95 NTE Electronics, Inc. Voice (973) 7485089 FAX (973) 7486224 http://www.nteinc.com Circuit Breakers R185 Series Features Type III Manual Reset with PushtoTrip Switch Water Resistant, Splash and Dust Proof Housing Single Pole, Thermal Device Surface Mount, Protective Stud Insulator Included Typically Used in DC Power Systems in Marine, Truck, and RV Applications. Add On Protection for Accessories NTE Type No. Current Rating Amps NTE Type No. Current Rating Amps R18525A 25 R18580A 80 R18530A 30 R18590A 90 R18535A 35 R185100A 100 R18540A 40 R185120A 120 R18550A 50 R185130A 130 R18560A 60 R185140A 140 R18570A 70 R185150A 150 Trip Times Rated Load Trip Times 100% Hold, No Trip within 30 Minutes 150% Trip within 30 Minutes 200% Trip in12 45 Seconds 300% Trip in 3.5 12 Seconds Thermal Circuit Breaker, Hydraulic and HiAmp Protector D94 2.913 (74.0) 2.244 (57.0) 1.445 (36.7) 1.819 (46.2) .197 (5.0) 1.913 (48.6) 1.063 (27.0) .264 (6.7) Dia. (2 Places) 1/428 Thread (2 Places) Molded Cover Reset Lever Electrical Specifications Electrical Characteristics Rating: 25A to 150A @ 32 VDC Interrupt Rating: 2000 Amps @ 32 VDC Insulation Resistance: 100 megohms @ 500 VDC Dielectric Strength: 1800V, 1 minute Mechanical Characteristics Termination: 1/428 threaded stud Mounting: Surface Mount Environmental Characteristics Operating: 32 C to +82 C Storage: 34 C to +149 C

Upload: others

Post on 09-May-2020

6 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: R185 Series Thermal Circuit Breakers | Relays | NTE ...Circuit Breakers R185 Series Features Type III Manual Reset with Push−to−Trip Switch Water Resistant, Splash and Dust Proof

95NTE Electronics, Inc. Voice (973) 748−5089 FAX (973) 748−6224 http://www.nteinc.com

Circuit BreakersR185 Series

FeaturesType III Manual Reset with Push−to−Trip SwitchWater Resistant, Splash and Dust Proof HousingSingle Pole, Thermal DeviceSurface Mount, Protective Stud Insulator IncludedTypically Used in DC Power Systems in Marine, Truck, and RVApplications. Add On Protection for Accessories

NTE Type No.Current Rating

Amps NTE Type No.Current Rating

Amps

R185−25A 25 R185−80A 80

R185−30A 30 R185−90A 90

R185−35A 35 R185−100A 100

R185−40A 40 R185−120A 120

R185−50A 50 R185−130A 130

R185−60A 60 R185−140A 140

R185−70A 70 R185−150A 150

Trip TimesRated Load Trip Times

100% Hold, No Trip within 30 Minutes

150% Trip within 30 Minutes

200% Trip in12 − 45 Seconds

300% Trip in 3.5 − 12 Seconds

Thermal Circuit Breaker, Hydraulicand Hi−Amp ProtectorD94

2.913(74.0)

2.244(57.0)

1.445(36.7)

1.819(46.2)

.197(5.0)

1.913 (48.6)

1.063 (27.0)

.264 (6.7) Dia.(2 Places)

1/4−28 Thread(2 Places)

Molded Cover

Reset Lever

Electrical SpecificationsElectrical CharacteristicsRating: 25A to 150A @ 32 VDCInterrupt Rating: 2000 Amps @ 32 VDCInsulation Resistance: 100 megohms @ 500 VDCDielectric Strength: 1800V, 1 minute

Mechanical CharacteristicsTermination: 1/4−28 threaded studMounting: Surface Mount

Environmental CharacteristicsOperating: −32 C to +82 CStorage: −34 C to +149 C