see4423 chapter1 introduction[1]
DESCRIPTION
introduction to power system protectionTRANSCRIPT
![Page 1: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/1.jpg)
OFFICE: CENTER OF ELECTRICAL ENERGY SYSTEM (CEES)FACULTY ELECTRICAL ENGINEERING UNIVERSITI TEKNOLOGI MALAYSIA 81310 UTM JOHOR BAHRUJOHOR DARUL TAKZIM
ROOM NO: P07-412Tel: 07-5536262
![Page 2: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/2.jpg)
WELCOME
• POWER SYSTEM ENGINEERING• SEE 4423
• LECTURER: ASSOC PROF MD SHAH MAJID• ROOM NO: P08-409/P07-417(CEES)• TEL: 07 -5535295/5536262 (CEES)• E-mail: [email protected], [email protected]
![Page 3: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/3.jpg)
SEE 4423POWER SYSTEM ENGINEERING
SEMESTER II SESSION 2009/2010
Assoc Prof MD SHAH MAJID
![Page 4: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/4.jpg)
4
SEE 4423POWER SYSTEM ENGINEERING
SEMESTER 1 SESSION 2009/2010
![Page 5: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/5.jpg)
CHAPTER 1
INTRODUCTION TO PROTECTION SYSTEM
![Page 6: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/6.jpg)
Introduction:Need for Protective Systems
• Power system consists of; generators, transformers, transmission and distribution lines, etc…..etc.
– Sistem kuasa mengandungi: penjana, pengubah, talian penghantaran dan pengagihan dsbnya
• Short circuits and other abnormal conditions often occur on a power system– Litar pintas dan keadaan tidak normal kerap berlaku pada sistem kuasa
• Heavy current associated with short circuits is likely to cause damage to equipments
– Arus yg tinggi ketika litar pintas mungkin menyebabkan kerosakan pada peralatan jika geganti perlindungan dan pemutus litar tidak di bekalkan untuk perlindungan bagi setiap seksyen sistem kuasa
![Page 7: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/7.jpg)
Need for Protective Systems
• Short circuit is a faults (power engineer)
• Failure of conducting path due to a break in a conductor is a type of fault
• Fault occurs – automatic protective device is needed to isolate the faulty element as quickly as possible to keep the healthy section of the system in normal operation
• Fault must be cleared within fraction of a second
• Uncleared short circuits may cause total failure of the system
![Page 8: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/8.jpg)
• A protective scheme includes transducers, protective relays and circuit breakers to isolate the faulty section of the system from the healthy section
• Protection is needed not only against short circuit but also against any abnormal condition– Overspeed of generators and motors– Overvoltage– Underfrequency– Loss of excitation– Overheating of stator or rotor of an alternator– Etc…etc…etc
• Protection is a pre-requisite for an effective and reliable system
• A protective relay does not anticipate or prevent the occurrence of fault, rather it takes action only after a fault has occurred – except Buchholz relay; a gas actuated relay
![Page 9: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/9.jpg)
Nature and causes of Faults
• Faults are caused either by;
– Insulation failure –– Conducting path failure
• results in short circuit
• Faults on transmission and distribution lines are caused by overvoltage– Lightning and switching surges– External conducting objects falling on overhead line.
• Birds also may cause faults on overhead line if their bodies touch one of the phase and earth wire
![Page 10: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/10.jpg)
• If conductors are broken – failure of conducting path and the conductor becomes open-circuited– If broken conductor fall to the ground, results in short circuit
• Joint failure on cables and overhead lines also cause a failure of the conducting path
• Opening of one or two of the three phases makes the system unbalanced– Set-up harmonics
![Page 11: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/11.jpg)
• Other causes of faults in o/h line– Direct lightning strokes– Aircraft– Snakes– Ice and snow loading– Abnormal loading– Storm– Earthquakes– Creepers– Etc…..etc……etc……etc
![Page 12: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/12.jpg)
• Cables, transformer generators and other equipment:– Failure of solid insulation due to aging– Heat– Moisture– Overvoltage– Mechanical damage– Accidental with earth– Flashover due to overvoltages– Etc…etc…..etc
![Page 13: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/13.jpg)
Types of faults
• Symmetrical faults
• Unsymmetrical faults
• Symmetrical faults– Kerosakan tiga fasa atau tiga fasa ke bumi
• Unsymmetrical faults – Single line to earth, line-to-line, double line to
earth, open-circuited phases
![Page 14: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/14.jpg)
• Faults can interrupt power system in several ways:
– Heavy current to flow
• Effect : overheating of power system component
– Fault is a short circuit and exist as electrical arc and liquid e.g air
• Effect: equipment faulty and fire
![Page 15: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/15.jpg)
• Fault – can increase/decrease voltage system outside its acceptable range
– Can cause unstable three phase system, improper operation of three phase equipments
– Prevent power flow
– Can cause system to be unstable and collapse
![Page 16: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/16.jpg)
• Faults incur MONEY.
• If fault is isolated as quickly as possible and accurate –less money required
• Cost of protective equipment is 5% of the total cost of the system
![Page 17: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/17.jpg)
• PROTECTION DOES NOT MEAN PREVENTION
– A protective relay does not anticipate or prevent the occurrence of fault, rather it takes action only after a fault has occurred – except Buchholz relay; a gas actuated relay
![Page 18: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/18.jpg)
Functions of Protective System
• Fast and automatically opens the faulty section in the power system
• Increase system reliability and security – only affected area will be isolated and maintain the healthy line– Ensure consumers receive continuity of supply
• Delay in isolating the fault – System unstable, loss of synchronism, total failure of the system– Fire
![Page 19: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/19.jpg)
Requirements of Protective System
• The basic requirements of a protective system are as follows:
– Discrimination/selectivity– Sensitivity– Reliable – Stability– Speed
![Page 20: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/20.jpg)
(Discrimination/Selectivity)
• Ability to select either to operate or not – Keupayaan untuk memilih sama ada bekerja atau tidak
• Select to isolate the faulty section only (the rest normal condition) – Memilih untuk mengasingkan bahagian rosak sahaja (yang lain berkeadaan
normal)
• The nearest circuit breaker will trip – Pemutus litar yang hampir sahaja terbelantik (trip)
![Page 21: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/21.jpg)
SD1SD2 SD3
SD1 SD2SD3
Radial protection system
![Page 22: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/22.jpg)
Sensitivity
• Relay should operate when the magnitude of the current exceeds the preset value
• This value is called pick up current
• Should not operate when current is below its pick-up value
• Should be sufficiently sensitive to operate when the operatinfg current just exceeds the pick-up value – relate with minimum operating current
![Page 23: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/23.jpg)
Reliability
• A protective system must operate reliably when a fault occurs in its zone of protection
• Failure may due to its protective element system; CT, PT, CB, relay etc….
• Reliability of protective system 95%
![Page 24: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/24.jpg)
Stability
• A protective system should remain stable even when a large current is flowing through its protective zone due to an external fault
• Concerned circuit breaker is supposed to clear the fault
![Page 25: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/25.jpg)
SD1 SD2SD3
Radial system protection
YesNo
![Page 26: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/26.jpg)
Speed-fast operation
• Isolate fault as quickly as possible (at shortest time possible )
• Isolate disturbances before loss of synchronism and plant stop operation – time should not exceed critical clearing time
• Speed balanced with economy – Cost of protective equipment should be relevant to the cost of the protected
zone
• Avoid fire to equipments, interruption of supply to consumer, voltage drop operating time; 1 cycle, ½ cycle are also available; distribution system > 1 cycle
![Page 27: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/27.jpg)
Operating time
• Total time to accomplish the isolation
• Calculated at the instance of fault until the given trip signal
• Must be low for the sake of plant and equipment safety
• Delay time – for discrimination
![Page 28: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/28.jpg)
Protection economy
• Protection system can be designed as: – Simple and cheap
– Complex and expensive
• Baesd on:– The cost of fault
– Safety level requirement
![Page 29: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/29.jpg)
Protection economics…
• Cost of fault– Cost of damage toward the plant
– Cost loss of revenue due to cut-out supply
– Cost of customers confidence
• Higher the cost of fault, more expensive the protection system
• Higher the plant kVA, more complex protection system required
![Page 30: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/30.jpg)
Protection system at customer level
• Simple fuse – protect equipment and certain circuits
• Fius ringkas melindungi alat-alat dan litar tertentu
• Miniature circuit breaker- MCB
![Page 31: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/31.jpg)
Protection system at distribution level
• Fuse and switch fuse
• Automatic reclosing circuit breaker– For rural area
– Transient fault is corrected by self clearing
![Page 32: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/32.jpg)
Protection system at transmission level
• Technical consideration outweighs the economy
• 275kV dan 400kV System require a protection system which is:– very reliable– Full discrimation– High speed
• Expensive and complex
• Provide back-up protection
![Page 33: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/33.jpg)
Zone of Protection
• Power system is divided into several zones
• Each zone of protection is provided with 2 types of protection:
– Primary protection
– Backup protection
GENERATOR PROTECTION
CIRCUIT BREAKER
HV SWITCHGEAR PROTECTION
TRANSFORMER PROTECTION
EHV SWITCHGEAR PROTECTION
TRANSMISSION LINE PROTECTION
EHV SWITCHGEAR PROTECTION
ZONE OF PROTECTION
![Page 34: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/34.jpg)
Protection zone
• Region or area encompass a protection system
![Page 35: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/35.jpg)
SD1 SD2SD3
Radial protection system
CB1CB2
CB3
Protection zone CB3
![Page 36: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/36.jpg)
Main/primary protection
• In general primary protection is provided for each transmission line segment, major piece of equipment and switchgear
• If fault occurs, it is the duty of the primary protective scheme to clear the fault
• First line of defence - Responsible to isolate fault as quickly as possible
• Fails, back-up protection clears the fault
![Page 37: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/37.jpg)
Backup Protection
• Act when primary protection fails – second line of defence
• Usually several back up protection scheme will act to control the power system
• Longer time delay
![Page 38: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/38.jpg)
Back-up protection
SD1 SD2SD3
Radial protection system
Main protection
![Page 39: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/39.jpg)
Zone of protection
• Zone of protection usually overlap
![Page 40: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/40.jpg)
Fault detection
• Current magnitude
• Current in abnormal path (earth)
• Current balance (current out#current in)• Voltage balance
• Changes in impedance
• Protective system damage(Buchholz), power flow direction, temeprature & pressure
![Page 41: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/41.jpg)
Protective system components
1. Circuit breaker
2. Transducer – current transformer (CT), voltage transformer (VT), potential transformer (PT)
3. Communication links– Pilot wire
– Radio link
– Overlapping signal, power line carrier (PLC)
![Page 42: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/42.jpg)
Protective system components
4. Relay – Electromagnetic
– Static – improve reliability,versatile, fast response (1/4 cycle)
– Microprocessor- VLSI teknologi – current interest to power engineers; adv:attractive flexibility due to programmable approach, can provide protection at low cost and compete with conventional relays
5. Fuse
![Page 43: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/43.jpg)
Transducer
Serves as a sensor to detect abnormal system conditions and to transform the high values of short
circuit current and voltage to a lower values
43
![Page 44: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/44.jpg)
Protective relays
• Process the signals provided by the transducers which may be in the form of current, voltage or a combination of current and voltage
44
![Page 45: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/45.jpg)
Circuit breaker
• Mechanical device used to energize and interrupt an electric circuit
45
![Page 46: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/46.jpg)
Ex. Protective system: power flow balance
R1 R2
1. PL 1. P.L2. CT, PT
3
4. Relay
![Page 47: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/47.jpg)
Classifications of relay based on its function
• Overcurrent relay
• Undervoltage relay
• Impedance relay
• Under frequency relay
• Directional relay etc….etc….etc
![Page 48: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/48.jpg)
Classification of protective scheme
• Overcurrent protection
• Distance protection
• Current carrier protection
• Differential protection
![Page 49: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/49.jpg)
Transformer in a protective system
• CT assume ideal• Normal rating:
– 1:1, 2:1. 2.5:1, 4:1, 5:1– 20:1, 40:1, 100:1, 200:1, 300:1,
600:1– 1000:1, 2000:1, 4500:1
• Secondary coil is connected to a “sensitive device” eg voltmeter
• Low Stray impedance so that voltage drop small
VpVs
Ip
Is
Feeder conductor
VT
CT
![Page 50: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/50.jpg)
Current transformer (CT)
• Normal rating – 1A (Europe)– 5A (USA)
• Example :– 50:5, 100:5, 150:5, 200:5, 250:5– 450:5, 500:5,……1000:5, ……, 6000:
• Secondary coil is connected to a “current sensing device” of zero impedance
• Shunt impedance high so that I0 low.
![Page 51: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/51.jpg)
(current transformer CT)
• Working principle similar to voltage transformer
• Supply by current source
• Primary winding connected in series with power circuit – Carries full load current
• Transformer impedance (referred to secondary and can be neglected)
• Secondary coil connected to load (burden)
![Page 52: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/52.jpg)
(current transformer CT)
• Secondary winding feeds the protective system
• Current is reduced but must be almost the same with the power system current
• Secondary rated current 5 A or 1 A
• Fault current 10 – 20 X rated current. Transformer must be capable to operate reliably/accurately at this value
• Burden usually usually small – flux do not saturate
![Page 53: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/53.jpg)
Current transformer construction
Primary winding
(1 turn)- from power system
Core
Power system current
Secondary winding wound on the core
Bar Type
![Page 54: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/54.jpg)
Current transformer construction
Wound type
![Page 55: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/55.jpg)
design
• CT – similar to a normal transformer emf equation
• Average induced voltage = product of No. of turn and rate of change of flux magnet; eaverage
= N(dΦ/dt)
• Knee point voltage(rms) = 4.44 BAfN
![Page 56: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/56.jpg)
Burden
• Defined as the load connected across its secondary CT – express in VA (VA taken as nominal secondary
current of CT) or– Impedance (at the rated secondary current at a
given power factor usually 07. lagging
• Increase in impedance – increase burden• CT unloaded if secondary winding is short
circuited
![Page 57: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/57.jpg)
Example
• 5VA burden at 1A transformer, gives 5 Ohms impedance.
• 5VA/1A = 5V• impedance = 5V/1A = 5Ω
• or
• At 5A CT• 5VA/5A• impedance = 1V/5A = 0.2 Ω
![Page 58: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/58.jpg)
Example
• CT ratio 300/1, core area 40x30 mm
• Voltage at knee point?
• V = 4.44 x 0.0018 x 300 x 50 = 120 V
• 1.5 x 40 x 30 x10-6 = 0.0018 Wb ( B for sheet steel, 1.5 tesla at knee point)
![Page 59: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/59.jpg)
CT open circuit
• If burden high, Es high– exceed Vkp (knee point voltage)• Io high ; I2 less
• Limited value when the secondary CT open circuit; I2 = 0;• Then N1I1 = N2 (I2+Io) = N2Io
• This will drive the CT to saturation level• dΦ/dt = 100 x Vkp (induced = 100 Vkp )• Cause insulation failure and overheated
![Page 60: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/60.jpg)
Current transformer equivalent circuit
Load (burden) R
x r
I0’
Ic’Im’
Ip’
Es
Is
Vs
(nominal ratio) Kn
npp KII / ' = nKII / 0 '0 =
Ip = primary current
I0 = primary excitation current (no load)
![Page 61: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/61.jpg)
Ip’
Current transformer equivalent circuit
Load (burden) R
x r
I0’
Ic’Im’Es
Is
Vs
θ
Ip’
Is
Ic’
Im’
I0’
Es
φ
'0
' III ps −=
'0 ' III sp +=
![Page 62: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/62.jpg)
relationship Es and φ (flux)
)2
sin(N s
πωωφ += te m
dtdNesφ =
tm ωφφ sin =
te ms ωωφ cosN =
N=no of turn in secondary
°∠= 902
N msE ωφ
![Page 63: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/63.jpg)
(Nominal Turn Ratio)• Determine from the given current ratio
– Eg.1000/5 (bar type)
1200rationominalKn ===
s
p
II
![Page 64: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/64.jpg)
Actual Ratio• Actual ratio value Ip and Is
s
pt
s
p
II
K
II
′×=
′×= ratiowindingratioactual
![Page 65: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/65.jpg)
• Winding ratio= secondary coil turn if transformer is of bar type l– Kt = N2/1
• Ideally
• Practically
1=′
s
p
II
1⟩′
s
p
II
Actual turn≥ nominal ratio
![Page 66: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/66.jpg)
CT error
• Current error or ratio error
• Phase error
• Composite error
![Page 67: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/67.jpg)
Ratio error or current error
100%ratio actualration actual-ratio nominal
error ratio ×=
Nominal ratio= Kn
Turn ratio= Kt
No compensation Kn=Kt
s
pt I
IK
′×=ratioactual
![Page 68: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/68.jpg)
Cont’d
'
'n
'
'
n
K
Kerrorratio
pt
pts
s
pt
s
pt
IK
IKI
II
K
II
K
−=
−=
%100error ratio '
'
×−
=p
ps
I
II
difference in magnitude between Ip’ and Is
Kn=Kt
(no compensation)
![Page 69: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/69.jpg)
Phase ErrorDifference in angle between Ip’ and Is
Phase error= θ
Ip’
Is
I0’
φIm’
θα
Es
![Page 70: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/70.jpg)
Compensating winding
• Secondary coil winding is reduced (1 or 2 turn) to compensate current error due by I0’.
• Secondary coil current will be high, but the value will be minimised by the excitation current component
• This can minimised the current error
![Page 71: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/71.jpg)
Example T1
• A current transformer 50 Hz has a secondary current of 3A,Sebuah• Secondary impedance circuit (0.6+j0.45),• Maximum flux 0.253 weber• Magnetisation current and core loss current (primary circuit) at this load
are 0.2 and 0.15 A respectively• Turn ratio1:10, assume no compensation• Determine no of turn, ratio error and phase error of transformer
![Page 72: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/72.jpg)
Ip’
CT equivalent circuit
Load (burden)
= 0.6+j0.45
r
I0’
Ic’Im’Es
Is=3 ∠ αº
Vs
θ
Ip’
Is
Ic’
Im’
I0’
Es
φ '0
' III ps −=
'0 ' III sp +=
npp KII / ' = nKII / 0 '0 =
α
![Page 73: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/73.jpg)
Is=3 ∠ αº
N1:N2 = 1:10
Im = 0.2 A
Ic = 0.15 A
°∠××
= 902
ωφmss
NE °+∠=°∠×°∠=
=
)87.36(25.287.3675.03
ααZIE ss
°=−=°=°+
13.5387.3690
90)87.36(α
α
Kt = 10 = Kn
Ip’
Is
I0’
φIm’
θα
Ic’
Es
![Page 74: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/74.jpg)
∴ N1:N2 = 4:40
40502253.0
225.2
25.22
=××
×=
=××
π
ωφ
s
ms
N
N
![Page 75: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/75.jpg)
Is=3 ∠ αº
Im = 0.2 A
Ic = 0.15 A
15.020.00 jI +=
015.002.0101)15.020.0(0
j
jI
+=
×+=′
°∠=°∠++=
+′=′
9975.52024.313.533015.0020.0
0
jIII sp
Ip’
Is
I0’φ
Im’
θ
Ic’
Es
![Page 76: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/76.jpg)
%794.0
%100024.3
024.33errorratio
−=
×−
=′
′+=
p
ps
I
II
1325.09975.5213.53errorphase
=−=
![Page 77: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/77.jpg)
Ex 1
• A current transformer has 15 turn on the primary and 75 turn on the secondary. The relay burden is (1.2+j2.6)Ω and secondary winding impedance of the transformer is (3.6+j0.4)Ω. If the magnitude of the secondary voltage is 26 volt and magnetization current referred to secondary is 0.24∠-45o amp. Determine the ratio error and phase error.
![Page 78: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/78.jpg)
Ex 2
• A new non compensated CT with a cross sectional area of 40 cm2 has a nominal ratio of 2000/5. When 5A is supplied to a relay, the combination of load relay and secondary winding impedance is (10+j5.77) Ω. If the magnetisation amp-turn is 100 and core loss amp-turn is 50, determine the ratio error and phase error. Using the same data, calculate also the compensating turn to reduce the ratio error to a minimum.
![Page 79: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/79.jpg)
Ex. 3
• A CT, 50 Hz has a primary winding of 10 turn and its cross sectional area is 8 cm2. Secondary current is 5A. The total load and secondary impedance is 0.8+j0.5 Ω. The excitation current required at the primary winding to establish a working flux with the secondary open is 0.6∠45o amp. If the flux density is 0.1878 wb/m2,determine the nominal ratio of the transformer. Determine also the ratio error and phase error of the transformer.
![Page 80: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/80.jpg)
Composite error
• BS 3938:1973– (r.m.s.) value; difference between ideal secondary
current (i.e CT is ideal ; no excitation component) with actual secondary current.
• Encompass (current error, phase error and harmonic effect)
![Page 81: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/81.jpg)
Accuracy limit current of a protection system CT
• Accuracy limit current (saturation current)– The maximum current a CT can sustain before
exceed its accuracy
– Specify either in term of primary current or secondary current
• Accuracy limit factor (saturation factor)– Ratio of accuracy limit primary current and
rated primary current
– Standard values are 5, 10, 15, 20 and 30
![Page 82: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/82.jpg)
CT specification
• Expressed in– VA at rated current /class accuracy/accuracy limit factor
– Burden standard rated values
• 2.5,5,7.5,10,15 and 30 VA
– 2 accuracy class: 5P and 10P – gives composite error at rated accuracy limit 5% and 10% respectively
– Standard accuracy limit factor:
• 5, 10, 15, 20 and 30
![Page 83: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/83.jpg)
Rating of CT
• Method to explain CT
– 10VA/5P/25
Accuracy limit current is 25 x rated current
Transformer works in good condition/reliably until 25 x its rated curentClass – error
do not exceed 5%
Rated burden
![Page 84: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/84.jpg)
Ex 1
• CT 10VA/5P/15
• Calculate the accuracy limit factor when the burden is half of its initial value.
• Secondary resistance of CT 0.15 ohm
![Page 85: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/85.jpg)
Solution
Es
r
Burden (R)
Burden impedance 10VA at rated current 5A
V
RI
IRIIVVA
2
=
××=×=
ohmR 4.0510 2 ==
![Page 86: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/86.jpg)
Solution
Es
r
Burden (R)V
Total impedance referred to secondary winding
= 0.15 + 0.4 = 0.55 ohm
Accuracy limit current= Accuracy limit factor × Rated current
A75515 currentlimit accuracy
=×=
Accuracy limit factor= ratio accuracy limit current and rated current
![Page 87: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/87.jpg)
VV
25.41750.55 emfsecondary
=×=
When burden is half
R = 0.2 ohm
Total secondary impedance= 0.15 + 0.2 = 0.35 ohm
Es
r
Burden (R=0.4)
![Page 88: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/88.jpg)
Smaller the burden, the higher the accuracy Therefore :
burden has to be low possible
A8.11735.0/25.41 current limit accuracy new
==
56.235/8.117factorlimit accuracy new
==
![Page 89: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/89.jpg)
CT Class X
• BS 3938 – CT for special application is known as Class “X’
• Expressed in turn ratio, knee point voltage, excitation current at the specified voltage and secondary winding resistance
– Application – scheme where the phase fault stability and/or accurate time grading required
• Transformer rating specify in term of e.m.f maximum that can be use by the transformer
• knee point– Point where an increase of 10% in secondary e.m.f require an addition of 50% excitation current
![Page 90: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/90.jpg)
Definition of knee point
Excitation voltage
Excitation current
+10%
+50%
Knee point
![Page 91: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/91.jpg)
Voltage transformer/potential transformer(VT/PT)
• Supply voltage lower than the sistem voltage
• Nominal sekunder voltage110V
• 2 types– Wound ( electromagnetic) type(> 132 kV non economical)– Capacitor type- CVT
• Element X and C consist of tuning circuit – to reduce the ratio and phase angle error secondary voltage
![Page 92: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/92.jpg)
1/ωC2 = ωL pd 50 Hz; V2 = V’
Vp
C1
C2
L
V2V’ Vs
Rb
Xb
V’ = 12 kV, C1 = 2000pF
Talian
C2 L
V’V2 110 V
![Page 93: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/93.jpg)
Protection techniques
• Protection scheme:– Arrangements of CT, VT, pilot wire and relay so
that the required operating characteristics can be obtained
• Each section of the power system network is monitored by several protection scheme.
![Page 94: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/94.jpg)
Main/primary scheme usually consists of:
Unit Scheme
Backup scheme consists of:
Non Unit Scheme
![Page 95: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/95.jpg)
Unit scheme
• ZONE OF PROTECTION IS WELL DEFINED
![Page 96: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/96.jpg)
Protected zone
R
R
FAULT:Non similar current flow in the relay CB will trip
CT CT
relay
P
Q
Pilot wire
Difference current scheme: circulating current
Unit protection scheme
![Page 97: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/97.jpg)
Protected zon
RFAULT:Current flow in circuit, result e1≠e2
CT
Differencec current scheme: voltage balance
R
Healthy and fault external zone (through fault):
No current in relay, e1=e2
e1 e2
![Page 98: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/98.jpg)
Balance power direction
R1 R2
PL P.LCT, PT
Relay
Trip
Restrain
Restrain
Trip
![Page 99: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/99.jpg)
R1 R2
Trip
Restrain
Restrain
Trip
Power flow entering the feeder (from point A) will cause relay (R1) close trip contact CB1
CB1 CB2
Power flow exit fron the feeder (at point B) will cause relay R2 rotate and close restrain contact of the further circuit breaker (remote) (CB1)
(relay R2 send restrain signal CB1)
A B
![Page 100: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/100.jpg)
R1 R2
Trip
Restrain
Restrain
Trip
Power enter at A and exit at B, block trip will prevent the CB from opening.
CB1 CB2
A B
![Page 101: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/101.jpg)
R1 R2
Trip
Restrain
Restrain
Trip
Power enter at A and at B (fault occurs), both CB open
CB1 CB2
A B
![Page 102: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/102.jpg)
R1 R2
Trip
Restrain
Restrain
Trip
Power enter at A and no power at B, circuit breaker A, CB1 will open
CB1 CB2
A B
![Page 103: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/103.jpg)
NON UNIT SCHEME
supervise/monitor one or several points in the power system
signal will be detected at the points
this signal is the input to the relay
section monitored/supervised is not clearly definedZONE OF PROTECTION IS NOT WELL DEFINED
![Page 104: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/104.jpg)
2 examples of non unit scheme(1.) Over Current Protection
(2.) Distance Protection
![Page 105: See4423 chapter1 introduction[1]](https://reader034.vdocuments.net/reader034/viewer/2022052208/554a220db4c9051b578b45dc/html5/thumbnails/105.jpg)
‘click here to add title
•Q & A