section 260501 basic electrical materials and … 26(33).pdfupdated 12/15/2010 printed 03/19/2014...

31
Updated 12/15/2010 Printed 03/19/2014 260501 - 1 Project No. Q1559-E SECTION 260501 BASIC ELECTRICAL MATERIALS AND METHODS PART 1 GENERAL 1.01 SUBMITTALS A. Product Data: Catalog sheets, specifications and installation instructions. 1. For fire rated construction, prove that materials and installation methods proposed for use are in accordance with the listing requirements of the classified construction. PART 2 PRODUCTS 2.01 RACEWAYS, FITTINGS AND ACCESSORIES A. Rigid Ferrous Metal Conduit: Steel, hot dipped galvanized on the outside and inside, UL categorized as Rigid Ferrous Metal Conduit (identified on UL Listing Mark as Rigid Metal Conduit - Steel or Rigid Steel Conduit), by Allied Tube & Conduit Corp., LTV Copperweld, or Wheatland Tube Co. B. Electrical Metallic Tubing: Steel, galvanized on the outside and enameled on the inside, UL categorized as Electrical Metallic Tubing (identified on UL Listing Mark as Electrical Metallic Tubing), by Allied Tube & Conduit Corp., LTV Copperweld, or Wheatland Tube Co. C. Liquid-tight Flexible Metal Conduit: UL categorized as liquid-tight flexible metal conduit (identified on UL Listing Mark as Liquid-Tight Flexible Metal Conduit, also specifically marked with temperature and environment application data), by AFC Cable Systems Inc., Anamet Electrical Inc., Electri-Flex Co., or Universal Metal Hose Co. D. Insulated Bushings, Plastic Bushings, and Insulated Grounding Bushings: By Appleton Electric Co., Cooper/Crouse-Hinds, OZ/Gedney Co., or Thomas & Betts Corp. E. Connectors and Couplings: 1. Locknuts: UL, steel/zinc electroplate; Appleton Electric Co.’s BL-50 Series, Cooper/Crouse-Hinds’ 11 Series, OZ/Gedney Co.’s 1-50S Series, Raco Inc.’s 1002 Series, Steel City/T&B Corp.’s LN-101 Series, or Thomas & Betts Corp.’s 141 Series. 2. Couplings (For Rigid Metal and IMC Conduit): Standard galvanized threaded couplings as furnished by conduit manufacturer, Allied Tube & Conduit Corp.’s Kwik-Couple, or Thomas & Betts Corp.’s Shamrock. 3. Three Piece Conduit Coupling (For Rigid Metal and IMC Conduit): Steel, malleable iron, zinc electroplate; Allied Tube & Conduit Corp.’s Kwik-Couple, Appleton Electric Co.’s EC-50 Series, Cooper/Crouse- Hinds’ 190M Series, OZ/Gedney Co.’s 4-50 Series, Raco Inc.’s 1502

Upload: others

Post on 21-Apr-2020

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: SECTION 260501 BASIC ELECTRICAL MATERIALS AND … 26(33).pdfUpdated 12/15/2010 Printed 03/19/2014 260501 - 1 Project No. Q1559-E SECTION 260501 BASIC ELECTRICAL MATERIALS AND METHODS

Updated 12/15/2010

Printed 03/19/2014 260501 - 1 Project No. Q1559-E

SECTION 260501

BASIC ELECTRICAL MATERIALS AND METHODS PART 1 GENERAL 1.01 SUBMITTALS A. Product Data: Catalog sheets, specifications and installation instructions. 1. For fire rated construction, prove that materials and installation methods

proposed for use are in accordance with the listing requirements of the classified construction.

PART 2 PRODUCTS 2.01 RACEWAYS, FITTINGS AND ACCESSORIES A. Rigid Ferrous Metal Conduit: Steel, hot dipped galvanized on the outside and

inside, UL categorized as Rigid Ferrous Metal Conduit (identified on UL Listing Mark as Rigid Metal Conduit - Steel or Rigid Steel Conduit), by Allied Tube & Conduit Corp., LTV Copperweld, or Wheatland Tube Co.

B. Electrical Metallic Tubing: Steel, galvanized on the outside and enameled on the

inside, UL categorized as Electrical Metallic Tubing (identified on UL Listing Mark as Electrical Metallic Tubing), by Allied Tube & Conduit Corp., LTV Copperweld, or Wheatland Tube Co.

C. Liquid-tight Flexible Metal Conduit: UL categorized as liquid-tight flexible

metal conduit (identified on UL Listing Mark as Liquid-Tight Flexible Metal Conduit, also specifically marked with temperature and environment application data), by AFC Cable Systems Inc., Anamet Electrical Inc., Electri-Flex Co., or Universal Metal Hose Co.

D. Insulated Bushings, Plastic Bushings, and Insulated Grounding Bushings: By

Appleton Electric Co., Cooper/Crouse-Hinds, OZ/Gedney Co., or Thomas & Betts Corp.

E. Connectors and Couplings: 1. Locknuts: UL, steel/zinc electroplate; Appleton Electric Co.’s BL-50

Series, Cooper/Crouse-Hinds’ 11 Series, OZ/Gedney Co.’s 1-50S Series, Raco Inc.’s 1002 Series, Steel City/T&B Corp.’s LN-101 Series, or Thomas & Betts Corp.’s 141 Series.

2. Couplings (For Rigid Metal and IMC Conduit): Standard galvanized threaded couplings as furnished by conduit manufacturer, Allied Tube & Conduit Corp.’s Kwik-Couple, or Thomas & Betts Corp.’s Shamrock.

3. Three Piece Conduit Coupling (For Rigid Metal and IMC Conduit): Steel, malleable iron, zinc electroplate; Allied Tube & Conduit Corp.’s Kwik-Couple, Appleton Electric Co.’s EC-50 Series, Cooper/Crouse-Hinds’ 190M Series, OZ/Gedney Co.’s 4-50 Series, Raco Inc.’s 1502

Page 2: SECTION 260501 BASIC ELECTRICAL MATERIALS AND … 26(33).pdfUpdated 12/15/2010 Printed 03/19/2014 260501 - 1 Project No. Q1559-E SECTION 260501 BASIC ELECTRICAL MATERIALS AND METHODS

Updated 12/15/2010

Printed 03/19/2014 260501 - 2 Project No. Q1559-E

Series, Steel City/T & B Corp.’s EK-401 Series, or Thomas & Betts Corp.’s 675 Series.

4. Electrical Metallic Tubing Couplings and Insulated Connectors: Compression type, steel/zinc electroplate; Appleton Electric Co.’s TW-50CS1, TWC-50CS Series, Cooper/Crouse-Hinds’ 1650, 660S Series, Raco Inc.’s 2912, 2922 Series, Steel City/T & B Corp.’s TC-711 Series, or Thomas & Betts Corp.’s 5120, 5123 Series.

5. Liquid-tight Flexible Metal Conduit Connectors: a. Dry, Damp Locations: Steel, malleable iron, zinc electroplate,

insulated throat; Appleton Electric Co.’s STB Series, Cooper/Crouse-Hinds’ LTB Series, OZ/Gedney Co.’s 4Q-50T Series, Raco Inc.’s 3512 Series, Steel City/T & B Corp.’s LT-701 Series, or Thomas & Betts Corp.’s 5332 Series.

b. Wet Locations: OZ/Gedney Co.’s 4Q-TG Series (hot-dip/mechanically galvanized), or Thomas & Betts Corp.’s 3322 Series (PVC coated).

F. Conduit Bodies (Threaded): 1. Dry, Damp Locations: Zinc electroplate malleable iron or cast iron alloy

bodies with zinc electroplate steel covers; Appleton Electric Co.’s Unilets, Cooper/Crouse-Hinds’ Condulets, OZ/Gedney Co.’s Conduit Bodies, or Thomas & Betts Corp.’s Conduit Bodies.

2. Wet Locations: Malleable iron or cast iron alloy bodies and covers with hot dipped galvanized or other specified corrosion resistant finish; Cooper/Crouse-Hinds’ Condulets (Corro-free epoxy powder coat), Thomas & Betts Corp.’s Conduit Bodies (hot dipped galvanized), or OZ/Gedney Co.’s Conduit Bodies (hot dipped galvanized). Stainless steel cover screws, covers gasketed to suit application.

G. Expansion Fittings: 1. Dry, Damp Locations: a. Malleable iron, zinc electroplate finish: Appleton Electric Co.’s

XJ or OZ/Gedney Co.’s AX (TX for EMT), with external bonding jumper.

b. Electrogalvanized Steel: Cooper/Crouse-Hinds’ XJG (XJG-EMT for EMT), or Thomas & Betts Corp.’s XJG, with internal grounding.

2. Wet Locations: Cooper/Crouse-Hinds XJG (Corro-free epoxy powder coat), OZ Gedney Co.’s AX, EXE (end type, hot dipped galvanized), or Thomas & Betts Corp.’s XJG (hot dipped galvanized).

H. Deflection Fittings: 1. Dry, Damp Locations: Appleton Electric Co.’s DF, Cooper/Crouse-

Hinds’ XD, or OZ/Gedney Co.’s Type DX. 2. Wet Locations: Ductile iron couplings with hot dipped galvanized

finish, neoprene sleeve, and stainless steel bands, Appleton Electric Co.’s CF; or bronze couplings, neoprene sleeve, and stainless steel bands, OZ/Gedney Co.’s Type DX.

I. Sealant for Raceways Exposed to Different Temperatures: Sealing compounds

and accessories to suit installation; Appleton Electric Co.’s DUC, or Kwiko

Page 3: SECTION 260501 BASIC ELECTRICAL MATERIALS AND … 26(33).pdfUpdated 12/15/2010 Printed 03/19/2014 260501 - 1 Project No. Q1559-E SECTION 260501 BASIC ELECTRICAL MATERIALS AND METHODS

Updated 12/15/2010

Printed 03/19/2014 260501 - 3 Project No. Q1559-E

Sealing Compound with fiber filler, Cooper/Crouse-Hinds’ Chico A Sealing Compound with Chico X fiber, Electrical Products Division 3M Scotch products, OZ Gedney Co.’s DUX or EYC sealing compound with EYF damming fiber, or Thomas & Betts Corp.’s Blackburn DX.

2.02 OUTLET, JUNCTION, AND PULL BOXES A. Galvanized Steel Outlet Boxes: Standard galvanized steel boxes and device

covers by Appleton Electric Co., Beck Mfg./Picoma Industries, Cooper/Crouse-Hinds, Raco/Div. of Hubbell , or Steel City/T & B Corp.

B. Galvanized Steel Junction and Pull Boxes: Code gage, galvanized steel screw

cover boxes by Delta Metal Products Inc., Hoffman Enclosures Inc., Hubbell Wiegmann, Lee Products Co., or Rittal/Electromate.

2.03 CONDUCTORS AND ACCESSORIES A. Date of Manufacture: No insulated conductor more than one year old when

delivered to the site will be acceptable. B. Acceptable Companies: American Insulated Wire Corp., BICC General Cable

Industries Inc., Cerro Wire & Cable Co. Inc., Pirelli Cable Corp., Rome Cable Corp., or Southwire Co..

C. Conductors: Annealed uncoated copper or annealed coated copper in

conformance with the applicable standards for the type of insulation to be applied on the conductor. Conductor sizes No. 8 and larger shall be stranded.

D. Types: 1. Electric Light and Power Wiring: a. General: Rated 600V, NFPA 70 Type FEP, THHN, THW,

THW-2, THWN, THWN-2, XHH, XHHW, XHHW-2. E. Connectors: 1. General: Connectors specified are part of a system. Furnish connectors

and components, and use specific tools and methods as recommended by connector manufacturer to form complete connector system.

2. Splices: a. Spring Type: 1) Rated 105° C, 600V; Buchanan/Ideal Industries Inc.’s B-

Cap, Electrical Products Div./3M’s Scotchlok Type Y, R, G, B, O/B+, R/Y+, or B/G+, or Ideal Industries Inc.’s Wing Nuts or Wire Nuts.

2) Rated 150° C, 600V; Ideal Industries Inc.’s High Temperature Wire-Nut Model 73B, 59B.

b. Indent Type with Insulating Jacket: 1) Rated 105° C, 600V; Buchanan/Ideal Industries Inc.’s

Crimp Connectors, Ideal Industries Inc.’s Crimp

Page 4: SECTION 260501 BASIC ELECTRICAL MATERIALS AND … 26(33).pdfUpdated 12/15/2010 Printed 03/19/2014 260501 - 1 Project No. Q1559-E SECTION 260501 BASIC ELECTRICAL MATERIALS AND METHODS

Updated 12/15/2010

Printed 03/19/2014 260501 - 4 Project No. Q1559-E

Connectors, Penn-Union Corp.’s Penn-Crimps, or Thomas & Betts Corp.’s STA-KON.

c. Indent Type (Uninsulated): Anderson/Hubbell’s Versa-Crimp, VERSAtile, Blackburn/T&B Corp.’s Color-Coded Compression Connectors, Electrical Products Div./3M’s Scotchlok 10000, 11000 Series, Framatome Connectors/Burndy’s Hydent, Penn-Union Corp.’s BCU, BBCU Series, or Thomas & Betts Corp.’s Compression Connectors.

d. Connector Blocks: NIS Industires Inc.’s Polaris System, or Thomas & Betts Corp.’s Blackburn AMT Series.

e. Resin Splice Kits: Electrical Products Div./3M’s Scotchcast Brand Kit Nos. 82A Series, 82-B1 or 90-B1, or Scotchcast Brand Resin Pressure Splicing Method.

f. Heat Shrinkable Splices: Electrical Products Div./3M’s ITCSN, Raychem Corp.’s Thermofit Type WCS, or Thomas & Betts Corp.’s SHRINK-KON Insulators.

g. Cold Shrink Splices: Electrical Products Div./3M’s 8420 Series. F. Tapes: 1. Insulation Tapes: a. Plastic Tape: Electrical Products Div./3M’s Scotch Super 33+ or

Scotch 88, Plymouth Rubber Co.’s Plymouth/ Bishop Premium 85CW.

b. Rubber Tape: Electrical Products Div./3M’s Scotch 130C, or Plymouth Rubber Co.’s Plymouth/Bishop W963 Plysafe.

2. Moisture Sealing Tape: Electrical Products Div./3M’s Scotch 2200 or 2210, or Plymouth Rubber Co.’s Plymouth/Bishop 4000 Plyseal-V.

3. Electrical Filler Tape: Electrical Products Div./3M’s Scotchfil, or Plymouth Rubber Co.’s Plymouth/Bishop 125 Electrical Filler Tape.

4. Color Coding Tape: Electrical Products Div./3M’s Scotch 35, or Plymouth Rubber Co.’s Plymouth/Bishop Premium 37 Color Coding.

G. Wire-Pulling Compounds: To suit type of insulation; American Polywater

Corp.’s Polywater Series, Electric Products Div./3M’s WL, WLX, or WLW, Greenlee Textron Inc.’s Y-ER-EAS, Cable Cream, Cable Gel, Winter Gel, Ideal Industries Inc.’s Yellow 77, Aqua-Gel II, Agua-Gel CW, or Thomas & Betts Corp.’s Series 15-230 Cable Pulling Lubricants, or Series 15-631 Wire Slick.

2.04 SUPPORTING DEVICES A. Fasteners: Furnish all fasteners and hardware compatible with the materials and

methods required for attachment of supporting devices. 1. Nuts, Bolts, Screws, Washers: a. General: Furnish zinc-coated fasteners, with galvanizing

complying with ASTM A 153 for exterior use or where built into exterior walls. Furnish fasteners for the type, grade and class required for the particular installation.

Page 5: SECTION 260501 BASIC ELECTRICAL MATERIALS AND … 26(33).pdfUpdated 12/15/2010 Printed 03/19/2014 260501 - 1 Project No. Q1559-E SECTION 260501 BASIC ELECTRICAL MATERIALS AND METHODS

Updated 12/15/2010

Printed 03/19/2014 260501 - 5 Project No. Q1559-E

b. Standard Nuts and Bolts: Regular hexagon head type, complying with ASTM A 307, Grade A.

c. Lag Bolts: Square head type, complying with FS FF-B-561C. d. Machine Screws: Cadmium plated steel, complying with FS FF-

S-92. e. Wood Screws: Flat head carbon steel, complying with FS FF-S-

111. f. Plain Washers: Round, general assembly grade carbon steel,

complying with FS FF-W-92. g. Lock Washers: Helical spring type carbon steel, complying with

FS FF-W-84. B. “C” Beam Clamps: 1. For 1 inch Conduit Maximum: B-Line Systems Inc.’s BG-8-C2, BP-8-

C1 Series, or Caddy Fastener Div./Erico Products Inc.’s BC-8P and BC-8PSM Series.

2. For 3 inch Conduit Maximum: Appleton Electric Co.’s BH-500 Series beam clamp with H50WB Series hangers, Kindorf/T&B Corp.’s 500 Series beam clamp with 6HO-B Series hanger, or OZ/Gedney Co.’s IS-500 Series beam clamp with H-OWBS Series hanger.

3. For 4 inch Conduit Maximum: Kindorf/T&B Corp.’s E-231 beam clamp and E-234 anchor clip and C-149 series lay-in hanger, or Unistrut Corp.’s P2676 beam clamp and P-1659A Series anchor clip with J1205 Series lay in hanger.

4. For Threaded Rods (100 lbs. load max.): Caddy Fastener Div./Erico Products Inc.’s BC-4A.

5. For Threaded Rods (200 lbs. load max.): Appleton Electric Co.’s BH-500 Series, Kindorf/T&B Corp.’s 500 Series, or OZ/Gedney Co.’s IS-500 Series.

6. For Threaded Rods (300 lbs. load max.): Kindorf/T&B Corp.’s E-231 beam clamp and E-234 anchor clip, or Unistrut Corp.’s P2676 beam clamp and P-1659A Series anchor clip.

C. Fastener Fittings for Wood and Existing Masonry: Kindorf/T&B Corp.’s E-243,

E-244, E-245, E-170, or Versabar Corp.’s VX-4310, VX-2308, VX-4308, VX-4309.

D. Channel Support System and Accessories: 12 gage galvanized steel channel and

accessories; B-Line System Inc.’s B-22 (1-5/8 x 1-5/8 inches), B-12 (1-5/8 x 2-7/16 inches), B-11 (1-5/8 x 3-1/4 inches), Kindorf/T&B Corp.’s B-900 (1-1/2 x 1-1/2 inches), B-901 (1-1/2 x 1-7/8 inches), B-902 (1-1/2 x 3 inches), Unistrut Corp.’s, P-3000 (1-3/8 x 1-5/8 inches), P-5500 (1-5/8 x 2-7/16 inches), P-5500 (1-5/8 x 3-1/4 inches), or Versabar Corp.’s VA-1 (1-5/8 x 1-5/8 inches), VA-3 (1-5/8 x 2-1/2 inches).

E. Supporting Fasteners (Metal Stud Construction): Metal stud supports, clips and

accessories as produced by Caddy/Erico Products Inc. 2.05 NAMEPLATES AND TAGS

Page 6: SECTION 260501 BASIC ELECTRICAL MATERIALS AND … 26(33).pdfUpdated 12/15/2010 Printed 03/19/2014 260501 - 1 Project No. Q1559-E SECTION 260501 BASIC ELECTRICAL MATERIALS AND METHODS

Updated 12/15/2010

Printed 03/19/2014 260501 - 6 Project No. Q1559-E

A. General: Precision engraved letters and numbers with uniform margins, character size minimum 3/16 inch high.

1. Phenolic: Two color laminated engraver’s stock, 1/16 inch minimum thickness, machine engraved to expose inner core color (white).

2. Aluminum: Standard aluminum alloy plate stock, minimum .032 inches thick, engraved areas enamel filled or background enameled with natural aluminum engraved characters.

3. Materials for Outdoor Applications: As recommended by nameplate manufacturer to suit environmental conditions.

2.06 CONCRETE WORK (FOOTINGS)

A. Concrete: Minimum Strength: 3000 psi @ 28 days Aggregate: ASTM C33, Size 57 Cement: 588 #/cu. yd. minimum, ASTM C150 Type I or II Slump: 4" maximum (Prior to addition of superplasticizers) Air: 5% - 7%

B. Anchor Bolts: ASTM F1554 Grade 36

C. Forms: 1-Time-use, round concrete form, sizes as required for bollard and pedestal

footings as shown on plans. Cut forms on site to meet depths shown on plans. Basis of Design Product: Subject to compliance with requirements, provide:

Sonotube Round Concrete Forms or equal Comply with manufacturer’s recommendations for form and concrete placement.

2.07 TEMPORARY LIGHTING

A. Lighting Requirements: 1. Provide both interior and exterior lighting as required to provide adequate

illumination for safe and proper construction operations and Project site security.

2. Provide a minimum of one 200 watt lamp per 500 square feet of building floor area, with maximum spacing of 20 feet on center.

3. Provide one 200 watt lamp per landing at each stairway. 4. Provide adequate lighting for personnel safety at barricades, ladders,

openings and other similar locations. 5. Provide adequate lighting for personnel safety at barricades, ladders,

openings and other similar locations. 6. All lighting branch circuits to be loaded to a maximum of 1500 watts per 20

amp circuit. Lighting branch circuits shall be independent of temporary receptacle circuits.

7. In lieu of providing a temporary lighting system, existing lighting fixtures may be used until the time of removal or replacement. Use shall not affect the project schedule or phasing. Any new lighting fixtures damaged by construction use shall be replaced without additional cost to the Contract or Director’s Representative.

8. Do not use any portion of the new permanent lighting systems for temporary construction lighting purposes.

9. Lamp holders and lighting fixtures shall be medium base pigtail type lampholders with approved lamp guard protectors. Provide weatherproof light fixtures where exposed to moisture.

Page 7: SECTION 260501 BASIC ELECTRICAL MATERIALS AND … 26(33).pdfUpdated 12/15/2010 Printed 03/19/2014 260501 - 1 Project No. Q1559-E SECTION 260501 BASIC ELECTRICAL MATERIALS AND METHODS

Updated 12/15/2010

Printed 03/19/2014 260501 - 7 Project No. Q1559-E

10. Do not suspend temporary lights by their electric cords unless cords and lights are specifically designed for that purpose.

B. Conductors: Insulated copper, with conductor insulation rated for applied voltage,

and insulation and jacketing suitable for the conditions of use. Branch circuit conductors to be minimum size #12 AWG, and #10 AWG for circuits longer than 100 feet unless otherwise required.

C. Conduit and Raceway: Types as required and permitted by code.

2.08 LIGHTING FIXTURES

A. General: 1. See lighting fixture schedule on drawings for basis of design manufacturer.

Provide basis of design or engineer approved equal. 2. Fixture types as described below or on project Drawings indicate the Basis

of Design. 3. Substitute lighting fixtures will be reviewed for equivalency, however, the

Contractor accepts responsibility to provide complete data and photometric layout with the submittal.

4. Lighting fixture manufacturers’ series or catalog numbers listed indicate general quality, type, and style, but may not cover all required design features and details. Provide lighting fixtures having all features, details and accessories as noted in the fixture descriptions. Provide all fittings, hangers, clamps, brackets, yokes, flanges and miscellaneous devices required for a complete installation.

5. Provide lighting fixtures with ballasts, drivers, etc. integral to fixture and prewired.

B. LED Lighting Fixtures: 1. Source Requirements: CRI 80 (minimum), color temperature 4000 K,

average rated life of 50,000 hours. 2. Rated for ambient operating temperatures from -20°C to 40°C. 3. Correlated Color Temperature (CCT) to be nominal 4000 K. 4. Color Rendering Index (CRI) to be 88 at 4000 K. 5. Driver (power supply) shall be rated for the available voltage and frequency,

Power Factor (PF) 0.90 minimum, Total Harmonic Distortion (THD) less than 20%, and comply with FCC 47 CFR part 15.

6. UL Listed for the application. 7. The useful life shall be a minimum of 50,000 hours and meet the L70

standard for output degradation. PART 3 EXECUTION 3.01 RACEWAY INSTALLATION A. Number of Raceways: Do not change number of raceways to less than the

number indicated on the drawings. 1. Each raceway shall enclose one circuit unless otherwise indicated on the

drawings.

Page 8: SECTION 260501 BASIC ELECTRICAL MATERIALS AND … 26(33).pdfUpdated 12/15/2010 Printed 03/19/2014 260501 - 1 Project No. Q1559-E SECTION 260501 BASIC ELECTRICAL MATERIALS AND METHODS

Updated 12/15/2010

Printed 03/19/2014 260501 - 8 Project No. Q1559-E

B. Number of Raceways: Do not change number of raceways to less than the

number indicated on the drawings except when appropriate for advantageous reuse of existing exposed and concealed raceways (The contract documents do not indicate location, number, size or condition of existing raceways). Existing raceways may be reused if the following conditions are met:

1. The existing raceway must be of adequate size for the new conductors to be installed therein (NFPA 70 Chapter 9, Tables 1, 4, & 5; Appendix C, Tables C1-C12a). More circuits may be enclosed by existing raceways than the circuiting shown on the drawings provided conductor sizes are increased to compensate for derating (adjustment factors) and other considerations required by NFPA 70 Article 310-15.

2. Remove existing conductors. 3. Demonstrate to the Director’s Representative that the existing raceway is

clear of obstructions and in good condition. 4. Check ground continuity. When ground continuity of existing raceway

is inadequate install insulated grounding bushings, grounding wedges, bonding straps, grounding jumpers or equipment grounding conductors to establish effective path to ground.

5. Install insulated bushings to replace damaged or missing bushings. Replace non-insulated bushings with insulated bushings on raceway sizes 1 inch and larger.

6. Install vertical conductor supports to replace existing or missing vertical conductor supports.

7. Install extension rings on existing boxes when the number of new conductors installed therein exceeds NFPA 70 requirements.

8. Furnish the Director’s Representative with marked up drawings showing size and routing of existing raceways with number and size of new conductors installed therein. The drawings will be forwarded to the design engineer for verification of NFPA 70 compliance.

C. Conduit Installed Concealed: 1. Install conduit concealed unless otherwise indicated on the drawings. 2. Existing Construction: a. Run conduit in existing chases and hung ceilings. b. If conduit cannot be installed concealed due to conditions

encountered in the building, report such conditions and await approval in writing before proceeding.

D. Conduit Installed Exposed: 1. Install conduit exposed where indicated on the drawings. If not

indicated, conduit may be installed exposed, as approved, in: a. Unfinished spaces, and finished spaces housing mechanical or

electrical equipment that is generally accessible only to facility maintenance personnel.

b. Areas where existing conduits have been installed exposed. c. Areas where conduit cannot be installed concealed. 2. Install conduit tight to the surface of the building construction.

Exception:

Page 9: SECTION 260501 BASIC ELECTRICAL MATERIALS AND … 26(33).pdfUpdated 12/15/2010 Printed 03/19/2014 260501 - 1 Project No. Q1559-E SECTION 260501 BASIC ELECTRICAL MATERIALS AND METHODS

Updated 12/15/2010

Printed 03/19/2014 260501 - 9 Project No. Q1559-E

a. Where otherwise indicated or directed. 3. Install vertical runs perpendicular to the floor. 4. Install runs on the ceiling perpendicular or parallel to the walls. 5. Install horizontal runs parallel to the floor. 6. Do not run conduits near heating pipes. 7. Installation of conduit directly on the floor will not be permitted. E. Conduit Size: Not smaller than 3/4 inch electrical trade size. Where type FEP,

THHN, THWN, THWN-2, XHH, XHHW, or XHHW-2 conductors are specified for use, the minimum allowable conduit size for new Work shall be based on Type THW conductors.

F. Raceways Exposed to Different Temperatures: Where portions of an interior

raceway system are exposed to widely different temperatures, seal interior and exterior of raceway to prevent circulation of air from a warmer to a colder section through the raceway installation.

1. Heated Areas to Unheated Areas: After conductors are installed, seal

interior of the raceway at the nearest conduit body, outlet or junction box in the heated area adjoining the unheated area.

G. Raceway Schedule: 1. Rigid Ferrous Metal Conduit: Install in all locations unless otherwise

specified or indicated on the drawings. 2. Electrical Metallic Tubing: a. May be installed concealed as branch circuit conduits above

suspended ceilings where conduit does not support fixtures or other equipment.

b. May be installed concealed as branch circuit conduits in hollow areas in dry locations, including:

1) Hollow concrete masonry units, except where cores are to be filled.

2) Drywall construction with sheet metal studs, except where studs are less than 3-1/2 inches deep.

c. May be installed exposed as branch circuit conduits in dry non-hazardous locations at elevations over 10’-0” above finished floor where conduit does not support fixtures or other equipment.

3. Liquid-tight Flexible Metal Conduit: Install equipment grounding

conductor in liquid-tight flexible metal conduit and bond at each box or equipment to which conduit is connected:

a. Use 1 to 3 feet of liquid-tight flexible metal conduit (UL listed and marked suitable for the installation’s temperature and environmental conditions) for final conduit connection to:

1) Motors with weather-protected or totally enclosed housings.

2) Equipment subject to vibration (damp and wet locations).

3) Equipment requiring flexible connection for adjustment or alignment (damp and wet locations).

Page 10: SECTION 260501 BASIC ELECTRICAL MATERIALS AND … 26(33).pdfUpdated 12/15/2010 Printed 03/19/2014 260501 - 1 Project No. Q1559-E SECTION 260501 BASIC ELECTRICAL MATERIALS AND METHODS

Updated 12/15/2010

Printed 03/19/2014 260501 - 10 Project No. Q1559-E

H. Fittings and Accessories Schedule: 1. General: a. Use fittings and accessories that have a temperature rating equal

to, or higher than the temperature rating of the conductors to be installed within the raceway.

b. Use zinc electroplate or hot dipped galvanized steel/malleable iron or cast iron alloy fittings and accessories in conjunction with ferrous raceways in dry and damp locations, unless otherwise specified or indicated on the drawings.

c. Use malleable iron or cast iron alloy fittings and accessories having hot dipped/mechanically galvanized finish or other specified corrosion resistant finish in conjunction with ferrous raceways in wet locations, unless otherwise specified or indicated on the drawings.

d. Use insulated grounding bushings or grounding wedges on ends of conduit for terminating and bonding equipment grounding conductors (when required) if cabinet or boxes are not equipped with grounding/bonding screws or lugs.

e. Use caps or plugs to seal ends of conduits until wiring is installed (to exclude foreign material).

f. Use insulated grounding bushings on the ends of conduits that are not directly connected to the enclosure (such as stub-ups under equipment, etc.), and bond between bushings and enclosure with equipment grounding conductor.

g. Use expansion fittings where raceways cross expansion joints. h. Use deflection fittings where raceways cross expansion joints

that move in more than one plane. i. Use 2 locknuts and an insulated bushing on end of each conduit

entering sheet metal cabinet or box in dry or damp locations. 1) Plastic bushing may be used in lieu of insulated bushing

on 1/2 and 3/4 inch conduit. 2) Terminate conduit ends within cabinet/box at the same

level. 2. For Rigid Metal Conduit: Use threaded fittings and accessories. Use 3

piece conduit coupling where neither piece of conduit can be rotated. 3. For Electrical Metallic Tubing: Use compression type connectors and

couplings. 4. For Wireways: Use wireway manufacturer’s standard fittings and

accessories. 3.02 OUTLET, JUNCTION AND PULLBOX INSTALLATION A. Mounting Position of Wall Outlets For Wiring Devices: Unless otherwise

indicated, install boxes so that the long axis of each wiring device will be vertical.

B. Height of Wall Outlets: Unless otherwise indicated, locate outlet boxes with

their center lines at the following elevations above finished floor:

Page 11: SECTION 260501 BASIC ELECTRICAL MATERIALS AND … 26(33).pdfUpdated 12/15/2010 Printed 03/19/2014 260501 - 1 Project No. Q1559-E SECTION 260501 BASIC ELECTRICAL MATERIALS AND METHODS

Updated 12/15/2010

Printed 03/19/2014 260501 - 11 Project No. Q1559-E

C. Supplementary Junction and Pull Boxes: In addition to junction and pull boxes

indicated on the drawings and required by NFPA 70, provide supplementary junction and pull boxes as follows:

1. When required to facilitate installation of wiring. 2. At every third 90 degree turn in conjunction with raceway sizes over 1

inch. 3. At intervals not exceeding 100 feet in conjunction with raceway sizes

over 1 inch. D. Box Schedule for Concealed Conduit System: 1. Non-Fire Rated Construction: a. Depth: To suit job conditions and comply with NFPA 70 Article

370. b. For Lighting Fixtures: Use galvanized steel outlet boxes

designed for the purpose. 1) For Fixtures Weighing 50 lbs. or Less: Box marked

“FOR FIXTURE SUPPORT”. 2) For Fixtures More Than 50 lbs: Box listed and marked

with the weight of the fixture to be supported (or support fixture independent of the box).

c. For Ceiling Suspended Fans: 1) For Fans Weighing 35 lbs or Less: Marked “Acceptable

for Fan Support.” 2) For Fans Weighing More Than 35 lbs, up to 70 lbs:

Marked “Acceptable for Fan Support up to 70 lbs (or support fan independent of the box).”

d. For Junction and Pull Boxes: Use galvanized steel boxes with flush covers.

e. For Switches, Receptacles, Etc: 1) Plaster or Cast-In-Place Concrete Walls: Use 4 inch or

4-11/16 inch galvanized steel boxes with device covers. 2) Walls Other Than Plaster or Cast-In-Place Concrete:

Use type of galvanized steel box which will allow wall plate to cover the opening made for the installation of the box.

2. Recessed Boxes in Fire Rated (2 hour maximum) Bearing and Nonbearing Wood or Steel Stud Walls (Gypsum Wallboard Facings):

a. Use listed single and double gang metallic outlet and switch boxes. The surface area of individual outlet or switch boxes shall not exceed 16 square inches.

b. The aggregate surface area of the boxes shall not exceed 100 square inches per 100 square feet of wall surface.

c. Securely fasten boxes to the studs. Verify that the opening in the wallboard facing is cut so that the clearance between the box and the wallboard does not exceed 1/8 inch.

d. Separate boxes located on opposite sides of walls or partitions by a minimum horizontal distance of 24 inches. This minimum separation distance may be reduced when wall opening protective materials are installed according to the requirements of their classification.

Page 12: SECTION 260501 BASIC ELECTRICAL MATERIALS AND … 26(33).pdfUpdated 12/15/2010 Printed 03/19/2014 260501 - 1 Project No. Q1559-E SECTION 260501 BASIC ELECTRICAL MATERIALS AND METHODS

Updated 12/15/2010

Printed 03/19/2014 260501 - 12 Project No. Q1559-E

e. Use wall opening protective material in conjunction with boxes installed on opposite sides of walls or partitions of staggered stud construction in accordance with the classification requirements for the protective material.

3. Other Fire Rated Construction: Use materials and methods to comply with the listing requirements for the classified construction.

E. Box Schedule for Exposed Conduit System: 1. Dry and Damp Locations: Use zinc electroplate or hot dipped

galvanized threaded type malleable iron or cast iron alloy outlet, junction, and pullboxes or conduit bodies provided with a volume marking in conjunction with ferrous raceways unless otherwise specified or indicated on the drawings.

a. Galvanized steel boxes may be used in conjunction with conduit sizes over 1 inch in non-hazardous dry and damp locations.

b. Galvanized steel boxes may be used in conjunction with electrical metallic tubing where it is allowed (specified) to be installed exposed as branch circuit conduits at elevations over 10’-0” above finished floor.

2. Wet Locations: Use threaded type malleable iron or cast iron alloy outlet junction, and pullboxes or conduit bodies (provided with a volume marking) with hot dipped galvanized or other specified corrosion resistant coating in conjunction with ferrous raceways unless otherwise specified or indicated on the drawings.

a. Use corrosion resistant boxes in conjunction with plastic coated rigid ferrous metal conduit.

3. Finishing Collar or Combination Finishing Collar/Outlet Box (Surface Mounted Equipment Used With Exposed Raceway):

a. Use finishing collar where surface mounted equipment is installed on an exposed raceway outlet box and the equipment base is larger than the outlet box.

b. Use combination finishing collar/outlet box where surface mounted equipment is not indicated to be installed on an exposed raceway outlet box, but raceway cannot be run directly into equipment body due to equipment design.

3.03 CONDUCTOR INSTALLATION A. Install conductors in raceways after the raceway system is completed. B. Do not change, group or combine circuits other than as indicated on the

drawings. C. Do not change, group or combine circuits other than as indicated on the drawings

except as permitted when reusing existing raceways. D. Conductor Size: Install conductors of size shown on drawings. Where size is not

indicated, the minimum size allowed is: 1. For Electric Light and Power Branch Circuits: No. 12 AWG. 2. For Class 1 Circuits:

Page 13: SECTION 260501 BASIC ELECTRICAL MATERIALS AND … 26(33).pdfUpdated 12/15/2010 Printed 03/19/2014 260501 - 1 Project No. Q1559-E SECTION 260501 BASIC ELECTRICAL MATERIALS AND METHODS

Updated 12/15/2010

Printed 03/19/2014 260501 - 13 Project No. Q1559-E

a. No. 18 and No. 16 AWG may be used provided they supply loads that do not exceed 6 amps (No. 18 AWG), or 8 amps (No. 16 AWG).

b. Larger than No. 16 AWG: Use to supply loads not greater than the ampacities given in NFPA 70 Section 310-15.

3. For Class 2 Circuits: Any size to suit application. 4. For Class 3 Circuits: No. 18 AWG. E. Color Coding: 1. Color Coding for 120/208 Volt Electric Light and Power Wiring: a. Color Code: 1) 2 wire circuit - black, white. 2) 3 wire circuit - black, red, white. 3) 4 wire circuit - black, red, blue, white. b. White to be used only for an insulated grounded conductor

(neutral). If neutral is not required use black and red, or black, red and blue for phase to phase circuits.

1) “White” for Sizes No. 6 AWG or Smaller: a) Continuous white outer finish, or: b) Three continuous white stripes on other than

green insulation along its continuous length. 2) “White” for Sizes Larger Than No. 6 AWG: a) Continuous white outer finish, or: b) Three continuous white stripes on other than

green insulation along its continuous length, or: c) Distinctive white markings (color coding tape)

encircling the conductor, installed on the conductor at time of its installation. Install white color coding tape at terminations, and at 1’ 0” intervals in gutters, pullboxes, and manholes.

c. Colors (Black, Red, Blue): 1) For Branch Circuits: Continuous color outer finish. 2) For Feeders: a) Continuous color outer finish, or: b) Color coding tapes encircling the conductors,

installed on the conductors at time of their installation. Install color coding tapes at terminations, and at 1’ 0” intervals in gutter, pullboxes, and manholes.

F. Identification: Use tags to identify feeders and designated circuits. Install tags

so that they are easily read without moving adjacent feeders or require removal of arc proofing tapes. Attach tags with non-ferrous wire or brass chain.

1. Interior Feeders: Identify each feeder in pullboxes and gutters. Identify by feeder number and size.

2. Exterior Feeders: Identify each feeder in manholes and in interior pullboxes and gutters. Identify by feeder number and size, and also indicate building number and panel designation from which feeder originates.

Page 14: SECTION 260501 BASIC ELECTRICAL MATERIALS AND … 26(33).pdfUpdated 12/15/2010 Printed 03/19/2014 260501 - 1 Project No. Q1559-E SECTION 260501 BASIC ELECTRICAL MATERIALS AND METHODS

Updated 12/15/2010

Printed 03/19/2014 260501 - 14 Project No. Q1559-E

3. Street and Grounds Lighting Circuits: Identify each circuit in manholes and lighting standard bases. Identify by circuit number and size, and also indicate building number and panel designation from which circuit originates.

G. Conductor Schedule - Types and Use: 1. Electric Light and Power Circuits: a. FEP, THHN, THW, THW-2, THWN, THWN-2, XHH, XHHW,

or XHHW-2: Wiring in dry or damp locations (except where special type insulation is required).

b. THWN, THWN-2, XHHW, XHHW-2, USE, or USE-2: Wiring in wet locations (except where type USE or USE-2 insulated conductors are specifically required, or special type insulation is required).

c. THHN, THWN or THWN-2: Wiring installed in existing raceway systems (except where special type insulation is required).

d. THHN, THW-2, THWN-2, XHHW, or XHHW-2: Wiring for electric discharge lighting circuits (fluorescent, HID), except where fixture listing requires wiring rated higher than 90° C.

e. THWN Marked “Gasoline and Oil Resistant”: Wiring to gasoline and fuel oil pumps.

f. USE, or USE-2: Wiring indicated on the drawings to be direct burial in earth.

g. USE, or USE-2 Marked “Sunlight Resistant”: 1) Service entrance wiring from overhead service to the

service equipment. 2) Wiring exposed to the weather and unprotected (except

where special type insulation is required). H. Connector Schedule - Types And Use: 1. Temperature Rating: Use connectors that have a temperature rating,

equal to, or greater than the temperature rating of the conductors to which they are connected

3.04 SUPPORTING DEVICE INSTALLATION A. Attachment of Conduit System: 1. Wood Construction: Attach conduit to wood construction by means of

pipe straps with wood screws or lag bolts. 2. Masonry Construction: Attach conduit to masonry construction by

means of pipe straps and masonry anchorage devices. 3. Steel Beams: Attach conduit to steel beams by means of “C” beam

clamps and hangers. 4. Multiple Parallel Conduit Runs: Use channel support system.

Page 15: SECTION 260501 BASIC ELECTRICAL MATERIALS AND … 26(33).pdfUpdated 12/15/2010 Printed 03/19/2014 260501 - 1 Project No. Q1559-E SECTION 260501 BASIC ELECTRICAL MATERIALS AND METHODS

Updated 12/15/2010

Printed 03/19/2014 260501 - 15 Project No. Q1559-E

5. Conduit Above Suspended Ceiling: Do not rest conduit directly on runner bars, T-bars, etc. Support conduit from ceiling supports or from construction above suspended ceiling.

B. Support of Lighting Fixtures: 1. General: Support fixtures with suitable accessories. 3.05 LIGHTING FIXTURES

A. General: Securely support and/or suspend all lighting fixtures from structural members, independently from any ceiling support system. Lay-in, flanged, and recessed downlight fixtures shall not be supported by the framing members of the suspended ceiling system.

B. Install lighting fixtures as described in the Lighting Fixture Schedule, complete with lamps and ballasts. Install all necessary accessory fittings, hangers, clamps, brackets, yokes, plaster flanges, outlet boxes, and miscellaneous devices required for a complete installation as recommended by the manufacturer.

C. Lamps and Ballasts: Install specified lamps as recommended by the lamp and

lighting fixture manufacturers. Follow lamp manufacturer’s recommendations for handling and installing lamps. Make all field connections necessary for factory installed ballasts and install all special ballasts as recommended by the manufacturer

D. Final Acceptance: Replace all burned out, defective and inoperative lamps, and all

noisy, defective and inoperative ballasts, starters, etc. prior to Owner’s acceptance.

END OF SECTION

Page 16: SECTION 260501 BASIC ELECTRICAL MATERIALS AND … 26(33).pdfUpdated 12/15/2010 Printed 03/19/2014 260501 - 1 Project No. Q1559-E SECTION 260501 BASIC ELECTRICAL MATERIALS AND METHODS

Updated 12/15/2010

Printed 03/19/2014 260543 - 1 Project No. Q1559-E

SECTION 260543

UNDERGROUND CONDUIT SYSTEM PART 1 GENERAL 1.01 SUBMITTALS A. Product Data: Catalog sheets, specifications and installation instructions. PART 2 PRODUCTS 2.01 MATERIALS A. Rigid Nonmetallic Conduit And Fittings (Concrete Encased): Cantex, Inc.'s

Schedule 40, Carlon Electrical Products Inc.'s Plus 40, CertainTeed Corp.'s Schedule 40, Omni/Opti-Com Manufacturing Network, Inc.'s Schedule 40 or Queen City Plastic Inc.'s Schedule 40.

B. Duct Seal: Appleton Electric Co.'s DUC Weatherproof Compound, Manville

Corp.'s Duxseal, OZ/Gedney Co.'s DUX, or Thomas & Betts Corp.'s DX. C. Drag Line: Minimum 1/8 inch polypropylene monofilament utility rope;

American Synthetic Ropes' Flotorope, Greenlee Tool Co.'s 2 ply Rope 431, or Thomas Industries/Jet Line Products' Rope 232.

D. End Bells: 1. For Rigid Ferrous Metal Conduit: OZ/Gedney Co.'s Type TNS. 2. For Rigid Nonmetallic Conduit: Conduit manufacturer's standard end

bells. E. Insulated Grounding Bushings: Appleton Electric Co.'s GIB-50 Series, Crouse

Hinds GLL Series, OZ/Gedney Co.'s IBC-50L Series, Raco Inc.'s 1212 Series, or Thomas & Betts Corp.'s 3870 or BG Series.

PART 3 EXECUTION 3.01 PREPARATION A. Before installing any Work, lay out the proposed course for the conduits, location

of manholes, etc. and have same approved by the Director's Representative. 3.02 INSTALLATION

Page 17: SECTION 260501 BASIC ELECTRICAL MATERIALS AND … 26(33).pdfUpdated 12/15/2010 Printed 03/19/2014 260501 - 1 Project No. Q1559-E SECTION 260501 BASIC ELECTRICAL MATERIALS AND METHODS

Updated 12/15/2010

Printed 03/19/2014 260543 - 2 Project No. Q1559-E

A. Spacing: 1. Arrangement for Power and Signal Service: Separate power system

conduits from signal system conduits with minimum 6 inches thick concrete wall or 12 inches of earth.

2. Conduit Bank: Separate individual conduits a minimum of 3 inches. Use spacers and levelers located no more than 8 feet apart.

B. Depth: 1. Existing Grade To Remain: Unless otherwise indicated or directed,

install conduit more than 18 inches below existing finished grade. 2. Existing Grade To Be Altered: Unless otherwise indicated or directed,

install conduit more than 18 inches below the existing grade where the finished grade is to be higher than the existing grade. Where the finished grade is to be lower than the existing grade, install conduit more than 18 inches below finished grade.

3. Under Roads and Parking Lots: a. Rigid Ferrous Metal Conduit: Unless otherwise indicated or

directed, install rigid ferrous metal conduit more than 24 inches below top surface of roads and parking lots.

b. Rigid Nonmetallic Conduit (Concrete Encased): Unless otherwise indicated or directed, install concrete encased rigid nonmetallic conduit more than 30 inches below top surface of roads and parking lots.

4. Crossing Obstructions: Use rigid ferrous metal conduit where top of conduit system is less than 18 inches below finished grade when crossing obstructions (heating tunnels, etc.).

5. In Rock: a. Unless otherwise indicated on the drawings install rigid ferrous

metal conduit or concrete encased rigid nonmetallic conduit at depths previously specified. Backfill with suitable material in accordance with SECTION 310000 - EARTHWORK.

b. Where conduit is indicated to be installed at lesser depths, use rigid ferrous metal conduit. Cover conduit with minimum 2 inches of concrete. In exposed rock area fill trench with concrete to surface level of rock. Where rock is not exposed, complete backfill in accordance with SECTION 310000 - EARTHWORK.

C. Pitch: 1. Pitch conduit away from buildings. 2. Pitch conduit toward manhole a minimum of 12 inches per 100 feet. On

runs where it is impossible to maintain the grade all one way, grade from center so that conduits pitch both directions down toward manholes.

D. Concrete Encasement for Rigid Non-Metallic Conduit Using Either of the Two

Methods Indicated Below: (Concrete Encasement for Rigid Ferrous Metal Conduit is not Required):

1. Single Pour Method.

Page 18: SECTION 260501 BASIC ELECTRICAL MATERIALS AND … 26(33).pdfUpdated 12/15/2010 Printed 03/19/2014 260501 - 1 Project No. Q1559-E SECTION 260501 BASIC ELECTRICAL MATERIALS AND METHODS

Updated 12/15/2010

Printed 03/19/2014 260543 - 3 Project No. Q1559-E

2. Two Pour Method: a. Lay rigid nonmetallic conduits on a continuous concrete footing

not less than 3 inches thick and as wide as the encasement. Install footings straight and true both in line of run and transversely, and finished with an even surface. Incorporate anchoring devices into the footing for use in tying down the conduits. Grade footings so that conduits maintain required pitch. Before installing spacers, levelers, and conduits, let concrete footings harden as required to prevent damage to the footings.

1) Where conduits enter building or manhole wall, reinforce footings for 10 feet with No. 4 rods, 4 inches on center.

2) Footings are not required for rigid ferrous metal conduit. b. After rigid nonmetallic conduits have been laid on footing with

spacers and levelers (located no more than 8 feet apart), tie conduits down to the footing, then surround the conduits by concrete not less than 2 inches thick on top and 2 inches on each side. Separate individual conduits a minimum of 3 inches so that each conduit is completely enveloped in concrete.

1) Where conduits enter building or manhole walls, reinforce encasement for 10 feet with No. 4 rods, 4 inches on center.

2) Encasement is not required for rigid ferrous metal conduit.

c. Form sides of the concrete encasement. Exception: Earth cuts will be permitted as the form where trenches are neatly excavated in stable soils.

E. Conduits in Filled Ground: Where indicated reinforce the footing and

encasement for rigid nonmetallic conduits 10 feet beyond limits of fill. Reinforcement, footing or encasement is not required for rigid ferrous metal conduit.

F. Cleaning Conduits: Take precautions to prevent foreign matter from entering

conduits during installation. After installation clean conduits with tools designed for the purpose.

G. Sealing Ends of Conduits: 1. Occupied Conduits: Seal ends of conduits to be used for Work of this

contract until cables are to be installed. After cable installation, seal conduits at building entrances and first manhole outside building. Seal with duct seal.

2. Conduits For Future Use: Seal the ends of spare and empty conduits at building entrances and manholes. Seal with plastic plugs or a contrasting color cement/sand mixture.

Page 19: SECTION 260501 BASIC ELECTRICAL MATERIALS AND … 26(33).pdfUpdated 12/15/2010 Printed 03/19/2014 260501 - 1 Project No. Q1559-E SECTION 260501 BASIC ELECTRICAL MATERIALS AND METHODS

Updated 12/15/2010

Printed 03/19/2014 260543 - 4 Project No. Q1559-E

3.03 CONDUIT SCHEDULE - TYPES AND USE A. Rigid Nonmetallic Conduit (Concrete Encased): May be installed in all locations

except: 1. Where conduit stubs up or rises through slab or finished grade. 2. Where other type raceways are specified or indicated on the drawings.

END OF SECTION

Page 20: SECTION 260501 BASIC ELECTRICAL MATERIALS AND … 26(33).pdfUpdated 12/15/2010 Printed 03/19/2014 260501 - 1 Project No. Q1559-E SECTION 260501 BASIC ELECTRICAL MATERIALS AND METHODS

Updated 12/15/2010

Printed 03/19/2014 260924 - 1 Project No. Q1559-E

SECTION 260924

AUTOMATIC LIGHTING CONTROLS PART 1 GENERAL 1.01 SUBMITTALS A. Waiver of Submittals: The "Waiver of Certain Submittal Requirements" in

Section 013300 does not apply to this Section. B. Submittals Package: Submit the shop drawings, and the product data specified

below at the same time as a package. C. Shop Drawings: Wiring and/or schematic diagram of the control circuits as

proposed to be installed (standard diagrams will not be accepted). D. Product Data: Catalog sheets, specifications and installation instructions. PART 2 PRODUCTS 2.01 LIGHTING CONTROL EQUIPMENT

A. Lighting Control Relays: 277 volt AC, 20 amp, 2 pole (N.O.) with pilot contacts, and visual on-off indicator. Relay shall mount in standard manufacturer’s cabinet, operates in any position, operating temperature of 0º to 60ºC (32º to 140ºF), relative humidity of 10% to 95% non-condensing, non-explosive or non-corrosive atmosphere, UL listed. Acceptable Manufacturers: Intelligent Lighting Controls, Inc. 2 PC Series; General Electric; Nextlight; or approved equal.

B. Outdoor motion sensors

1. Manufacturers: Subject to compliance with requirements, provide products by the following, or equal: a. Wattstopper/Legrand

2. Basis of Design Product: Subject to compliance with requirements, provide a. Wattstopper/Legrand; Low Temperature Occupancy Sensor CB100-

3 or equal C. Exterior Photocell

1. Manufacturers: Subject to compliance with requirements, provide products by the following, or equal: a. Wattstopper/Legrand

2. Basis of Design Product: Subject to compliance with requirements, provide a. Wattstopper/Legrand; EM Photocell or equal

Page 21: SECTION 260501 BASIC ELECTRICAL MATERIALS AND … 26(33).pdfUpdated 12/15/2010 Printed 03/19/2014 260501 - 1 Project No. Q1559-E SECTION 260501 BASIC ELECTRICAL MATERIALS AND METHODS

Updated 12/15/2010

Printed 03/19/2014 260924 - 2 Project No. Q1559-E

2.02 LIGHTING CONTROL PANELBOARDS

2.02.1 MANUFACTURERS

A. Products: Subject to compliance with requirements, provide the following 1. Watt Stopper/Legrand; LP8 Peanut Lighting Control Panel, or equal.

B. Basis-of-Design Product: Subject to compliance with requirements, provide or comparable product by one of the following: 1. The Watt Stopper/Legrand, or equal.

C. Source Limitations: Obtain lighting controls and power distribution components from single manufacturer.

2.02.2 SYSTEM DESCRIPTION

A. Input signal from field-mounted or on-board signal source shall open or close one or more electrically operated circuit breakers in the lighting control panelboards. Any combination of inputs shall be programmable to any combination outputs.

B. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.

C. Comply with 47 CFR, Subpart A and Subpart B, for Class A digital devices.

D. Install a lighting control system consisting of relay/contactor panel(s), control switches, occupancy sensors, photocells and other controlling devices. The devices are connected by low voltage and line voltage wiring. The general operation of lighting and controlled loads shall include:

1) Scheduled on/off loads: Time on, time off by automatic time schedule with after hour override capability and shutoff.

2) Exterior Lighting: Motion Sensors, Photocell, astronomic on/time off, time on/photocell or astronomic off.

2.02.3 PERFORMANCE REQUIREMENTS

A. Expansion Requirements: Capacity for future expansion of number of control functions by 25 percent of current capacity; to include equipment ratings, housing capacities, spare spaces for circuit breakers, terminals, number of conductors in control cables, and control software.

Page 22: SECTION 260501 BASIC ELECTRICAL MATERIALS AND … 26(33).pdfUpdated 12/15/2010 Printed 03/19/2014 260501 - 1 Project No. Q1559-E SECTION 260501 BASIC ELECTRICAL MATERIALS AND METHODS

Updated 12/15/2010

Printed 03/19/2014 260924 - 3 Project No. Q1559-E

202.4 PANELBOARDS

A. The lighting panelboards may contain remotely operated circuit breakers and standard branch circuit breakers specified in Section 260001 "Panelboards".

B. Assemblies: Comply with UL 67 and NEMA PB 1.

C. Surge Protective Device: Field mounted, complying with Section 260001 "Surge Protection for Low-Voltage Electrical Power Circuits."

D. Surge Protective Device: Integrally mounted, complying with UL 1449 Type 1. 1. Comply with IEEE C62.41, Category C, 200-kA short-circuit current rating. 2. Non-modular type with the following features and accessories:

Digital-display indicator lights for power and protection status.

E. Enclosures: Comply with UL 50 and NEMA 250.

F. Future Devices: Mounting brackets, bus connections, filler plates, and necessary appurtenances required for future installation of devices.

G. Panelboard Short-Circuit Current Rating: Rated for series-connected system with integral or remote upstream overcurrent protective devices and labeled by an NRTL. Include size and type of allowable upstream and branch devices, listed and labeled for series-connected, short-circuit rating by an NRTL.

H. Panelboard Short-Circuit Current Rating: Fully rated to interrupt 10-Ka symmetrical short-circuit current available at terminals.

I. Lighting Control Panel shall be UL listed and consist of the following: 1. Enclosure / Tub: NEMA 1 2. Cover: Surface or flush as required, hinged, lockable, and shall restrict access

to line voltage section. 3. Interior: Barrier for separation of high voltage (class 1) and low voltage

(class 2) wiring. It shall include intelligence boards, power supply and control relays. Clock display and keypad shall be mounted on interior cabinet door for easy user access and programming.

J. Features 1. Panel shall accept up to eight single pole relays. Relays shall be individual

latching relays with 20 Amp load contacts for ballast (including HID, magnetic or electronic type ballasts), tungsten and general purpose loads. Provide isolated auxiliary contacts for pilot light switching. Relays shall use quick connectors and be individually replaceable to facilitate ease of use.

2. Where indicated, panels shall provide space within the high voltage section of the enclosure to accommodate up to 12 multi-pole contactors. Two sections of DIN rail mounting shall be provided as standard. No field drilling or fabrication shall be required for mounting contactors or other accessories within the enclosure.

Page 23: SECTION 260501 BASIC ELECTRICAL MATERIALS AND … 26(33).pdfUpdated 12/15/2010 Printed 03/19/2014 260501 - 1 Project No. Q1559-E SECTION 260501 BASIC ELECTRICAL MATERIALS AND METHODS

Updated 12/15/2010

Printed 03/19/2014 260924 - 4 Project No. Q1559-E

3. The lighting control panel shall provide a stagger up delay, override push buttons, pilot light outputs, and LED status light indicators for each relay or contactor control channel.

4. The clock shall have a backlight display, user keypad and shall provide 8 channels of time or astronomical control. Preprogrammed lighting control scenarios shall include: scheduled on/off, manual on/scheduled off, manual on/automatic switch sweep off, astronomic or photocell on/off and astronomic or photocell control with scheduled on/off. Time clock shall provide up to 42 holidays, automatic daylight savings adjustment, astronomic coordinates by major cities, and help screens. Program memory shall be non-volatile and clock shall retain time keeping during power outages for at least 48 hours.

5. The panel shall have have 8 universal switch inputs that are low voltage, self-configuring and shall not require programming to accept momentary on/ momentary off switch, push button switch (cycling), maintained switch or 24VDC signals from occupancy sensors, photocells or other interfacing devices.

6. Occupancy sensor and time control shall be integrated to allow occupancy sensor control after hours with hold on of lighting during occupancy scheduled time. During occupied time, control scenarios shall be selectable for time schedule of lighting on or occupancy sensor detection of lighting on initially and then hold on of lighting during occupied hours. Control shall provide selectable occupancy sensor blink warning prior to shut off and adjustable occupancy sensor time delay from the time clock keypad.

2.02.5 CIRCUIT BREAKERS

A. Remotely operated branch circuit breakers used for lighting control shall provide branch-circuit overcurrent protection.

B. Labeled with SWD and HID Ratings: Comply with UL 489 for 15- and 20-A, single-pole branch devices. 15- and 20-A circuit breakers, if scheduled, shall be a product of the same manufacturer and be of the same class as the rated circuit breakers.

C. Switching Endurance Rating: Not less than 50,000 full-load open/close/open remote operations.

D. Remotely Operated Circuit Breakers: Manual override switch or handle position shall enable or disable the remote operation of the device and allow breaker handle to manually control the breaker's on-off status.

Page 24: SECTION 260501 BASIC ELECTRICAL MATERIALS AND … 26(33).pdfUpdated 12/15/2010 Printed 03/19/2014 260501 - 1 Project No. Q1559-E SECTION 260501 BASIC ELECTRICAL MATERIALS AND METHODS

Updated 12/15/2010

Printed 03/19/2014 260924 - 5 Project No. Q1559-E

2.02.6 CONTROLLERS

A. Description: Controllers shall contain the power supply and electronic control for operating and monitoring remotely operated branch circuit breakers. 1. Comply with UL 916; with a microprocessor-based, solid-state, 365-day

timing and control unit. 2. Power Supply: Powered from the panelboard, sized to provide control power

for the operation of the remotely operated circuit breakers, controller, bus system, low-voltage inputs, field-installed occupancy sensors, and low-voltage photo sensors.

3. Integral keypad and digital-display front panel for local setup, including the following: a. Blink notice, time adjustable from software. b. Ability to log and display remotely operated breaker on-time. c. Capability for accepting downloadable firmware so that the latest

production features may be added in the future without replacing the module.

4. Nonvolatile memory shall retain all setup configurations. After a power failure, the controller shall automatically reboot and return to normal system operation.

5. Ethernet Communications: Comply with ASHRAE 135 protocols. a. Each input connected to the controller shall control any remotely operated

breaker in any other networked lighting control panel. b. A schedule programmed at one controller shall be able to control any

remotely operated breaker in any other networked lighting control panel. 6. Time Synchronization: The timing unit shall be updated not less than every 4

hour(s) with the network time server. 7. Web Server: Display information listed below over a standard Web-enabled

server for displaying information over a standard Web browser. a. A secure, password-protected login screen for modifying operational

parameters, accessible to authorized users via Web page interface. b. Separate Web page, showing status of each main and slave lighting control

panel with the arrangement of breakers on the page matching the physical appearance of the panel. Status shall include breaker nametags, pole configuration, location in panel, actual contact state (on-off/tripped/manual), and breaker on-time and blink information in real time.

c. Panel summary showing the master and slave panels connected to the controller.

d. Controller diagnostic information. e. Show front panel mimic screens for setting up controller parameters, input

types, zones, and operating schedules. These mimic screens shall also allow direct breaker control and zone overrides.

8. Alarm and E-mail Notification: Automatically initiate alarms based on preconfigured conditions listed below and routing alarm alerts as set at the control panel.

Page 25: SECTION 260501 BASIC ELECTRICAL MATERIALS AND … 26(33).pdfUpdated 12/15/2010 Printed 03/19/2014 260501 - 1 Project No. Q1559-E SECTION 260501 BASIC ELECTRICAL MATERIALS AND METHODS

Updated 12/15/2010

Printed 03/19/2014 260924 - 6 Project No. Q1559-E

a. General Alarms: Power loss, non-responding breakers, loss and restoration of sub-net communications, loss and restoration of serial port communications, loss and restoration of BAS commands.

b. Specific Alarms: Input status, zone status, breaker status on-time (0 to 99999 hours).

c. E-mail Notification: Automatically route e-mail messages to five individual e-mail addresses. Within the body text of the e-mail, include a link that automatically redirects the user to the associated panels' status Web page.

B. Timing Unit: 1. 365-day calendar, astronomical clock, and automatic adjustments for

daylight savings and leap year. 2. Clock configurable for 12-hour (A.M./P.M.) or 24-hour format. 3. 16 independent schedules, each having 24 time periods. Schedule periods

settable to the minute. 4. Day-of-week, day-of-month, day-of-year with one-time or repeating

capability. 5. 32 special date periods.

C. With eight inputs, each configurable to the following parameters: 1. Normally open, normally closed, two-wire maintained toggle, two-wire

momentary toggle, two-wire momentary on, two-wire momentary off, or three-wire momentary operation.

2. On and off-delay timers for local override operation, adjustable from five minutes to 12 hours. Local override shall be by field-installed, two-wire momentary toggle switch.

2.02.7 CONTROL NETWORK

A. Compliance with ASHRAE 135: Controllers shall support serial MS/TP and Ethernet IP communications, and shall be able to communicate directly via BAS RS-485 serial networks and Ethernet 10Base-T networks as a native device.

2.02.8 MANUAL SWITCHES AND PLATES

A. Keypads: Programmable, designed to control lighting applications and functions associated with the equipment of this Section. The units shall be able to control any system output device, including remotely operated circuit breakers, relays, dimmers, and analog outputs.

B. Push-Button Switches: Modular, momentary-contact, low-voltage type. 1. Integral green LED pilot light to indicate when circuit is on. 2. Internal white LED locator light to illuminate when circuit is off.

Page 26: SECTION 260501 BASIC ELECTRICAL MATERIALS AND … 26(33).pdfUpdated 12/15/2010 Printed 03/19/2014 260501 - 1 Project No. Q1559-E SECTION 260501 BASIC ELECTRICAL MATERIALS AND METHODS

Updated 12/15/2010

Printed 03/19/2014 260924 - 7 Project No. Q1559-E

C. Legend: Engraved or permanently silk-screened on wall plate where indicated. Use designations indicated on Drawings.

2.02.9 CONDUCTORS AND CABLES

A. Comply with requirements in Section 260001 "Low-Voltage Electrical Power Conductors and Cables."

B. Digital and Multiplexed Signal Cables: Unshielded, twisted-pair cable with copper conductors, complying with TIA/EIA-568-B.2, Category 5e for horizontal copper cable.

PART 3 EXECUTION 3.01 LIGHTING CONTROL EQUIPMENT

A. Sensor Installation 1. Coordinate layout and installation of building mounted devices with other

construction that penetrates walls or is supported by them, including light fixtures, HVAC equipment, and partition assemblies.

2. Install and aim sensors in locations to achieve not less than 90 percent coverage of areas indicated. Do not exceed coverage limits specified in manufacturer's written instructions.

B. Contactor Installation 1. Mount electrically held lighting contactors with elastomeric isolator pads to

eliminate structure-borne vibration, unless contactors are installed in an enclosure with factory-installed vibration isolators.

C. Wiring Installation 1. Wiring Method: Comply with Section 260001 "Low-Voltage Electrical

Power Conductors and Cables." Minimum conduit size is 1/2 inch (13 mm). 2. Wiring within Enclosures: Comply with NECA 1. Separate power-limited

and nonpower-limited conductors according to conductor manufacturer's written instructions.

3. Size conductors according to lighting control device manufacturer's written instructions unless otherwise indicated.

4. Splices, Taps, and Terminations: Make connections only on numbered terminal strips in junction, pull, and outlet boxes; terminal cabinets; and equipment enclosures.

D. Identification 1. Identify components and power and control wiring according to

Section 260553 "Identification for Electrical Systems” a. Identify controlled circuits in lighting contactors. b. Identify circuits or luminaires controlled by photoelectric and

occupancy sensors at each sensor 2. Label time switches and contactors with a unique designation.

Page 27: SECTION 260501 BASIC ELECTRICAL MATERIALS AND … 26(33).pdfUpdated 12/15/2010 Printed 03/19/2014 260501 - 1 Project No. Q1559-E SECTION 260501 BASIC ELECTRICAL MATERIALS AND METHODS

Updated 12/15/2010

Printed 03/19/2014 260924 - 8 Project No. Q1559-E

E. Field Quality Control 1. Manufacturer’s Field Service: Engage a factory-authorized service

representative to test and inspect components, assemblies, and equipment installations, including connections.

2. Perform the following tests and inspections with the assistance of a factory-authorized service representative: a. Operational test: After installing time switches and sensors, and

after electrical circuitry has been energized, start units to confirm proper unit operation.

b. Test and adjust controls and safeties. Replace damaged and malfunctioning controls and equipment.

3. Lighting control devices will be considered defective if they do not pass tests and inspections.

4. Prepare test and inspection reports F. Adjusting

1. Occupancy Adjustments: When requested within 1 month from date of Substantial Completion, provide on-site assistance in adjusting sensors to suit actual occupied conditions. Provide up to two visits to Project during other-than-normal occupancy hours for this purpose. a. For motion sensors, verify operation at outer limits of detector

range. Set time delay to suit Owner's operations. b. For daylighting controls, adjust set points and deadband controls to

suit Owner's operations. G. Demonstration

1. Engage a factory-authorized service representative to train Owner's maintenance personnel to adjust, operate, and maintain lighting control devices

3.02 PANELBOARDS

A. Receive, inspect, handle, and store panelboards according to NECA 407 and NEMA PB 1.1.

B. Examine panelboards before installation. Reject panelboards that are damaged or rusted or have been subjected to water saturation.

C. Examine elements and surfaces to receive panelboards for compliance with installation tolerances and other conditions affecting performance of the Work.

D. Proceed with installation only after unsatisfactory conditions have been corrected.

3.02.1 WIRING INSTALLATION

A. Comply with NECA 1.

Page 28: SECTION 260501 BASIC ELECTRICAL MATERIALS AND … 26(33).pdfUpdated 12/15/2010 Printed 03/19/2014 260501 - 1 Project No. Q1559-E SECTION 260501 BASIC ELECTRICAL MATERIALS AND METHODS

Updated 12/15/2010

Printed 03/19/2014 260924 - 9 Project No. Q1559-E

B. Wiring Method: Install cables in raceways and cable trays except within consoles, cabinets, desks, and counters and except in accessible ceiling spaces and in gypsum board partitions where unenclosed wiring method may be used. Conceal raceway and cables except in unfinished spaces. 1. Install plenum cable in environmental air spaces, including plenum ceilings. 2. Comply with requirements for cable trays specified in Section 260001 "Cable

Trays for Electrical Systems." 3. Comply with requirements for raceways and boxes specified in

Section 260001 "Raceways and Boxes for Electrical Systems."

C. Wiring Method: Conceal conductors and cables in accessible ceilings, walls, and floors where possible.

D. Wiring within Enclosures: Bundle, lace, and train conductors to terminal points with no excess and without exceeding manufacturer's limitations on bending radii. Install lacing bars and distribution spools.

3.02.2 PANELBOARD INSTALLATION

A. Comply with NECA 1.

B. Install panelboards and accessories according to NECA 407 and NEMA PB 1.1.

C. Mounting Height: 90 inches to top of trim above finished floor unless otherwise indicated.

D. Mount panelboard cabinet plumb and rigid without distortion of box. Mount recessed panelboards with fronts uniformly flush with wall finish and mating with back box.

E. Install filler plates in unused spaces.

3.02.3 IDENTIFICATION

A. Panelboard Nameplates: Label each panelboard with a nameplate complying with requirements for identification specified in Section 260001 "Identification for Electrical Systems."

Page 29: SECTION 260501 BASIC ELECTRICAL MATERIALS AND … 26(33).pdfUpdated 12/15/2010 Printed 03/19/2014 260501 - 1 Project No. Q1559-E SECTION 260501 BASIC ELECTRICAL MATERIALS AND METHODS

Updated 12/15/2010

Printed 03/19/2014 260924 - 10 Project No. Q1559-E

3.02.4 FIELD QUALITY CONTROL

A. Manufacturer’s Field Service: Engage a factory-authorized service representative to test and inspect components, assemblies, and equipment installations, including connections.

B. Perform the following tests and inspections with the assistance of a factory-authorized service representative: 1. Perform each visual and mechanical inspection and electrical test stated in

NETA Acceptance Testing Specification. Certify compliance with test parameters.

2. Correct malfunctioning units on-site, where possible, and retest to demonstrate compliance; otherwise, replace with new units and retest.

3. Perform the following infrared scan tests and inspections and prepare reports: a. Initial Infrared Scanning: After Substantial Completion, but not more

than 60 days after Final Acceptance, perform an infrared scan of each panelboard. Remove front panels so joints and connections are accessible to portable scanner.

b. Follow-up Infrared Scanning: Perform an additional follow-up infrared scan of each panelboard 11 months after date of Substantial Completion.

c. Instruments and Equipment:

1) Use an infrared scanning device designed to measure temperature or to detect significant deviations from normal values. Provide calibration record for device.

C. Acceptance Testing Preparation: 1. Test insulation resistance for each panelboard bus, component, connecting

supply, feeder, and control circuit. 2. Test continuity of each circuit.

D. Panelboard will be considered defective if it does not pass tests and inspections.

E. Prepare test and inspection reports, including a certified report that identifies panelboards included and describes scanning results. Include notation of deficiencies detected, remedial action taken, and observations made after remedial action.

3.02.5 STARTUP SERVICE

A. Engage a factory-authorized service representative to perform startup service. 1. Complete installation and startup checks according to manufacturer's written

instructions. 2. Confirm correct communication wiring, initiate communications between

panels, and program the lighting control system according to approved zone

Page 30: SECTION 260501 BASIC ELECTRICAL MATERIALS AND … 26(33).pdfUpdated 12/15/2010 Printed 03/19/2014 260501 - 1 Project No. Q1559-E SECTION 260501 BASIC ELECTRICAL MATERIALS AND METHODS

Updated 12/15/2010

Printed 03/19/2014 260924 - 11 Project No. Q1559-E

configuration schedules, time-of-day schedules, and input override assignments.

3.02.6 ADJUSTING

A. Occupancy Adjustments: When requested within 12 months from date of Substantial Completion, provide on-site assistance in adjusting system to suit actual occupied conditions. Provide up to two visits to Project during other-than-normal occupancy hours for this purpose.

3.02.7 SOFTWARE SERVICE AGREEMENT

A. Technical Support: Beginning at Substantial Completion, service agreement shall include software support for two years.

B. Upgrade Service: At Substantial Completion, update software to latest version. Install and program software upgrades that become available within two years from date of Substantial Completion. Upgrading software shall include operating system and new or revised licenses for using software. 1. Upgrade Notice: At least 30 days to allow the Director’s Representative to

schedule and access the system and to upgrade computer equipment if necessary.

3.02.8 DEMONSTRATION

A. Engage a factory-authorized service representative to train Owner's maintenance personnel to adjust, operate, and maintain control modules.

END OF SECTION

Page 31: SECTION 260501 BASIC ELECTRICAL MATERIALS AND … 26(33).pdfUpdated 12/15/2010 Printed 03/19/2014 260501 - 1 Project No. Q1559-E SECTION 260501 BASIC ELECTRICAL MATERIALS AND METHODS

Updated 12/15/2010

Printed 03/19/2014 262815 - 1 Project No. Q1559-E

SECTION 262815

CIRCUIT BREAKERS FOR EXISTING PANELBOARDS PART 1 GENERAL 1.01 SUBMITTALS A. Not required. PART 2 PRODUCTS 2.01 CIRCUIT BREAKERS A. Similar to existing circuit breakers. B. Compatible with existing panelboard. C. Number of poles and ampere trip rating as indicated on drawings. D. Complete with accessories required for installation. PART 3 EXECUTION 3.01 INSTALLATION A. Install new circuit breakers in existing panelboards where indicated. B. Add new circuits equally across phases to prevent overloading any phase in the

panelboard. After new and existing circuits are energized, take current reading on panelboard feeder during a heavy usage time period. If phases are substantially unbalanced, rearrange both new and existing circuits in panelboard to equally distribute load between all phases, and provide new typewritten directory indicating equipment controlled by each circuit breaker.

END OF SECTION