proven overfill prevention solutions for bulk liquid …...proven overfill prevention solutions for...

2
Automatic Tank Gauging (ATG) Automatic Overfill Prevention System (AOPS) Proven Overfill Prevention Solutions for Bulk Liquid Storage Tanks The Rosemount Tank Gauging system is API 2350 and IEC 61511 compliant for automatic and manual overfill prevention systems. The system is open and scalable to ensure that you can comply with updated standards, today and in the future. There is now another option to help you stay on top of your PFD avg , safe and fully integrated remote partial proof-tests. Test the integrity of your devices from the comfort of your control room and spend less time in hazardous areas. The Rosemount™ 5900S with 2-in-1 technology provides dual level data in two independent layers of protection, using only one housing and a single tank nozzle. Installation time is reduced, not least in tanks with only one opening, including floating roof tanks with still-pipes and LPG tanks. Independent Protection Layers Meet the never ending challenge of fulfilling the latest safety regulations with overfill prevention solutions you can trust. 2-in-1 Functionality Comply with Regulations Remote Proof-Testing The first and most important line of defense against overfills is the basic process control system which secures continuous surveillance of tank fills. The overfill prevention system serves as a second defense layer against overfills should the first layer fail. One overfill occurs statistically every 3300 filling operations.Marsh and McLennan 2015. This equals one overfill every 10 years for a group of 10 tanks where each tank is filled three times per month. Rosemount 5900S 2-in-1 Radar Level Gauge

Upload: others

Post on 23-Jun-2020

16 views

Category:

Documents


0 download

TRANSCRIPT

Automatic Tank Gauging (ATG)

Automatic Overfill Prevention System (AOPS)

Proven Overfill Prevention Solutions for Bulk Liquid Storage Tanks

The Rosemount Tank Gauging system is API 2350 and IEC 61511

compliant for automatic and manual overfill prevention systems.

The system is open and scalable to ensure that you can comply with updated standards, today and in

the future.

There is now another option to help you stay on top of your PFDavg,

safe and fully integrated remote partial proof-tests.

Test the integrity of your devices from the comfort of your control

room and spend less time in hazardous areas.

The Rosemount™ 5900S with 2-in-1 technology provides dual level data in two independent layers of protection, using only one housing and a single tank nozzle.

Installation time is reduced, not least in tanks with only one opening, including floating roof tanks with still-pipes and LPG tanks.

Independent Protection Layers

Meet the never ending

challenge of fulfilling

the latest safety regulations with

overfill prevention solutions

you can trust.

2-in-1 Functionality

Comply with Regulations

Remote Proof-Testing

The first and most important line of defense against overfills is the basic process control system which secures continuous surveillance of tank fills.

The overfill prevention system serves as a second defense layer against overfills should the first layer fail.

“One overfill occurs statistically

every 3300 filling operations.”

Marsh and McLennan 2015.

This equals one overfill every 10 years for a group of 10 tanks where

each tank is filled three times per month.

Rosemount 5900S 2-in-1 Radar Level Gauge

The Rosemount Tank Gauging system provides both Automatic Tank Gauging and Overfill Prevention in the same system. It is IEC 61511 certified as a system solution, with the same products meeting specifications for both process control and safety applications.

Yet every tank, operation, and site is different. Therefore, the Rosemount Tank Gauging system offers three different recommended configurations for combining tank gauging and overfill prevention. Thus they provide the flexibility to help you optimize your operation while simultaneously staying safe.

Achieve SIL 2 or SIL 3 Overfill Safety

00807-0100-5901 Rev. BA 02/19

SIL 3

SafetyInstrumentedSystem (SIS)

2-in-1 RadarLevel Gauge

TankMaster InventoryManagement Software

Includes Visual & Audible Level Alert High and Level Alarm High-High (optional)

Connection toTankMaster

(optional)

Tank Hub

Tank Hub

System HubSystem Hub

Automatic Tank Gauging (ATG)Automatic Overfill Prevention System (AOPS)

Graphical FieldDisplay

RadarLevel Gauge

Multiple PointTemperature

SIL 2 Relay and/or 4-20 mA Analog Signal

SIL 2

Leve

l

Multiple PointTemperature

2-in-1 RadarLevel Gauge

SafetyInstrumentedSystem (SIS)

Ove

rfill

Automatic Tank Gauging (ATG)

TankMaster InventoryManagement SoftwareConnection to

TankMaster(optional)

Tank Hub

Tank Hub

System HubSystem Hub

Graphical FieldDisplay

Automatic Overfill Prevention System (AOPS)

SIL 2 Relay and/or 4-20 mA Analog Signal

Features SIL2 configuration SIL2 and ATG combined configuration SIL3 configuration

Safety level SIL 2 SIL 2 SIL 3

Sensor Rosemount 5900S / 5900C Radar Level Gauge Rosemount 5900S 2-in-1 Radar Level Gauge Rosemount 5900S 2-in-1 Radar Level Gauge

Output 4-20 mA and/or relay 4-20 mA and/or relay Relay

Proof-test Remote proof-test Remote proof-test Remote proof-test

Coverage factor 99% 99% 99%

IEC 61508 certificate ROS 1312032 C004 ROS 1312032 C005 ROS 1312032 C001

4-20mA Relay 4-20mA & relay

λDU 218 193 254

SFF 91.9% 91.6% 90.9%

PFDavg 1,089*10^-3 9,692*10^-4 1,260*10^-3

4-20mA Relay 4-20mA & relay

λDU 218 193 254

SFF 91.9% 91.6% 90.9%

PFDavg 1,089*10^-3 9,692*10^-4 1,260*10^-3

λDU 16

SFF 99%

PFDavg 8,116*10^-5

SIL 2

SafetyInstrumentedSystem (SIS)

RadarLevel Gauge

TankMaster InventoryManagement Software

Includes Visual & Audible Level Alert High and Level Alarm High-High (optional)

Connection toTankMaster

(optional)

Tank Hub

Tank Hub

System HubSystem Hub

Automatic Tank Gauging (ATG)Automatic Overfill Prevention System (AOPS)

Graphical FieldDisplay

RadarLevel Gauge

Multiple PointTemperature

SIL 2 Relay and/or 4-20 mA Analog Signal

Standard Terms and Conditions of Sale can be found at: www.Emerson.com/en-us/Terms-of-UseThe Emerson logo is a trademark and service mark of Emerson Electric Co. © 2017 Emerson. All rights reserved.

Emerson Automation SolutionsBox 150 (Visiting address: Layoutvägen 1)SE-435 23 Mölnlycke, Sweden +46 31 337 00 00 [email protected]