mAdc, 750 Ohm

"F"Board

Two (2) Pair Triac Outputs, 2A,24 - 120Vac

Two (2) Analog InputsPot, 4 - 20mAdc, 1 - 5 Vdc

"G"Board

Two (2) Relay Outputs, 120 Vac,8 Amps. Max

Four (4) Discrete Inputs,120Vac, Opto-Isolated

"J"Board

Page 18: Preferred Utilities Manufacturing Corp Preferred Utilities Manufacturing Corporation 31-35 South St. Danbury CT  Oxygen Trim Overview

English Used For Operation & Configuration...

Intuitive, Easy to configure “Soft Wired” Blockware

Flexible Configuration Methods No Cost - Front Panel Edit Menus Low Cost - PC3_Edit™ Spreadsheet Full Featured - PC3_Draw ™ CAD

RS232 Up/Download to Laptops

PCC-III - Configuration

Page 19: Preferred Utilities Manufacturing Corp Preferred Utilities Manufacturing Corporation 31-35 South St. Danbury CT  Oxygen Trim Overview

English Used For Operation & Configuration…

PCC-III - Front Panel Editing

Edit keys

Edit Display Indicators

Edit Displays

Page 20: Preferred Utilities Manufacturing Corp Preferred Utilities Manufacturing Corporation 31-35 South St. Danbury CT  Oxygen Trim Overview

QUICK MENU

EDIT A BLOCK

PASSWORD MENU

(ENTER S/M) OR (EXIT S/M)

MEMORY MENU

COM MENU

CALIBRATE I/O

UTILITIES MENU

MAIN Menu:

ALL S/M or (EXIT S/M)A0 b0c1 AUTO or (S/M)A0 b0c2 AUTO or (S/M)

SERVICE MANUAL Menu:

ENTER PASSWORDSECURE CONTROLLERTIMEOUTCHANGE OPERATOR PASSWORDCHANGE TECHNICIAN PASSWORD

PASSWORD Menu:

ENTER THE BLOCK NUMBER...Bxx FUNCTION TYPEBxx IO1 DESCRIPTIONBxx IO2 DESCRIPTION.

.

Bxx P01 DESCRIPTIONBxx P02 DESCRIPTION..

EDIT A BLOCK Menu:

COPY PRIMARY TO BACKUPCOPY BACKUP TO PRIMARYERASE PRIMARYCOMPARE MEMORIESREMAINING MEMORY REPORTCONFIG. NAMEEPROM VER.

MEMORY Menu:

EXAMINE BLOCKFIND FUNCTIONFIND USAGEFORCE BLOCKUN-FORCE A BLOCKUN-FORCE ALL BLOCKSDISPLAY SCAN TIMEEDIT QUICK MENUBLOCK TIMING

UTILITIES SUB-MENU

COM PORTADDRESSBAUDPARITYRTU/ASCII+/- DATATIME OUTTEST CABLE

COM PORT Menu:

BOARD O INPUTS(BOARD 1 INPUTS)(BOARD 2 INPUTS)BOARD O OUTPUTS(BOARD 1 OUTPUTS)(BOARD 2 OUTPUTS)

CALIBRATION Menu:

HI PSI ALM SPLO PSI ALM SPHI LEVEL ALM SPLO LEVEL ALM SPPSI GAINPSI REPEAT/MINLEVEL GAINLEVEL REPEAT/MIN

QUICK Menu:

PCC-III - Front Panel Edit Menus

Page 21: Preferred Utilities Manufacturing Corp Preferred Utilities Manufacturing Corporation 31-35 South St. Danbury CT  Oxygen Trim Overview

PCC-III - Front Door Removed

RS232 BLOCKWARE DOWNLOAD PORT

BACKUP MEMORY WRITE PROTECT JUMPER

FRONT PANEL CABLE CONNECTOR

BACKUP MEMORY MODULE

REMOVE ONE SCREW TO TAKE AWAY FRONT PANEL

Page 22: Preferred Utilities Manufacturing Corp Preferred Utilities Manufacturing Corporation 31-35 South St. Danbury CT  Oxygen Trim Overview

PCC-III - PC3_Edit ™ Spreadsheet

Page 23: Preferred Utilities Manufacturing Corp Preferred Utilities Manufacturing Corporation 31-35 South St. Danbury CT  Oxygen Trim Overview

C o n fig u r a tio n

PR EFER R ED I NSTR UMENTS3 1 -3 5 S o u th S tre e t

D a n b u ry , C o n n e c tic u t

A D iv is io n O f P re fe rred U tilitie s M an fac tu rin g C o rp .

PC3-XXXX

JO B N A M E :

C U S TO M E R :

M O D E L#: P C C -III-xxxx

S heet: 1 o f 1

D R A W N :

JO B N O : Jxxxx

P C C -III B lo ck w are

S E R IA L # : X X X X

A P P R 'D :

R E V IS IO N :

S U P E R S E D E S : FO LD E R : \xxxx

R E F . D W G :

PANEL

140

P C C -IIIFR O N T P A N E L

IN D IC A TIO N S &C O N TR O LS

DIN

C H A N 0-5

20

R em ote A larmS ilence

ROUT

C H A N 0-1

147

C om m on A larm

AS

D IS 1

DIS 2

DIS 3

DIS 4

DIS 5

DIS 6

DIS 7

DIS 8

DIS 9

DIS 10

O UT BG 1

A/M PB1

ALM 1

ALM 2

ALM 3

ALM 4

ALM 5

ALM 6

ALM 7

ALM 8

ALM 9

ALM 10

PV BG 2

SP BG 2

O UT BG 2

A/M PB2

LO O P

D1

AOUT

C H A N 0-1

141

B oiler F iringR ate

0-100%

AIN

C H A N 0-1

11

S team D rumP ressure

FPT/HM anual

A uto

113

PID

110

FPCON

4

DIS 3

SP

D3

PV

D IS 2D2

PB 2

42

M an/A uto

LED 2

72

A/M PB1H

A/M 1

ASW

114

A

0%

B

DIN

C H A N 0-1

16

S

TM

low = m odula te

TM

O UT BG 1

O UT BG 1TS

O UT1

DIS 2PV1

DIS 3 SP1

TM

DIS 1

LED 4

74

PB 4

44

PLINK

45

HIALM

60

LOALM

63

ALM 1

ALM 2

PV

PV

A1

A2

1

AE

PCC-III Visio™ PC3_Draw

Blockware CADAllows PCC-III to be

configured using a library of block

templates with simple “drag” & “drop” mouse

operations

Page 24: Preferred Utilities Manufacturing Corp Preferred Utilities Manufacturing Corporation 31-35 South St. Danbury CT  Oxygen Trim Overview

Oxygen Analyzer Logic

AABO

FLUEGAS

TEMP80

AABO

CELLOHMS

82

AABO

DIAGCODE

83

ZAINch. 1-10-10%

OXYGEN

21

OxygenAnalyzer

Oxygen

DIS CH 1

PV BG 1

DABO

NORMAL

84

LOALM

1=DE56

Flue °F

DIS CH 2

DIS CH 3

Cell Imp.

DIS CH 4

Diag.

DIS CH 5

Cell OKNOT

85

Cell Fault

ALM 3

ALM 4

HIALM

1=DE49

High Flue Temp.Alarm

HIALM

1=DE50

ALM 1

ALM 2

MB

MB

MB

MB

PV

PV

AABO

CELLTEMP

81

MBCell °C

PV

SP BG 1

LEDMID.

RIGHT

76

DOUT

ch. 0-1

143

4

5

9

PS

OC

-

Low OxygenAlarm

ROUT

ch. 0-2

INVERT148

8U

7U

6U

NO

C

NC

High Flue TempShutdown

Page 25: Preferred Utilities Manufacturing Corp Preferred Utilities Manufacturing Corporation 31-35 South St. Danbury CT  Oxygen Trim Overview

Efficiency Logic

DIN

ch. 0-4

19

7L

1L

H

N

Fuel SelectClosed = Gas

AINch. 0-2Z 0.000S 5.000

12

27

19

20

+24

+

-

JackshaftPosition(0-100%)

DIS CH 7

SCALEX1 0.00Y1 12.50

X2 100.00Y2 100.00

31

Steam FlowTurndown

AINch. 0-4Z 1.000S 5.000

14

27

23

24

+24

+

-

Combustion AirTemperature

(0-150°F)

BEFF

#2 Oil& Gas

35

LOALM

0=DE48

AOUT

ch. 0-14-20 mA

141

11

12

+

-

Boiler EfficiencyBy Losses

DIS CH 8

DIS CH 6

Oxygen

ALM 5

FGT

CAT

OXY

FR

B

PV

Flue °F

ASW

36

DIN

ch. 0-1

16

4L

1L

H

N

Fuel Valve

S

0% A

DAETDR ON SEC

120

46

D Out BG1

LEDTOPLEFT

71

On = GasOff = Oil

FS

DOUT

ch. 0-2

144

4

6

9

PS

OC

-

Low EfficiencyAlarm

LEDMID.LEFT

75

On=Alarm

Page 26: Preferred Utilities Manufacturing Corp Preferred Utilities Manufacturing Corporation 31-35 South St. Danbury CT  Oxygen Trim Overview
Page 27: Preferred Utilities Manufacturing Corp Preferred Utilities Manufacturing Corporation 31-35 South St. Danbury CT  Oxygen Trim Overview
Page 28: Preferred Utilities Manufacturing Corp Preferred Utilities Manufacturing Corporation 31-35 South St. Danbury CT  Oxygen Trim Overview
Page 29: Preferred Utilities Manufacturing Corp Preferred Utilities Manufacturing Corporation 31-35 South St. Danbury CT  Oxygen Trim Overview

Controllers “Learn” Fuel-Air ratios Fuel and Air controllers are placed in Manual Burner is adjusted for optimum “low fire” “Store” button is pressed Air Flow SP, Oxygen SP, FD and FGR damper

curve points automatically calculated and entered. Process is repeated for up to 10 more load points

No calculating or entering of numeric data “Edit” points by re-Learning or via Edit Menu Separate Sets of Curves for Gas and Oil

Easy Commissioning with “Learn” Mode...

Page 30: Preferred Utilities Manufacturing Corp Preferred Utilities Manufacturing Corporation 31-35 South St. Danbury CT  Oxygen Trim Overview

Tools for Commissioning Front Panel Edit Keys Allow Commissioning

without laptops or handheld devices “Quick Menus” for rapid editing of tuning constants,

alarm setpoints, and key parameters “Last Parameter” selection Optional Password Protection with Time-out Copy between Primary and Backup Memories

“Examine”, “Block Force” and, “Service Manual” Troubleshooting Modes

Laptop Commissioning with PC3_Edit ™ or PC3_Draw

Page 31: Preferred Utilities Manufacturing Corp Preferred Utilities Manufacturing Corporation 31-35 South St. Danbury CT  Oxygen Trim Overview

Shallow case allows smaller enclosure Weather / Rain Proof case avoids glass doors No need for external isolation relays Built in 215mA transmitter power supply Largest quantity of I/O in a single enclosure “Examine”, “Block Force” and “Learn”

modes for efficient commissioning Free project proven combustion solutions 30 years of combustion experience to ensure

a smooth project

Lowest Installed Cost

Page 32: Preferred Utilities Manufacturing Corp Preferred Utilities Manufacturing Corporation 31-35 South St. Danbury CT  Oxygen Trim Overview

Summary

CB Oxygen Trim From Preferred.. Simple commissioning

Simplified approach to calibration Easy calibration Learn Mode

Low Cost & Field Proven. 10 year old sensor Thousands of PCC Controllers installed.

Page 33: Preferred Utilities Manufacturing Corp Preferred Utilities Manufacturing Corporation 31-35 South St. Danbury CT  Oxygen Trim Overview

Preferred Utilities Manufacturing Corp

For further information, contact...

Preferred Utilities Manufacturing Corporation31-35 South St. • Danbury • CT

T: (203) 743-6741 • F: (203) 798-7313www.preferred-mfg.com