regulating valve

Upload: mohammed-hassan-b-koraina

Post on 01-Mar-2018

233 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/25/2019 Regulating Valve

    1/18

    Regulator Application & Installation Notes

    The following are considerations for all steam regulator installations, as system operation is dependent uponproper design, installation, start-up and maintenance procedures:

    REGULATING VALVE APPLICATIONS

    GENERAL REGULATOR APPLICATION & INSTALLATION NOTES

    ENGINEERING

    296428 Jones Boulevard Limerick Airport Business Center Pottstown PA 19464 Tel: 610-495-5131 Fax: 610-495-5134

    www.watsonmcdaniel.com

    Inlet & Outlet Pipe Sizing

    Improperly sized piping can contribute to erraticcontrol and excessive noise in a steam system.Make certain inlet and outlet piping to the regulatoris adequately sized for the flow, velocity andpressure requirements.

    RULE OF THUMB:Inlet piping is typically 1-2 sizes larger and outletpiping 2-3 sizes larger than the connection portsof a properly sized regulator.

    Straight Run of Pipe Before and After the Valve

    Pipe fittings, bends and other accessories contributeto fluid turbulence in a system which can result inerratic control. To limit this and ensure optimumsystem operation, follow recommended guidelinesfor minimum straight run lengths of pipe before andafter a regulator.

    Note: Any isolation valves or pipeline accessoriesshould be full-ported.

    Reducer Selection

    Concentric pipe reducers should be avoidedon the inlet side of regulators as they can allowentrained condensate to collect, potentially

    leading to damaging and dangerous waterhammer.Therefore, when reducers are required in the steampiping to accommodate properly sized valves andpipes, use eccentric reducers on regulator inletsand concentric or eccentric reducers on regulatoroutlets.

    10 PIPEDIAMETERS

    MINIMUM

    10 PIPEDIAMETERS

    MINIMUM

    1-2 SIZESLARGER THANREGULATORINLET PORT

    2-3 SIZESLARGER THANREGULATOR

    OUTLET PORT

    CONCENTRIC REDUCER

    ECCENTRIC REDUCER

    STEAM

    STEAM

    CONDENSATEACCUMULATED ATLOW POINT

    REGULATOR

  • 7/25/2019 Regulating Valve

    2/18

    REGULATING VALVE APPLICATIONS

    GENERAL REGULATOR APPLICATION & INSTALLATION NOTES

    Strainers with Blowdown Valves

    Regardless of any filters provided on a regulator, astrainer with blowdown valve is recommended before(upstream of) all regulator installations. Pipeline

    debris and scale can damage internal valvecomponents, potentially leading to poor operationand/or failure.

    Note: Consider strainer orientation to avoidcollection of condensate (see diagram).

    Drip Legs & Steam Traps

    To prevent condensate accumulated duringshutdown from possibly damaging the regulator orpiping at start-up, an adequately sized drip leg withsteam trap should be installed prior to all regulators.This will also help protect the regulator duringnormal operation.

    Note: Separators may be necessary when boilercarryover or wet steam is a concern.

    Proper Start-up & Maintenance Procedures

    It is important to follow good start-up practicesto avoid operational complications and potentialsystem damage. Starting a steam system tooquickly or using an improper sequence may lead

    to a potentially hazardous working environment.Lack of system maintenance over time can alsocontribute to this situation.

    It is imperative to develop proper start-up andmaintenance procedures and train personnel onthe importance of following them at all times.

    Consult equipment manufacturers for specificguidelines, if necessary.

    29428 Jones Boulevard Limerick Airport Business Center Pottstown PA 19464 Tel: 610-495-5131 Fax: 610-495-5134

    www.watsonmcdaniel.com

    BLOWDOWN VALVE ORIENTED ATSAME ELEVATION AS STRAINER PORTSTO AVOID CONDENSATE COLLECTION

    BLOWDOWN VALVEBELOW STRAINER PORTS

    INLETPORT

    OUTLETPORT

    DRIP

    LEG

    STEAMTRAP

    DRAIN VALVE

  • 7/25/2019 Regulating Valve

    3/18

    ENGINEERING

    298428 Jones Boulevard Limerick Airport Business Center Pottstown PA 19464 Tel: 610-495-5131 Fax: 610-495-5134

    www.watsonmcdaniel.com

    REGULATING VALVE APPLICATIONS

    SINGLE STAGE PRESSURE REDUCING STATION USING SPRING-LOADED PILOT

    PURPOSE: For reducing system inlet pressure to a constant outlet pressure.

    OPERATION: The pressure reducing valve (PRV) can be easily adjusted to set the desired outlet pressure and

    modulates to maintain that pressure setting. The PRV requires no external power source.

    INSTALLATION GUIDELINES: (see Figure 8)

    This example depicts a pilot-operated steam PRV, whereby an external sensing line is required to sensedownstream pressure. The end of the sensing line is placed away from the turbulent flow of the valve outlet.This helps to improve accuracy of the set pressure. Set pressure is adjusted by turning a screw on the pilot

    to increase or decrease compression on a balancing spring.

    For optimum operation and service life, maintain recommended minimum piping straight runs before andafter the PRV. Inlet pipe diameters are typically 1-2 sizes larger and outlet pipe diameters 2-3 sizes larger

    than the end connections of an appropriately sized PRV. The purpose of increasing the pipe size downstream

    of the regulator is to keep the steam velocity constant on both sides of the regulator.

    The pressure sensing line should slope downwards, away from the regulator, to prevent condensate from

    entering the pilot.

    Eccentric reducers are used on valve inlets to prevent accumulation of pipeline moisture which could becomeentrained with high-velocity steam, possibly resulting in dangerous waterhammer.

    While the separator shown upstream is appropriate for protection of the PRV, it is not always required as a

    properly sized drip leg with steam trap may be sufficient. It is recommended for systems where steam is knownto be wet and the entrained moisture could affect valve performance and/or result in component damage.

    Consider installing a properly sized bypass line with globe valve to provide continuous operation should

    regulator maintenance be required.

    Consider low-cracking pressure (1/4 PSI opening pressure) check valves after steam traps when discharginginto condensate return lines. Check valves eliminate the possibility of condensate backing up through the

    steam trap into the system.

    A safety relief valve (SRV) is appropriate where applicable codes dictate their requirement, or anywhereprotection of downstream piping and equipment from over-pressurization is desired. The SRV needs to handle

    the complete volume of steam from the regulator and bypass loop. Consult the factory for appropriate SRVsizing guidelines.

  • 7/25/2019 Regulating Valve

    4/18

    SIN

    GLESTAGEPRESSUREREDUCINGSTATIONUSING

    SPRING-LOADEDPILOT

    (HDREGULATORAPPLICATIONS

    )

    GATE

    VALVE

    STEAM

    TRAP

    DRIP

    PAN

    ELBOW

    ISOLATION

    VALVE

    CHEC

    K

    VALV

    E

    IS

    OLATION

    VALVE

    CHECK

    VALVE

    ISOLATION

    VALVE

    STEAM

    TRAP

    GATE

    VALVE

    ISOLATION

    VALVE

    ISOLATION

    VALVE

    CHECK

    VALVE

    ISOLATION

    VALVE

    STEAM

    TRAP

    STRAINER

    STRAINER

    STRAINER

    HDPREG

    ULATOR

    VENT

    S

    RV

    STEAM

    INLET

    SEPARATO

    R

    APPLICATION

    DEPENDENT

    PRESSURE

    SENSING

    LINE

    STRAINER

    10PIPE

    DIAMETERSMINIMUM

    BYPASS

    GLOBE

    VALVE

    10PIPE

    DIAMETERSMINIMUM

    TOCONDEN

    SATE

    RETURN

    TOCONDENSATE

    RETURN

    TO

    CONDENSATE

    RETURN

    29428 Jones Boulevard Limerick Airport Business Center Pottstown PA 19464 Tel: 610-495-5131 Fax: 610-495-5134

    www.watsonmcdaniel.com

    REGULATING VALVE APPLICATION

    SINGLE STAGE PRESSURE REDUCING STATION USING SPRING-LOADED PILO

    DRAIN

    VALVE

    ECCENTRIC

    REDUCER

    CONCENTRIC

    REDUC

    ER

    Figure 8:

    DRAIN

    VALVE

    STEAM

    OUTLET

  • 7/25/2019 Regulating Valve

    5/18

    REGULATING VALVE APPLICATIONS

    PRESSURE REDUCING STATION with AIR-LOADED PILOT for REMOTE INSTALLATIONS

    PURPOSE: For reducing system inlet pressure to a constant outlet pressure when valve is located in a remotelocation and/or using air pressure for control is desired.

    OPERATION: This combination of HD regulating valve and A-pilot (HDA) allows air to be used to control outletpressure in lieu of the spring of a standard P-pilot. Using air allows for simple adjustment of controlpressure when valve is installed in a remote and/or difficult to access location.

    INSTALLATION GUIDELINES: (see Figure 9)

    The desired set outlet pressure will determine the specific A-Pilot required as well as the air supply pressureto attain the set pressure. Consult the appropriate section of this catalog or the factory for selection guidelines.

    For optimum operation and service life, maintain recommended minimum piping straight runs before and

    after the PRV. Inlet pipe diameters are typically 1-2 sizes larger and outlet pipe diameters 2-3 sizes largerthan the end connections of an appropriately sized PRV. The purpose of increasing the pipe size downstream

    of the regulator is to keep the steam velocity constant on both sides of the regulator.

    The pressure sensing line should slope downwards, away from the regulator, to prevent condensate fromentering the pilot.

    Eccentric reducers are used on valve inlets to prevent accumulation of pipeline moisture which could become

    entrained with high-velocity steam, possibly resulting in dangerous waterhammer.

    While the separator shown upstream is appropriate for protection of the PRV, it is not always required, as aproperly sized drip leg with steam trap may be sufficient. It is recommended for systems where steam is knownto be wet and the entrained moisture could affect valve performance and/or result in component damage.

    Consider installing a properly sized bypass line with globe valve to provide continuous operation shouldregulator maintenance be required.

    Consider low-cracking pressure (1/4 PSI opening pressure) check valves after steam traps when discharging

    into condensate return lines. Check valves eliminate the possibility of condensate backing up through thesteam trap into the system.

    A safety relief valve (SRV) is appropriate where applicable codes dictate their requirement, or anywhereprotection of downstream piping and equipment from over-pressurization is desired. The SRV needs to handle

    the complete volume of steam from the regulator and bypass loop. Consult the factory for appropriate SRVsizing guidelines.

    300428 Jones Boulevard Limerick Airport Business Center Pottstown PA 19464 Tel: 610-495-5131 Fax: 610-495-5134

    www.watsonmcdaniel.com

    ENGINEERING

  • 7/25/2019 Regulating Valve

    6/18

    PRESSU

    REREDUCINGSTATIONw

    ithAIR-LOADEDPILOTforREMOTEINSTALLATIONS

    (HDREGULATORAPPLICATIONS)

    SEPARATOR

    TOCONDEN

    SATE

    RETURN

    HDA

    REGULA

    TOR

    CHECK

    VALVE

    STEAM

    INLET

    CHECK

    VALVE

    CHECK

    VALVE

    ISOLATION

    VALVE

    IS

    OLATION

    VALVE

    ISOLATION

    VALVE

    ISOLATION

    VAL

    VE

    STEAM

    TRAP

    STEAM

    TRAP

    ISOLATION

    VALVE

    ISOLATION

    VALVE

    STRAINER

    STRAINER

    STRAINER

    GATE

    VALVE

    GATE

    VALVE

    DRIP

    PAN

    ELBOW

    DRAIN

    VALVE

    DRAIN

    VALVE

    VENT

    S

    RV

    BYPASS

    GLOBE

    VALVE

    10PIPE

    DIA

    METERSMINIMUM

    10PIPE

    DIAM

    ETERSMINIMUM

    PL2

    AIRSUPPLY

    CONTROL

    AIRLINE

    STEAM

    TRAP

    STR

    AINER

    TO

    CONDENSATE

    RETURN

    TOCONDENSATE

    RETURN

    PRESSURE

    SENSINGLINE

    AIR

    REGULATOR

    REGULATING VALVE APPLICATIONS

    PRESSURE REDUCING STATION with AIR-LOADED PILOT for REMOTE INSTALLATIONS

    Figure 9:

    30428 Jones Boulevard Limerick Airport Business Center Pottstown PA 19464 Tel: 610-495-5131 Fax: 610-495-5134

    www.watsonmcdaniel.com

    STEAM

    OUTLET

    APPLICATION

    DEPENDENT

    A

    PILOT

  • 7/25/2019 Regulating Valve

    7/18

    REGULATING VALVE APPLICATIONS

    TWO-STAGE (SERIES) PRESSURE REDUCING STATION

    302428 Jones Boulevard Limerick Airport Business Center Pottstown PA 19464 Tel: 610-495-5131 Fax: 610-495-5134

    www.watsonmcdaniel.com

    PURPOSE: For reducing system inlet pressure to a constant outlet pressure when the pressure drop exceedsthe recommended operation of a single-stage pressure regulating valve (PRV).

    OPERATION: The 1st stage PRV reduces inlet pressure to an intermediate pressure. The 2nd stage PRV thenreduces pressure to the final outlet pressure. Individual valve setting and operation is the sameas for single-stage applications.

    INSTALLATION GUIDELINES: (see Figure 10)

    This example depicts a two-stage (series) pilot-operated steam PRV pressure reducing station using HDP regulatorsAn external sensing line is required to sense downstream pressure from each regulator. The end of each sensingline is placed away from the turbulent flow at the valve outlet. This helps to improve accuracy of the set pressures.

    Set pressure for each PRV is adjusted by turning a screw on the pilot to increase or decrease compression on abalancing spring.

    For optimum operation and service life, maintain recommended minimum piping straight runs before and

    after the PRV. Inlet pipe diameters are typically 1-2 sizes larger and outlet pipe diameters 2-3 sizes largerthan the end connections of an appropriately sized PRV. The purpose of increasing the pipe size downstream

    of the regulator is to keep the steam velocity constant on both sides of the regulator.

    Each pressure sensing line should slope downwards, away from the regulator, to prevent condensate fromentering the pilot.

    Eccentric reducers are used on valve inlets to prevent accumulation of pipeline moisture which could become

    entrained with high-velocity steam, possibly resulting in dangerous waterhammer.

    While the separator shown upstream is appropriate for protection of the PRV, it is not always required, as aproperly sized drip leg with steam trap may be sufficient. It is recommended for systems where steam is known

    to be wet and the entrained moisture could affect valve performance and/or result in component damage.

    Consider installing a properly sized bypass line with globe valve on each stage, to provide continuous operationshould regulator maintenance be required.

    Consider low-cracking pressure (1/4 PSI opening pressure) check valves after steam traps when discharging

    into condensate return lines. Check valves eliminate the possibility of condensate backing up through thesteam trap into the system.

    A safety relief valve (SRV) is appropriate where applicable codes dictate their requirement, or anywhere

    protection of downstream piping and equipment from over-pressurization is desired. The SRV needs to handlethe complete volume of steam from the regulator and bypass loop. Consult the factory for appropriate SRVsizing guidelines.

    ENGINEERING

  • 7/25/2019 Regulating Valve

    8/18

    STEAM

    TRAP

    DRIP

    PAN

    ELBOW

    STEAM

    TRAP

    VENT

    SRV

    SEPARATOR

    APPLICATION

    DEPENDENT

    BYPASS

    GLOBE

    VALVE

    GATE

    VALVE

    STEAM

    TRAP

    ISOLATION

    VALVE

    CHECK

    VALVE

    GATE

    VALVE

    GATE

    VALVE

    STRAINER

    PRESSURE

    SENSING

    LINE

    GATE

    VALVE

    STRAINER S

    TEAM

    TRAP

    TO

    CONDENSATE

    RETURN

    ISOLATIO

    N

    VALVE

    BYPASS

    GLOBE

    VALVE

    STEAM

    INLET

    TOCONDENSATE

    RETURN

    TOCONDENSATE

    RETURN

    HDP

    REGULATOR1

    0PIPE

    DIAMETERS

    MINIMUM

    10PIPE

    DIAMETERS

    MINIMUM

    10PIPE

    DIAMETERS

    MINIMUM

    20PIPE

    DIAMETERSMINIMUM

    REGULATING VALVE APPLICATIONS

    TWO-STAGE (SERIES) PRESSURE REDUCING STATION

    Figure 10:

    30428 Jones Boulevard Limerick Airport Business Center Pottstown PA 19464 Tel: 610-495-5131 Fax: 610-495-5134

    www.watsonmcdaniel.com

    DRAIN

    VALVE

    DRAIN

    VALVE

    HDP

    REGULATOR

    PRESSURE

    SENSINGLINE

    DRAIN

    VALVE

    TWO-STAGE(SERIES)PRESSUREREDUCING

    STATION

    (HDREGULATORAPPLICATIONS)

    2ndStage

    1stStage

    STEAM

    OUTLET

    P

    PILOT

    PPILOT

  • 7/25/2019 Regulating Valve

    9/18

    REGULATING VALVE APPLICATIONS

    PARALLEL PRESSURE REDUCING STATION

    304428 Jones Boulevard Limerick Airport Business Center Pottstown PA 19464 Tel: 610-495-5131 Fax: 610-495-5134

    www.watsonmcdaniel.com

    PURPOSE: For reducing system inlet pressure to a constant outlet pressure when steam flow rates vary widely.

    OPERATION: Typically referred to as 1/3 - 2/3 system, one valve may be sized for 1/3 of the total load demand

    and the other for 2/3. When full load is required, both valves will be open and regulating. The primaryvalve is set at a pressure 2 PSI higher than the secondary valve to allow the secondary valve set atthe lower pressure to modulate closed when flow demand is reduced and outlet pressure begins to

    rise. The primary valve may be selected as either the larger or smaller PRV, based on expectedload demands.

    INSTALLATION GUIDELINES (see Figure 11)

    This example depicts a parallel pilot-operated steam PRV pressure reducing station using HDP regulators.

    An external sensing line is required to sense downstream pressure from each regulator. The end of each sensingline is placed away from the turbulent flow at the valve outlet. This helps to improve accuracy of the set pressures.

    Set pressure for each PRV is adjusted by turning a screw on the pilot to increase or decrease compression on abalancing spring.

    Proper setting of the valves is key to proper operation. The chosen primary valve should be set at a pressure

    approximately 2 PSI higher than that of the secondary valve.

    For optimum operation and service life, maintain recommended minimum piping straight runs before andafter the PRV. Inlet pipe diameters are typically 1-2 sizes larger and outlet pipe diameters 2-3 sizes largerthan the end connections of an appropriately sized PRV. The purpose of increasing the pipe size downstream

    of the regulator is to keep the steam velocity constant on both sides of the regulator.

    Each pressure sensing line should slope downwards, away from the regulator, to prevent condensate fromentering the pilot.

    Eccentric reducers are used on valve inlets to prevent accumulation of pipeline moisture which could becomeentrained with high-velocity steam, possibly resulting in dangerous waterhammer.

    While the separator shown upstream is appropriate for protection of the PRV, it is not always required, as a

    properly sized drip leg with steam trap may be sufficient. It is recommended for systems where steam is knownto be wet and the entrained moisture could affect valve performance and/or result in component damage.

    Consider installing a properly sized bypass line with globe valve to provide continuous operation shouldregulator maintenance be required.

    Consider low-cracking pressure (1/4 PSI opening pressure) check valves after steam traps when discharginginto condensate return lines. Check valves eliminate the possibility of condensate backing up through thesteam trap into the system.

    A safety relief valve (SRV) is appropriate where applicable codes dictate their requirement, or anywhereprotection of downstream piping and equipment from over-pressurization is desired. The SRV needs to handlethe complete volume of steam from the regulator and bypass loop. Consult the factory for appropriate SRV

    sizing guidelines.

    ENGINEERING

  • 7/25/2019 Regulating Valve

    10/18

    VENT

    SRV

    DRIP

    PAN

    ELBOW

    10PIPE

    DIAMETERSMINIMUM

    10PIPE

    DIAMETERSMINIMUM

    A

    PPLICATION

    D

    EPENDENT

    S

    EPARATOR

    GATE

    VALVE

    STEAM

    TRAP

    ISOLATION

    VALVE

    CH

    ECK

    VALVE

    STEAM

    TRAP

    TOCONDENSATE

    RETURN

    TO

    CONDENSATE

    RETURN

    TOCONDENS

    ATE

    RETURN

    ISOLATION

    VALVE

    STRAINER

    STEAM

    TRAP

    GATE

    VALVE

    BYPASS

    GLOBE

    VALVE

    ISOLATION

    VA

    LVE

    CHECK

    VALVE

    TOCONDENSATE

    RETURN

    SEPARATOR

    HDPREGULATOR

    STEAM

    INLET

    ISOLATION

    VALVE

    STRAINER

    STEAM

    TRAP

    PRESSURE

    SENSINGLINE

    STRAINER

    STRAINER

    REGULATING VALVE APPLICATIONS

    PARALLEL PRESSURE REDUCING STATION

    Figure 11:

    30428 Jones Boulevard Limerick Airport Business Center Pottstown PA 19464 Tel: 610-495-5131 Fax: 610-495-5134

    www.watsonmcdaniel.com

    PARAL

    LELPRESSUREREDUCINGSTATION

    (HDREGULATORAPPLICATIONS)

    Primary

    DRAIN

    VALVE

    DRAIN

    VALVEA

    PPLICATION

    D

    EPENDENT

    GATE

    VALVE

    GATE

    VALVE

    Secondary

    PRESSURE

    SENSINGLINE

    HDP

    RE

    GULATOR

    STEAM

    OUTLET

    P

    PILOT

    PPILOT

  • 7/25/2019 Regulating Valve

    11/18

    REGULATING VALVE APPLICATIONS

    TWO-STAGE PARALLEL PRESSURE REDUCING STATION

    306

    ENGINEERING

    PURPOSE: For reducing system inlet pressure to a constant outlet pressure when both flow conditions vary

    widely and a high pressure drop (i.e. higher than the recommended range of a single stage regulator)is required.

    OPERATION: This system is a combination of Two-Stage (Series) and Parallel pressure reducing stations and

    operates based on the individual principles of each system. This allows for accurate control of outletpressure when both high pressure and high flow turndowns are required.

    INSTALLATION GUIDELINES: (see Figure 12)

    This example depicts a two-stage parallel pilot-operated steam PRV pressure reducing station using HDP regulators

    An external sensing line is required to sense downstream pressure from each regulator. The end of each sensingline is placed away from the turbulent flow at the valve outlet. This helps to improve accuracy of the set pressures.

    Set pressure for each PRV is adjusted by turning a screw on the pilot to increase or decrease compression on abalancing spring.

    Proper setting of the valves is key to proper operation. The chosen 1st stage primary valve should be set at a

    pressure approximately 2 PSI higher than that of the 1st stage secondary valve.

    For optimum operation and service life, maintain recommended minimum piping straight runs before andafter the PRV. Inlet pipe diameters are typically 1-2 sizes larger and outlet pipe diameters 2-3 sizes largerthan the end connections of an appropriately sized PRV. The purpose of increasing the pipe size downstream

    of the regulator is to keep the steam velocity constant on both sides of the regulator.

    Each pressure sensing line should slope downwards, away from the regulator, to prevent condensate fromentering the pilot.

    Eccentric reducers are used on valve inlets to prevent accumulation of pipeline moisture which could becomeentrained with high-velocity steam, possibly resulting in dangerous waterhammer.

    While the separator shown upstream is appropriate for protection of the PRV, it is not always required, as a

    properly sized drip leg with steam trap may be sufficient. It is recommended for systems where steam is knownto be wet and the entrained moisture could affect valve performance and/or result in component damage.

    Consider installing a properly sized bypass line with globe valve on each stage, to provide continuous operationshould regulator maintenance be required.

    Consider low-cracking pressure (1/4 PSI opening pressure) check valves after steam traps when discharginginto condensate return lines. Check valves eliminate the possibility of condensate backing up through thesteam trap into the system.

    A safety relief valve (SRV) is appropriate where applicable codes dictate their requirement, or anywhere

    protection of downstream piping and equipment from over-pressurization is desired. The SRV needs to handle

    the complete volume of steam from the regulator and bypass loops. Consult the factory for appropriate SRVsizing guidelines.

    428 Jones Boulevard Limerick Airport Business Center Pottstown PA 19464 Tel: 610-495-5131 Fax: 610-495-5134

    www.watsonmcdaniel.com

  • 7/25/2019 Regulating Valve

    12/18

    REGULATING VALVE APPLICATIONS

    TWO-STAGE PARALLEL PRESSURE REDUCING STATION

    30

    VENT

    SRV

    DRIP

    PAN

    ELBOW

    10PIPE

    DIAMETERS

    MINIMUM

    APPLICATION

    DEPENDENT

    STEAM

    TRAP

    TOCONDENSATE

    RETURN

    STEAM

    TRAP

    BYPASS

    GLOBE

    VALVE

    SEPARATOR

    STEAM

    INLET

    BYPASS

    GLOBEVALVE

    SEPARATOR

    STEAM

    TRAP

    STEAM

    TRAP

    ISOLATION

    VALVE

    CHECK

    VALVE

    ISOLATION

    VALVE

    10PIPE

    DIAMETERS

    MINIMUM

    GATE

    VALVE

    HDP

    REGULATO

    R

    GATE

    VALVE

    GATE

    VALVE

    GA

    TE

    VALVE

    GATE

    VALVE

    GATE

    VALVE

    STEAM

    TRAP

    GATE

    VALVE

    GA

    TE

    VALVE

    20PIPE

    DIAMETER

    S

    MINIMUM

    TO

    CONDENSATE

    RETURN

    Figure 12:

    2ndStage

    1stStage

    T W O S T A G E P A R A L L E L P R E S S U R E R E D U C I N G

    S T A T I O NPR

    ESSURE

    SENSINGLINE

    PRESSURE

    SENSINGLINE

    Primary

    Secondary

    PRESSURE

    SENSINGLINE

    PRESSURE

    SENSINGLINE

    STRAINER

    HDP

    REGULATOR

    STRAINER

    HDP

    REGULATOR

    TOCONDENSATE

    RETURN

    HDP

    REGULA

    TOR

    TOCONDENSATE

    RETURN

    DRAIN

    VALVE

    DRAIN

    VALVE

    STRAINER

    DRAIN

    VALVE

    STEAM

    OUTLET

    PP

    ILOT

    P

    PILOT

  • 7/25/2019 Regulating Valve

    13/18

    REGULATING VALVE APPLICATIONS

    TEMPERATURE CONTROL of a HEAT EXCHANGER with PRESSURE LIMITING

    ENGINEERING

    PURPOSE: For accurately controlling both temperature of a product being heated in heat transfer equipmentas well as limiting the pressure of the incoming steam, providing optimum heat transfer characteristics

    OPERATION: When a pilot-operated HD valve is selected, a single valve can be used for both pressure and

    temperature control when equipped with a P-pilot and T-pilot (HDPT). As temperature at the sensingbulb falls below set point, the valve begins to modulate open to supply steam for heating. Supply

    pressure to the heat exchanger is then controlled by adjusting the pressure pilot to the recommendedvalue for optimum heat transfer and/or a limiting pressure of the heat transfer equipment. The HDPT

    Regulator requires no external power source.

    INSTALLATION GUIDELINES: (see Figure 13)

    The temperature and pressure pilots should be set individually, starting slowly and gradually with the T-pilot.

    Care should be given to the installation of the temperature sensing bulb to ensure full immersion in the liquid.The sensing bulb should be placed as close as possible to the heat exchanger vessel to ensure accurate

    temperature control of the process fluid.

    For optimum operation and service life, maintain recommended minimum piping straight runs before andafter the PRV. Inlet pipe diameters are typically 1-2 sizes larger and outlet pipe diameters 2-3 sizes larger

    than the end connections of an appropriately sized PRV. The purpose of increasing the pipe size downstreamof the regulator is to keep the steam velocity constant on both sides of the regulator.

    The pressure sensing line should slope downwards, away from the regulator, to prevent condensate from

    entering the pilot.

    Eccentric reducers, if required, are used on valve inlets to prevent accumulation of pipeline moisture which couldbecome entrained with high-velocity steam, possibly resulting in dangerous waterhammer.

    While the separator shown upstream is appropriate for protection of the PRV, it is not always required, as a

    properly sized drip leg with steam trap may be sufficient. It is recommended for systems where steam is knownto be wet and the entrained moisture could affect valve performance and/or result in component damage.

    Consider low-cracking pressure (1/4 PSI opening pressure) check valves after steam traps when discharging

    into condensate return lines. Check valves eliminate the possibility of condensate backing up through thesteam trap into the system.

    The vacuum breaker and auxiliary air vent located at the top of the heat exchanger vessel promotes proper

    drainage and optimum heat transfer. The vacuum breaker allows system equalization with atmospheric air toallow gravity condensate drainage when vacuum is formed from condensing steam. The air vent improvesheat-up times and overall heat transfer by expelling accumulated air on start-up.

    A safety relief valve (SRV) is appropriate where applicable codes dictate their requirement, or anywhere

    protection of downstream piping and equipment from over-pressurization is desired. Consult the factory for

    appropriate SRV sizing guidelines.

    308428 Jones Boulevard Limerick Airport Business Center Pottstown PA 19464 Tel: 610-495-5131 Fax: 610-495-5134

    www.watsonmcdaniel.com

  • 7/25/2019 Regulating Valve

    14/18

    REGULATING VALVE APPLICATIONS

    TEMPERATURE CONTROL of a HEAT EXCHANGER with PRESSURE LIMITING

    30

    APPLICATION

    DEPENDENT

    F&TTRAP

    F&T

    TRAP

    HEAT

    EXCHANGER

    HDPT

    REGU

    LATOR

    COLDWATER

    INLETS

    RV

    DRIPPAN

    ELBOW

    AV2000

    AIR

    VENT

    HOT

    WATER

    OUT

    LET

    WVBSS

    VACUUM

    BREAKER

    STEAM

    SUPPLY

    TE

    MPERATURECONTROLofaHEATEXCHANGERwith

    PRESSURELIMITING

    (HDRE

    GULATORAPPLICATIONS)

    Figure 13:

    428 Jones Boulevard Limerick Airport Business Center Pottstown PA 19464 Tel: 610-495-5131 Fax: 610-495-5134

    www.watsonmcdaniel.com

    SEPARATOR

    DRAIN

    VALVE

    DRAIN

    VALVE

    GATEVALVE

    STRAINER

    ISOLATION

    VALVE

    STRAINER

    ISOLATION

    VALVE

    TEMP

    ERATURE

    SENS

    INGBULB

    PRESSURE

    SENSINGLINE

    CAPILLARY

    T

    PILOT

    PPILOT

    VENT

  • 7/25/2019 Regulating Valve

    15/18

    ENGINEERING

    REGULATING VALVE APPLICATIONS

    AUTOMATIC TEMPERATURE CONTROL of a BATCH PROCESSwith Electrical Time Sequence Programmer (Solenoid Pilot)

    PURPOSE: For accurately controlling temperature of a batch process where on-off operation is to be

    electronically controlled.

    OPERATION: Operation is similar to that of the pressure and temperature combination pilot-operated regulator

    whereby the temperature (T) pilot senses the temperature inside the autoclave and appropriatelymodulates the flow of steam. Pressure is limited by the pressure (P) pilot. The solenoid valve

    (S-pilot) is electronically activated to control on-off operation of the batch process. (The HD Regulatoroperating with these three pilots is known as the HDPTS Regulator.)

    INSTALLATION GUIDELINES: (see Figure 14)

    The temperature and pressure pilots should be set individually, starting slowly and gradually with the T-pilot.

    For optimum operation and service life, maintain recommended minimum piping straight runs before andafter the PRV. Inlet pipe diameters are typically 1-2 sizes larger and outlet pipe diameters 2-3 sizes larger

    than the end connections of an appropriately sized PRV. The purpose of increasing the pipe size downstreamof the regulator is to keep the steam velocity constant on both sides of the regulator.

    The pressure sensing line should slope downwards, away from the regulator, to prevent condensate fromentering the pilot.

    Eccentric reducers, if required, are used on valve inlets to prevent accumulation of pipeline moisture which could

    become entrained with high-velocity steam, possibly resulting in dangerous waterhammer.

    While the separator shown upstream is appropriate for protection of the PRV, it is not always required, as a

    properly sized drip leg with steam trap may be sufficient. It is recommended for systems where steam is knownto be wet and the entrained moisture could affect valve performance and/or result in component damage.

    Consider low-cracking pressure (1/4 PSI opening pressure) check valves after steam traps when discharging

    into condensate return lines. Check valves eliminate the possibility of condensate backing up through thesteam trap into the system.

    The thermostatic air vent located at the top of the autoclave chamber promotes optimum heat transfer.The air vent improves heat-up times and overall heat transfer by expelling accumulated air on start-up.

    A safety relief valve (SRV) is appropriate where applicable codes dictate their requirement, or anywhereprotection of downstream piping and equipment from over-pressurization is desired. Consult the factory for

    appropriate SRV sizing guidelines.

    310428 Jones Boulevard Limerick Airport Business Center Pottstown PA 19464 Tel: 610-495-5131 Fax: 610-495-5134

    www.watsonmcdaniel.com

  • 7/25/2019 Regulating Valve

    16/18

    REGULATING VALVE APPLICATIONS

    AUTOMATIC TEMPERATURE CONTROL of a BATCH PROCESSwith Electrical Time Sequence Programmer (Solenoid Pilot)

    AUTOMATICTEMPERATURE

    CONTROLofaBATCHP

    ROCESSwithElectricalTimeSequenceProgrammer(Soleno

    idPilot)

    (HDREGU

    LATORAPPLICATIONS)

    TO

    CONDENSATE

    RETURN

    F&T

    TRAP

    F&T

    TRAP

    SEPARATOR

    HDPTS

    REGULATOR

    SRV

    DRIP

    PAN

    ELBOW

    STEAM

    FILTER

    TODRAIN

    AUTOCLAVE

    TH

    ERMOSTATIC

    AIRVENT

    THERMOSTATIC

    STEAM

    TRAP

    POWER

    ELECTRIC

    OPERATOR

    F&T

    TRAP

    STEAM

    SUPPLY

    Figure 14:

    31428 Jones Boulevard Limerick Airport Business Center Pottstown PA 19464 Tel: 610-495-5131 Fax: 610-495-5134

    www.watsonmcdaniel.com

    TO

    CONDENSATE

    RE

    TURN

    DRAIN

    VALVE

    G

    ATE

    V

    ALVE

    STRAINER

    ISOLATION

    VALVE

    DRAIN

    VALVE

    APPLICAT

    ION

    DEPENDE

    NT

    CAPILLARY

    PRESSURE

    SENSING

    LINE

    TPILOT

    PPILOT

    TEMPERATURE

    SENSINGBULB

    VENT

    GATE

    VALVE

    TOCONDENSATE

    RETURN

    ISOLATION

    VALVE

    STRAINER

    SPILOT

    CHECK

    VALVE

  • 7/25/2019 Regulating Valve

    17/18

    312428 Jones Boulevard Limerick Airport Business Center Pottstown PA 19464 Tel: 610-495-5131 Fax: 610-495-5134

    www.watsonmcdaniel.com

    REGULATING VALVE APPLICATIONS

    TEMPERATURE CONTROL of a SEMI-INSTANTANEOUS HEATER using aSelf-Contained Temperature Regulating Valve

    PURPOSE: For accurate control of the temperature of a product being heated when the benefits of a

    self-contained regulator are required.

    OPERATION:A self-contained temperature regulating valve (TRV) such as the W91, offers response times andcharacteristics suitable for semi-instantaneous heating applications. The temperature sensing bulb

    senses the temperature of the liquid being heated and allows modulation of the valve for appropriatesupply of steam.

    INSTALLATION GUIDELINES: (see Figure 15)

    Care should be given to the installation of the temperature sensing bulb to ensure full immersion in the liquid.

    The sensing bulb should be placed as close as possible to the heater tank to ensure accurate temperaturecontrol of the process fluid.

    For optimum operation and service life, maintain recommended minimum piping straight runs before and

    after the PRV. Inlet pipe diameters are typically 1-2 sizes larger and outlet pipe diameters 2-3 sizes largerthan the end connections of an appropriately sized PRV. The purpose of increasing the pipe size downstream

    of the regulator is to keep the steam velocity constant on both sides of the regulator.

    All pressure sensing lines should slope downwards, away from the regulator, to prevent condensate fromentering the pilot.

    Eccentric reducers, if required, are used on valve inlets to prevent accumulation of pipeline moisture which could

    become entrained with high-velocity steam, possibly resulting in dangerous waterhammer.

    While the separator shown upstream is appropriate for protection of the PRV, it is not always required, as aproperly sized drip leg with steam trap may be sufficient. It is recommended for systems where steam is known

    to be wet and the entrained moisture could affect valve performance and/or result in component damage.

    Consider installing a properly sized bypass line with globe valve to provide continuous operation shouldregulator maintenance be required.

    Consider low-cracking pressure (1/4 PSI opening pressure) check valves after steam traps when discharging

    into condensate return lines. Check valves eliminate the possibility of condensate backing up through thesteam trap into the system.

    The vacuum breaker and auxiliary air vent located at the top of the heater tank promotes proper drainageand optimum heat transfer. The vacuum breaker allows system equalization with atmospheric air to allow

    gravity condensate drainage when vacuum is formed from condensing steam. The air vent improves heat-uptimes and overall heat transfer by expelling accumulated air on start-up.

    A safety relief valve (SRV) is appropriate where applicable codes dictate their requirement, or anywhere

    protection of downstream piping and equipment from over-pressurization is desired. The SRV needs to handle

    the complete volume of steam from the regulator and bypass loop. Consult the factory for appropriate SRVsizing guidelines.

    ENGINEERING

  • 7/25/2019 Regulating Valve

    18/18

    SEMI-INSTANTANEOUSHOTWATE

    RHEATERWITHW91TEM

    PERATUREREGULATOR

    (TEMPERATUR

    EREGULATORAPPLICATIONS)

    ISOLA

    TION

    VALVE

    TO

    CONDENSATE

    RE

    TURN

    SEPARATOR

    BYPASSLINE

    HOT

    WATER

    OUTLET

    SEMI-INSTANTANE

    OUS

    HEATER

    APPLICATION

    DEPENDENT

    COLD

    WATER

    INLE

    T

    ISOLATION

    VALVE

    CHECK

    VALVE

    STEAM

    INLET

    STEAM

    TRAP

    STRAINER

    W91

    TEMPERATURE

    REGULATING

    VALVE

    CAPILLARY

    TEMPERATURE

    SENSING

    BULB

    STEAM

    TRAP

    3428 Jones Boulevard Limerick Airport Business Center Pottstown PA 19464 Tel: 610 495 5131 Fax: 610 495 5134

    REGULATING VALVE APPLICATIONS

    TEMPERATURE CONTROL of a SEMI-INSTANTANEOUS HEATER using aSelf-Contained Temperature Regulating Valve

    Figure 15:

    STRAINER

    GLOBE

    VALVE

    GATE

    VALVE

    GATE

    VALVE

    TO

    CONDENSATE

    RETURN

    DRAIN

    VALVE

    AV2000

    AIRVENT

    WVBSS

    VACUUM

    BREAKER