Page 1: S&C Type FVR Vacuum Substation Circuit BreakerC Type FVR Vacuum Substation Circuit Breaker 15 kV to 38 kV, ... Air Flow Switches ... • Control Diagram Number • Closing Time

S&C ELECTRIC COMPANY

Specialists in Electric Power Switching and Protection

Instruction Sheet 767-500March 17, 2003

©

2003

New Publication

6065

-300

1

S&C Type FVR Vacuum Substation Circuit Breaker

15 kV to 38 kV, 110 kV BIL to 150 kV BIL, 1200 A to 4000 A, Class 6065

Instructions for Installation

Page 2: S&C Type FVR Vacuum Substation Circuit BreakerC Type FVR Vacuum Substation Circuit Breaker 15 kV to 38 kV, ... Air Flow Switches ... • Control Diagram Number • Closing Time
Page 3: S&C Type FVR Vacuum Substation Circuit BreakerC Type FVR Vacuum Substation Circuit Breaker 15 kV to 38 kV, ... Air Flow Switches ... • Control Diagram Number • Closing Time

3 767-500

SECTION 1—INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Catalog Numbers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

SECTION 2—SAFETY PRECAUTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . 6

SECTION 3—RECEIVING, HANDLING, AND STORAGE . . . . . . . . . . . . . 8

Receiving . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

Handling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

Identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

SECTION 4—DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

Fan Cooling Circuit (4000 A circuit breakers only) . . . . . . . . . . . . . . 10

Fan Control Current Transformer (CT) . . . . . . . . . . . . . . . . . . . . 11

Current Sensing Relay (CSR) . . . . . . . . . . . . . . . . . . . . . . . . . . 11

Fan Control Relay (CR) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

Fan Test Switch (TF) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

Fan Alarm Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

Alarm Time Delay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

Air Flow Switches (FS1, FS2) . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

High-Voltage Compartment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

Vacuum Interrupters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

Current Transformers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

Low-Voltage Compartment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

Operating Mechanism . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

Closing Springs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

Opening Springs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

Control Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

Low-Voltage Instrument Door (Optional) . . . . . . . . . . . . . . . . . . . . . . 19

Indicator Lights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

Circuit Breaker Control Switch . . . . . . . . . . . . . . . . . . . . . . . . . . 19

SECTION 5—OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

Charging the Closing Spring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

Closing Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

Opening Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

Manual Opening Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

Mechanical Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

Electrical Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

Manual Trip Reset Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

Fan Operation (4000 A circuit breakers only) . . . . . . . . . . . . . . . . . . 21

Automatic Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

Manual Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

SECTION 6—INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

Foundation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

Lifting the Circuit Breaker . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

Initial Circuit Breaker Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

Arc-Resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

Cable Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

Pre-Operation Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27

CONTENTS

TABLE OF CONTENTS

Page 4: S&C Type FVR Vacuum Substation Circuit BreakerC Type FVR Vacuum Substation Circuit Breaker 15 kV to 38 kV, ... Air Flow Switches ... • Control Diagram Number • Closing Time

767-500 4

SECTION 7—MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28General Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28Insulating Surfaces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28Air Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29Vacuum Interrupters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29Contact Erosion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29E-Gap . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30Contact Gap . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30Hi-Pot (Dielectric) Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30Resistance Measurement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31Lubrication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31

SECTION 8—REPLACEMENT PARTS . . . . . . . . . . . . . . . . . . . . . . . . . .32Ordering Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32

SECTION 9—MAINTENANCE LOG . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34

Figure 1: 110 kV BIL to 150 kV BIL, Type FVR Vacuum Circuit Breaker, Front View. . . . . . . . . . . . . . . . . . . . . . . . . .10

Figure 2: Typical Fan Control Schematic, 4000 A Circuit Breaker . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

Figure 3: Vacuum Interrupter Assembly . . . . . . . . . . . . . . . . . . . . . . 13Figure 4: High-Voltage Compartment Interior . . . . . . . . . . . . . . . . . . 13Figure 5: Operating Mechanism (Two Views with and

without Mechanism Cover) . . . . . . . . . . . . . . . . . . . . . . . . . .14Figure 6: Typical Control Schematic—Breaker in Open Position,

Springs Discharged. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16Figure 7: Low-Voltage Compartment, Rear View . . . . . . . . . . . . . . . 18Figure 8: Low-Voltage Instrument Door (Optional) . . . . . . . . . . . . . . 19Figure 9: Gear and Ratchet Detail . . . . . . . . . . . . . . . . . . . . . . . . . . . 20Figure 10: Plan View for Type FVR Circuit Breaker. . . . . . . . . . . . . . . 22Figure 11: Vent Covers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25Figure 12: Vent Deflectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25Figure 13: Vent Lids. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25Figure 14: Air Filter Locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29Figure 15: Measuring E-Gap . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30Figure 16: Vacuum Interrupter Assembly . . . . . . . . . . . . . . . . . . . . . . 31

Table 1: Catalog Numbering Scheme. . . . . . . . . . . . . . . . . . . . . . . . . 5Table 2: Hi-Pot Test Voltages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27Table 3: Nominal E-Gap Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . 30Table 4: Resistance Measurement Values . . . . . . . . . . . . . . . . . . . . 31Table 5: Lubrication Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31Table 6: Replacement Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32

FIGURES

TABLES

TABLE OF CONTENTS

Page 5: S&C Type FVR Vacuum Substation Circuit BreakerC Type FVR Vacuum Substation Circuit Breaker 15 kV to 38 kV, ... Air Flow Switches ... • Control Diagram Number • Closing Time

5 767-500

This bulletin contains instructions for installation, operation, and maintenance of the S&C Type FVR series circuit breakers (up to 150 kV BIL) manufactured by Square D.

It is important to read and understand this bulletin completely before performing the installation, operation, and maintenance steps provided. Electrical equipment should be installed and serviced only by qualified personnel. Qualified personnel should establish procedures that ensure the safety of personnel and equipment.

The Type FVR circuit breaker is designed for outdoor substation applications and provides interrupting capability for medium voltage systems up to 38 kV. Circuits in which these circuit breakers are placed are capable of overvoltages. Complex medium voltage systems may require a detailed overvoltage system analysis and the addition of overvoltage protection.

All Type FVR circuit breakers except those rated at or above 3000 A have been designed with an arc-resistant enclosure. The 4000 A rating requires the use of a fan circuit.

The following is an explanation and sample of the catalog numbering scheme:

Table 1: Catalog Numbering Scheme

* = Fan cooled

NOTE: Not to be used for ordering.

TypeVoltage Class

Continuous Current Rating

BIL RatingInterruption Rating

SeriesDesignation

FVR—Vacuum1 = 15 kV2 = 27 kV3 = 38 kV

06 = 600 A08 = 800 A12 = 1200 A20 = 2000 A30 = 3000 A35 = 3500 A40 = 4000 A*

11 = 110 kV12 = 125 kV15 = 150 kV

12 = 12 kA16 = 16 kA20 = 20 kA25 = 25 kA31 = 31.5 kA40 = 40 kA

A

SECTION 1—INTRODUCTION

Catalog Numbers

Catalog Number—FVR 1 12 11 16 A

Series Designation

Interrupting Rating

BIL Rating

Continuous Current Rating

Voltage Class

Type

INTRODUCTION

Page 6: S&C Type FVR Vacuum Substation Circuit BreakerC Type FVR Vacuum Substation Circuit Breaker 15 kV to 38 kV, ... Air Flow Switches ... • Control Diagram Number • Closing Time

767-500 6

SECTION 2—SAFETY PRECAUTIONS

HAZARD OF ELECTRIC SHOCK, BURN, OR EXPLOSION.

• Only qualified personnel familiar with medium voltage circuits are to perform work described in this set of instructions. Workers must understand the hazards involved in working with or near medium voltage equipment.

• Perform such work only after reading and understanding all of the instructions contained in this bulletin.

• Before performing visual inspections, tests, or maintenance on this device, disconnect all sources of electric power. Assume all circuits are live until they are completely de-energized, tested, grounded, and tagged. Pay particular attention to the design of the power system. Consider all sources of power, including the possibility of backfeeding. Before performing maintenance on this device, disconnect all sources of control power.

• Turn off all power supplying this equipment before working on or inside equipment.

• Always use a properly rated voltage sensing device to confirm that power is off.

• Replace all devices, doors, and covers before turning on the power to this equipment.

• Handle this equipment carefully and install, operate and maintain it correctly in order for it to function properly. Neglecting fundamental installation and maintenance requirements may lead to personal injury, as well as damage to electrical equipment or other property.

• Be aware of potential hazards, wear personal protective equipment, and take adequate safety precautions.

• Do not make any modifications to the equipment or operate the system with interlocks removed. Contact your local S&C Electric Company representative for additional instructions if the equipment does not function as described in this manual.

• Carefully inspect your work area and remove any tools and objects left inside the equipment.

• All maintenance must be performed in accordance with local codes and under the following conditions:

— The circuit breaker must be isolated from all power sources.

— Control voltage must be removed from the controls.

— The circuit breaker must be in the open position.

— All circuit breaker springs must be discharged.

• All instructions in this manual are written with the assumption that the customer has taken these measures before performing maintenance or testing.

Failure to follow these instructions will result in death or serious injury.

DANGER

SAFETY PRECAUTIONS

Page 7: S&C Type FVR Vacuum Substation Circuit BreakerC Type FVR Vacuum Substation Circuit Breaker 15 kV to 38 kV, ... Air Flow Switches ... • Control Diagram Number • Closing Time

7 767-500

Read these instructions carefully and look at the equipment to become familiar with the device before trying to install, operate, or maintain it. The following special messages may appear throughout this bulletin or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure.

The addition of either symbol to a “Danger” or “Warning” safety label indicates that an electrical hazard exists which will result in personal injury if the instructions are not followed.

This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow this symbol to avoid possible injury or death.

This is the radiation area or radioactive materials symbol. It is used to alert you to potential equipment or materials that may cause radiation exposure. Obey all safety messages that follow this symbol to avoid possible exposure, injury, or death.

NOTE: Provides additional information to clarify or simplify a procedure.

Electrical equipment should be installed, operated, serviced, and maintained only by qualified electrical personnel. This document is not intended as an instruction manual for untrained persons. No responsibility is assumed by S&C Electric Company for any consequences arising out of the use of this manual.

NOTICE

DANGERDANGER indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.

WARNINGWARNING indicates a potentially hazardous situation which, if not avoided, can result in death or serious injury.

CAUTIONCAUTION indicates a potentially hazardous situation which, if not avoided, can result in minor or moderate injury.

CAUTION, used without the safety alert symbol, indicates a potentially hazardous situation which, if not avoided, can result in property damage.

CAUTION

PLEASE NOTE

SAFETY PRECAUTIONS

Page 8: S&C Type FVR Vacuum Substation Circuit BreakerC Type FVR Vacuum Substation Circuit Breaker 15 kV to 38 kV, ... Air Flow Switches ... • Control Diagram Number • Closing Time

767-500 8

Upon receipt, check the packing list against the equipment received to ensure the order and shipment are complete. Claims for shortages or errors must be made in writing to S&C Electric Company within 60 days after delivery. Failure to give such notice will constitute unqualified acceptance and a waiver of all such claims by the purchaser.

Immediately inspect the equipment for any damage which may have occurred in transit. If damage is found or suspected, file a claim with the carrier immediately and notify S&C Electric Company. Delivery of equipment to a carrier at any of the S&C Electric Company plants or other shipping points constitutes delivery to the purchaser regardless of freight payment and title. All risk of loss or damage pass to the purchaser at that time.

For details concerning claims for equipment shortages and other errors, refer to S&C Electric Company “Terms and Conditions of Sale”.

Lifting eyes (see Figure 1 on page 10) are provided on the roof of the Type FVR circuit breaker for lifting by crane. No spreader bars are required. Handle the equipment with care. Protect the bushings from rough treatment to avoid chipping.

If lifting the circuit breaker by forklift, place the forklift forks underneath the low-voltage compartment (see Figure 1 on page 10) and secure the circuit breaker to the forklift with a strap. The floor of the low-voltage compartment is reinforced to support the weight of the circuit breaker. Do not lift by the side vent housings or any other protrusions. If another handling method is necessary, contact S&C Electric Company to make special preparations.

View the OPEN-CLOSED indicator (see Figure 5 on page 14) to verify the mechanism/breaker position. The Type FVR circuit breaker is shipped with the breaker in the closed position.

SECTION 3—RECEIVING, HANDLING, AND STORAGE

Receiving

Handling

TOP HEAVY LOAD.

If lifting the circuit breaker by forklift, stabilize the circuit breaker with a safety strap to reduce the possibility of tipping.

Failure to follow this instruction can result in death or serious injury.

WARNING

DO NOT LIFT CIRCUIT BREAKER BY SIDE VENT HOUSINGS.

Damaged vent housings can constrict proper air flow and expose interior of high-voltage compartment to weather.

Failure to follow this instruction can result in equipment damage.

CAUTION

RECEIVING, HANDLING, AND STORAGE

Page 9: S&C Type FVR Vacuum Substation Circuit BreakerC Type FVR Vacuum Substation Circuit Breaker 15 kV to 38 kV, ... Air Flow Switches ... • Control Diagram Number • Closing Time

9 767-500

If the circuit breaker must be stored before operation, keep it in a clean, dry, corrosion-free area protected from damage. Inspect the circuit breaker regularly when stored for prolonged periods.

NOTE: The Type FVR circuit breaker is equipped with strip heaters that must be energized during storage to prevent condensation within the circuit breaker housing. Verify that the heater thermostat is set at 75° F (24° C).

The rating nameplate is located on the inside of the rear low-voltage door and includes the following information:

• Catalog Number• Weight (lbs)• Rated Max. Voltage (kV RMS)• Reclosing time (cycles)• Duty Cycle (O–CO–15 seconds–CO)• Closing Coil Voltage• Serial Number• Factory Order Number• Rated Frequency (hz)• Full Wave BIL (kV Pk)• Charging Motor Voltage• Manufacture Date• Maintenance Manual Number• Interrupt Time (cycles)• 1 Minute Withstand (kV RMS)• Rated Short Circuit (kA RMS)• Spare Auxiliary Switch Contacts• Customer PO Number• Control Diagram Number• Closing Time (cycles)• Close and Latch (kA RMS)• Tripping Coil Voltage

Storage

Identification

RECEIVING, HANDLING, AND STORAGE

Page 10: S&C Type FVR Vacuum Substation Circuit BreakerC Type FVR Vacuum Substation Circuit Breaker 15 kV to 38 kV, ... Air Flow Switches ... • Control Diagram Number • Closing Time

767-500 10

The Type FVR circuit breaker enclosure contains two separate compartments; a high-voltage compartment and a low-voltage compartment (see Figure 1).

Figure 1: 110 kV BIL to 150 kV BIL, Type FVR vacuum circuit breaker, front view.

Added cooling capacity is required on 4000 A breakers when the primary current exceeds 3600 A. A fan (FM1 & FM2) is mounted in each vent housing (see Figure 1) to create additional airflow required for cooling the breaker. A selector switch (SS) mounted to the right of the mechanism; is used to select automatic or manual mode of operation. For fan operation instructions see “Fan Operation (4000 A circuit breakers only)” on page 21.

The fan cooling circuit consists of:

— fan control current transformer (CT)— current sensing relay (CSR)— fan control relay (CR)— fan test switch— fan alarm circuit— alarm time delay— air flow switches (FS1, FS2)

SECTION 4—DESCRIPTION

Bushing studs

Roof bushings

Lifting eye

Vent lid

Vent housing(Fan location for 4000 A breakers)

Ground padsManual trip knob

Viewing window

Adjustable legs

Galvanizedbase channel

6055

9501

High-voltagecompartment

Low-voltagecompartment

Fan Cooling Circuit (4000 A circuit breakers only)

DESCRIPTION

Page 11: S&C Type FVR Vacuum Substation Circuit BreakerC Type FVR Vacuum Substation Circuit Breaker 15 kV to 38 kV, ... Air Flow Switches ... • Control Diagram Number • Closing Time

11 767-500

With the selector switch (SS) in the AUTO position, a separate 4000/5 current transformer senses the primary current and controls the fan operation. This current transformer (CT) is mounted on the number 4 bushing.

With the selector switch (SS) in the AUTO position, the current sensing relay monitors the secondary current of the current transformer (CT). The relay opens its normally closed output contact when the primary current exceeds 3600 A. When the primary current reaches 3240 A, the relay drops out shutting off the fan circuit.

NOTE: Do not alter the settings of this relay.

With the selector switch (SS) in the AUTO position, the normally energized fan control relay (CR) is de-energized when the current sensing relay’s normally closed output contacts open. The (CR) relay applies control power to both fans through its normally closed contacts. The (CR) relay also has an “off” time delay contact which is used in the Customer’s Alarm Circuit.

This push button switch activates the fans if pressed while the selector switch (SS) is in the “auto” position. This test will verify the fan control relay circuitry is operating correctly.

This circuit is used to detect any malfunction in the operation of the fan circuit. The fan alarm circuit contacts close when either of the two fans fail to activate the flow switch. Connect this circuit to an alarm or light to warn against insufficient airflow. The circuit consists of two airflow switches (FS1 & FS2) which are located in the airflow path of each blower. These switches are connected in series with the “off” time delay contact of the control relay (CR). This circuit functions in both the “automatic” and “manual” mode.

When initially energized, the fans require a few seconds to develop enough airflow to actuate their respective air flow switches (FS1 & FS2). To avoid a false alarm during start-up periods, the “off” time delay contacts on the control (CR) relay blocks the alarm circuit briefly. This delay (10 seconds) gives the fans time to build adequate airflow to activate the switches.

Each airflow switch contains a set of normally closed contacts that are wired into the Customer Alarm Circuit. If the switch is not activated by the airflow from the fan, the signal is sent to the alarm circuit.

Fan Control Current Transformer (CT)

Current Sensing Relay (CSR)

Fan Control Relay (CR)

Fan Test Switch (TF)

Fan Alarm Circuit

Alarm Time Delay

Air Flow Switches (FS1, FS2)

DESCRIPTION

Page 12: S&C Type FVR Vacuum Substation Circuit BreakerC Type FVR Vacuum Substation Circuit Breaker 15 kV to 38 kV, ... Air Flow Switches ... • Control Diagram Number • Closing Time

767-500 12

Figure 2: Typical fan control schematic, 4000 A circuit breaker, (refer to customer order drawings for actual schematic).

21

43

21

43

165 21

A1 A

2

1A 2A

BA2

15

16

TA-F2

TA-F1

CT4000/5A

X1

CSRCB2

X2

13A 13NC

NC

COM

COM

OFFDELAY

120 VAC60 Hz

FM1 FM2

CR

CRCR

CSR

CSR

PH1-1 PH3-1

CH1-1 CH3-1

TBF-1

CH1-2

CH2-2

PH2-1PH2-2

CH2-1

CH4-2

PH4-1PH4-2

CH4-1

CH3-2

PH1-2 PH3-2

SS TFSSFU

FU

F1/10A

F1/10A

CUSTOMER'S ALARMRATING 10 A @ 120 VAC

TA-F3

TA-F4

TBF-3

FS2

FS110 SECCR/TD

TBF-4

6065

3040

LEGEND

CSR Current Sensing Relay CT Current Transformer

FM1 Fan Motor (Left) SS Auto/Manual Selector Switch

FM2 Fan Motor (Right) TBF Fan Control Terminal Block

CR Fan Control Relay FU Fuse

TF Test Fan Push Button PH Disconnect Male Plug Housing

FS1 Air Flow Switch (Left) CH Disconnect Female Plug

FS2 Air Flow Switch (Right)

NOTE: The SS Selector Switch is shown in the AUTO position. All other contacts are shown with relays de-energized.

DESCRIPTION

Page 13: S&C Type FVR Vacuum Substation Circuit BreakerC Type FVR Vacuum Substation Circuit Breaker 15 kV to 38 kV, ... Air Flow Switches ... • Control Diagram Number • Closing Time

13 767-500

The primary circuit connection to the circuit breaker is made through the roof bushings (see Figure 1 on page 10) located on the top of the high-voltage compartment.

Vacuum interrupters (see Figure 3), mounted horizontally within the high-voltage compartment, perform interruption in a Type FVR circuit breaker. The vacuum interrupters consist of a pair of contacts—one contact is movable and one contact is fixed. The vacuum interrupters require only a short gap to provide the dielectric withstand capability of the interrupter.

Figure 3: Vacuum interrupter assembly.

NOTE: Some vacuum interrupter assembly equipment shown in Figure 3 may vary on circuit breakers.

When specified by the customer, current transformers (see Figure 4) are mounted around the bushings on the inside of the roof. Current transformer (CT) circuit wiring extends from the CT case to the shorting type terminal blocks located in the low-voltage compartment. The CTs are selected based on the electrical needs of each application.

Figure 4: High-voltage compartment interior.

NOTE: Some vacuum interrupter assembly equipment shown in Figure 4 may vary on circuit breakers.

High-Voltage Compartment

Vacuum Interrupters

Vacuum interrupter

6065

3003

Current Transformers

Current transformers

Bushing

Vent deflector

Flex connector

Crossbar

6065

3004

Crossbar stops

DESCRIPTION

Page 14: S&C Type FVR Vacuum Substation Circuit BreakerC Type FVR Vacuum Substation Circuit Breaker 15 kV to 38 kV, ... Air Flow Switches ... • Control Diagram Number • Closing Time

767-500 14

The operating mechanism, indicators, controls, relays, meters and miscellaneous accessories are housed within the low-voltage compartment.

The Type FVR circuit breaker uses a stored-energy operating mechanism (see Figure 5) in which charged springs open and close the circuit breaker. The operating mechanism contains all controls and interlocks. The mechanism is mounted in the low-voltage compartment so it can be accessed easily for inspection and servicing.

NOTE: To remove the mechanism cover (see Figure 5), carefully unclip the back of the cover from the mechanism frame.

Figure 5: Operating mechanism (two views with and without mechanism cover).

The operating mechanism has three indicators. The OPEN-CLOSED indicator (see Figure 5) shows the position (open or closed) of the vacuum interrupter contacts. The CHARGED-DISCHARGED indicator (see Figure 5) displays the state (charged or discharged) of the closing springs. The COUNTER (see Figure 5) indicates the number of trip (open) operations the circuit breaker has performed.

The closing springs (see Figure 5) close the circuit breaker when the CLOSE push button is pressed or when the closing coil is energized. These springs are charged (compressed) either manually with the charging handle or electrically by the spring charging motor.

When control power is applied to the circuit breaker, the spring charging motor is energized. The charging motor turns the gears that drive the ratchet assembly up and down.

The ratchet assembly (see Figure 9 on page 20) rotates the drive shaft compressing the closing springs. As the spring loads pass top-dead center, the drive shaft rotates a few degrees until the closing latch roller engages the closing latch. The drive shaft can rotate no further; the closing springs are

Low-Voltage Compartment

Operating Mechanism

Spring charging motor (obstructed from view)

Opening springsGear boxMotor limit switch (obstructed from view)

Drive bar

CHARGED-DISCHARGED indicator

OPEN-CLOSED indicatorCounterMechanism coverOPEN push button

Latch check switchCLOSE push buttonClosing springsClose coilManual charging handleTrip coil

Auxiliary switchesManual trip reset switch (69 switch)

6065

3005

6065

3006

Indicators

Closing Springs

DESCRIPTION

Page 15: S&C Type FVR Vacuum Substation Circuit BreakerC Type FVR Vacuum Substation Circuit Breaker 15 kV to 38 kV, ... Air Flow Switches ... • Control Diagram Number • Closing Time

15 767-500

held in this charged position until a closing operation is initiated by depressing the CLOSE push button or closing coil.

The opening springs (see Figure 5 on page 14) open the circuit breaker when the OPEN push button is pressed or the trip coil is energized. These springs are charged (compressed) whenever the circuit breaker is in the closed position.

A typical schematic diagram for the control circuit of the Type FVR circuit breaker is shown in Figure 6 on page 16. A copy of the exact schematic diagram(s) and wiring diagram(s) for the circuit breaker are located in the manual holder on the rear door of the low-voltage compartment. The remaining paragraphs in this section discuss the function of the control circuit components.

• Motor Limit SwitchThe motor limit switch (see Figure 5 on page 14) energizes the spring charging motor when a closing spring charging operation is required. In turn, it de-energizes the spring charging motor when the closing springs are fully charged. The motor limit switch is connected to the spring charging motor. When the closing springs are in the discharged position, the motor limit switch cam actuates the motor limit switch. This energizes the motor and disables the closing coil. Once the closing springs are charged fully, the cam allows the switch to open, de-energizing the spring charging motor.

• Spring Charging MotorWhen energized by the closing of the motor limit switch, the spring charging motor (see Figure 5 on page 14) drives the series of connected gears and cam. The cam then raises and lowers the ratchet assembly and rotates the drive shaft. As the drive shaft rotates, the closing springs compress to the charged position. When the closing springs are fully charged, the motor limit switch contacts open, de-energizing the spring charging motor.

Opening Springs

Control Circuit

DESCRIPTION

Page 16: S&C Type FVR Vacuum Substation Circuit BreakerC Type FVR Vacuum Substation Circuit Breaker 15 kV to 38 kV, ... Air Flow Switches ... • Control Diagram Number • Closing Time

767-500 16

Figure 6: Typical control schematic—breaker in open position, springs discharged.

MotorCircuit Circuit Open Circuit

Close Coil Breaker Status Trip Coil

10

AC/DCSOURCE

15 A

15 A

3 51

2 4 6

52/LS

5

6

52/M

1

2

6

52/CC

1

2

52/LS1

2

52/LC2

1

52/b9

10

52/Y

1

4

69

1

3

CS/C

52/a

7

852/Y

6

8

52/Y

2

7

14 16

5 41

52/b13

1452/a

15

16

1513

CS/T

52/a4

3

52/a11

12

52/TC

1

2

(-)

4

5 97

(+)

9

Heater Circuit

(Each heater rated 240 V, 500 W)

240 Vac

8H/10A 23

31

2 4

35

36

HTR

HTR

L E G E N D

8C

G R

MOV

52/Y

1

3

LEGEND

52/M Spring Charging Motor 52/LC Latch Check Switch

52/Y Anti-pump Relay 52/LS Motor Limit Switch

CS Circuit Breaker Control Switch 52/CC Close Coil

52/a Auxiliary Switch(Open When Circuit Breaker is Open)

52//TC Trip Coil

8C Control Power Switch

52/b Auxiliary Switch(Closed When Circuit Breaker is Open) 69 Manual Trip Reset Switch

(69 switch)

23 Heater Thermostat 8H Heater Power Switch

MOV Metal Oxide Varistor

6055

3008

Trip CoilCircuit

DESCRIPTION

Page 17: S&C Type FVR Vacuum Substation Circuit BreakerC Type FVR Vacuum Substation Circuit Breaker 15 kV to 38 kV, ... Air Flow Switches ... • Control Diagram Number • Closing Time

17 767-500

• Auxiliary SwitchThe auxiliary switch (see Figure 5 on page 14) is a multi-stage switch used to operate circuits that are dependent upon the position of the circuit breaker contacts. The schematic diagram indicates how each of the auxiliary switch stages interconnect with the circuit breaker circuitry. The following describes the function of each stage:— The two sets of a-type contacts, connected in series with the trip coil

(52/TC), de-energize the trip coil when the circuit breaker is in the open position.

— The b-type contact, connected in series with the closing coil (52/CC), de-energizes the closing coil when the circuit breaker contacts are in the closed position.

— For user convenience additional a- and b-type contacts are included for optional use.

• Trip and Close CoilsThe trip and close coils (see Figure 5 on page 14) are located in the lower center of the operating mechanism. When energized, these coils release the open or close latches located inside the mechanism.

• Anti-Pump RelayAn anti-pump relay (see Figure 7 on page 18) is provided to inhibit multiple close-open operations in the event that a continuous close signal is applied. The circuit breaker will not reclose until the closing signal is removed and then reapplied.The circuit breaker control switch (see Figure 6 on page 16) energizes the closing coil when turned to the closed position. If this switch remains closed, the anti-pump relay prevents the closing springs from being continuously charged and discharged. The anti-pump relay performs this function by only allowing the closing coil to be energized if:

— The control switch is closed.— The closing springs have reached the fully charged position.— The spring charging motor has been de-energized.

• Latch Check SwitchThe latch check switch (see Figure 5 on page 14) allows the circuit breaker to be used for reclosing applications. When the trip latch moves out of its normal position, it activates the latch check switch. The closing circuit cannot be energized until the trip latch fully returns to its normal position and the mechanism is in position to allow a close operation.

DESCRIPTION

Page 18: S&C Type FVR Vacuum Substation Circuit BreakerC Type FVR Vacuum Substation Circuit Breaker 15 kV to 38 kV, ... Air Flow Switches ... • Control Diagram Number • Closing Time

767-500 18

• Heater CircuitryIn normal configurations, two strip heaters (see Figure 7) are mounted at the lower rear of the operating mechanism to reduce condensation. For colder temperatures, two additional strip heaters are mounted in the upper portion of the low-voltage compartment. In some applications, higher wattage heaters may be used.

• Heater Power SwitchWhen opened, the heater power switch (see Figure 6 on page 16) completely disconnects the heater circuitry from the control power.

• ThermostatThe thermostat controls the temperature within the circuit breaker housing. The thermostat is shipped set at 75° F (24° C) and should not be field adjusted.

Figure 7: Low-voltage compartment, rear view.

Terminal blocks

Conduit access plate

Shock absorber

Strip heaters

Heater thermostat

Anti-pump relay

Vent/filter

6065

9507

DESCRIPTION

Page 19: S&C Type FVR Vacuum Substation Circuit BreakerC Type FVR Vacuum Substation Circuit Breaker 15 kV to 38 kV, ... Air Flow Switches ... • Control Diagram Number • Closing Time

19 767-500

When specified by the customer, Type FVR circuit breakers are equipped with an instrument door located inside the rear door of the low-voltage compartment. This panel allows for local electrical operation of the circuit breaker.

The low-voltage instrument door has indicator lights and a circuit breaker control switch. The low-voltage instrument door can be customized to include auxiliary components when specified by the customer. Refer to auxiliary component manufacturer’s instruction materials for proper operation of devices not included in this manual.

Figure 8: Low-voltage instrument door (optional).

Red (closed) and green (open) indicator lights (see Figure 8) located on the low-voltage instrument door indicate the status of the circuit breaker.

The circuit breaker control switch (see Figure 8) allows local operation of the circuit breaker without direct exposure to the low-voltage compartment.

Low-Voltage Instrument Door (Optional)

Indicator lights

Circuit breaker control switch

6065

3022

Indicator Lights

Circuit Breaker Control Switch

DESCRIPTION

Page 20: S&C Type FVR Vacuum Substation Circuit BreakerC Type FVR Vacuum Substation Circuit Breaker 15 kV to 38 kV, ... Air Flow Switches ... • Control Diagram Number • Closing Time

767-500 20

The closing springs—located on the left side of the mechanism—can be charged manually by moving the charging handle up and down or electrically with control power. The closing springs are fully charged when the CHARGED/DISCHARGED indicator reads CHARGED and the charging handle can no longer be raised.

When control power is applied to the circuit breaker, the spring charging motor will be energized automatically. As the motor gears (see Figure 9) turn, the drive shaft rotates, compressing the closing springs until the spring loads pass top-dead center. At this point, the closing roller engages the closing cam. The drive shaft can rotate no further and the motor limit switch de-energizes the spring charging motor. The closing springs are held in this charged position until a closing operation is initiated.

After charging the springs, close the circuit breaker by pressing the CLOSE push button or energizing the closing coil electrically.

The CLOSE push button releases the closing spring latch and allows the closing springs to discharge. The mechanism linkages force the drive bar upward, which, in turn, pushes the crossbar (see Figure 4 on page 13) upward. The crossbar then drives the pushrods inward, closing the vacuum interrupter contacts.

Figure 9: Gear and ratchet detail.

SECTION 5—OPERATION

HAZARD OF ELECTRIC SHOCK, BURN, OR EXPLOSION.

Only qualified personnel familiar with medium-voltage circuits should operate this equipment.

Failure to follow this instruction can result in death or serious injury.

WARNING

Charging the Closing Spring

Closing Operation

Motor gears

Drive shaft

Ratchet assembly

Latch check switch

6065

3011

OPERATION

Page 21: S&C Type FVR Vacuum Substation Circuit BreakerC Type FVR Vacuum Substation Circuit Breaker 15 kV to 38 kV, ... Air Flow Switches ... • Control Diagram Number • Closing Time

21 767-500

The opening springs become charged (or compressed) automatically when the circuit breaker is in the closed position. If the OPEN push button is pressed or the trip coil is energized, the mechanism releases the opening latch and allows the opening springs to discharge. The opening springs pull the crossbar downward, opening the vacuum interrupter contacts.

An opening operation can be initiated manually.

The circuit breaker can be opened (tripped) mechanically either by the external manual trip knob (see Figure 1 on page 10) or the OPEN push button located on the operating mechanism inside the low-voltage compartment (see Figure 5 on page 14). The external manual trip knob allows the circuit breaker to be manually tripped without requiring entry through the low-voltage compartment door.

The circuit breaker can be opened electrically by the breaker control switch located on the low-voltage instrument door (see Figure 8 on page 19).

When a manual trip operation is performed, the manual trip reset switch (69 switch) opens automatically, disabling the closing circuit. The manual trip reset switch, located directly under the operating mechanism (see Figure 5 on page 14), needs to be manually reset before an electrical closing operation can occur. To reset the manual trip reset switch follow the steps below:

1. Turn off all power to the circuit breaker.

2. Reset the manual trip reset switch by moving the toggle switch upwards.

3. Replace all devices, doors, and covers before turning on the power to the equipment.

4. Reapply the power to the circuit breaker.

The fan circuit for 4000 A circuit breakers can be operated either automatically or manually.

With the selector switch (SS) in the AUTO

position, the fans turn on automatically when the primary current exceeds 3600 A. The fans shut off when the primary current drops below 3240 A. To minimize fan wear, operate the fan controls in the automatic mode.

If there is a problem with the automatic controls, the selector switch (SS) may be placed in the “manual” position. This position will connect the control power directly to the fans. The fans operate continuously in the manual mode.

Opening Operation

Manual Opening Operation

Mechanical Operation

Electrical Operation

HAZARD OF ELECTRIC SHOCK, BURN, OR EXPLOSION.

• Turn off all the power supplying this equipment before working on or inside equipment.

• Replace all devices, doors, and covers before turning on the power to this equipment.

Failure to follow these instructions will result in death or serious injury.

DANGERManual Trip Reset Switch

Fan Operation (4000 A circuit breakers only)

Automatic Operation

Manual Operation

OPERATION

Page 22: S&C Type FVR Vacuum Substation Circuit BreakerC Type FVR Vacuum Substation Circuit Breaker 15 kV to 38 kV, ... Air Flow Switches ... • Control Diagram Number • Closing Time

767-500 22

The S&C Type FVR Circuit Breaker is designed for installation on a concrete pad. The pad must be flat, level, and free of debris for proper operation.

The following diagram shows the Type FVR plan view:

Figure 10: Plan view for Type FVR circuit breaker.

SECTION 6—INSTALLATION

Foundation

Dual measurements in.(mm)

44.00 in.* 52.50 in. **(1118 mm* 1335mm**)

3.25 in.* 7.5 in.**(83 mm* 191 mm**)

2 in. (51 mm)

1.62 in.(41 mm)

8 x 14 in. Control conduit entrance. Customer installs cutouts in coverplates as needed.

1.12 x 1.50 Slots. Typically use 7/8 in. UNC bolts for mounting.

Rear

Mechanism side

*110/125 kV BIL**150 kV BIL

3 in. (76 mm)

3 in. (76 mm)

2 in. (51 mm)

5.50 in.(140 mm)

21 in. (533 mm)

5.50 in.(140 mm)

27 in. (686 mm)

38 in.(965 mm)

6065

3010

INSTALLATION

Page 23: S&C Type FVR Vacuum Substation Circuit BreakerC Type FVR Vacuum Substation Circuit Breaker 15 kV to 38 kV, ... Air Flow Switches ... • Control Diagram Number • Closing Time

23 767-500

Lifting eyes (see Figure 1 on page 10) are provided on the roof of the Type FVR circuit breaker for lifting by crane. No spreader bars are required. Handle the equipment with care.

If lifting the circuit breaker by forklift, place the forklift forks underneath the low-voltage compartment (see Figure 1 on page 10) and secure the circuit breaker to the forklift with a strap. The floor of the low-voltage compartment is reinforced to support the weight of the circuit breaker. Do not lift by the side vent housings or any other protrusions. If another handling method is necessary, contact S&C Electric Company to make special preparations.

Connect the circuit breaker ground pads (see Figure 1 on page 10) to the substation grounding grid. Use the ground pad hardware provided.

Lifting the Circuit Breaker

TOP HEAVY LOAD.

If lifting the circuit breaker by forklift, stabilize the circuit breaker with a safety strap to reduce the possibility of tipping.

Failure to follow this instruction can result in death or serious injury.

WARNING

DO NOT LIFT CIRCUIT BREAKER BY SIDE VENT HOUSINGS.

Damaged vent housings can constrict proper air flow and expose interior of high-voltage compartment to weather.

Failure to follow this instruction can result in equipment damage.

CAUTION

Grounding

INSTALLATION

Page 24: S&C Type FVR Vacuum Substation Circuit BreakerC Type FVR Vacuum Substation Circuit Breaker 15 kV to 38 kV, ... Air Flow Switches ... • Control Diagram Number • Closing Time

767-500 24

Before connecting the Type FVR vacuum substation circuit breaker to the primary circuit, prepare it for operation as follows:

1. Check the indicators to verify that the circuit breaker is in the open position with all springs discharged. If it is not in this position, press the OPEN push button, the CLOSE push button, and then the OPEN push button (see Figure 5 on page 14).NOTE: The circuit breaker is normally shipped in the closed position.

2. Examine the entire circuit breaker for damage, dirt, and moisture.3. Use a clean, dry cloth to remove dirt and moisture that may have

collected on the insulating parts.4. Cycle the circuit breaker manually several times, checking for proper

operation. To do so, move the charging handle (see Figure 5 on page 14) up and down until the closing springs are fully charged. A full charge is indicated when the charging handle can no longer be raised and the CHARGED-DISCHARGED indicator reads “charged”. Close the circuit breaker by pressing the CLOSE push button, and then open it by pressing the OPEN push button.

5. Verify that the heater thermostat (see Figure 7 on page 18) is set at 75° F (24° C).

6. Inspect and remove all loose parts, tools, and miscellaneous construction items left inside the circuit breaker before the power is energized.

7. Replace all doors and covers and fasten them securely. For arc-resistant protection all doors must be closed and covers installed.

HAZARD OF ELECTRIC SHOCK, BURN, OR EXPLOSION.

• This equipment must be installed and serviced only by qualified personnel.

• Turn off all the power supplying this equipment before working on or inside equipment.

• Always use a properly rated voltage sensing device to confirm that the power is off.

• Isolate and ground both the line and the load side of the circuit breaker.

• Make sure the breaker is in the OPEN position before inspecting this equipment or connecting the circuit breaker to your system.

• Replace all devices, doors, and covers before turning on the power to this equipment.

Failure to follow these instructions will result in death or serious injury.

DANGERInitial Circuit Breaker Preparation

INSTALLATION

Page 25: S&C Type FVR Vacuum Substation Circuit BreakerC Type FVR Vacuum Substation Circuit Breaker 15 kV to 38 kV, ... Air Flow Switches ... • Control Diagram Number • Closing Time

25 767-500

All Type FVR circuit breakers except those rated at or above 3000 A have an arc-resistant enclosure. For proper operation of this feature, the following is required:

• High-voltage panels installed and mounting bolts tightened.

• Low-voltage doors shut with all door handles latched closed.

• Ensure that the glass polyester vent covers (see Figure 11) are in place with the mounting springs relaxed. The springs offer the required spacing for ventilation and also allow the cover to close the opening should an arc occur.

Figure 11: Vent covers.

• Ensure vent deflectors (see Figure 12) are installed and in good repair. Vent deflectors are part of the high-voltage side sheets. They are used to fold into the vent housing forcing the exhaust through the vent lids (see Figure 13) if an arc occurs. If these parts are removed or broken during shipment, a replacement should be ordered.

Figure 12: Vent deflectors.

• Ensure that vent lids (see Figure 13) are in good repair. Do not caulk around the vent lids. If needed, the lid is designed to open quickly and allow the pressure from an arc to exhaust. If the lid is damaged enough to jeopardize the seal, a replacement should be ordered.

Figure 13: Vent lids.

Arc-Resistance

Vent covers

6055

3013

Vent deflector60

6530

04

Vent lid

6065

9509

INSTALLATION

Page 26: S&C Type FVR Vacuum Substation Circuit BreakerC Type FVR Vacuum Substation Circuit Breaker 15 kV to 38 kV, ... Air Flow Switches ... • Control Diagram Number • Closing Time

767-500 26

The Type FVR circuit breaker is connected to the primary circuit through aerial lugs which are not included unless specified by the customer. Follow the instructions below when attaching the aerial lugs to the circuit breaker bushing studs.

1. Install the aerial lug onto the bushing stud.2. After the aerial lug bottoms out, rotate the lug counter-clockwise to align

the lug pad properly.3. Tighten lug bolts onto the bushing stud alternately and evenly. Torque

¹⁄₂-inch hardware to 55 ft.-lbs. (61 N•m). Torque ³⁄₈-inch hardware to 25 ft.-lbs. (34 N•m).

4. Connect line and load cables to aerial lugs. Torque grade 5, ¹⁄₂-inch hardware to 55 ft.-lbs. (75 N•m). Minimize cable stress. DO NOT OVERTIGHTEN.

Cable Connection

HAZARD OF EQUIPMENT DAMAGE.

BE CAREFUL NOT TO OVERTIGHTEN. It is critical that the aerial lug is not overtightened. Always loosen the aerial lug counter-clockwise to align the lug pad properly.

Failure to follow this instruction can result in equipment damage.

CAUTION

INSTALLATION

Page 27: S&C Type FVR Vacuum Substation Circuit BreakerC Type FVR Vacuum Substation Circuit Breaker 15 kV to 38 kV, ... Air Flow Switches ... • Control Diagram Number • Closing Time

27 767-500

Perform a hi-pot (dielectric) test to verify that circuit breaker is in good working condition.

1. With the circuit breaker in the open position, perform a hi-pot test across the bushings of each pole.

2. With the circuit breaker in the closed position, perform a phase-to-ground and phase-to-phase hi-pot test for each pole.

3. Gradually increase the voltage to the levels indicated in Table 2.

4. Verify that the circuit breaker sustains the specified voltage without flashover for one minute. If it does not, inspect the insulators for leakage paths. If necessary, clean the surface of each insulator and repeat steps 1–3. If test results continue to differ from target values, DO NOT place the equipment into service and contact your S&C Electric Company field sales representative.

5. After each hi-pot test, discharge the bushings and vacuum interrupter mid-band rings to ground.

Table 2: Hi-Pot Test Voltages

Equipment RatingField Test Voltage

Ac Dc

15 kV 38 kV 54 kV

27 kV 45 kV 63 kV

38 kV 60 kV 85 kV

HAZARD OF ELECTRIC SHOCK, BURN, OR EXPLOSION.

When performing the hi-pot (dielectric) test:

• Turn off all power supplying this equipment before working on or inside equipment.

• Do not exceed the voltages specified in Table 2.

• Keep all persons at least 6 ft (1.8 m) away from the circuit breaker being tested.

• Discharge the bushings and vacuum interrupter mid-band rings to ground after each test. These areas can retain a static charge after a hi-pot test.

Failure to follow these instructions will result in death or serious injury.

DANGERPre-Operation Tests

HAZARD OF RADIATION (X-RAY) EXPOSURE.

This device may emit x-rays if voltage higher than rated maximum is applied across the open contacts, or if contacts are spaced less than rated stroke. In such a case, personnel must be protected with appropriate shielding.

Failure to follow this instruction can result in death or serious injury.

WARNING

INSTALLATION

Page 28: S&C Type FVR Vacuum Substation Circuit BreakerC Type FVR Vacuum Substation Circuit Breaker 15 kV to 38 kV, ... Air Flow Switches ... • Control Diagram Number • Closing Time

767-500 28

Because of wide variations in operating uses and environments, a maintenance schedule should be developed for the particular end use. Until a schedule is determined, inspect Type FVR circuit breakers every two years or 2000 operations, whichever occurs first.

Inspect Type FVR Circuit Breakers after several (10 max.) full-rated fault conditions and record any contact erosion (see “Contact Erosion” on page 29).

Visually inspect the entire circuit breaker and operating mechanism for loose parts or connections. Examine the circuit breaker for evidence of overheating or excessive dirt or moisture. If such evidence is found contact your S&C Electric Company field sales representative.

Use a clean, dry cloth to remove all dirt and moisture from the outside of the vacuum interrupters and from all insulating parts.

SECTION 7—MAINTENANCE

HAZARD OF ELECTRIC SHOCK, BURN, OR EXPLOSION.

• This equipment must be installed and serviced only by qualified personnel.

• Turn off all power supplying this equipment before working on or inside.

• Always use a properly rated voltage sensing device to confirm that power is off.

• Replace all devices, doors, and covers before turning on the power to this equipment.

• All maintenance must be performed in accordance with local codes and under the following conditions:

— The circuit breaker must be isolated from all power sources.

— Control voltage must be removed from the controls.

— The circuit breaker must be in the open position.

— All circuit breaker springs must be discharged.

• All instructions in this manual are written with the assumption that the customer has taken these measures before performing maintenance or testing.

• Open the circuit breaker and discharge all springs by pressing the OPEN and CLOSE push buttons in the order OPEN-CLOSE-OPEN.

• Qualified personnel should establish procedures that ensure the safety of personnel and equipment.

Failure to follow these instructions will result in death or serious injury.

DANGER

General Inspection

Insulating Surfaces

MAINTENANCE

Page 29: S&C Type FVR Vacuum Substation Circuit BreakerC Type FVR Vacuum Substation Circuit Breaker 15 kV to 38 kV, ... Air Flow Switches ... • Control Diagram Number • Closing Time

29 767-500

Thoroughly clean or replace the air filters. Air filters (see Figure 14) are located on the floor of the low-voltage compartment, inside the side vent housings, and on the floor of the high-voltage compartment in circuit breakers rated at or above 3000 A. Install air filters correctly for proper air flow.

NOTE: To maintain proper air flow, replace only with identical filter elements.

Figure 14: Air filter locations.

NOTE: This topic is included for information only. Adjustments to a new circuit breaker are not necessary, nor are they required for routine maintenance.

To monitor the condition of the vacuum interrupters, perform the following checks. If interrupter measurements differ from target values, contact S&C Electric Company for corrective procedures.

Contact erosion is the difference between the E-gap currently measured and the initial E-gap factory measurement. When contact erosion exceeds approximately 0.12 in. (.305 mm), the vacuum interrupter needs to be replaced. Contact S&C Electric Company for replacement.

Air Filters

Side vent housing

Floor of high-voltage compartment (only in circuit breakers rated at or above 3000 A)

Floor of low-voltage compartment (inside)

6065

9501

Vacuum Interrupters

Contact Erosion

MAINTENANCE

Page 30: S&C Type FVR Vacuum Substation Circuit BreakerC Type FVR Vacuum Substation Circuit Breaker 15 kV to 38 kV, ... Air Flow Switches ... • Control Diagram Number • Closing Time

767-500 30

To measure E-gap (see Figure 15), place the circuit breaker in the closed position. The nominal E-gap settings for a vacuum interrupter assembly are shown in Table 3. The actual end-of-life E-gap is shown on a label mounted to the floor of the high-voltage compartment.

Table 3: Nominal E-Gap Settings

* End-of-life E-gap settings shown in Table 3 are nominal. For actual end-of-life E-gap measurements refer to label mounted to the floor of the high-voltage compartment.

Perform this measurement with a standard pin gauge (not supplied).

When the measurement reaches the end-of-life dimension, the vacuum interrupter bottle will need to be replaced. Do not reset E-gap. Contact S&C Electric Company for assistance.

Figure 15: Measuring E-gap.

The contact gap dimension is recorded on the label mounted to the floor of the high-voltage compartment and is provided for reference purposes only.

Hi-pot (high potential) tests need to be performed as part of a series of pre-operational tests (see “Pre-Operation Tests” on page 27), regular maintenance, and as a method of determining adequacy against breakdown of insulating materials and spacings under normal conditions. Consistent unacceptable test results may indicate a loss of vacuum. Contact S&C Electric Company for technical assistance.

Equipment Rating Initial E-gap *End-of-Life E-gap

110 kV BIL (≤ 25 kA) 0.21 ± 0.03 in. (5.33 ± 0.76 mm) 0.09 inch (2.29 mm)

125 kV BIL (≤ 25 kA) 0.21 ± 0.03 in. (5.33 ± 0.76 mm) 0.09 inch (2.29 mm)

150 kV BIL (≤ 31.5 kA) 0.20 ± 0.03 in. (5.08 ± 0.76 mm) 0.08 inch (2.03 mm)

110 kV BIL (≤ 40 kA) 0.20 ± 0.03 in. (5.08 ± 0.76 mm) 0.08 inch (2.03 mm)

E-Gap

Molded pushrod

Bias spring

Bias spring washer

Standard pin gauge

Nylock nut

6065

9511

Contact Gap

Hi-Pot (Dielectric) Test

MAINTENANCE

Page 31: S&C Type FVR Vacuum Substation Circuit BreakerC Type FVR Vacuum Substation Circuit Breaker 15 kV to 38 kV, ... Air Flow Switches ... • Control Diagram Number • Closing Time

31 767-500

The resistance measurement from the line side bushing to the load side bushing should not exceed the values shown in Table 4. Readings exceeding these values using a micro-ohmmeter indicates a high resistance. Either a loose connection exists or the vacuum interrupter needs to be replaced. Contact S&C Electric Company for replacement procedure.

Table 4: Resistance Measurement Values

Figure 16: Vacuum interrupter assembly.

NOTE: Some vacuum interrupter assembly equipment shown in Figure 16 may vary on circuit breakers.The location of each lubrication point and the method of lubrication required is shown in Table 5. Under normal conditions, lubricate after two years or 2000 operations, whichever occurs first. More adverse conditions may require more frequent lubrication intervals and different procedures. Variations should be based on the experience of the operating company.

Use a high-grade, heavy-duty lubricant such as Mobil 28® red grease, S&C Electric Company part number 1615-100950, or approved equivalent. Always wipe the area clean before applying lubrication.

For detailed pictures of each lubrication point, see instruction bulletin RD-6565.

Equipment Rating Maximum Resistance Measurement

1200 A150 micro-ohms

2000 A

3000 A 110 micro-ohms

3500, 4000 A 95 micro-ohms

Table 5: Lubrication Chart

Lubrication PointDuring Maintenance Period

Method of Lubrication

Gear teeth

Wipe clean and apply lubricant. Use Mobil® 28 red grease, S&C Electric Company part number 1615-100950, or equivalent.

Spring guides

Contact surfaces on guide cams and trip latch

Charging lever connecting arm

Shock absorber guide slots

Pushrod guide slots

Resistance Measurement

Rear riser

Front riser

Rear bottle support

Vacuum interrupter

Front bottle support

Bottle clamp

Molded pushrod

Bias spring washer

6055

3041

Pivot block

Nylock nut

Lubrication

MAINTENANCE

Page 32: S&C Type FVR Vacuum Substation Circuit BreakerC Type FVR Vacuum Substation Circuit Breaker 15 kV to 38 kV, ... Air Flow Switches ... • Control Diagram Number • Closing Time

767-500 32

Table 6 lists factory-recommended replacement parts. Each replacement part is shipped with complete assembly and adjustment instructions.

When ordering replacement parts:

• Always specify the complete rating information, circuit breaker serial number, and factory order number.

• Specify kit number, description of part, and operating voltage for electrical components.

Table 6: Replacement Parts

NOTE: Standard hardware components are not listed and should be purchased locally. Fasteners must be Grade 5 or better.

DescriptionReplacementKit Number

Rated Voltage

Charging motor and Gear Box Assembly

46011-659-50 48 Vdc

46011-659-51 125 Vdc

46011-659-52 250 Vdc

46011-659-51 120 Vac

46011-659-52 240 Vac

Anti-pump Relay 46011-671-50 48 Vdc

46011-671-51 125 Vdc

46011-671-52 250 Vdc

46011-671-53 120 Vac

46011-671-54 240 Vac

Closing Coil 46011-672-53 48 Vdc

46011-672-51 125 Vdc

46011-672-51 250 Vdc

46011-672-53 120 Vac

46011-672-51 240 Vac

Trip Coil 46011-673-50 24 Vdc

46011-673-54 48 Vdc

46011-673-52 125 Vdc

46011-673-53 250 Vdc

46011-673-54 120 Vac

46011-673-55 240 Vac

Dual Trip Coil 46011-674-50 24 Vdc

46011-674-51 48 Vdc

46011-674-52 125 Vdc

46011-674-53 250 Vdc

46011-674-51 120 Vac

46011-674-55 240 Vac

Undervoltage Trip Coil 46011-684-50 24 Vdc

46011-684-51 48 Vdc

46011-684-52 125 Vdc

46011-684-53 250 Vdc

46011-684-51 120 Vac

46011-684-55 240 Vac

SECTION 8—REPLACEMENT PARTS

Ordering Instructions

REPLACEMENT PARTS

Page 33: S&C Type FVR Vacuum Substation Circuit BreakerC Type FVR Vacuum Substation Circuit Breaker 15 kV to 38 kV, ... Air Flow Switches ... • Control Diagram Number • Closing Time

33 767-500

* Basic mechanism (Order motor and coils separately, if needed.)

NOTE: Standard hardware components are not listed and should be purchased locally. Fasteners must be Grade 5 or better.

Table 6: Replacement Parts (Continued)

DescriptionReplacementKit Number

Rating

Air FiltersHigh-Voltage Compartment 46011-680-50 1200 A/2000 A

Air FiltersLow-Voltage Compartment 46011-681-50 1200 A/2000 A

Air FiltersHigh-Voltage Compartment 46011-680-51 3000/3500/4000 A

Air FiltersLow-Voltage Compartment 46011-681-51 3000/3500/4000 A

Auxiliary Switch 46011-676-50 All Ratings

Latch Check Switch 46011-675-50 All Ratings

Mechanism Cover 46011-679-50 All Ratings

Motor Limit Switch 46011-677-50 All Ratings

Type RI Mechanism* 46011-669-50 All Ratings

Vacuum Interrupter 46011-660-50 110 kV BIL, ≤ 25 kA(1200 A /2000 A)

46011-661-50 110 kV BIL, ≤ 40 kA(1200 A /2000 A)

46011-661-51 110 kV BIL, 40 kA3000/3500/4000 A

46011-662-50 125 kV BIL, ≤ 25 kA(1200 A /2000 A)

46011-663-50 150 kV BIL, ≤ 31.5 kA(1200 A /2000 A)

Bushing 46011-664-50 110/125 kV BIL, 1200 A

46011-664-51 110/125 kV BIL, 2000 A

46011-664-52 110 kV BIL, 3000 A

46011-664-53 110 kV BIL, 40 kA3500/4000 A

46011-664-54 150 kV BIL, 1200 A

46011-664-55 150 kV BIL, 2000 A

Blower Fan 46011-543-50 4000 A

Air Flow Switch 46011-544-50 4000 A

REPLACEMENT PARTS

Page 34: S&C Type FVR Vacuum Substation Circuit BreakerC Type FVR Vacuum Substation Circuit Breaker 15 kV to 38 kV, ... Air Flow Switches ... • Control Diagram Number • Closing Time

767-500 34

SECTION 9—MAINTENANCE LOG

DATE INITIALS ACTIONS

MAINTENANCE LOG

Page 35: S&C Type FVR Vacuum Substation Circuit BreakerC Type FVR Vacuum Substation Circuit Breaker 15 kV to 38 kV, ... Air Flow Switches ... • Control Diagram Number • Closing Time

35 767-500

MAINTENANCE LOG (CONTINUED)

DATE INITIALS ACTIONS

MAINTENANCE LOG

Page 36: S&C Type FVR Vacuum Substation Circuit BreakerC Type FVR Vacuum Substation Circuit Breaker 15 kV to 38 kV, ... Air Flow Switches ... • Control Diagram Number • Closing Time

767-500 36

MAINTENANCE LOG (CONTINUED)

DATE INITIALS ACTIONS

MAINTENANCE LOG

Prin