pumps and pumping stations

32
Pumps and Pumping Stations Pumps add energy to fluids and therefore are accounted for in the energy equation Energy required by the pump depends on: Discharge rate Resistance to flow (head that the pump must overcome) Pump efficiency (ratio of power entering fluid to power supplied to the pump) Efficiency of the drive (usually an electric motor) 2 2 1 1 2 2 1 2 2 2 pump L v p v p z H z H g g 2 2 L f minor v H h h h K g

Upload: sera

Post on 28-Jan-2016

181 views

Category:

Documents


17 download

DESCRIPTION

Pumps and Pumping Stations. Pumps add energy to fluids and therefore are accounted for in the energy equation Energy required by the pump depends on: Discharge rate Resistance to flow (head that the pump must overcome) - PowerPoint PPT Presentation

TRANSCRIPT

Page 1: Pumps and Pumping Stations

Pumps and Pumping Stations

• Pumps add energy to fluids and therefore are accounted for in the energy equation

• Energy required by the pump depends on:– Discharge rate– Resistance to flow (head that the pump must overcome)– Pump efficiency (ratio of power entering fluid to power supplied

to the pump)– Efficiency of the drive (usually an electric motor)

2 21 1 2 2

1 22 2pump L

v p v pz H z H

g g

2

2L f minor f i

vH h h h K

g

Page 2: Pumps and Pumping Stations

Pump Jargon• (Total) Static head – difference in head between suction

and discharge sides of pump in the absence of flow; equals difference in elevation of free surfaces of the fluid source and destination

• Static suction head – head on suction side of pump in absence of flow, if pressure at that point is >0

• Static discharge head – head on discharge side of pump in absence of flow

Total static head

Static suction head

Static discharge

head

Page 3: Pumps and Pumping Stations

Pump Jargon• (Total) Static head – difference in head between suction

and discharge sides of pump in the absence of flow; equals difference in elevation of free surfaces of the fluid source and destination

• Static suction lift – negative head on suction side of pump in absence of flow, if pressure at that point is <0

• Static discharge head – head on discharge side of pump in absence of flow

Total static head Static suction

lift

Static discharge

head

Page 4: Pumps and Pumping Stations

Pump Jargon

Total static head (both) Static suction

lift

Static discharge

head

Static suction head

Static discharge

head

Static suction head

Static suction lif

Static discharge head

Static d t

Total static h

ischarge he d

ead

a

Note: Suction and discharge head / lift measured from pump centerline

Page 5: Pumps and Pumping Stations

Pump Jargon• (Total) Dynamic head, dynamic suction head or lift, and dynamic

discharge head – same as corresponding static heads, but for a given pumping scenario; includes frictional and minor headlosses

Total dynamic

head

Dynamic suction lift

Dynamic discharge

head

Energy Line

Page 6: Pumps and Pumping Stations

Example. Determine the static head, total dynamic head (TDH), and total headloss in the system shown below.

Total static head 730 ft 630 ft 100 ft

pd =48 psig

ps =6 psig

El = 630 ft

El = 640 ft

El = 730 ft

2.31 ftTDH 48 6 psi 124.7 ft

psi

TDH Static head 124.7 100 ft 24.7 ftLH

Page 7: Pumps and Pumping Stations

Example. A booster pumping station is being designed to transport water from an aqueduct to a water supply reservoir, as shown below. The maximum design flow is 25 mgd (38.68 ft3/s). Determine the required TDH, given the following:• H-W ‘C’ values are 120 on suction side and 145 on discharge side• Minor loss coefficients are

0.50 for pipe entrance0.18 for 45o bend in a 48-in pipe0.30 for 90o bend in a 36-in pipe0.16 and 0.35 for 30-in and 36-in butterfly valves, respectively

• Minor loss for an expansion is 0.25(v22 v1

2)/2g

Short 30 pipe w/30 butterfly valve

El = 6349 to 6357 ft

El = 6127 to 6132 ft

30 to 48 expansion

4000of 48 pipe w/two 45o bends

8500of 36 pipe w/one 90o bend and eight butterfly valves

Page 8: Pumps and Pumping Stations

1. Determine pipeline velocities from v = Q/A..

v30= 7.88 ft/s, v36= 5.47 ft/s, v48= 3.08 ft/s

2. Minor losses, suction side:230

230

2 230 48

2o 48

,minor

Entrance: 0.50 0.49 ft2

Butterfly valve: 0.16 0.16 ft2

Expansion: 0.25 0.21 ft2

Two 45 bends: 2* 0.18 0.05 ft2

0.91 ft

L

L

L

L

L

vh

g

vh

g

v vh

g

vh

g

h

Page 9: Pumps and Pumping Stations

3. Minor losses, discharge side:

236

2o 36

,minor

8 Butterfly valves: 8* 0.35 1.30 ft2

One 90 bend: 0.30 0.14 ft2

1.90 ft

L

L

L

vh

g

vh

g

h

Page 10: Pumps and Pumping Stations

1.85

2.630.43f

Qh L

CD

1.85

, 2.63

38.74000 2.76 ft

0.43 120 48 /12f suctionh

4. Pipe friction losses:

1.85

2.630.43fh Q

SL CD

1.85

, 2.63

38.78500 16.77 ft

0.43 145 36 /12f dischargeh

Page 11: Pumps and Pumping Stations

5. Loss of velocity head at exit:236Exit: 0.46 ft

2L

vh

g

Static head 6357 6127 ft 230 ft

6. Total static head under worst-case scenario (lowest water level in aqueduct, highest in reservoir):

, ,TDH

230 0.91 1.90 2.76 16.77 0.46 ft

252.8 ft

static L minor f L exitH h h h

7. Total dynamic head required:

Page 12: Pumps and Pumping Stations

Pump Power

• P = Power supplied to the pump from the shaft; also called ‘brake power’ (kW or hp)

• Q = Flow (m3/s or ft3/s)• TDH = Total dynamic head = Specific wt. of fluid (9800 N/m3 or 62.4 lb/ft3 at 20oC)• CF = conversion factor: 1000 W/kW for SI, 550 (ft-lb/s)/hp for US• Ep = pump efficiency, dimensionless; accounts only for pump,

not the drive unit (electric motor)

TDH

CF p

QP

E

Useful conversion: 0.746 kW/hp

Page 13: Pumps and Pumping Stations

Example. Water is pumped 10 miles from a lake at elevation 100 ft to a reservoir at 230 ft. What is the monthly power cost at $0.08/kW-hr, assuming continuous pumping and given the following info:

• Diameter D = 48 in; Roughness = 0.003 ft, Efficiency Pe =80%• Flow = 25 mgd = 38.68 ft3/s• T = 60o F• Ignore minor losses

El = 100 ft

10 mi of 48 pipe,

=0.003 ft

El = 230 ft 2

1

21

2

v

g1p

22

1 2pump

vz H

g 2p

2 Lz H

2 1TDHpump stat L fH z z H H h

TDH stat fH h

Page 14: Pumps and Pumping Stations

El = 100 ft

10 mi of 48 pipe,

=0.0003 ft

El = 230 ft 2

1

TDH stat fH h

230 100 ft 130 ftstatH

2

2f

L vh f

D g

/ 3.08 ft/sv Q A

Find f from Moody diagram

65 2

3.08 ft/s 4 ftRe 1.01x10

1.22x10 ft /s

vD

40.003 ft7.5x10

4 ftD

Page 15: Pumps and Pumping Stations

El = 100 ft

10 mi of 48 pipe,

=0.0003 ft

El = 230 ft 2

1

6Re 1.01x1047.5x10

D

0.0185f

Page 16: Pumps and Pumping Stations

2

2

3.08 ft/s10*5280 ft0.0187 36.4 ft

4 ft 2 32.2 ft/sfh

TDH 130 36.4 ft 166.4 ftstat fH h

3 338.68 ft /s 166.4 ft 62.4 lb/ftTDH918 hp

CF ft-lb/s550 0.80

hpp

QP

E

kW $0.08 hrDaily cost 918 hp 0.746 24 $1315 / d

hp kW-hr d

Page 17: Pumps and Pumping Stations

Pump Selection

• System curve – indicates TDH required as a function of Q for the given system– For a given static head, TDH depends only on HL, which is

approximately proportional to v2/2g

– Q is proportion to v, so HL is approximately proportional to Q2 (or Q1.85 if H-W eqn is used to model hf)

– System curve is therefore approximately parabolic

Page 18: Pumps and Pumping Stations

Example. Generate the system curve for the pumping scenario shown below. The pump is close enough to the source reservoir that suction pipe friction can be ignored, but valves, fittings, and other sources of minor losses should be considered. On the discharge side, the 1000 ft of 16-in pipe connects the pump to the receiving reservoir. The flow is fully turbulent with D-W friction factor of 0.02. Coefficients for minor losses are shown below.

40 ft

6 ft

K values

Suction Discharge

1 @ 0.10 1 @ 0.12

1 @ 0.12 1 @ 0.20

1 @ 0.30 1 @ 0.60

2 @ 1.00 4 @ 1.00

Page 19: Pumps and Pumping Stations

The sum of the K values for minor losses is 2.52 on the suction side and 5.52 on the discharge side. The total of minor headlosses is therefore 8.04 v2/2g.

An additional 1.0 v2/2g of velocity head is lost when the water enters the receiving reservoir.

The frictional headloss is: 2 2 21000 ft

0.02 152 1.33 ft 2 2f

L v v vh f

D g g g

Total headloss is therefore (8.04+1.0+15.0)v2/2g = 24.04 v2/2g. v can be written as Q/A, and A = D2/ 4 = 1.40 ft2. The static head is 34 ft. So:

2

22 22

52

TDH 34 ft 24.042

/1.40 ft s34 ft 24.04 34 ft 0.19

ft2 32.2 ft/s

stat L

vH H

g

QQ

Page 20: Pumps and Pumping Stations

22

5

sTDH 34ft 0.19

ftQ

0

20

40

60

80

100

120

140

160

180

0 5 10 15 20 25

Discharge, Q (ft3/s)

TD

H (

ft)

Static head

System curve

Page 21: Pumps and Pumping Stations

Pump Selection

• Pump curve – indicates TDH provided by the pump as a function of Q; – Depends on particular pump; info usually provided by manufacturer– TDH at zero flow is called the ‘shutoff head’

• Pump efficiency– Can be plotted as fcn(Q), along with pump curve, on a single graph– Typically drops fairly rapidly on either side of an optimum; flow at

optimum efficiency known as “normal” or “rated” capacity– Ideally, pump should be chosen so that operating point corresponds

to nearly peak pump efficiency (‘BEP’, best efficiency point)

Page 22: Pumps and Pumping Stations

Shutoff head

Rated capacity

Rated hp

Pump Performance and Efficiency Curves

Page 23: Pumps and Pumping Stations

Pump Selection

Page 24: Pumps and Pumping Stations

Pump Efficiency• Pump curves depend on pump geometry (impeller D) and speed

Page 25: Pumps and Pumping Stations

Pump Selection• At any instant, a system has a single Q and a single TDH, so both

curves must pass through that point; operating point is intersection of system and pump curves

Page 26: Pumps and Pumping Stations

Pump System Curve• System curve may change over time, due to fluctuating reservoir levels,

gradual changes in friction coefficients, or changed valve settings.

Page 27: Pumps and Pumping Stations

Pump Selection: Multiple Pumps• Pumps often used in series or parallel to achieve desired pumping

scenario• In most cases, a backup pump must be provided to meet maximum

flow conditions if one of the operating (‘duty’) pumps is out of service.• Pumps in series have the same Q, so if they are identical, they each

impart the same TDH, and the total TDH is additive• Pumps in parallel must operate against the same TDH, so if they are

identical, they contribute equal Q, and the total Q is additive

Adding a second pump moves the operating point “up” the system curve, but in different ways for series and parallel operation

Page 28: Pumps and Pumping Stations

Example. A pump station is to be designed for an ultimate Q of 1200 gpm at a TDH of 80 ft. At present, it must deliver 750 gpm at 60 ft. Two types of pump are available, with pump curves as shown. Select appropriate pumps and describe the operating strategy. How will the system operate under an interim condition when the requirement is for 600 gpm and 80-ft TDH?

TD

H (

ft)

Flow rate (gpm)

Pump A onlyPump B only

System curve

Eff

icie

ncy

, % Pump B

Pump A

10

100

40

50

30

20

90

80

70

60

0

120

110

200 400 120010008006000

70

60

50

40

Page 29: Pumps and Pumping Stations

Either type of pump can meet current needs (750 gpm at 60 ft); pump B will supply slightly more flow and head than needed, so a valve could be partially closed. Pump B has higher efficiency under these conditions, and so would be preferred.

TD

H (

ft)

Flow rate (gpm)

Pump A onlyPump B only

System curve

Eff

icie

ncy

, % Pump B

Pump A

10

100

40

50

30

20

90

80

70

60

0

120

110

200 400 120010008006000

70

60

50

40

Page 30: Pumps and Pumping Stations

The pump characteristic curve for two type-B pumps in parallel can be drawn by taking the curve for one type-B pump, and doubling Q at each value of TDH. Such a scenario would meet the ultimate need (1200 gpm at 80 ft), as shown below.

TD

H (

ft)

Flow rate (gpm)

A onlyB only Two B’s

System curve

Eff

icie

ncy

, % Pump B

Pump A

10

100

40

50

30

20

90

80

70

60

0

120

110

200 400 120010008006000

70

60

50

40

Page 31: Pumps and Pumping Stations

A pump characteristic curve for one type-A and one type-B pump in parallel can be drawn in the same way. This arrangement would also meet the ultimate demand. Note that the type-B pump provides no flow at TDH>113 ft, so at higher TDH, the composite curve is identical to that for just one type-A pump. (A check valve would prevent reverse flow through pump B.) Again, since type B is more efficient, two type-B pumps would be preferred over one type-A and one type-B.

TD

H (

ft)

Flow rate (gpm)

A onlyB only Two B’s

System curve

Eff

icie

ncy

, % Pump B

Pump A

10

100

40

50

30

20

90

80

70

60

0

120

110

200 400 120010008006000

70

60

50

40

One A and one B in parallel

Page 32: Pumps and Pumping Stations

At the interim conditions, a single type B pump would suffice.

A third type B pump would be required as backup.T

DH

(ft

)

Flow rate (gpm)

A onlyB only Two B’s

System curve

Eff

icie

ncy

, % Pump B

Pump A

10

100

40

50

30

20

90

80

70

60

0

120

110

200 400 120010008006000

70

60

50

40

One A and one B in parallel