LIST OF STRUCTURAL DRAWINGS
SHEET NO.
S101 GENERAL NOTES AND TYPICAL DETAILS
S102 TYPICAL DETAILS
S201 PART FOUNDATION PLAN
S401 SECTIONS AND DETAILS
S402 SECTIONS AND DETAILS
SHEET TITLE
G E N E R A L N O T E S
A. GENERAL INFORMATION
1. READ STRUCTURAL DOCUMENTS IN CONJUNCTIONE WITH CONTRACT DOCUMENTS, WHICH INCLUDE, BUT ARE
NOT LIMITED TO, ARCHITECTURAL, MECHANICAL, AND ELECTRICAL DOCUMENTS.
2. CONTRACTOR TO BE RESPONSIBLE FOR CHECKING SITE CONDITIONS AGAINST DOCUMENTS, BEFORE
PROCEEDING WITH THE WORK, AND REPORT DISCREPANCIES TO THE CONSULTANT.
3. CONTRACTOR TO PROVIDE LABOUR, MATERIALS, AND EQUIPMENT TO COMPLETE ALL STRUCTURAL WORK
INDICATED.
4. CARRY OUT CONSTRUCTION OPERATIONS, INCLUDING THE INSTALLATION OF TEMPORARY GUYING AND SHORING
REQUIRED, ENSURING THAT THE EXISTING STRUCTURE OR MEMBERS ALREADY ERECTED ARE NOT LOADED IN
EXCESS OF THEIR SAFE LOAD CARRYING CAPACITY.
5. STRUCTURAL DOCUMENTS DO NOT NECESSARILY SHOW ALL OPENINGS AND SLAB VARIATIONS REQUIRED. THE
CONTRACTOR SHALL REFER TO ARCHITECTURAL, MECHANICAL, AND ELECTRICAL DRAWINGS FOR THE EXACT
LOCATION, NUMBER, AND SIZE OF OPENINGS, TRENCHES, PITS, SUMPS, SLEEVES, AND DEPRESSIONS. PROVIDE
STRUCTURAL FRAMING AT THESE LOCATIONS IN ACCORDANCE WITH THE APPLICABLE TYPICAL DETAIL.
B. REFERENCE STANDARDS/CODES AND ACTS
1. CONFORM WITH THE 2012 BUILDING CODE (ONTARIO REGULATION 332/12, AMENDED BY ONTARIO REGULATIONS
191/14, 563/17, AND 88/19 ), AND ANY APPLICABLE ACTS OF ANY AUTHORITY HAVING JURISDICTION, AND THE
FOLLOWING:
2. ALL STANDARDS AND PUBLICATIONS REFERENCED BY THE STANDARDS NOTED ABOVE ARE TO APPLY.
3. WHERE THERE ARE DIFFERENCES BETWEEN THE DOCUMENTS AND THE STANDARDS, CODES AND ACTS, THE
MOST STRINGENT SHALL GOVERN.
C. SUBMITTALS
1. SUBMIT FOR REVIEW BY THE VARIOUS CONSULTANTS, DETAILED INFORMATION FOR ALL TEMPORARY AND
PERMANENT STRUCTURAL WORK. THIS INCLUDES, BUT IS NOT LIMITED TO
1.1 CONTRACTOR SHALL ALLOW FOR A TURN AROUND TIME OF 5 WORKING DAYS FOR THE REVIEW OF
THESE SUBMISSIONS.
2. OUR REVIEW OF THE SHOP DRAWINGS IS ONLY FOR GENERAL CONFORMITY WITH STRUCTURAL CONTRACT
DOCUMENTS AND SPECIFICATIONS. COMMENTS MADE ON THE SHOP DRAWINGS DURING THIS REVIEW DO NOT
RELIEVE THE CONTRACTOR FROM COMPLIANCE WITH THE REQUIREMENTS OF THE STRUCTURAL CONTRACT
DOCUMENTS AND SPECIFICATIONS, NOR DO THEY AUTHORIZE ANY CHANGES TO THE CONTRACT.REVIEW OF A
SPECIFIC ITEM SHALL NOT INCLUDE REVIEW OF AN ASSEMBLY OF WHICH THE ITEM IS A COMPONENT. THE
CONTRACTOR'S RESPONSIBILITIES INCLUDE ALL QUANTITIES, DETAIL DIMENSIONS, FIELD MEASUREMENTS,
FABRICATION PROCESS, MEANS, METHODS, SEQUENCES AND PROCEDURES OF CONSTRUCTION, COORDINATION
OF WORK WITH ALL TRADES AND PERFORMING ALL WORK IN A SAFE AND SATISFACTORY MANNER. THE REVIEW
OF SHOP DRAWINGS DOES NOT IMPLY ANY CHANGE IN ANY OTHER CONSULTANTS' OR PROFESSIONALS'
RESPONSIBILITY RELATED TO DESIGN OF SPECIFIC ITEMS AS OUTLINED BY THE SPECIFICATIONS (SUCH AS
STRUCTURAL STEEL CONNECTIONS, STEEL JOISTS, PRECAST ELEMENTS, ETC.). AFTER REVIEW, THE DRAWINGS
WILL BE STAMPED AND RETURNED TO SHOW ONE OF THE FOLLOWING:
NOT REVIEWED SHOWS WORK WHICH IS NOT WITHIN THE SCOPE OF STRUCTURAL CONSULTING
SERVICES.
REVIEWED NO DEVIATIONS FROM THE CONTRACT DOCUMENTS NOTED.
NOTED WE HAVE MADE COMMENTS, TO BE REVIEWED/INCORPORATED.
SUBMIT RECORD PRINT.
RESUBMIT REVISE AND RESUBMIT FOR REVIEW.
D. MATERIALS
1. PROVIDE ONLY NEW STRUCTURAL MATERIALS IN ACCORDANCE WITH THE REFERENCE STANDARDS AND THE
FOLLOWING, UNLESS OTHERWISE NOTED.
1.1 CONCRETE:
1.2 REINFORCING STEEL: CONFORM TO CSA G30 SERIES, GRADE 400.
1.3 WELDED WIRE FABRIC: CONFORM TO CSA G30 SERIES, GRADE 386, IN FLAT SHEETS.
1.4 STRUCTURAL STEEL:
(a) STRUCTURAL WIDE FLANGE AND WELDED WIDE FLANGE SHAPES (W, WWF) TO CONFORM TO
CAN/CSA-G40.20/G40.21 GRADE 350W.
(b) ANGLES AND CHANNELS (L, C) AND PLATES TO CONFORM TO CAN/CSA-G40.20/G40.21 GRADE
300W.
(c) HOLLOW STRUCTURAL SECTIONS (HSS) TO CONFORM TO ASTM A500 GRADE C.
1.5 PRIME PAINT: CONFORM TO CISC/CPMA STANDARD 2-75.
1.6 HOT DIP GALVANIZING: TO CSA G164, MINIMUM ZINC COATING OF 600G/M2.
1.7 STRUCTURAL BOLTS, NUTS AND WASHERS: CONFORM TO ASTM A325M.
1.8 ANCHOR RODS - CONFORM TO THE REQUIREMENTS OF ASTM F1554 GRADE.
1.9 CONCRETE ANCHORS: NELSON STUDS MADE FROM ASTM A-108 COLD ROLLED DEFORMED WIRE
MEETING ASTM A-496.
1.10 ALL COLD FORMED STEEL STUDS/SILLS/FRAMING SHALL CONFORM TO CAN/CSA-S136-01, CAN/CSA
S304.1-04 & CAN/CSA-A370-04 AND ARE BASED UPON MEMBERS PRODUCED BY BAILEY METAL PRODUCTS
OR APPROVED EQUIVALENT.
1.10.1 STEEL SHALL MEET THE REQUIREMENTS OF ASTM A653 STANDARD SPECIFICATION FOR SHEET
METAL, ZINC COATED (GALVANIZED) BY THE HOT-DIP PROCESS, STRUCTURAL (PHYSICAL)
QUALITY. MINIMUM GRADES ARE:
1.10.1.1 GRADE A 228 MPa MINIMUM YIELD FOR 1.146 mm MATERIAL AND THINNER
1.10.1.2 GRADE D 345 MPa MINIMUM YIELD FOR 1.438 mm MATERIAL AND THICKER.
1.10.2 SECTION PROPERTIES SHALL BE COMPUTED ON THE BASIS OF THE BLACK METAL THICKNESS'
SHOWN. THE UNDER-RUN IN THICKNESS PERMITTED BY ASTM A653 IS NOT ACCOUNTED FOR IN
THE DESIGN CALCULATIONS.
1.10.3 ERECTION TOLERANCES:
1.10.3.1 PLUMB: NOT TO EXCEED L/500TH OF MEMBER LENGTH.
1.10.3.2 CAMBER: NOT TO EXCEED L/1000TH OF MEMBER LENGTH.
1.10.3.3 SPACING: NOT MORE THAN 3.175 mm FROM DESIGN SPACING.
1.10.3.4 GAP BETWEEN END OF STUD AND TRACK WEB: NOT MORE THAN 4.8 mm.
1.10.4 DEFLECTION:
1.10.4.1 LIVE LOAD DEFLECTION BASED UPON L/360
1.11 NON-SHRINK GROUT = COMPRESSIVE STRENGTH OF 35 MPa AT 24 HOURS.
1.12 BLOCK: CONFORM TO CAN3-A165 SERIES, MINIMUM COMPRESSIVE STRENGTH = 15.0 MPa (MIN.) BASED
ON NET AREA.
1.13 MORTAR: CONFORM TO CSA A179 TYPE S FOR LOADBEARING WALLS UNLESS NOTED.
1.14 MASONRY GROUT: CONFORM TO CSA A179, 15 MPa MINIMUM COMPRESSIVE STRENGTH AT 28 DAYS, 250
mm (10") SLUMP, MAXIMUM AGGREGATE SIZE 10 MM (3/8").
1.15 POST-INSTALLED ANCHORS: PROVIDED BY HILTI (CANADA) CORPORATION. CONTACT HILTI AT (800)
363-4458 FOR PRODUCT RELATED QUESTIONS.
E. EXECUTION
1. FOUNDATIONS
1.1. FOUND ALL FOOTINGS FROST SLAB ON SOIL CAPABLE OF SUSTAINING A MINIMUM ULTIMATE LIMIT
STATES/ SERVICE LIMIT STATES BEARING STRESS (ULS/SLS) OF 30 kn/m² / 25 kn/m² .
1.2. FOUND ALL FOOTINGS WHICH WILL BE EXPOSED TO FROST ACTION IN THE COMPLETED BUILDING A
MINIMUM OF 1200 mm (4'-0") BELOW FINISHED GRADE.
1.3. DO NOT EXCEED A RISE OF 7 IN A RUN OF 10 IN THE LINE OF SLOPE BETWEEN ADJACENT FOOTING
EXCAVATIONS OR ALONG STEPPED FOOTINGS. FOR STEPPED FOOTINGS, USE STEPS NOT EXCEEDING
600 mm (2'-0") IN HEIGHT AND 1200 mm (4'-0") (MIN.) IN LENGTH.
1.4. SOIL BEARING CAPACITY SPECIFIED MUST BE VERIFIED BY THE SOIL ENGINEER PRIOR TO THE PLACING
OF FOOTINGS AND ANY NON-CONFORMANCE WITH THE SPECIFIED MINIMUM CAPACITIES MUST BE
IMMEDIATELY REPORTED TO THE STRUCTURAL ENGINEERS.
2. SLAB ON GRADE
2.1 PLACE SLAB-ON-GRADE ON SUB-GRADE MATERIAL CAPABLE OF SUSTAINING A MINIMUM BEARING
CAPACITY OF 25 kPa (500 psf) WITHOUT SETTLEMENT RELATIVE TO THE BUILDING FOOTINGS.
2.2 UNLESS OTHERWISE NOTED, PROVIDE IMMEDIATELY UNDER SLABS-ON-GRADE A MINIMUM OF 200 mm
(8") OF COMPACTED (MTC) GRANULAR 'B' MATERIAL. COMPACTION TO ACHIEVE A MINIMUM OF 98%
STANDARD PROCTOR MAXIMUM DRY DENSITY.
3. CONCRETE
3.1. WHEN ATMOSPHERIC TEMPERATURE IS AT OR BELOW 5°C OR WHEN THERE IS A POSSIBILITY OF IT
FALLING TO THAT LIMIT, PLACE CONCRETE IN ACCORDANCE WITH THE REQUIREMENTS OF CAN/CSA
A23.1 "COLD WEATHER CONCRETING" AND ACI 306 "RECOMMENDED PRACTICE FOR COLD WEATHER
CONCRETING". WHEN ATMOSPHERIC TEMPERATURE IS AT OR ABOVE 27°C PLACE CONCRETE IN
ACCORDANCE WITH CAN/CSA A23.1 "HOT WEATHER CONCRETING" AND ACI 305 "RECOMMENDED
PRACTICES FOR HOT WEATHER CONCRETING".
4. STRUCTURAL STEEL
4.1. PAINT ALL STRUCTURAL STEEL TO REQUIREMENTS OF CISC/CPMA 2-75. TOUCH UP ALL FIELD WELDS.
4.2. ALL STRUCTURAL STEEL EXPOSED TO WEATHER SHALL BE GALVANIZED IN ACCORDANCE WITH CSA
G164.
4.3. ALL WELDS SHALL CONFORM TO CSA STANDARD W59.
4.4. ALL WELDS EXPOSED TO VIEW SHALL BE GROUND SMOOTH.
4.5. ANY ORGANIZATION UNDERTAKING TO WELD UNDER THIS CONTRACT SHALL BE CERTIFIED BY THE
CANADIAN WELDING BUREAU UNDER REQUIREMENTS OF DIVISION 1 OR DIVISION 2.1 OF W47.1.
4.6. UNLESS A REINFORCED MASONRY OR CONCRETE LINTEL IS SHOWN, IN MASONRY WALLS OR MASONRY
PARTITIONS PROVIDE LOOSE STEEL LINTELS IN ACCORDANCE WITH REQUIREMENTS OF DOCUMENTS
OVER ALL DOORWAYS, OTHER OPENINGS, AND RECESSES, INCLUDING THOSE FOR MECHANICAL OR
ELECTRICAL SERVICES. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO COORDINATE THE
LOCATION, SIZE AND NUMBER OF OPENINGS REQUIRED BY THE MECHANICAL AND ELECTRICAL
CONSULTANT.
4.7. DO NOT SPLICE STRUCTURAL STEEL SECTIONS WITHOUT PRIOR APPROVAL OF THE CONSULTANT. ALL
SPLICES SHALL DEVELOP THE FULL CAPACITY OF THE SECTION AND ARE TO BE TESTED BY NON
DESTRUCTIVE METHODS, BY AN INDEPENDENT INSPECTION AND TESTING COMPANY, AT THE
CONTRACTOR'S EXPENSE.
4.8. COMPLETELY FILL VOIDS BENEATH STEEL BASES ON CONCRETE WITH AN APPROVED NON-SHRINK 36
MPa (5 ksi) GROUT
4.9. SEE ARCHITECTURAL DRAWINGS FOR FIREPROOFING REQUIREMENTS. CONFIRM COMPATIBILITY OF
FIREPROOFING MATERIAL WITH STEEL PAINT.
5. MASONRY
5.1. PROVIDE A MINIMUM LENGTH OF 200 mm (8") OF 100% SOLID MASONRY UNITS FOR BEARING OF STEEL,
CONCRETE OR REINFORCED MASONRY LINTELS.
5.2. SUPPLY AND PLACE REINFORCEMENT AND CONCRETE FOR REINFORCED MASONRY LINTELS IN
ACCORDANCE WITH TYPICAL DETAILS SHOWN.
6. POST-INSTALLED ANCHORS
6.1. ANCHOR CAPACITY USED IN DESIGN SHALL BE BASED ON THE TECHNICAL DATA PUBLISHED BY HILTI OR
SUCH OTHER METHOD AS APPROVED BY THE STRUCTURAL ENGINEER OF RECORD. SUBSTITUTION
REQUESTS FOR ALTERNATE PRODUCTS MUST BE APPROVED IN WRITING BY THE STRUCTURAL
ENGINEER OF RECORD PRIOR TO USE. CONTRACTOR SHALL PROVIDE CALCULATIONS DEMONSTRATING
THAT THE SUBSTITUTED PRODUCT IS CAPABLE OF ACHIEVING THE PERFORMANCE VALUES OF THE
SPECIFIED PRODUCT. SUBSTITUTIONS WILL BE EVALUATED FOR COMPLIANCE WITH THE RELEVANT
BUILDING CODE FOR SEISMIC USES, LOAD RESISTANCE, INSTALLATION CATEGORY, AND AVAILABILITY OF
COMPREHENSIVE INSTALLATION INSTRUCTIONS. ADHESIVE ANCHOR EVALUATION WILL ALSO CONSIDER
CREEP, IN-SERVICE TEMPERATURE AND INSTALLATION TEMPERATURE.
6.2. INSTALL ANCHORS PER THE MANUFACTURER INSTRUCTIONS, AS INCLUDED IN THE ANCHOR PACKAGING.
6.3. OVERHEAD ADHESIVE ANCHORS MUST BE INSTALLED USING THE HILTI PROFI SYSTEM.
6.4. THE CONTRACTOR SHALL ARRANGE AN ANCHOR MANUFACTURER'S REPRESENTATIVE TO PROVIDE
ONSITE INSTALLATION TRAINING FOR ALL OF THEIR ANCHORING PRODUCTS SPECIFIED. THE
STRUCTURAL ENGINEER OF RECORD MUST RECEIVE DOCUMENTED CONFIRMATION THAT ALL OF THE
CONTRACTOR'S PERSONNEL WHO INSTALL ANCHORS ARE TRAINED PRIOR TO THE COMMENCEMENT OF
INSTALLING ANCHORS.
6.5. ANCHOR CAPACITY IS DEPENDANT UPON SPACING BETWEEN ADJACENT ANCHORS AND PROXIMITY OF
ANCHORS TO EDGE OF CONCRETE. INSTALL ANCHORS IN ACCORDANCE WITH SPACING AND EDGE
CLEARANCES INDICATED ON THE DRAWINGS.
6.6. EXISTING REINFORCING BARS IN THE CONCRETE STRUCTURE MAY CONFLICT WITH SPECIFIC ANCHOR
LOCATIONS. UNLESS NOTED ON THE DRAWINGS THAT THE BARS CAN BE CUT, THE CONTRACTOR SHALL
REVIEW THE EXISTING STRUCTURAL DRAWINGS AND SHALL UNDERTAKE TO LOCATE THE POSITION OF
THE REINFORCING BARS AT THE LOCATIONS OF THE CONCRETE ANCHORS, BY HILTI FERROSCAN, HILTI
PS 1000, GPR, X-RAY, CHIPPING OR OTHER MEANS.
7. ALTERATIONS AND/OR CONNECTIONS TO EXISTING STRUCTURE
7.1. INSPECT THE EXISTING BUILDING AND BECOME THOROUGHLY FAMILIAR WITH THE EXISTING
CONDITIONS.
7.2. PRIOR TO PROCEEDING WITH THE WORK, DETERMINE THE EXACT FOUNDING ELEVATIONS OF EXISTING
FOOTINGS ADJACENT TO THE NEW WORK. REPORT THESE FINDINGS TO THE CONSULTANT.
7.3. PRIOR TO FABRICATION OF STRUCTURAL STEEL, OPEN UP ALL AREAS WHERE CONNECTIONS ARE TO BE
MADE TO EXISTING WORK AND TAKE FIELD MEASUREMENTS. MODIFY METHODS FOR CONNECTING TO
SUIT SITE CONDITIONS FOUND AND TO THE APPROVAL OF THE CONSULTANT. CARRY OUT LOCAL
REPAIRS TO THE EXISTING WORK AS NECESSARY AND AS DIRECTED BY THE CONSULTANT.
7.4. SHORE EXISTING WORK AS REQUIRED UNTIL ALL NEW WORK HAS BEEN COMPLETED AND REVIEWED BY
THE CONSULTANT.
7.5. PROVIDE SLOTTED HOLES AND FRICTION TYPE BOLTED CONNECTIONS TO CONNECT NEW STEEL TO
EXISTING WORK.
7.6. SHORE FLOORS AS REQUIRED TO SUPPORT CRANES, HOISTS AND OTHER CONSTRUCTION EQUIPMENT.
7.7. DO NOT CUT CONCRETE REINFORCEMENT UNLESS REVIEWED AND APPROVED BY THE CONSULTANT.
7.8. WHERE REQUIRED TO AVOID CUTTING EXISTING REINFORCEMENT, MODIFY THE LAYOUT OF NEW
THROUGH BOLTS, EXPANSION ANCHORS AND OTHER ANCHORING DEVICES.
7.9. MAKE GOOD THE EXISTING WORK.
F. QUALITY CONTROL
1. GENERAL
1.1 IMPLEMENT A SYSTEM OF QUALITY CONTROL TO ENSURE THAT THE MINIMUM STANDARDS SPECIFIED
HEREIN ARE ATTAINED.
1.2 BRING TO THE ATTENTION OF THE CONSULTANT ANY DEFECTS IN THE WORK OR DEPARTURES FROM
THE CONTRACT DOCUMENTS, WHICH MAY OCCUR DURING CONSTRUCTION. THE CONSULTANT WILL
DECIDE UPON CORRECTIVE ACTION AND GIVE RECOMMENDATIONS IN WRITING.
1.3 THE CONSULTANT'S GENERAL REVIEW DURING CONSTRUCTION AND INSPECTION AND TESTING BY
INDEPENDENT INSPECTION AND TESTING AGENCIES REPORTING TO THE CONSULTANT ARE BOTH
UNDERTAKEN TO INFORM THE OWNER/CLIENT OF THE CONTRACTOR'S PERFORMANCE AND SHALL IN NO
WAY AUGMENT THE CONTRACTOR'S QUALITY CONTROL OR RELIEVE THE CONTRACTOR OF
CONTRACTUAL RESPONSIBILITY.
2. NOTIFICATION
2.1 PRIOR TO COMMENCING SIGNIFICANT SEGMENTS OF THE WORK, GIVE THE CONSULTANT AND
INDEPENDENT INSPECTION AND TESTING COMPANIES APPROPRIATE NOTIFICATION (MINIMUM 24 HOURS)
SO AS TO AFFORD THEM REASONABLE OPPORTUNITY TO REVIEW THE WORK. FAILURE TO MEET THIS
REQUIREMENT MAY BE CAUSE FOR THE CONSULTANT TO CLASSIFY THE WORK AS DEFECTIVE.
3. INSPECTION AND TESTING
3.1 AN INDEPENDENT INSPECTION AND TESTING COMPANY SHALL MAKE INSPECTIONS OR PERFORM TESTS
AS THE CONSULTANT DIRECTS. THE INDEPENDENT INSPECTION AND TESTING COMPANIES SHALL BE
RESPONSIBLE ONLY TO THE CONSULTANT AND SHALL MAKE ONLY SUCH INSPECTIONS OR TESTS AS
THE CONSULTANT MAY DIRECT.
3.2 THE FOLLOWING ITEMS REQUIRE TESTING AND/OR INSPECTION BY A CERTIFIED, INDEPENDENT
INSPECTION AND TESTING COMPANY UNLESS OTHERWISE NOTED. THE TESTING FIRM SHALL SUBMIT
COPIES OF ALL STRUCTURAL TESTING AND INSPECTION REPORTS TO THE CONSULTANT FOR REVIEW:
4. DEFECTIVE MATERIALS AND WORK
4.1 WHERE EVIDENCE EXISTS THAT DEFECTIVE WORK HAS OCCURRED OR THAT WORK HAS BEEN
CARRIED OUT INCORPORATING DEFECTIVE MATERIALS, THE CONSULTANT MAY HAVE TESTS,
INSPECTIONS OR SURVEYS PERFORMED, ANALYTICAL CALCULATIONS OF STRUCTURAL STRENGTH
MADE, AND THE LIKE, IN ORDER TO HELP DETERMINE WHETHER THE WORK MUST BE CORRECTED OR
REPLACED. TESTS, INSPECTIONS OR SURVEYS OR CALCULATIONS CARRIED OUT UNDER THESE
CIRCUMSTANCES WILL BE MADE AT THE CONTRACTOR'S EXPENSE, REGARDLESS OF THEIR RESULTS,
WHICH MAY BE SUCH THAT, IN THE CONSULTANT'S OPINION, THE WORK MAY BE ACCEPTABLE.
4.2 ALL TESTING SHALL BE CONDUCTED IN ACCORDANCE WITH THE REQUIREMENTS OF THE 2012 BUILDING
CODE (ONTARIO REGULATION 332/12, EXCEPT WHERE THIS WOULD, IN THE CONSULTANT'S OPINION,
CAUSE UNDUE DELAY OR GIVE RESULTS NOT REPRESENTATIVE OF THE REJECTED MATERIAL IN PLACE.
IN THIS CASE, THE TESTS SHALL BE CONDUCTED IN ACCORDANCE WITH THE STANDARDS GIVEN BY THE
CONSULTANT.
4.3 MATERIALS OR WORK, WHICH FAIL TO MEET SPECIFIED REQUIREMENTS, MAY BE REJECTED BY THE
CONSULTANT WHENEVER FOUND AT ANY TIME PRIOR TO FINAL ACCEPTANCE OF THE WORK
REGARDLESS OF PREVIOUS INSPECTION. IF REJECTED, DEFECTIVE MATERIALS OR WORK SHALL BE
PROMPTLY REMOVED AND REPLACED OR REPAIRED TO THE SATISFACTION OF THE CONSULTANT, AT NO
EXPENSE TO THE OWNER.
REF CODE TITLE
a) CAN/CSA A23.1 CONCRETE MATERIALS AND METHODS OF CONCRETE CONSTRUCTION.
b) CAN/CSA A23.2METHODS OF TEST FOR CONCRETE.
c) CAN/CSA A23.3 DESIGN OF CONCRETE STRUCTURES.
d) CAN/CSA-S16LIMIT STATES DESIGN OF STEEL STRUCTURES.
e) S136 COLD FORMED STEEL STRUCTURAL MEMBERS.
f) CAN/CSA G40.20/G40.21STRUCTURAL QUALITY STEEL.
g) RSIC REINFORCING STEEL INSTITUTE OF CANADA (RSIC),
MANUAL OF STANDARD PRACTICE
h) CAN/CSA-A370 CONNECTORS FOR MASONRY
i) CSA-A371 MASONRY CONSTRUCTION FOR BUILDINGS.
k) S304.1
l) CSA G30.18
DESIGN OF MASONRY STRUCTURES
CARBON STEEL BARS FOR CONCRETE REINFORCING
ITEM
SUBMISSION
REQUIRED
SUBMISSION
TO BE SEALED BY
PROFESSIONAL
ENGINEER
COMMENTS
TEMPORARY SHORING YESYES
STRUCTURAL STEEL
SHOP DRAWINGS
YESYES
LIGHT-GAUGE (COLD -
FORMED) STEEL FRAMING
SHOP DRAWINGS
YESYES
TOLERANCE FOR SLUMP SHALL BE +/-20 mm FOR SPECIFIED SLUMP LESS THAN 80 mm AND +/- 30 mm FOR
SPECIFIED SLUMP BETWEEN 80 mm AND 170 mm
* SPECIAL CONCRETE HANDLING AND PLACING METHODS OR THE USE OF A SUPER PLASTICIZER WILL BE
REQUIRED TO PLACE THIS CONCRETE. FINAL PLASTICIZED SLUMP SHALL BE +/- 125 mm.
** WHERE AGGREGATES SMALLER THAN 14 mm ARE USED, INCREASE AIR CONTENT BY 1%
*** CONCRETE EXPOSED TO DE-ICING CHEMICALS SHALL HAVE DCI TYPE N CORROSION INHIBITOR
@ 11L/m
3
DOSAGE OR APPROVED EQUIVALENT.
STRUCTURAL ELEMENT
AND EXPOSURE
EXPOSURE CLASS
PER CSA A23.1
SLABS-ON-GRADE NOT
EXPOSED TO CHLORIDES
OR FREEZING
CONCRETE
STRENGTH
f'c (MPa)
25
SLUMP
(mm)
40*
MAX W/C
RATIO
0.45
AIR
CONTENT
FROST SLAB35 80 0.40
C-1 5%-8%
EXTERIOR PAVING32 60
C-2 0.45 5%-8%
ITEM REQUIRED COMMENTS
SOIL BEARING CAPACITY YES BY GEOTECHNICAL CONSULTANT
SOIL COMPACTION YES BY GEOTECHNICAL CONSULTANT
STRUCTURAL STEEL ERECTION YES
STRUCTURAL STEEL WELDING YES VISUALLY INSPECT ALL FIELD WELDING
REVIEW MEMBER SIZE, PLUMBNESS,
BOLTED CONNECTIONS, ETC.
TD-G01 STRUCTURAL ABBREVIATIONS
A BOLT ANCHOR BOLT
ADJ ADJUSTABLE
AESS ARCHITECTURAL EXPOSED
STRUCTURAL STEEL
AFF ABOVE FINISHED FLOOR
AIFB ASPHALT IMPREGNATED
FIBREBOARD
ALT ALTERNATE
ARCH ARCHITECTURAL
ASL ADDITIONAL ACCUMULATED
SNOW LOAD
@ AT
B, BOTT BOTTOM
B/B BACK TO BACK
BEW BOTTOM EACH WAY
BH BOREHOLE
BLL BOTTOM LOWER LAYER
BLDG BUILDING
BM BEAM
BPL BEARING/BASE PLATE
BRDG BRIDGING
BUL BOTTOM UPPER LAYER
c CAMBER
C EPOXY COATED
c/c, o/c CENTRE TO CENTRE
CA, CB COLUMN ABOVE,
COLUMN BELOW
CANT CANTILEVER
Cf COMPRESSIVE FORCE (FACTORED)
CJ CONTROL JOINT
CL CLEAR
CL, CENTRELINE
COL COLUMN
COMP COMPOSITE
CONC CONCRETE
CONT CONTINUOUS
C/W COMPLETE WITH
DEMO DEMOLITION
DET DETAIL
DIA, Ø DIAMETER
DIAG DIAGONAL
DIM DIMENSION
DL DEAD LOAD
DP DEEP
DWG(S) DRAWING(S)
DWL(S) DOWEL(S)
DN DOWN
EA EACH
EE EACH END
EF EACH FACE
ELEC ELECTRICAL
EL ELEVATION
ELEV ELEVATOR
EMBED EMBEDMENT
EQ EQUAL
ES EACH SIDE
EX, EXIST EXISTING
EJ, EXP JT EXPANSION JOINT
E-W EAST WEST
EW EACH WAY
EXT EXTERIOR
f'c 28 DAYS CONCRETE
COMPRESSIVE STRENGTH
FDN FOUNDATION
FF FAR FACE
FIN FINISHED
FL FLOOR
ft FOOT, FEET
FTG FOOTING
Fy YIELD STRENGTH
GA GAUGE
GALV GALVANIZED
GEN GENERAL
HEF HORIZONTAL EACH FACE
Hf HORIZONTAL FORCE (FACTORED)
HH HOOK EACH END
HIF HORIZONTAL INSIDE FACE
HOF HORIZONTAL OUTSIDE FACE
H, HORZ HORIZONTAL
HSC HORIZONTALLY SLOTTED CONNECTION
HSS HOLLOW STEEL SECTION
IF INSIDE FACE
IN INCH(ES)
INT INTERIOR
JT JOINT
K KIP, 1000 LBS
K-ft KIP FEET
kg KILOGRAM(S)
KLF KIPS PER LINEAR FOOT
kN KILONEWTON
kN-m KILONEWTON METRE
kN/m KILONEWTON PER METRE
kPa KILOPASCAL
KSF KIPS PER SQUARED FOOT
KSI KIPS PER SQUARED INCH
L SINGLE ANGLE
LE LEFT END
LG LONG
LL LIVE LOAD, LOWER LAYER
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
m METRE
MC MOMENT CONNECTION
(FULL MOMENT UNLESS NOTED)
MECH MECHANICAL
Mf MOMENT (FACTORED)
ML MIDDLE LAYER
mm MILLIMETRE
MPa MEGAPASCAL
Mxf BENDING MOMENT
ABOUT x-x AXIS (FACTORED)
Myf BENDING MOMENT
ABOUT y-y AXIS (FACTORED)
NF NEAR FACE
NIC NOT IN CONTRACT
N-S NORTH-SOUTH
NTS NOT TO SCALE
OF OUTSIDE FACE
OPEN OPENING
OWSJ OPEN WEB STEEL JOIST
Pf AXIAL FORCE (FACTORED)
PC PRECAST
PL PLATE
PLF POUNDS PER LINEAR FOOT
PROJ PROJECTION
PSF POUNDS PER SQUARE FOOT
PT PRESSURE TREATED
RD ROOF DRAIN
Rf REACTION (FACTORED)
RAD RADIUS
REINF REINFORCED, REINFORCEMENT
REF REFERENCE
RE RIGHT END
REQ'D REQUIRED
REV REVISION, REVISED
R/W REINFORCED WITH
SDF STEP DOWN FOOTING
SECT SECTION
SIM SIMILAR
SL SLAB
SOG SLAB ON GRADE
SPDD STANDARD PROCTOR DRY DENSITY
ST STRAIGHT
STIFF STIFFENER
STIR STIRRUP
STRUCT STRUCTURAL
STD STANDARD
SQ SQUARE
T TOP
Tf TENSILE FORCE (FACTORED)
TEMP TEMPORARY, TEMPERATURE
TEW TOP EACH WAY
TJ TIE JOIST
TLL TOP LOWER LAYER
TMf TORSIONAL MOMENT (FACTORED)
TOD TOP OF DECK
TOS TOP OF STEEL/SLAB
TRANS TRANSVERSE
TUL TOP UPPER LAYER
TYP TYPICAL
UL UPPER LAYER
U/N UNLESS NOTED OTHERWISE
U/S UNDERSIDE
V, VERT VERTICAL
Vf VERTICAL SHEAR FORCE (FACTORED)
VBF VERTICAL BRACED FRAME
VEF VERTICAL EACH FACE
VIF VERTICAL INSIDE FACE
VOF VERTICAL OUTSIDE FACE
VSC VERTICALLY SLOTTED CONNECTION
W WIDE FLANGE BEAM
WT WEIGHT, STRUCTURAL TEE
WWF WELDED WIRE FABRIC OR WELDED WIDE FLANGE
W.P. WORKING POINT
C
L
100 mm (4") EMBED
NEW SLAB ON GRADE, MATCH
EXISTING SLAB THICKNESS
EXISTING
100 mm (4") SLAB
ON GRADE
PROVIDE 10m (MIN) DOWELS
250 mm (10") LG @ 600 mm (2'-0") c/c
(STAGGERED). DRILL AND EPOXY INTO
EXISTING SLAB EDGE USING HIT HY 200
ADHESIVE OR EQUIVALENT
NEW MECHANICAL
SERVICE
BACKFILL TRENCH WITH
COMPACTED GRANULAR MATERIAL
NOTES:
1. REFER TO MECHANICAL, ELECTRICAL AND ARCHITECTURAL DRAWINGS FOR
LOCATION AND EXTENT OF NEW UNDER SLAB SERVICES.
2. PRIOR TO CUTTING OF EXISTING SLAB, THE CONTRACTOR SHALL SCAN THE
EXISTING SLAB FOR BURIED SERVICES.
DOWEL BEYOND
OFFSET BY 300 mm (1'-0")
SLAB ON GRADE TRENCH INFILL
AT NEW UNDERSLAB SERVICES
PD-C101
IF WIDTH OF TRENCH GREATER
THAN 600 mm (2'-0") PROVIDE
1 - LAYER WWF 152x152 MW 18.7x18.7 REINF.
LOCATE MESH 2" FROM TOP OF SLAB.
PROVIDE CONCRETE BRICK SUPPORT
AS REQUIRED TO SUPPORT MESH.
2018_06
DWG. No.:
DATE: NOV. 2018
PROJECT No.:
TITLE:
Tel. (905) 623 7476
J.R. FREETHY ARCHITECT
BOWMANVILLE ONTARIO325 LAKE ROAD, SUITE 202
PROJECT:
L1C 4P8
CLIENT:
BAYVIEW HEIGHTS
PUBLIC SCHOOL
CHILD CARE
CLIENT:
1400 GARVOLIN ROAD, PICKERING, ON
Project No. 19-1648
All reproduction & intellectual property rights reserved c 2019
207 Adelaide St. E., Suite 200
Toronto, ON M5A 1M8
416-599-(LINK) 5465
www.engineeringlink.ca
1 ISSUED FOR COORDINATION RAD 2019 - 09 - 26
2 ISSUED FOR COORDINATION RAD 2019 - 12 - 06
3 RAD 2021 - 02 - 16ISSUED FOR PERMIT & TENDER
S101
TD-M01
LATERAL SUPPORT FOR TOP OF MASONRY WALL
AT PARTITION PERPENDICULAR TO JOIST OR BEAM
25 mm (1") COMPRESSIBLE MATERIAL
25 mm (1") COMPRESSIBLE MATERIAL
STEEL BEAM OR OWSJ
MASONRY WALL
CONC SLAB OR ROOF DECK
2 102x76x6 x 150 (6") LG (LLV)
WELDED TO U/S STEEL BEAM OR OWSJ.
AT PARTITION BELOW BEAM OR OWSJ AND PARALLEL TO BEAM
OR OWSJ SPAN
25 mm (1") COMPRESSIBLE MATERIAL
STEEL BEAM OR OWSJ
MASONRY WALL
CONC SLAB OR ROOF DECK
L102x102x6 x 150 mm (6") LG
EACH SIDE WELDED TO U/S STEEL FRAMING.
STAGGERED CLIPS
BY 150 mm (6")
L65x65x6 @ 2000 mm
(6'-6") MAX FROM BEAM
BOTTOM FLANGE/BOTTOM
CHORD OF JOIST TO
TOP FLANGE/TOP CHORD
OF ADJACENT BEAM/JOIST
AT UNDERSIDE OF STEEL FRAMING
NOTE:
IF BEAM/JOIST SPACING EXCEEDS
1500 mm (5'-0") c/c, PROVIDE
ADDITIONAL LATERAL SUPPORT AS PER
TD-M02 FOR CONCRETE SLAB OR
TD-M03 FOR STEEL DECK
NOTE:
1. SPACING OF LATERAL SUPPORT
TO BE 1500 mm (5'-0") AND
600 mm (2'-0") FROM WALL ENDS
2. REFER ALSO TO TYPICAL DETAIL
TD-M03 FOR REQUIREMENTS IN
HIGH SEISMIC ZONES.
TD-M04MASONRY LINTELS FOR NON-LOAD BEARING WALLS
CLEAR SPAN (L)
90 (4")
190 (8")
140 (6")
240 (10")
290 (12")
NOTES:
1. FIRST AND SECOND DIMENSIONS INDICATED FOR THE LINTEL SIZE ARE
THE WIDTH AND DEPTH OF THE LINTEL RESPECTIVELY.
2. PROVIDE 40 mm (1 5/8") COVER FOR THE TOP AND BOTTOM LINTEL
REINFORCEMENT. EXTEND TOP & BOTTOM REINFORCEMENT TO WITHIN
50 mm (2 1/2") FROM EXTENT OF LINTEL.
WALL
THICKNESS
L < 1200
(4'-0")
1200 < L < 1800
(4'-0") (6'-0")
1800 < L < 2400
(6'-0") (8'-0")
2400 < L < 3000
(8'-0") (10'-0")
90x190 (4"x8")
REINF 1-10 T&B
90x190 (4"x8")
REINF 1-15 T&B
140x190 (6"x8")
REINF 1-10 T&B
190x190 (8"x8")
REINF 1-10 T&B
240x190 (10"x8")
REINF 2-10 T&B
290x190 (12"x8")
REINF 2-10 T&B
140x190 (6"x8")
REINF 1-15 T&B
190x190 (8"x8")
REINF 1-15 T&B
240x190 (10"x8")
REINF 2-10 T&B
290x190 (12"x8")
REINF 2-10 T&B
140x390 (6"x16")
REINF 1-15 T&B
190x390 (8"x16")
REINF 1-15 T&B
240x390 (10"x16")
REINF 2-15 T&B
290x390 (12"x16")
REINF 2-15 T&B
140x390 (6"x16")
REINF 1-15 T&B
190x390 (8"x16")
REINF 1-15 T&B
240x390 (10"x16")
REINF 2-15 T&B
290x390 (12"x16")
REINF 2-15 T&B
CO
VE
R
ELEVATION
LOCATION OF CONTROL JOINTS WHERE
NOTED IN ARCH DETAILS
REINFORCEMENT
ALL SOLID MASONRY WHEN
PIERS ARE LESS THAN
600 mm (2'-0") WIDE
50 mm
(2")
50 mm
(2")
200
(8")
20
0 m
m
(8
")
SOLID MASONRY BEARING
CLEAR SPAN
WALL THICKNESS
REDUCED BY REBATES.
INCLUDE IN SPAN.
l00x100x10
LENGTH OF ANGLE
> MASONRY WALL
THICKNESS
25 mm
(1") MAX
CONCRETE
LINTEL SUPPORTED BY
CONCRETE OR STEEL
MEMBER
CONNECT TO STEEL WITH 6
mm (1/4") WELD T&B FOR
FULL LENGTH OF ANGLE
2-20Ø (2-3/4"Ø)
HILTI KWIK BOLTS
(OR EQUIVALENT)
100 mm (4") MIN
EMBEDMENT
200
(8")
TD-M17
LATERAL SUPPORT FOR TOP OF MASONRY WALL
AT UNDERSIDE OF CONCRETE SLAB ON STEEL PAN
EXISTING ROOF
0
TYPICAL CONNECTION OF NEW CONCRETE
BLOCK WALL TO EXISTING CONCRETE SLAB
65 CONCRETE SLAB
ON STEEL PAN
NEW CONC BLOCK WALL
(SEE ARCH)
NEW L102x102x6 x 150 mm LG.
@ 1500 mm o/c MAX AND
600 mm FROM WALL ENDS.
EACH ANGLE TO BE
C/W 2 - 6 mmØ x 44 mm LG
TAPCON CONCRETE ANCHORS
25 mm
GAP TO BE
FILLED WITH
NONCOMBUSTIBLE
COMPRESSIBLE
MATERIAL
TYP
TD-M07ANCHORAGE OF MASONRY ABUTTING STEEL COLUMN
C
L
MASONRY STRAP
ANCHOR BY OTHERS
C
L
WALL
TIES STRAP
NOTES:
1. REFER TO ARCHITECTURAL DRAWINGS AND
SPECIFICATIONS FOR MINIMUM SLEEVE
SPACING. MAXIMUM SLEEVE SPACING
SHALL BE 4 x WALL THICKNESS ( t ).
2. REFER TO ARCHITECTURAL DRAWINGS FOR
LOCATION AND EXTENT OF MASONRY.
10
(3
/8
")
51
(2")
C
L
5 (3/16) BENT PL
SLEEVE
TIE STRAP
BY OTHERS
C
L
MASONRY STRAP
ANCHOR BY OTHERS
5 (3/16)
BENT PL SLEEVE
x 64 (2 1/2") LG
SHOP WELD TO BEAM
6 mm 75-300
(1/4") 3-12
6 mm 75-300
(1/4") 3-12
5 (3/16)
BENT PL SLEEVE
x 64 (2 1/2") LG
SHOP WELD TO COL
10
(3
/8
")
51
(2")
ELEVATION @ COLPLAN @ COL
t
t
BOTTOM PLATE REFER TO PLAN
MIN SIZE 6mm (1/4") THICK x
t - 10 (t - 1/2") WIDE
TD-S01
STEEL LINTELS FOR NON-LOAD BEARING
MASONRY WALLS
CLEAR SPAN
NOTES:
1. CONNECT BACK TO BACK DOUBLE ANGLE LINTELS USING 16 mm (5/8") Ø BOLTS AT 450 mm (18") c/c MAX OR BY
WELDING AT TOP AND BOTTOM USING 6 mm (1/4") WELDS x 50 mm (2") LONG AT 450 mm (18") c/c MAX. FIRST BOLT OR
WELD TO BE A MAX OF 75 mm (3") FROM END OF LINTEL
2. FULLY PACK LINTEL ENDS WITH STEEL SHIMS TO ENSURE EVEN BEARING.
3. LINTELS AS COVERED UNDER THIS DETAIL ARE NOT NECESSARILY SHOWN ON THE STRUCTURAL DRAWINGS. REFER
TO ARCHITECTURAL, MECHANICAL AND ELECTRICAL DRAWINGS FOR OPENING LOCATIONS AND SIZES.
WALL THICKNESS
UP TO
1200 (4'-0")
1200 (4'-0") TO
1800 (6'-0")
1800 (6'-0") TO
2400 (8'-0")
2400 (8'-0") TO
3000 (10'-0")
DETAIL
25 (1")
MAX
25 (1") MAX
STEEL
COLUMN
CONNECTION OF
ANGLE TO COLUMN
SHALL BE CAPABLE
OF SUPPORTING
A VERTICAL
SHEAR FORCE
Vf=20 kN (4.5 kips)
LINTEL SUPPORTED BY STEEL COLUMN
LINTEL SUPPORTED BY
POURED CONCRETE ELEMENT
L178x102x9.5 (LLV)
LENGTH LESS THAN
WIDTH OF MASONRY WALL
STEEL LINTEL
STEEL
LINTEL
L178x102x9.5 (LLV) + 2-19Ø
(3/4") HILTI KWIK BOLT
3 ANCHORS PROVIDE MIN
100 mm (4") EMBED.
LENGTH LESS THAN
MASONRY WALL
THICKNESS
STEEL LINTEL
PROVIDE FULLY GROUTED
OR SOLID MASONRY
FULL HEIGHT WHERE PIER
IS LESS THAN 600 mm (2'-0")
WIDE
SPAN
200 (8")
BEARING MIN
20
0
(8
")
PIER
WHERE WALL THICKNESS IS REDUCED
BY RECESSES INCLUDE WIDTH IN SPAN
REINFORCING IS SHOWN ON
PLAN OR DETAILS. WHERE
AT SIDES OF OPENINGS
PLACE TO CLEAR
LINTEL BEARING.
+>150
(6")
STANDARD ELEVATION
L127x89x6.4 (LLV)
90 (3 1/2")
VENEER
140 (5 1/2")
L89x89x6.4
190 (7 1/2") 240 (9 1/2") 290 (11 1/2")
L127x89x6.4 (LLV)
L127x89x9.5 (LLV)
2-L89x64x6.4 (LLV)
2-L64x64x6.4
2-L89x64x7.9 (LLV)
2-L89x89x6.4
2-L76x89x6.4
(LLH)
2-L102x89x7.9
(LLV)
2-L152x89x7.9
(LLV)
L102x102x6.4 +
L76x127x6.4 (LLH)
L76x102x6.4 +
L76x127x6.4 (LLH)
L102x102x9.5 +
L89x127x7.9 (LLH)
L152x102x7.9 (LLV)
+ L127x127x7.9
3-L89x89x6.4
3-L76x89x6.4
(LLH)
3-L102x89x6.4
(LLV)
3-L127x89x6.4
(LLV)
FULLY GROUTED
2-L89x64x9.5 (LLV)
2018_06
DWG. No.:
DATE: NOV. 2018
PROJECT No.:
TITLE:
Tel. (905) 623 7476
J.R. FREETHY ARCHITECT
BOWMANVILLE ONTARIO325 LAKE ROAD, SUITE 202
PROJECT:
L1C 4P8
CLIENT:
BAYVIEW HEIGHTS
PUBLIC SCHOOL
CHILD CARE
CLIENT:
1400 GARVOLIN ROAD, PICKERING, ON
Project No. 19-1648
All reproduction & intellectual property rights reserved c 2019
207 Adelaide St. E., Suite 200
Toronto, ON M5A 1M8
416-599-(LINK) 5465
www.engineeringlink.ca
1 ISSUED FOR COORDINATION RAD 2019 - 09 - 26
2 ISSUED FOR COORDINATION RAD 2019 - 12 - 06
3 RAD 2021 - 02 - 16ISSUED FOR PERMIT & TENDER
S102
NTS
KEY PLAN
S201
A
1 : 50
PART FOUNDATION PLAN
S201
B
S201
B
17 18 19 20 21 22 23 24 25
D
F
EXISTING 100 CONC SLAB ON GRADE.
SITE VERIFY.
WIDEN EXIST WALL OPENING. REFER TO ARCH. REMOVE EXIST LINTEL &
REPLACE WITH NEW STEEL LINTEL PER TYPICAL DETAIL TD-S01. PROVIDE
TEMPORARY NEEDLE + SHORING AS REQUIRED TO INSTALL NEW LINTEL.
INFILL EXIST WALL OPENING
W/ CONC BLOCK TO MATCH
EXIST. REFER ALSO TO
ARCH DWGS. SITE VERIFY.
EXIST 100 BRICK VENEER W/ 92 LIGHT
@ 300 c/c GAUGE STEEL STUD BACK-UP
WALL. TYPICAL AT EXTERIOR.
SITE VERIFY.
508
SIT
E V
ER
IF
Y
C EC
1
L
E
C
1E
X
W
2
0
0
x
3
6
C
O
L
NEW WALL OPENING. REFER TO ARCH. PROVIDE NEW GALV
STEEL LINTEL FOR BRICK VENEER PER TYPICAL DETAILS.
MODIFY EXIST BACKING STUD WALL TO ACCOMMODATE NEW
OPENING. PROVIDE TEMPORARY SHORING AS REQUIRED TO
SUPPORT BRICK VENEER DURING LINTEL INSTALLATION.
WIDEN EXIST WALL OPENING. REFER TO ARCH. REMOVE EXIST
BRICK LINTEL AND REPLACE W/ NEW GALV STEEL LINTEL PER
TYPICAL DETAILS. MODIFY EXIST BACKING STUD WALL TO
ACCOMMODATE NEW OPENING. LOCALLY DEMOLISH EXIST KNEE
WALL AT DOOR. PROVIDE TEMPORARY NEEDLE + SHORING FOR
BRICK VENEER AS REQUIRED TO INSTALL NEW LINTEL.
WIDEN EXIST WALL OPENING. REFER TO ARCH. REMOVE EXIST
BRICK LINTEL AND REPLACE W/ NEW GALV STEEL LINTEL PER
TYPICAL DETAILS. MODIFY EXIST BACKING STUD WALL TO
ACCOMMODATE NEW OPENING. LOCALLY DEMOLISH EXIST KNEE
WALL AT DOOR. PROVIDE TEMPORARY NEEDLE + SHORING FOR
BRICK VENEER AS REQUIRED TO INSTALL NEW LINTEL.
FS1
NEW 200 CONC FROST SLAB REINF W/ 15M @ 300 EW MIDDLE
LAYER ON UNSHRINKABLE FILL BASE. REFER TO SECTION. SEE
ARCH FOR EXACT DIMENSIONS AND SLOPE.
F
S
1
E
C
1F
T
G
1
E
C
1F
T
G
1
E
C
1F
T
G
1
E
C
1F
T
G
1
S401
2
LOCALLY REMOVE EX STEEL
ANGLE KNEE WALL SUPPORTS
@ DOOR OPENING. REFER TO
SECTIONS.
S401
3
ADD NEW P2
STUB POST EA SIDE DOOR.
REFER TO SECTION.
NEW WALL OPENING. REFER TO ARCH.
PROVIDE NEW STEEL LINTEL ABOVE PER TYPICAL
DETAIL. PROVIDE TEMPORARY NEEDLE SHORING
AS REQUIRED TO INSTALL NEW LINTEL.
P
1
INFILL EXIST WALL OPENING.
REFER TO ARCH FOR ASSEMBLY
INFILL EXIST WALL
OPENING. REFER TO
ARCH FOR ASSEMBLY
EXIST 300x1375 CONT
CONC GRADE BEAM
BELOW. TYPICAL
ALONG GRIDLINE 'D'.
P1
NEW HSS 89x89x9.5 POST W/
225x10x100 BASE PLATE W/
TWO -12Ø HILTI HAS-E GALV
TREADED ROD ANCHORS +
HILTI HY 200 ADHESIVE.
PROVIDE 65 EMBED. TYPICAL.
NEW WALL OPENING. REFER TO ARCH.
PROVIDE NEW STEEL LINTEL ABOVE PER TYPICAL
DETAIL TD-S01. PROVIDE TEMPORARY NEEDLE
SHORING AS REQUIRED TO INSTALL NEW LINTEL.
F
T
G
1
E
X
5
6
0
Ø
C
O
N
C
C
A
I
S
S
O
N
+
9
1
5
x
7
6
0
x
4
8
0
C
O
N
C
P
I
L
E
C
A
P
T
/
O
P
I
L
E
C
A
P
-
1
.
2
0
0
(
S
I
T
E
V
E
R
I
F
Y
)
+
4
0
0
x
3
6
0
P
I
E
R
T
/
O
P
I
E
R
-
0
.
1
5
0
(
S
I
T
E
V
E
R
I
F
Y
)
TYP @ ALL
NEW BLOCK
PARTITION
DEMOLISH EXIST NON-LOAD
BEARING CONC BLOCK PARTITION
WALL. MAKE GOOD EXIST SLAB ON
GRADE AT BASE OF WALL.
DEMOLISH EXIST NON-LOAD
BEARING CONC BLOCK PARTITION
WALL. MAKE GOOD EXIST SLAB ON
GRADE AT BASE OF WALL.
DEMOLISH EXIST NON-LOAD
BEARING CONC BLOCK PARTITION
WALL. MAKE GOOD EXIST SLAB ON
GRADE AT BASE OF WALL.
S401
1
LOCALLY REMOVE EX STEEL
ANGLE KNEE WALL SUPPORTS
@ DOOR OPENING. REFER TO
SECTIONS.
NEW LIGHT WEIGHT NON-LOAD BEARING BLOCK
PARTITION WALL. REFER TO ARCH DWGS. PROVIDE
FULLY GROUTED BOND COURSE R/W 1-15M AT THE BASE
OF ALL WALLS. PROVIDE NEW STEEL LINTELS ABOVE ALL
OPENINGS AS PER TYPICAL DETAIL. REFER TO ARCH AND
MECH DWGS FOR OPENING LOCATIONS AND SIZES.
PROVIDE LATERAL SUPPORT CLIPS AT U/S 2ND FLOOR AS
PER TYPICAL DETAILS. TYPICAL ALL NEW NON-LOAD
BEARING PARTITION WALLS.
1. TOP OF EXISTING SLAB ON GRADE IS 0.0 m BELOW FINISHED GROUND FLOOR ELEVATION
0.0 m EXCEPT AS CROSSED AND NOTED. AREAS CROSSED AND NOTED TO BE READ FROM
GROUND FLOOR ELEVATION 0.0 m.
2. MAKE GOOD ALL EXTERIOR AND INTERIOR FINISHES AS PER ARCHITECT AND OWNER
REQUIREMENTS.
3. CONTRACTOR TO MAKE GOOD ALL BLOCK SAW CUT TO ARCHITECT'S AND OWNER'S
REQUIREMENTS.
4. REFER TO ARCH. DRAWINGS FOR EXTENT OF DEMOLITION AND FINAL OPENING SIZES.
5. REFER TO ARCHITECTURAL AND MECHANICAL DRAWINGS FOR ELEVATION OF ALL NEW
LINTELS AT OPENINGS THROUGH NEW NON-LOAD BEARING CONCRETE BLOCK PARTITION
WALLS.
6. WE HAVE REVIEWED THE LOADS IMPOSED BY THE NEW LIGHT-WEIGHT MASONRY
PARTITIONS ON THE EXISTING SLAB ON GRADE AND IN OUR OPINION, THEY MAY BE
INSTALLED WITHOUT REINFORCING, EXCEPT WHERE SHOWN.
7. REFER TO ARCH AND MECHANICAL DRAWINGS FOR NEW BELOW SLAB SERVICES AND
TRENCHING REQUIREMENTS. LOCALLY REMOVE SLAB ON GRADE AS REQUIRED FOR
INSTALLATION. MAKE GOOD SLAB ON GRADE AS PER TYPICAL DETAILS.
8. PROVIDE CLEAN SAW CUT AND CORING LINES AT ALL NEW MECHANICAL OPENINGS. MAKE
GOOD ALL DAMAGED BLOCK/ BRICK ADJACENT TO OPENINGS, UNLESS NOTED OTHERWISE
ON PLAN. PROVIDE STEEL LINTELS ABOVE ALL OPENINGS IN ACCORDANCE WITH TYPICAL
DETAILS. REFER TO MECHANICAL FOR NUMBER OF OPENINGS AND LOCATIONS.
9. AS A MINIMUM PROVIDE 9 GAUGE @ 400 C/C JOINT REINFORCING IN ALL NEW NON-LOAD
BEARING MASONRY WALL AND PARTITIONS.
10. WHERE NEW MASONRY INTERSECTS EXISTING PROVIDE DUR-O-WAL DA 2200 JOINT
STABILIZER ANCHORS AT 400 c/c VERTICALLY.
11. WE HAVE REVIEWED THE REMOVAL OF EXISTING WALLS, AS NOTED ON PLAN, AND IN OUR
OPINION THEIR REMOVAL DOES NOT IMPACT THE STRUCTURAL PERFORMANCE,
INCLUDING LATERAL SYSTEMS OF THE BUILDING.
12. FULLY INFILL ALL ABANDONED DUCT OPENINGS. INFILL USING CONC BLOCK TO MATCH
EXISTING. PACK TIGHT TO U/S EXIST LINTELS/ SLAB ABOVE. CONTRACTOR TO CONFIRM
EXACT LOCATION AND NUMBER OF ABANDONED OPENINGS WITH MECH.
13. STRUCTURAL DOCUMENTS DO NOT NECESSARILY SHOW ALL NEW MECHANICAL/
ELECTRICAL SERVICE. PENETRATIONS THROUGH EXIST CONCRETE BLOCK WALLS. REFER
TO MECHANICAL/ ELECTRICAL DRAWINGS FOR ALL SUCH LOCATIONS. FOR OPENINGS
THROUGH WALL GREATER THAN 300 WIDE PROVIDE NEW STEEL LINTEL PER TYPICAL
DETAIL TD-S01. OFFSET OPENINGS SUCH THAT THEY DO NOT FALL DIRECTLY BELOW
BEARING OF EXIST STRUCTURAL BEAMS/ JOISTS ABOVE. TYPICAL.
ADD NEW P2
STUB POST EA SIDE
DOOR. REFER TO
SECTION.
PROVIDE 10M DOWELS @ 400 c/c
x 300 LG. DRILL & EPOXY INTO
EXIST MORTAR JOINTS.
PROVIDE 100 EMBED. TYPICAL
EA END WALL INFILL.
F
T
G
2
E
X
5
6
0
Ø
C
O
N
C
C
A
I
S
S
O
N
+
7
6
0
x
7
6
0
x
4
8
0
C
O
N
C
P
I
L
E
C
A
P
T
/
O
P
I
L
E
C
A
P
-
0
.
1
8
0
(
S
I
T
E
V
E
R
I
F
Y
)
E
C
2
F
T
G
2
E
C
2
F
T
G
2
E
C
2F
T
G
2
E
C
2E
X
W
2
0
0
x
5
9
E
C
2
F
T
G
2
EXIST 140 NON-LOAD BEARING CONC
BLOCK PARTITION WALL. SITE VERIFY.
N
KNEE WALL
REFER TO ARCH
S401
3
NEW WALL OPENING. REFER TO ARCH. PROVIDE NEW CONT L152x102x9.5
(LLV) GALV STEEL LINTEL (ACROSS BOTH OPENINGS) FOR BRICK VENEER TO
REMAIN ABOVE. MODIFY EXIST BACKING STUD WALL TO ACCOMMODATE
NEW. PROVIDE TEMPORARY SHORING AS REQUIRED TO SUPPORT BRICK
VENEER DURING LINTEL INSTALLATION.
S401
5
TYP @ P1
S401
5
TYP @ P1
FULLY GROUT END
PIER FULL HEIGHT
FULLY GROUT END
PIER FULL HEIGHT
EXIST FHC OPENING
TO REMAIN
S402
1
S402
3TYP
CORRIDOR
OPENING
S402
3
SIM
NEW MECH WALL VENT OPENING
ABOVE PROVIDE GALV STEEL LINTEL
FOR BRICK VENEER PER TYPICAL
DETAIL. PROVIDE TEMPORARY
SHORING FOR BRICK AS REQUIRED
TO INSTALL. TYPICAL ALL MECH WALL
VENT LOCATION. CONFIRM EXACT
NUMBER AND LOCATION W/
MECHANICAL
S402
1
FULLY GROUT END
PIER FULL HEIGHT
FULL GROUT PIER TO
REMAIN BETWEEN
OPENINGS.
2018_06
DWG. No.:
DATE: NOV. 2018
PROJECT No.:
TITLE:
Tel. (905) 623 7476
J.R. FREETHY ARCHITECT
BOWMANVILLE ONTARIO325 LAKE ROAD, SUITE 202
PROJECT:
L1C 4P8
CLIENT:
BAYVIEW HEIGHTS
PUBLIC SCHOOL
CHILD CARE
CLIENT:
1400 GARVOLIN ROAD, PICKERING, ON
Project No. 19-1648
All reproduction & intellectual property rights reserved c 2019
207 Adelaide St. E., Suite 200
Toronto, ON M5A 1M8
416-599-(LINK) 5465
www.engineeringlink.ca
1 ISSUED FOR COORDINATION RAD 2019 - 09 - 26
2 ISSUED FOR COORDINATION RAD 2019 - 12 - 06
3 RAD 2021 - 02 - 16ISSUED FOR PERMIT & TENDER
S201
EXIST GROUND FLOOR
EL 0.000 m
U/S NEW WINDOW
CONFIRM WITH ARCH
TOP OF OPENING
EL + 1.730 m
CONFIRM WITH ARCH
EXIST GRADE
EL VARIES
EXIST 92 LIGHT GAUGE
STEEL STUD. SITE VERIFY
10
5
EX
TE
NT
N
EW
W
AL
L O
PE
NIN
G
CO
NF
IR
M W
IT
H A
RC
H
± 508
SITE VERIFY
305
SITE VERIFY
EXIST CONC GRADE BEAM
NEW FULL HEIGHT BUILT-UP
LIGHT GAUGE STEEL STUD COLUMN
BEYOND. TYPICAL EACH SIDE
NEW OPENING BY STUD SUPPLIER
NEW BUILT-UP LIGHT GAUGE
STEEL LINTEL ABOVE OPENING
BY STUD SUPPLIER
PROVIDE TEMPORARY SHORING
AS REQUIRED
EXIST 100 BRICK VENEER
NEW GALV STEEL LINTEL FOR
VENEER AS PER TYPICAL DETAIL
MAINTAIN EXIST BRICK BELOW NEW
OPENING. MAKE GOOD AS PER ARCH
DWGS.
NEW OPENING
REFER TO ARCHEXIST 100 BRICK VENEER
NEW BUILT-UP STUD COLUMN BY STUD
SUPPLIER
TYPICAL EACH SIDE OPENING
EXIST WALL STUD
TO REMAIN
MODIFIED EXIST 92 LIGHT GAUGE
STUDS ABOVE OPENING
BY STUD SUPPLIER
SIT
E
VE
RIF
Y
EXIST 100 CONC
SLAB ON GRADE
1:10
S401
2
1:10
S401
4
S401
4
D
D
T/O GROUND FLOOR
ELEV: +0 (SITE VERIFY)
W140
WALL
C
L
NEW NON LOAD BEARING
MASONRY PARTITION.
REFER TO ARCH.
EXIST SLAB ON GRADE
REINF. BOND COURSE
PER PLAN
1:10
S401
1
EXIST GROUND FLOOR
EL 0.000 m
U/S LINTEL
EL CONFIRM WITH ARCH
LOCALLY DEMOLISH TOP OF EXIST GRADE BEAM
ACROSS EXTENT OF NEW DOOR CONCRETE SILL.
TERMINATE REMOVAL OF EXIST CONCRETE
LEVEL W/ EXIST SLAB ON GRADE. DO NOT OVER
CHIP. EXTENT OF REMOVAL SHALL NOT EXCEED
WIDTH OF NEW DOOR OPENING. CONFIRM
CLEAR DIMENSION W/ ARCH.
10
5
EX
TE
NT
N
EW
D
OO
R O
PE
NIN
G
CO
NF
IR
M W
IT
H A
RC
H
± 508
SITE VERIFY
305
SITE VERIFY
EXIST CONC GRADE BEAM
NEW BUILT-UP LIGHT GAUGE STUD COLUMN
EACH SIDE OF OPENING AND BUILT-UP STUD
LINTEL SIMILAR TO 2/S401
BY STUD SUPPLIER
NEW FROST SLAB. REFER TO
PLAN FOR REINF. CONFIRM
DIMENSIONS, SLOPE & ELEVATION
W/ ARCH.
MODIFIED EXIST WALL STUDS
ABOVE OPENING SIMILAR TO
2/S401 BY STUD SUPPLIER
SIT
E
VE
RIF
Y
EXIST 100 CONC SLAB ON GRADE
PROVIDE TEMPORARY
SHORING AS REQUIRED
EXISTING LINTEL TO REMAIN
OVER EXIST WINDOW
1:10
S401
3
S401
4
SIM
D
EXIST CONT L89x89
TO REMAIN
2- L76x76x6.4 STUB POST
TO REMAIN
SLOPE
± 1
20
0 M
IN
UNSHRINKABLE FILL
FORM SIDES OF FROST SLAB
ALL SIDES . TYPICAL.
20
0
15M DOWELS x300 LG @ 300 c/c.
DRILL AND EPOXY INTO EXIST USING HILTI
HIT HY 200 ADHESIVE. PROVIDE 90 EMBED.
ALIGN DOWEL W/ FROST SLAB REINF.
S402
1
FOR CUTTING OF KNEE
WALL FRAMING TYP @
DOORS ( 2 LOCATIONS)
D
1:10
S401
5
U/S NEW LINTEL
EL CONFIRM WITH ARCH
100
EXIST GRADE
± 485
SITE VERIFY
EX 2ND FLOOR
EL +3.610 SITE VERIFY
TYP
TJ @ COL
NEW HSS 76x76x7.9 OUTRIGGER
CENTRED ON EX EC1 & NEW P1
EC1
± 300
EXIST GRADE BEAM
PROVIDE 25
NON-SHRINK GROUT
EX 5mm CONT BENT PL
TO REMAIN
SITE VERIFY
EX AGGREGATE PANEL
VENEER TO REMAIN
EX BACK UP FRAMING TO
REMAIN
EX BRICK VENEER OVER
WINDOWS ( ± 4 COURSES) TO
REMAIN. CONFIRM W/ ARCH.
REMOVE & REBUILD DURING
LINTEL INSTALL OR PROVIDE
TEMPORARY SHORING
EX 18 WF
EX L127x102 (LLV) SHELF
NEW CONT L152x102x9.5 (LLV)
GALV SHELF ANGLE CONT
ACROSS TWO NEW WINDOW
OPENINGS PROVIDE MIN 200
SOLID BEARING EACH END
± 25 mm GAP
REFER TO ARCH FOR
CLADDING BTW NEW
WINDOWS. TIE BACK TO
NEW P1 POST W/ CLIPS
SIMILAR TO TYPICAL
DETAIL TD-M07
NEW P1
EX CONT L89x89 LOCALLY CUT
OUT ANGLE AT P1 & REWELD
L89x89 TO EACH SIDE NEW
POST ALL AROUND. TYPICAL
EX BRICK VENEER TO
REMAIN BELOW OPENING.
CONFIRM W/ ARCH. TYPICAL
GRIND TOP OF EXIST GRADE
BEAM LEVEL AT NEW BASE
PLATE MAX +/- 19mm
REMOVAL. TYPICAL.
NEW GALV STEEL LINTEL FOR
VENEER AS PER TYPICAL DETAIL
EXISTING / NEW BRICK VENEER
REFER TO ARCH
INFILL EXTENT OLD WINDOW W/
NEW LIGHT GAUGE STEEL STUD.
REFER TO ARCH.
6mm CAP PLATE
± 10 mm MAX TOE ANGLE
TO FACE VENEER
EXIST STUD LINTEL TO REMAIN.
SITE VERIFY
S401
2018_06
DWG. No.:
DATE: NOV. 2018
PROJECT No.:
TITLE:
Tel. (905) 623 7476
J.R. FREETHY ARCHITECT
BOWMANVILLE ONTARIO325 LAKE ROAD, SUITE 202
PROJECT:
L1C 4P8
CLIENT:
BAYVIEW HEIGHTS
PUBLIC SCHOOL
CHILD CARE
CLIENT:
1400 GARVOLIN ROAD, PICKERING, ON
Project No. 19-1648
All reproduction & intellectual property rights reserved c 2019
207 Adelaide St. E., Suite 200
Toronto, ON M5A 1M8
416-599-(LINK) 5465
www.engineeringlink.ca
1 ISSUED FOR COORDINATION RAD 2019 - 09 - 26
2 ISSUED FOR COORDINATION RAD 2019 - 12 - 06
3 RAD 2021 - 02 - 16ISSUED FOR PERMIT & TENDER
C
P2
EXIST GROUND FLOOR
EL 0.000 m
P2
NEW HSS 76x76x6.4 STUB POST W/
200x10x150 BASE PL WITH TWO - 12 Ø
HILTI HAS-E RODS + HILTI HY200
ADHESIVE. PROVIDE 115 EMBEDMENT.
± 200
AT DOOR
± 100
AT SIDELITE
N
E
W
D
O
O
R
A
N
D
S
I
D
E
L
I
T
E
± 9
80
S
IT
E V
ER
IF
Y
L
C
P2
L
LOCALLY REMOVE KNEE WALL
FRAMING WITHIN OPENING.
TOP EXIST
GRADE BEAM
SITE VERIFY
LOCALLY DEMOLISH TOP OF
GRADE BEAM @ DOOR
REFER TO 3/S401.
EXIST TWO - L76x76x6.4
STUB POST @ ± 1750 c/c
SITE VERIFY
WALL INFILL STUD NOT SHOWN
FOR CLARITY
EXIST CONT L89x89, TYP.
S402
2
1:10
S402
1
P2
C
P2
L
150
NEW P2 FULLY WELD TO
EX L89x89
EX CONT L89x89
EX GRADE BEAM
300
1:10
S402
2
10
5
SIT
E V
ER
IF
Y
@ P2 TYP
NS & FS
5
EXIST GROUND FLOOR
EL 0.000 m
10
0
SIT
E V
ER
IF
Y
EXIST SLAB ON GRAGE
1:10
S402
3
PROVIDE TEMPORARY
SHORING AS REQUIRED
TO INSTALL LINTEL
MAKE GOOD/ PATCH EXIST SLAB
ACROSS OPENING AS REQUIRED
LOCALLY DEMO BLOCK @ NEW
OPENING
U/S LINTEL
SEE ARCH
NEW LINTEL PER
TYPICAL DETAIL
EXISTING NON-LOAD BEARING CONC
BLOCK WALL (SITE VERIFY)
S402
2018_06
DWG. No.:
DATE: NOV. 2018
PROJECT No.:
TITLE:
Tel. (905) 623 7476
J.R. FREETHY ARCHITECT
BOWMANVILLE ONTARIO325 LAKE ROAD, SUITE 202
PROJECT:
L1C 4P8
CLIENT:
BAYVIEW HEIGHTS
PUBLIC SCHOOL
CHILD CARE
CLIENT:
1400 GARVOLIN ROAD, PICKERING, ON
Project No. 19-1648
All reproduction & intellectual property rights reserved c 2019
207 Adelaide St. E., Suite 200
Toronto, ON M5A 1M8
416-599-(LINK) 5465
www.engineeringlink.ca
1 ISSUED FOR COORDINATION RAD 2019 - 09 - 26
2 ISSUED FOR COORDINATION RAD 2019 - 12 - 06
3 RAD 2021 - 02 - 16ISSUED FOR PERMIT & TENDER