Energex Register of Completed Embedded Generator Projects > 200 kW

July 2014 - June 2019

Energex Register of Completed Projects

Version Control

Version Date Description

1.0 29/10/2016 Initial

2.0 19/09/2017 2017 update

3.0 15/10/2018 2018 update

4.0 04/10/2019 2019 update

Contact details Energex Limited Customer Connections Planning Manager Phone: 13 12 53 Email: [email protected]

GPO Box 1461 Brisbane QLD 4001 26 Reddacliff Street Newstead QLD 4006 Telephone 13 12 53 www.energex.com.au

Energex Limited ABN 40 078 849 055

© Energex Limited 2015 ® Energex and Energex Positive Energy are registered trademarks of Energex Limited ABN 40 078 849 055

This work is copyright. Material contained in this document may be reproduced for personal, in-house or non-commercial use, without formal permission or charge, provided there is due acknowledgement of Energex Limited as the source. Requests and enquiries concerning reproduction and rights for a purpose other than personal, in-house or non-commercial use, should be addressed to the Group Manager Corporate Communications, Energex, GPO Box 1461 Brisbane QLD 4001.

Energex Register of Completed Projects

Contents

1 Introduction ........................................................................................................ 1

2 Purpose of this Register ................................................................................... 1

3 Details included in the Register ........................................................................ 1

4 More Information ............................................................................................... 1

5 Project Register ................................................................................................. 2

6 Single Line Diagram Types ............................................................................... 6

7 Protection Schemes and Requirements .......................................................... 9

8 PQ Voltage and Power Factor Control ........................................................... 10

9 Fault Level Contribution Factor ...................................................................... 10

Energex Register of Completed Projects P a g e | 1

1 Introduction

This register of completed embedded generation projects has been developed to improve the level of technical information available, on projects that have been successfully connected to Energex’s distribution network.

2 Purpose of this Register

Under Chapters 5 and 5A of the National Electricity Rules, Energex is required to publish a register of completed embedded generation projects. This register:

• includes details of all embedded generation projects (i.e. for systems with a generation capacity of 200 kW or greater) completed within the preceding five year period; and

• Update annually for all completed projects in the 5 year period preceding the review date.

3 Details included in the Register

A register of the plant of completed embedded generation projects includes, but is not limited to:

• technology of generating unit (e.g. synchronous generating unit, induction generator, photovoltaic array, etc) and it’s make and model;

• maximum power generation capacity of all embedded generating units comprised in the relevant generating system;

• contribution to fault levels;

• the size and rating of the relevant transformer;

• a single line diagram of the connection arrangement;

• protection systems and communication systems;

• voltage control and reactive power capability; and

• details specific to the location of a facility connected to the network that are relevant to any of the details in the bullet points above.

4 More Information

For more information about the embedded generation projects, please contact us: Email - [email protected] Phone - 13 12 53

Energex Register of Completed Projects P a g e | 2

5 Project Register

Year Completed Location

Network Connection

Voltage (kV)

Technology of generating unit

(e.g. synchronous

generating unit, induction

generator, photovoltaic

array, etc) and its make and

model

Generator Unit details (Make and Model) Generator

Voltage Level (kV)

Maximum power generation

capacity of all embedded

generating units comprised in the

relevant generating system (kw)

Contribution to fault

levels (kA)

The size and rating of the relevant transformer

(Voltages & kVA)

A single line diagram of

the connection

arrangement (Refer

Section 6)

Protection systems and communication systems

(Refer Section 7)

Voltage control, power factor control and/or reactive power capability (Refer Section 8)

Details specific to the location of

a facility connected to the

network, that are relevant to

any of the details

2013/14 South Brisbane 11 Synchronous

generation unit 2 x 3MVA Gas Jenbacher 616 GS, 4 x 3.0MVA Diesel MTU 20V400G63L 11 4800 3.1 N/A Type 2 Level 2 0.9 lagging to 0.9 leading Non-Export

2014/15 Mt Cotton 0.4 Solar photovoltaic array

8 x SMA STP20000TL, 2 x SMA STP10000TL 0.4 200 0.33 11/0.415kV 750kVA Type 4 Level 1 Between at least 0.80 lagging to

0.80 leading Non-Export

2015/16 Kenmore 0.4 Solar photovoltaic array

8 x 25kW Schneider Conext CL-20/25E 0.4 200 0.33 11/0.415kV 1000kVA Type 4 Level 1 & 2 Between at least 0.80 lagging to 0.80 leading Non-Export

2015/16 Wacol 0.4 Synchronous & induction generator

1 X 750 Diesel Stamford MX341 0.4 750 7.3 11/0.415kV 1000kVA Type 4 Level 1 & 2 Between at least 0.80 lagging to 0.80 leading Non-Export

2015/16 Churchill 0.4 Solar photovoltaic array

12 x SMA Sunny TriPower 60 Inverters 0.4 720 1.203 11/0.415kV 1500kVA Type 4 Level 1 Between at least 0.80 lagging to 0.80 leading Non-Export

2015/16 Strathpine 0.4 Synchronous generation unit 1 x 720kW Diesel Caterpillar 0.4 720 7.99 11/0.415kV 750kVA Type 3 Level 1 Between at least 0.80 lagging to

0.80 leading Non-Export

2015/16 Wacol 0.4 Solar photovoltaic array

2 x Fronius AGILO 100.0-3 0.4 200 0.33 11/0.415kV 1500kVA Type 4 Level 1 Between at least 0.80 lagging to 0.80 leading Non-Export

2015/16 Robina 11 Synchronous Generator unit 2 X 1.12 MW Cummins 1400kVA D5 0.415 2800 1.03 11/0.415kV 1500kVA Type 1 Level 1 and

2 0.9 lagging to 0.9 leading Non-Export

2016/17 South Brisbane 0.4 Synchronous

Generator unit Meccalte Eco 43-2SN/4 0.4 1100 8.6 11/0.415kV 1500kVA Type 1 Level 2 Between at least 0.80 lagging to 0.80 leading Non-Export

2016/17 Brendale 0.4 Solar photovoltaic array

Inverters 15 X ABB TRIO-50.0-TL 0.4 750 1.5 11/0.415kV 1500kVA Type 4 Level 1 Between at least 0.80 lagging to 0.80 leading Non-Export

2016/17 Valdora 33 Solar photovoltaic array

6 x SMA 2500-EV 0.55 15000 0.325 N/A Type 5 Level 2 Voltage, power factor & reactive power control Non-Export

2016/17 Springfield Central 11

Solar photovoltaic array

36 x ECO 25: 37.57 KWdc & SYMO 20.0: 26.4 kW de & SYMO 10.0: 21.6kW de

0.4 380 1.6 11/0.415kV 1500kVA Type 1 Level 2 Between at least 0.80 lagging to 0.80 leading Full Export

2016/17 Hemmant 0.4 Solar photovoltaic array

9x27.6kW Solar Edge 0.4 248 0.49 11/0.415kV 500kVA Type 4 Level 1 Between at least 0.80 lagging to 0.80 leading Non-Export

2017/18 South Brisbane 0.4 Synchronous

generating units 1 x 500kVA Diesel, 1 x 250kVA Diesel 0.4 1750 N/A, Non Parallel 11/0.415kV Type 3 Level 1 Between at least 0.80 lagging to

0.80 leading Non-Export

Energex Register of Completed Projects P a g e | 3

Year Completed Location

Network Connection

Voltage (kV)

Technology of generating unit

(e.g. synchronous

generating unit, induction

generator, photovoltaic

array, etc) and its make and

model

Generator Unit details (Make and Model) Generator

Voltage Level (kV)

Maximum power generation

capacity of all embedded

generating units comprised in the

relevant generating system (kw)

Contribution to fault

levels (kA)

The size and rating of the relevant transformer

(Voltages & kVA)

A single line diagram of

the connection

arrangement (Refer

Section 6)

Protection systems and communication systems

(Refer Section 7)

Voltage control, power factor control and/or reactive power capability (Refer Section 8)

Details specific to the location of

a facility connected to the

network, that are relevant to

any of the details

2017/18 HillcreStreet 0.4

Solar photovoltaic array

8 x SMA STP25000TL-30 0.4 200 0.33 11/0.415kV 1500kVA Type 4 Level 1 Unity power factor Non-Export

2017/18 Loganholme 0.4

Solar photovoltaic array

8 x Schneider CL25000E 0.4 200 0.34 11/0.415kV 750kVA Type 4 Level 1 Between at least 0.80 lagging to 0.80 leading Non-Export

2017/18 Burleigh Waters 0.4

Solar photovoltaic array

10 X ABB Trio Trio-TM-50.0-400 52000W 0.4 500 0.6 11/0.415kV 1000kVA Type 4 Level 1 Between at least 0.80 lagging to

0.80 leading Non-Export

2017/18 Stapylton 0.4 Solar photovoltaic array

27 x Delta RPI M30A 0.4 800 1.33 2 x 11/0.415kV 1500kVA Type 4 Level 1 Between at least 0.80 lagging to 0.80 leading Partial Export

2017/18 Thornlands 0.4 Solar photovoltaic array

10 x Schneider CL25000E 0.4 250 0.42 11/0.415kV 500kVA Type 4 Level 1 Between at least 0.80 lagging to 0.80 leading Non-Export

2017/18 Burpengary East 0.4

Solar photovoltaic array

Multiple inverters 0.4 236 0.44 11/0.415kV 750kVA Type 4 Level 1 Between at least 0.80 lagging to 0.80 leading Full Export

2017/18 Petrie 0.4 Synchronous generation unit 1 x 511kVA Diesel powered generator 0.4 511 5 11/0.415kV 750kVA Type 3 Level 1 Between at least 0.80 lagging to

0.80 leading Non-Export

2017/18 Indooroopilly 0.4

Solar photovoltaic array

3 X Solaredge SE17K 14 X Solaredge SE27.6K 0.4 438 0.73 11/0.415kV 750kVA Type 4 Level 1 Between at least 0.80 lagging to

0.80 leading Non-Export

2017/18 Auchenflower 0.4 Synchronous

generation unit MTU Cummins 0.4 850 7.7 11/0.415kV 1000kVA Type 4 Level 1 Fixed power factor 0.85 Full Export

2017/18 Kallangur 0.4 Solar photovoltaic array

Inverters 12 X FRONIUS SYMO 20.0-3 0.4 240 0.4 11/0.415kV 750kVA Type 4 Level 1 Between at least 0.80 lagging to 0.80 leading Non-Export

2017/18 Caboolture 0.4 Solar photovoltaic array

9 x ABB Trio-TM-50.0-400 50kW 0.4 450 0.751 11/0.415kV 1500kVA Type 4 Level 1 Between at least 0.80 lagging to 0.80 leading Partial Export

2017/18 Willawong 0.4 Synchronous generating unit Honny Power, Genset Model: HGM775C 0.4 775 6.48 11/0.415kV 750kVA Type 3 Level 1 Between at least 0.80 lagging to

0.80 leading Non-Export

2018/19 Forest Glen 0.4 Solar photovoltaic array

5 x SMA STP 60-10, 3 X Schneider Inverters CL25000E 0.4 375 0.63 11/0.415kV 1000kVA Type 4 Level 1 Volt-var as per STNW1174 Partial Export

2018/19 Somerset Dam 33 Hydro generator 1 X Baster DECS250 AVR and

Rivermaster Governor 11 4336 3.4 33/11kV 5000kVA Type 5 Level 2 Protection

Between 0.9 lagging and 0.9 leading Full Export

2018/19 Hope Island 0.4

Solar photovoltaic array

5 x Power One PVS-100-TL 0.4 500 0.77 11/0.415 Type 4 Level 1 Volt-var as per STNW1174 Non-Export

Energex Register of Completed Projects P a g e | 4

Year Completed Location

Network Connection

Voltage (kV)

Technology of generating unit

(e.g. synchronous

generating unit, induction

generator, photovoltaic

array, etc) and its make and

model

Generator Unit details (Make and Model) Generator

Voltage Level (kV)

Maximum power generation

capacity of all embedded

generating units comprised in the

relevant generating system (kw)

Contribution to fault

levels (kA)

The size and rating of the relevant transformer

(Voltages & kVA)

A single line diagram of

the connection

arrangement (Refer

Section 6)

Protection systems and communication systems

(Refer Section 7)

Voltage control, power factor control and/or reactive power capability (Refer Section 8)

Details specific to the location of

a facility connected to the

network, that are relevant to

any of the details

2018/19 Dalby 33 Synchronous generation unit 2 x Caterpillar V12 370kW Gas Fuelled 11 700 56 N/A Type 2 Level 1 & 2 Between 0.9 lagging and 0.9

leading Full Export

2018/19 Wacol 0.4 Solar Photovoltaic Array

Inverters 97 x Fronius Eco 27.0-3-S 0.4 2619 4.5 9 x 11/0.415kV 1500kVA Type 4 Level 1 Between at least 0.80 lagging to 0.80 leading Non-Export

2018/19 Coomera 11 Solar Photovoltaic Array

73 x SolarEdge SE27.6K 0.4 2014 0.13 N/A Type 5 Level 1 Between at least 0.80 lagging to 0.80 leading Non-Export

2018/19 Carole Park 0.4

Solar Photovoltaic Array

2 x ABB-100-PVS 0.4 200 0.345 11/0.415kV 750kVA Type 4 Level 1 Between at least 0.80 lagging to 0.80 leading Non-Export

2018/19 Nerang 0.4 Solar Photovoltaic Array

4 x SMA STP 50-40 0.4 200 0.35 11/0.415kV 1000kVA Type 4 Level 1 Between at least 0.80 lagging to 0.80 leading Non-Export

2018/19 Brendale 0.4 Solar Photovoltaic Array

8 x SolarEdge SE82.8K 0.4 248 0.427 11/0.415kV 1500kVA Type 4 Level 1 Between at least 0.80 lagging to 0.80 leading Full Export

2018/19 North Lakes 0.4

Solar Photovoltaic Array

2 x Fronius SYMO 17.5-3-M, 2 x Fronius SYMO 20.0-3-M, 8 x Fronius ECO 27.0-3-S

0.4 291 0.504 11/0.415kV 750kVA Type 4 Level 1 Between at least 0.80 lagging to 0.80 leading Full Export

2018/19 Arundel 0.4 Solar Photovoltaic Array

10 x SMA STP25000TL-30 0.4 250 0.43 11/0.415kV 1000kVA Type 4 Level 1 Between at least 0.80 lagging to 0.80 leading Non-Export

2018/19 North Lakes 0.4

Solar Photovoltaic Array

34 x SolarEdge SE27.6K 0.4 938 1.63 11/0.415kV 1000kVA Type 4 Level 1 Between at least 0.80 lagging to 0.80 leading Non-Export

2018/19 Ascot 0.4 Solar Photovoltaic Array

13xFronius Eco 27.0-3-S 0.4 351 0.607 11/0.415kV 1000kVA Type 4 Level 1 Between at least 0.80 lagging to 0.80 leading Non-Export

2018/19 Morayfield 0.4 Solar Photovoltaic Array

6 x Fronius ECO 27.0-3-S + 5 x Fronius ECO 25.0-3-S 0.4 368 0.634 2 x 11/0.415kV 1000kVA Type 4 Level 1 Between at least 0.80 lagging to

0.80 leading Non-Export

2018/19 Birtinya 0.4 Solar Photovoltaic Array

18 X SolarEdge SE27.6K 0.4 496 0.856 11/0.415kV 1500kVA Type 4 Level 1 Between at least 0.80 lagging to 0.80 leading Partial Export

2018/19 Arana Hills 11 Synchronous generation unit

1 x 1.067MW Synchronous Machine Generator, land fill gas fuelled engine 0.4 1067 0.39 N/A Type 3 Level 1 Between at least 0.80 lagging to

0.80 leading Full Export

2018/19 Goodna 0.4 Synchronous generation unit Kohler KV375C2 0.4 300 3.03 11/0.415kV 500kVA Type 3 Level 1 Between at least 0.80 lagging to

0.80 leading Non-Export

2018/19 Narangba 0.4 Solar photovoltaic array

13 x SMA Sunny Tripower Core 1 - 50kW 0.4 650 1.13 11/0.415kV 1500kVA,

11/0.415kV 1000kVA Type 4 Level 1 Between at least 0.80 lagging to 0.80 leading Partial Export

Energex Register of Completed Projects P a g e | 5

Year Completed Location

Network Connection

Voltage (kV)

Technology of generating unit

(e.g. synchronous

generating unit, induction

generator, photovoltaic

array, etc) and its make and

model

Generator Unit details (Make and Model) Generator

Voltage Level (kV)

Maximum power generation

capacity of all embedded

generating units comprised in the

relevant generating system (kw)

Contribution to fault

levels (kA)

The size and rating of the relevant transformer

(Voltages & kVA)

A single line diagram of

the connection

arrangement (Refer

Section 6)

Protection systems and communication systems

(Refer Section 7)

Voltage control, power factor control and/or reactive power capability (Refer Section 8)

Details specific to the location of

a facility connected to the

network, that are relevant to

any of the details

2018/19 Redcliffe 0.4 Synchronous generation unit

1 x gas powered 970kW 415V synchronous AC generator, 2 x diesel 252kW, 415V standby generators

0.4 1871 18.9 2 x 11/0.415kV 1000kVA, 1 x 1500 Type 3 Level 1 Between at least 0.80 lagging to

0.80 leading Non-Export

2018/19 Pinkenba 11 Synchronous generation unit GE Jenbacher 3.3 1388 11.140 6000 Type 2 Level 1 Between at least 0.80 lagging to

0.80 leading Non-Export

2018/19 Eight Mile Plains 0.4 Synchronous

generation unit Stamford HC1434F/444F 0.4 320 3.23 11/0.415kV 500kVA Type 3 Level 1 Between at least 0.80 lagging to 0.80 leading Non-Export

2018/19 Nerang 0.4 Solar Photovoltaic Array

8 x SMA / STP25000TL-30 0.4 200 0.344 11/0.415kV 1500kVA Type 4 Level 1 Between at least 0.80 lagging to 0.80 leading Partial Export

2018/19 Coopers Plains 0.4

Solar Photovoltaic Array

10 x Schneider CL25000E 0.4 250 0.43 11/0.415kV 1500kVA Type 4 Level 1 Between at least 0.90 lagging to 0.90 leading Full Export

2018/19 Noosaville 0.4 Solar photovoltaic array

8 x SMA STP-25000TL-30 0.4 200 0.344 11/0.415kV Type 4 Level 1 Volt-var as per STNW1174 Full Export

2018/19 Cleveland 0.4 Solar Photovoltaic Array

4 x SolarEdge SE82.8K + 2 x SolarEdge 27.6K 0.4 386 0.666 11/0.415kV 1500kVA Type 4 Level 1 Between at least 0.80 lagging to

0.80 leading Full Export

2018/19 Chermside 0.4 Solar Photovoltaic Array

10 x Schneider CL25000-E 0.4 250 0.44 11/0.415kV 750kVA Type 4 Level 1 Between at least 0.80 lagging to 0.80 leading Non-Export

Energex Register of Completed Projects P a g e | 6

6 Single Line Diagram Types

Type 1 – High Voltage Connection with Low Voltage Generating System (Synchronous or Induction Machine, or IES)

Energex

Customer

HV Network

LV Generating system- Synchronous, Induction machine or- IES connected

Connection Point

Type 2 – High Voltage Connection with High Voltage Generating System (Synchronous or Induction Machine)

Energex

Customer

HV Network

HV Generating system

Connection Point

Energex Register of Completed Projects P a g e | 7

Type 3 – Low Voltage Connection with Low Voltage Generating System(Synchronous or Induction Machine)

Energex

Customer

HV Network

415V Generating system

Connection Point

Type 4 – Low Voltage Connection with Inverter Energy System (IES) e.g. Solar PV or Battery Energy Storage System

Energex

Customer

HV Network

LV IES connected Generating system

Connection Point

Energex Register of Completed Projects P a g e | 8

Type 5 – High Voltage Connection with Switching Statione.g. Transmission or sub transmission network

Energex

Customer

HV Network

Generating system- Synchronous, Induction machine or- IES connected

Network Coupling

Points

Connection Point

Auxiliary supply transformer

Energex Register of Completed Projects P a g e | 9

7 Protection Schemes and Requirements

Level 1 Backup Protection • Over and under voltage

• Over and under frequency

• Voltage vector shift and

• Rate of change of frequency

• Reverse Power

Level 2 Backup Protection • Neutral voltage detection/unbalance, or

• Direct intertrip from network circuit breaker (for systems above 200kW).

Energex Register of Completed Projects P a g e | 10

8 PQ Voltage and Power Factor Control

New connection standards have been published. Any new connections must adhere to the requirements under the STNW1174, Standard for the Connection of Embedded Generating Systems to a Distributor’s LV Network, or STNW1175, Standard for the Connection of Embedded Generating Systems to a Distributor’s HV Network, as relevant. For low voltage customers, pursuant to clause 36(2)(d) of the Electricity Regulation, Energex requires the Customer to ensure that the inverter operates in the volt-var requirements of STNW1174. This standard can be found on the Energex website, via Connections > Major Business Connections > Large Generation and Batteries. For high voltage customers, the power factor is to reflect the agreed voltage or power factor control arrangement. Please note connections must comply with the requirements set out in STNW1175, which can be found on the Energex website, via Connections > Major Business Connections > Large Generation and Batteries.

9 Fault Level Contribution Factor

Indicative fault level contribution from generating systems:

Generator Type Fault level contribution factor

Synchronous Generator unit 7 X Rating

Solar/Inverter Generator unit 1.2 X Rating

Energex Register of Completed Projects P a g e | 11