SEPTEMBER 2014
Elevator QEI / Maintenance
Performance Report
PASSENGER ELEVATORS 1 AND 2
CALHOUN GREENWAY APARTMENTS
3140 CHOWEN AVENUE
MINNEAPOLIS, MN
FOR: BIGOS MANAGEMENT, INC.
8325 WAYZATA BLVD, SUITE 200
GOLDEN VALLEY, MN 55426
BY: ELEVATOR CONSULTING SERVICES, INC.
BIGOS MANAGEMENT, INC.
NI- NEEDS IMPROVEMENT 2 CALHOUN GREENWAY-BUILDING 3140
OK- ACCEPTABLE SEPTEMBER 2014 QEI/MAINTENANCE REVIEW
KEY
UNSAT Unsatisfactory NW Not Working
NC Not Checked NA Not Applicable
OK Satisfactory NI Needs Improvement
ITEMS IN RED ARE THE ELEVATOR CONTRACTOR’S RESPONSIBILITY
ITEMS IN BLUE ARE THE BUILDING’S RESPONSIBILITY
BIGOS MANAGEMENT, INC.
NI- NEEDS IMPROVEMENT 3 CALHOUN GREENWAY-BUILDING 3140
OK- ACCEPTABLE SEPTEMBER 2014 QEI/MAINTENANCE REVIEW
Equipment Inventory -- Main Machine Room
Control Type: SELECTIVE COLLECTIVE DUPLEX
Contract Speed: 125 FPM
Machine Type: SCHUMACHER PUMP UNIT
SCHUMACHER CONTROLLER
Door Equipment: GAL MOVFR
Door Size/Type: 36” WIDE X 84” HIGH-1SSS
Number of Openings: FIVE (5)
Travel: 36’-27’ ABOVE *1
Floors Served: G, *1, 2, 3, 4
City/ State Number: ELEVATOR #1- 72989.3533
MN ELEVATOR #2- 72990.3534
Capacity: 2000 LBS
Fire Service Log: OK
Maintenance Log: OK
Oil Monitoring Log: OK
MSDS Documentation: YES OILS, SOLVENTS, LUBRICANTS
Inspector’s Key Box: YES
Inspector’s Keys: YES
Service Vendor: SCHUMACHER
BIGOS MANAGEMENT, INC.
NI- NEEDS IMPROVEMENT 4 CALHOUN GREENWAY-BUILDING 3140
OK- ACCEPTABLE SEPTEMBER 2014 QEI/MAINTENANCE REVIEW
PERFORMANCE
ELEVATOR 1 2 Speed Up: 125 FPM 125 FPM
Speed Down: 125 FPM 125 FPM
Perform Up: 16.5 SEC 16.0 SEC
Perform Down: 17.0 SEC 17.0 SEC
Door Open: 3.0 SEC 3.0 SEC
Door Close: 3.3 SEC 3.5 SEC
Car Call Dwell: 4.0 SEC 4.0 SEC
Hall Call Dwell: 5.0 SEC 5.0 SEC
Nudging: 25 SEC 25 SEC
REDUCED TORQUE REDUCED TORQUE
Door Pressure 8 LBS 10 LBS
Ride Quality
Ride: OK OK
Deceleration Up: OK OK
Deceleration Down: OK OK
Noise: OK OK
Acceleration Up: OK OK
Acceleration Down: OK OK
Stop: OK OK
Leveling: OK OK
BIGOS MANAGEMENT, INC.
NI- NEEDS IMPROVEMENT 5 CALHOUN GREENWAY-BUILDING 3140
OK- ACCEPTABLE SEPTEMBER 2014 QEI/MAINTENANCE REVIEW
Equipment Room
Access: OK
Headroom: OK
Enclosure: OK
Lighting: OK
Cleanliness: OK
Air Circulation, Ventilation: OK
A.C.
Pipes, Ducts, Non-Elevator : OK
Parts: MINOR
GFIC Receptacle: YES
Fire Extinguisher: OK
11/2013
Guarding: OK
Self Closing, Locking door: OK
Numbering of Units: OK
Sprinkler in Room: NO
Lockable, fused disconnect: OK
110 Volt Disconnect: YES
Earth Ground: OK
Shunt Trip Protection: NO
Shunt Trip Monitored: N/A
BIGOS MANAGEMENT, INC.
NI- NEEDS IMPROVEMENT 6 CALHOUN GREENWAY-BUILDING 3140
OK- ACCEPTABLE SEPTEMBER 2014 QEI/MAINTENANCE REVIEW
Equipment Room Continued
Signage on Door: NI
ACCESS DOOR TO MACHINE ROOM
Oil Line Shut Off: YES
Smoke Detector: YES
Emergency Evacuation Guide: YES
BIGOS MANAGEMENT, INC.
NI- NEEDS IMPROVEMENT 7 CALHOUN GREENWAY-BUILDING 3140
OK- ACCEPTABLE SEPTEMBER 2014 QEI/MAINTENANCE REVIEW
Control Panel
ELEVATOR 1 2 Type of Control: S.S. LOGIC S.S. LOGIC
MAnufacturer: SCHUMACHER SCHUMACHER
Installation Date: 07/01/2011 08/08/2011
Installation Code: A 17.1 2005 A 17.1 2005
Controller Data Tag: YES YES
Cleanliness: GOOD GOOD
Identification: JOB #: SO-20029 SO-230030
SERIAL #: 20029 ?
Software Version: NC NC
Guarding: OK OK
U.L. / CSA Labeled: YES YES
CSA CSA
Fire Service Alternate Floor: YES YES
BIGOS MANAGEMENT, INC.
NI- NEEDS IMPROVEMENT 8 CALHOUN GREENWAY-BUILDING 3140
OK- ACCEPTABLE SEPTEMBER 2014 QEI/MAINTENANCE REVIEW
Components
ELEVATOR 1 2 Relays: OK OK
Enclosure/Open Style: ENCLOSED ENCLOSED
Contacts: OK OK
Resistors: OK OK
P.C. Boards/Timers: OK OK
Wiring: OK OK
Performance: NC NC
Camera Wire: NO NO
Telephone: YES YES
Phone Number: 612.952.7804 612.952.7804
Programmed Site: SCHUMACHER SCHUMACHER
BIGOS MANAGEMENT, INC.
NI- NEEDS IMPROVEMENT 9 CALHOUN GREENWAY-BUILDING 3140
OK- ACCEPTABLE SEPTEMBER 2014 QEI/MAINTENANCE REVIEW
Starters
ELEVATOR 1 2 Type: S.S. S.S.
Size: E03 E03
Manufacturer: SIEMENS SIEMENS
Contacts: OK OK
Wiring: OK OK
Mounting: OK OK
Phase Protection: YES YES
Up Starts: 03-2012 65,641 63,330
09/12/2012 95,825 111,491
03/07/2013 119,720 161,698
09/12/2013 146,384 225,264
03/25/2014 171,448 277,461
09/20/2014 195,337 332,101
BIGOS MANAGEMENT, INC.
NI- NEEDS IMPROVEMENT 10 CALHOUN GREENWAY-BUILDING 3140
OK- ACCEPTABLE SEPTEMBER 2014 QEI/MAINTENANCE REVIEW
Battery Rescuvator
ELEVATOR 1 2 Manufacturer: SCHUMACHER SCHUMACHER
Model: N/A N/A
Serial #: N/A N/A
Battery: EATON EATON
Wiring: OK OK
Operational: YES YES
BIGOS MANAGEMENT, INC.
NI- NEEDS IMPROVEMENT 11 CALHOUN GREENWAY-BUILDING 3140
OK- ACCEPTABLE SEPTEMBER 2014 QEI/MAINTENANCE REVIEW
Pump Unit
ELEVATOR 1 2 Manufacturer: SCHUMACHER SCHUMACHER
Model: N/A N/A
Cleanliness: OK OK
Leaks: OK OK
Noise: OK OK
Sheave : N/A N/A
Belts: N/A N/A
Hose Condition: N/A N/A
Oil Level: OK OK
Oil: OK OK
Pump: OK OK
Oil Line Shut Offs: YES YES
Subm / Dry: SUB SUB
Valves: OK OK
MAXTON UC 4 MAXTON UC 4
Muffler: YES YES
Seals: OK OK
Covers: OK OK
Annual No Load Test: OK OK
Tagged: 10/09/2013 10/09/2013
BIGOS MANAGEMENT, INC.
NI- NEEDS IMPROVEMENT 12 CALHOUN GREENWAY-BUILDING 3140
OK- ACCEPTABLE SEPTEMBER 2014 QEI/MAINTENANCE REVIEW
Motor
ELEVATOR 1 2 Manufacturer: IMPERIAL IMPERIAL
Type: ES ES
Isolation: OK OK
Grounded: OK OK
Bearings: OK OK
Covers: OK OK
Frame: 217Z 217Z
HP: 25 25
RPM: 3400 3400
AMPS: 78.2 78.2
Starts/Hour: 80 80
NEMA Code: A A
BIGOS MANAGEMENT, INC.
NI- NEEDS IMPROVEMENT 13 CALHOUN GREENWAY-BUILDING 3140
OK- ACCEPTABLE SEPTEMBER 2014 QEI/MAINTENANCE REVIEW
Hoistway
ELEVATOR 1 2 Selector Car Top Device SCHUMACHER STS-1
Cleanliness: OK OK
Sensors: OK OK
Tape Guides: OK OK
Tape: OK OK
Limit Switches
Roller Noise OK OK
Operation: OK OK
Type: EEC EEC
Rails
Cleanliness: OK OK
Lubrication: N/A N/A
Type: T-8 LBS T-8 LBS
Fastening: OK OK
Solid/Roller Guide: ROLLER-OTIS ROLLER
BIGOS MANAGEMENT, INC.
NI- NEEDS IMPROVEMENT 14 CALHOUN GREENWAY-BUILDING 3140
OK- ACCEPTABLE SEPTEMBER 2014 QEI/MAINTENANCE REVIEW
Cable Condition
ELEVATOR 1 2 Traveling: OK OK
NEOPRENE NEOPRENE
Suspension: OK OK
Spares: OK OK
Kellum Grips: YES YES
TAPED TAPED
Hoist Cables: N/A N/A
Shackles: N/A N/A
Hoistway Venting
Existing: YES
Motorized: NO
Key Switch: NO
Safety Bars: OK
Size (3%) YES
BIGOS MANAGEMENT, INC.
NI- NEEDS IMPROVEMENT 15 CALHOUN GREENWAY-BUILDING 3140
OK- ACCEPTABLE SEPTEMBER 2014 QEI/MAINTENANCE REVIEW
Hoistway Equipment
ELEVATOR 1 2 Car Top
Cleanliness: OK OK
Maintenance Station: OK OK
Stop Switch: OK OK
Data Plate: YES YES
Light: OK OK
Light Guard: OK OK
Guides: OK OK
GFIC Receptacles: OK OK
Escape Hatch Locked: OK OK
Windows in Hoistway: NO NO
Multiple Hoistways: NO NO
Car Top Railing: N/A N/A
Stenciled: YES YES
BIGOS MANAGEMENT, INC.
NI- NEEDS IMPROVEMENT 16 CALHOUN GREENWAY-BUILDING 3140
OK- ACCEPTABLE SEPTEMBER 2014 QEI/MAINTENANCE REVIEW
Door Operator
ELEVATOR 1 2
Type: GAL MOVFR GAL MOVFR
Cleanliness: OK OK
Door Protection: SCANNER SCANNER
Lubrication: OK OK
Belts: OK OK
Chains: OK OK
Hangers: OK OK
Arms: OK OK
Bearings: OK OK
Noise: OK OK
Tracks: OK OK
Upthrust: OK OK
Restrictor: OK OK
Gibs: OK OK
BIGOS MANAGEMENT, INC.
NI- NEEDS IMPROVEMENT 17 CALHOUN GREENWAY-BUILDING 3140
OK- ACCEPTABLE SEPTEMBER 2014 QEI/MAINTENANCE REVIEW
Car Enclosure
Ventilation: OK
FAN
Walls: FORMICA TOP
STAINLESS STEEL BOTTOM
Returns: STAINLESS STEEL
Car Lighting: OK
SUSPENDED 3 PANELS
Ceiling: OK
Position Indicators: LED
Handrail/Bumpers: 1-BACKWALL @ 32”-ROUND S.S.
Flooring: TILE
Car Doors: STAINLESS STEEL
Sills: ALUMINUM
Platform: STEEL
Certificate Frame: NO
Car Riding Lantern: YES
Camera: NO
Card Reader: NO
BIGOS MANAGEMENT, INC.
NI- NEEDS IMPROVEMENT 18 CALHOUN GREENWAY-BUILDING 3140
OK- ACCEPTABLE SEPTEMBER 2014 QEI/MAINTENANCE REVIEW
Entrance Equipment
ELEVATOR 1 2 Cleanliness OK OK
Lubrication: OK OK
Tracks: OK OK
Hangers: OK OK
Gibs: OK OK
Interlocks: OK OK
Clutch Release Rollers: OK OK
Clutch Release Assemblies: OK OK
Noise: OK OK
Upthrusts: OK OK
Closers / Spirators: OK OK
Braille: OK OK
Sills: OK OK
Running Clearance: OK OK
1 13/8” 1 3/8”
Sills: OK OK
Escutcheons: YES YES
Star of Life: NO NO
Identification Tactile: YES YES
BIGOS MANAGEMENT, INC.
NI- NEEDS IMPROVEMENT 19 CALHOUN GREENWAY-BUILDING 3140
OK- ACCEPTABLE SEPTEMBER 2014 QEI/MAINTENANCE REVIEW
Emergency Fire Box
Main Egress Landing: 1st FLOOR
Existing in Lobby: YES
Machine Room Key: YES
Phase I, II Keys: YES
Lunar Key: YES
Keys Tagged: YES
BIGOS MANAGEMENT, INC.
NI- NEEDS IMPROVEMENT 20 CALHOUN GREENWAY-BUILDING 3140
OK- ACCEPTABLE SEPTEMBER 2014 QEI/MAINTENANCE REVIEW
Fixtures
Car Operating Panel
Type: INNOVATION
Style: N/A
Condition: GOOD
Illuminated: YES
Height Compliance: OK
Braille Identification: YES
Buttons: YES
Phone (HELP): A. D. A. COMPLIANT
Phone Monitored : SCHUMACHER
Call Back Number : 612-925-7804
Alarm Button: OK
Stop Switch: OK
KEYED
Emergency Light: OK
Capacity Plate/Engraved: OK
Certificate Frame: NO
Certificate: YES
Independent Service: YES
BIGOS MANAGEMENT, INC.
NI- NEEDS IMPROVEMENT 21 CALHOUN GREENWAY-BUILDING 3140
OK- ACCEPTABLE SEPTEMBER 2014 QEI/MAINTENANCE REVIEW
Service Cabinet
Light Switch: YES
TOGGLE
Fan Switch: YES
TOGGLE
Independent Service: NO
Access Enable: N/A
Emergency Light Test: YES
BUTTON
Inspection: YES
KEYED
Stop Switch N/A
GFI Outlet: YES
BIGOS MANAGEMENT, INC.
NI- NEEDS IMPROVEMENT 22 CALHOUN GREENWAY-BUILDING 3140
OK- ACCEPTABLE SEPTEMBER 2014 QEI/MAINTENANCE REVIEW
Fire Service Cabinet
Fire Fighters Instructions: YES
Phase II key Switch: YES
3 POSITION
OFF / HOLD / ON
Call Cancel Button: YES
Stop Switch: YES
TOGGLE
Fire Hat: OK
Phone Jacks: NO
Door Open Front: YES
Door Open Rear: N/A
Door Close Front: YES
Door Close Rear: N/A
BIGOS MANAGEMENT, INC.
NI- NEEDS IMPROVEMENT 23 CALHOUN GREENWAY-BUILDING 3140
OK- ACCEPTABLE SEPTEMBER 2014 QEI/MAINTENANCE REVIEW
Hall Buttons
Type: INNOVATION
Condition: GOOD
Illuminated: OK
Height: OK
Mechanical: OK
Lanterns: CAR ONLY
Fire Signage: OK
Phase I Key Switch: YES
Phase I Instructions: YES
Fire Hat / Indicator Light: YES
Vent Key: NO
Vent Light: N/A
Main Lobby Panel: NO
Concealed Riser: NO
Card Reader(s): NO
BIGOS MANAGEMENT, INC.
NI- NEEDS IMPROVEMENT 24 CALHOUN GREENWAY-BUILDING 3140
OK- ACCEPTABLE SEPTEMBER 2014 QEI/MAINTENANCE REVIEW
Main Lobby Panel
Existing: NO
Location: N/A
Position Indicators: N/A
Emergency Power Key Switch: N/A
Emergency Power Independent Light: N/A
Fire Service Key Switch: N/A
Selection Switch: N/A
BIGOS MANAGEMENT, INC.
NI- NEEDS IMPROVEMENT 25 CALHOUN GREENWAY-BUILDING 3140
OK- ACCEPTABLE SEPTEMBER 2014 QEI/MAINTENANCE REVIEW
Pit Equipment
ELEVATOR 1 2 Cleanliness: OK OK
Car Buffer: OK OK
Counter Weight Buffer: N/A N/A
Lights: OK OK
Light Switch: OK OK
Light Guards: OK OK
Stop Switch: YES YES
Ladder: OK OK
GFIC Receptacles: OK OK
Jack Seal: OK OK
PVC Liner: NONE NONE
Oil Line Shut Off: YES YES
Piston Pan: NO NO
Piston: OK OK
Rupture Valves: NO NO
High Pressure Vics: NO NO
Sump Hole/Drain: NO NO
Sump Pump: NO NO
Sump Pump Cover: NO NO
Pit Bucket: OK OK
Sprinkler: NO NO
BIGOS MANAGEMENT, INC.
NI- NEEDS IMPROVEMENT 26 CALHOUN GREENWAY-BUILDING 3140
OK- ACCEPTABLE SEPTEMBER 2014 QEI/MAINTENANCE REVIEW
Pit Equipment Continued
ELEVATOR 1 2 Heat Head: NO NO
Smoke Head: NO NO
Scavenger Pump: NO NO
Bottom Access: YES OK
+LUNAR KEY
Runby: OK OK
Oil Return/Jack Line: NO NO
Governor Sheaves: N/A N/A
Cables: N/A N/A
Cable Ties: N/A N/A
BIGOS MANAGEMENT, INC.
NI- NEEDS IMPROVEMENT 27 CALHOUN GREENWAY-BUILDING 3140
OK- ACCEPTABLE SEPTEMBER 2014 QEI/MAINTENANCE REVIEW
Bottom of Car
ELEVATOR 1 2 Cleanliness: OK OK
Static Weights: NO NO
Safeties: N/A N/A
Traveling Cable Suspension: OK OK
Toe Guard Length: OK OK
21” 21”
Toe Guard Stenciled: YES YES
Isolation: OK OK
Light Fixture: OK OK
Light Guard: OK OK
Slide/Roller Guides: ROLLER ROLLER
OTIS OTIS
Receptacle: YES YES
GFI Receptacle: YES YES
Platform-Fire Rated: YES YES
BIGOS MANAGEMENT, INC.
NI- NEEDS IMPROVEMENT 28 CALHOUN GREENWAY-BUILDING 3140
OK- ACCEPTABLE SEPTEMBER 2014 QEI/MAINTENANCE REVIEW
CALHOUN GREENWAY APARTMENTS
BUILDING 3140-DUPLEX ELEVATORS 1 AND 2
MAINTENANCE CORRECTIVE ITEMS
The following minimum items need corrective action taken:
Annual No Load Test: 10/09/2013
NONE
BIGOS MANAGEMENT, INC.
NI- NEEDS IMPROVEMENT 29 CALHOUN GREENWAY-BUILDING 3140
OK- ACCEPTABLE SEPTEMBER 2014 QEI/MAINTENANCE REVIEW
CALHOUN GREENWAY APARTMENTS
BUILDING 3140-DUPLEX ELEVATORS 1 AND 2
RECOMMENDED IMPROVEMENTS
1. An “Access to Machine Room” sign is needed in G-Level Lobby.
Items in blue should receive higher consideration or priority of adoption. These are mandated by
code for compliance and should be completed as soon as possible.
BIGOS MANAGEMENT, INC.
NI- NEEDS IMPROVEMENT 30 CALHOUN GREENWAY-BUILDING 3140
OK- ACCEPTABLE SEPTEMBER 2014 QEI/MAINTENANCE REVIEW
CALHOUN GREENWAY
BUILDING 3140-DUPLEX ELEVATORS 1 AND 2
ADA RECOMMENDATIONS
RULE 4.10.3 HALL CALL BUTTON EXISTING DOES MEET REQUIREMENTS
RULE 4.10.4 HALL LANTERNS/CDI’S EXISTING DOES MEET REQUIREMENTS
RULE 4.10.5 BRAILLE EXISTING DOES MEET REQUIREMENTS
RULE 4.10.6 DOOR PROTECTION & REOPENING EXISTING DOES MEET REQUIREMENT
RULE 4.10.10 FLOOR SURFACE EXISTING DOES MEET REQUIREMENTS
RULE 4.10.11 LIGHT LEVEL IN CAB EXISTING DOES MEET REQUIREMENTS FOR LUMENS
RULE 4.10.12 CAR CONTROLS EXISTING DOES MEET REQUIREMENTS FOR STYLE AND HEIGHT
RULE 4.10.13 CAR POSITION INDICATORS – NO PI’S EXISTING DOES MEET REQUIREMENTS
RULE 4.10.14 EMERGENCY COMMUNICATIONS EXISTING DOES MEET MINIMUM REQUIREMENTS
RULE NEII -12 HANDRAILS EXISTING DOES MEET REQUIREMENTS.