second revision no. 25-nfpa 79-2013 [ section no. …...second revision no. 25-nfpa 79-2013 [...

74
8/27/13 TerraView™ submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 1/64 Second Revision No. 25-NFPA 79-2013 [ Section No. 1.1.1 ] 1.1.1 The provisions of this standard shall apply to the electrical/electronic equipment, apparatus, or systems of industrial machines operating from a nominal voltage of 600 volts or less, and commencing at the point of connection of the supply circuit conductors to the electrical equipment of the machine. Submitter Information Verification Submitter Full Name: [ Not Specified ] Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Wed Jul 10 10:28:54 EDT 2013 Committee Statement Committee Statement: The TC understands document scopes are the jurisdiction of the NEC CC and offers a revision of the paragraph in the interest of clarifying the scope of NFPA 79. Revising the paragraph as offered will align the text of this section with existing requirements in the Standard such as the main disconnecting means requirements in Chapter 5 and with the new text relative to working spaces in 11.5. Using common terminology will assist readers of NFPA 79 with understanding where the Standard starts. Response Message:

Upload: others

Post on 18-Apr-2020

14 views

Category:

Documents


1 download

TRANSCRIPT

8/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 1/64

Second Revision No. 25-NFPA 79-2013 [ Section No. 1.1.1 ]

1.1.1

The provisions of this standard shall apply to the electrical/electronic equipment,apparatus, or systems of industrial machines operating from a nominal voltage of 600volts or less, and commencing at the point of connection of the supply circuit conductorsto the electrical equipment of the machine.

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jul 10 10:28:54 EDT 2013

Committee Statement

CommitteeStatement:

The TC understands document scopes are the jurisdiction of the NEC CC and offersa revision of the paragraph in the interest of clarifying the scope of NFPA 79.Revising the paragraph as offered will align the text of this section with existingrequirements in the Standard such as the main disconnecting means requirementsin Chapter 5 and with the new text relative to working spaces in 11.5. Using commonterminology will assist readers of NFPA 79 with understanding where the Standardstarts.

ResponseMessage:

8/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 2/64

Second Revision No. 57-NFPA 79-2013 [ Section No. 2.4 ]

2.4 References for Extracts in Mandatory Sections.

NFPA 70®, National Electrical Code®, 2011 2014 edition.

NFPA 70E®, Standard for Electrical Safety in the Workplace®, 2012 2015 edition.

Submitter Information Verification

Submitter Full Name:Jenny Depew

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Mon Aug 26 11:29:56 EDT 2013

Committee Statement

Committee Statement: Update the revision dates of NFPA referenced documents

Response Message:

8/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 3/64

Second Revision No. 47-NFPA 79-2013 [ Section No. 3.3.5 ]

3.3.5* Adjustable Speed Drive.

A combination of the power converter, motor, and motor mounted auxiliary devices suchas encoders, tachometers, thermal switches and detectors, air blowers, heaters, andvibration sensors. [ 70: 430.2]

Submitter Information Verification

Submitter Full Name:Mark Cloutier

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Aug 12 11:59:11 EDT 2013

Committee Statement

CommitteeStatement:

Citation was deleted to reflect the removal of the definition from NEC2014

Response Message:

8/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 4/64

Second Revision No. 42-NFPA 79-2013 [ Section No. 3.3.16 ]

3.3.16* Cable Trunking System.

A system of enclosures comprised of a base and a removable cover intended for thecomplete surrounding of insulated conductors, cables, and cords.

Submitter Information Verification

Submitter Full Name:Mark Cloutier

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jul 24 11:50:43 EDT 2013

Committee Statement

CommitteeStatement:

Delete the term "Cable Trunking" from the definitions and move to AnnexJ.

Response Message:

8/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 5/64

Second Revision No. 48-NFPA 79-2013 [ Section No. 3.3.20.4 ]

3.3.19.4* Liquidtight Flexible Nonmetallic Conduit (LFNC).

A raceway of circular cross section of various types as follows: (1) A smooth seamlessinner core and cover bonded together and having one or more reinforcement layersbetween the core and covers, designated as Type LFNC-A; (2) A smooth inner surfacewith integral reinforcement within the conduit raceway wall, designated as Type LFNC-B;(3) A corrugated internal and external surface without integral reinforcement within theconduit wall, designated as LFNC-C. LFNC is flame resistant and with fittings and isapproved for the installation of electrical conductors. [70:356.2]

Submitter Information Verification

Submitter Full Name:Mark Cloutier

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Aug 12 12:02:31 EDT 2013

Committee Statement

CommitteeStatement:

Conduit was changed to raceway and the last sentence was removed tomatch the definition in NEC 2014.

ResponseMessage:

8/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 6/64

Second Revision No. 49-NFPA 79-2013 [ Section No. 3.3.29 ]

3.3.28 Device.

A unit of an electrical system, other than a conductor, that carries or controls electricenergy as its principal function. [70:100]

Submitter Information Verification

Submitter Full Name:Mark Cloutier

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Aug 12 12:26:13 EDT 2013

Committee Statement

Committee Statement: Changed definition to match NEC 2014.

Response Message:

8/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 7/64

Second Revision No. 44-NFPA 79-2013 [ Section No. 3.3.33 ]

3.3.33* Duct.

An enclosed channel designed expressly for holding and protecting electricalconductors, cables, and busbars.

Submitter Information Verification

Submitter Full Name:Mark Cloutier

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jul 24 12:44:39 EDT 2013

Committee Statement

CommitteeStatement:

Delete the term "Duct" because it is no longer used in the standard. Relocate theterm to Annex J to help users understand the "Cross Reference" between theNEC/79 terms and IEC/EN terms.

ResponseMessage:

8/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 8/64

Second Revision No. 50-NFPA 79-2013 [ Section No. 3.3.42 ]

3.3.40 Exposed (as applied to live parts).

Capable of being inadvertently touched or approached nearer than a safe distance by aperson. It is applied to parts not suitably guarded, isolated, or insulated. [ 70: 100]

Submitter Information Verification

Submitter Full Name:Mark Cloutier

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Aug 12 12:43:49 EDT 2013

Committee Statement

CommitteeStatement:

The following sentence is now an informational note in 2014 edition of NFPA 70: "Itis applied to parts not suitably guarded, isolated, or insulated." This is a majorchange and NFPA 79 does not contain informational notes. The 79 TC will have tomake this change in the next edition. The citation to NEC was removed because thedefinitions do not match.

ResponseMessage:

8/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 9/64

Second Revision No. 51-NFPA 79-2013 [ Section No. 3.3.50 ]

3.3.48 Grounding Conductor, Equipment. (EGC)

The conductive path(s) installed to connect that provides a ground-fault current path andconnects normally non–current-carrying metalparts of equipment together and to thesystem grounded conductor or to the grounding electrode conductor, or both. [70:100]

Submitter Information Verification

Submitter Full Name:Mark Cloutier

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Aug 12 13:14:44 EDT 2013

Committee Statement

Committee Statement: The definition was changed to match the NEC 2014.

Response Message:

8/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 10/64

Second Revision No. 5-NFPA 79-2013 [ Section No. 3.3.55 ]

3.3.53 Industrial Control Panel.

An assembly of two or more components consisting of one of the following: (1) powercircuit components only, such as motor controllers, overload relays, fused disconnectswitches, and circuit breakers; or (2) control circuit components only, such aspushbuttons, pilot lights, selector switches, timers, switches, and control relays; or (3)a combination of power and control circuit components. These components, withassociated wiring and terminals, are mounted on, or contained within, an enclosure ormounted on a subpanel. The industrial control panel does not include the controlledequipment. [ 70: 409]

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 08 15:25:00 EDT 2013

Committee Statement

CommitteeStatement:

The bracketed reference was added to reflect that the definition is extracted fromthe NEC. This is part of the effort to standardize definitions throughout the NFPAsystem by the Glossary Of Terms (GOT) committee. SR was edited to reflect theNEC 2014 definition.

ResponseMessage:

Public Comment No. 8-NFPA 79-2013 [Section No. 3.3.55]

8/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 11/64

Second Revision No. 52-NFPA 79-2013 [ Section No. 3.3.56 ]

3.3.54 Industrial Machinery (Machine).

A power-driven machine (or a group of machines working together in a coordinatedmanner), not portable by hand while working, that is used to process material by cutting;forming; pressure; electrical, thermal, or optical techniques; lamination; or a combinationof these processes. Machine It can include associated equipment used to transfermaterial or tooling, including fixtures, to assemble/disassemble, to inspect or test, or topackage. [The associated electrical equipment, including the logic controller(s) andassociated software or logic together with the machine actuators and sensors, areconsidered as part of the industrial machine.] [70:670.2]

Submitter Information Verification

Submitter Full Name:Mark Cloutier

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Aug 12 14:19:13 EDT 2013

Committee Statement

CommitteeStatement:

In 2014 edition, 2nd sentence begins ‘It can include,’ not ‘Machine can include’Changed to match since it is an extracted definition

ResponseMessage:

8/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 12/64

Second Revision No. 53-NFPA 79-2013 [ Section No. 3.3.61 ]

3.3.59 In Sight From (Within Sight From, Within Sight).

Where this standard specifies that one equipment shall be “in sight from,” “within sightfrom,” or “within sight of ,” and so forth, of another equipment, the specified equipment isto be visible and not more than 15 m (50 ft) distant from the other. [70:100]

Submitter Information Verification

Submitter Full Name:Mark Cloutier

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Aug 12 14:24:11 EDT 2013

Committee Statement

CommitteeStatement:

In NEC 2014 edition, 1st sentence, ‘within sight’ is ‘within sight of’. Changed tomatch since it is an extracted definition.

ResponseMessage:

8/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 13/64

Second Revision No. 6-NFPA 79-2013 [ Section No. 3.3.72 ]

3.3.70 Overcurrent Protective Device, Branch-Circuit.

A device capable of providing protection for service, feeder, and branch circuits andequipment over the full range of overcurrents between its rated current and its interruptingrating. Branch-circuit overcurrent protective Such devices are provided with interruptingratings appropriate for the intended use but no less than 5000 amperes. [ 70: 100]

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 08 15:43:55 EDT 2013

Committee Statement

CommitteeStatement:

The proposed change puts the definition in line with the proposed action by NECCMP 10 for the 2014 edition of the NEC. This is in section 100 of the NEC. Thecomment is in line with creating consistency in NFPA definitions, as isrecommended by NFPA Standards Council for the GOT committee, FR-15, PI 115,this definition is extracted from the 2014 NEC, and was accepted at the ROC stage.

ResponseMessage:

Public Comment No. 9-NFPA 79-2013 [Section No. 3.3.72]

8/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 14/64

Second Revision No. 54-NFPA 79-2013 [ Section No. 3.3.92 ]

3.3.90* Short-Circuit Current Rating (SCCR) .

The prospective symmetrical fault current at a nominal voltage to which an apparatus orsystem is able to be connected without sustaining damage exceeding definedacceptance criteria. [70:100]

Submitter Information Verification

Submitter Full Name:Mark Cloutier

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Aug 12 14:29:07 EDT 2013

Committee Statement

CommitteeStatement:

‘(SCCR)’ does not appear in the 2014 edition of NFPA 70. Changed to matchNEC 2014 because it is an extracted definition.

ResponseMessage:

8/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 15/64

Second Revision No. 55-NFPA 79-2013 [ Section No. 3.3.101 ]

3.3.99 System Isolation Equipment.

A redundantly monitored, remotely operated contactor-isolation contactor-isolatingsystem, packaged to provide the disconnecting/isolation function, capable of verifiableoperation from multiple remote locations by means of lockout switches, each having thecapability of being padlocked in the OFF off (open) position. [70:430.2]

Submitter Information Verification

Submitter Full Name:Mark Cloutier

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Aug 12 14:31:26 EDT 2013

Committee Statement

CommitteeStatement:

‘contactor-isolation’ is ‘contactor-isolating’ in the NEC 2014 edition. ‘OFF’ is “off” in2014 edition. Change to match because it is an extracted definition.

ResponseMessage:

8/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 16/64

Second Revision No. 7-NFPA 79-2013 [ Section No. 5.3.1.1 ]

5.3.1.1

Global SR-7 Hide Deleted

A supply circuit disconnecting means shall be provided for the following:

(1) Each incoming supply circuit to a machine

(2) The supply circuit to a feeder system using collector wires, collector bars, slip-ringassemblies, or flexible cable systems (reeled, festooned) to a machine or a numberof machines

(3) Each on-board power source (e.g., generators, uninterruptible power supplies)

Exception: Communication, remote control, and signaling circuits of less than 50 voltsshall not be required to be provided with a supply circuit disconnecting means.

5.3.1.1.1*

Each disconnecting means required by 5.3.1.1 shall be legibly marked to indicate theequipment it disconnects.

5.3.1.1.2

Where a machine is supplied by more than one supply circuit, a marking shall beinstalled at each supply circuit disconnect location denoting the location of all othersupply circuit disconnects.

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 09 08:35:29 EDT 2013

Committee Statement

CommitteeStatement:

It is not necessary or practical to include a disconnecting means for limited energycircuits. This comment is submitted based on the committee statement on PI 81.See Article 725 and 800 in the NEC for an explanation of remote control andcommunication circuits respectively.

ResponseMessage:

Public Comment No. 43-NFPA 79-2013 [Section No. 5.3.1.1]

8/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 17/64

Second Revision No. 8-NFPA 79-2013 [ Section No. 5.3.1.3 ]

5.3.1.3

The Each supply circuit disconnecting means other than attachment plugs andreceptacles shall be mounted within the control enclosure or immediately adjacentthereto.

Exception No. 1: Externally mounted supply circuit disconnecting means, whetherinterlocked or not interlocked with the control enclosure, supplying machines totaling 2hp or less shall be permitted to be mounted up to 6 m (20 ft) away from the enclosure,providing that provided the disconnecting means is in sight from and readily accessibleto the operator.

Exception No. 2: A supply circuit disconnecting means mounted in a separateenclosure and interlocked in accordance with 6.2.4 6.2.3 with the control enclosure(s)it supplies shall be permitted to be mounted up to 6 m (20 ft) away, providingthat provided the disconnecting means is in sight from the control enclosure(s) andreadily accessible to the operator. The control enclosure(s) shall be marked indicatingthe location of the disconnecting means. The disconnecting means shall be markedindicating the industrial machine it supplies.

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 09 09:11:24 EDT 2013

Committee Statement

CommitteeStatement:

The exception was added at the first draft meeting prior to the relocation of theinterlocking requirements from 6.2.3 to 6.2.4. The proposed change coordinates thataction with the new exception. The committee changed the word "the" to "each" toclarify it would apply to each supply circuit disconnecting means.

ResponseMessage:

Public Comment No. 11-NFPA 79-2013 [Section No. 5.3.1.3]

Public Comment No. 24-NFPA 79-2013 [Sections 5.3.1.3, 5.3.1.4]

8/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 18/64

Second Revision No. 9-NFPA 79-2013 [ Section No. 5.3.1.4 ]

5.3.1.4

Each supply circuit disconnecting means mounted within or adjacent to the controlenclosure shall be interlocked with the control enclosure in accordance with 6.2.4.Where the supply circuit disconnecting means is not adjacent to the control enclosure,or where the supply disconnecting means is an attachment plug and receptacle, thecontrol enclosure shall comply with 6.2.5 and a safety sign shall be provided inaccordance with Section 16.2 .

Exception: Where a supply circuit disconnecting means, supplying machines totaling 2hp or less is not located within or adjacent to the control enclosure it supplies, thecontrol enclosure shall comply with 6.2.4 or 6.2.5 . Where a supply disconnectingmeans is an attachment plug and receptacle, the control enclosure it supplies shallcomply with 6.2.5 . Where 6.2.5 is used, a safety sign shall be provided inaccordance with 16.2 .

Supplemental Information

File Name Description

SR-9_new_5.3.1.4.1373379951893.docx

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 09 09:18:15 EDT 2013

Committee Statement

CommitteeStatement:

The additional language in the exception to 5.3.1.4 clarifies the intent of 5.3.1.3 thatonly separately mounted disconnects for small machines totaling 2 hp or less arenot required to be interlocked with the control enclosures in accordance with 6.2.4.The second sentence was changed to an exception to clarify where interlocking ispermitted.

ResponseMessage:

8/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 19/64

Second Revision No. 36-NFPA 79-2013 [ Section No. 5.3.3.2 ]

5.3.3.2*

When the supply circuit disconnecting device is an attachment plug and receptacle(plug/socket combination), it shall fulfill all of the following requirements:

(1) Have a load-break rating or be interlocked with a switching device that is load-breakrated, and complies with 5.3.3.1(6). Attachment An attachment plug andreceptacle (plug/socket combination) rated greater than 20 A amperes or 2 hp shallbe listed as a switch-rated plug and receptacle (plug/socket combination).

(2) Be of such a type and be so installed as to prevent unintended contact with liveparts at any time, even during insertion or removal of the connectors.

(3) Have a first-make, last-break electrical grounding (protective) (earthing) contact.

(4) Have a retaining means to prevent unintended or accidental disconnection whererated at more than 20 A amperes.

(5) Be located within sight from the operator station and be readily accessible.

Submitter Information Verification

Submitter Full Name:Mark Cloutier

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jul 24 11:27:13 EDT 2013

Committee Statement

CommitteeStatement:

During the first Revision only parenthetical (protective bonding) and other (grounding)terms were deleted– missed parenthetical terms (Earth/Earthing) and (Protective).The TC agrees that (Earth/Earthing) and (Protective) parenthetical terms be removedfor clarity.

ResponseMessage:

8/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 20/64

Second Revision No. 10-NFPA 79-2013 [ Section No. 6.2.4.2 ]

6.2.4.2

The interlocking means shall meet the following requirements:

(1) Utilize a device or tool as specified by the manufacturer of the interlock to allowqualified persons to defeat the interlock

(2) Be reactivated automatically when the door(s) is closed

(3) Prevent closing of the disconnecting means while the enclosure door door of theenclosure containing the disconnect is open, unless an interlock is operated bydeliberate action

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 09 11:09:34 EDT 2013

Committee Statement

CommitteeStatement:

With the new permission to allow separately mounted disconnects for machinery in5.3.1.3 (FR45), the proposed change clarifies that this portion of the interlockrequirements is mandated only for the enclosure containing the disconnect itself.

ResponseMessage:

Public Comment No. 25-NFPA 79-2013 [Section No. 6.2.4.2]

8/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 21/64

Second Revision No. 56-NFPA 79-2013 [ Section No. 6.5.3.2 ]

6.5.3.2 Means of Discharge.

The discharge circuit shall be either permanently connected to the terminals of thecapacitor or capacitor bank, or provided with automatic means of connecting it to theterminals of the capacitor bank up on removal of voltage from the line. Manual means ofswitching or connecting the discharge circuit shall not be used. [70:460.6(B)]

Submitter Information Verification

Submitter Full Name:Mark Cloutier

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Aug 12 14:38:48 EDT 2013

Committee Statement

CommitteeStatement:

‘upon’ is ‘on’ in the NEC 2014 edition. Changed to match because it is aextracted definition.

ResponseMessage:

8/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 22/64

Second Revision No. 41-NFPA 79-2013 [ Section No. 7.2.5 ]

7.2.5 Receptacle (Socket) Outlets and Their Associated Conductors for AccessoryCircuits.

7.2.5.1

Overcurrent protection shall be provided for the circuits feeding general purposereceptacle (socket) outlets intended primarily for supplying power to maintenanceequipment.

7.2.5.2

Overcurrent protective devices shall be provided in the ungrounded phase conductors ofeach circuit feeding receptacle (socket) outlets. Overcurrent protection for thesereceptacle (socket) outlets shall not exceed 15 amperes.

Submitter Information Verification

Submitter Full Name:Mark Cloutier

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jul 24 11:46:33 EDT 2013

Committee Statement

CommitteeStatement:

During the first Revision only parenthetical (protective bonding) and other (grounding)terms were deleted– missed parenthetical term (Socket). The TC agrees that(Socket) parenthetical term be removed for clarity.

ResponseMessage:

Second Revision No. 31-NFPA 79-2013 [ Section No. 7.2.10.1 [Excluding

any Sub-Sections] ]

Each motor controller and its associated wiring shall be protected as an individual branchcircuit by a short-circuit protective device (SCPD) as specified by the controllermanufacturer. The maximum rating of the designated SCPD shall be as shown in Table7.2.10.1.

Table 7.2.10.1 Maximum Rating or Setting of Fuse and Circuit Breakers: Motor, MotorBranch Circuit, and Motor Controller

Full-Load Current (%)

8/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 23/64

Fuse Class with Non–Time Delay Full-Load Current (%)

AC-2 AC-3 AC-4

R 300 300 300

CF or J 300 300 300

CC 300 300 300

T 300 300 300

Type2 of Application2

Fuse Class with Time Delay1 AC-2 AC-3 AC-4

RK-53 150 175 175

RK-1 150 175 175

CF or J 150 175 225

CC 150 300 300

Instantaneous trip circuit breaker4 800 800 800

Inverse trip circuit breaker5 150 250 250

Note: Where the values determined by Table 7.2.10.1 this table do not correspond to thestandard sizes or ratings, the next higher standard size, rating, or possible setting shallbe permitted.

1 Where the rating of a time-delay fuse (other than CC type) specified by the table is notsufficient for the starting of the motor, it shall be permitted to be increased but shall in nocase be permitted to exceed 225 percent. The rating of a time-delay Class CC fuse andnon–time-delay Class CC, J, CF, or T fuse shall be permitted to be increased but shall inno case exceed 400 percent of the full-load current.

2 Types of starting duty are as follows:

 (a) AC-2: All light-starting duty motors, including slip-ring motors; starting, switching off.

 (b) AC-3: All medium starting duty motors including squirrel-cage motors; starting,switching off while running, occasional inching, jogging, or plugging but not to exceed 5operations per minute or 10 operations per 10 minutes and all wye-delta and two-stepautotransformer starting motors.

 (c) AC-4: All heavy starting duty motors including squirrel-cage motors; starting,plugging, inching, jogging.

3Unless a motor controller is listed for use with RK-5 fuses, Class RK-5 fuses shall beused only with NEMA-rated motor controllers.

4Instantaneous trip circuit breakers shall be permitted to be used only if they comply withall of the following:

 (a) They are adjustable.

 (b) Part of a combination controller has motor-running protection and also short-circuitand ground-fault protection in each conductor.

 (c) The combination is especially identified for use.

 (d) It is installed per any instructions included in its listing or labeling.

 (e) They are limited to single motor applications, circuit breakers with adjustable tripsettings shall be set at the controller manufacturer's recommendation, but not greater

8/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 24/64

than 1300 percent of the motor full-load current.

5Where the rating of an inverse time circuit breaker specified in Table 7.2.10.1 this tableis not sufficient for the starting current of the motor, it shall be permitted to be increasedbut in no case exceed 400 percent for full-load currents of 100 amperes or less or 300percent for full-load currents greater than 100 amperes.

Exception: Table 7.2.10.1 shall not apply to Design B energy efficient motor circuits.The provisions of NFPA 70, shall be observed for Design B energy efficient motorcircuits.

Supplemental Information

File Name Description

Table_7.2.10.1_with_legislative_changes.docx

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jul 10 12:52:04 EDT 2013

Committee Statement

CommitteeStatement:

This revision adds Class CF fuses to the permitted fuse types listed since Class CFfuses have the same performance requirements as Class J fuses. The table withchanges shown in legislative text is attached.

ResponseMessage:

Each motor controller and its associated wiring shall be protected as an individual branch circuit by a short-circuit protective device (SCPD) as specified by the controller manufacturer. The maximum rating of the designated SCPD shall be as shown in Table 7.2.10.1. Table 7.2.10.1 Maximum Rating or Setting of Fuse and Circuit Breakers: Motor, Motor Branch Circuit, and Motor Controller

Fuse Class with Non–Time Delay Full-Load Current (%) AC-2 AC-3 AC-4

R 300 300 300 CF or J 300 300 300

CC 300 300 300 T 300 300 300

Type2 of Application2 Fuse Class with Time Delay1 AC-2 AC-3 AC-4

RK-53 150 175 175 RK-1 150 175 175

CF or J 150 175 225 CC 150 300 300

Instantaneous trip circuit breaker4 800 800 800 Inverse trip circuit breaker5 150 250 250 Note: Where the values determined by Table 7.2.10.1 do not correspond to the standard sizes or ratings, the next higher standard size, rating, or possible setting shall be permitted. 1 Where the rating of a time-delay fuse (other than CC type) specified by the table is not sufficient for the starting of the motor, it shall be permitted to be increased but shall in no case be permitted to exceed 225 percent. The rating of a time-delay Class CC fuse and non–time-delay Class CC, J, CF or T fuse shall be permitted to be increased but shall in no case exceed 400 percent of the full-load current. 2 Types of starting duty are as follows: ?(a) AC-2: All light-starting duty motors, including slip-ring motors; starting, switching off. ?(b) AC-3: All medium starting duty motors, including squirrel-cage motors; starting, switching off while running, occasional inching, jogging, or plugging but not to exceed 5 operations per minute or 10 operations per 10 minutes, and all wye-delta and two-step autotransformer starting motors. ?(c) AC-4: All heavy starting duty motors including squirrel-cage motors; starting, plugging, inching, jogging. 3Unless a motor controller is listed for use with RK-5 fuses, Class RK-5 fuses shall be used only with NEMA-rated motor controllers. 4Instantaneous trip circuit breakers shall be permitted to be used only if they comply with all of the following: ?(a) They are adjustable. ?(b) Part of a combination controller has motor-running protection and also short-circuit and ground-fault protection in each conductor. ?(c) The combination is especially identified for use. ?(d) It is installed per any instructions included in its listing or labeling.

jdepew
Sticky Note
Attachment for SR 31

?(e) They are limited to single motor applications, circuit breakers with adjustable trip settings shall be set at the controller manufacturer's recommendation, but not greater than 1300 percent of the motor full-load current. 5Where the rating of an inverse time circuit breaker specified in Table 7.2.10.1 is not sufficient for the starting current of the motor, it shall be permitted to be increased but in no case exceed 400 percent for full-load currents of 100 amperes or less or 300 percent for full-load currents greater than 100 amperes. Exception: Table 7.2.10.1 shall not apply to Design B energy efficient motor circuits. The provisions of NFPA 70, shall be observed for Design B energy efficient motor circuits

8/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 25/64

Second Revision No. 2-NFPA 79-2013 [ Section No. 7.2.10.3 ]

7.2.10.3

Where the branch-circuit short-circuit and ground-fault protective device is selected not toexceed that allowed by 7.2.10.1 for the smallest rated motor, two or more motors or oneor more motors and other load(s), with each motor having individual overload protection,shall be permitted to be connected to a branch circuit where it can be determined thatthe branch-circuit short-circuit and ground-fault protective device will not open undersevere normal conditions of service that might be encountered. The short-circuit andground-fault protection is shall be provided by a single inverse time circuit breaker orsingle set of fuses.

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 08 14:10:11 EDT 2013

Committee Statement

CommitteeStatement:

Replacing "is" with "shall be" aligns with the manual of style for normativetext.

Response Message:

Public Comment No. 27-NFPA 79-2013 [Section No. 7.2.10.3]

8/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 26/64

Second Revision No. 11-NFPA 79-2013 [ Section No. 7.8.3 ]

7.8.3 Equipment Protection.

Where provided, SPDs shall be connected across the terminals of all equipmentrequiring such protection.

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 09 11:21:20 EDT 2013

Committee Statement

CommitteeStatement:

Surge Protection Devices are installed by choice and the designer or installershould be permitted to decide where to connect them in accordance with themanufacturers instructions.

ResponseMessage:

Public Comment No. 47-NFPA 79-2013 [Section No. 7.8.3]

8/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 27/64

Second Revision No. 28-NFPA 79-2013 [ Section No. 8.2.2.1 ]

8.2.2.1

Conductors used for grounding and bonding purposes shall be copper. Stipulations onstranding and flexing as outlined in Chapter 12 shall apply.

Exception: Machine members or structural parts of the electrical equipment shall bepermitted to be used in the equipment grounding circuit provided that the cross-sectional area of these parts provide the same or better conductivity as the minimumcross-sectional area of the copper conductor required. The cross sectional area shallbe in accordance with one or more of the following:

Steel — 10 times that of copper

Iron — 6 times that of copper

Aluminum — 2 times that of copper

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jul 10 11:37:11 EDT 2013

Committee Statement

CommitteeStatement:

The machine members and structural parts are not suitable for use as anequipment grounding conductor in all cases or over the life of the equipment.

ResponseMessage:

8/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 28/64

Second Revision No. 37-NFPA 79-2013 [ Section No. 8.3.2 ]

8.3.2

Ungrounded control circuits shall be provided with an insulation-monitoring device thateither indicates a ground (earth) fault or interrupts the circuit automatically after a ground(earth) fault.

Exception: Class 2 low-voltage circuits in Article 725 of NFPA 70, shall not requireinsulation monitoring.

Submitter Information Verification

Submitter Full Name:Mark Cloutier

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jul 24 11:33:14 EDT 2013

Committee Statement

CommitteeStatement:

During the first Revision only parenthetical (protective bonding) and other (grounding)terms were deleted– missed parenthetical terms (Earth/Earthing) and (Protective).The TC agrees that (Earth/Earthing) and (Protective) parenthetical terms be removedfor clarity.

ResponseMessage:

8/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 29/64

Second Revision No. 38-NFPA 79-2013 [ Section No. 9.4.2 ]

9.4.2 Protection Against Unintended Operation Due to Ground (Earth) Faults andVoltage Interruptions.

9.4.2.1 Ground (Earth) Faults.

Ground (earth) faults on any control circuit shall not cause unintentional starting orpotentially hazardous motions, or prevent stopping of the machine. Grounded controlcircuits shall be in accordance with Section 8.2 and Section 8.3. Ungrounded controlcircuits shall be provided with an insulation monitoring device that either indicates aground (earth) fault or interrupts the circuit automatically after a ground (earth) fault. Arestart of the machine with a detected ground (earth) fault shall be prevented.

9.4.2.2 Voltage Interruptions.

9.4.2.2.1

The requirements detailed in Section 7.5 shall apply.

9.4.2.2.2

Where a memory is used, its functioning in the event of power failure shall be ensured(e.g., by using a nonvolatile memory) where such loss of memory results in a hazardouscondition.

Submitter Information Verification

Submitter Full Name:Mark Cloutier

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jul 24 11:38:53 EDT 2013

Committee Statement

CommitteeStatement:

During the first Revision only parenthetical (protective bonding) and other (grounding)terms were deleted– missed parenthetical terms (Earth/Earthing) and (Protective).The TC agrees that (Earth/Earthing) and (Protective) parenthetical terms be removedfor clarity.

ResponseMessage:

8/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 30/64

Second Revision No. 14-NFPA 79-2013 [ Section No. 11.3.2 ]

11.3.2

Enclosures of control equipment shall provide the degree of protection required for theenvironment. A minimum degree of protection of at least NEMA Type 1 is required.

Exception: Where removable collectors on collector wire or collector bar systems areused and NEMA Type 1 enclosures are not practicable, suitable protection shall beprovided (e.g., elevation, guarding).

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 09 14:34:12 EDT 2013

Committee Statement

CommitteeStatement:

The term "Type" is what is commonly used to refer to the degree ofprotection for enclosures.

ResponseMessage:

Public Comment No. 42-NFPA 79-2013 [Section No. 11.3.2]

8/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 31/64

Second Revision No. 22-NFPA 79-2013 [ Section No. 11.5 [Excluding

any Sub-Sections] ]

Access and working space for control cabinets and compartments operating at 600 volts,nominal, or less to ground and likely to require examination, adjustment, servicing, ormaintenance while energized shall comply with the provisions of Chapter 11. Sufficientaccess and working space shall be provided and maintained around all control cabinetsand compartments to permit ready and safe operation and maintenance of such controlcabinets and compartments. Working space for cabinets and compartments that containsupply conductors to industrial machinery that are covered by Article 670 of NFPA 70shall be in accordance with the NEC .

Supplemental Information

File Name Description

79_Figure_11-5_draft7_.1373463184710.docx Annex A.11.5 figure

Add_new_figure_A_11.5_figure_text.1375103558926.docx

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jul 10 08:56:18 EDT 2013

Committee Statement

CommitteeStatement:

This change correlates the NFPA 79 requirements with the Informational Note to670.1 in the NEC. The terms cabinets and compartments are used to be consistentwith the terminology within the document. An (*) was added to point to the newlyadded annex A material. Annex A.11.5 Figure and text are attached This addressesthe directive of the CC note 1 to reconsider the actions on PI 94.

ResponseMessage:

Public Comment No. 12-NFPA 79-2013 [Section No. 11.5 [Excluding any Sub-Sections]]

Public Comment No. 49-NFPA 79-2013 [Section No. 11.5 [Excluding any Sub-Sections]]

FIGURE A.11.5 Clarification of Working Space Requirements at the Termination Location of Incoming Supply Conductors

Termination of Supply Conductors Integral to the Industrial Machine

Control Panel or Compartment (5.3.1.3 Disconnecting Means)

Additional Industrial Machine Control Panel or Compartment

(optional)

NEC Article 110, Part II Working

Space Requirements

NEC Article 110, Part II Working

Space Requirements

NFPA 79, Chapter 11 Working Space Requirements

NFPA 79, Chapter 11 Working Space Requirements

Termination of Supply Conductors Externally Mounted Supply Circuit

Disconnecting Means (5.3.1.3 Exception No. 1 & 2)

Industrial Machine Control Panel or Compartment

Additional Industrial Machine Control Panel or Compartment

(optional)

Integral Disconnecting Means

Example

Applicable Working Space Requirements

Externally Mounted Disconnecting Means

Example

Source Busway, Panelboard,

Switchboards or Similar Distribution

Source Busway, Panelboard,

Switchboards or Similar Distribution

A.11.5

Clarification of Working Space Requirements at the Termination Location of Incoming Supply Conductors

Figure A.11.5 identifies the requirements for determining the working spaces for about electrical equipment associated with industrial machinery.

The left side of Figure A.11.5 depicts a situation where the incoming supply circuit disconnecting means, required by 5.3.1.1, is located in the industrial machine control panel or compartment.

The right side of Figure A.11.5 depicts a situation where the incoming supply circuit disconnecting means, required by 5.3.1.1, is externally mounted to the industrial machine control cabinet or the compartment it supplies.

Formatted: Font: Bold

Formatted: Font: Bold

Formatted: Font: Bold

Formatted: Font: Bold

8/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 32/64

Second Revision No. 24-NFPA 79-2013 [ Section No. 11.5.1.2 ]

11.5.1.2

The width of the working space in front of control cabinets and compartments shall be thewidth of the opening into the control cabinet or compartment, or 762 mm (30 in.),whichever is greater. Where control equipment or devices are mounted on or through thefixed area around the opening into the control cabinet or compartment, the width of theworking space in front of the control cabinet or compartment shall include the width of thefixed area containing the control equipment and devices.

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jul 10 10:03:53 EDT 2013

Committee Statement

CommitteeStatement:

The added language clarifies that the working space includes the width of controlequipment or devices mounted to or through the fixed area(s) or flanges of the controlcabinet or compartment allowing safer servicing, maintenance and normal operatingconditions.

ResponseMessage:

Public Comment No. 10-NFPA 79-2013 [Section No. 11.5.1.2]

Second Revision No. 4-NFPA 79-2013 [ Section No. 12.5.1 ]

12.5.1

8/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 1/2

Second Revision No. 4-NFPA 79-2013 [ Section No. 12.5.1 ]

12.5.1

The ampacities of conductors shall not exceed the corresponding temperature values given inTable 12.5.1 before any correction factors for ambient temperature or adjustment factors forthe number of current-carrying conductors have been applied.

Table 12.5.1 Conductor Ampacity Based on Copper Conductors with 60°C (140°F), 75°C(167°F), and 90°C (194°F) Insulation in an Ambient Temperature of 30°C (86°F)

Conductor Size (AWG)

Ampacity

60°C (140°F) 75°C (167°F) 90°C (194°F)

30 — 0.5 0.5

28 — 0.8 0.8

26 — 1 1

24 2 2 2

22 3 3 3

20 5 5 5

18 7 7 14

16 10 10 18

14 20 20 25

12 25 25 30

10 30 35 40

8 40 50 55

6 55 65 75

4 70 85 95

3 85 100 110

2 95 115 130

1 110 130 150

1/0 125 150 170

2/0 145 175 195

3/0 165 200 225

4/0 195 230 260

250 215 255 290

300 240 285 320

350 260 310 350

400 280 335 380

500 320 380 430

600 355 420 475

700 385 460 520

750 400 475 535

800 410 490 555

900 435 520 585

8/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 2/2

900 435 520 585

1000 455 545 615

Notes:

(1) Wire types listed in 12.3.1 shall be permitted to be used at the ampacities listed in thistable.

(2) The sources for the ampacities in this table are Table 310.15(B)( 16) of NFPA 70.

Supplemental Information

File Name Description

Table_12.5.1_with_legislative_changes_to_Note_2_.1375108282710.docx

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 08 14:43:12 EDT 2013

Committee Statement and Meeting Notes

CommitteeStatement:

This change correlates with the changes to relocate "Table 310.16" to "Table 310.15(B)(16)" in the 2011 NEC. The TC editorially corrected the reference to be consistent withthe NEC reference. The corrected table showing legislative text is attached.

ResponseMessage:

Committee Notes:

Date Submitted By

Jul 29,2013

[ Not Specified]

The extra work of attaching the table with legislative text was done because TERRA has problems with simple changes to tables even those of just text changes.

Public Comment No. 14-NFPA 79-2013 [Section No. 12.5.1]

12.5.1 The ampacities of conductors shall not exceed the corresponding temperature values given in Table 12.5.1 before any correction factors for ambient temperature or adjustment factors for the number of current-carrying conductors have been applied. Table 12.5.1 Conductor Ampacity Based on Copper Conductors with 60°C (140°F), 75°C (167°F), and 90°C (194°F) Insulation in an Ambient Temperature of 30°C (86°F)

Conductor Size (AWG) Ampacity

60°C (140°F) 75°C (167°F) 90°C (194°F) 30 — 0.5 0.5

28 — 0.8 0.8

26 — 1 1

24 2 2 2

22 3 3 3

20 5 5 5

18 7 7 14

16 10 10 18

14 20 20 25

12 25 25 30

10 30 35 40

8 40 50 55

6 55 65 75

4 70 85 95

3 85 100 110

2 95 115 130

1 110 130 150 1/0 125 150 170

2/0 145 175 195

3/0 165 200 225

4/0 195 230 260

250 215 255 290

300 240 285 320

350 260 310 350

400 280 335 380

Formatted: Font: Bold

Formatted: Font: Bold

Conductor Size (AWG) Ampacity

60°C (140°F) 75°C (167°F) 90°C (194°F) 500 320 380 430

600 355 420 475

700 385 460 520

750 400 475 535

800 410 490 555

900 435 520 585

1000 455 545 615 Notes: (1) Wire types listed in 12.3.1 shall be permitted to be used at the ampacities listed in this table. (2) The sources for the ampacities in this table are Table 310.16 310.15(B)(16)of NFPA 70.

Formatted: Font: Italic

8/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 1/2

Second Revision No. 3-NFPA 79-2013 [ Section No. 12.5.5 ]

12.5.5

Where ampacity derating is required correction for ambient temperature correction for otherthan 30°C (86°F) or adjusted adjustment for more than three current-carrying conductors in araceway or cable is required , the factor(s) shall be taken from Table 12.5.5(a) and Table12.5.5(b). Sizing of conductors within control enclosures in wiring harnesses or wiringchannels shall be based on the ampacity in cable or raceway. These factors shall apply tocontrol conductors, Article 725, Class 1, of NFPA 70, Article 725, Class 1, controlconductors, only if their continuous load exceeds 10 percent of the conductor ampacity.

Table 12.5.5(a) Ambient Temperature Correction Factors

For ambient temperatures other than 30°C (86°F), multiply the allowable ampacitiesshown ampacity by the appropriate factor shown below.

Ambient Temperature(°C)

CorrectionFactor

60°C

CorrectionFactor

75°CCorrection Factor

90°F

21–25 1.08 1.05 1.04

26–30 1.00 1.00 1.00

31–35 0.91 0.94 0.96

36–40 0.82 0.88 0.91

41–45 0.71 0.82 0.87

46–50 0.58 0.75 0.82

51–55 0.41 0.67 0.76

56–60 — 0.58 0.71

61–70 — 0.33 0.58

71–80 — — 0.41

Table 12.5.5(b) Adjustment Factors for More Than Three Current-Carrying Conductors in aRaceway or Cable

Number of Current-Carrying Conductors

Percent of Values in Table 12.5.5(a) as Adjusted forAmbient Temperature I i f Necessary

4–6 80

7–9 70

10–20 50

21–30 45

31–40 40

41 and above 35

Supplemental Information

File Name Description

12.5.5_table_with_SR_3_changes_in_legislative_text.1375108686542.docx

8/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 2/2

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 08 14:19:43 EDT 2013

Committee Statement and Meeting Notes

CommitteeStatement:

The term "derating" was deleted and the remaining language was changed to beconsistent with the use of the terms "adjustment factors" and "correction factors" in thestandard. The title of Table 12.5.5(a) was edited as there are no allowable ampacitiesshown, only factors.

ResponseMessage:

Committee Notes:

Date Submitted By

Jul 8,2013

[ Not Specified]

ensure language "allowable ampacity shown by" was removed when initial PC was submitted

Jul 29,2013

[ Not Specified]

The added work of adding The table with legislative changes as an attached was done because TERRA has problems with changes to tables even with just the text.

Public Comment No. 34-NFPA 79-2013 [Section No. 12.5.5]

Public Comment No. 48-NFPA 79-2013 [Section No. 12.5.5]

12.5.5 Where ampacity derating is required correction for ambient temperature correction for other than 30°C (86°F) or adjusted adjustment for more than three current-carrying conductors in a raceway or cable is required, the factor(s) shall be taken from Table 12.5.5(a) and Table 12.5.5(b). Sizing of conductors within control enclosures in wiring harnesses or wiring channels shall be based on the ampacity in cable or raceway. These factors shall apply to control conductors, Article 725, Class 1, of NFPA 70, Article 725, Class 1, control conductors, only if their continuous load exceeds 10 percent of the conductor ampacity. Table 12.5.5(a) Ambient Temperature Correction Factors For ambient temperatures other than 30°C (86°F), multiply the allowable ampacities shown ampacity by the appropriate factor shown below.

Ambient Temperature (°C) Correction Factor 60°C Correction Factor

75°C Correction Factor

90°F 21–25 1.08 1.05 1.04 26–30 1.00 1.00 1.00 31–35 0.91 0.94 0.96 36–40 0.82 0.88 0.91 41–45 0.71 0.82 0.87 46–50 0.58 0.75 0.82 51–55 0.41 0.67 0.76 56–60 — 0.58 0.71 61–70 — 0.33 0.58 71–80 — — 0.41

Table 12.5.5(b) Adjustment Factors for More Than Three Current-Carrying Conductors in a Raceway or Cable Number of Current-Carrying

Conductors Percent of Values in Table 12.5.5(a) as Adjusted for

Ambient Temperature iIf Necessary 4–6 80 7–9 70

10–20 50 21–30 45 31–40 40

41 and above 35

Formatted: Font: Bold

Formatted: Font: Bold

8/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 1/2

Second Revision No. 29-NFPA 79-2013 [ Section No. 12.6.1.1 ]

12.6.1.1

16 AWG shall be permitted if part of a jacketed multiconductor cable assembly or flexiblecord, or individual conductors used in a cabinet or enclosure, under the following conditions:

(1) Non-motor power circuits of 8 amperes or less, provided all the following conditions aremet:

(a) Circuit is protected in accordance with Chapter 7.

(b) Overcurrent protection does not exceed 10 amperes.

(c) Overcurrent protection is provided by one of the following:

i. A listed molded-case circuit breaker marked for use with 16 AWG wire

ii. Listed fuses marked for use with 16 AWG wire

iii. Class CC, Class J, Class CF, or Class T fuses

(2) Motor power circuits supplying a motor having a full-load current rating of 8 amperes orless, provided all the following conditions are met:

(a) Circuit is protected in accordance with Chapter 7.

(b) Circuit is provided with Class 10 overload protection.

(c) Overcurrent protection is provided by one of the following:

i. A listed molded-case circuit breaker marked for use with 16 AWG wire

ii. Listed fuses marked for use with 16 AWG wire

iii. Class CC, Class J, or Class CF, Class T fuses

(3) Motor power circuits supplying a motor having a full-load current rating of 5.5 amperes orless, provided all the following are met:

(a) Circuit is protected in accordance with Chapter 7.

(b) Circuit is provided with Class 20 overload protection.

(c) Overcurrent protection is provided by one of the following:

i. A listed molded-case circuit breaker marked for use with 16 AWG wire

ii. Listed fuses marked for use with 16 AWG wire

iii. Class CC, Class J, or Class CF, Class T fuses

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

8/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 2/2

State:

Zip:

Submittal Date: Wed Jul 10 12:44:04 EDT 2013

Committee Statement and Meeting Notes

CommitteeStatement:

This revision adds Class CF fuses to the permitted fuse types listed since Class CFfuses have the same performance requirements as Class J fuses.

ResponseMessage:

8/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 1/2

Second Revision No. 30-NFPA 79-2013 [ Section No. 12.6.1.2 ]

12.6.1.2

18 AWG shall be permitted if part of a jacketed multiconductor cable assembly or flexiblecord, or individual conductors used in a cabinet or enclosure, under the following conditions:

(1) Non-motor power circuits of 5.6 amperes or less, provided all the following conditionsare met:

(a) Circuit is protected in accordance with Chapter 7.

(b) Overcurrent protection does not exceed 7 amperes.

(c) Overcurrent protection is provided by one of the following:

i. A listed molded-case circuit breaker marked for use with 18 AWG wire

ii. Listed fuses marked for use with 18 AWG wire

iii. Class CC, Class J, or Class CF, Class T fuses

(2) Motor power circuits supplying a motor having a full-load current rating of 5 amperes orless, provided all the following conditions are met:

(a) Circuit is protected in accordance with Chapter 7.

(b) Circuit is provided with Class 10 overload protection.

(c) Overcurrent protection is provided by one of the following:

i. A listed molded-case circuit breaker marked for use with 18 AWG wire

ii. Listed fuses marked for use with 18 AWG wire

iii. Class CC, Class J, or Class CF, Class T fuses

(3) Motor power circuits supplying a motor having a full-load current rating of 3.5 amperes orless, provided all the following are met:

(a) Circuit is protected in accordance with Chapter 7.

(b) Circuit is provided with Class 20 overload protection.

(c) Overcurrent protection is provided by one of the following:

i. A listed molded-case circuit breaker marked for use with 18 AWG wire

ii. Listed fuses marked for use with 18 AWG wire

iii. Class CC, Class J, or Class CF, Class T fuses

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

8/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 2/2

State:

Zip:

Submittal Date: Wed Jul 10 12:48:29 EDT 2013

Committee Statement and Meeting Notes

CommitteeStatement:

This revision adds Class CF fuses to the permitted fuse types listed since Class CFfuses have the same performance requirements as Class J fuses.

ResponseMessage:

8/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 1/1

Second Revision No. 39-NFPA 79-2013 [ Section No. 13.1.2.6 ]

13.1.2.6

The equipment grounding (protective) conductor shall be placed as close as practicable tothe associated live (insulated) conductors in order to decrease the impedance of the loop inthe event of a fault.

Submitter Information Verification

Submitter Full Name:Mark Cloutier

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jul 24 11:42:45 EDT 2013

Committee Statement and Meeting Notes

CommitteeStatement:

During the first Revision only parenthetical (protective bonding) and other (grounding)terms were deleted– missed parenthetical terms (Earth/Earthing) and (Protective). TheTC agrees that (Earth/Earthing) and (Protective) parenthetical terms be removed forclarity.

ResponseMessage:

Committee Notes:

Date Submitted By

Aug 9,2013

Barbara Ingalls 13.1.2.6 Okay to delete 'in order' for conciseness?

8/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 41/64

Second Revision No. 32-NFPA 79-2013 [ Section No. 13.1.3 ]

13.1.3 Conductors of Different Circuits.

Conductors of different circuits shall be permitted to be laid side by side and occupy thesame raceway (duct) (e.g., wireway or cable trunking), or be in the same multiconductorcable assembly, provided that the arrangement does not impair the functioning of therespective circuit. Functionally associated circuit conductors, including power, control,remote input/output, signaling, and communication cables shall be permitted in the sameraceway or cable assembly regardless of voltage, provided all are insulated for themaximum voltage of any circuit within the raceway or cable assembly. Where thosecircuits operate at different voltages, the conductors shall be separated by barriers orshall be insulated for the highest voltage to which any conductor within the sameraceway (duct) or cable assembly is subjected.

Exception: Different voltage insulation levels or conductor properties shall be permittedin the same cable assembly, provided the cable assembly has been designed andtested to the identified application.

Submitter Information Verification

Submitter Full Name:Mark Cloutier

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jul 24 10:57:47 EDT 2013

Committee Statement

CommitteeStatement:

During the first Revision only parenthetical (protective bonding) and other (grounding)terms were deleted– missed parenthetical terms (Ducts) and (Cable TrunkingSystems). The TC agrees that all parenthetical terms be removed for clarity.

ResponseMessage:

8/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 42/64

Second Revision No. 15-NFPA 79-2013 [ Section No. 13.1.4 ]

13.1.4 Conductors Equipment Supplied from Separate Supply Circuit Disconnects orTwo or More Sources of Power .

Where the equipment is supplied from two or more sources of power or from two or moreindependent supply circuit disconnecting means, the power wiring from each supplysource or from each supply circuit disconnecting means shall be run in separateraceways and shall not terminate in or pass through common junction boxes.

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 09 15:13:57 EDT 2013

Committee Statement

CommitteeStatement:

The additional text will further clarify the requirements are for the supply sourcecircuits. The title was changed and text was added to the section to further clarifythe requirements are for situations where the equipment is supplied from multiplesupply sources or circuits. These requirements originated in the JIC Standards andhave resided in more than one Chapter due to revisions of NFPA 79. For thesereasons the original intent of the requirements has been lost. Significant researchwas done to follow the history and the original requirements were clearly related tosupply conductors. The proposed revisions will further clarify that relationship. Theterm "supply circuit" was chosen to identify the proper disconnecting means and toalign with 5.3.

ResponseMessage:

Public Comment No. 32-NFPA 79-2013 [Section No. 13.1.4]

8/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 43/64

Second Revision No. 40-NFPA 79-2013 [ Section No. 13.2.2 ]

13.2.2 Identification of the Equipment Grounding (Protective) Conductor.

13.2.2.1*

The color GREEN with or without one or more YELLOW stripes shall be used to identifythe equipment grounding conductor where insulated or covered. This color identificationshall be strictly reserved for the equipment grounding conductor.

Exception No. 1: In multiconductor cable-connected assemblies where equipmentgrounding is not required, the solid color GREEN shall be permitted for other thanequipment grounding.

Exception No. 2: It shall be permitted to use conductors of other colors, provided theinsulation or cover is appropriately identified at all points of access.

Exception No. 3: For grounded control circuits, use of a GREEN insulated conductorwith or without one or more YELLOW stripes or a bare conductor from the transformerterminal to a grounding terminal on the control panel shall be permitted.

13.2.2.2

Where the equipment grounding (protective) conductor is identified by its shape,position, or construction (e.g., a braided conductor) or where the insulated conductor isnot readily accessible, color coding throughout its length shall not be required. The endsor accessible portion shall be clearly identified by the symbol in Figure 8.2.1.3.4, thecolor GREEN with or without one or more YELLOW stripes, or the bicolor combinationGREEN-AND-YELLOW.

Submitter Information Verification

Submitter Full Name:Mark Cloutier

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jul 24 11:43:54 EDT 2013

Committee Statement

CommitteeStatement:

During the first Revision only parenthetical (protective bonding) and other (grounding)terms were deleted– missed parenthetical terms (Earth/Earthing) and (Protective).The TC agrees that (Earth/Earthing) and (Protective) parenthetical terms be removedfor clarity.

ResponseMessage:

8/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 44/64

Second Revision No. 33-NFPA 79-2013 [ Section No. 13.4.2 ]

13.4.2 External Raceways (Ducts) .

13.4.2.1

All conductors of the same ac circuit routed to the same location shall be contained inthe same raceway (duct) .

13.4.2.2

Conductors external to the electrical equipment enclosure(s) shall be enclosed inraceways (ducts) described in Section 13.5.

Exception: Cables and cable connectors need not be enclosed in a raceway where theyare protected and supported in accordance with 13.1.6.

13.4.2.3

Fittings used with raceways (ducts) or multiconductor cable shall be identified for use inthe physical environment.

13.4.2.4

Flexible conduit or multiconductor cable with flexible properties shall be used where it isnecessary to employ flexible connections to pendant pushbutton stations. The weight ofthe pendant stations shall be supported by means other than the flexible conduit or themulticonductor cable with flexible properties, except where the conduit or cable isspecifically designed for that purpose.

13.4.2.5

Flexible conduit or multiconductor cable with flexible properties shall be used forconnections involving small or infrequent movements. They shall also be permitted tocomplete the connection to stationary motors, position switches, and other externallymounted devices. Where prewired devices (e.g., position switches, proximity switches)are supplied, the integral cable shall not be required to be enclosed in a raceway (duct) .

Submitter Information Verification

Submitter Full Name:Mark Cloutier

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jul 24 11:05:15 EDT 2013

Committee Statement

CommitteeStatement:

During the first Revision only parenthetical (protective bonding) and other (grounding)terms were deleted– missed parenthetical terms (Ducts) and (Cable TrunkingSystems). The TC agrees that (Ducts) and (Cable Trunking Systems) parentheticalterms be removed for clarity.

ResponseMessage:

8/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 45/64

Second Revision No. 34-NFPA 79-2013 [ Section No. 13.5 ]

13.5 Raceways, (Ducts), Support Systems (Cable Supports), Connection Boxes, andOther Boxes.

13.5.1 General Requirements.

13.5.1.1

Raceways, (ducts), factory elbows and couplings, and associated fittings shall be listedand shall be identified for the environment.

Exception: Raceways (ducts) fabricated as part of the machine that comply with therequirements of 13.5.6 shall not be required to be listed.

13.5.1.2

All sharp edges, burrs, rough surfaces, or threads that the insulation of the conductorscan come in contact with shall be removed from raceways (ducts) and fittings. Wherenecessary, additional protection consisting of a flame-retardant, oil-resistant insulatingmaterial shall be provided to protect conductor insulation.

13.5.1.3

Drain holes shall not be permitted in raceways, (ducts), junction boxes, and pull boxeswhere the holes would compromise the intended enclosure integrity. Drain holes of 6.4mm (1⁄4 in.) diameter shall be permitted in wireways, (cable trunking systems),connection boxes, and other boxes used for wiring purposes that are subject toaccumulations of oil or moisture.

13.5.1.4

Raceways shall be securely fastened in place and supported.

Exception: Flexible raceways shall not be required to be secured or supported whereelsewhere permitted in this chapter.

13.5.2* Percentage Fills of Raceways (Ducts) .

The combined cross-sectional area of all conductors and cables shall not exceed 50percent of the interior cross-sectional area of the raceway (duct) . The fill provisions shallbe based on the actual dimensions of the conductors or cables used.

13.5.3 Rigid Conduit and Fittings.

13.5.3.1 General Requirements.

13.5.3.1.1

The minimum electrical trade size shall be metric designator 16 (trade size 1⁄2).

13.5.3.1.2*

The maximum electrical trade size shall be metric designator 155 (trade size 6).

13.5.3.1.3

Where conduit enters a box or enclosure, a bushing or fitting providing a smoothlyrounded insulating surface shall be installed to protect the conductors from abrasion,unless the design of the box or enclosure is such that it provides the same protection.Where conduit bushings are constructed entirely of insulating material, a locknut shall beprovided both inside and outside the enclosure to which the conduit is attached.

Exception: Where threaded hubs or bosses that are an integral part of an enclosureprovide a smoothly rounded or flared entry for conductors.

8/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 46/64

13.5.3.1.4

Conduit bends shall be made in such a manner that the conduit shall not be damagedand the internal diameter of the conduit shall not be effectively reduced. The radius of thecurve of any field bend to the center line of the conduit shall be not less than shown inTable 13.5.3.1.4.

Table 13.5.3.1.4 Minimum Radii of Conduit Bends

Conduit Size

One-Shot and

Full-Shoe Benders Other Bends

Metric Designator Trade Size mm in. mm in.

16 1⁄2 101.6 4 101.6 4

21 3⁄4 114.3 41⁄2 127 5

27 1 146.05 53⁄4 152.4 6

35 11⁄4 184.15 71⁄4 203.2 8

41 11⁄2 209.55 81⁄4 254 10

53 2 241.3 91⁄2 304.8 12

63 21⁄2 266.7 101⁄2 381 15

78 3 330.2 13 457.2 18

91 31⁄2 381 15 533.4 21

103 4 406.4 16 609.6 24

129 5 609.6 24 762 30

155 6 762 30 914.4 36

13.5.3.1.5

A run of conduit shall contain not more than four quarter bends or a combination of bendstotaling 360 degrees between pull points.

13.5.3.2 Metal-Type Nonflexible Conduit.

13.5.3.2.1 General Requirements.

13.5.3.2.1.1

Conduits shall be securely held in place and supported at each end.

13.5.3.2.1.2

Fittings shall be compatible with the conduit and identified for the application. Fittingsshall meet the following requirements:

(1) Fittings and conduits shall be threaded using an electrical conduit die unlessstructural difficulties prevent assembly.

(2) Running threads shall not be used on conduit for connection at couplings.

(3) Metallic tubing shall not be threaded.

(4) Where threadless fittings are used, the conduit shall be securely fastened to theequipment.

13.5.3.2.2* Rigid Metal Conduit (RMC).

Rigid metal conduit and fittings shall be of galvanized steel or of a corrosion-resistantmaterial identified for the conditions of service.

13.5.3.2.3* Intermediate Metal Conduit (IMC).

Intermediate metal conduit shall be a steel raceway of circular cross-section with integralor associated couplings, approved for the installation of electrical conductors and usedwith approved fittings to provide electrical continuity.

13.5.3.2.4* Electrical Metallic Tubing (EMT).

8/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 47/64

13.5.3.2.4* Electrical Metallic Tubing (EMT).

Electrical metallic (steel) tubing shall be a metallic tubing of circular cross-sectionapproved for the installation of electrical conductors when joined together with approvedfittings. The maximum size of tubing shall be metric designator 103 (trade size 4).

13.5.3.3 Rigid Nonmetallic Conduit (RNC) (PVC Schedule 80).

13.5.3.3.1*

Rigid nonmetallic conduit (RNC) (PVC Schedule 80) shall be of nonmetallic materialapproved for the installation of electrical conductors and identified for use where subjectto physical damage.

13.5.3.3.2

Conduit shall be securely held in place and supported as specified in Table 13.5.3.3.2. Inaddition, conduit shall be securely fastened within 900 mm (3 ft) of each box, enclosure,or other conduit termination.

Table 13.5.3.3.2 Support of Rigid Nonmetallic Conduit (RNC)

Conduit Size Maximum Spacing Between Supports

Metric Designator Trade Size mm or m ft

16–27 1⁄2–1 900 mm 3

35–53 11⁄4–2 1.5 m 5

63–78 21⁄2–3 1.8 m 6

91–129 31⁄2–5 2.1 m 7

155 6 2.5 m 8

13.5.3.3.3*

Expansion fittings shall be installed to compensate for thermal expansion andcontraction.

13.5.3.3.4

All joints between lengths of conduit and between conduit and couplings, fittings, andboxes shall be made with fittings approved for the purpose.

13.5.4 Flexible Metal Conduit (FMC) and Fittings.

13.5.4.1 General Requirements.

13.5.4.1.1

Flexible metal conduit (FMC) and liquidtight flexible metal conduit (LFMC) minimumelectrical trade size shall be metric designator 12 (trade size 3⁄8).

Exception: Thermocouples and other sensors

13.5.4.1.2*

The maximum size of FMC and LFMC shall be metric designator 103 (trade size 4).

13.5.4.1.3

FMC and LFMC shall be installed in such a manner that liquids will tend to run off thesurface instead of draining toward the fittings.

13.5.4.1.4

Fittings shall be compatible with the conduit and identified for the application. Connectorsshall be the “union” types.

13.5.4.2 Flexible Metal Conduit (FMC).

Flexible metal conduit shall be identified for use in the expected physical environment.

13.5.4.3 Liquidtight Flexible Metal Conduit (LFMC).

Liquidtight flexible metal conduit shall be identified for use in the expected physicalenvironment.

13.5.5 Liquidtight Flexible Nonmetallic Conduit (LFNC) and Fittings.

8/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 48/64

13.5.5.1

Liquidtight flexible nonmetallic conduit (LFNC) is a raceway of circular cross section ofthe following types:

(1) A smooth, seamless inner core and cover that is bonded together and has one ormore reinforcement layers between the core and cover, designated as Type LFNC–A

(2) A smoother inner surface with integral reinforcement within the conduit wall,designated as Type LFNC–B

(3) A corrugated internal and external surface with or without integral reinforcementwithin the conduit wall, designated as Type LFNC–C

13.5.5.2

LFNC shall be resistant to kinking and shall have physical characteristics of the sheathof multiconductor cables.

13.5.5.3

The conduit shall be identified for use in the expected physical environment.

13.5.5.4

LFNC minimum electrical trade size shall be metric designator 12 (trade size 3⁄8 in.).

13.5.5.5*

The maximum electrical trade size of LFNC shall be metric designator 103 (trade size 4in.).

13.5.5.6

Fittings shall be compatible with the conduit and identified for the application.

13.5.5.7

Flexible conduit shall be installed in such a manner that liquids will tend to run off thesurface instead of draining toward the fittings.

13.5.6 Wireways (Cable Trunking Systems).

13.5.6.1

Wireways (cable trunking systems) external to enclosures shall be rigidly supported andclear of all moving or contaminating portions of the machine.

13.5.6.2

Covers shall be shaped to overlap the sides; gaskets shall be permitted. Covers shall beattached to wireways by hinges or chains and held closed by means of captive screws orother suitable fasteners. On horizontal wireway, the cover shall not be on the bottom.Hinged covers shall be capable of opening at least 90 degrees.

13.5.6.3

Where the wireway is furnished in sections, the joints between sections shall fit tightly,but shall not be required to be gasketed.

13.5.6.4

The only openings permitted shall be those required for wiring or for drainage.

13.5.6.5

Wireways shall not have opened but unused knockouts.

13.5.6.6

Metal thickness and construction of wireways shall comply with ANSI/UL 870.

13.5.7* Machine Compartments and Wireways.

8/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 49/64

13.5.7* Machine Compartments and Wireways.

The use of compartments or wireways within the column or base of a machine to encloseconductors shall be permitted, provided the compartments or wireways are isolated fromcoolant or oil reservoirs and are entirely enclosed. Conductors run in enclosedcompartments or wireways shall be secured and arranged so that they are not subject todamage.

13.5.8 Connection Boxes and Other Boxes.

13.5.8.1

Connection boxes and other boxes used for wiring purposes shall be readily accessiblefor maintenance. Those boxes shall provide protection against the ingress of solid bodiesand liquids, taking into account the external influences under which the machine isintended to operate.

13.5.8.2

Those boxes shall not have opened but unused knockouts or any other openings andshall be constructed so as to exclude materials such as dust, flyings, oil, and coolant.

13.5.9 Motor Connection Boxes.

13.5.9.1

Motor connection boxes shall enclose only connections to the motor and motor-mounteddevices (e.g., brakes, temperature sensors, plugging switches, tachometer generators).

13.5.9.2

Electrical connections at motor terminal boxes shall be made with an identified method ofconnection. Twist-on wire connectors shall not be used for this purpose.

13.5.9.3

Connectors shall be insulated with a material that will not support combustion.

13.5.9.4

Soldered or insulation-piercing–type connectors (lugs) shall not be used.

13.5.10 Cable Trays.

Cable trays to be used for cable or raceway support on industrial machines shall bepermitted. Cable trays shall be permitted to support the following:

(1) Single conductors 1/0 or larger that are otherwise permitted on industrial machines

(2) Multiconductor flexible cables and cables with flexible properties that are otherwisepermitted on industrial machines

(3) Raceways functionally associated with industrial manufacturing systems

(4) Special conductors and cables that are otherwise permitted on industrial machines(See Section 12.9.)

13.5.11 Cords in Cable Trays.

Cords shall not be installed in cable trays.

Submitter Information Verification

Submitter Full Name:Mark Cloutier

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

8/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 50/64

Submittal Date: Wed Jul 24 11:09:11 EDT 2013

Committee Statement

CommitteeStatement:

During the first Revision only parenthetical (protective bonding) and other (grounding)terms were deleted– missed parenthetical terms (Ducts) and (Cable TrunkingSystems). The TC agrees that (Ducts) and (Cable Trunking Systems) parentheticalterms be removed for clarity.

ResponseMessage:

Second Revision No. 16-NFPA 79-2013 [ Section No. 16.2.7 ]

16.2.7

A safety sign shall be provided adjacent to the main supply circuit disconnect operatinghandle to warn qualified persons of potential electric arc flash hazards. The marking onthe sign shall be located so as to be clearly visible to qualified persons beforeexamination, adjustment, servicing, or maintenance of the equipment.

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 09 15:26:03 EDT 2013

Committee Statement

CommitteeStatement:

Requirements for arc flash marking are detailed in 16.2.3, 16.2.3.1, and 16.2.3.2.Deleting the redundant section clarifies the language for the user.

ResponseMessage:

Public Comment No. 26-NFPA 79-2013 [Section No. 16.2.7]

8/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 51/64

Second Revision No. 17-NFPA 79-2013 [ Section No. 16.4.1 ]

16.4.1

Control equipment shall be legibly and durably marked in a way that is plainly visible afterthe equipment is installed. A nameplate giving the following information shall be attachedto the outside of the enclosure, or on the machine immediately adjacent to the enclosure:

(1) Name or trademark of supplier

(2) Serial number, where applicable Model, serial number, or other designation

(3)

(4) Ampere rating of the largest motor or load

(5) Maximum ampere rating of the short-circuit and ground-fault protective device,where provided

(6) Short-circuit current rating of the industrial control panel

(7) Electrical diagram number(s) or the number of the index to the electrical drawings

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 09 15:45:17 EDT 2013

Committee Statement

CommitteeStatement:

This revision allows the manufacturer of the machine to use alternate meansof identifying the equipment.

ResponseMessage:

Public Comment No. 22-NFPA 79-2013 [Section No. 16.4.1]

Second Revision No. 35-NFPA 79-2013 [ Section No. 17.5 ]

17.5 Installation Diagram.

17.5.1*

* Rated voltage, number of phases and frequency (if ac), and full-load current foreach supply

8/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 52/64

17.5.1*

The installation diagram shall provide all information necessary for the preliminary work ofsetting up the machine.

17.5.2

The specified position of the electrical supply to be installed on site shall be clearlyindicated.

17.5.3*

The data necessary for choosing the type, characteristics, rated currents, and setting ofthe overcurrent protective device(s) for the supply circuit conductors to the electricalequipment of the machine shall be stated.

17.5.4*

Where necessary, the size, purpose, and location of any raceways (ducts) in thefoundation that are to be provided by the user shall be detailed.

17.5.5*

The size, type, and purpose of raceways, (ducts), cable trays, or cable supportsbetween the machine and the associated equipment that are to be provided by the usershall be detailed.

17.5.6*

Where necessary, the diagram shall indicate where space is required for the removal orservicing of the electrical equipment.

17.5.7*

Where it is appropriate, an interconnection diagram or table shall be provided. Thatdiagram or table shall give full information about all external connections. Where theelectrical equipment is intended to be operated from more than one source of electricalsupply, the interconnection diagram or table shall indicate the modifications orinterconnections required for the use of each supply.

Submitter Information Verification

Submitter Full Name:Mark Cloutier

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jul 24 11:12:34 EDT 2013

Committee Statement

CommitteeStatement:

During the first Revision only parenthetical (protective bonding) and other (grounding)terms were deleted– missed parenthetical terms (Ducts) and (Cable TrunkingSystems). The TC agrees that (Ducts) and (Cable Trunking Systems) parentheticalterms be removed for clarity.

ResponseMessage:

8/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 53/64

Second Revision No. 12-NFPA 79-2013 [ New Section after A.7.7 ]

A.8.1

See Annex J for descriptions of various grounding and bonding terminologies used inIEC and ANSI standards.

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 09 11:34:21 EDT 2013

Committee Statement

CommitteeStatement:

With the removal of parenthetical IEC terminology, the current annex note 8.1 is notappropriate but should be changed to direct the user to the new Annex J.

ResponseMessage:

Public Comment No. 29-NFPA 79-2013 [New Section after A.7.7]

Public Comment No. 28-NFPA 79-2013 [Section No. 8.1]

8/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 54/64

Second Revision No. 18-NFPA 79-2013 [ Section No. A.9.2 ]

A.9.2

Some examples of safety-related functions can be functions are emergency stopping,interlocking, temperature or speed control, etc. and so forth, IEC 62061, ISO 13849-1,ISO 13849-2, ANSI B11.0, ANSI B11-TR4, and ANSI B11-TR6 are examples ofapplicable functional safety standards. Compliance with other standards for particularapplications and types of machinery can require additional or specific functional safetyrequirements.

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 09 16:01:37 EDT 2013

Committee Statement

CommitteeStatement:

The revised text provides guidance that compliance to machine/application specificstandards can require additional or specific functional safety requirements.

ResponseMessage:

Public Comment No. 35-NFPA 79-2013 [Section No. A.9.2]

Second Revision No. 45-NFPA 79-2013 [ Section No. J.2 ]

J.2 NEC NFPA 70 Terms.

Bonded (Bonding). Connected to establish electrical continuity and conductivity. [ 70,2011] [ 70: 100]

Discussion. Bonding is accomplished if items are connected together regardless ofwhether or not there is a connection to ground (earth).

Bonding Conductor or Jumper. A reliable conductor to ensure the required electricalconductivity between metal parts required to be electrically connected. [ 70, 2011][ 70: 100]

Discussion. Bonding conductor sizes are provided in the specific requirements related towhat the bonding is intended to accomplish such as being suitable for fault current or

8/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 55/64

minimizing voltage differences.

Bonding Jumper, Equipment. The connection between two or more portions of theequipment grounding conductor. [ 70, 2011] [ 70: 100]

Discussion. Equipment bonding jumpers are typically short in length and used to ensurea reliable connection such as between an enclosure and its hinged door.

Bonding Jumper, Supply-Side. A conductor installed on the supply side of a service orwithin a service equipment enclosure(s), or for a separately derived system, that ensuresthe required electrical conductivity between metal parts required to be electricallyconnected. [ 70, 2011] [ 70: 250.2]

Discussion. Conductors that are intended to carry fault current for ungroundedconductors that do not have overcurrent protection at their supply point are consideredsupply-side bonding jumpers. Examples are those for tap conductors and transformersecondary conductors. Conductor sizing is based on a percentage of the ungroundedconductors.

Bonding Jumper, System. The connection between the grounded circuit conductorand the supply-side bonding jumper, or the equipment grounding conductor, or both, at aseparately derived system. [ 70, 2011] [ 70: 100]

Discussion. System bonding jumpers provide a fault current path for grounded systems.They can be conductors, busbars, or other suitable means.

Effective Ground-Fault Current Path. An intentionally constructed, low-impedanceelectrically conductive path designed and intended to carry current under ground-faultconditions from the point of a ground fault on a wiring system to the electrical supplysource and that facilitates the operation of the overcurrent protective device or ground-fault detectors . on high-impedance grounded systems. [ 70, 2011] [ 70: 100]

Discussion. Equipment made of conductive materials that contains electricalconductors is commonly considered to be "likely to become energized" because aninsulation failure can occur and energize the equipment. This type of equipment isgenerally required to be provided with an effective ground fault current path. Anequipment grounding conductor or bonding jumper is commonly used to provide aneffective ground fault current path. The earth is not permitted as the only path for thisfault current.

Ground. The earth. [ 70, 2011] [ 70: 100]

Discussion. Systems or equipment are either connected to the earth or are consideredungrounded systems.

Ground Fault. An unintentional, electrically conducting conductive connectionbetween an ungrounded conductor of an electrical circuit and the normally non–current-carrying conductors, metallic enclosures, metallic raceways, metallic equipment, orearth. [ 70, 2011] [ 70: 100]

Discussion. An insulation failure is a common example of a condition that results in aground fault.

Grounded (Grounding). Connected (connecting) to ground or to a conductive bodythat extends the ground connection. [ 70, 2011] [ 70: 100]

Discussion. Equipment that is connected to an equipment grounding conductor can beconsidered grounded, as the equipment grounding conductor extends the groundconnection.

Grounded, Solidly. Connected to ground without inserting any resistor or impedancedevice. [ 70, 2011] [ 70: 100]

8/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 56/64

Discussion. Solidly grounded is a method of system grounding. Using resistors orreactors are other options for grounding some types of systems.

Grounded Conductor. A system or circuit conductor that is intentionally grounded.[ 70, 2011] [ 70: 100]

Discussion. The grounded conductor is commonly grounded by a grounding electrodeconductor. Depending on the type of electrical system, this can be a neutral conductor,phase conductor, or line conductor. Insulated grounded conductors are generallyrequired to be identified with white or gray coloring.

Ground-Fault Current Path. An electrically conductive path from the point of a groundfault on a wiring system through normally non–current-carrying conductors, equipment,or the earth to the electrical supply source. [ 70, 2011] [ 70: 100]

Informational Note: Examples of ground-fault current paths could consist of are anycombination of equipment grounding conductors, metallic raceways, metallic cablesheaths, electrical equipment, and any other electrically conductive material such asmetal , water , and gas piping , ; steel framing members, stucco mesh , ; metalducting , ; reinforcing steel , ; shields of communications cables, and the earth itself.[ 70, 2011] [ 70: 100]

Discussion. Current will take all paths that exist when a voltage difference exists. Someof these paths can be effective ground-fault current paths and others such as the earthare not.

Grounding Conductor, Equipment (EGC). The conductive path(s) installed toconnect that provides a ground-fault current path and connects normally non–current-carrying metal parts of equipment together and to the system grounded conductor or tothe grounding electrode conductor, or both. [ 70, 2011] [ 70: 100]

Informational Note No. 1: It is recognized that the equipment grounding conductor alsoperforms bonding. [ 70: 100]

Informational Note No. 2: See 250.118 for a list of acceptable equipment groundingconductors. [ 70: 100]

Discussion. Equipment grounding conductors are commonly used to provide aneffective ground-fault current path. Insulated equipment grounding conductors aregenerally required to be identified with a green coloring.

Grounding Electrode. A conducting object through which a direct connection to earthis established. [ 70, 2011] [ 70: 100]

Discussion. Underground metal water pipes, concrete encased steel reinforcing rods,and ground rods are typical grounding electrodes.

Grounding Electrode Conductor. A conductor used to connect the system groundedconductor or the equipment to a grounding electrode or to a point on the groundingelectrode system. [ 70, 2011] [ 70: 100]

Discussion. Grounding electrode conductors are what actually accomplish the groundingof equipment or systems.

Metal Wireways. Sheet metal troughs with hinged or removable covers for housingand protecting electrical wires and cable and in which conductors are laid in place afterthe wireway raceway has been installed as a complete system. [ 70, 2011][ 70: 376.2]

Discussion. Wireways are a type of raceway used to contain electrical conductors andare commonly available in square cross sections.

8/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 57/64

Neutral Conductor. The conductor connected to the neutral point of a system that isintended to carry current under normal conditions. [ 70, 2011] [ 70: 100]

Discussion. Neutral conductors only exist if the system has a neutral point and aregenerally also grounded conductors.

Neutral Point. The common point on a wye-connection in a polyphase system ormidpoint on a single-phase, 3-wire system, or midpoint of a single-phase portion of a 3-phase delta system, or a midpoint of a 3-wire, direct-current system. [ 70, 2011][ 70: 100]

Informational Note: At the neutral point of the system, the vectorial sum of the nominalvoltages from all other phases within the system that utilize the neutral, with respect tothe neutral point, is zero potential.

Discussion. A neutral point only exists on systems that have multiple "connectionpoints" with a connection point in the middle.

Separately Derived System. A premises wiring system whose power is derived from asource of electric energy or equipment other than a service. Such systems have nodirect connection from circuit conductors of one system to circuit conductors of anothersystem, other than connections through the earth, metal enclosures, metallic raceways,or equipment grounding conductors. [ 70, 2011] An electrical source, other than aservice, having no direct connection(s) to circuit conductors of any other electricalsource other than those established by grounding and bonding connections. [ 70: 100]

Discussion. Transformers, generators, and batteries that are not directly connected toother sources are examples of separately derived systems. System bonding jumpers,equipment grounding conductors, and grounding electrode conductors are notconsidered direct connections.

Service. The conductors and equipment for delivering electric energy from the servingutility to the wiring system of the premises served. [ 70, 2011] [ 70: 100]

Discussion. Services only exist if a utility is supplying the electricity.

Ungrounded. Not connected to ground or to a conductive body that extends theground connection. [ 70, 2011] 70: 100]

Discussion. Systems that have no direct connection to ground (earth) are consideredungrounded, such as vehicle-supplied battery systems and transformer or generatorsystems that are not connected to ground. A slang term commonly used for these typesof systems is "floating."

Submitter Information Verification

Submitter Full Name:Mark Cloutier

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jul 24 13:45:03 EDT 2013

Committee Statement

8/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 58/64

CommitteeStatement:

Discussion points were added to help the user better understand the termsin the document.

ResponseMessage:

Second Revision No. 43-NFPA 79-2013 [ Section No. J.3 ]

J.3 Terms and Definitions Used in IEC 60204-1 Relating to Protective and FunctionalBonding Extracted from the Draft of the 2nd CD for the 6th Edition.

Cable Trunking System. A system of enclosures comprised of a base and aremovable cover intended for the complete surrounding of insulated conductors, cables,and cords.

Discussion. Cable trunk ing is commonly used within enclosures to support and containconductors.

Duct. An enclosed channel designed expressly for holding and protecting electricalconductors, cables, and busbars.

3.24

equipotential bonding

Equipotential Bonding. provision Provision of electric connections between conductiveparts, intended to achieve equipotentiality

[IEV 195-1-10]

Discussion. Connecting conductive parts together minimizes voltage differences but byitself does not provide an effective fault current path.

3.25

exposed conductive part

Exposed Conductive Part. conductive Conductive part of electrical equipment, whichcan be touched and which is not live under normal operating conditions, but which canbecome live under fault conditions

[IEV 826-12-10, modified]

Discussion. Often linked with “structural parts"; electrical parts that are not normally livegenerally do need to be bonded to the protective bonding circuit.

3.26

extraneous conductive part

Extraneous Conductive Part. conductive Conductive part not forming part of theelectrical installation and liable to introduce a potential, generally the earth potential

[IEV 826-12-11, modified]

NOTE Examples of extraneous conductive parts can include ladders, handrails, pipes,machine parts, etc. ” that appear with this definition.

Discussion. Generally, the machine is considered an extraneous conductive part.

8/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 59/64

3.29

fault protection

Fault Protection. protection Protection against electric shock under single-faultconditions

[195-06-02]

Discussion. Overcurrent protective devices and insulation are types of fault protection.

3.30

functional bonding

Functional Bonding. equipotential Equipotential bonding necessary for properfunctioning of electrical equipment

3.36

live part

Live Part. conductor Conductor or conductive part intended to be energized in normaluse, including a neutral conductor, but, by convention, not a PEN conductor

NOTE This term does not necessarily imply a risk of electric shock.

Discussion. PLCs and drives generally do not need special bonding, and there are only afew devices that need separate “functional” bonding, such as some scales.

3.40

neutral conductor

N

Neutral Conductor N. conductor Conductor electrically connected to the neutral pointof a system and capable of contributing to the distribution of electrical energy

[IEV 195-02-06, modified]

Plug/Socked Combination. Component and a suitable mating component,appropriate to terminate conductors, intended for connection or disconnection of two ormore conductors.

Note Examples of plug/socket combinations include:

– connectors which fulfill the requirements of IEC 61984

– a plug and socket-outlet, a cable coupler, or an appliance coupler in accordance withIEC 60309-1

– a plug and socket;outlet in accordance with IEC 60884-1 or an appliance coupler inaccordance with IEC 608320-1

3.46

protective bonding

Protective Bonding. equipotential Equipotential bonding for protection against electricshock

NOTE Measures for protection against electric shock can also reduce the risk of burns orfire.

Discussion. The network of protective conductors, along with the necessary bondingjumpers, provide the protective bonding, including the connection to the “main earthingterminal PE."

8/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 60/64

3.47

protective bonding circuit

Protective Bonding Circuit. protective Protective conductors and conductive partsconnected together to provide protection against electric shock in the event of aninsulation failure

3.48

protective conductor

Protective Conductor. conductor Conductor required for protective bonding by somemeasures for protection against electric shock for electrically connecting any of thefollowing parts:

– exposed conductive parts;

– extraneous conductive parts;

– main earthing terminal (PE)

[IEV 826-13-22, modified]

Submitter Information Verification

Submitter Full Name:Mark Cloutier

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jul 24 11:55:52 EDT 2013

Committee Statement

CommitteeStatement:

The definition of "Cable Trunking" and "Duct" were removed from the definitions inChapter 3 because they are no longer used in the document. They were moved toAnnex J for informational purposes to help users understand the "Cross reference"between NEC/79 terms and IEC/EN terms and to harmonize with IEC terms.Discussion points were added to further enhance understanding of terms used inother standards and how they relate to terms used in NFPA 79.

ResponseMessage:

8/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 61/64

Second Revision No. 19-NFPA 79-2013 [ Section No. K.1.2.2 ]

K.1.2.2 EN Publications.

European Committee for Electrotechnical Standardization (CENELEC), 35, Rue deStassartstraat, B-1050 Brussels, Belgium. CENELEC Online Info Service:[email protected]

EN 60204-1 , Safety of machinery — Electrical equipment of machines — Part 1:General requirements, 2006 + A1 2009 .

EN 61010-1, Safety requirements for electrical equipment for measurement, control, andlaboratory use — Part 1: General requirements,2006 2010 .

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 09 16:06:15 EDT 2013

Committee Statement

CommitteeStatement:

The TC editorially corrected the reference to EN 60204-1 and EN 61010-1.

Response Message:

Public Comment No. 38-NFPA 79-2013 [Section No. K.1.2.2]

Second Revision No. 20-NFPA 79-2013 [ Section No. K.1.2.3 ]

K.1.2.3 IEC Publications.

International Electrotechnical Commission, 3, rue de Varembé, P.O. Box 131, CH-1211Geneva 20, Switzerland.

IEC 60034-1 Ed. 12.0 , Rotating electrical machines — Part 1: Rating and performance,1999–2008 2010 .

IEC 60072-1 Ed. 6.0 , Dimensions and output series for rotating electrical machines —Part 1: Frame numbers 56 to 400 and flange numbers 55 to 1080, 1991–2003 1991 .

IEC 60204-1, Ed. 4.1 5.1, Safety of machinery — Electrical equipment of machines —Part 1: General requirements, 2000–2005 2009 .

8/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 62/64

IEC 60332-1 Ed. 1.0 [Series] , Tests on electric cables under fire conditions — Part 1:Test on a single vertical insulated wire or cable, 1993–2004 2004 .

IEC 60364-4-4 1 Ed. 5.0 , Electrical installations of buildings — Part 4-41: Protection forsafety — Protection against electric shock , 2001–2008 2005 .

IEC 60364-5-53 Ed. 3.1 , Electrical Installations of Buildings — Part 5-53: Selection andErection of Electrical Equipment — Isolation, Switching and Control, 2002–2006 2006 .

IEC 60417-1 60417 DB [Database] , Graphical symbols for use on equipment — Part 1:Overview and application, 2000–2005 2002 .

IEC 60417-2, Graphical symbols for use on equipment — Part 2: Symbol originals ,1998–2008.

IEC 60529, Ed. 2.1, Degrees of protection provided by enclosures (IP Code), 2001–2002 2001 .

IEC 60621-3 Ed. 1.0 , Electrical installations for outdoor sites under heavy conditions(including open-cast mines and quarries). Part 3: General requirements for equipmentand ancillaries, 1979–2001 1979 .

IEC 60742, Ed. 1.0, Isolating transformers and safety isolating transformers, 1983.

IEC 60870-5-1 Ed. 1.0 , Telecontrol equipment and systems. Part 5: Transmissionprotocols — Section One: Transmission frame formats, 1990–2002 1990 .

IEC 60947-4-1 Ed. 3.1 , Low-voltage switchgear and controlgear — Part 4-1: Contactorsand motor-starters— Electromechanical contactors and motor-starters, 2000–2011 2012 .

IEC 60947-5-1 Ed. 3.1 , Low-voltage switchgear and controlgear — Part 5-1: Controlcircuit devices and switching elements — Electromechanical control circuit devices,2000–2003 2009 .

IEC 60947-7-1 Ed. 3.0 , Low-voltage switchgear and controlgear — Part 7: Ancillaryequipment — Section 1: Terminal blocks for copper conductors, 1999–2008 2009 .

IEC 61010-1 Ed. 3.0 , Safety requirements for electrical equipment for measurement,control, and laboratory use — Part 1: General requirements, 2001 2010 .

IEC 61310-1 Ed. 2.0 , Safety of machinery — indication, mark ing and actuation — Part1: Requirements for visual, auditory and tactile signals, 1995 2007 .

IEC 61310-3 Ed. 2.0 , Safety of machinery — indication, mark ing and actuation — Part3: Requirements for the location and operation of actuators, 1999 2007 .

IEC 61508 Ed. 2.0 , [Series] Functional safety of electrical/electronic/programmableelectronic safety-related systems, 1998–2000 2010 .

IEC 61558-1 Ed. 2.1 , Safety of power transformers, power supply units and similar —Part 1: General requirements and tests, 1998–2007 2009 .

IEC 61800-5-2 Ed. 1.0 , Adjustable speed electrical power drive systems — Part 5-2:Safety Requirements — Functional,2006 2007 .

IEC 62061 Ed. 1.1 , Safety of machinery — Functional safety of electrical, electronic andprogrammable control systems, 2005 2012 .

NOTE: The IEC publishes consolidated editions of its publications with all theamendments and corrigenda included with the base document. For example:

Edition 1.0 is a base document without any amendments.

Edition 1.1 is the base 1.0 edition consolidated with one amendment.

8/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 63/64

Edition 1.2 is the base 1.0 edition consolidated with two amendments.

Edition 2.0 is the second edition of a base document. This may include new informationcombined as well as amendments from edition 1.x.

Edition 2.1 is the second edition of a document consolidated with amendment 1 to thatedition.

Supplemental Information

File Name Description

Annex_K_1_2_3.docx referenced document revision dates

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 09 16:20:51 EDT 2013

Committee Statement

CommitteeStatement:

Updates to reflect current revisions that were omitted in PI66, FR-30. Although IEC60621-3 and IEC 60742 have been withdrawn by the IEC, references have beenretained to correlate with existing annex notes. Attached is the file with the correctIEC publication information to be loaded into Annex K.

ResponseMessage:

Public Comment No. 39-NFPA 79-2013 [Section No. K.1.2.3]

K.1.2.3 IEC Publications. International Electrotechnical Commission, 3, rue de Varembé, P.O. Box 131, CH-1211 Geneva 20, Switzerland.

IEC 60034-1 Ed. 12.0, Rotating electrical machines — Part 1: Rating and performance, 1999–20081999–2010.

IEC 60072-1 Ed. 6.0, Dimensions and output series for rotating electrical machines — Part 1: Frame numbers 56 to 400 and flange numbers 55 to 1080, 1991–2003.

IEC 60204-1, Ed. 45.1, Safety of machinery — Electrical equipment of machines — Part 1: General requirements, 2000–20052000–2009.

IEC 60332-1 Ed.1.0 [Series], Tests on electric cables under fire conditions — Part 1: Test on a single vertical insulated wire or cable, 1993–2004.

IEC 60364-4-141 Ed. 5.0, Electrical installations of buildings — Part 4-41: Protection for safety — Protection against electric shock, 2001–20082001–2005.

IEC 60364-5-53 Ed. 3.1, Electrical Installations of Buildings — Part 5-53: Selection and Erection of Electrical Equipment — Isolation, Switching and Control, 2002–2006.

IEC 60417-

1

DB [Database], Graphical symbols for use on equipment

— Part 1: Overview and application, 2000–2005 , 2002.

IEC

60417-2, Graphical symbols for use on equipment — Part 2: Symbol originals, 1998–2008. IEC 60529, Ed. 2.1, Degrees of protection provided by enclosures (IP Code), 2001–20022001–2009.

IEC 60621-3 Ed. 1.0, Electrical installations for outdoor sites under heavy conditions (including open-cast mines and quarries). Part 3: General requirements for equipment and ancillaries, 1979–2001.

IEC 60742, Ed. 1.0, Isolating transformers and safety isolating transformers, 1983.

IEC 60870-5-1 Ed. 1.0, Telecontrol equipment and systems. Part 5: Transmission protocols — Section One: Transmission frame formats, 1990–2002.

IEC 60947-4-1 Ed. 3.1, Low-voltage switchgear and controlgear — Part 4-1: Contactors and motor-starters— Electromechanical contactors and motor-starters, 2000–20112012.

IEC 60947-5-1 Ed. 3.1, Low-voltage switchgear and controlgear — Part 5-1: Control circuit devices and switching elements — Electromechanical control circuit devices, 2000–20032009.

Formatted: Left: 0.81"

Formatted: Font: Italic

Formatted: Space After: 6 pt

Formatted: Font: Italic

Formatted: Space After: 6 pt

IEC 60947-7-1 Ed. 3.0, Low-voltage switchgear and controlgear — Part 7: Ancillary equipment — Section 1: Terminal blocks for copper conductors, 1999–20082009.

IEC 61010-1 Ed. 3.0, Safety requirements for electrical equipment for measurement, control, and laboratory use — Part 1: General requirements, 20012010.

IEC 61310-1 Ed. 2.0, Safety of machinery — indication, marking and actuation — Part 1: Requirements for visual, auditory and tactile signals, 19952007.

IEC 61310-3 Ed. 2.0, Safety of machinery — indication, marking and actuation — Part 3: Requirements for the location and operation of actuators, 19992007.

IEC 61508 Ed. 2.0, [Series] Functional safety of electrical/electronic/programmable electronic safety-related systems, 1998–20002010.

IEC 61558-1 Ed, 2.1, Safety of power transformers, power supply units and similar — Part 1: General requirements and tests, 1998–20072009.

IEC 61800-5-2 Ed. 1.0, Adjustable speed electrical power drive systems — Part 5-2: Safety Requirements — Functional, 20062007.

IEC 62061, Ed 1.1, Safety of machinery — Functional safety of electrical, electronic and programmable control systems, 20052012.

NOTE: The IEC publishes consolidated editions of its publications with all the amendments and corrigenda included with the base document. For example:

Edition 1.0 is a base document without any amendments.

Edition 1.1 is the base 1.0 edition consolidated with one amendment.

Edition 1.2 is the base 1.0 edition consolidated with two amendments.

Edition 2.0 is the second edition of a base document. This may include new information combined as well as amendments from edition 1.x.

Edition 2.1 is the second edition of a document consolidated with amendment 1 to that edition.

8/27/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 64/64

Second Revision No. 21-NFPA 79-2013 [ Section No. K.1.2.5 ]

K.1.2.5 ISO Publications.

International Organization for Standardization, 1, ch. de la Voie-Creuse, Case postale 56,CH-1211 Geneva 20, Switzerland.

ISO 7000, Graphical symbols for use on equipment — Index and synopsis, 1989 2012 .

ISO 12100, Safety of machinery — Basic concepts, general principles for design — Part1: Basic terminology, methodology, 2003 2010 .

ISO 13849-1, Safety of machinery — Safety-related parts of control systems — Part 1:General principles for design, 1990 2006 .

ISO 13849-2, Safety of machinery — Safety-related parts of control systems — Part 2:Validation, 2003 2012 .

ISO 13850, Safety of machinery — Emergency stop — Principles for design, 1996 2006 .

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jul 10 08:31:04 EDT 2013

Committee Statement

CommitteeStatement:

Reference dates for ISO publications were revised to reflect latest revisionsneeded for proper application.

ResponseMessage:

Public Comment No. 37-NFPA 79-2013 [Section No. K.1.2.5]