    PCB

    PARAMETRIZATION

    Instructions for SERVICE

    UPDATES:

    20/08/2012 2edition PCB sof tware version V3.5.0-89 or higher

  • 8/10/2019 SERVICE Luna Platinum Ed 8

    2/42

    CONTENTS

    1 CONTROL PANEL MENU.................................................................................................................................... 3

    1.1 ENGINEERMENU.......................................................... ........................................................... ....................... 3

    2 PARAMETER LIST................................................................................................................................................ 4

    3 ERROR LIST......................................................................................................................................................... 28

    4 GAS ADAPTIVE SYSTEM.................................................. ........................................................... ..................... 33

    5

    FAULT FINDING......................................................... ........................................................... ............................... 34

    6 BURNER PHASE (FAULT HISTORY)............................................................................................................. . 54

  • 8/10/2019 SERVICE Luna Platinum Ed 8

    3/42

    1 CONTROL PANEL MENU

    The following procedure is used to access the four boiler pro- gramming menus:

    from the main menu C; A e C for approx. 6 seconds; B to see menus 1 - 2 - 3 - 4; B to confirm the selected menu; C to go back one menu at a time to the main menu.

    The four menus are:

    1 ENDUSER (visible pressing the button C)2 COMMISSIONING (visible with a buttons combination)3 ENGINEER (visible only with PASSWORD 10101)

    4 OEM (visible only with PASSWORD)

    1.1 ENGINEER menu

    Access Engineermenu as described in section 1.This level includes all parameters present on Enduser and Commissioning menus.The details of this menu are given in next section.Some menus are avaible only if the system is correctly configured (e.g. solar menu).The parameters with grey underlight are different default values depending on boilermodel.

  • 8/10/2019 SERVICE Luna Platinum Ed 8

    4/42

    2 PARAMETER LISTParameter Level INFORMATION

    1 Room temperature Displayed if the control panel is configured as room unit

    1 Room temperature min Displayed if the control panel is configured as room unit

    1 Room temperature max Displayed if the control panel is configured as room unit

    1 Boiler temperature

    1 Outside temp

    1 Outside temp min

    1 Outside temp max

    1 Instant HW heater temp

    1 State central heating CH1

    1 State central heating CH2 Displayed if the heating circuit is activated

    1 State central heating CH3 Displayed if the heating circuit is activated

    1 State hot water

    1 State boiler

    1 State SithermPro Only with LMS15 pcb

    1 Telephone customer service

    Parameter Level SET TIME AND DATE1 1 Hours / minutes

    2 1 Day / month

    3 1 Year

    5 3 Start of summertime

    6 3 End of summertime

    Parameter Level OPERATOR SECTION20 1 Change Language

    24 2 LightingOffTemporarilyPermanently

    26 3 Operation lockOnOff

    Block of the control panel buttons A e B

    27 1 Programming lockOnOff

    The parameters can be displayed but not cha

    29 2 Units1 C , bar2 F , PSI

    40 2 Used as

    Operator unit 1Room unit 1Room unit 2Room unit 3

    The control panel is installed in the boilerThe control panel is configured as room unit oThe control panel is configured as room unit oThe control panel is configured as room unit o

    42 2 Assignment device 1

    Temps / mode CH1Central heating 1 and 2

    Central Heating 1 and 3All central heatings

    As room unit 1, the action of the respective co

    circuit 1 or to 2 heating circuits.

    43 2 Action operation0 Locally1 Centrally

    The room unit controls only the respective heOnly room unit 1 can be Centrally. It also con

    54 2 Readjustment room sensor -3C+3C

    70 2 Software version

    Parameter Level WIRELESS 120 2 Binding Activation of wireless link with basic unit

    121 2 Test mode Test mode is used for checking the wireless communication

    130 2 Room unit 1 Check of link

  • 8/10/2019 SERVICE Luna Platinum Ed 8

    5/42

    131 2 Room unit 2 Check of link

    132 2 Room unit 3 Check of link

    133 2 Outside sensor Check of link

    134 2 Repeater Check of link

    135 2 Operator unit Check of link

    140 2 Delete all devices

    Parameter Level TIME CENTRAL HEATING 1 2 31 2 3

    1 Select days Selection of days or groups of days for time program500 520 540

    514 534 554 1 Select default timings? Is it possibile to select up to 3 preselect time programs

    501 521 541 1 1st Time ON502 522 542 1 1st Time OFF

    503 523 543 1 2nd Time ON

    504 524 544 1 2nd Time OFF

    505 525 545 1 3rd Time ON

    506 526 546 1 3rd Time OFF

    516 536 556 1 Default valuesYesNo

    Parameter Level TIME HOT WATER 560 1 Select days Selection of days or groups of days for time program

    574 1 Select default timings? Is it possibile to select up to 3 preselect time programs

    561 1 1st Time ON

    562 1 1st Time OFF

    563 1 2nd Time ON

    564 1 2nd Time OFF

    565 1 3rd Time ON566 1 3rd Time OFF

    576 1 Default valuesYesNo

    Parameter Level TIME AUXILIARY 600 1 Select days Selection of days or groups of days for time program

    614 1 Select default timings? Is it possibile to select up to 3 preselect time programs

    601 1 1st Time ON

    602 1 1st Time OFF

    603 1 2nd Time ON

    604 1 2nd Time OFF

    605 1 3rd Time ON

    606 1 3rd Time OFF

    616 1 Default valuesYesNo

    Parameter Level HOLIDAY HEATING 1 2 31 2 31 Select Is it possibile to select up to 8 holiday periods

    641 651 661

    642 652 662 1 Start Day and month of holiday start

    643 653 663 1 End Day and month of holiday end

    648 658 668 1 Operating levelOffReduced

  • 8/10/2019 SERVICE Luna Platinum Ed 8

    6/42

  • 8/10/2019 SERVICE Luna Platinum Ed 8

    7/42

  • 8/10/2019 SERVICE Luna Platinum Ed 8

    8/42

  • 8/10/2019 SERVICE Luna Platinum Ed 8

    9/42

  • 8/10/2019 SERVICE Luna Platinum Ed 8

    10/42

    2463 3 Settling time HW Validity time of parameter 2462

    2670 3 ParameterActivation of Super Over Temperature Function (SOT):OnOff

    2672 3 Parameter Increase of boiler setpoint for the control of SOT

    2675 3 Parameter

    2681 3 Parameter Precirculation time on DHW way (3WV position) during precirculation function

    2682 3 Parameter Precirculation time on CH way (3WV position) during precirculation function

    Parameter Level SITHERM PRO2700 3 Ion current filtered Ionization current actual value

    2702 3 Position stepper motor Gas valve stepper motor position2703 3 Learning value gas quality Gas calorific power measurement

    2706 3 Operating phase

    2720 2 Release sel type of gasRelease of ga type selection:0 Off1 On

    2721 2 Type of gasType of gas:1 Natural gas2 Liquefied gas

    2725 3 Sel individual boiler setting

    Activation of combustion adjustment:

    OffSet low-fire ion currentSave low-fire ion currentSet high-fire ion currentSave high-fire ion current

    Activation of correction at low powerStored of correction at low power

    Activation of correction at high powerStored of correction at high power

    2726 3 Ind boil setting ion curr LF Setting of correction at low power2729 3 Ind boil setting ion curr HF Setting of correction at high power

    2740 3 Triggering drift test

    Manual test of combustion adjustment:

    01234

    DisabledTest done at high and low powerTest done only at high powerTest done only at low powerTest done at high and low power alternativ

    2741 3 Parameter Last test result at low power

    2742 3 Parameter Last test filtred result at low power

    2743 3 Parameter Correction at low power

    2744 3 Parameter Threshold of correction at low power

    2745 3 Parameter Last test result at high power

    2746 3 Parameter Last test filtred result at high power

    2747 3 Parameter Correction at high power2748 3 Parameter Threshold of correction at high power

    2749 3 Reset drift test Reset of correction results

    Parameter Level CASCADE

    3510 3 Lead strategy Lead strategy:

  • 8/10/2019 SERVICE Luna Platinum Ed 8

    11/42

  • 8/10/2019 SERVICE Luna Platinum Ed 8

    12/42

  • 8/10/2019 SERVICE Luna Platinum Ed 8

    13/42

  • 8/10/2019 SERVICE Luna Platinum Ed 8

    14/42

    5040 3 Discharging protection

    Attivazione della pompa Q3 in caso di temperatura di mandata troppo alta This fpump (Q3) is activated only when the heat source temperature is high enough:

    OffAlwaysTimed

    DisabledEnabled

    Active only if the heat source is not able to

    5050 3 Charging temp max Maximum charging temperature from solar collector

    5051 3 Storage tank temp max Maximum hot water tank temperature

    5055 3 Recooling temp Recooling hot water tank temperature

    5056 3 Recooling heat gen/CHsTank recooling through heating circuit:On

    Off

    5057 3 Recooling collector

    Tank recooling through solar collector:OffSummer

    Always

    5060 3 El imm heater optg mode

    Electric immersion heater used for DHW tank:

    Substitute

    Summer

    Always

    The electric immersion heater is only usedmessage or has been shut down via boilerThe electric immersion heater is used wheswitched to summer operation. The DHW at least one of the heating circuits has swielectric immersion heater is also used if thor has been shut down via boiler lock.DHW is always heated with the electric im

    5061 3 El immersion heater release

    Electric immersion heater release:24h/day

    Hot water releaseTime hot water

    5062 3 El immersion heater controlElectric immersion heater control mode:External thermostatHot water sensor

    5070 3 Hot water boostIf the DHW temperature drops by more than 2 switching differentials (l5024) belOnOff

    5071 3 Charging prio time push The DHW storage tank is charged with absolute priority during the set period of

    5085 3 Excess heat drawSurplus heat can be fed to the DHW storage tank:OnOff

    5090 3 With bufferDHW storage tank receives its heat via buffer storage tank:YesNo

    5092 3 With prim contr/system pump

    DHW storage tank receives its heat via the primary controller or withthe help of the system pump:YesNo

    5093 3 With solar integrationDHW storage tank receives its heat from the solar collectors:YesNo

    Parameter Level INSTANTANEOUS HW HEATER

  • 8/10/2019 SERVICE Luna Platinum Ed 8

    15/42

    5464 2 Hot water preheat release

    Preheat mode:24h/dayHot water releaseTime central heating CH3Time hot waterTime auxiliary

    5470 1 HW preheat time when no CH Preheat time

    5476 3 Keep hot periodically Duration time of preheat function

    5482 3 Flow switch time cons Minimum response time of the flow switch for detecting consumption

    5490 3 Parameter

    5491 3 Parameter

    Parameter Level CONFIGURATION

    5710 2 Temps / mode CH1Heating circuit 1 activation:0 Off1 On

    5711 3 Cooling circuit 1Cooling circuit 1 activation:Off4-pipe system cooling

    5715 2 Temps / mode CH2Heating circuit 2 activation:0 Off1 On

    5721 2 Temps / mode CH3Heating circuit 3 activation:OffOn

    5730 2 Hot water sensor

    DHW sensor selection:

    1 Hot water sensor B32 Thermostat3 HW outlet sensor B38

    DHW storage tank sensorSensor used as DHW thermostatInstantaneous water heater outlet sensor

    5731 2 HW controlling element

    Actuator type for DHW request control:

    No charging requestCharging pumpDiverting valve

    No functionActuator used as charging pumpActuator used as diverting valve

    5732 3 Pump off change div valve Set the time the pumps are deactivated when the diverting valve switches over

    5733 3 Delay pump off Set the delay time for the pumps to be deactivated after the diverting valve has

    5734 3 Basic pos HW div valve

    Default DHW diverting valve position:

    Last requestCentral heatingHot water

    Default for boiler with DHW tankDefault for instantaneous water heater boi

    5736 3 Hot water separate circuitThe DHW separate circuit can only be employed in a cascaded system:On

    Off

    5737 3 Optg action HW div valveThe diverting valve position selected here is the position used when the output iPosition on HWPosition on CH

    5738 3 Midposition DHW div valveDHW diverting valve can be driven to the mid-position:OnOff

    5774 3 Ctrl boiler pump/HW valveActivation mode of boiler pump and DHW diverting valve:All requestsRequest CH1/HW only

  • 8/10/2019 SERVICE Luna Platinum Ed 8

    16/42

    5840 3 Solar controlling elementActuator configuration in case of solar storage tanks:

    Charging pumpDiverting valve

    Used as charging pumpUsed as diverting valve

    5841 3 External solar exchanger

    In the case of solar plant diagrams with 2 storage tanks, it must be selected wheexchanger for both the DHW and the buffer storage tank or for only one of themCommonlyHot water storage tankBuffer storage tank

    5870 3 Combi storage tank

    Functions specific to combi storage tanks are activated via this setting (for examinstalled in the buffer storage tank can be used for both space heating and DHW

    YesNo

    5890 2 Relay output QX1

    0 None1 Circulating pump Q42 El imm heater HW K63 Collector pump Q54 Cons circuit pump VK1 Q155 Boiler pump Q16 Bypass pump Q127 Alarm output K108 2nd pump speed CH1 Q219 2nd pump speed CH2 Q2210 2nd pump speed CH3 Q2311 heating pump CH3 Q2012 Cons circuit pump VK2 Q1813 System pump Q1414 Heat gen shutoff valve Y415 Solid fuel boiler pump Q1016 Time setting 5 K1317 Buffer return valve Y1518 Solar pump ext exch K919 Solar ctrl elem buffer K820 Solar ctrl elem swi pool K1822 Swimming pool pump Q1925 Cascade pump Q2526 St tank transfer pump Q1127 Hot water mixing pump Q3528 HW interm circ pump Q3329 Heat request K2730 Refrigeration request K2833 Heating pump CH1 Q234 Heating pump CH2 Q635 Hot water ctrl elem Q336 Instant WH ctrl elem Q3438 Water refill K3439 2nd boiler pump speed Q2740 Status output K3541 Status information K3642 Flue gas damper K3743 Fan shutdown K38

    DHW circulating pump

    Solar collector pumpConsumer circuit 1 pumpBoiler pump

    Alarm relay signals faults

    Pump/zone valve for heating circuit 3

    Pump activated at every heat request from

    Solid flue boiler pumpThe relay is controlled according to setting

    Contact to heat swimming pool by solar (in

    Common cascade pump

    Cooling request from cooling circuit 1Pump/zone valve for heating circuit 1Pump/zone valve for heating circuit 2Pump/diverting valve for DHW tankPump/diverting valve for instantaneous DHWater refill electrovalve2nd boiler pump speed

    External fan control

    5891 3 Relay output QX2 See relay output QX1

    5892 3 Relay output QX3 See relay output QX1

  • 8/10/2019 SERVICE Luna Platinum Ed 8

    17/42

  • 8/10/2019 SERVICE Luna Platinum Ed 8

    18/42

  • 8/10/2019 SERVICE Luna Platinum Ed 8

    19/42

    6051 2 Voltage value 2 H2 module 1 Parameter for characteristic definition of sensor

    6052 2 Funct value 2 H2 module 1 Parameter for characteristic definition of sensor

    6054 2 Function input H2 module 2 See function input H1

    6055 2 Contact type H2 module 2NONC

    6057 2 Voltage value 1 H2 module 2 Parameter for characteristic definition of sensor

    6058 2 Funct value 1 H2 module 2 Parameter for characteristic definition of sensor

    6059 2 Voltage value 2 H2 module 2 Parameter for characteristic definition of sensor

    6060 2 Funct value 2 H2 module 2 Parameter for characteristic definition of sensor

    6062 2 Function input H2 module 3 See function input H1

    6063 2 Contact type H2 module 3 NONC

    6065 2 Voltage value 1 H2 module 3 Parameter for characteristic definition of sensor

    6066 2 Funct value 1 H2 module 3 Parameter for characteristic definition of sensor

    6067 2 Voltage value 2 H2 module 3 Parameter for characteristic definition of sensor

    6068 2 Funct value 2 H2 module 3 Parameter for characteristic definition of sensor

    6097 2 Sensor type collectorSolar collector sensor type:1 NTC2 PT1000

    6098 3 Readjustm collector sensor Correction of readed collector sensor value

    6100 2 Readjustm outside sensor Correction of readed outside sensor value

    6110 3 Time constant building Time thermic constant building

    6120 3 System frost protectionPlant frost protection (only with outside sensor):OnOff

    6200 2 Save sensors Stored of sensor used in plant

    6205 3 Reset to default parameters Not used

    6212 2 Check no. heat source 1 Manufactoring information

    6213 2 Check no. heat source 2 Manufactoring information

    6215 2 Check no. storage tank Manufactoring information

    6217 2 Check no. heating circuits Manufactoring information

    6220 3 Software version Manufactoring information

    6230 2 Info 1 OEM Manufactoring information

    6231 2 Info 2 OEM Manufactoring information

    Parameter Level LPB SYSTEM

    6600 3 Device address Choice of cascade device address from 1 to 16 (1 = master)

    6601 3 Segment address Choice of cascade segment from 0 to 14

    6604 3 Bus power supply functionBus power supply type:OffTimed

    6605 3 Bus power supply stateBus power supply state:OnOff

    6610 3 Display system messagesVisualization of system messages:YesNo

    6612 3 Alarm delay Alarm time delay

    6620 3 Action changeover functionsAction function changeover:SystemSegment

  • 8/10/2019 SERVICE Luna Platinum Ed 8

    20/42

    6621 3 Summer changeoverSummer changeover:LocallyCentrally

    6623 3 Optg mode changeoverOption mode changeover:LocallyCentrally

    6624 3 Manual source lockLock mode:LocallySegment

    6625 3 Hot water assignment

    DHW assignment:

    Local CHsAll CHs in segmentAll CHs in system

    DHW used the setting of boilerDHW used the setting of boiler in same caDHW used the setting of boiler in cascade

    6630 3 Cascade master

    Cascade master:

    AlwaysAutomatically

    Cascade master is the boiler also if addresCascade master is the boiler with address

    6631 3 Ext source with eco mode

    In ECO mode, external heat sources on the LPB are operated as follows:OffOn hot waterOn

    6632 3 Note OT limit ext sourceExternal heat sources can be locked or released according to their own parameYesNo

    6640 3 Clock mode

    Clock mode:

    AutonomouslySlave without remote setting

    Slave with remote settingMaster

    Every boiler has own time programSlave boilers not use the master time prog

    Slave boilers use the master time programThe master time program is used

    6650 3 Outside temp sourceBoiler address where is connected outside sensor:- - . - - no outside sensor connectedThe first 2 numbers are hte segment number, the second part is the boiler numb

    Parameter Level FAULT

    6704 2 Display SW diagnostic codeVisualization of diagnostic code:0 No1 Yes

    6705 1 SW diagnostic code Diagnostic code currently pending

    6706 1 Burn ctrl phase lockout pos Lockout phase indicating where the fault occured

    6710 2 Reset alarm relay Reset of alarm relay

    6740 3 Flow temp 1 alarm value displayed

    6741 3 Flow temp 2 alarm value displayed

    6742 3 Flow temp 3 alarm value displayed6743 3 Boiler temp alarm value displayed

    6745 3 Hot water charging alarm value displayed

    6800 2 History 1 Last fault occured

    6805 2 SW diagnostic code 1 Diagnostic code of last fault occured

    6806 2 Burner control phase 1 Lockout phase indicating where the last fault occured

    6810 - 6996 2 History from 2 to 20 Previous fault history

    Parameter Level SERVICE/SPECIAL OPERATION

    7040 3 Burner hours interval Burner hours before boiler maintenance

  • 8/10/2019 SERVICE Luna Platinum Ed 8

    21/42

    7041 3 Burn hrs since maintenance Burner hours reset after boiler maintenance

    7042 3 Burner start interval Burner ignition number before boiler maintenance

    7043 3 Burn starts since maint Burner ignition number reset after boiler maintenance

    7044 3 Maintenance interval Operation boiler time before boiler maintenance

    7045 2 Time since maintenance Operation boiler time reset after boiler maintenance

    7051 3 Message ionization current Ionization current value

    7130 2 Chimney sweep functionChimney swwp function:OnOff

    7131 2 Burner output

    Burner output power during chimney sweep function:

    Partial loadFull loadMax heating load

    7140 2 Manual controlManual control function:OnOff

    7143 2 Controller stop functionController stop function:OnOff

    7145 2 Controller stop setpoint Power setpoint during controller stop function

    7146 2 Deaeration functionDeaeration function:OnOff

    7147 2 Type of venting

    Deaeration function mode:NoneHeating circuit continuous

    Heating circuit cycledHot water continuousHot water cycled

    7170 2 Telephone customer service

    7231 2 Refilll time current week value displayed

    7232 2 Refill time to date value displayed

    7233 2 Number of refills to date value displayed

    7244 3 Press superv water refill

    Used sensor for water pressure supervision for refill function:NoneWith input H1With input H2 module 1With input H2 module 2With input H2 module 3With input H3

    7250 3 PStick storage pos Selection of the dataset number to write/read

    7251 3 Parameter Description of dataset selected

    7252 3 PStick command

    Actions with Pstick:No operationReading from stickWriting on stick

    7253 3 PStick progressThe progress made appears as a percentage which, when stick operation is actpercentage already completed.

    7254 3 Parameter

    Status of Pstick:No stickNo operationWriting on stick

  • 8/10/2019 SERVICE Luna Platinum Ed 8

    22/42

    Reading from stickEMC test activeWriting errorReading errorIncompatible data setWrong stick typeStick format errorCheck data setData set disabledReading disabled

    Parameter Level INPUT/OUTPUT TEST

    7700 3 Relay test

    Operatin relays test:No testEverything offRelay output QX1Relay output QX2Relay output QX3Relay output QX4Relay output QX21 module 1Relay output QX21 module 2Relay output QX21 module 3Relay output QX22 module 1Relay output QX22 module 2Relay output QX22 module 3Relay output QX23 module 1

    Relay output QX23 module 2Relay output QX23 module 3

    7730 3 Outside temp B9 value displayed

    7750 3 Hot waterr temp B3 value displayed

    7760 3 Boiler temp B2 value displayed

    7820 3 Sensor temp BX1 value displayed

    7821 3 Sensor temp BX2 value displayed

    7822 3 Sensor temp BX3 value displayed

    7830 3 Sensor temp BX21 module 1 value displayed

    7831 3 Sensor temp BX22 module 1 value displayed

    7832 3 Sensor temp BX21 module 2 value displayed

    7833 3 Sensor temp BX22 module 2 value displayed

    7834 3 Sensor temp BX21 module 3 value displayed

    7835 3 Sensor temp BX22 module 3 value displayed

    7840 3 Voltage signal H1 value displayed

    7841 3 Contact state H1 value displayed7845 3 Voltage signal H2 value displayed

    7846 3 Contact state H2 value displayed

    7848 3 Voltage signal H2 module 2 value displayed

    7849 3 Contact state H2 module 2 value displayed

    7851 3 Voltage signal H2 module 3 value displayed

    7852 3 Contact state H2 module 3 value displayed

    7862 3 Frequency H4 value displayed

    7860 3 Contact state H4 value displayed

    7865 3 Contact state H5 value displayed

  • 8/10/2019 SERVICE Luna Platinum Ed 8

    23/42

  • 8/10/2019 SERVICE Luna Platinum Ed 8

    24/42

    8131 3 state displayed

    8138 3 Cascade flow temp value displayed

    8139 3 Cascade flow temp setp value displayed

    8140 3 Cascade return temp value displayed

    8141 3 Cascade return temp setp value displayed

    8150 3 Source seq ch'over current value displayed

    Parameter Level DIAGNOSTICS HEAT GENERATION

    8304 3 Boiler pump Q1 value displayed

    8308 3 Boiler pump speed value displayed

    8310 2 Boiler temperature value displayed

    8311 2 Boiler setpoint value displayed

    8312 3 Boiler switching point value displayed

    8313 3 Parameter value displayed

    8314 2 Boiler return temp value displayed

    8315 2 Boiler return temp setpoint value displayed

    8316 2 Flue gas temp value displayed

    8318 3 Flue gas temp max value reset

    8321 2 Primary exchanger temp value displayed

    8323 2 Fan speed value displayed

    8324 3 Set point fan value displayed

    8325 3 Current fan control value displayed

    8326 2 Burner modulation value displayed

    8327 3 Water pressure value displayed

    8329 3 Ionization current value displayed

    8330 3 Hours run 1st stage value reset8331 3 Start counter 1st stage value reset

    8338 3 Hours run heating mode value reset

    8339 3 Hours run HW value reset

    8390 3 Current phase number value displayed

    8499 3 Collector pump 1 value displayed

    8501 3 Solar ctrl elem buffer value displayed

    8502 3 Solar ctrl elem swi pool value displayed

    8510 3 Collector temp 1 value displayed

    8511 3 Collector temp 1 max value reset

    8512 3 Collector temp 1 min value reset

    8513 3 dt collector 1/exchanger 1 value displayed

    8513 3 dt collector 1/HW value displayed

    8514 3 dt collector 1/buffer value displayed

    8515 3 dt collector 1/swimming pool value displayed

    8519 3 Solar flow temp value displayed8520 3 Solar return temp value displayed

    8527 1 Total Solar Gain value reset

    8530 1 Hours run solar value reset

    8531 1 Hours run collect overtemp value reset

    8532 1 Hours run collector pump value reset

    8560 3 Solid fuel boiler temp value displayed

    8570 3 Hours run solid fuel boiler value reset

    Parameter Level DIAGNOSTICS CONSUMERS

  • 8/10/2019 SERVICE Luna Platinum Ed 8

    25/42

    8700 3 Outside temp value displayed

    8701 3 Outside temp min. value reset

    8702 3 Outside temp max. value reset

    8703 3 Outside temp attenuated value reset

    8704 3 Outside temp composite value displayed

    8730 3 Central heating pump 1 value displayed

    8731 3 Heat circ mix valve 1 open value displayed

    8732 3 Heat circ mix valve 1 close value displayed

    8740 3 Room temp 1 value displayed

    8741 3 Room setpoint 1 value displayed8743 3 Flow temp 1 value displayed

    8744 3 Flow temp setpoint 1 value displayed

    8749 3 Room thermostat 1 value displayed

    8760 3 Central heating pump 2 value displayed

    8761 3 Heat circ mix valve 2 open value displayed

    8762 3 Heat circ mix valve 2 close value displayed

    8770 3 Room temp 2 value displayed

    8771 3 Room setpoint 2 value displayed

    8773 3 Flow temp 2 value displayed

    8774 3 Flow temp setpoint 2 value displayed

    8779 3 Room thermostat 2 value displayed

    8790 3 Central heating pump 3 value displayed

    8791 3 Heat circ mix valve 3 open value displayed

    8792 3 Heat circ mix valve 3 close value displayed

    8800 3 Room temp 3 value displayed8801 3 Room setpoint 3 value displayed

    8804 3 Flow temp 3 value displayed

    8803 3 Flow temp setpoint 3 value displayed

    8809 3 Room thermostat 3 value displayed

    8820 3 Hot water pump value displayed

    8830 3 Hot water temp 1 value displayed

    8831 3 Hot water temp setpoint value displayed

    8832 3 Hot water temp 2 value displayed

    8835 3 Hot water circulation temp value displayed

    8836 3 HW charging temp value displayed

    8852 3 Instant HW heater temp value displayed

    8853 3 Instant HW heater setpoint value displayed

    8860 3 Hot water flow value displayed

    8875 3 Flow temp setp VK1 value displayed

    8885 3 Flow temp setp VK2 value displayed8895 3 Flow temp setp VK3 value displayed

    8900 3 Swimming pool temp value displayed

    8901 3 Swimming pool setpoint value displayed

    8930 3 Primary controller temp value displayed

    8931 3 Primary controller setpoint value displayed

    8950 3 Common flow temp value displayed

    8951 3 Common flow temp setpoint value displayed

    8952 3 Common return temp value displayed

    8962 3 Common output setpoint value displayed

  • 8/10/2019 SERVICE Luna Platinum Ed 8

    26/42

    8980 3 Buffer temp 1 value displayed

    8981 3 Buffer setpoint value reset

    8982 3 Buffer temp 2 value displayed

    8983 3 Buffer temp 3 value displayed

    9005 3 Water pressure H1 value displayed

    9006 3 Water pressure H2 value displayed

    9009 3 Water pressure H3 value displayed

    9031 3 Relay output QX1 value displayed

    9032 3 Relay output QX2 value displayed

    9033 3 Relay output QX3 value displayed

    9050 3 Relay output QX21 module 1 value displayed9051 3 Relay output QX22 module 1 value displayed

    9052 3 Relay output QX23 module 1 value displayed

    9053 3 Relay output QX21 module 2 value displayed

    9054 3 Relay output QX22 module 2 value displayed

    9055 3 Relay output QX23 module 2 value displayed

    9056 3 Relay output QX21 module 3 value displayed

    9057 3 Relay output QX22 module 3 value displayed

    9058 3 Relay output QX23 module 3 value displayed

    Parameter Level BURNER CONTROL

    9500 3 Prepurge time Fan running time of prepurge

    9504 3 Required speed prepurging Prepurging fan speed

    9512 2 Required speed ignition Ignition fan speed

    9524 2 Required speed LF Minimum power fan speed

    9529 2 Required speed HF Maximum power fan speed9540 3 Postpurge time Fan running time of postpurge

    9650 3 Chimney drying

    Mode:OffTemporarilyPermanently

    9651 3 Req speed chimney drying Fan speed during the function

    9652 3 Duration chimney drying Operation time of function

  • 8/10/2019 SERVICE Luna Platinum Ed 8

    27/42

  • 8/10/2019 SERVICE Luna Platinum Ed 8

    28/42

    3 ERROR LIST

    ErrorInternal

    CodeDescription

    10 Outside sensorCentral heating enabled without any control (roomthermostat, room unit o outside sensor) or outside sensorfault

    20 Boiler sensor 11 Short circuit

    2 Open circuit

    25 Boiler sensor solid fuel Solid fuel boiler sensor not found or in short circuit

    26 Common flow sensor Common flow sensor not found or in short circuit

    28 Flue gas temp sensor

    539 Short circuit (lockout)

    540 Open circuit (lockout)

    543 Short circuit (temporary error)

    544 Open circuit (temporary error)

    30 Flow sensor 1 Flow sensor mixing zone 1 not found or in short circuit

    31 Flow sensor cooling 1 Flow sensor cooling circuit not found or in short circuit

    32 Flow sensor 2 Flow sensor mixing zone 2 not found or in short circuit

    38 Flow sensor prim contr Flow sensor primary controller not found or in short circuit

    40 Return sensor 11 Short circuit

    2 Open circuit

    46 Return sensor cascade Return sensor cascade not found or in short circuit

    47 Common return sensor Common return sensor not found or in short circuit

    50HW sensor 1 (boiler withtank)

    1 Short circuit

    2 Open circuit

    52 HW sensor 2 Solar DHW sensor not found or in short circuit

    54 HW flow sensor DHW flow sensor not found or in short circuit

    57 HW circulation sensor DHW circulation sensor not found or in short circuit

    60 Room sensor 1 Room sensor circuit 1 not found or in short circuit

    65 Room sensor 2 Room sensor circuit 2 not found or in short circuit

    68 Room sensor 3 Room sensor circuit 3 not found or in short circuit

    70 Storage tank sensor 1 Storage tank sensor 1 not found or in short circuit

    71 Storage tank sensor 2 Storage tank sensor 2 not found or in short circuit

    72 Storage tank sensor 3 Storage tank sensor 3 not found or in short circuit

    73 Collector sensor 1 Solar collector sensor 1 not found or in short circuit

    74 Collector sensor 2 Solar collector sensor 2 not found or in short circuit

    78 Water pressure sensor

    506 Short circuit (lockout)

    560 Short circuit (temporary error)

    793 Automatic filling loop error (lockout)797 Automatic filling loop error (temporary error)

    81 LPB short-circuit/comm LPB bus error

    82 LPB address collision More than 1 boiler using in the same address

    83 BSB short-circuit No comunication / comunication error

    84 BSB address collision More than 1 room unit using in the same Central heating

    85 BSB Radio communication No radio comunication

    91 Data loss in EEPROM 499 Internal counter out of range

    98 Extension module 1 External modul 1 not found

    99 Extension module 2 External modul 2 not found

    100 2 clock time masters Not correct configuration of clock time

    105 Maintenance message

    109 Boiler temp supervision503 Flatness 2 test on flow sensor

    504 Flatness 2 test on return sensor

  • 8/10/2019 SERVICE Luna Platinum Ed 8

    29/42

    110 Lockout SLT

    419 Maximum temperature of Electronic Safe Limit temperature

    420Return temperature higher than flow temperature more than10K (temporary error)

    421Return temperature egual or higher than flow temperaturemore than 10K-2

    426 Temperature slope

    427 Unlock limit of temperature slope not reached

    428 Flow return temperature higher than 56K (temporary error)

    429 Unlock limit of Flow return temperature higher than 56K

    431Accepted times return temperature higher than flowtemperature more than 10K reached (lockout error)

    436 Electronic Safe Limit temperature on return temperature

    437 Accepted times Temperature slope reached

    438Accepted times Flow return temperature higher than 56Kreached (lockout error)

    111 Shutdown limit thermost Maximum limit of flow temperature

    117 Water pressure too high

    565 Static water pressure limit (lockout error) > 2.8 bar

    566 Static water pressure limit (temporary error) > 2.8 bar

    118 Water pressure too low Static pressure limit (lockout error) < 0.5 bar

    119 Shutd water press swi563 Water pressure limit (lockout error)

    564 Water pressure limit (temporary error)

    121 Flow temp CH1 Flow temperature Central heating 1 not reached

    122 Flow temp CH2 Flow temperature Central heating 2 not reached

    125 Boiler temp too high

    500Reached limit of flow temperature of flow setpoint plus 30Kfor 2 times in 10 minutes

    501 No flow temperature variation for 20 seconds

    502 No return temperature variation for 20 seconds

    126 HW charg temp Maximum temperature of DHW charging not reached

    127 Legionella temp Legionella limit temperature not reached

    128 Loss of flame in op Loss of flame during operation

    130 Flue gas temp too high Flue temperature limit reached

    132 Safety shutdown Lock on GP contact

    133 Safety time exceeded Loss of flame during ignition phase

    151 BMU internal

    325 Software error

    326 Software error

    327Software error

    328 Software error

    329 Software error

    330 Ingniter relay closing error

    331 Ingniter relay opening error

    332 Gas valve relay closing error

    333 Gas valve relay opening error

    334 Ingnition error of canal 2

    335 Swithing off error of canal 2

    336 Safety relay closing error

    337 Safety relay opening error

    338 Ingnition error of canal 1

    339 Swithing off error of canal 1

    152 Parameterization345 Software error on micro 1

    346 Gas type change error

  • 8/10/2019 SERVICE Luna Platinum Ed 8

    30/42

    347 Max fan speed = Postpurge fan speed accepted

    572 Input HX parameterization: limit thermostat

    573 Input HX parameterization574 Input HX parameterization: air presure switch

    575 10V signal input parameterization

    576 Input H6 with 2 different funtions associated

    577 Input H7 with 2 different funtions associated

    578 Input B4 with 2 different funtions associated

    579 Bypass pump Q12 parameterization

    580 Cooling request K28 parameterization

    581 Water filling K34 parameterization

    153 Unit locked Hardware reset button pressed more than 10 seconds

    160 Fan speed threshold Fan speed threshold not reached

    164 Flow press switch CH561 Flow pressure switch Central heating (lockout error)

    562 Flow pressure switch Central heating (temporary error)

    171 Alarm contact 1 active800 Alarm contact input H1

    805 Alarm contact input H4

    172 Alarm contact 2 active

    801 Alarm contact input H2 of extension module 1

    802 Alarm contact input H2 of extension module 2

    803 Alarm contact input H2 of extension module 3

    806 Alarm contact input H5

    173 Alarm contact 3 active 807 Alarm contact input H6

    174 Alarm contact 4 active804 Alarm contact input H3

    808 Alarm contact input H7

    176 Water press 2 too high 565 Static water pressure limit (lockout error)

    177 Water press 2 too low 565 Static water pressure limit (lockout error)

    178 Limit thermostat CH1 Limit thermostat Central heating 1 (mix zone)

    179 Limit thermostat CH2 Limit thermostat Central heating 2 (mix zone)

    195 Water refill time791 Water refill time for sigle refilling elapsed (lockout error)

    795 Water refill time elapsed (temporary error)

    196 Water refill time/week792 Water refill time weekly elapsed (lockout error)

    796 Water refill time weekly elapsed (temporary error)

    241 Flow sensor yield Flow sensor yield not found or in short circuit

    242 Return sensor yield Return sensor yield not found or in short circuit243 Swimming pool sensor Swimming sensor not found or in short circuit

    260 Flow sensor 3 Flow sensor mixing zone 1 not found or in short circuit

    270 Exc temp diff h' exch 507Temperature differential between flow temperature andexchanger temperature - Dry fire (lockout error)

    320 HW charging sensor Charging DHW sensor not found or in short circuit

    321 HW outlet sensor1 Short circuit

    2 Open circuit

    322 Water press 3 too high 565 Static water pressure limit (lockout error)

    323 Water press 3 too low 565 Static water pressure limit (lockout error)

    324 BX same sensors More than one sensor with the same function associated

    325 BX/e'module same sensMore than one sensor (also on external module) with thesame function associated

    326 BX/m'grp same sensMore than one sensor (also on mixing zone) with the samefunction associated

    327 E'module same funct More than one sensor on external module with the same

  • 8/10/2019 SERVICE Luna Platinum Ed 8

    31/42

    function associated

    328 Mix group same functMore than one sensor on mixing zone with the samefunction associated

    329 E'mod/m'grp same functMore than one sensor (external module and mixing zone)with the same function associated

    330 BX1 no function No function associated to input BX1

    331 BX2 no function No function associated to input BX2

    332 BX3 no function No function associated to input BX3

    333 BX4 no function No function associated to input BX4

    334 BX5 no function No function associated to input BX5

    335 BX21 no function No function associated to input BX21

    336 BX22 no function No function associated to input BX22

    337 B1 no function No function associated to input B1

    338 B12 no function No function associated to input B12

    339 Coll pump Q5 missing Collector pump Q5 not found or not configurated

    340 Coll pump Q16 missing Collector pump Q16 not found or not configurated

    343 Solar integration missing Solar integrated not found or not configurated

    344 Solar buffer K8 missing Solar buffer not found or not configurated

    345 Sol swi pool K18 missing Swimming pool from solar not found or not configurated

    346 Boiler pump Q10 missing Collector pump Q16 not found or not configurated

    347 Solid fuel boil comp sensSolid fuel boiler comparative sensor not found or notconfigurated

    348 Solid fuel boil addr err Solid fuel boiler address error

    349 Buff valve Y15 missing Buffer valve not found or not configurated

    350 Buffer address error Buffer address error

    351 Prim/sys pump addr err System pump address error

    353 Casc sens B10 missing Cascade sensor not found or not configurated

    371 Flow temp CH3 Flow temperature Central heating 3 not reached

    372 Limit thermostat CH3 Limit thermostat Central heating 3 (mix zone)

    373 Extension module 3 External modul 3 not found

    374 Sitherm Pro calculation

    359 Control value out of range

    360 Calculated value over the threshold

    361 Calculated value under the threshold

    362 Gas valve stepper position over the threshold

    363 Gas valve stepper position under the threshold

    364 Ionization current out of range

    365 R value out of range

    375 BV stepper motor

    366 Open contact on stepper motor

    367 Short circuit on stepper motor

    368 Low supply voltage on stepper motor

    369 High supply voltage on stepper motor

    370 Prevention of startup for a stepper motor is interrupted

    376 Drift test limit value

    221 Fan speed out of range

    357 Fan speed out of range

    358Ionization or fan speed with electrode drift test not in thedefined area. Problem: Power supply, blower-PWM setting

    371 Too much corrrection of drift test

    372 Too much corrrection of drift test

    373 Drift test performed 4 times consecutive (temporary error)

    768 Control value limit reached during the test drift

    769 Ionization drift crash during testing

  • 8/10/2019 SERVICE Luna Platinum Ed 8

    32/42

    377 Drift test prevented 418 Drift test counter monitor has excedded

    384 Extraneous ligth Flame present with gas valve closed

    385 Mains undervoltage Low supply voltage

    386 Fan speed tolerance Fan speed out of range

    429 Dyn water pres too high558 Dynamic water pressure too high (lockout error)

    559 Dynamic test times excedded (lockout error)430 Dyn water pres too low 557 Dynamic pressure test failed (lockout error)

    431Primary exch sensor(aluminium exchanger)

    1 Short circuit (temporary error)

    2 Open circuit (temporary error)

    547 Short circuit (lockout error)

    548 Open circuit (lockout error)

    432 Function ground missing746 Feedback error from PCB (SR)

    747 Feedback erro from gas valve realy (BV1)

    433 Heat exch temp508 Exchanger temperature > 95C (lockout error)

    509 Exchanger temperature > 95C (temporary error)

  • 8/10/2019 SERVICE Luna Platinum Ed 8

    33/42

    4 GAS ADAPTIVE SYSTEM

    LUNA4 is provided with a brand new system GAC (Gas Adaptive Control): the electroniccontrol together with the gas valve grant an automatic control of the combustion and ensurethe following advantages during the installation as well as for the end user:

    Reduction of the time for the installation, as any manual intervention has been deleted(adjustment or nozzles change); The boiler is able to adapt to the quality of the gas and to the length of the flue tubesmaintaining a constant efficiency helping a reduction of the gas consumption and generatingless pollution.

    The Gas Adaptive System maintains correct combustion by comparing the measured FlameSignal and the Reference Flame Signal. The Reference Signal follows a set curve dependingon fan speed and it is part of the software.

    The system measures constantly the signal during the operation of the boiler and adjusts thegas flow rate in order to maintain the correct signal and the correct CO level. In this way isalso considered the oxidation of the component (flame electrode and burner).

    The electronic gas valve has a modulator used to set the properly flame signal and so thecorrect air / gas ratio (LAMBDA).If the system is not able to assure the correct flame signal the boiler goes in lockout.

    The flame signal detected by the burner control is independent from:- value and type of supply voltage;- quality of the ground in the installation.

  • 8/10/2019 SERVICE Luna Platinum Ed 8

    34/42

    5 FAULT FINDING1 Initial Fault Finding Checks

    1. Check that gas, water and electrical supplies are availableat the boiler.

    2. Electrical supply = 230V ~ 50 Hz.

    4. The preferred minimum gas pressure is 10 mbar.

    5. Carry out electrical system checks, i.e. Earth Continuity,Resistance to Earth, Short Circuit and Polarity with a suitablemeter.

    6. Ensure all external controls are calling for heat and checkall external and internal fuses. Before any servicing orreplacement of parts, ensure the gas and electrical suppliesare isolated.

    18.2 Error Codes1. If a fault occurs on the boiler an error code may be shownby the facia display.

    2. The codes are either a flashing two or three digit, numberpreceded by the symbol 'E'.

    E20, E28, E40, E50, E83, E151, E160 and E384 indicate possiblefaulty components.

    E110 and E111 shows overheat of the primary.

    E117 is displayed when the primary water pressure is morethan 2.7 bar.

    E118 is displayed when the primary water pressure is lessthan 0.5 bar.

    E133 indicates that the gas supply has been interrupted,ignition has failed or the flame has not been detected.

    E125 is displayed in either of two situations:-i) If within 15 seconds of the burner lighting the boilertemperature has not changed by 1.ii) If within 10 minutes of the burner lighting the boilertemperature twice exceeds the selected temperature by 30.In these instances poor primary circulation is indicated.

    E128 is displayed if there has been a flame failure during normalburner operation.

    3. By pressing the 'Reset' button for between 1-3 seconds whenE 110, E125 & E133 are displayed it is possible to relight theboiler.

    4. If this does not have any effect, or error codes are displayedregularly further investigation is required.

    .

    NOTE: These checks must be repeated after anyservicing or fault finding.

    NOTE: When instructed press and hold

    the Reset for between 1-3 seconds toreset the boiler.

    E20 Central Heating Flow NTC Fault

    E28 Flue NTC Fault

    E40 Central Heating Return NTC Fault

    E50 Hot Water NTC Fault

    E83 Communications error

    E109 Pre-Circulation Fault

    E110 Safety Thermostat Operated

    E111 Maximum flow temperature exceeded

    E117 System Water Pressure Too High

    E118 System Water Pressure Too Low

    E125 Circulation Fault (Primary Circuit)

    E128 Flame Failure

    E130 Flue NTC Operated

    E133 Interruption Of Gas Supply or Flame Failure

    E151 PCB Fault

    E160 Fan or Fan Wiring Fault

    E384 False flame

    Table Of Error Codes

    .

  • 8/10/2019 SERVICE Luna Platinum Ed 8

    35/42

    Refer to Annex 1 Illustrated Wiring Diagram for position of terminals and componentsCentral Heating - Follow operational sequence

    NO

    Turn on mains power.The display illuminates

    Go to section A

    *Error 110 flashingError 111 flashingError 133 flashingError 125 flashing

    Press the Reset button forbetween 1-3 seconds

    If the E110 or E111 is stillflashing. Go to section H

    Error 20, 28, 40 or 50 flashing Go to section D

    Error E109 flashing Go to section J

    Set the Central Heatingtemperature toMaximum. Pump runs.

    Ensure all controls andProgrammers are callingfor heat

    Ensure controls are set todemand and verify the

    contacts are closed

    Go to section B

    Error E125 flashingafter 1 minute

    Fan runs after up to 3 minutes Error 160 flashingGo to section C

    Fan runs at correct speed Error 160 flashingGo to section C

    Spark at ignition electrodes forup to 5 seconds and for 4attempts.

    Error 133 flashingGo to section FPress the Reset button forbetween 1-3 seconds

    Check the Central HeatingNTC sensorGo to section D

    Burner output modulates tomaintain the temperature set

    Burner goes out Fan stops after 10 secondsOperation sequencesuccessful

    YES

    YES

    YES

    YES

    YES

    YES

    YES YES

    YES

    YES

    YES

    YES

    YES NO

    NO

    NO

    NO

    NO

    NO

    NO

    NO

    NO

    Go to section E

    Burner lights Burner does not stay alightafter 5 seconds

    YES

    YES

    NO

    YES

    NO3 way valve open to centralheating circuit

    Go to section K

    NO

    YES

    Error 117 or 118 flashing Go to section I

    YES

    NO

    Error E110 or E111flashing

    NO

    Go to section H

    YES

    CH Rad. Symbol flashes

    NO

    Error E130 flashing Go to section MYES

    *If Error 83, 151 or 384 is flashing or re-occurs regularlycheck all PCB and communication connections, if this hasno effect chan e PCB.

    Error 133 flashing. Go to section GYES

    Error 128 or Error 374 flashing. Go to section N

    NO

  • 8/10/2019 SERVICE Luna Platinum Ed 8

    36/42

  • 8/10/2019 SERVICE Luna Platinum Ed 8

    37/42

    Fault Finding Solutions Sections

    Main terminals L and N Check electrical supply

    YESMain terminal fuse Replace fuse

    NO

    PCB X10 connectorMains terminals L & N

    Check wiring

    NO

    A

    Connection OK atconnector x40

    Is there 230V at:

    NO

    1.

    2.

    3.

    BSwitch to DHW mode maximum flow rate and pressreset. During the next three minutes is there:-

    230V atPump

    NO

    230V at PCB connector x13 pump terminalsBlue to Brown (See Wiring Diagram)

    Replace PCB

    NO

    230V between PCB connector x13 pumpterminal Blue and PCB connector x11 pumpterminal Black.(See Wiring Diagram)

    YES

    Displayilluminated

    C

    Is there 230V AC at fan terminals connectorX11 blue to brown. See Wiring Diagram

    1.

    Fan jammed of faulty winding

    YES

    Replace PCB

    NO

    Replace fan

    YES

    Fan connections correct at fan and PCBConnectors X11 & X23 See Wiring Diagram

    YES

    Make connections

    NO

    Main or DisplayPCB fault

    NO

    YES

    Replace PCB

    YES

    ReplacePump

    YES

    NO

    Check wiring

  • 8/10/2019 SERVICE Luna Platinum Ed 8

    38/42

    D

    Cold resistance approximately10k@ 25 C (DHW and CH sensors)(resistance reduces with increase in temp.)

    Replace sensorNO

    G

    Gas at burner Ensure gas is on and purgedNO

    Check wiring & PCB X15 connector, is there 24 VDC across Gas valve terminals black to green.See Wiring Diagram.

    Replace PCB

    NO

    Replace gas valveYES

    F Check and correct if necessary1. Ignition electrode and lead2. Electrode connection3. Spark gap and position

    Check wiring.Voltage at PCB X15 connector is24V DC across the igniter unitterminals Blue to Brown for 5

    seconds during ignition phase . SeeWiring Diagram

    YES

    Replace PCBNO

    Replace igniter unitYES

    Check and correct if necessary

    1.CO2 values - see instruction2. Flame sensing electrode and lead connections3. Flame sensing electrode position

    2.

    Replace PCB

    NO

    Replace flame sensing electrode

    YES

    E

    Check the gas supply pressure:For Natural Gas greater than10 - 11 mbar

    1.

    Flame current should be more than 1,7 A

    Temperature sensor faulty.Check correct location and wiring

    YES

  • 8/10/2019 SERVICE Luna Platinum Ed 8

    39/42

    YES

    YESI CH system pressure less than 0.5 baror more than 2.7 bar.

    Restore System Pressure

    J Ensure that the system andboiler are fully vented. System fault, correct.

    NO

    Check flow temperature sensor connectionsand position.Cold resistance approximately.10k@ 25 C (CH sensors)(resistance reduces with increase in temp.)

    YES

    Replace sensorNO

    Check wiring and pcb connection atconnector x22 is there approx. 5 VDC between the green and black

    terminals

    NOReplace pressure sensor

    YES

    YES

    Go to section B

    K Is there 230V at:

    Motor, 3 way valve

    1

    2

    PCB connector x13 3 way valve terminalsBlue to Black central heating modeBlue to Brown domestic hot water mode

    See Wiring Diagram

    YES

    Replace motor 3 way valve

    NO

    Replace PCB

    Check 3 way valve cable.

    Replace PCBNO

    Overheat thermostat operated orfaulty.

    YES

    ReplacePCB

    Check for and correct anysystem faults.

    NO

    Replace safety thermostatYES

    Is E110 or E111 stillflashing

    Check Flow, Return,sensors. See section D

    Allow to cool. Continuityacross thermostat terminals

    more than 1.5 ohm

    YESNO

    NO

    H

  • 8/10/2019 SERVICE Luna Platinum Ed 8

    40/42

    L Is mains water filter andassembly clean and the rotor freeto move.

    NO

    Clean or replace

    YES

    PCB connector x22Hall effect sensor terminals.Check that the voltage is approximately5 V DC between Red and BlueSee Wiring Diagram

    Replace Hall Effect SensorYES

    NO

    Replace PCB

    Temperature sensors faulty.Cold resistance approximately10k@ 25 C (CH sensor)20k@ 25 C (Flue sensor)(resistance reduces with increase in temp.)

    1.

    Replace sensorNO

    If pump is running the heat exchanger could beobstructed

    2. Replace heat exchangerYES

    M

    N

    E128 flashingE374 flashing

    NO

    E376 flashing

    YES NO 1.

    2.

    Replace PCB

    NO

    Replace flamesensingelectrode

    YES

    Replace gasvalve

    YES

    Replace PCBNO

    1.Reset Drift Test results:

    -press both buttons for 6 seconds-enter at specialist level-go to Sitherm Pro menu-go to parameter 2749-select yes

    Check if there isrecirculation of flue gas inthe sealed chamber

    Check supply pressure atthe gas valveCheck and correct ifnecessary:1. Selection of gas type2. Flame sensingelectrode and leadconnections3. Flame sensingelectrode position

    Check wiring and PCB -X25 connector (stepper

    motor gas valve) and X15(EV gas valve)

    Check and correct ifnecessary:1. Selection of gas type2. Flame sensingelectrode position

    YES

  • 8/10/2019 SERVICE Luna Platinum Ed 8

    41/42

    WIRING DIAGRAM

  • 8/10/2019 SERVICE Luna Platinum Ed 8

    42/42

    6 BURNER PHASE (fault history)

    Phase Description

    1 Permitted afterburn time2 Permitted time with air pressure switch closed or fan speed

    3 Permitted time with fan speed

    4 Standby

    5 Start prevention

    6 Maximum fan ramp-up time to prepurge speed

    7 Maximum fan ramp-up time to ignition speed

    8 Preventilation

    9 Maximum time to reach ignition speed after prepurging

    10 Maximum waiting time 1

    11 Maximum waiting time 212 Preignition time

    13 1st safety time (gas valve open)

    14 2nd safety time (gas valve close)

    15 Interval (flame stabilization)

    16 Control mode

    17 Change to postpurging at last operating speed

    18 Change to postpurging at prepurge speed

    19 Postpurging at last operating speed

    20 Temporary error

    21 Lock-out error

    22 Postpurging at prepurge speed23 Chimney drying