GE Industrial Solutions
P/V II-12Air Insulated SwitchgearLeading the future of electrification
GEGE is a diversified organization covering a myriad of market segments, including infrastructure,
finance and media. From energy, water, transportation and health to access to money and
information, GE serves customers in more than 100 countries and employs more than 300,000
people worldwide.
The company traces its beginnings from Thomas A. Edison, who established the Edison Electric Light
Company in 1878. In 1892, a merger of Edison General Electric Company and Thomson-Houston
Electric Company created the General Electric Company. GE is the only company listed in the Dow
Jones Industrial Index today that was also included in the original index in 1896.
Industrial SolutionsGE Industrial Solutions, a division of GE Energy Management, is a global leading provider in
power distribution, offering a wide range of services and products which include medium and low
voltage power distribution equipment and components, motor & control systems and service
products that are safe, reliable and offer high performance.
Honour
2007 World’s Best R&D Companies
2011 World’s Most Admired Companies
2011 Best Global Brand
2008 World’s Most Respected Companies
2010 World's Most Innovative Companies
2009 World’s Most Respected Companies
More Than 90 Years of Interrupter ExperienceGE pioneered experimental vacuum interrupters in the 1920s. Refined it and introduced the world's first 15kV Vacuum circuit breaker in the 1960s. To date, this interrupter design has been the world leader in vacuum technology and has accumulated over 55 years of reliable field service.
World Class QualityManufactured, assembled and tested all in the same sophisticated facility, SecoVac is the product of state of the art manufacturing processes assured by ISO 9001:2008 and ISO 14001 certification.
AUniversal ApplicationsSecoGear is designed, assembled and tested to meet or exceed applicable IEC, GB and DL standards. It is suitable for applications in all major industries including T&D, Oil & Gas, Automotive, Processing plants, Iron and Steel mills, Mining, Commercial buildings, etc.It provides protection for all types of applications: coble, overhead lines, motors, capacitors, transformers, busbar sections, etc.
ecoEnvironment ConsciousnessSelecting low environmental impact technologies has become increasingly important to engineers tasked with choosing equipment for an application. W i th commitment to env i ronment protection, the solid insulation of epoxy resin is used for SecoVac series MV embedded pole vacuum circuit breaker instead of SF6 gas.
GEGE is a diversified organization covering a myriad of market segments, including infrastructure,
finance and media. From energy, water, transportation and health to access to money and
information, GE serves customers in more than 100 countries and employs more than 300,000
people worldwide.
The company traces its beginnings from Thomas A. Edison, who established the Edison Electric Light
Company in 1878. In 1892, a merger of Edison General Electric Company and Thomson-Houston
Electric Company created the General Electric Company. GE is the only company listed in the Dow
Jones Industrial Index today that was also included in the original index in 1896.
Industrial SolutionsGE Industrial Solutions, a division of GE Energy Management, is a global leading provider in
power distribution, offering a wide range of services and products which include medium and low
voltage power distribution equipment and components, motor & control systems and service
products that are safe, reliable and offer high performance.
Honour
2007 World’s Best R&D Companies
2011 World’s Most Admired Companies
2011 Best Global Brand
2008 World’s Most Respected Companies
2010 World's Most Innovative Companies
2009 World’s Most Respected Companies
90
1
SecoGear P/V II-12 Air Insulated switchgear
SecoGear P/V II-12 indoor A.C. metal-clad withdrawable switchgear is latest indoor electric distribution equipment produced by GE industrial system. The switchgear applies to three-phase A.C. indoor distribution single busbar or single busbar sectionalizing system, with rated voltage of 3.6-12kV, rated current of 4000A and lower, and rated frequency of 50Hz, for control, protect and inspect the circuits of power system.The rails middle-assembed structure is adopted in the switchgear. The frame structure is made of folded high quality steel plates bolted together. With perfect interlocks, the switchgear has psssed tests of the internal fault arc, condensation, and harsh environment. Being equipped with VB2 type high performance vacuum breaker developed by GE with its advanced technology, safety and reliability are fully guaranteed. If request , fixed type load switch can be installed in the switchgear.
Environmenal dataMax ambient temperature +40℃Min ambient temperature -15℃Mean ambient temperature within 24h no more than 35℃ Maximum average relative humidity:Over 24 hour period 95%Over 1 month period 90%Saturated steam pressure:Daily average: <2.2kPaMonthly average: <1.8kPaAltitude category does not exceed 1000mEarthquake intensity no more than 8 degreeSite free from fire/explosion, severe contamination, corrosion and violent shock and ambient air is not polluted obviously by dustWeatherproof in accordance with the specification in level 1 in GB3906.
Note: when the relative humidity is above 70%, the heater shall be put into use for preventing condensation. When the normal service condition is different from the above
mentioned, please confer with us.
Applicable standardsGB3906 3.6-40.5kV AC metal-enclosed switchgear and ControlgearGB/T11022 Common specifications for high-voltage switchgear and controlgear standardsDL/T404 Indoor AC high-voltage switchgear panelIEC62271-200 AC metal-enclosed switchgear and controlgear for rated voltages above 1 kV and up to and including 52 kV
2
StructureThe switchgear consists of two parts: cubicle and withdrawable parts. The cubicle are made of high quality steel plate (zinc plate coated with aluminum can also be used at the customers' request). The degree of protection for the enclosure is IP4X and IP2X (when the door of the circuit breaker compartment is open). The switchgear can be equipped with VB2 type withdrawable vacuum circuit breaker truck or fixed type load switch. The rails of truck are assembled on the middle side of the cubicle to avoid fault that the disconnecting contacts of the truck can not engaged with the contacts fixed in the cubicle caused by the floor out of shape. At the same time, the height of the power cable terminal can be rised and the convenience for operation and maintenance improve. The switchgears can be arranged face to face but can not be installed against wall.
*Only for the structure 650mm in width ; Once there is a switchgear with 650mm in width, the depth of the other cubicles will change accordingly.When cables come in switchgear from the top, then should add rear channel cabinet with 200mm depth. When the busbars come in from the top, should add rear channel cabinet with 350mm.
Height (a) mm 2200
Width (b)
Rated breaking current ≤31.5ARated current of branched
busbar≤1250Amm
650800
Rated breaking current:40kARated current of branched
busbar≤1250Amm 840
Rated breaking current:40kARated current of branched
busbar>1250Amm 1000
Depth of the frame
mm1550 1590*
Depth of the rear cover
plate(d)mm 30
A. Busbar compartmentB. Truck compartmentC. Cable compartmentD. LV compartment1. Pressure relief flap2. Enclosure3. Removable partition4. Branch busbar5. Main busbar6. Fixed contact
7. Bushing spout8. Current transformer 9. Earthing switch10. Cable sealing terminal box11. Arrestor12. Bottom plate13. Secondary terminal box14. Removable partiton15. Secondary terminal panel16. Shutter
17. Secondary plug18. Vacuum circuit breaker19. Earthing for moving truck20. Racking mechanism21. Earthing switch operation mechanism22. Control cable duct23. Main earthing busbar
Construction of P/V Ⅱ-12 for cable incoming and feeder
3
Truck compartment The truck compartment is on the middle front of the cubicle. Mount specified truck rail on both sides of the compartment for the truck to move along between the test and servicing positions. On the rear cover of the compartment , there is bushing type CT or bushing spouts and protective metal shutters, which can be moved up and down. The shutters can open automatically during truck moving to servicing position from test position; the movable contacts will be inserted into the fixed contacts. When the truck moves into test position, the protective shutters will go down to cover the fixed contacts to make it isolated. This can protect personnel from touching the live parts.The operation of the truck shall be carried out with the door of the cubicle closed. The position of the truck can be viewed through the window on the door. In the meantime, the close/open button on the breaker panel and position indicator, indicator for spring charging also can be viewed.
Withdrawable PartsBased on the purposes , the withdrawable parts can be classified as circuit breaker truck, PT truck, link truck, metering truck and etc. The same truck can be interchangeable easily. The primary arms installed on each phase are all equipped with spring fingers. Trucks can be in test and servicing positions, each of which has a locating device to ensure the trucks is allowed being operated only when they are at the proper positions.Before the truck is moved, the breaker should be in open.
Busbar compartmentThe upper rear of the cubicle is main busbar compartment . Main busbars can be led from one cubicle to another. The bushings installed on the partition not only support the main busbar but also prevent the faulty spreading to the adjacent cubicle. Branched busbar can be connected to the main busbar and bushing spout with bolts. All busbars can be covered with heat-shinkable tubings according to customer' s special requirements.The busbar joints can also be covered with insulation boot.
The enclosure and partition The enclosure of the switchgear is made of folded high quality steel plates connected with fasteners. The assembled switchgear has integrity in dimension. The cubicle is divided into truck compartment , busbar compartment , cable compartment and LV compartment by metal partitions. Each function unit is separated from others.
4
Cable compartmentThe lower rear of the cubicle is cable compartment , in which current transformer, earthing switch and arresters can be installed. With the rear cover plate removed, the operator can enter the cubicle to install cables. 1 or 3 cables can be connected to the terminal in parallel at the same time. The Height of the cable terminals can reach 680mm. In the bottom of the compartment there is removable steel plate as well as cable clips and seal rings with variable radius.In addition, heaters are set in both truck compartment and cable compartment to prevent condensation caused by high ambient humidity.
Pressure-relief All the truck compartments, busbar compartment and cable compartment have pressure relief duct. In the case that internal arc fault occurs to the truck, busbar or cable compartments, the pressure inside the compartment rise. The pressure-relief plate will be opened automatically to release pressure and gas. At this time because the seal ring installed on the door is enclosed, the safety of the operators in front of the panel is guaranteed.
Earthing DeviceThere are fixed earthing contacts on both sides of the truck compartement , and there are moveable earthing contacts installed on both sides of the truck to ensure that the truck be earthed reliably from the test position to servicing positon. The earthing resistance is less than 300 μΩ.After the cubicle is arranged properly, earthing busbar of cubicles be connected and be connected to the earth.
InterlocksPerfect and reliable interlocks facilities are incorporated to ensure safe operation. These include the following: a. Only when earthing switch is in Open (at this time the rear
cover can’t be open), can the truck be racked in from test position to servicing position.
b. Only when the breaker is in open , can the truck be racked between the test position and servicing position in cubicle.
c. When the earthing switch is closed (at this time the rear cover can be open), the truck can’t be racked in from the test position to serving position.
d. When the rear cover is open, the earthing switch can’t be open .
e. The earthing switch can be closed, only when the breaker truck is on test position or outside the cubicle.
f. When the truck is on servicing position, the secondary plug will be locked and can’t be removed.
g. Only when the breaker truck is on test position or servicing positon, can the breaker carries out opening and closing operation.
h. All the doors of HV compartments are equipped with locks and be opened or closed with special tools.
Note: It is allowed to use capacitive voltage detection system.
LV compartmentLV compartment is on the upper front of the cubicle.The secondary instruments such as the metering instruments, operating switch, buttons and relays, etc, can be installed. There are some little holes on the side plate of the compartment for wirings.
5
Technical data for switchgear
Technical data for closing and opening electric magnet coils
Technical data for VB2 circuit breakers
Technical data for spring operation mechanism of VB2-12 circuit breaker
Description Unit Data
Rated voltage kV 3.6、7.2、12
Rated insulation level1min Power frequency withstand voltage kV 42
Lightning impulse voltage (peak) kV 75
Rated frequency Hz 50
Rated current of main busbar A 630、1250、1600、2000、2500、3150、4000
Rated current of branch busbar A 630、1250、1600、2000、2500、3150、4000(forcing cooling)
Short-time withstand current (4s) kA 25、31.5、40
Rated peak withstand current kA 63、80、100 (125)
Degree of protection Enclosure IP4X, IP2X (if the truck compartment door is open)
Description Unit Data
Rated voltage kV 3.6、7.2、12
Rated insulation level1min Power frequency withstand voltage kV 42
Lightning impulse voltage (peak) kV 75
Rated frequency Hz 50
Rated current A630、1250、1600、2000、2500、3150、4000
(forcing cooling in panel)
Short-time withstand current (4s) kA 25、31.5、40
Rated peak withstand current (peak value) kA 63、80、100 (125)
Times of rated short-circuit current breaking Times 50、30 (breaking current 40kA)
Operation sequence Open-0.3s-close-open-180s-close-open
Mechanical service life Times 30000
Contact stroke mm 9±1
Over-travel mm 5±1
Average closing speed m/s 0.5~1
Average opening speed m/s 1~1.3
Contact closing bouncing time ms ≤2
Three-phase contact close and open asynchronization ms ≤2
Description Unit Data
Rated working voltage (Un) V AC、DC110 AC、DC220
The rated input power of motor W 300
Charging time under rated working voltage S ≤10
Normal working voltage scope 85%~110%Un
Description Unit Data
Rated working voltage V DC110 DC220
Rated working current A 1.91 1
Resistance of the magnet coil at 20°C Ω 57±2.5 220±0.5
Normal working voltage scopeClosing: 85%-110%Un
Breaking: 65%-120%, when <30%Un, breaking is not allowed
Technical data for energy charging motor
6
LDJ3-12 ( JAG-12)Technical data for LDJ3-12 (Q) (JAG-12(Q)) current transformer
Rated current ratio
Accuracy class and protect class
Rated output VA Rated short time withstand current
kA/s
Rated peak withstand current
kA (peak)0.2S 0.2, 0.5 5P10 5P20
5/5 (1)
0.2S/0.2S0.2/0.2
0.2S/5P100.2/5P100.5/5P10
10
10 15 5
0.6/2 210/5 (1) 1.1/2 315/5 (1) 1.7/2 520/5 (1) 2.7/2 730/5 (1) 4/2 1040/5 (1) 5/2 1350/5 (1)
9/2 2360/5 (1)75/5 (1) 13.5/2 34
100/5 (1) 18/2 45150/5 (1)
27/2 68200/5 (1)300/5 (1)
15
2010
40/2 100400/5 (1) 25500/5 (1) 30
15600/5 (1) 40800/5 (1)
50 201000/5 (1)
20 50/2 1251250/5 (1) 60 25
As an absorption device for operation overvoltage of vacuum circuit breaker, the following type metal-oxide arresters (MOA) are available: HY2.5w (to protect motor), HY5WS (distribution), HY5WZ and (parallel compensation capacitor).
1000
100
10
10.001 0.01 0.1 1 10
1250/5800、1000/5600/5500/5400/5300/53~200/5
Seco
ndar
y Vo
ltage
(V)
Secondary excitation current (A)
Size of P2 outgoing plate
P2 outgoing plate
In=5~600A
64
3240
80
40±0
.2
290±0.5
448±2
178±0.5
152±
0.5
147±
0.5
120±
0.2
190±
1.5
4-M8
150
85
108±0.2122148
2
A
108 13
5
16
72
182
126
2-M12×25A Side
2-M12×22 4-M12×22
60 40 80
In=800~1250A
7
Scheme No. 01 02 03 04
Main circuit diagram
Rated current (A) 630~1250 630~1250 630~1250 630~1250
Major equipment
Vacuum breaker VB2-12 1 1 1 1
CT JAG-12 (LZZB-12) 2 2 3 3
PT JDZ8
PT JDZX8
HV fuse RN2-10
** Earthing switch JNH1-12 1 1
Arrester HY5WS
Application Cable incoming or outgoing
Cubicle width (mm) 800 (650) (840) 800 (650) (840) 800 (650) (840) 800 (650) (840)
Scheme No. 05 06 07 08
Major equipment
Rated current (A) 630~1250 630~1250 630~1250 630~1250
Major equipment
Vacuum breaker VB2-12 1 1
CT JAG-12 (LZZB-12) 2 3
PT JDZ8
PT JDZX8
HV fuse RN2-10
** Earthing switch JNH1
Arrester HY5WS 3 3
Application CouplingCable incoming/
outgoingDisconnect or
couplingCubicle width (mm) 800 (650) (840) 800 (650) (840) 800 (650) (840) 800 (650) (840)
Note: * When the cubicle width is 650mm, the CT for LZZ8-12 can only be available. ** When the cubicle width is 650mm, the earthing switch will be JN15A.
Main circuit diagram scheme
8
Scheme No. 09 10 11 12
Main circuit diagram
Rated current (A)
Major equipment
Vacuum breaker VB2-12
CT JAG-12 (LZZB-12)
PT JDZ8 2 2
PT JDZX8 3 3
HV fuse RN2-10 3 3 3 3
Earthing switch
Arrester HY5WS 3 3
Application PT
Cubicle width (mm) 800 (650) (840) 800 (650) (840) 800 (650) (840) 800 (650) (840)
Scheme No. 13 14 15 16
Main circuit diagram
Rated current (A)
Major equipment
Vacuum breaker VB2-12
CT JAG-12 (LZZB-12)
PT JDZ8 2 2
PT JDZX8 3 3
HV fuse RN2-10 3 3 3 3
Earthing switch
Arrester HY5WS 3 3
Application PT & coupling
Cubicle width (mm) 800 (650) (840) 800 (650) (840) 800 (650) (840) 800 (650) (840)
9
Scheme No. 17 18 19 20
Main circuit diagram
Rated current (A) 630~1250 630~1250
Major equipment
Vacuum breaker VB2-12
CT JAG-12 (LZZB-12)
PT JDZ8 2
PT JDZX8 3
HV fuse RN2-10 3 3
** Earthing switch JNH1-12
Arrester HY5WS 3 3
Application PT Cable incoming or outgoing
Cubicle width (mm) 800 (650) (840) 800 (650) (840) 800 (650) (840) 800 (650) (840)
Scheme No. 21 22 23 24
Main circuit diagram
Rated current (A) 630~1250 630~1250 630~1250 630~1250
Major equipment
Vacuum breaker VB2-12 1 1
CT JAG-12 (LZZB-12) 2 3
PT JDZ8 2 2
PT JDZX8 2 2
HV fuse RN2-10 3 3
Earthing switch JNH1-12
Arrester HY5WS
Application Overhead incomingMetering & incoming
Metering &coupling
Cubicle width (mm) 800 (650) (840) 800 (650) (840) 800 (650) (840) 800 (650) (840)
Main circuit diagram scheme
10
Scheme No. 25 26 27 28
Main circuit diagram
Rated current (A) 630~1250 630~1250 630~1250 630~1250
Major equipment
Vacuum breaker VB2-12
CT JAG-12 (LZZB-12) 2 2
PT JDZ8 2 2
PT JDZX8
HV fuse RN2-10 3 3
Earthing switch
Arrester HY5WS
Application Metering & CouplingCable incoming or
outgoingDisconnect or
coupling
Cubicle width (mm) 800 (650) (1000) 1000 (800) (650) 1000 1000
Scheme No. 29 30 31 32
Main circuit diagram
Rated current (A) 1600~4000 1600~4000 1600~4000 1600~4000
Major equipment
Vacuum breaker VB2-12 1 1 1 1
CT JAG-12 (LZZB-12) 2 2 3 3
PT JDZ8
PT JDZX8
HV fuse RN2-10
Earthing switch JNH1-12 1 1
Arrester HY5WS
Application Cable incoming or outgoing
Cubicle width (mm) 1000 1000 1000 1000
11
Scheme No. 33 34 35 36
Main circuit diagram
Rated current (A) 1600~4000 1600~4000 1600~4000 1600~4000
Major equipment
Vacuum breaker VB2-12 1 1 1 1
CT JAG-12 (LZZB-12) 2 3 2 3
PT JDZ8
PT JDZX8
HV fuse RN2-10
Earthing switch
Arrester HY5WS
Application Coupling overhead outgoing
Cubicle width (mm) 1000 1000 1000 1000
Scheme No. 37 38 39 40
Main circuit diagram
Rated current (A) 1600~4000 1600~3150 1600~4000 1600~3150
Major equipment
Vacuum breaker VB2-12 1 1 1 1
CT JAG-12 (LZZB-12) 2 2 3 3
PT JDZ8
PT JDZX8
HV fuse RN2-10
Earthing switch JNH1-12 1 1
Arrester HY5WS
Application Cable incoming or outgoing
Cubicle width (mm) 1000 1000 1000 1000
Main circuit diagram scheme
12
Scheme No. 41 42 43 44
Main circuit diagram
Rated current (A) 1600~4000 1600~3150 1600~4000 1600~3150
Major equipment
Vacuum breaker VB2-12 1 1 1 1
CT JAG-12 (LZZB-12) 2 2 3 3
PT JDZ8
PT JDZX8
HV fuse RN2-10
Earthing switch JNH1-12 1 1
Arrester HY5WS
Application Cable incoming or outgoing
Cubicle width (mm) 1000 1000 1000 1000
Scheme No. 51 52 53 54
Main circuit diagram
Rated current (A) 630~1250 630~1250 630~1250 630~1250
Major equipment
Vacuum breaker VB2-12 1 1 1 1
CT JAG-12 (LZZB-12) 2 3 2 3
PT JDZ8 2 2 2 2
PT JDZX8
HV fuse XRNP-12 3 3 3 3
** Earthing switch JNH1
Arrester HY5WS
Appication Incoming or PT PT & coupling
Cubicle width (mm) 800 (650) (840) 800 (650) (840) 800 (650) (840) 800 (650) (840)
13
Scheme No. 55 56 57 58
Main circuit diagram
Rated current (A) 630~1250 630~1250 630~1250 630~1250
Major equipment
Vacuum breaker VB2-12
CT JAG-12 (LZZB-12) 2 3 2 3
PT JDZR8-10A 2 2 2 2
PT JDZX8
HV fuse XRNP-12 3 3 3 3
Earthing switch JNH1
Arrester HY5WS
Appication Incoming or PT PT & coupling
Cubicle width (mm) 800 (650) (840) 800 (650) (840) 800 (650) (840) 800 (650) (840)
Scheme No. 59 60 61 62
Main circuit diagram
Rated current (A) 630~1250 630~1250 630~1250 630~1250
Major equipment
Load switch FN5-12 1 1
Disconnector GN19-12 1 1
CT LQJ-10 2 3 2 3
PT JDZ 2
PT JDZJ 3
HV fuse RN2-10 3 3 3 3
Arrester HY5WS
Application Metering & incoming
Cubicle width (mm) 1000 1000 1000 1000
Main circuit diagram scheme
14
Scheme No. 63 64 65
Main circuit diagram
Rated current (A)
Major equipment
PT JDZ8 2
PT JDZX8 3
HV fuse RN-10 3 3
Transformer SC1-30 (50) 1
HV fuse SDLNJ 3
CT BHG-0.66 3
LV circuit breaker C45 1~6
Application PT & incoming Station transformer
Cubicle width (mm) 800 (650) (840) 800 (650) (840) 800 (650) (840)
Scheme No. 66 67 68 69
Main circuit diagram
Rated current (A) 630~1250 630~1250 630~1250 630~1250
Major equipment
Vacuum breaker VB2-12 1 1 1 1
CT JAG-12 (LZZB-12) 2 2 3 3
PT JDZ8
PT JDZX8
HV fuse RN-10
** Earthing switch JNH1 1 1
Arrester HY5WS
Application Cable upper incoming/outgoing
Cubicle width (mm) 800 (650) (840) 800 (650) (840) 800 (650) (840) 800 (650) (840)
15
Examples of the scheme applicaiton
Example 1
Example 2
Scheme No. 70 71 72 73
Main circuit diagram
Rated current (A) 630~1250 630~1250 630~1250 630~1250
Major equipment
Vacuum breaker VB2-12 1 1 1 1
CT JAG-12 (LZZB-12) 2 2 3 3
PT JDZ8
PT JDZX8
HV fuse RN-10
** Earthing switch JNH1 1 1
Arrester HY5WS
Application Overhead incoming/outgoing
cubicle width (mm) 800 (650) (840) 800 (650) (840) 800(650) (840) 800 (650) (840)
Main circuit diagram scheme
16
Seco
ndar
y co
mpo
nent
s of
circ
uit b
reak
ers
Seco
ndar
y co
mpo
nent
s on
truc
ksH
K58
-pin
avi
atio
n pl
ugS8
Lim
it sw
itch
(test
pos
ition
)M
Ener
gy s
tora
ge m
otor
S9Li
mit
switc
h (s
ervi
cing
pos
ition
)V1
, V2
rec
tifier
X02
Wiri
ng T
erm
inal
s of
the
truc
kS1
0, S
11, S
12En
ergy
sto
rage
pos
ition
sw
itch
S21,
S22
Ener
gy s
tora
ge p
ositi
on s
witc
hS4
1, S
42En
ergy
sto
rage
pos
ition
sw
itch
HQ
Clos
ing
coil
TQO
peni
ng c
oil
GT1
Ove
r cur
rent
trip
ping
co i
lG
T2O
ver c
urre
nt tr
ippi
ng c
oil
GT3
Ove
r cur
rent
trip
coi
lD
LAu
xilia
ry s
witc
h
Serv
icin
g p
ositi
on
Test
pos
ition
Hk
25 S21
S10
A1 A2 S11
S22
35
HK
341422
14
1321
13S4
2S1
4
2214
2113
V1A~
HQ
B-21 22
14
C+
D~
A~ A2
B-V2
A~3032
4345
331
511
623
727
828
299
4910
471
5557
5453
HK
S8
1X0
2
13 14
23 24
33 34
43 44
53 54
34
68 9
75
2
X02
S913
11 12
1517 18
1614
101413
2423
3433
4443
5453
50H
K51
5856
220
4840
C+
D~
A2A1TQ
GT1
GT2
GT31
11 2
22
1113
2123
3331
4343
5351
6361
7173D
L
7472
6264
5254
4432
3424
2214
12
442
4446
1315
2122
1617
3718
3839
193342
S41
3641
2426
17
Transportation and StorageDuring the transportation and storage of the switchgear, the following should be noted:(1) Don' t tilt , collide and upside down or violent shake.(2) Prevent it from rain and dampnessDon' t remove the electric components randomly so as to keep the integrity of the product.
OrderWhen ordering, customers shall provide the following documents:(1) Primary circuit scheme and the single line system drawing(2) The array diagram of the switchgears and arrangement diagram of the station(3) The specification and quantity of the electrical equipment installed in each switchgear with the list of equipments.(4) The secondary circuit diagrams.
Documents and accessoriesFor this product , the following documents and accessories will be provided:(1) Product certificate(2) Product manual(3) Array diagram and secondary wiring (4) The operation handle of breaker, earthing switch and energy storage (5) Proper number of special lifting trucks for circuit breakers
Installation FoundationThe construction of the foundation ground shall conform to the local specifications for electric power construction and acceptance.The allowable error of the channel steel, frame structure shall not be greater than 1mm/m. the total length variation:±3mm.Structure reference of foundation frame is shown in figure 1 & figure2.The foundation of switchgear is formed by pouring concrete in twice, once pouring the installation foundation, the second time, supplement concrete on the surface. The thickness shall be 60mm in normal; the supplemented height shall be lower than channel steel 1-3mm.
Note: red figures in the diagram show the sizes when the cubicle' s width is 650mm.
Figure 1 cable chute sketch
1450
16101650
8014301415
600460
6030
1200
300 60
40
Benchmark in frontof the cubicle door Normal panel (Including front door and rear cover)
Secondary cable chute
Primary cable chute
Channel steal 63×40×4.8
Concre
tesupplement layer
1~3
mm
18
Note: The red letters in the diagram show the sizes when there is panel with width of 650mm in the array. Figure 2 Reference structure of concrete ground foundation frame
200
80*
10010
00*
200 200 200 100600(800)450(800)
1610
1650
1530
1370
1385
140
110
600
480
740
600(800)450(800)
600(800)450(800)
16101650
1450
13701395
100
600460
800(1000)650(1000)
7545
7545
7545
7545
800(1000)650(1000)
800(1000)650(1000)
800(1000)650(1000)
800(1000)650(1000)
800(1000)650(1000)
800(1000)650(1000)
600(800)450(800)
600(800)450(800)
600(800)450(800)
200 200 200
1000*
1000*
1500
Dou
ble
arra
ys 2
000
B
A-A
B-B
B
A
A
63×40×4.840
7575
80*
200
(80)
60*
1~3
1000*
n×
600(800)450(800)
n×
800(1000)650(1000)
n×
Benc
hmar
k of
the
front
doo
r of t
he p
anel
Nor
mal
pan
el (i
nclu
ding
the
front
doo
r and
rear
sea
l pla
te)
Sing
le a
rray
Foundational channel steel
Primary cable hole
Secondary cable hol
dismensions in mmMin. size
e
Denchmark of the front door of the panel
Double arrays 2500
Single array 1500
Korea3rd Floor, GE Tower, 71-3, Cheongdam-dong, Gangnam-guSeoul, Korea 135-100T : +82 2 6201 4501F : +82 2 6201 4344
Japan11F, Akasaka Park Bldg.,5-2-20, Akasaka, Minato-kuTokyo 107-6111T : +81 3 3588 5288F : +81 3 3585 3010
North Asia
MalaysiaLevel 6, 1 Sentral, Jalan Travers, Kuala Lumpur SentralKuala Lumpur, Malaysia 50470T : +603 2273 9788F : +603 2273 7988
Thailand25th floor, CRC Tower, All Seasons Place, 87/2 Wireless Road, Lumpini, Pathumwan, Bangkok 10330T : +66 2 648 0240F : +66 2 648 0200
IndonesiaBRI II Tower, 27th floor, Jl. Jend. Sudirman No. 44-46Jakarta 10210T: +62 21 573 0430F: +62 21 574 7089
Singapore240 Tanjong Pagar Road, #06-00 GE TowerSingapore 088540T : +65 6326 3718F : +65 6326 3015
Philippines8F Net Cube Building, 30th Street, Corner 3rd Avenue, Crescent West Park, Global City Taguig 1634T : +63 2 877 7000F : +63 2 846 0629
VietnamSaigon Centre, Unit 1, Floor 7, Le Loi Boulevard, District 1HoChiMinh CityT : +84 8 3914 6700F : +84 8 3827 8229
South East Asia
Australia125-127 Long Street, Smithfield, Sydney, NSW 2164T : +61 2 8788 6911F : +61 2 8788 7224
New ZealandLevel 1, 8 Tangihua Street, Auckland, North IslandT : +64 9 353 6706F : +64 9 353 6707
Australia & New Zealand
IndiaPolt No. 42/1 & 45/14, Electronic City-Phase IIBangalore-560100T: (080) 41434000F: (080) 41434199
India
Shanghai4F, Building 2, CTP, No.1 Hua Tuo Rd. Zhang Jiang Hi-Tech Park, Shanghai, China 201203T : +86 21 3877 7888F : +86 21 3877 7600
Taiwan6F, No. 8, Min Sheng E. Rd., Sec. 3, Taipei 10480T : +886 2 2183 7000F : +886 2 2516 6829
Greater China
SpainP.I. Clot del Tufau, s/n, E-08295 Sant Vicenç de CastelletT: +34 900 993 625
BelgiumNieuwevaart 51, B-9000 GentT: +32 (0)9 265 21 11
FinlandKuortaneenkatu 2, FI-00510 HelsinkiT: +358 (0)10 394 3760
FranceParis Nord 2, 13, rue de la PerdrixF-95958 Roissy CDG CédexT: +33 (0)800 912 816
PolandUl. Odrowaza 15, 03-310 WarszawaT: +48 22 519 76 00andUl. Leszczyńska 6, Bielsko-Biała 43-300T: +48 33 828 62 33
Russia27/8, Electrozavodskaya street, Moscow, 107023T: +7 495 937 11 11
South AfricaUnit 4, 130 Gazelle Avenue, Corporate Park Midrand 1685P.O. Box 76672 Wendywood 2144T: +27 11 238 3000
United Arab Emirates1101, City Tower 2, Sheikh Zayed Road, P.O. Box 11549, DubaiT: +971 43131202
United KingdomHoughton Centre, Salthouse Road, Blackmills, NorthamptonNN4 7EXT: +44 (0)800 587 1239
ItalyCentro Direzionale Colleoni, Via Paracelso 16Palazzo Andromeda B1, I-20041 Agrate Brianza (MB)T: +39 2 61 773 1
NetherlandsParallelweg 10, Nl-7482 CA HaaksbergenT: +31 (0)53 573 03 03
GermanyRobert-Bosch Str. 2a, 50354 Hürth-EfferenT: +49 (0) 2233/ 9719-0
PortugalRua Camilo Castelo Branco, 805, Apartado 27704401-601 Vila Nova de GaiaT: +351 22 374 60 00
HungaryVaci ut 81-83. H-1139 BudapestT: +36 1 447 6050
Europe & Middle East
BrazilAv. María Coelho Aguiar, 215, Bloco C - 6.AndarJd.São Luiz, 05804-900, São PauloT: +55 11 36141900
MexicoAv. Churubusco 3900 Nte, Col. Industrial Benito JuárezMonterrey, N.L. 64517T: (01-800) 800-1968
Latin America790 N.W. 107th Avenue, Suite 200, Miami, Fl 33172 USAT: +1 305 551 5155
ChileVespucio Norte, Avenida Presidente Eduardo FreiMontalva 6001, Edificio N° 66Comuna: Conchalí, Sector el Cortijo, SantiagoT: (56 2) 928-4700
Latin America
USA41 Woodford Avenue, Plainville CT, USA 06062and12305 Kurland Drive, Houston, TX USA 77034T: +1 800-431-7867
North America
GE Industrial Solutions
Printing Code: IN201301B20EN
© Copyright GE Industrial Solutions 2013
For more information, please visitwww.geindustrial.com
You may be interested in other MV Seco-family productsFor more information, please visit www.geindustrial.com