public comment no. 14-nfpa 24-2017 [ section no. 2.3.3 ] · awwa c206, field welding of steel water...

26
Public Comment No. 14-NFPA 24-2017 [ Section No. 2.3.3 ] 2.3.3 AWWA Publications. American Water Works Association, 6666 West Quincy Avenue, Denver, CO 80235. AWWA C104/A21.4, Cement-Mortar Lining for Ductile-Iron Pipe and Fittings, 2014. AWWA C105/A21.5, Polyethylene Encasement for Ductile-Iron Pipe Systems, 2010. AWWA C110/A21.10, Ductile-Iron and Gray-Iron Fittings, 2012. AWWA C111/A21.11, Rubber-Gasket Joints for Ductile-Iron Pressure Pipe and Fittings, 2012. AWWA C115/A21.15, Flanged Ductile-Iron Pipe with Ductile-Iron or Gray-Iron Threaded Flanges, 2011. AWWA C150/A21.50, Thickness Design of Ductile-Iron Pipe, 2014. AWWA C151/A21.51, Ductile-Iron Pipe, Centrifugally Cast, 2009. AWWA C153/A21.53, Ductile-Iron Compact Fittings, 2011. AWWA C200, Steel Water Pipe 6 in. (150 mm) and Larger,2012, Errata, 2012. AWWA C203, Coal-Tar Protective Coatings and Linings for Steel Water Pipe,2015. AWWA C205, Cement-Mortar Protective Lining and Coating for Steel Water Pipe 4 in. (100 mm) and Larger — Shop Applied,2012. AWWA C206, Field Welding of Steel Water Pipe,2011. AWWA C207, Steel Pipe Flanges for Waterworks Service — Sizes 4 in. Through 144 in. (100 mm Through 3,600 mm), 2013. AWWA C208, Dimensions for Fabricated Steel Water Pipe Fittings, 2012. AWWA C300, Reinforced Concrete Pressure Pipe, Steel-Cylinder Type, 2011. AWWA C301, Prestressed Concrete Pressure Pipe, Steel-Cylinder Type, 2014. AWWA C302, Reinforced Concrete Pressure Pipe, Noncylinder Type, 2011. AWWA C303, Reinforced Concrete Pressure Pipe, Bar-Wrapped, Steel-Cylinder Type, 2008. AWWA C600, Installation of Ductile Iron Water Mains and Their Appurtenances, 2010. AWWA C602, Cement-Mortar Lining of Water Pipe Lines in Place,4 in. (100 mm) and Larger, 2011. AWWA C900, Polyvinyl Chloride (PVC) Pressure Pipe, 4 in. Through 12 in. (100 mm Through 300 mm), for Water Transmission and Distribution, 2007, Errata, 2008. AWWA C905, Polyvinyl Chloride (PVC) Pressure Pipe and Fabricated Fittings, 14 in. Through 48 in. (350 mm Through 1200 mm), for Water Transmission and Distribution, 2010, Erratum, 2013. AWWA C906, Polyethylene (PE) Pressure Pipe and Fittings, 4 in. (100 mm) Through 63 in. (1575 mm) for Waterworks, 2015. AWWA C909, Molecularly Oriented Polyvinyl Chloride (PVCO) Pressure Pipe, 4 in. through 24 in. (100 mm through 600 mm), for Water, Wastewater, and Reclaimed Water Service, 2009. AWWA M11, A Guide for Steel Pipe Design and Installation, 4th edition, 2004. Statement of Problem and Substantiation for Public Comment Reference is made to the statement of problem and substantiation of Public Comment No.15-NFPA 24-2017 [ Section No. 10.1.1.1 ] . Related Item Public Input No. 24-NFPA 24-2016 [ Section No. 10.1.1.1 ] National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... 1 of 26 9/28/2017, 11:06 AM

Upload: others

Post on 22-Mar-2020

9 views

Category:

Documents


0 download

TRANSCRIPT

Public Comment No. 14-NFPA 24-2017 [ Section No. 2.3.3 ]

2.3.3 AWWA Publications.

American Water Works Association, 6666 West Quincy Avenue, Denver, CO 80235.

AWWA C104/A21.4, Cement-Mortar Lining for Ductile-Iron Pipe and Fittings, 2014.

AWWA C105/A21.5, Polyethylene Encasement for Ductile-Iron Pipe Systems, 2010.

AWWA C110/A21.10, Ductile-Iron and Gray-Iron Fittings, 2012.

AWWA C111/A21.11, Rubber-Gasket Joints for Ductile-Iron Pressure Pipe and Fittings, 2012.

AWWA C115/A21.15, Flanged Ductile-Iron Pipe with Ductile-Iron or Gray-Iron Threaded Flanges, 2011.

AWWA C150/A21.50, Thickness Design of Ductile-Iron Pipe, 2014.

AWWA C151/A21.51, Ductile-Iron Pipe, Centrifugally Cast, 2009.

AWWA C153/A21.53, Ductile-Iron Compact Fittings, 2011.

AWWA C200, Steel Water Pipe 6 in. (150 mm) and Larger,2012, Errata, 2012.

AWWA C203, Coal-Tar Protective Coatings and Linings for Steel Water Pipe,2015.

AWWA C205, Cement-Mortar Protective Lining and Coating for Steel Water Pipe 4 in. (100 mm) andLarger — Shop Applied,2012.

AWWA C206, Field Welding of Steel Water Pipe,2011.

AWWA C207, Steel Pipe Flanges for Waterworks Service — Sizes 4 in. Through 144 in. (100 mm Through3,600 mm), 2013.

AWWA C208, Dimensions for Fabricated Steel Water Pipe Fittings, 2012.

AWWA C300, Reinforced Concrete Pressure Pipe, Steel-Cylinder Type, 2011.

AWWA C301, Prestressed Concrete Pressure Pipe, Steel-Cylinder Type, 2014.

AWWA C302, Reinforced Concrete Pressure Pipe, Noncylinder Type, 2011.

AWWA C303, Reinforced Concrete Pressure Pipe, Bar-Wrapped, Steel-Cylinder Type, 2008.

AWWA C600, Installation of Ductile Iron Water Mains and Their Appurtenances, 2010.

AWWA C602, Cement-Mortar Lining of Water Pipe Lines in Place,4 in. (100 mm) and Larger, 2011.

AWWA C900, Polyvinyl Chloride (PVC) Pressure Pipe, 4 in. Through 12 in. (100 mm Through 300 mm), forWater Transmission and Distribution, 2007, Errata, 2008.

AWWA C905, Polyvinyl Chloride (PVC) Pressure Pipe and Fabricated Fittings, 14 in. Through 48 in.(350 mm Through 1200 mm), for Water Transmission and Distribution, 2010, Erratum, 2013.

AWWA C906, Polyethylene (PE) Pressure Pipe and Fittings, 4 in. (100 mm) Through 63 in. (1575 mm) forWaterworks, 2015.

AWWA C909, Molecularly Oriented Polyvinyl Chloride (PVCO) Pressure Pipe, 4 in. through 24 in. (100 mmthrough 600 mm), for Water, Wastewater, and Reclaimed Water Service, 2009.

AWWA M11, A Guide for Steel Pipe Design and Installation, 4th edition, 2004.

Statement of Problem and Substantiation for Public Comment

Reference is made to the statement of problem and substantiation of Public Comment No.15-NFPA 24-2017 [ Section No. 10.1.1.1 ] .

Related Item

Public Input No. 24-NFPA 24-2016 [ Section No. 10.1.1.1 ]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

1 of 26 9/28/2017, 11:06 AM

Public Comment No. 252-NFPA 13-2017 [ Section No. 2.3.6 ]

Public Comment No. 254-NFPA 13-2017 [ Section No. 6.1.1.1 ]

Public Comment No.15-NFPA 24-2017 [ Section No. 10.1.1.1 ]

Submitter Information Verification

Submitter Full Name: Ariel Carp

Organization: On my behalf

Street Address:

City:

State:

Zip:

Submittal Date: Wed May 10 11:27:50 EDT 2017

Committee Statement

CommitteeAction:

Rejected

Resolution: The committee does not believe that steel pipe should be used for underground service unlesslisted.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

2 of 26 9/28/2017, 11:06 AM

Public Comment No. 4-NFPA 24-2017 [ Sections 5.9.2.1, 5.9.2.2, 5.9.2.3, 5.9.2.4 ]

Sections 5.9.2.1, 5 5 .9.2.2, 5.9.2.3, 5.9.2.4

5.9.2.1

The When not designated by the AHJ, the fire department connection(s) shall use an NH internalthreaded an internal swivel fitting(s) with an with NH standard thread (s.) , except as permitted by5.9.2.3 and 5.9.2.4 .

5.9.2.2

At least one of the connections shall be the one of which being a 2.5 to 7. 5 NH 5 NH standard thread ,as specified in NFPA 1963 NFPA 1963 .

5.9.2.3

Where local fire department connections use threads that do not conform to NFPA 1963, the AHJ shalldesignate the thread to be used.

5.9. 2.4

Nonthreaded couplings shall be permitted where required by the AHJ.

5.9.2.4.1

Nonthreaded When nonthreaded couplings are designated for use by the AHJ, the couplings shall belisted.

Statement of Problem and Substantiation for Public Comment

What is the purpose for so much extra verbiage? It seems as though this section could be significantly shortened since so much of it is repetitive and redundant.

Related Item

FDC

Submitter Information Verification

Submitter Full Name: Ryan Wyse

Organization: Hebron Fire Department

Street Address:

City:

State:

Zip:

Submittal Date: Fri Mar 24 16:09:04 EDT 2017

Committee Statement

CommitteeAction:

Rejected

Resolution: The committee believes that the current structure of the section is appropriate and conforms tothe Manual of Style.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

3 of 26 9/28/2017, 11:06 AM

Public Comment No. 1-NFPA 24-2017 [ Section No. 6.6.1 ]

6.6.1*

Sectional valves shall be provided at appropriate locations within piping sections such that the number offire protection connections outlets between sectional valves does not exceed six.

Statement of Problem and Substantiation for Public Comment

One of our consultant was counting the pipe segments of the network for deciding the number and location of isolation valves, while I understand that only outlets should be counted.

Related Item

PI

Submitter Information Verification

Submitter Full Name: Ravinder Thakur

Organization: DORC

Street Address:

City:

State:

Zip:

Submittal Date: Mon Mar 20 00:54:25 EDT 2017

Committee Statement

CommitteeAction:

Rejected

Resolution: The text is clear in that the standard is referring to sprinkler system connectons, not pieces ofpipe.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

4 of 26 9/28/2017, 11:06 AM

Public Comment No. 9-NFPA 24-2017 [ Section No. 7.1.1.2 ]

7.1.1.2

A listed control valve shall be installed in each hydrant connection.

7.1.1.2.1

A valve required by 7.1.1.2 shall be permitted to be a listed, nonindicating valve, such as an undergroundgate valve in a roadway box.

7.1.1.2.2

Valves required by 7.1.1.2 shall be installed within 20 ft (6.1 m) of the hydrant.

7.1.1.2. 1 2 .1

Valves shall be clearly identified and kept free of obstructions.

7.1.1.2. 2 3

Where valves cannot be located in accordance with 7.1.1.2.1, valve locations shall be permitted whereapproved by the AHJ.

Statement of Problem and Substantiation for Public Comment

As currently written in 7.1.1.2, the standard does require a fire hydrant’s control valve to be listed. This omission should be rectified.

Additionally, while a Committee Statement was not provided to explain why Public Input No. 31 was resolved, it was expressed during the first Draft Meeting that indicating valves in accordance with 6.1.1 should not be necessary to control a fire hydrant and that it should not be necessary to obtain AHJ permission to utilize a nonindicating valve in a roadway box. If this is the Committee’s intent then it should be clearly stated in the standard.

Related Item

Public Input No. 31

Submitter Information Verification

Submitter Full Name: Larry Keeping

Organization: PLC Fire Safety Solutions

Street Address:

City:

State:

Zip:

Submittal Date: Wed May 03 21:54:12 EDT 2017

Committee Statement

CommitteeAction:

Accepted

Resolution: SR-1-NFPA 24-2017

Statement: As currently written in 7.1.1.2, the standard does require a fire hydrant’s control valve to be listed.This omission should be rectified.

Additionally, while a Committee Statement was not provided to explain why Public Input No. 31 was

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

5 of 26 9/28/2017, 11:06 AM

resolved, it was expressed during the first Draft Meeting that indicating valves in accordance with6.1.1 should not be necessary to control a fire hydrant and that it should not be necessary to obtainAHJ permission to utilize a nonindicating valve in a roadway box. If this is the Committee’s intentthen it should be clearly stated in the standard.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

6 of 26 9/28/2017, 11:06 AM

Public Comment No. 3-NFPA 24-2017 [ Section No. 7.2 ]

7.2 Number and Location.

7.2.1*

Hydrants shall be provided and spaced in accordance with the requirements of the AHJ.

7.2.2

Public hydrants shall be permitted to be recognized as meeting all or part of the requirements ofSection 7.2.

7.2.3*

Hydrants shall be located not less than 40 ft (12 m) from the buildings to be protected.

7.2.4

Where hydrants cannot be located in accordance with 7.2.3, hydrants located closer than 40 ft (12 m) fromthe building or wall hydrants shall be permitted to be used where approved by the AHJ.

7.2.5

When hydrants are located between a fire pump and its water source, the hydrant shall be identified in amanner approved by the AHJ.

Statement of Problem and Substantiation for Public Comment

Many times, a fire hydrant is placed between a fire pump and where the private main connects to the public water system. In the event the fire pump fails to operate, this hydrant provides a water source for the fire department to use when supplying the FDC. The problem we find is that these hydrants are not identified in any way, so they look just like all of the other hydrants. Should the fire pump be operating properly and this hydrant is used as a water source, it will steal water from the fire pump. This will then provide less water to the sprinkler system and to the other private fire hydrants that the fire pump supports. These hydrants should be identified in a way that tells firefighters not to use them when the fire pump is in operation. Since so many departments have different requirements for how their hydrants are marked, it should be the responsibility of the AHJ to develop a system of identifying these hydrants and their use.

Related Item

PI

Submitter Information Verification

Submitter Full Name: Ryan Wyse

Organization: Hebron Fire Department

Street Address:

City:

State:

Zip:

Submittal Date: Fri Mar 24 15:47:01 EDT 2017

Committee Statement

Committee Action: Rejected

Resolution: It is impractical to label every hydrant that is upstream of a fire pump.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

7 of 26 9/28/2017, 11:06 AM

Public Comment No. 15-NFPA 24-2017 [ Section No. 10.1.1.1 ]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

8 of 26 9/28/2017, 11:06 AM

10.1.1.1 Listing.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

9 of 26 9/28/2017, 11:06 AM

Piping manufactured in accordance with Table 10.1.1.1 shall be permitted to be used.

Table 10.1.1.1 Manufacturing Standards for Underground Pipe

Materials and Dimensions

Ductile Iron

Cement-Mortar Lining for Ductile-Iron Pipe and Fittings

Polyethylene Encasement for Ductile-Iron Pipe Systems

Rubber-Gasket Joints for Ductile-Iron Pressure Pipe and Fittings

Flanged Ductile-Iron Pipe with Ductile-Iron or Gray-Iron Threaded Flanges

Thickness Design of Ductile-Iron Pipe

Ductile-Iron Pipe, Centrifugally Cast

Standard for the Installation of Ductile Iron Water Mains and Their Appurtenances

Concrete

Steel

Steel Water Pipe 6 in. (150 mm) and Larger

Coal-Tar Protective Coatings and Linings for Steel Water Pipe

Cement-Mortar Protective Lining and Coating for Steel Water Pipe 4 in. (100 mm) and Larger — Shop Applied

Field Welding of Steel Water Pipe

Steel Pipe Flanges for Waterworks Service — Sizes 4 in. Through 144 in. (100 mm Through 3,600 mm)

Dimensions for Fabricated Steel Water Pipe Fittings

A Guide for Steel Pipe Design and Installation

Concrete

Reinforced Concrete Pressure Pipe, Steel-Cylinder Type

Prestressed Concrete Pressure Pipe, Steel-Cylinder Type

Reinforced Concrete Pressure Pipe, Non-Cylinder Type

Reinforced Concrete Pressure Pipe, Steel-Cylinder Type, Pretensioned

Cement-Mortar Lining of Water Pipe Lines in Place, 4 in. (100 mm) and Larger

Plastic

Polyvinyl Chloride (PVC) Pressure Pipe, 4 in. Through 12 in. (100 mm Through 300 mm), for Water Transmissio

Polyvinyl Chloride (PVC) Pressure Pipe and Fabricated Fittings, 14 in. Through 48 in. (350 mm Through 1200 m

Polyethylene (PE) Pressure Pipe and Fittings, 4 in. (100 mm) Through 63 in. (1575 mm) for Waterworks

Molecularly Oriented Polyvinyl Chloride (PVCO), 4 in. Through 24 in. (100 mm Through 600 mm) for Water, Was

Brass

Specification for Seamless Red Brass Pipe, Standard Sizes

Copper

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

10 of 26 9/28/2017, 11:06 AM

Materials and Dimensions

Specification for Seamless Copper Tube

Specification for Seamless Copper Water Tube

Requirements for Wrought Seamless Copper and Copper-Alloy Tube

Statement of Problem and Substantiation for Public Comment

Reference is made to the statement of problem and substantiation of Public Input No. 24-NFPA 24-2016 [ Section No. 10.1.1.1 ] .

Related Item

Public Input No. 24-NFPA 24-2016 [ Section No. 10.1.1.1 ]

Public Comment No. 252-NFPA 13-2017 [ Section No. 2.3.6 ]

Public Comment No. 254-NFPA 13-2017 [ Section No. 6.1.1.1 ]

Public Comment No. 14-NFPA 24-2017 [ Section No. 2.3.3 ]

Submitter Information Verification

Submitter Full Name: Ariel Carp

Organization: On my behalf

Street Address:

City:

State:

Zip:

Submittal Date: Wed May 10 11:31:51 EDT 2017

Committee Statement

CommitteeAction:

Rejected

Resolution: The committee believes that steel pipe is not appropriate for underground service unlessspecifically listed for underground service.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

11 of 26 9/28/2017, 11:06 AM

Public Comment No. 5-NFPA 24-2017 [ Section No. 10.1.1.1 ]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

12 of 26 9/28/2017, 11:06 AM

10.1.1.1 Listing.

Piping manufactured in accordance with Table 10.1.1.1 shall be permitted to be used.

Table 10.1.1.1 Manufacturing Standards for Underground Pipe

Materials and Dimensions Standard

Ductile Iron

Cement-Mortar Lining for Ductile-Iron Pipe and FittingsAWWAC104/A21.4

Polyethylene Encasement for Ductile-Iron Pipe SystemsAWWAC105/A21.5

Rubber-Gasket Joints for Ductile-Iron Pressure Pipe and FittingsAWWAC111/A21.11

Flanged Ductile-Iron Pipe with Ductile-Iron or Gray-Iron Threaded FlangesAWWAC115/A21.15

Thickness Design of Ductile-Iron PipeAWWAC150/A21.50

Ductile-Iron Pipe, Centrifugally CastAWWAC151/A21.51

Standard for the Installation of Ductile Iron Water Mains and Their Appurtenances AWWA C600

Concrete

Reinforced Concrete Pressure Pipe, Steel-Cylinder Type AWWA C300

Prestressed Concrete Pressure Pipe, Steel-Cylinder Type AWWA C301

Reinforced Concrete Pressure Pipe, Non-Cylinder Type AWWA C302

Reinforced Concrete Pressure Pipe, Steel-Cylinder Type, Pretensioned AWWA C303

Cement-Mortar Lining of Water Pipe Lines in Place, 4 in. (100 mm) and Larger AWWA C602

Plastic

Polyvinyl Chloride (PVC) Pressure Pipe, 4 in. Through 12 in. (100 mm Through 300mm), for Water Transmission and Distribution

AWWA C900

Polyvinyl Chloride (PVC) Pressure Pipe and Fabricated Fittings, 14 in. Through 48 in.(350 mm Through 1200 mm), for Water Transmission and Distribution

AWWA C905

Polyethylene (PE) Pressure Pipe and Fittings, 4 in. (100 mm) Through 63 in. (1575 mm)for Waterworks

AWWA C906

Molecularly Oriented Polyvinyl Chloride (PVCO), 4 in. Through 24 in. (100 mm Through600 mm) for Water, Wastewater, and Reclaimed Water Service

AWWA C909

Brass

Specification for Seamless Red Brass Pipe, Standard Sizes ASTM B43

Copper

Specification for Seamless Copper TubeASTMB75/B75M

Specification for Seamless Copper Water Tube ASTM B88

Requirements for Wrought Seamless Copper and Copper-Alloy Tube

Stainless Steel

Specification for Standard Specification for Seamless, Welded, and Heavily ColdWorked Austenitic Stainless Steel Pipes

ASTM B251

ASTMA312/312M

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

13 of 26 9/28/2017, 11:06 AM

Statement of Problem and Substantiation for Public Comment

The addition of this material into this section would allow the use of an appropriate material already allowed for use in Table 6.3.1.1 of the 2016 version of NFPA 13, and is currently included in Table 7.3.1.1 of the proposed 2019 version. This is the same material for the same application.

Related Public Comments for This Document

Related Comment Relationship

Public Comment No. 6-NFPA 24-2017 [Section No. 10.2.1.1]

Related Item

FDR

Submitter Information Verification

Submitter Full Name: Chris Haldiman

Organization: Watts Water Technologies

Street Address:

City:

State:

Zip:

Submittal Date: Mon Apr 24 09:44:41 EDT 2017

Committee Statement

CommitteeAction:

Accepted

Resolution: SR-22-NFPA 24-2017

Statement: The addition of this material into this section would allow the use of an appropriate material alreadyallowed for use in Table 6.3.1.1 of the 2016 version of NFPA 13, and is currently included in Table7.3.1.1 of the proposed 2019 version. This is the same material for the same application.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

14 of 26 9/28/2017, 11:06 AM

Public Comment No. 11-NFPA 24-2017 [ Section No. 10.2.1.1 ]

10.2.1.1

Fittings manufactured in accordance with Table 10.2.1.1 shall be permitted to be used.

Table 10.2.1.1 Fittings Materials and Dimensions

Materials and Dimensions Standard

Cast Iron

Gray Iron Threaded Fittings, Classes 125 and 250 ASME B16.4

Gray Iron Pipe Flanges and Flanged Fittings, Classes 12, 125, and 250 ASME B16.1

Ductile Iron

Ductile Iron and Gray Iron Fittings AWWA C110/A21.10

Ductile-Iron Compact Fittings AWWA C153/A21.53

Malleable Iron

Malleable Iron Threaded Fittings, Classes 150 and 300 ASME B16.3

Steel Factory-Made Wrought Steel Buttweld Fittings ASME B16.9 Buttwelding Ends ASMEB16.25 Specification for Piping Fittings of Wrought Carbon Steel and Alloy Steel for Moderate and High

TemperatureService ASTM A234/A234M Pipe Flanges and Flanged Fittings NPS 1 ⁄ 2 through24 ASME B16.5 Forged Fittings, Socket-Welded and Threaded ASME B16.11 Steel Pipe Flanges forWaterworks Service — Sizes 4 in. Through 144 in. (100 mm Through 3,600 mm) AWWAC207 Dimensions for Fabricated Steel Water Pipe Fittings AWWA C208

Copper

Wrought Copper and Copper Alloy Solder-Joint Pressure Fittings ASME B16.22

CastCopper Alloy Solder Joint Pressure Fittings ASME B16.18

Bronze Fittings

Cast Copper Alloy Threaded Fittings, Classes 125 and 250 ASME B16.15

Statement of Problem and Substantiation for Public Comment

As per the decision during the last cycle to delete the references to steel pipe from Table 10.1.1.1 and as confirmed during the First Draft per the resolution of PI No. 24, the references to steel pipe fittings should be similarly deleted

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

15 of 26 9/28/2017, 11:06 AM

from table 10.2.1.1, because they are not suitable for underground service.

As noted in the Committee Statement for PI No. 24, “Steel piping used for underground needs to be listed due to issues surrounding corrosion.”

Related Item

Public Input No. 24

Submitter Information Verification

Submitter Full Name: Larry Keeping

Organization: PLC Fire Safety Solutions

Street Address:

City:

State:

Zip:

Submittal Date: Wed May 03 22:20:20 EDT 2017

Committee Statement

CommitteeAction:

Rejected but see related SR

Resolution: SR-7-NFPA 24-2017

Statement: As per the decision during the last cycle to delete the references to steel pipe from Table 10.1.1.1and as confirmed during the First Draft per the resolution of PI No. 24, the references to steel pipefittings should be similarly deleted from table 10.2.1.1, because they are not suitable forunderground service.

As noted in the Committee Statement for PI No. 24, “Steel piping used for underground needs to belisted due to issues surrounding corrosion.”

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

16 of 26 9/28/2017, 11:06 AM

Public Comment No. 6-NFPA 24-2017 [ Section No. 10.2.1.1 ]

10.2.1.1

Fittings manufactured in accordance with Table 10.2.1.1 shall be permitted to be used.

Table 10.2.1.1 Fittings Materials and Dimensions

Materials and Dimensions Standard

Cast Iron

Gray Iron Threaded Fittings, Classes 125 and 250 ASME B16.4

Gray Iron Pipe Flanges and Flanged Fittings, Classes 12, 125, and 250 ASME B16.1

Ductile Iron

Ductile Iron and Gray Iron FittingsAWWAC110/A21.10

Ductile-Iron Compact FittingsAWWAC153/A21.53

Malleable Iron

Malleable Iron Threaded Fittings, Classes 150 and 300 ASME B16.3

Steel

Factory-Made Wrought Steel Buttweld Fittings ASME B16.9

Buttwelding Ends ASME B16.25

Specification for Piping Fittings of Wrought Carbon Steel and Alloy Steel for Moderateand High TemperatureService

ASTMA234/A234M

Pipe Flanges and Flanged Fittings NPS 1⁄2 through 24 ASME B16.5

Forged Fittings, Socket-Welded and Threaded ASME B16.11

Steel Pipe Flanges for Waterworks Service — Sizes 4 in. Through 144 in. (100 mmThrough 3,600 mm)

AWWA C207

Dimensions for Fabricated Steel Water Pipe Fittings AWWA C208

Copper

Wrought Copper and Copper Alloy Solder-Joint Pressure Fittings ASME B16.22

CastCopper Alloy Solder Joint Pressure Fittings ASME B16.18

Bronze Fittings

Cast Copper Alloy Threaded Fittings, Classes 125 and

25025

Stainless Steel

Specification for Standard Specification for Seamless, Welded, and Heavily ColdWorked Austenitic Stainless Steel Pipes

ASME B16.15

ASTMA312/312M

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

17 of 26 9/28/2017, 11:06 AM

Statement of Problem and Substantiation for Public Comment

The addition of this material into this section would allow the use of an appropriate material already allowed for use in Table 6.3.1.1 of the 2016 version of NFPA 13, and is currently included in Table 7.3.1.1 of the proposed 2019 version. This is the same material for the same application.

Related Public Comments for This Document

Related Comment Relationship

Public Comment No. 5-NFPA 24-2017 [Section No. 10.1.1.1] Same material.

Related Item

FDR

Submitter Information Verification

Submitter Full Name: Chris Haldiman

Organization: Watts Water Technologies

Street Address:

City:

State:

Zip:

Submittal Date: Mon Apr 24 09:48:17 EDT 2017

Committee Statement

CommitteeAction:

Rejected but see related SR

Resolution: SR-7-NFPA 24-2017

Statement: As per the decision during the last cycle to delete the references to steel pipe from Table 10.1.1.1and as confirmed during the First Draft per the resolution of PI No. 24, the references to steel pipefittings should be similarly deleted from table 10.2.1.1, because they are not suitable forunderground service.

As noted in the Committee Statement for PI No. 24, “Steel piping used for underground needs to belisted due to issues surrounding corrosion.”

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

18 of 26 9/28/2017, 11:06 AM

Public Comment No. 10-NFPA 24-2017 [ Section No. 10.4.3.2 ]

10.4.3.2 *

Private fire service mains shall not be permitted to extend more than 10 ft (3 m) under the building exceptas allowed in 10.4.3.2.1.

10.4.3.2.1

Where private fire service mains extend more than 10 ft (3 m) into the building, they shall be run in acovered trench.

10.4.3.2.1.1 *

The trench shall be accessible from within the building.

10.4.3.2.1.2

The trench shall have rigid walls and a base.

10.4.3.2.1.3

The trench shall be constructed of noncombustible materials.

10.4.3.2.1.4 *

Provisions for draining water shall be provided for the trench.

10.4.3.2.1.5

Where the piping in the trench is installed under foundations or footers, the foundation or footer sufficientclearance shall be arched to create a minimum of 24 in. (610 mm) clearance. provided in accordancewith 10.4.3.

2.

1.

5

2 .

1 Where acceptable to the AHJ, pipe sleeves shall be permitted to be used.

10.4.3.2.2

Piping in the trench shall be permitted to be in accordance with 10.1.1 .

10.4.3.2.2.1

Where the trench is entirely of concrete construction, aboveground

Aboveground piping in accordance with NFPA 13 shall be permitted to be used.

10.4.3.2.2.2

Where piping installed in the trench is in accordance with 10.1.1 , all joints shall be restrained inaccordance with 10.6.2 or 10.6.3 .

10.4.3.2.3 *

Where piping is installed in a trench as permitted by 10.4.3.2.1 , a valve shall be provided where theunderground piping enters the trench.

10.4.3.2.4

A valve shall be installed before the piping enters under the building and within 24 in. (600 mm) of wherethe piping enters the building.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

19 of 26 9/28/2017, 11:06 AM

Statement of Problem and Substantiation for Public Comment

These revisions are offered for the following reasons:

- 10.4.3.2.1: Since 10.4.3.2.2 allows pipe as per 10.1.1 (ie. PVC or PE), the trench must be covered to protect it from damage.

- 10.4.3.2.1.5: The 24 in. requirement is in conflict with 10.4.3.1.2, which only requires 12” clearance for pipe passing below a footing or foundation.

- 10.4.3.2.1.5.1: Deleted since it is redundant to 10.4.3.1.2.1, which incidentally, does not require AHJ permission to utilize a sleeve.

- 10.4.3.2.2.1: Since 10.4.3.2.1.3 already requires a trench to be noncombustible, the allowance for aboveground piping should be automatically permitted. Above ground piping should be allowed if the trench is built using brick or block or stone. Concrete should not be mandatory.

- 10.4.3.2.4: Deleted since it is in conflict with 10.4.3.2.3. As currently proposed 10.4.3.2.4 would require 2 valves within close proximity of each other – one immediately outside the building and then one right inside the building, in the trench.

Related Item

First Revision No. 14

Submitter Information Verification

Submitter Full Name: Larry Keeping

Organization: PLC Fire Safety Solutions

Street Address:

City:

State:

Zip:

Submittal Date: Wed May 03 22:07:14 EDT 2017

Committee Statement

Committee Action: Rejected

Resolution: See Committee action and statement on SR 8.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

20 of 26 9/28/2017, 11:06 AM

Public Comment No. 2-NFPA 24-2017 [ New Section after 10.4.3.2.4 ]

10.4.3.2.5

When piping is installed in a trench under the building, the bury depths of 10.4.2.2 shall not apply once thepipe is more than 10 ft (3.0 m) into the building.

Statement of Problem and Substantiation for Public Comment

The bury depth rules for freezing and protection of the piping from damage should not be applied once the pipe is far enough into the building. The 10 foot limitation is arbitrary but was chosen for freeze protection purposes.

Related Item

First Revision No. 14

Submitter Information Verification

Submitter Full Name: Peter Schwab

Organization: Wayne Automatic Fire Sprinkler

Street Address:

City:

State:

Zip:

Submittal Date: Fri Mar 24 13:46:55 EDT 2017

Committee Statement

Committee Action: Rejected

Resolution: See committee action and statement on SR 8.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

21 of 26 9/28/2017, 11:06 AM

Public Comment No. 8-NFPA 24-2017 [ Section No. 10.10.1 ]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

22 of 26 9/28/2017, 11:06 AM

10.10.1 Approval of Underground Piping.

The installing contractor shall be responsible for the following:

(1) Notifying the AHJ and the owner's representative of the time and date testing is to be performed

(2) Performing all required acceptance tests

(3) Completing and signing the contractor's material and test certificate(s) shown in Figure 10.10.1

Figure 10.10.1 Sample of Contractor's Material and Test Certificate for Underground Piping.

Revise Figure 10.10.1 in theTest Descrition for Flushing as follows:

Flushing: Flow the required rate until water is verifed to be clear of debris at outlets such a hydrantsand blow-offs Flush at one of the flow ates specifd in 10.10.2.1.3.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

23 of 26 9/28/2017, 11:06 AM

Statement of Problem and Substantiation for Public Comment

As currently proposed, the text on flushing still speaks to “collection of foreign material”, but the standard does not call for such collection, it only requires that the water is verified to be clear.

Related Item

First Revision No. 15

Submitter Information Verification

Submitter Full Name: Larry Keeping

Organization: PLC Fire Safety Solutions

Street Address:

City:

State:

Zip:

Submittal Date: Wed May 03 21:39:59 EDT 2017

Committee Statement

CommitteeAction:

Accepted

Resolution: SR-4-NFPA 24-2017

Statement: As currently proposed, the text on flushing still speaks to “collection of foreign material”, but thestandard does not call for such collection, it only requires that the water is verified to be clear.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

24 of 26 9/28/2017, 11:06 AM

Public Comment No. 12-NFPA 24-2017 [ Section No. 10.10.2.1.3.1 ]

10.10.2.1.3.1

Where the flow rates established in Table 10.10.2.1.3 are not attainable, the maximum flow rate available tothe system shall be acceptable.

10.10.2.1.3.2

In lieu of flushing with the waterflow rates prescribed in 10.10.2.1.3 and 10.10.2.1.3.1 water main swabbingof the piping, by the forceful introduction of a large spnge through the pipe, to remove debris, shall bepermitted.

10.10.2.1.3.2.1

Water main swabbing shall be repeated, as necessay, until the last sponge that has fully penetrated thepipe is clean and the discharge water is clear.

Statement of Problem and Substantiation for Public Comment

Water conservation has become a very large issue in many regions and the water flow rates prescribed by the standard are very high and often not permitted by the municipal authority. Water main swabbing is an excellent alternative to the current flushing requirements. It is more obtrusive than flushing and thus more effective and can use significantly less water to achieve the desired results

Related Item

Public Input No. 22

Submitter Information Verification

Submitter Full Name: Larry Keeping

Organization: PLC Fire Safety Solutions

Street Address:

City:

State:

Zip:

Submittal Date: Wed May 03 22:26:04 EDT 2017

Committee Statement

Committee Action: Rejected but held

Resolution: Introduces a concept that was not previously considered by the committee.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

25 of 26 9/28/2017, 11:06 AM

Public Comment No. 16-NFPA 24-2017 [ Sections A.1.4, A.3.2.1 ]

Sections A.1.4, A.3.2.1

A.1.4

It is the intent of the committee to recognize that future editions of this standard are a further refinement ofthis edition and earlier editions. The changes in future editions will reflect the continuing input of the fireprotection community in its attempt to meet the purpose stated in this standard. Compliance with allrequirements of a future edition could be considered as providing an equivalent level of system integrity andperformance of the system.

A.3.2.1 Approved.

The National Fire Protection Association does not approve, inspect, or certify any installations, procedures,equipment, or materials; nor does it approve or evaluate testing laboratories. In determining theacceptability of installations, procedures, equipment, or materials, the authority having jurisdiction may baseacceptance on compliance with NFPA or other appropriate standards. In the absence of such standards,said authority may require evidence of proper installation, procedure, or use. The authority havingjurisdiction may also refer to the listings or labeling practices of an organization that is concerned withproduct evaluations and is thus in a position to determine compliance with appropriate standards for thecurrent production of listed items.

This new langauge (A.1.4) needs to be correleated with all NFPA documents - NFPA 13R does not includethis annex section

Statement of Problem and Substantiation for Public Comment

This annex language was accepted to NFPA 13, NFPA 13D, NFPA 24 and NFPA 14. This is a positive change to the standard and this new language should be correlated with the other NFPA documents.

Related Item

PI-3

FR-21

Submitter Information Verification

Submitter Full Name: Roland Asp

Organization: National Fire Sprinkler Association

Affilliation: NFSA Engineering and Standards Committee

Street Address:

City:

State:

Zip:

Submittal Date: Wed May 10 11:32:46 EDT 2017

Committee Statement

Committee Action: Rejected

Resolution: No changes proposed. Text in A.1.4 already exists.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

26 of 26 9/28/2017, 11:06 AM