puralev 200mu - levitronix · user manual for puralev® 200mu pl-4031-00, rev07, dco# 20-144 3 1...

37
User Manual for PuraLev ® 200MU www.levitronix.com PL-4031-00, Rev07, DCO# 20-144 First Release: 23-Mar-12 Last Update: 09-Jul-2020 PuraLev ® 200MU 2.4 bar (35 psi) 21 liters/min (5.5 gallons/min) USER MANUAL This manual contains information necessary for the safe and proper use of the PuraLev ® 200MU. Included are specifications for the standard configurations of the pump system and instructions regarding its use, installation, operation, adjustment, inspection and maintenance. For special configurations of the pump system refer to accompanying information. If the system must be configured for other parameter settings, then the Levitronix ® Service Software version V2.0.5.0 or higher (with according manual Levitronix Doc.# PL-4046-00) is necessary. Familiarize yourself with the contents of the manual to ensure the safe and effective use of this product. After reading this manual, please store the manual where the personnel responsible for operating the pump system can readily refer to it at any time.

Upload: others

Post on 26-Jan-2021

1 views

Category:

Documents


0 download

TRANSCRIPT

  • User Manual for PuraLev® 200MU

    www.levitronix.com

    PL-4031-00, Rev07, DCO# 20-144 First Release: 23-Mar-12 Last Update: 09-Jul-2020

    PuraLev® 200MU 2.4 bar (35 psi) 21 liters/min (5.5 gallons/min)

    USER MANUAL

    This manual contains information necessary for the safe and proper use of the PuraLev® 200MU. Included are specifications for the standard configurations of the pump system and instructions regarding its use, installation, operation, adjustment, inspection and maintenance. For special configurations of the pump system refer to accompanying information. If the system must be configured for other parameter settings, then the Levitronix® Service

    Software version V2.0.5.0 or higher (with according manual Levitronix Doc.# PL-4046-00) is necessary. Familiarize yourself with the contents of the manual to ensure the safe and effective use of this product. After reading this manual, please store the manual where the personnel responsible for operating the pump system can readily refer to it at any time.

  • User Manual for PuraLev® 200MU www.levitronix.com

    PL-4031-00, Rev07, DCO# 20-144 2

    Table of Contents

    1 SAFETY PRECAUTIONS ............................................................................................................................................................... 3

    2 SPECIFICATIONS .......................................................................................................................................................................... 4 2.1 Specification of Components ................................................................................................................................................. 4 2.2 System Overview and General Specification ......................................................................................................................... 6 2.3 General Environmental Conditions ........................................................................................................................................ 7 2.4 Pressure-Flow Curves ........................................................................................................................................................... 8 2.5 Maximum Static Pressure for Pump Heads ........................................................................................................................... 8 2.6 Basic Dimensions of Main Components ................................................................................................................................ 9

    3 ENGINEERING INFORMATION ................................................................................................................................................... 11 3.1 Sealing and Material Concept ............................................................................................................................................. 11 3.2 Power Consumption ............................................................................................................................................................ 12 3.3 Temperature Monitoring ...................................................................................................................................................... 12 3.4 Thermal Management ......................................................................................................................................................... 13 3.5 Hydraulic Circuit Design ...................................................................................................................................................... 16

    4 INSTALLATION ........................................................................................................................................................................... 17 4.1 Electrical Installation of Controller ....................................................................................................................................... 17 4.2 Mechanical Installation of the Pump/Motor .......................................................................................................................... 23 4.3 Mechanical Installation of Motors in ATEX Zone 2 Areas .................................................................................................... 23 4.4 Mechanical Installation of the Controller .............................................................................................................................. 23 4.5 Mechanical Installation of Adaptor/Extension Cables .......................................................................................................... 24

    5 OPERATION ................................................................................................................................................................................ 25 5.1 System Operation with Controller LPC-200.1-02 (Stand-Alone) .......................................................................................... 25 5.2 System Operation with Controller LPC-200.2-02 (Extended PLC) ....................................................................................... 28 5.3 System Operation for ATEX / IECEx Applications ............................................................................................................... 30

    6 INSTRUCTION FOR USE OF PUMP HEAD ................................................................................................................................. 31 6.1 Description and Preparation ................................................................................................................................................ 31 6.2 General Warnings and Cautions ......................................................................................................................................... 31 6.3 Replacement of Pump Head ............................................................................................................................................... 31 6.4 Re-Assembling of Pump Head ............................................................................................................................................ 32 6.5 Assembly into a Circuit ........................................................................................................................................................ 32 6.6 Maintenance ....................................................................................................................................................................... 32 6.7 Precautions for Autoclaving and SIP (Steam-In-Place) ........................................................................................................ 33

    7 TROUBLESHOOTING ................................................................................................................................................................. 34 7.1 Troubleshooting for Operation with Controller LPC-200.1-02............................................................................................... 34 7.2 Troubleshooting for Operation with Controller LPC-200.2-02............................................................................................... 34 7.3 Troubleshooting with Levitronix® Service Software .............................................................................................................. 34

    8 TECHNICAL SUPPORT ............................................................................................................................................................... 34

    9 APPENDIX ................................................................................................................................................................................... 35 9.1 Regulatory Status ............................................................................................................................................................... 35 9.2 Symbols and Signal Words ................................................................................................................................................. 37

  • User Manual for PuraLev® 200MU www.levitronix.com

    PL-4031-00, Rev07, DCO# 20-144 3

    1 Safety Precautions The PuraLev® 200MU pump system is designed to be used in industrial production machines and equipment containing hydraulic circuits. Typical applications are Pharmaceutical manufacturing equipment. Installation shall be done by qualified personnel only. Following safety precautions and all “CAUTION”, “WARNING” and “DANGER” indications in the relevant sections shall be followed.

    CAUTION Do not under any circumstances open the controller or motor. Levitronix® does

    not assume responsibility for any damage, which occurs under such circumstances.

    CAUTION

    High magnetic field strength of pump impeller.

    The pump system contains a rotor magnet with high field strength. This may alter or damage the calibration of sensitive electronic devices and measuring instruments in the immediate surroundings. Keep at a safe distance from computers, monitors and all magnetic data storage media (e.g. disks, credit cards, audio and video tapes etc.)

    ! WARNING

    Hazardous voltage may be present.

    In case of the usage of an inadequate AC/DC power supply, mains voltages may be present (even if the system is designed for up to 24-48VDC). The usage of a galvanic separated power supply, which is certified by a 3rd party (UL or CE), is highly recommended.

    The controller must be grounded and placed in a spill protected electrical cabinet. Do not under any circumstances open the powered controller. The usage of galvanic separated AC/DC supply is highly recommended.

    ! WARNING

    High magnetic field strength of pump impeller.

    The pump system contains a rotor magnet with high field strength. Pacemakers may be influenced and magnetic forces may lead to contusions. Keep distance to pacemakers and handle impeller with care.

    ! WARNING

    TOXIC CHEMICALS may be present.

    When using the system to pump chemicals, skin contact and toxic gases may be hazardous to your health. Wear safety gloves and other appropriate safety equipment.

    ! WARNING

    Motors for ATEX / IECEx applications: only specific types of motors BSM-1.x are classified for the use in ATEX Zone 2 classified locations. Refer to the corresponding section in the manual.

  • User Manual for PuraLev® 200MU www.levitronix.com

    PL-4031-00, Rev07, DCO# 20-144 4

    2 Specifications

    2.1 Specification of Components Figure 1 shows the main system components (motor, controller and pump head) and Figure 2 illustrates the accessories for the pump system.

    Figure 1: Pump system with standard components

    Figure 2: Accessories

    3a

    1a

    2a

    2b

    3b 1b

    7a

    7f

    7c

    7b

    7d

    7e

    8

    5

    6

    4 9

  • User Manual for PuraLev® 200MU www.levitronix.com

    PL-4031-00, Rev07, DCO# 20-144 5

    Pump System Name Article # Pump head Motor Controller Note

    PuraLev 200MU.26 100-90865 LPP-200.17 (with drain port)

    BSM-1.4

    LPC-200.1-02

    Direct cabling between motor and controller PuraLev 200MU.27 100-90866 LPC-200.2-02

    PuraLev 200MU.29 100-90868 LPP-200.16 (without drain port)

    LPC-200.1-02

    PuraLev 200MU.30 100-90869 LPC-200.2-02

    PuraLev 200MU.32 (ATEX/IECEx) 100-90871 LPP-200.17 (with drain port)

    BSM-1.6 (ATEX/IECEx)

    LPC-200.1-02 Adaptor/Extension (0.5 - 10m) cables according to Table 3 (Position 5a and 5b) have to be ordered as separate article with specified length. Ex Cable Sealing System can be ordered according to Table 4.

    PuraLev 200MU.33 (ATEX/IECEx) 100-90872 LPC-200.2-02

    PuraLev 200MU.35 (ATEX/IECEx) 100-90874 LPP-200.16 (without drain port)

    LPC-200.1-02

    PuraLev 200MU.36 (ATEX/IECEx) 100-90875 LPC-200.2-02

    Table 1: Standard system configurations

    Pos. Component Article Name Article # Characteristics Value / Feature

    1a

    1b

    Pump Head

    LPP-200.17 (with drain port)

    LPP-200.16 (without drain port)

    100-90864

    100-90863

    Impeller / Pump Housing Sealing Ring Fittings

    PFA / PVDF (FDA, USP-VI, Animal/BSE/TSE free) EPDM (FDA, USP-VI, Animal/BSE/TSE free)

    Triclamp ½” for in/outlet, Triclamp ½“ for drain port (BS-4825-3)

    Max. Flow Max. Diff.-Pressure Max. Viscosity

    21 liters/min / 55 gallons/min 2.4 bar / 35 psi < 20 cP

    Wet Pump Volume/Surface 25 ml / 158 cm2 (without drain port)

    Max. Liquid Temp. 900C / 1940F

    Possible Sterilization Methods CIP, SIP, Autoclaving

    2a Motor BSM-1.4 100-10005 Housing

    - ETFE (chemical resistant) coated Aluminum - waterproofed (IP67)

    Cable / Connectors 1x 5m cables with FEP jacket / 1x D-SUB (direct cable to controller)

    2b Motor (ATEX / IECEx)

    BSM-1.6 100-10063

    Cable / Connectors 1x 2m cable with FEP jacket / 1x circular (M23, IP-67) (needs extension adaptor cable for connection to controller)

    ATEX / IECEx Marking II 3G Ex nA IIC T5 Gc

    II 3D Ex tc IIIC T100°C Dc

    3a

    Standalone Controller (User Panel)

    LPC-200.1-02 100-30030 (Enable connector included)

    Voltage / Electrical Power 200 W / 24-48 VDC

    Housing Protection IP20

    Interfaces for Standalone Controller

    Panel to set speed (automatic storage on internal EEPROM)

    PLC with 1x analog input (“Speed”) 4 - 20 mA 1x digital input (“Enable”) 0 - 24 V (optocoupler) 1x digital output (“Status”) 0 - 24 V (relais)

    Standard Firmware C9.25

    3b

    Extended Controller (PLC and USB)

    LPC-200.2-02 100-30031 (PLC connector included )

    Interfaces for Extended Controller

    PLC with

    - up to 4 digital inputs 0 - 24V (optocoupler) - up to 4 digital outputs 0 - 24 V (relais) - up to 2 analog inputs 4 - 20mA - up to 2 analog inputs 0 – 10 V - up to 2 analog outputs 0 – 5 V

    USB interface (for service and system monitoring)

    Standard Firmware C9.48

    Table 2: Specification of standard components

    Pos. Component Article Name Article # Characteristics Value / Feature

    4 Extension Adaptor Cable for Power

    MCA-1.5-05 (0.5m) MCA-1.5-30 (3m) MCA-1.5-50 (5m) MCA-1.5-70 (7m) MCA-1.5-100 (10m)

    190-10225 190-10231 190-10199 190-10232 190-10233

    Jacket Material Connectors

    PVC-jacket Wallmountable circular Hummel to D-SUB connector

    Table 3: Specification of adaptor/extension cables

    Pos. Component Article Name Article # Characteristics Value / Feature

    5 Air Cooling Module ACM-1.1 190-10003 Material / Connection Port PVDF / NPT ¼”

    Air Pressure / Consumption ~ 0.5bar (7.2 psi)

    6 Mounting Base Plate MBP-1.1 190-10004 Material PVDF

    7 (a-f)

    ATEX Cable Sealing System

    ACS-A.1 100-90292 Sleeve (a) / Gasket (b) Frame (c) Cable Module (d)

    Stainless Steel and EPDM Roxylon (EPDM rubber) Roxylon (EPDM rubber)

    Note: Lubricant (e) and measurement plates (f) are included.

    8a AC/DC Power Supply

    TSP 360-124 (Standard Traco Supply) 100-40016

    Voltage / Power Output / Voltage Input Dimensions Certifications

    24 VDC / 360 W 85 – 132 / 187 – 264 VAC, autoselect 125 x 125 x 80 mm UL, CSA, CB, Semi F47

    8b AC/DC Supply TSP 360-148 100-40017 Voltage / Power Output 48 VDC / 360 W

    9 Autoclaving Reinforcing Tool

    ART-200.1 190-10280 Purpose Material Mounting Screws

    Stabilization of pump housing during autoclaving. Anodized Aluminum 4 pcs M3 x 14 mm (Stainless steel)

    Table 4: Specification of accessories

  • User Manual for PuraLev® 200MU www.levitronix.com

    PL-4031-00, Rev07, DCO# 20-144 6

    2.2 System Overview and General Specification

    2.2.1 Stand-Alone System Configuration

    The stand-alone pump system configuration (Figure 3), consists of a controller with an integrated user panel to set the speed manually. The speed is automatically stored in the internal EEPROM of the controller. As an option, the speed can also be set with an analogue signal.

    Figure 3: Standard system configuration for standalone operation (Speed setting with integrated user panel)

    2.2.2 Extended System Configuration

    The extended version of the pump system (Figure 4) consists of a controller with an extended PLC interface.

    This allows setting the speed by an external signal and enables precise closed-loop flow or pressure control

    in connection with either a flow or a pressure sensor. A USB interface allows communication with a PC in

    connection with the Levitronix® Service Software. Hence parameterization, firmware updates and failure

    analysis are possible.

    Figure 4: Standard system configuration for extended operation (Pressure or flow control with external sensor)

    Chemical Resistance and IP67 Space

    Motor

    Pump Head

    Fluid In

    Fluid Out

    Motor Cable

    Adaptor/Extension Power Supply24-48 VDC

    200 W

    Controller

    for

    Standalone

    OperationStand AloneOperation

    Speed Control

    PLC Interface

    Speed Setting- 1x Digital Input (Enable)

    - 1x Digital Output (Status)

    - 1x Analog Input (Speed)

    Drain Port

    Chemical Resistance and IP67 Space

    Motor

    Pump Head

    Fluid In

    Fluid Out

    Motor Cable

    USB

    - Service

    - Firmware Update

    - Configuration etc.

    Flow- or

    Pressure

    Sensor

    Adaptor/Extension Cable

    Extended PLC Interface

    Speed, Flow

    or Pressure Setting- 4 Digital Inputs

    - 4 Digital Outputs

    - 4 Analoge Inputs

    - 2 Analoge Outputs

    Power Supply

    24-48 VDC / 200 W

    Controller

    for

    Extended

    Operation

    Drain Port

    Motor option with direct cabling to controller

    Motor option with Direct cabling to controller

    Pump head option without drain port

    1b

    Pump head option without drain port

    1a

    4

    3a

    2b

    2a

    1b

    1a

    4

    3b

    2a

    2b

  • User Manual for PuraLev® 200MU www.levitronix.com

    PL-4031-00, Rev07, DCO# 20-144 7

    2.2.3 ATEX / IECEx System Configuration

    Together with the standard pump-head and controllers an ATEX / IECEx certified motor allows installation of motor and pump head within an ATEX Zone 2 area (see Figure 5). The ATEX / IECEx motor (Pos. 2c in Table 2) comes delivered with special connectors and according extension cables (see Table 3). One option to lead the cables outside of the Ex area is an Ex certified cable sealing system as listed in Table 4.

    Figure 5: System configuration for ATEX / IECEx applications

    2.3 General Environmental Conditions

    Usage Indoor 1

    Altitude Up to 2000 m

    Operating ambient temperature 0 to 40 0C

    Storage ambient temperature (Extremes for Transportation)

    -20 to 80 0C

    Operating humidity range (relative humidity) 15 – 95% (non-condensing)

    Storage humidity range (relative humidity) (Extremes for Transportation)

    15 – 95% (non-condensing)

    Normal storage conditions Ambient temp.: 20 to 30 0C Relative humidity: 50% (non-condensing)

    DC supply fluctuations 10% of nominal voltage

    Transient over-voltages typically present on the mains supply

    Surge immunity according to EN 61000-4-5 (tested together with certified AC/DC power supply)

    Pollution degree 2

    Table 5: Environmental conditions for pump system Note 1: Contact Levitronix® technical department (see Section 8) for outdoor usage.

    Pump Head

    Fluid In

    Fluid Out

    Motor Power Cable

    Adaptor/Extension Cable Power Supply24-48 VDC / 200 W

    All

    Controller

    Types

    ATEX conform cable sealing system

    Cabinet Boundary for

    ATEX Zone 2 Area

    ATEX Zone 2 Classified Location

    Chemical Resistance and IP-67 Space

    Drain Port

    ATEX Motor

    Pump head option without drain port

    1b

    1a

    4

    3

    2b

    7

  • User Manual for PuraLev® 200MU www.levitronix.com

    PL-4031-00, Rev07, DCO# 20-144 8

    2.4 Pressure-Flow Curves

    Figure 6: Pressure/flow rate curves (Measured with pump head LPP-200.16 but representative for LPP-200.17)

    2.5 Maximum Static Pressure for Pump Heads

    Figure 7: Specification for maximum static pressure of pump head LPP-200.16/17 (Pressure limits only valid for pump head mounted on motor)

    0

    10

    20

    30

    0.0 1.0 2.0 3.0 4.0 5.0

    0.0

    0.5

    1.0

    1.5

    2.0

    2.5

    0.0 2.5 5.0 7.5 10.0 12.5 15.0 17.5 20.0 22.5

    [psi]

    [gallons/min]

    [bar]

    [liters/min]

    Specific gravity = 1 g/cm3

    Viscosity = 0.7 cPLiquid Temp.: 40C

    8000 rpm

    7000 rpm

    6000 rpm

    5000 rpm

    Speed Limit for 24V ≈ 9500 rpmSpeed Limit for 48V = 10000 rpm

    9000 rpm

    10000 rpm

    Supply Voltage: 48 VDC

    Supply Voltage: 24 VDC

    0

    20

    40

    60

    80

    100

    120

    140

    77 87 97 107 117 127 137 147 157 167 177 187

    0

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    25 30 35 40 45 50 55 60 65 70 75 80 85 90

    [psi]

    [°F]

    [bar]

    Liquid Temperature in [°C]

    Max. Static Pressure for LPP-200.5/6/12/14

    Safety Factor = 1.3 (according to EN12162)Limitation: Given by deformation. Burst pressure is significantly higherAmbient Temp = 25 C Note: Pressure limit only valid for pumphead mounted on motor

  • User Manual for PuraLev® 200MU www.levitronix.com

    PL-4031-00, Rev07, DCO# 20-144 9

    2.6 Basic Dimensions of Main Components

    Figure 8: Basic dimensions (in mm and [inch]) of motor BSM-1.x with pump head LPP-200.17 (for other configurations refer to according drawings)

    6pcs M4x15 Screws (INOX A4)

    4pcs M3x14 Screws (INOX A4) (For Pump Head Motor Mounting)

    Drain Port 1/2“ Triclamp

    9.5mm BS-4825-3

    Outlet 1/2“ Triclamp 9.5mm BS-4825-3

    Inlet 1/2“ Triclamp

    9.5mm BS-4825-3

  • User Manual for PuraLev® 200MU www.levitronix.com

    PL-4031-00, Rev07, DCO# 20-144 10

    Cable Jacket

    Cable OD Motor Sensor

    Minimum Bending Radius Permanent Installation

    Minimum Bending Radius Sometimes Moved

    FEP 8.50 mm 7x Cable OD 15 x Cable OD

    PVC 9.50 mm 5x Cable OD 11 x Cable OD

    Table 6: Specifications for min. bending radius of motor and adaptor cables for BSM-1 Note: If not mentioned explicitly all the cables are not suited for constant dynamic bending and movement!

    Figure 9: Basic dimensions (in mm) of controller LPC-200.2-02 (Same basic dimensions for LPC-200.1-02)

    Alternative for mounting DIN rail clips

  • User Manual for PuraLev® 200MU www.levitronix.com

    PL-4031-00, Rev07, DCO# 20-144 11

    3 Engineering Information

    3.1 Sealing and Material Concept

    Figure 10: Sealing and material concept (Motor BSM-1.x with pump head LPP-200.17)

    System Component

    Item Materials

    No Description

    Pump Head LPP-200.16/17

    1 Pump housing (lid and bottom) PVDF

    2 Static triclamp sealing O-ring of pump casing EPDM

    3 6x M4x15mm screws for pump casing Stainless Steel (INOX A4)

    4 Impeller LPI-200.5 PFA

    5 Rotor magnet Rare-earth material

    6 4 M3x14mm screws for pump/motor mounting Stainless Steel (INOX A4)

    Motors BSM-1.3 BSM-1.6

    7 Sealing O-ring for motor housing FPM (= FKM)

    8 Cable bushing FPM, cable jacket is FEP

    9 Motor housing ETFE coating, waterproof (IP-67) Coils and electromagnetic circuit potted with an epoxy compound (UL94 V0).

    Table 7: Materials used in the BSM-1.x motors and LPP-200.16/17 pump heads (For other configurations refer to according specifications and drawings)

    3

    2

    1

    4

    5

    6

    8

    9

    7

  • User Manual for PuraLev® 200MU www.levitronix.com

    PL-4031-00, Rev07, DCO# 20-144 12

    3.2 Power Consumption Figure 11 shows the typical power consumption of the system. If other AC/DC power supplies than the standard specified ones are used, it is recommended to evaluate them under demanding operating situations like fast braking from maximum speed and during power on and take-off of the impeller.

    Figure 11: Electrical power consumption (Controller LPC-200.x, pump head LPP-200.16 and motor BSM-1.x. Representative for pump head LPP-200.17.)

    3.3 Temperature Monitoring To avoid overheating of the system, the controller and motor temperatures are monitored. If the controller temperature exceeds 70°C (158°F) or the motor temperature 90°C (194°F) for a duration of more than 10 minutes, the system goes into an error state and the pump stops. At 80°C (176 F) controller temperature or 100°C (212°F) motor temperature, the system stops immediately.

    Start Temperature

    Monitoring

    WARNING YES Temperature > 70°C ?

    Temperature > 80°C ?

    YES

    YES ERROR

    Temperature higher than 70°C for more than 10

    minutes?

    NO

    ERROR YES

    NO

    NO

    Start Temperature

    Monitoring

    WARNING YES Temperature > 90°C ?

    Temperature > 100°C ?

    YES

    YES ERROR

    Temperature higher than 90°C for more than 10

    minutes?

    NO

    ERROR YES

    NO

    NO

    Figure 12: Controller temp. monitoring Figure 13: Motor temperature monitoring

    0.0 1.0 2.0 3.0 4.0 5.0

    0

    25

    50

    75

    100

    125

    150

    175

    200

    0.0 2.5 5.0 7.5 10.0 12.5 15.0 17.5 20.0 22.5

    [gallons/min]

    [Watts]

    [liters/min]

    Specific gravity = 1 g/cm3

    Viscosity = ~ 0.7 cPLiquid Temp.: 40 C

    8000 rpm

    7000 rpm

    6000 rpm

    9000 rpm10000 rpm

    5000 rpm

    ---- 48 VDC Supply24 VDC Supply

  • User Manual for PuraLev® 200MU www.levitronix.com

    PL-4031-00, Rev07, DCO# 20-144 13

    3.4 Thermal Management

    3.4.1 Motor Temperature

    The motor temperature depends on the ambient and liquid temperature, as well as on the hydraulic operation point. Figure 14, Figure 15 and Figure 17 illustrate the temperature characteristics of the motor depending on these parameters. For higher liquid temperatures and hydraulic operating points active cooling is recommended for example with the air cooling module ACM-1.1 (see Figure 16).

    Figure 14: Temperature curves for the BSM-1.x motor @ 25 C liquid temperature (Pump head LPP-200.16 and representative for LPP-200.17, temperature measured inside of the motor, contact temp. of surface is below this temp.)

    Figure 15: Temperature curves for the BSM-1.x motor @ 70 C liquid temperature (Pump head LPP-200.16 and representative for LPP-200.17, temperature is measured inside of the motor, contact temp. is below this temp.)

    77

    97

    117

    137

    157

    177

    197

    0.0 1.0 2.0 3.0 4.0 5.0

    25

    35

    45

    55

    65

    75

    85

    95

    0.0 2.5 5.0 7.5 10.0 12.5 15.0 17.5 20.0 22.5

    [F]

    [gallons/min]

    [°C]

    [liters/min]

    Ambient Temp = 25 C Liquid Temp. = 25 CViscosity = 0.7 cP

    10000 rpm9000 rpm

    8000 rpm

    7000 rpm

    6000 rpm

    Absolute Temperature Limit

    Recommended Operational Limit

    ---- 48 VDC Supply24 VDC Supply

    77

    97

    117

    137

    157

    177

    197

    0.0 1.0 2.0 3.0 4.0 5.0

    25

    35

    45

    55

    65

    75

    85

    95

    0.0 2.5 5.0 7.5 10.0 12.5 15.0 17.5 20.0 22.5

    [F]

    [gallons/min]

    [°C]

    [liters/min]

    Ambient Temp = 25 C Liquid Temp. = 70 CViscosity = 0.7 cP

    ---- 48 VDC Supply24 VDC Supply

    4000 rpm

    9000 rpm 7000 rpm

    6000 rpm

    5000 rpm

    8000 rpmAbsolute Temperature Limit

    Recommended Operational Limit

  • User Manual for PuraLev® 200MU www.levitronix.com

    PL-4031-00, Rev07, DCO# 20-144 14

    Figure 16: Temperature curves of motor BSM-1.x with air cooling module ACM-1.1 (Pump head LPP-200.6 and representative for LPP-200.12/14, liquid. temp = 90 0C, Air Cooling Module ACM-1.1 with 0.5 bar air at 20 0C)

    Figure 17: Influence of liquid temperature on motor temperature (Measurement at 7000 rpm 11 lpm but gradients are representative for other operational points)

    The above curves are measurements of the motor temperature at certain liquid and ambient temperatures. Equation (Eq. 1) shows how to calculate the motor temperature for other liquid and ambient temperatures based on these curves.

    77

    97

    117

    137

    157

    177

    197

    0.0 1.0 2.0 3.0 4.0 5.0

    25

    35

    45

    55

    65

    75

    85

    95

    0.0 2.5 5.0 7.5 10.0 12.5 15.0 17.5 20.0 22.5

    [F]

    [gallons/min]

    [°C]

    [liters/min]

    Ambient Temp = 25 C Liquid Temp. = 90 CViscosity = 0.7 cP

    Air cooling with ACM-1.10.5 bar, ~20 C air

    Absolute Temperature Limit

    Recommended Operational Limit

    ---- 48 VDC Supply24 VDC Supply

    10000 rpm 9000 rpm

    6000 rpm

    7000 rpm

    8000 rpm

    y = 0.49x + 41.731

    y = 0.28x + 26.05

    77

    97

    117

    137

    157

    177

    197

    77 87 97 107 117 127 137 147 157 167 177 187

    25

    35

    45

    55

    65

    75

    85

    95

    25 30 35 40 45 50 55 60 65 70 75 80 85 90

    [F]

    [F]

    [°C]

    Liquid Temperature in [°C]

    Ambient Temp = 25 C Specific gravity = 1 g/cm³ Viscosity = 0.7 cP

    No Active Cooling:Temperature Gradiant = 0.49(Liquid vs. Motor Temperature)

    Active Cooling with ACM-1.1 (0.5 bar @ 20 C):Temperature Gradiant = 0.28(Liquid vs. Motor Temperature)

    Absolute Temperature Limit

  • User Manual for PuraLev® 200MU www.levitronix.com

    PL-4031-00, Rev07, DCO# 20-144 15

    orliquid/mot gradient eTemperaturtgetemperatur AmbientT

    etemperatur LiquidTetemperatur MotorT

    CTtgCTCTCTTTTT

    LMA

    LM

    ALMLALMALM

    17 Figure see14 Figure see

    ==

    ==

    −+−+== )25()25()25,25(),( 0000

    (Eq. 1)

    All above presented thermal data are typical values, which are partly based on measurements and partly on interpolations with a simplified thermal model and are therefore only guideline values and are suitable for a first layout of the basic thermal concept. It is recommended to check the thermal values with the motor placed on the final location and under worst case performance conditions of the application.

    In order to account for thermal variations (like ambient temperature, closed chemical cabinets or corners without ventilations) and to not significantly reduce the MTBF of the motor it is recommended to keep about 20 0C safety distance to the absolute thermal limit of the motor (90 0C) when designing the thermal concept of the pump system.

    3.4.2 Controller Temperature

    Depending on the ambient temperature and the placement of the controller additional cooling may be required (see Figure 18). To improve cooling of the controller, place the device into a moving air stream. If the controller is mounted in a compact area or adjacent to additional heat sources (e.g. a 2nd controller) ensure that there is sufficient ventilation.

    Figure 18: Temperature curves of controller LPC-200 vs. flow and speed (For pump head LPP-200.6 and motor BSM-1.x. Representative for LPP-200.12/14.)

    The above curves are measurements of the controller temperature at 250C ambient. Equation (Eq. 2) shows how to calculate the controller temperature for at other ambient temperatures based on this curve.

    etemperatur AmbientT

    etemperatur ControllerTCTCTTTT

    A

    C

    AACAC

    18 Figure see=

    =−+= )25()25()( 00

    (Eq. 2)

    77

    97

    117

    137

    157

    0.0 1.0 2.0 3.0 4.0 5.0

    25

    35

    45

    55

    65

    75

    0.0 2.5 5.0 7.5 10.0 12.5 15.0 17.5 20.0 22.5

    [F]

    [gallons/min]

    [°C]

    [liters/min]

    Ambient temp. = 25 C Specific gravity = 1 g/cm3

    Viscosity = 0.7 cP

    Absolute Temperature Limit

    10000 rpm9000 rpm

    6000 rpm

    7000 rpm

    8000 rpm

    8000 rpm

    9000 rpm

    ---- 48 VDC Supply24 VDC Supply

  • User Manual for PuraLev® 200MU www.levitronix.com

    PL-4031-00, Rev07, DCO# 20-144 16

    3.5 Hydraulic Circuit Design

    Following general design rules help to operate the pump system optimally considering efficiency, optimum priming behavior and low shear forces:

    1. The general rule for minimum shear forces and optimum priming behavior is to minimize the pressure drop in the inlet circuit and avoid negative pressure at the inlet of the pump head.

    2. Minimize tubing length at the inlet of the pump head and maximize the ID (not smaller than the pump head inlet ID of 9.5 mm is recommended). This reduces the pressure drop and the tendency of cavitation.

    3. Avoid any restrictions, valves, elbows, bended tubing and sharp edges at the inlet circuit of the pump head, which potentially causes cavitation resulting in higher shear forces and bubble collection in the pump head with the danger of priming loss.

    4. Choose correctly aligned sealing rings and fitting adaptors to connect tubing to the in- and outlet of the pump head. Consult the dimension drawings of the sealing ring and fitting adaptor manufacturer and check with the in- and outlet ID shown in Figure 8. Miss-aligned sealing rings and fittings can be the cause of increased shear forces and cavitation effects.

    5. Place the pump at the lowest point of the hydraulic circuit. Optimum is as much as possible below a tank or reservoir. This optimizes priming behavior and keeps the inlet pressure positive for low shear forces.

    6. Keep the liquid level in the reservoir tank or bag as high as possible, which increases the inlet pressure of the pump head and minimized heat up of the liquid.

    7. In general the pump system placement and hydraulic circuit shall be designed that gas bubbles can leave the pump housing and that the pump head remains primed.

    8. To minimize heat up of the liquid the overall pressure drop in the hydraulic circuit shall be reduced as much as possible.

    9. It shall be avoided to pump longer times against a closed valve, which can cause heat-up of the liquid and higher shear forces.

    10. At flows < 1 l/min it is recommended to use a bypass loop to assure that sufficient flow runs through the pump head to wash-out gas bubbles and avoid heat stagnation.

    11. At higher liquid temperature the rules mentioned above become more important due to higher cavitation tendency of the liquid.

    12. As the pump heads and the fittings are made out of plastics the usage of 3-part clamps instead of 2-part clamps (see Figure 19) for in- and outlet connection is recommended to prevent asymmetric stress during high temperature treatments like SIP (steam in place) or autoclaving causing sealing and leakage issues.

    Figure 19: 3-part clamps versus 2-parts

    13. Load and stress at the inlet and outlet by heavy tubing and inproper mounting alignment shall be avoided (see Figure 20) as this can cause leakage issues due to distortion of the plastic pump housing.

    Figure 20: Avoidance of stress forces and torques at the inlet and outlet of the pump head

    Contact the Levitronix® Technical Service department (see Section 8) for more detailed considerations and support on the design of the hydraulic circuit.

    Recommended Can cause assymetric stress with sealing issues

    Tubing fixation/support to avoid load at in- and outlet of pump system.

    Pump Heavy tubing at

    in- and outlet of pump

    Force/torque stress at the in- and outlet of the pump housing!

  • User Manual for PuraLev® 200MU www.levitronix.com

    PL-4031-00, Rev07, DCO# 20-144 17

    4 Installation 4.1 Electrical Installation of Controller

    4.1.1 Overview

    The LPC-200 controllers have signal processor controlled power converters with switched inverters for the drive and the bearing windings of the motor. The signal processor allows precise control of pump speed and impeller position. Figure 21 shows the interfaces of the standalone controller LPC-200.1 with stand-alone and minimal PLC functions and Figure 22 the interfaces of the LPC-200.2 controller with extended PLC functions and USB interface for communication.

    Figure 21: Overview of the controller LPC-200.1-02 for standalone operation

    Interface (as labeled) Description

    1 “MOTOR” - Position, field and temperature sensor signals from motor - Drive and bearing currents of the motor

    Torque spec. for tightening of connector screws: Min. = 0.4 Nm, Max. = 0.6 Nm

    2 “USER INTERFACE”

    1 Digital Input

    - Galvanic isolation with optocoupler

    - Lowest input voltage for high level detection: min. 5 V Typical 24 V / 16 mA, maximal 30 V / 20 mA

    - Highest input voltage for low level detection: max. 0.8 V

    - Minimum input resistance: RIN = 2.2 k

    1 Digital Output - Galvanic isolation with relay - Relay: 1A / 30VDC, 0.3A / 125 VAC

    1 Analog Input - Analog current input: 4 – 20 mA - 450 Ohm shunt input

    3 “POWER INPUT” DC power input -> 24V or 48V

    4 “Power on” Green LED LED is on if supply voltage of signal electronics is present.

    5 “Power Output off” Red LED

    Red LED is off if the switched output stage of the controller is enabled. If the LED is on, the bearing and drive coils of the motor carry no current.

    6 “RESET” Button Reset button of the controller stage. The button is sunk mounted and can be activated for example with a small screw driver.

    7 2-Digit Display “Speed” Rotational speed display in 100rpm

    8 “UP” Button Button for speed increasing and enabling of levitation

    9 “DOWN” Button Button for speed decreasing and disabling of levitation

    10 “Firmware” Label Firmware version and revision number

    Table 8: Description of interfaces of LPC-200.1-02 controller

    1

    2

    3

    4

    6

    7

    8

    9

    5

    10

  • User Manual for PuraLev® 200MU www.levitronix.com

    PL-4031-00, Rev07, DCO# 20-144 18

    Figure 22: Overview of the controller LPC-200.2-02 for extended operation

    Interface (as labeled) Description

    1 “MOTOR”

    - Position, field and temperature sensor signals from motor - Drive and bearing currents of the motor

    Torque spec. for tightening of connector screws: Min. = 0.4 Nm, Max. = 0.6 Nm

    2 “USER INTERFACE”

    2 Analog Input - Analog current input: 4 – 20 mA - 450 Ohm shunt input

    2 Analog Input

    - Analog voltage input 0 – 10 V

    - Direct connection, no galvanic isolation

    - 7.8 k input resistance

    2 Analog Output

    - Analog voltage output: 0 – 5 V

    - Direct connection, no galvanic isolation

    - Max. output current: 2mA

    4 Digital Input

    - Galvanic isolation with optocoupler

    - Lowest input voltage for high level detection: min. 5 V Typical 24 V / 16 mA, maximal 30 V / 20 mA

    - Highest input voltage for low level detection: max. 0.8 V

    - Minimum input resistance: RIN = 2.2 k

    4 Digital Output - Galvanic isolation with relay

    - Relay: 1A / 30VDC, 0.3A / 125 VAC

    3 “USB” USB interface

    4 “POWER INPUT” DC power input -> 24V or 48V

    5 “Power on” Green LED LED is on if supply voltage of signal electronics is present.

    6 “Power Output off” Red LED LED is off if the switched output stage of the controller is enabled. If the LED is on, the bearing and drive coils of the motor carry no current.

    7 “RESET” Button Reset button of the controller stage

    Table 9: Description of interfaces of LPC-200.2-02 controller

    1

    2 3

    4

    6

    7

    5

  • User Manual for PuraLev® 200MU www.levitronix.com

    PL-4031-00, Rev07, DCO# 20-144 19

    4.1.2 General Installation Instructions

    ! WARNING

    Hazardous voltage may be present.

    Always isolate the electrical power supply before making or changing connections to the unit.

    In case of the usage of an inadequate AC/DC power supply, mains voltages may be present (even if the system is designed for 24 - 48VDC). The usage of a galvanic separated power supply, which is certified by a 3rd party (UL or CE), is highly recommended.

    ! WARNING

    Hazardous voltage may be present.

    The controller housing must be properly grounded and placed in a spill protected electrical cabinet. Use one of the DIN-rail screws on the back side of the controller housing.

    Do not use different and longer screws, which may result in short-circuit within the controller.

    1. The controller casing must be grounded. The screws of the DIN-rail brackets can be used for grounding (see Figure 23).

    2. Connect the motor connector to the controller.

    3. Connect the controller type specific connectors: see Section 4.1.3 for standalone operation with the LPC-200.1-02, Section 4.1.4 for extended operation with LPC-200.1-02 and Section 4.1.5 for extended operation with LPC-200.2-02

    4. Depending on the required hydraulic operational point (see Figure 6), the pump system requires 24V or 48 DC supply voltage at a maximum power of 200 W. At a lower performance power supplies with smaller power or bigger supplies to supply several pump systems simultaneously may be used. Consult Figure 11 to get the power consumption depending on the flow. Contact Levitronix for consulting and support on the power supply solution.

    5. Connect the DC supply wires to the power input connector of the controller. Make sure that the polarity is correct (see Figure 21 and Figure 22) and that AC/DC power supply is off.

    6. To secure the connectors, tighten all retaining screws.

    Figure 23: Grounding of LPC-200 controller

  • User Manual for PuraLev® 200MU www.levitronix.com

    PL-4031-00, Rev07, DCO# 20-144 20

    4.1.3 Electrical Installation of Controller LPC-200.1-02 for Standalone Operation

    For standalone operation the LPC-200.1-02 is disabled when power is turned on. It can be enabled manually by using the “UP” button on the display. However, if the controller shall be enabled automatically, when power is applied the “ENABLE” pin on the “USER INTERFACE” connector (see Table 10) has to be active (typically 24V).

    4.1.4 Electrical Installation of Controller LPC-200.1-02 for Extended Operation

    If the LPC-200.1-02 shall to be controlled with external signals the “USER INTERFACE” can be used with the PIN designations described in Table 10.

    Pin Name Connector Pin Number

    Designation Levels Note

    Analog In, (Signal) 5 Reference Speed

    4..20 mA = 0..10000 rpm

    -> Speed Limit = 10000 rpm 20 mA -> Cut-off (min.) speed = 300 rpm

    Direct connection, no protection. Galvanic isolation on the user side is required. Ground Analog In 6

    Digital In, (Signal) 3

    Enable 24 V active

    0 V not active

    Is needed to enable the system with an external signal.

    Ground Digital In 4

    Digital Out 1

    Status Relay closed active, system on

    Relay open not active, system off

    This signal indicates if the system is active.

    Ground Digital Out 2

    Table 10: Description of „USER INTERFACE“ connector (Description is for standard firmware, for other configurations refer to alternate firmware documentation)

    Figure 24: „ENABLE“ connector - Delivered with controllers - Supplier: PTR Messtechnik GmbH, Germany - Connector Type: AK1550/06-3.81-GREEN

    Figure 25: Mounted “USER INTERFACE” connector and Pin numbering

    1 6

  • User Manual for PuraLev® 200MU www.levitronix.com

    PL-4031-00, Rev07, DCO# 20-144 21

    4.1.5 Installation of PLC Interface for Extended Controller LPC-200.2-02

    To operate the pump system with a PLC, a minimum set of two digital inputs and one analog input is needed. The digital and analog outputs can be used to monitor the pump status and operating parameters.

    CAUTION The analog inputs and outputs are not galvanic isolated from

    the controller electronics. To avoid ground loops and mal-functions, use floating analog signals.

    1. Detach the PLC connector from the controller.

    2. Connect the designated wires of a cable to the pins of the detached connector according to Table 11. Assignment and functions of the I/Os can be changed with the controller firmware version (refer to according firmware documentation).

    3. Connect the PLC connector (Figure 26) to the controller.

    Figure 26: PLC connector - Delivered with controller LPC-200.2-02 - Supplier: Weidmüller - Connector Type: B2L 3.5/28 SN BK BX

    Figure 27: Mounted PLC connector and Pin numbering

    1

    2

    27

    28

  • User Manual for PuraLev® 200MU www.levitronix.com

    PL-4031-00, Rev07, DCO# 20-144 22

    Pin Name Connect.

    Pin # Designation Levels Note

    Analog In1, (Signal) 18 Ref Value

    (Current Input)

    4..20 mA = 0..10000 rpm (speed mode) -> Cut-off (min.) speed = 300 rpm

    4..20 mA = 0..100% (process mode)

    - Grounds are internally connected

    - Direct connection, no protection. Galvanic isolation on the user side is required. - Default input settings: Current inputs selected. Voltage input can be selected with EEPROM–editor in Levitronix® Service Software.

    Ground Analog In1 17

    Analog In2, (Signal) 20 Actual Process Control Value

    (Current Input)

    4..20 mA = 0..100%

    Ground Analog In2 19

    Analog In3, (Signal) 22 Ref Value

    (Voltage Input)

    0..10 V = 0..10000 rpm -> Cut-off (min.) speed = 300 rpm

    0..10 V mA = 0..100% (process mode) Ground Analog In3 21

    Analog In4, (Signal) 24 Actual Process Control Value

    (Voltage Input)

    0..10 V = 0..100 %

    Ground Analog In4 23

    Analog Out1, (Signal) 26 Actual Speed 0..5 V = 0..10000 rpm Direct connection, no protection. Galvanic isolation on the user side is required. 5V is given by firmware, hardware allows up to 10V output voltage.

    Analog Out2, (Signal) 28 Actual Process Control Value

    0..5 V = 0..100%

    Com. Ground Analog Out 25, 27 -- --

    Digital In1, (Signal) 2

    Reset 24 V active

    0 V not active Resets error state

    Ground Digital In1 1

    Digital In2, (Signal) 4

    Process mode

    24 V active

    0 V not active Switches between process mode and speed mode

    Ground Digital In2 3

    Digital In3, (Signal) 6

    Enable 24 V active, system on

    0 V not active, system off

    The Enable signal switches the pump system on and off.

    Ground Digital In3 5

    Digital In4, (Signal) 8

    Not used -- --

    Ground Digital In4 7

    Digital Out1 10

    Status Relay closed active, system on

    Relay open not active, system off

    This signal indicates the state of the pump system.

    Ground Digital Out1 9

    Digital Out2 12

    Error Relay closed not active, system on

    Relay open active, system off

    When active, the system drives the impeller to zero rpm and shuts down. With a reset pulse the system can be re-initialized. Ground Digital Out2 11

    Digital Out3 14

    Warning Relay closed not active, system o.k.

    Relay open active, system not o.k.

    The warning signal indicates if a system fault has been detected. The warning signal indicates a system fault but the system does not shut down

    Ground Digital Out3 13

    Digital Out4 16

    Default Setting:

    Trend Warning

    Relay closed warning active

    Relay open warning not active

    Default setting: Relay closed if trend warning is active. Can be changed in EEPROM with Levitronix® Service Software.

    Ground Digital Out4 15

    Option:

    Priming Valve Signal

    Relay closed Priming valve active

    Relay open Priming valve inactive Can be used to control a priming valve for priming of the pump. Feature can be activated and configured with Levitronix® Service Software.

    Table 11: Signals of the PLC connector for standard firmware Note 1: For other configurations of PLC Inputs and Outputs refer to alternate firmware documentation. Note 2: Configurations canbe done with Levitronix® Service Software. Note 3: All ground wires have to be connected.

  • User Manual for PuraLev® 200MU www.levitronix.com

    PL-4031-00, Rev07, DCO# 20-144 23

    4.2 Mechanical Installation of the Pump/Motor • The motor can be fixed with four screws on the motor bottom (see Figure 8)

    • As an alternative the Mounting Base Plate MBP-1.1 (see Table 4) can be used to fix the motor.

    • The motor can either be mounted in horizontal or vertical position

    4.3 Mechanical Installation of Motors in ATEX Zone 2 Areas

    ! WARNING

    Motors for ATEX / IECEx applications. Only specific types of motors BSM-1.x are classified for the use in ATEX Zone 2 classified locations.

    An Ex conform solution is needed for the motor cable to leave the Ex area (see Figure 5). One option is an ATEX certified cable sealing system as listed in Table 4 and shown in Figure 5.

    A protective earth wire shall be attached to the motor placed in the ATEX Zone 2 area by using one of the four M4 threads on the backside of the motor.

    • Remove one of the four M4 screws on the backside of the motor

    • Use a crimp-type end together with a spacer sleeve to connect a earth wire

    • Attach the grounding wire with a M4 stainless steel screw to the motor according to Figure 28.

    Figure 28: Attachment of a protective earth wire to the backside of the motor

    4.4 Mechanical Installation of the Controller

    ! WARNING

    Hazardous voltage may be present.

    In order to avoiding fluid spills shorting mains or other voltages within the controller, place the controller in a spill protected environment (for example protected electronic cabinets). If explosive flammable gases are present, place the controller in an explosion-proof cabinet.

    CAUTION Make sure the controller is mounted in a position that allows free air circulation

    around the controller. A minimum distance of 10cm (4”) to other objects above or below the controller casing is recommended.

    • Use the Din-Rail bracket to mount the controller.

    • If no forced air-cooling is used, mount the controller in upright position.

    • The Din-Rail brackets can also be mounted on the controller back side according to Figure 9

    CAUTION

    Use only 3,5 x 6,5 mm self-tapping screw for the fixation of the Din-Rail brackets. The controller may be damaged if other type or too long screw types are used!

  • User Manual for PuraLev® 200MU www.levitronix.com

    PL-4031-00, Rev07, DCO# 20-144 24

    4.5 Mechanical Installation of Adaptor/Extension Cables For connecting the motor to the controller the adaptor cables MCA-1.x shall be used ed (see Table 3 for adaptor cables). For the cables which use an M23 threaded metallic Hummel connector type, check the connection according to the following pictures:

    Figure 29: Wrong and correct Hummel connector type assembly

    O-Ring visible Wrong Connection! O-Ring not visible Correct Connection!

    Gap > 2 mm

    Sensor Cable of Motor

    Gap 2 mm

    Sensor Adaptor Cable

  • User Manual for PuraLev® 200MU www.levitronix.com

    PL-4031-00, Rev07, DCO# 20-144 25

    5 Operation

    5.1 System Operation with Controller LPC-200.1-02 (Stand-Alone)

    5.1.1 State Diagram of LPC-200.1-02

    The controller LPC-200.1-02 allows stand-alone operation with manual speed setting (“Button Control Mode”) as well as extended operation with analog speed setting (“Analog Control Mode”). Figure 30 shows the state diagram which can be controlled with the manual buttons and the signals on the “USER INTERFACE” connector. The operation mode can be chosen by pressing the “UP” and “DOWN” buttons simultaneously during 5 seconds. For the standard firmware default setting ex factory is “Button Control Mode”. Additionally the motor temperature can be checked (see temperature monitoring for ATEX / IECEx maintenance under Section 5.3.2).

    Figure 30: State diagram for operation with LPC-200.1-02 controller Note 1: Description is for standard firmware. Note 2: For other configurations refer to alternate firmware documentation

    Button Control Mode Analog Control Mode

    Power On

    OFF

    ButtonControl

    ON

    (Speed Mode)

    ButtonControl

    Ref.-Speed set

    to stored value*

    OFF

    AnalogControl

    ON

    (Speed Mode)

    AnalogControl

    Ref.-Speed set by

    analog input

    R

    Reset Button

    Ref. Speed

    UP

    Ref. Speed

    DOWN

    ButtonControl saved

    in EEPROM

    AnalogControl saved

    in EEPROM

    !Error

    !Error

    Enable

    input = 0V

    Enable

    input = 0V

    Enable

    input = 24V

    Press up

    for 2 sec

    Press down

    for 2 sec

    Press up

    for 1 sec Press down

    for 1 sec

    If Speed

    @ 0 RPM

    Press both

    for 5 sec

    Enable

    input = 24V

    !Error

    !Error

    Press both

    for 5 sec

    Press both

    for 1 sec

    Motor

    TemperatureReturns to previously

    active mode after

    displaying temperature

    twice

    System Error

    ButtonControl

    System Error

    AnalogControl

    R

    Reset Button

    Press both

    for 5 sec

    Factory default setting.

  • User Manual for PuraLev® 200MU www.levitronix.com

    PL-4031-00, Rev07, DCO# 20-144 26

    5.1.2 Standalone Operation (Button Control Mode)

    ◼ When applying power the system defaults into the “Button Control Mode” and goes into the status “OFF Button

    Control” according to Figure 30. Levitation is disabled and the display indicates “OF”.

    ◼ Levitation can be enabled by pressing the “UP” button during 1 second (display shortly indicates “ON”) or by activating (typically 24V) the “ENABLE” pin on the “USER INTERFACE” connector (see Table 10). The system goes then into the status “ON Button Control” and is running at the speed, which is stored in the EEPROM.

    ◼ The speed can be changed by pressing accordingly the “UP” and “DOWN” buttons. As long as the digits on the display are blinking the set speed is shown. As soon as blinking stops the actual speed is shown and the set-speed is stored in the EEPROM of the controller.

    ◼ The system can be disabled by pressing the “DOWN” button until 0 rpm is achieved. Pressing further 1 second the “DOWN” button the system disables levitation and shows “OF” on the display. The system can also be disabled by deactivating (0 V) the “ENABLE” pin on the “USER INTERFACE” connector (see Table 10). Before disabling the system the speed is automatically reduced to 0 rpm and the impeller is properly touched down without grinding the wall.

    ◼ To show the motor temperature in the display the “UP” and “DOWN” button has to be pressed simultaneously for 1 second. After entering this mode, motor temperature is shown twice switching between “ C” and temperature value in °C. After finishing this procedure system returns automatically to previously active mode.

    ◼ In case of an error the “RESET” button (see Figure 21) can be used to restart the system or the power can be

    switched off and on.

    ◼ For error analysis the codes described in Table 12 are displayed (blinking between “Er” and the according code

    number).

    ◼ If the system shall be enabled automatically, when power is applied the “ENABLE” pin on the “USER INTERFACE” connector (see Table 10) has to be active (typically 24V). When switching on the power the

    system is running with the stored speed.

    ◼ For monitoring purposes a digital output on the “USER INTERFACE” connector (see Table 10) indicates the status of the system. When the impeller is rotating the digital output “Status” turns active.

    The digital input “ENABLE” is normally edge-triggered to allow control by digital input and buttons in order to enable/disable systems simultaneously. An exception is, when the system is powered up or a system reset occurs: than the system checks the level of the digital input and switches to the desired state. Hence on startup a high level of the digital input “ENABLE” is sufficient to switch on the system and a transition from low to high is not required.

    5.1.3 Extended Operation (“Analog Control Mode”)

    ◼ In order to be able to control the pump with external signals (PLC) the mode “Analog Control Mode” has to be

    set with the display buttons. The “UP” and “DOWN” buttons have to be pressed simultaneously during 5 seconds. The display should feedback the change by blinking between the stored speed value and “An”. The chosen mode is then stored in the EEPROM of the controller. After startup the system returns to the operation mode selected previously.

    ◼ The system and levitation can be enabled/disabled with the digital input on the “USER INTERFACE” connector (see Table 10). When disabling the running system the speed is automatically reduced to 0 rpm and the impeller is properly touched down without grinding the wall. The display is blinking between “An” and ”OF”. Alternatively “UP” button is also able to switch on system, with “DOWN” button the system can be switched off.

    ◼ The speed can be set with an analog signal on the “USER INTERFACE” connector according to Table 10. It is strongly recommended to use galvanic separated signal values.

    ◼ For monitoring purposes a digital output “Status” on the “USER INTERFACE” connector (see Table 10) indicates the status of the system. When the impeller is rotating the digital output “Status” turns active.

  • User Manual for PuraLev® 200MU www.levitronix.com

    PL-4031-00, Rev07, DCO# 20-144 27

    5.1.4 Errors Display on the Integrated Panel

    Error Source

    Errors Error Code on Display

    Motor No Motor Er 01

    Motor Motor cable (power wires) not connected to controller Er 02

    Motor Motor cable (sensor wires) not connected to controller Er 03

    Motor No Rotor Er 04

    Controller Short circuit Er 05

    Controller Over current in the bearing coils Er 06

    Controller Over current in the drive coils Er 07

    Controller

    DC-Link voltage out of range (Voltage range for monitoring: 18 – 54 VDC)

    If the voltage is out of extended range the system starts to reduce the speed and an error is generated. When reaching 0 rpm and the voltage is still out of extended range the system is disabled.

    Er 08

    Controller Communication problems EEPROM Controller Er 09

    Motor Communication problems EEPROM Motor Er 10

    Controller Controller temp. over 80 0C or more than 10 minutes above 70 0C Er 11

    Motor Motor temp. over 100 0C or more than 10 minutes above 90 0C Er 12

    Pump

    Dry running of pump circuit:

    -> Pump keeps running on reduced speed (5000 rpm) -> The system accelerates to the original speed value when the pump is refilled with liquid. -> Note that the speed is only reduced during dry running if the pump speed was ≥ 6000 rpm.

    Blinking dots on display

    Table 12: Errors and warnings with indication on display of LPC-200.1-02 Note 1: In case of an error the system can only be restarted with a reset or a power supply restart. Note 2: Description is for standard firmware Note 3: For other configurations of error codes refer to alternate controller or firmware documentation.

  • User Manual for PuraLev® 200MU www.levitronix.com

    PL-4031-00, Rev07, DCO# 20-144 28

    5.2 System Operation with Controller LPC-200.2-02 (Extended PLC)

    5.2.1 State Diagram of the PLC Interface

    Figure 31: PLC interface state diagram for standard firmware Note 1: For other configurations refer to alternate firmware documentation

    Off

    Status : not active

    State 1

    Power On

    ON

    (Speed Control Mode)

    Status : Active

    Error : not active

    State 5

    ERROR

    Status : not active

    Error : active

    State 4

    Priming: off

    Enable: active

    Reset: not active

    Reset: active

    ON(Process Control

    Mode)

    Status : Active

    Error : not active

    State 6

    Internal

    Error

    Internal Error

    Enable: not active

    Process Mode:

    active

    Process Mode:

    not active

    ON(Priming Mode)

    Status : active

    Error : not active

    State 10

    Priming: on

    Enable: active

    Reset: not active

    Enable:

    not active

    Timeout,

    Process

    Mode:

    not active

    Timeout,

    Process Mode:

    active

    Enable:

    not active

  • User Manual for PuraLev® 200MU www.levitronix.com

    PL-4031-00, Rev07, DCO# 20-144 29

    State “Off”: The pump system is switched off and the motor has no power. In this state, Levitronix® Service Software has full control.

    State “ON” (speed control mode): The pump system is switched ON and the impeller is rotating with the referenced speed. The motor has electrical power when in this state.

    State “ON” (process control mode): The pump system is switched ON and the impeller speed is controlled in order to get the referenced flow/pressure. The motor has electrical power when in this state.

    On (Priming mode) The pump system is switched ON and the impeller is rotating with the priming speed. The motor has electrical power when in this state. In this state, the Manual User Interface LUI is disabled. This mode can only be accessed by activating priming feature within EEPROM-editor in Levitronix® Service Software. Priming speed and Timeout-time can also be configured within EEPROM-editor.

    State “Error”: If an error according to Table 13. occurs in the pump system, the system defaults to the Error state. The designated digital output on the PLC Interface is activated. The pump system is switched OFF. By activating the “Reset” input the system gets back to the “Off” state.

    Error Source Errors Effect on Designated Digital Output of the PLC

    Motor No rotor Error = relay open

    Motor Temperature over 100°C Error = relay open

    Motor Temp. was higher than 90°C for more than 10 minutes. Error = relay open

    Motor Temperature more than 90°C Warning = relay open

    Motor No motor temperature signal Warning = relay open

    Motor Motor power cable not connected with controller Error = relay open

    Motor Motor sensor cable not connected with controller Error = relay open

    Controller Over-current Error = relay open

    Controller Power channel interrupted Error = relay open

    Controller Temperature over 80°C Error = relay open

    Controller Temp. was higher than 70°C for more than 10 minutes. Error = relay open

    Controller

    DC link (supply voltage) out of range (< 18 or > 54 V DC)

    If the voltage is out of range the system starts to reduce the speed and a warning is generated. When reaching 0 rpm and the voltage is still out of range the system is disabled and an error is generated. In case the voltage is again within the range during speed reduction the system switches to normal operation and no Error is generated.

    Error = relay open

    Controller Temperature over 70°C Warning = relay open

    Controller

    Dry Running Detection

    -> Pump keeps running on reduced speed (5000 rpm) -> The system accelerates to the set speed value when the pump is refilled with liquid -> Note that the speed is only reduced during dry running if the pump speed was ≥ 6000 rpm

    Warning = relay open

    Controller Process warning (high deviation between reference and actual value) Warning = relay open

    Controller Trend warning (actual speed too high) Warning = relay open

    Table 13: Errors and warnings with indication on PLC interface for standard firmware (For other configurations refer to alternate firmware documentation)

  • User Manual for PuraLev® 200MU www.levitronix.com

    PL-4031-00, Rev07, DCO# 20-144 30

    5.3 System Operation for ATEX / IECEx Applications

    5.3.1 General Safety Requirements

    Specific precautions may be considered while using the pump system in potential explosive gas atmospheres according to ATEX category 3G/3D (Zone 2 and 22).

    The user shall prevent priming issues during normal pump operation. Precautions have to be considered especially during installing and maintenance operations to prevent the occurrence of combustible atmospheres.

    The user shall prevent electrostatic charging of the system during cleaning processes by using dry cleaning cloth. User shall use wet cleaning rags to avoid issues with charging during a cleaning process.

    CAUTION

    Precautions have to be considered to prevent priming issues during installation operation and maintenance of the pump head / motor.

    ! WARNING

    Operational Temperature T5 Maximum allowed pump liquid temperature is 90°C / 194°F for the use in ATEX Zone2 applications.

    ! WARNING

    Do not operate the pump against closed valves

    Do not operate the pump against closed valve as this can cause heat up of the liquid.

    5.3.2 Control of Motor Casing Temperature

    To avoid high motor casing temperatures and to control the temperature sensor operation the following steps shall be considered:

    For operation with the LPC-200.2-02 controller the “Digital Out 3” of the PLC connector (see Table 11) shall be monitored for warnings during operation in order to check if the communication to the temperature sensor is established. If “Digital Out 3” is active (this output indicates warnings caused by various sources, inter alia communication problems with the motor) the pump system may be checked for correct operation. The motor temperature readings can be monitored via the Levitronix® Service Software.

    For standalone operation with the LPC-200.1-02 controller the display shall be checked periodically for error messages according to Table 12 (see error Er10 = “Communication problems EEPROM Motor”). The motor temperature readings can also be monitored via the display (see Section 5.1.2 for using the display).

    Additionally the motor casing temperature shall be periodically measured and compared to the internal motor temperature readings. This comparison measurement checks potential drifts of the internal motor temperature sensor. Adhesive foil made of aluminum can be used to improve the thermal junction between motor casing and the external temperature sensor.

    CAUTION

    To prevent possible drifts of the motor temperature sensor the sensor shall be checked and compared to an external measurement of the motor casing temperature. This comparison measurement should be carried out at maintenance procedures every 12 month. The internal temperature sensor should not vary more than -10 °C to the external measurements. Positive drifts are not considered as critical.

  • User Manual for PuraLev® 200MU www.levitronix.com

    PL-4031-00, Rev07, DCO# 20-144 31

    6 Instruction for Use of Pump Head

    6.1 Description and Preparation

    6.1.1 Description

    The LPP-200 Multi-Use pump heads are designed for applications in the Life Science industries operating with the PuraLev® 200MU pump system. The wetted parts are made out of biocompatible materials (FDA, USP VI, Animal-Free). The pump head is mounted to the Bearingless Motor (a MagLev drive motor) and the motor is connected to a controller generating the currents for rotation and the levitation of the impeller.

    Figure 32: Pump head LPP-200.17 with motor BSM-1.x

    Before starting using the LPP-200 Multi-Use pump heads make yourself familiar with the following warnings, cautions and instruction.

    6.1.2 Inspection Prior to Use

    The pump head should be inspected prior to use for any damage. Do not use the pump head if any damage is found. Contact Levitronix® regarding return of any suspected pump head.

    6.1.3 Traceability for Troubleshooting

    Traceability for trouble shooting is assured with a 6 digit serial number located on the top of the pump head (see Figure 34).

    6.2 General Warnings and Cautions

    ! WARNING

    High Magnetic Field Strength of Pump Impeller

    The pump head contains a rotor magnet with high field strength. Pace makers may be influenced and magnetic field may lead to contusions. Keep distance to pace makers and handle pump heads with care.

    CAUTION

    Magnetic Forces

    Pay attention to the magnetic forces when handling the pump head. It has to be avoided that magnetic parts are attracted, which can cause cracks or contamination. Specifically pay attention to the magnetic forces, when handling two pump heads at the same time.

    ! CAUTION

    The rotating impeller could cause injury. Do not run the pump system when opening the pump head.

    6.3 Replacement of Pump Head

    6.3.1 Preparation

    After removal of a new pump head from its packaging assure that no metallic part is magnetically attaching to the pump head. Before insertion into the motor remove the Fixation Disk, which comes delivered with the packaging in order to magnetically fix the impeller against movements during transportation.

    Figure 33: Metallic Fixation Disc

    6.3.2 Power Down the System

    Set the speed to 0 rpm, disable the system. After running at higher motor or liquid temperature the pump head might stick to the motor due to thermal expansion effects. In this case let the system cool down for a while before starting the replacement procedure.

    6.3.3 Pump head Removal from Motor

    Un-tighten the screws M1 to M4, which fix the pump head to the motor (see Figure 34). Do not use the pump housing screws P1 to P6. Remove the pump head axially and attach the Fixation Disk from the new pump head to it.

    Bearingless Motor BSM-1.x

    Pump Housing Lid

    Pump Housing Bottom

    Drain Port (Option without Drain Port)

    Outlet

    Inlet

    Impeller

    Triclamp Sealing Gasket

    6 Screws M4x15mm (fixation of pump housing)

    4 Screws M3x14mm (For fixation of

    Pump head on motor)

  • User Manual for PuraLev® 200MU www.levitronix.com

    PL-4031-00, Rev07, DCO# 20-144 32

    Figure 34: Screws of pump head (Stainless Steel INOX A4)

    6.3.4 Insertion and Fixation of New Pump Head

    Assure that on the new pump head the Fixation Disk is not attached anymore. Then insert the pump head smoothly into the motor. Rotate it until the pump head holes and the motor threads are aligned.

    6.3.5 Fixation of New Pump Head to Motor

    Tighten the 4 M3x14mm Screws M1 to M4 the order as numbered in Figure 34. Use 4 sequences with incremental torque steps in order to avoid to fixing the pump head asymmetrically to the motor.

    Sequence 1: 10 Ncm Sequence 3-4: 15 Ncm (Max. torque)

    6.3.6 Start-Up and Functionality Check

    Start up the system and check if the impeller is rotating properly. If the pump is not operating as expected make sure that the metallic Fixation Disk or another magnetic part has not accidentally attached itself to the bottom of

    the pump head.

    6.4 Re-Assembling of Pump Head If possible avoid to disassembling the pump head. If this can not be avoided, for example due to cleaning reasons, use the following instructions to reassemble a pump head.

    6.4.1 Insertion of Impeller and Sealing Gasket

    Insert the Impeller into the Housing Bottom and then insert the Triclamp Sealing Gasket into the relevant cavity (see Figure 32).

    6.4.2 Press the Lid into the Housing Bottom

    Press the Housing Lid in to the Housing Bottom. Do not use the pump screws for doing this.

    6.4.3 Tighten the Pump Head Screws

    Tighten the 6 M4x15mm Screws P1 to P6 in the order as numbered in Figure 34. To avoid an asymmetric lid to

    bottom alignment Use 4 sequences with torque increments until each screw is tightened with 30 Ncm.

    Sequence 1: 10 Ncm Sequence 3-4: 30 Ncm (Max. torque)

    6.4.4 Final Assembly Check

    Check the uniformity of the gap between lid and bottom and that all screws are tightened properly.

    Figure 35: Cross-section of pump head with check points

    6.5 Assembly into a Circuit The following points shall be considered, when integrating the pump head into circuit.

    6.5.1 Usage of Fixation Disk

    During handling, assembling and transportation of the pump head with the hydraulic circuit it is recommended to attach the Fixation Disk to the pump head bottom. This fixes the impeller mechanically and reduces the magnetic fields, which can attract other magnetic parts during handling, sterilization and transportation.

    6.5.2 Careful Handling of Multiple Pump Heads

    Take care to the magnetic forces of the impellers when handling multiple pump heads at the same time. Avoid two pump heads coming together with force due to the magnetic attraction, which might cause cracks.

    6.5.3 Avoidance of Mechanical Stress

    Do not apply too much bending forces to the fittings. It is recommended to use 3 way clamps (not 2 way) to attach stainless steel Triclamp fittings. This reduces the tendency to distort the fittings due to different expansion coefficients of plastics and steel.

    6.6 Maintenance

    6.6.1 Check of Pump Head Screws

    From time to time and specifically after heat treatments like steam sterilization or autoclaving it is recommended to check if the 6 pump head screws still are screwed on properly in order to assure proper sealing of the pump housing.

    6.6.2 Check of Sealing Property

    The pump head design has recesses between lid and bottom, which allow to seeing leakages immediately. Regularly check these recesses for liquid leakage.

    4 Screws M3x14mm (Screws M1-M4 for fixation of

    pump head on motor)

    6 Screws M4x15mm (Screws P1-P6 for fixation of pump housing)

    M1

    M2

    M3

    M4

    P1

    P3

    P2

    P4

    P6

    P5

    6 Screws M4x15mm (Screws P1-P6 for fixation of pump housing) Tightened with 30 cNm

    Circular uniform gap of approximately 1.5mm

    Serial # of Pump Head

  • User Manual for PuraLev® 200MU www.levitronix.com

    PL-4031-00, Rev07, DCO# 20-144 33

    6.7 Precautions for Autoclaving and SIP (Steam-In-Place) When autoclaving the pump head the, Autoclaving Reinforcing Tool ART-200.1 (see Figure 2 and Table 4) shall be used to minimize distortion effects of the pump housing cup during exposure to higher temperatures.

    Figure 36 illustrates the mounting of the pump head on to the ART-200.1. The pump head shall be fixed with 4 screws according to the same procedure as described in Section 6.3.5.

    Figure 36: Mounting of Autoclaving Reinforcing Tool ART-200.1

    After autoclaving and SIP (Steam-In-Place) it is recommended to periodically tighten up the pump housing screws to Section 6.4.3. The re-mounting to the motor after autoclaving shall be done according to Section 6.4.

    CAUTION Depending on the number of autoclaving or SIP cycles and the duration,

    distortion effects in the pump head may lead to performance reduction. It is therefore recommended to run the pump 10% below the maximum speed after autoclaving or SIP.

    Contact the Levitronix® Technical Service department (see Section 8) for more detailed considerations and support on autoclaving and SIP.

    4 Screws M3x14mm (Screws A1-A4 for

    fixation of pump housing) Tightened with 15 cNm

    A1

    A2

    A3

    A4

  • User Manual for PuraLev® 200MU www.levitronix.com

    PL-4031-00, Rev07, DCO# 20-144 34

    7 Troubleshooting

    7.1 Troubleshooting for Operation with Controller LPC-200.1-02 For troubleshooting and failure analysis with the stand-alone controller LPC-200.1-02 the following procedure is recommended:

    ◼ Check the status of the LEDs. The specific LEDs are described in Table 8

    ◼ Use the ERROR codes on the display. The specific error codes are described in Table 12

    ◼ A digital output on the “USER INTERFACE” connector (“Status”) indicates if the system is active. However, the source of an error cannot be identified by this signal

    7.2 Troubleshooting for Operation with Controller LPC-200.2-02 The integrated PLC provides Warning and Error signals according to Table 13. However, the source of error cannot be identified by these signals.

    For more detailed analysis the Levitronix Service Software can be used with a PC and a USB interface to the controller.

    7.3 Troubleshooting with Levitronix® Service Software

    The Levitronix Service Software allows communication with the pump system in connection with a PC and a

    USB interface. The software can be used for performing detailed troubleshooting.

    Note: Levitronix Service Software can not be used with the standalone controller LPC-200.1.

    8 Technical Support For troubleshooting, support and detailed technical information contact Levitronix Technical Service Department:

    Levitronix Technical Service Department Technoparkstr. 1 CH-8005 Zurich Switzerland Phone for US: 888-569 07 18 Phone for outside US: +1 888-569 07 18 E-Mail: [email protected]

    mailto:[email protected]

  • User Manual for PuraLev® 200MU www.levitronix.com

    PL-4031-00, Rev07, DCO# 20-144 35

    9 Appendix

    9.1 Regulatory Status

    9.1.1 CE Marking

    The Centrifugal Pump System Family PuraLev® 200MU, in its configurations as listed below is in conformity with the below mentioned European Directives. The pump system is thought to be used in hydraulic circuits of production equipment of Life Science markets like Biotech and Pharmaceuticals.

    Part Name Description

    Pump Heads LPP-200.x Pump housing configurations consisting of variations concerning fittings, O-Rings, wet materials (biocompatible) and performance.

    and impellers with various materials (biocompatible) and performance variations

    Motors BSM-1.x Bearingless motors: BSM-1.x (x = various cable, connector and coating options)

    Controllers LPC-200.x Controllers with 24-48 VDC input: LPC-200.x (x = various interfacing options)

    Accessories Motor controller adaptor cables of various length, air cooling module and others

    Machinery Directive 2006/42/EC:

    The machinery directive essentially has been followed by a risk analysis, according mitigation actions and a user manual for safe operation. For the design and testing the following standards are used as a guideline:

    EN809 Pumps for Fluids: basic requirements are followed.

    EN12162 Procedure for hydrostatic pressure testing in fluid pumps: used for max. pressure testing of pump head.

    ISO12100 Safety for machinery – principles for risk assessments: used for system risk analysis.

    EMC Directive 2014/30/EC:

    The following standards of the EMC directive are tested and confirmed at a certified laboratory:

    EN61000-6-2 Generic standards, Immunity for industrial environments

    EN61000-6-4 Generic standards, Emission standard for industrial environments

    9.1.2 Disposal of Equipment – WEEE Directive 2012/19/EU

    Follow local legislation for disposal of equipment. In the European Union (EU) marked ( ) devices are governed by the European WEEE Directive 2012/19/EU. Do not dispose with normal waste.

    9.1.3 IECEE CB Safety Certification

    Specific motors with pump heads and controllers of the Centrifugal Pump System PuraLev® 200MU are 3rd party tested and certified by Electrosuisse following the IECEE CB Scheme according to the following safety standards:

    IEC61010-1 Safety requirements for electrical equipment for measurement, control and laboratory use.

    The CB certification number is CH-7695.

    9.1.4 NRTL/ETL Safety Certification and Marking

    Specific motors with pump heads and controllers of the Centrifugal Pump System PuraLev® 200MU are tested by the US national recognized laboratory (NRTL) Intertek according to the following safety standards:

    UL61010-1 Safety requirements for electrical equipment for measurement, control and laboratory (US Standard).

    CSA-C22.2 No. 61010-1-12

    Safety requirements for electrical equipment for measurement, control and laboratory use (Canadian Standard).

    UL1004-1 Rotating Electrical Machines - General Requirements (US standard).

    The ETL control number for the listing is 4010272.

  • User Manual for PuraLev® 200MU www.levitronix.com

    PL-4031-00, Rev07, DCO# 20-144 36

    9.1.5 ATEX / IECEx Certification and Marking

    Specific motors together with the pump head of the PuraLev® 200MU pump system are in conformity with the requirements of the Directive 2014/34/EU and the applicable IEC standards. The following standards are tested and confirmed at a certified laboratory.

    IEC / EN 60079-0 Electrical apparatus for explosive gas atmospheres. General requirements.

    IEC / EN 60079-15 Electrical Apparatus for explosive gas atmospheres. Construction, test and marking of type of protection, “n” electrical apparatus.

    IEC / EN 60079-31 Explosive atmospheres – Part 31: Equipment dust ignition protection by enclosure “t”.

    IEC / EN 13463-1 Non-electrical equipment for use in potentially explosive atmospheres – Part1: Basic method and requirements.

    IEC / EN 13463-5 Non-electrical equipment for use in potential explosive atmospheres – Part5: Protection by constructional safety “c”.

    The Levitronix Ex motors are marked clearly and in accordance to the ATEX Directive and the relevant IECEx standards. The protection “Ex nA” means non sparking electrical apparatus.

    II 3G Ex nA IIC T5 Gc

    II 3D Ex tc IIIC T100°C Dc

    Classification: Category 3GD (Zone 2 for Gas and Zone 22 for Dust)

    Thermal Classification: Thermal classification of motor is T5 (< 100 0C = 212 0F) for maximum full-load operating temperature at a maximum liquid temperature of 900C / 194 0F.

    9.1.6 Biocompatibility

    We declare that the wet materials of the LPP-200 pump heads, in the configurations as listed below, satisfy the following biocompatibility specifications:

    Part Name Article# Impeller Material Housing Material Triclamp Gasket

    LPP-200.5 100-90525 High Purity PFA PVDF Platinum Cured Silicone

    LPP-200.6 100-90526 High Purity PFA PVDF Platinum Cured Silicone

    LPP-200.12 100-90723 High Purity PFA PVDF Platinum Cured Silicone

    LPP-200.14 100-90724 High Purity PFA PVDF Platinum Cured Silicone

    Table 14: Pump heads with biocompatibility

    FDA 21 CFR

    All wet raw materials used in the above mentioned pump heads meet specifications according to FDA 21 CFR (section 177.2510/177.1520 for PVDF, 177.1550 for PFA, 177.2600 for Silicone). This statement is based on declarations provided by our raw material or component suppliers. USP VI

    The wet raw materials used in the above mentioned pump heads meet the specifications of USP Class VI. The statement is based on declarations provided by our raw material and component suppliers. BSE/TSE and Animal Free

    Based on declarations provided by our raw material and component suppliers, we believe that the wet materials of the above mentioned pump heads have been manufactured without coming into contact with animal derived materials and that they do not contain potential spongiform or transmissible spongiform encephalopathy (BSE/TSE) risk components.

  • User Manual for PuraLev® 200MU www.levitronix.com

    PL-4031-00, Rev07, DCO# 20-144 37

    9.2 Symbols and Signal Words

    Symbol / Signal Word

    Description Type Source

    DANGER Indication of an imminently hazardous situation that, if not avoided, will result in death or severe injury. Limited to the most extreme situation

    Signal word SEMI S1-0701

    WARNING Indication of a potentially hazardous situation which, if not avoided, could result in death or severe injury.

    Signal word SEMI S1-0701

    CAUTION

    Indication of potentially hazardous situations which, if not avoided, could result in moderate or minor injury. Also alert against unsafe practice.

    Without safety alert indication of hazardous situation which, if not avoided, could result in property damage.

    Signal word SEMI S1-0701

    ! Safety alert for “Warning” and “Caution” Safety alert SEMI S1-0701

    ! Safety alert for “Danger” Safety alert SEMI S1-0701

    Caution (refer to accompanying documents) (is used on article labels for reference to manual)

    Refer to manual ISO 3864

    Toxic material, poison Hazard identification IEC 61310

    Corrosive material, corrosion Hazard identification IEC 61310

    Cut/sever hand, sharp object Hazard identification ANSI Z535.3

    Strong magnetic field Hazard identification SEMI S1-0701

    Danger: electricity, electrical hazard Hazard identification IEC 61310, ISO 3864

    Wear safety gloves Hazard avoidance Mandatory action

    IEC 61310

    Wear face shield Hazard avoidance Mandatory action

    SEMI S1-0701

    No pacemakers Hazard avoidance

    Prohibition SEMI S1-0701

    ATEX Logo

    Used for hazard identificat. in warnings

    --

    Table 15: Safety symbols and signal words