ENGLISH - 1/6 MI001351-I/E MI001351-I/E MI001351-I/E MI001351-I/E MI001351-I/E ENGLISH - 5/6 ENGLISH - 2/6 ENGLISH - 3/6 ENGLISH - 4/6 (*) The input filter slows down the response time to around 620 ms and guarantees the repeating of the disturbance signal at 50 / 60 Hz overlapping the measurement signal. Outp ut signa l Limit Over -range / F ault ±2,5 % Fault ±5 % 20 mA 20,4 mA 21 mA 4 mA 3,6 mA < 3,4 mA Electrical Connections Output Current Loop connection (regolated current). The use of shield cables is recommended for the electronic connections. Note: in order to reduce the instrument's dissipation, we recommend guaranteeing a load of > 250Ùto the current output. RTD 4 wires Connection 1 2 3 4 RTD 3 wires Connectio n 1 3 4 RTD 2 wires Connectio n 1 2 3 4 1200 800 400 0 RLoad=((U-5)/0.021) 5 10 15 20 25 30 Minimum Functioning Voltage (VDC) Diagram: Load Resistance vs Minimum Functioning Voltage RLoad (W) Highprecision 16 bit resolution Compact size Configuration by PC with KT120 dedicated software downloadable at www.seneca.it. Once the user has at his disposal the above listed accessories, the following parameters may be setStart and Full scale values. RTD Connection: 2 wires, 3 wires o 4 wires. 50 / 60 Hz Rejection (*): Disable or enable. Measurement filter: Disable or enable (1, 2 , 5 , 10, 30, 60 seconds). Output: Normal (4 - 20 mA) o Reversed (20 - 4 mA). RTD Type: PT100 or NI100. Cable Resistance Compensation for 2 wires measurement. Output signal in case of fault: towards the bottom of the output range or towards the top of the output range. Over-Range (**): NO (the fault alone causes a 2.5% over-range value) or YES ( a 2.5% It is besides possible the calibration of the output scale. J J J +    Iout RLoad 6 5 (**) See the table below for the corresponding values. T120 2 WIRE - LOOP POWERED TRANSMITTER FOR PT100 AND NI100 PROBES EN GeneralDescription The T120 instrument converts a temperature signal read by a PT100 (EN 60 751) or NI100 probe with connection by 2, 3 or 4 w ires into a signal normalised in current for 4 - 20 mA loop (2 wires technology). The module's main features are: Technical Features Measurement Range : Resistance Range : Minimum span : Current on sensor : Cable resistance : Connection : Resolution: -200 - +650 °C 18,5 Ù - 330 Ù 20 °C 750 m  A rated Max 25 Ù per wire 2, 3 or 4 wires 6 mW ~ PT100 Input- EN 60751/A2 (ITS-90) Measurement Range : Resistance Range : Minimum span : Current on sensor : Cable resistance : Connection : Resolution : -60 - +250 °C 69 Ù - 290 Ù 20 °C 750 m  A rated Max 25 Ù per wire 2, 3 or 4 wires 6 mW ~ NI100 Input 5 - 30 VDC 4 - 20 mA, 20 - 4 mA (2 wires t echnology) 1 kÙ @ 26 VDC, 21 mA (see on page 2, Load Resistance vs Minimum Functioning Voltage diagram) 1m  A (>14 bits) 102,5% of full scale value (see Table on Page 3) 105% of full scale value (see Table on Page 3) approximately 30 mA Operating Voltage : Current output : Load resistance : Resolution : Output in case of over- range : Output in case of fault : Current output protection : Output/Power Supply 50 Hz and 60 Hz (settable) Max of 0,1% (of measurement range) or 0,1 °C < 0,5 % 0,005 W/ W < 100 ppm, Typical : 30 ppm 100 ms (without 50/60 Hz Rejection) 300 ms (with 50/60 Hz Rejection) < 220 ms (without 50/60 Hz Rejection) < 620 ms (with 50/60 Hz Rejection) IP20 Other Features Network freq. Rejection : Transmission error : Error caused by EMI (*) Influence of cable resistance : Temperature Coefficient : SamplingTime: Response time (10..90 %) : Protection Index : St an d ar ds : EN6 10 00 - 6- 4 /2 00 2 -1 0 (e l ec tr om a gn et icemis s io n, industrial surroundings ) EN61000-6-2/20 06-10 (electromagn etic immunity, industrial surroundings ) Operating Conditions : StorageTemperature: Connections : Conductor Section : Wire stripping : Box: Dimensions : Temperature -40 - +85 °C Humidity 30 - 9 0 % at 40°C (non-conden sing)  Altitude: up to 2000 m.a.s.l -40 - +105 °C Springterminals 2 0,2..2,5 mm 8 mm Nylon / glass, (black colour) 20.0 mm x f 40.0 mm (*) EMI: electromagne tic interferences. The instrument leaves the factory with the following configuration (except for other indications on the box): RTDwiring Inputfilter ReversedOutput RTD Type MeasurementRangeStart Measurement Full- Scale Output signal in case of fault Over-Range 3 wires Enable NO PT100 0 °C 100 °C Towards the top of the output range YES: a 2.5% over-range value is acceptable; a 5% over-range value is considered a fault. Custumized Setting by PC and accessories Factory setting Input The module accepts input from a PT100 (EN 60 751) or NI100 temperature probe with connection by 2, 3 or 4 wires. The use of shield cables is recommended for the electronic connections. 2-wire connection This is the connection to be used for short distances ( < 10 m) between module and probe, bearing in mind that it adds an error (which may be removed by sofware programming) equivalent to the resistance contributed by the connection cables to the measurement. The module has to be programmed by PC for 2 wires connection. 3-wire connection This is the connection to be used for media-long distances ( > 10 m ) between module and probe. The instrument performs compensation for the resistance of the connection cables. In order for compensation to be correct, it is necessary that the resistance values of each conductors be the same because in order to perform compensation the instrument measures the resistance of only one conductor and assumes the resistance of the others conductors to be exactly the same. The module has to be programmed by PC for 3 wires connection. The configuration by PC use (see the drawing below) is possible with the following accessories: S117P: USB to RS232/TTL PM002411: connection cable between S117P and T120 KT120:Dedicatedprogrammingsoftware. The module may be programmed even if it is not supplied by the 4..20 mA loop, since the power supply is provided through the programming connector. Frontal Side: Terminals Position and Enumeration 4-wire connection This connection to be used for media-long distances ( > 10 m ) between module and probe. Provides the maximum precision because the instrument measure the resistance of the sensor independently of  the resistance of the connection cables. The module has to be programmed by PC for 4 wires connection. 1. Raising the plastic protection using the appropriate slot. 2. Move the plastic protective as in the drawing. Programming connector This document is property of SENECA srl. Duplication and reprodution are forbidden, if not authorized. Contents of the present documentation refers to products and technologies SENECA s.r.l. Via Germania, 34 - 35127 - Z.I. CAMIN - PADOVA- ITALY Tel. +39.049.8705355 - 8705359 - Fax +39.049.8706287 e-mail: info@seneca .it - www.seneca.it ISO9001-2000 MI001351-I/E ENGLISH - 6/6 Pattern of connecting terminal with push-wire connection Smaltimento dei rifiuti elettrici ed elettronici (applicabile nell’Unione Europea e negli altri paesi con servizio di raccolta differenziata). Il simbolo presente sul prodotto o sulla sua confezione indica che il prodotto non verrà trattato come rifiuto domestico. Sarà invece consegnato al centro di raccolta autorizzato per il riciclo dei rifiuti elettrici ed elettronici.  Assicurandovi che il prodotto venga smaltito in modo adeguato, eviterete un potenziale impatto negativo sull’ambiente e la salute umana, che potrebbe essere causato da una gestione non conforme dello smaltimento del prodotto. Il riciclaggio dei materiali contribuirà alla conservazione delle Size and dimensions      4      4  ,      0     m     m      1      6  ,      6     m     m      2      0  ,      0     m     m

Upload: salvador-castellanos-leon

Post on 06-Apr-2018

246 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Seneca t120 Manual

8/2/2019 Seneca t120 Manual

http://slidepdf.com/reader/full/seneca-t120-manual 1/1

ENGLISH - 1/6MI001351-I/E

MI001351-I/E MI001351-I/E

MI001351-I/E MI001351-I/E ENGLISH - 5/6

ENGLISH - 2/6

ENGLISH - 3/6

ENGLISH - 4/6

(*) The input filter slows down the response time to around 620 ms and guarantees therepeating of the disturbance signal at 50 / 60 Hz overlapping the measurement signal.

Output signal Limit Over-range / Fault ± 2,5 % Fault ± 5 %20 mA 20,4 mA 21 mA4 mA 3,6 mA < 3,4 mA

Electrical Connections

Output Current Loop connection (regolated current).

The use of shield cables is recommended for the electronic connections.

Note: in order to reduce the instrument's dissipation, we recommend guaranteeing a loadof > 250Ù to the current output.

RTD 4 wires Connection

1

2

3

4

RTD 3 wires Connection

1

3

4

RTD 2 wires Connection

1

2

3

4

1200

800

400

0

RLoad=((U-5)/0.021)

5 10 15 20 25 30

Minimum Functioning Voltage (VDC)

Diagram: Load Resistance vs Minimum Functioning Voltage

RLoad (W)

%High precision%16 bit resolution%Compact size%Configuration by PC with KT120 dedicated software downloadable atwww.seneca.it.

Once the user has at his disposal the above listed accessories, the following parametersmay be setStart and Full scale values.

%RTD Connection: 2 wires, 3 wires o 4 wires.

%50 / 60 Hz Rejection (*): Disable or enable.

%Measurement filter: Disable or enable (1, 2 , 5 , 10, 30, 60 seconds).

%Output: Normal (4 - 20 mA) o Reversed (20 - 4 mA).%RTD Type: PT100 or NI100.

%Cable Resistance Compensation for 2 wires measurement.

%Output signal in case of fault: towards the bottom of the output range or towards the top of the output range.%Over-Range (**): NO (the fault alone causes a 2.5% over-range value) or YES ( a 2.5%

It is besides possible the calibration of the output scale.

J J J

   -U

Iout

RLoad6

5

(**) See the table below for the corresponding values.

T1202 WIRE - LOOP POWERED TRANSMITTER FOR PT100 AND NI100 PROBESEN

General DescriptionThe T120 instrument converts a temperature signal read by a PT100 (EN 60 751)or NI100 probe with connection by 2, 3 or 4 w ires into a signal normalised in currentfor 4 - 20 mA loop (2 wires technology).The module's main features are:

Technical Features

Measurement Range :Resistance Range :Minimum span :Current on sensor :Cable resistance :

Connection :Resolution:

-200 - +650 °C

18,5 Ù - 330 Ù20 °C

750 m A rated

Max 25 Ù per wire

2, 3 or 4 wires6 mW~

PT100 Input- EN 60751/A2 (ITS-90)

Measurement Range :Resistance Range :Minimum span :Current on sensor :Cable resistance :Connection :Resolution :

-60 - +250 °C69 Ù - 290 Ù20 °C

750 m A ratedMax 25 Ù per wire2, 3 or 4 wires

6 mW~

NI100 Input 

5 - 30 VDC

4 - 20 mA, 20 - 4 mA (2 wires t echnology)

1 kÙ @ 26 VDC, 21 mA (see on page 2, Load Resistance vs Minimum Functioning Voltagediagram)

1m A (>14 bits)102,5% of full scale value (see Table on Page 3)

105% of full scale value (see Table on Page 3)approximately 30 mA

Operating Voltage :Current output :Load resistance :

Resolution :Output in case of over-range :Output in case of fault :Current output protection :

Output/Power Supply 

50 Hz and 60 Hz (settable)Max of 0,1% (of measurement range) or 0,1 °C< 0,5 %

0,005W /W< 100 ppm, Typical : 30 ppm100 ms (without 50/60 Hz Rejection)300 ms (with 50/60 Hz Rejection)< 220 ms (without 50/60 Hz Rejection)< 620 ms (with 50/60 Hz Rejection)

IP20

Other Features

Network freq. Rejection :Transmission error :Error caused by EMI (*)Influence of cable resistance :Temperature Coefficient :Sampling Time:

Response time (10..90 %) :

Protection Index :

S ta nd ards : E N6 10 00 -6 -4 /2 00 2-10 (el ec tr om ag ne ti c e mi ss io n,industrial surroundings)EN61000-6-2/2006-10 (electromagnetic immunity,industrial surroundings)

Operating Conditions :

Storage Temperature:Connections :Conductor Section :Wire stripping :Box:Dimensions :

Temperature -40 - +85 °CHumidity 30 - 90 % at 40°C (non-condensing) Altitude: up to 2000 m.a.s.l-40 - +105 °CSpring terminals

20,2..2,5 mm8 mmNylon / glass, (black colour)

20.0 mm x f 40.0 mm

(*) EMI: electromagnetic interferences.

The instrument leaves the factory with the following configuration (except for other indications on the box):

RTD wiringInput filter Reversed OutputRTD TypeMeasurement Range StartMeasurement Full- ScaleOutput signal in case of faultOver-Range

3 wiresEnableNOPT1000 °C100 °CTowards the top of the output rangeYES: a 2.5% over-range value is acceptable;a 5% over-range value is considered a fault.

Custumized Setting by PC and accessories

Factory setting 

Input The module accepts input from a PT100 (EN 60 751) or NI100 temperature probe withconnection by 2, 3 or 4 wires.

The use of shield cables is recommended for the electronic connections.

2-wire connectionThis is the connection to be used for short distances ( < 10 m) between module and probe,bearing in mind that it adds an error (which may be removed by sofware programming)equivalent to the resistance contributed by the connection cables to the measurement.The module has to be programmed by PC for 2 wires connection.

3-wire connectionThis is the connection to be used for media-long distances ( > 10 m ) between module andprobe. The instrument performs compensation for the resistance of the connection cables.In order for compensation to be correct, it is necessary that the resistance values of eachconductors be the same because in order to perform compensation the instrumentmeasures the resistance of only one conductor and assumes the resistance of the othersconductors to be exactly the same.The module has to be programmed by PC for 3 wires connection.

The configuration by PC use (see the drawing below) is possible with the followingaccessories:S117P: USB to RS232/TTLPM002411: connection cable between S117P and T120KT120: Dedicated programming software.The module may be programmed even if it is not supplied by the 4..20 mA loop, since thepower supply is provided through the programming connector.

Frontal Side: Terminals Position and Enumeration

4-wire connectionThis connection to be used for media-long distances ( > 10 m ) between module and probe.Provides the maximum precision because the instrument measure the resistance of thesensor independently of  the resistance of the connection cables .

The module has to be programmed by PC for 4 wires connection.

1. Raising the plasticprotection usingthe appropriate slot.

2. Move the plasticprotective as in thedrawing.

Programming connector 

This document is property of SENECA srl. Duplication and reprodution are forbidden, if notauthorized. Contents of the present documentation refers to products and technologies

SENECA s.r.l.Via Germania, 34 - 35127 - Z.I. CAMIN - PADOVA- ITALYTel. +39.049.8705355 - 8705359 - Fax +39.049.8706287e-mail: [email protected] - www.seneca.it

THEINTERNATI

ONALCERTIFICATION NETWORKR

ISO9001-2000

MI001351-I/E ENGLISH - 6/6

Pattern of connecting terminal with push-wire connection

Smaltimento dei rifiuti elettrici ed elettronici (applicabile nell’UnioneEuropea e negli altri paesi con servizio di raccolta differenziata).

Il simbolo presente sul prodotto o sulla sua confezione indica che il prodottonon verrà trattato come rifiuto domestico. Sarà invece consegnato al centrodi raccolta autorizzato per il riciclo dei rifiuti elettrici ed elettronici.

 Assicurandovi che il prodotto venga smaltito in modo adeguato, eviterete unpotenziale impatto negativo sull’ambiente e la salute umana, che potrebbeessere causato da una gestione non conforme dello smaltimento delprodotto. Il riciclaggio dei materiali contribuirà alla conservazione delle

Size and dimensions

     4     4 ,     0    m    m

     1     6 ,     6    m    m

     2     0 ,     0    m    m