protistor a070grb semiconductor protection fuses · d d amp-trap ®–form 101 a70grb semiconductor...

4
D PROTISTOR A070gRB SEMICONDUCTOR PROTECTION FUSES HIGHLIGHTS: Extremely Fast Acting Current Limiting Low l 2 t Excellent Cycling Capability gR APPLICATIONS: Protection of small inverters, UPS systems, motor drives and similar 700v or less equipment Ratings The A070gRB is a fast acting, full range fuse utilized in the protection of inverters, UPS and other discrete semi-conductor devices AC: 1-30A 160kA, 700V DC: 550VDC, L/R = 10mS UL Recognized Component UL File E76491 IEC 269-4 Compliance AC: UL Guide No. JFHR2 Approvals Features / Benefits International 10 X 38 mm (1 1/2 X 13/32) size for worldwide acceptance Ferrule mount 1 to 30A for design versatility Low I 2 t for improved semiconductor protection gR Class according to VDE 636-23 and IEC 269.4 38 (1.50) 10 x10, 3 (.406) Note: Fuses labels have both European and American references. FUSE HOLDERS FOR A070GRB FUSES USM Series .....ULTRASAFE TM Fuse Holders 303 Series ......Midget Fuse Blocks Gross Automation (877) 268-3700 · www.ferrazshawmutsales.com · [email protected]

Upload: others

Post on 19-Oct-2020

10 views

Category:

Documents


0 download

TRANSCRIPT

  • D ��D ��

    PRoTISToR

    A070gRB SEMICoNDUCToR PRoTECTIoN FUSES

    HIGHLIGHTS:Extremely Fast Acting Current LimitingLow l2tExcellent Cycling CapabilitygR

    APPLICATIoNS:Protection of small inverters, UPS systems, motor drives and similar 700v or less equipment

    Ratings

    The A070gRB is a fast acting, full range fuse utilized in the protection of inverters, UPS and other discrete semi-conductor devices

    AC: 1-30A 160kA, 700V

    DC: 550VDC, L/R = 10mS

    UL Recognized Component UL File E76491

    IEC 269-4 Compliance

    AC: UL Guide No. JFHR2

    Approvals

    Features/BenefitsInternational 10 X 38 mm (1 1/2 X 13/32) size for worldwide acceptanceFerrule mount 1 to 30A for design versatility Low I2t for improved semiconductor protectiongR Class according to VDE 636-23 and IEC 269.4

    38 (1.50)

    10

    x10, 3 (.406)

    Note: Fuses labels have both European and American references.

    FUSE HoLDERS FoR A070GRB FUSES

    USM Series . . . . .ULTRASAFETM Fuse Holders303 Series . . . . . .Midget Fuse Blocks

    Gross Automation (877) 268-3700 · www.ferrazshawmutsales.com · [email protected]

  • D ��D ��

    PRoTISToR

    A070gRB SEMICoNDUCToR PRoTECTIoN FUSESMelting Time Current Data (1 to 6A)

    Melting Time Current Data (8 to 30A)

    Peak Let Thru Current Data (1 to 6A)

    Peak Let Thru Current Data (8 to 30A)

    Tim

    e in

    Sec

    onds

    Tim

    e in

    Sec

    onds

    Max

    Inst

    anta

    niou

    s Pe

    ak L

    et T

    hru

    Max

    Inst

    anta

    niou

    s Pe

    ak L

    et T

    hru

    Current in Amperes

    Current in Amperes

    Available Current in RMS Symmetrical Amperes

    Available Current in RMS Symmetrical Amperes

    Gross Automation (877) 268-3700 · www.ferrazshawmutsales.com · [email protected]

  • D

    D ��

    D

    D ��

    AMP-TRAP®–Form 101

    A70gRB SEMICoNDUCToR PRoTECTIoN FUSES

    Maximum Arc Volts vs. System Voltage

    Clearing I2t vs. AC operating voltage

    Determines the peak arc voltage across fuse terminals as a function of applied voltage

    DC Voltage Capability vs. Time Constant DC Peak Arc Voltage

    Correction factor to determine clearing I2t of a fuse below its related voltage.

    1 to 6A

    DC Voltage Capability

    Tim

    e Co

    nsta

    nt (L

    /R)

    Max

    Pea

    k Ar

    c Vo

    ltage

    Max

    Pea

    k Ar

    c Vo

    ltage

    Corr

    ectio

    n fa

    ctor

    for I

    2 t

    Max

    Pea

    k Ar

    c Vo

    ltage

    Circuit Voltage

    Circuit Voltage (AC RMS)Circuit Voltage (AC RMS)

    Operating Voltage (AC RMS Volts)

    8 to 30A

    1 to 30A

    Gross Automation (877) 268-3700 · www.ferrazshawmutsales.com · [email protected]