service manual r410a revised edition-b [service ref.]...
TRANSCRIPT
SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS
SERVICE MANUAL R410A
Outdoor unit[Model Name]
PUHZ-P200YKA
PUHZ-P250YKA
[Service Ref.]
PUHZ-P200YKA.UKPUHZ-P200YKAR1.UKPUHZ-P250YKA.UKPUHZ-P250YKAR1.UK
PARTS CATALOG (OCB582)
CONTENTSTECHNICAL CHANGES ···································· 21. REFERENCE MANUAL ································· 32. SAFETY PRECAUTION ································· 33. FEATURES ····················································· 74. SPECIFICATIONS ·········································· 85. DATA ······························································· 96. OUTLINES AND DIMENSIONS ··················· 127. WIRING DIAGRAM ······································ 138. WIRING SPECIFICATIONS ·························· 14
9. REFRIGERANT SYSTEM DIAGRAM ············· 1910. TROUBLESHOOTING ·································· 2111. FUNCTION SETTING ··································· 7512. MONITORING THE OPERATION DATA BY THE REMOTE CONTROLLER ····8313. EASY MAINTENANCE FUNCTION ············· 9214. DISASSEMBLY PROCEDURE ····················· 95
Note:•Thismanualdescribesservicedataoftheoutdoorunitsonly.
No. OCH582REVISED EDITION-B
June 2015
•PleasevoidOCH582REVISEDEDITION-A.
Revision:•Added PUHZ-P200YKAR1.UKandPUHZ-P250YKAR1.UKinREVISEDEDITION-B.
•Somedescriptionshavebeenmodified.
2
TECHNICAL CHANGES
PUHZ-P200YKA.UK PUHZ-P200YKAR1.UKPUHZ-P250YKA.UK PUHZ-P250YKAR1.UK 1.SoftwaremodificationtobeabletoconnectwithPAC-IF013B-E/PAC-SIF013B-E(AHUinterface)hasbeenmade.
OCH582B
3
2-1. ALWAYS OBSERVE FOR SAFETYBefore obtaining access to terminal, all supply circuits must be disconnected.
INDOOR UNIT SERVICE MANUAL
ModelName ServiceRef. ServiceManualNo.
PLA-RP50/60/71/125/100BA PLA-RP50/60/71/125/100BAR4.UK OCH412OCB412
PCA-RP50/60/71/100/125KAQ PCA-RP50/60/71/100/125KAQR2(-ER) OCH491OCB491
PKA-RP50HAL PKA-RP50HALR1(-ER) OCH453OCB453
PKA-RP60/71/100KAL PKA-RP60/71/100KALR1.TH(-ER) OCH452OCB452
PSA-RP71/100/125KA PSA-RP71/100/125KA OCH528OCB528
PEAD-RP50/60/71/100/125JA(L)Q PEAD-RP50/60/71/100/125JA(L)QR2.UK HWE10090BWE10160
PEA-RP200/250GAQ PEA-RP200/250GAQ.TH-AF HWE10070BWE10140
2 SAFETY PRECAUTION
2-2. CAUTIONS RELATED TO NEW REFRIGERANTCautions for units utilizing refrigerant R410A
Preparation before the repair service.
• Prepare the proper tools.• Prepare the proper protectors.• Provide adequate ventilation.• After stopping the operation of the air conditioner, turn off the power-supply beaker.• Discharge the condenser before the work involving the electric parts.
Precautions during the repair service.
• Do not perform the work involving the electric parts with wet hands.• Do not pour water into the electric parts.• Do not touch the refrigerant.• Do not touch the hot or cold areas in the refrigerating cycle.• When the repair or the inspection of the circuit needs to be done without turning off the power, exercise great caution
not to touch the live parts.
1 REFERENCE MANUAL
OCH582B
4
[1] Cautions for service(1) Perform service after recovering the refrigerant left in unit completely.(2) Do not release refrigerant in the air.(3) After completing service, charge the cycle with specified amount of refrigerant.(4) When performing service, install a filter drier simultaneously.
Be sure to use a filter drier for new refrigerant.
[2] Additional refrigerant chargeWhen charging directly from cylinder·CheckthatcylinderforR410Aonthemarketisasyphontype.·Chargingshouldbeperformedwiththecylinderofsyphonstoodvertically.(Refrigerantischargedfromliquidphase.)
Gravimeter
Unit
Make sure that the inside and outside of refrige-rant piping is clean and it has no contaminantssuch as sulfur, oxides, dirt, shaving particles, etc,which are hazard to refrigerant cycle.In addition, use pipes with specified thickness.
Contamination inside refrigerant piping can cause deterio-ration of refrigerant oil, etc.
Store the piping indoors, and both ends of the piping sealed until just before brazing. (Leave elbow joints, etc. in their packaging.)If dirt, dust or moisture enters into refrigerant cycle, that can cause deterioration of refrigerant oil or malfunction of com-pressor.
The refrigerant oil applied to flare and flangeconnections must be ester oil, ether oil or alkylbenzene oil in a small amount.If large amount of mineral oil enters, that can cause deterio-ration of refrigerant oil, etc.
Use a vacuum pump with a reverse flow check valve.Vacuum pump oil may flow back into refrigerant cycle and that can cause deterioration of refrigerant oil, etc.
Charge refrigerant from liquid phase of gascylinder.If the refrigerant is charged from gas phase, composition change may occur in refrigerant and the efficiency will be lowered.
Use new refrigerant pipes.
In case of using the existing pipes for R22, be careful withthe following:· Be sure to clean the pipes and make sure that the insides of the pipes are clean.· Change flare nut to the one provided with this product. Use a newly flared pipe. · Avoid using thin pipes.
Do not use refrigerant other than R410A.
If other refrigerant (R22, etc.) is used, chlorine in refrige-rant can cause deterioration of refrigerant oil, etc.
Handle tools with care.
If dirt, dust or moisture enters into refrigerant cycle, that cancause deterioration of refrigerant oil or malfunction of com-pressor.
Do not use a charging cylinder.
If a charging cylinder is used, the composition of refrigera-nt will change and the efficiency will be lowered.
Use the following tools specifically designed for use with R410A refrigerant.The following tools are necessary to use R410A refrigerant.
Flare tool
Electronic refrigerant charging scale
Vacuum pump adaptorSize adjustment gauge
Gauge manifold
Torque wrenchGas leak detectorCharge hose
Tools for R410A
Ventilate the room if refrigerant leaks during operation. If refrigerant comes into contact witha flame, poisonous gases will be released.
Never use any refrigerant other than that specified.Doing so may cause a burst, an explosion, or fire when the unit is being used, serviced, or disposed of.Correct refrigerant is specified in the manuals and on the spec labels provided with our products.We will not be held responsible for mechanical failure, system malfunction, unit breakdown or accidents caused by failure to follow the instructions.
Use the specified refrigerant only.
OCH582B
Performtheairtight test,vacuumairpurging,additional refrigerantcharging(ifnecessary),andgasleakcheck.
•Refertotheflowchartbelowtodetermineiftheexistingpipescanbeusedandifitisnecessarytouseafilterdrier.•Ifthediameteroftheexistingpipesisdifferentfromthespecifieddiameter,refertotechnologicaldatamaterialstoconfirmifthepipescanbeused.
▼
▼
▼
▼
▼
▼ ▼
Measuretheexistingpipethicknessandcheckfordamage.The existing pipe thickness meets specifica-
tions and the pipes are not damaged.
Checkiftheexistingairconditionercanoperate.
Afteroperatingthecoolingsystemforabout30minutes,doapumpdownwork.
Disconnecttheexistingairconditionerfromthepipes.
Attachthenewairconditioner
Testrun Theexistingpipescannotbereused.Usenewpipes.
•Iftheexistingairconditionercannotoperate,usearefrigerantrecoverydevicetocollecttherefrigerant.
•Incaseexistingpipeswereusedforgasoroilheatpumpsystems,besuretocleanthepipesforP200/250models.
The existing pipe thickness does not meetspecifications or the pipes are damaged.
5
2-3. PRECAUTIONS WHEN REUSING EXISTING R22 REFRIGERANT PIPES(1) Flowchart
[3] Service tools Use the below service tools as exclusive tools for R410A refrigerant.
No. Toolname Specifications
1 Gaugemanifold · OnlyforR410A· Usetheexistingfittingspecifications.(UNF1/2)· Usehigh-tensionsidepressureof5.3MPa·Gorover.
2 Chargehose · OnlyforR410A· Usepressureperformanceof5.09MPa·Gorover.
3 Electronicscale —
4 Gasleakdetector · UsethedetectorforR134a,R407CorR410A.
5 Adaptorforreverseflowcheck · Attachonvacuumpump.
6 Refrigerantchargebase —
7 Refrigerantcylinder · OnlyforR410A · Topofcylinder(Pink)· Cylinderwithsyphon
8 Refrigerantrecoveryequipment —
OCH582B
6
(2) Cautions for refrigerant piping workNewrefrigerantR410Aisadoptedforreplacementinverterseries.AlthoughtherefrigerantpipingworkforR410AissameasforR22,exclusivetoolsarenecessarysoasnottomixwithdifferentkindofrefrigerant.FurthermoreastheworkingpressureofR410Ais1.6timeshigherthanthatofR22,theirsizesofflaredsectionsandflarenutsaredifferent.
1ThicknessofpipesBecausetheworkingpressureofR410AishighercomparedtoR22,besuretouserefrigerantpipingwiththicknessshownbelow.(Neverusepipesof0.7mmorbelow.)
2DimensionsofflarecuttingandflarenutThecomponentmoleculesinHFCrefrigerantaresmallercomparedtoconventionalrefrigerants.Inadditiontothat,R410Aisarefrigerant,whichhashigherriskofleakagebecauseitsworkingpressureishigherthanthatofotherrefriger-ants.Therefore,toenhanceairtightnessandstrength,flarecuttingdimensionofcopperpipeforR410Ahasbeenspeci-fiedseparatelyfromthedimensionsforotherrefrigerantsasshownbelow.ThedimensionBofflarenutforR410Aalsohaspartlybeenchangedtoincreasestrengthasshownbelow.SetcopperpipecorrectlyreferringtocopperpipeflaringdimensionsforR410Abelow.For1/2and5/8inchpipes,thedimensionBchanges.Usetorquewrenchcorrespondingtoeachdimension.
3ToolsforR410A(Thefollowingtableshowswhetherconventionaltoolscanbeusedornot.)
1/43/81/25/83/4
6.359.52
12.7015.8819.05
0.80.80.81.0—
0.80.80.81.01.0
Nominaldimensions (in)
Diagram below: Piping diameter and thicknessOutside
diameter (mm)Thickness (mm)
R410A R22
1/43/81/25/83/4
6.359.5212.7015.8819.05
9.113.216.619.7—
9.013.016.219.423.3
Nominaldimensions (in)
Flare cutting dimensionsOutsidediameter
Dimension A ( )+0-0.4 (mm)
(mm) R410A R221/43/81/25/83/4
6.359.52
12.7015.8819.05
17.022.026.0
29.0 —
17.022.024.027.036.0
Nominaldimensions (in)
Flare nut dimensionsOutsidediameter
Dimension B (mm)(mm) R410A R22
Gauge manifoldCharge hoseGas leak detectorRefrigerant recovery equipmentRefrigerant cylinderApplied oil
Safety charger
Charge valve
Vacuum pump
Flare tool
BenderPipe cutterWelder and nitrogen gas cylinderRefrigerant charging scaleVacuum gauge or thermis-tor vacuum gauge and vacuum valveCharging cylinder
Air purge, refrigerant chargeand operation checkGas leak checkRefrigerant recoveryRefrigerant chargeApply to flared section
Prevent compressor malfunction when charging refrigerant by spraying liquid refrigerantPrevent gas from blowing out when detaching charge hoseVacuum drying and airpurge
Flaring work of piping
Bend the pipesCut the pipesWeld the pipesRefrigerant chargeCheck the degree of vacuum. (Vacuum valve prevents back flow of oil and refri-gerant to thermistor vacuum gauge)Refrigerant charge
Tool exclusive for R410ATool exclusive for R410ATool for HFC refrigerantTool exclusive for R410ATool exclusive for R410AEster oil and alkylbenzeneoil (minimum amount)Tool exclusive for R410A
Tool exclusive for R410A
Tools for other refrigerants can be used if equipped with adap-ter for reverse flow checkTools for other refrigerants can be used by adjusting flaring dimensionTools for other refrigerants can be usedTools for other refrigerants can be usedTools for other refrigerants can be usedTools for other refrigerants can be usedTools for other refrigerants can be used
Tool exclusive for R410A
Tools and materials Use R410A tools Can R22 tools be used?
(Usable if equipped with adapter for rever- se flow) (Usable by adjusting flaring dimension)
Can R407C tools be used?
Ester oil: Alkylbenzene oil: minimum amount
(Usable if equipped with adapter for rever- se flow) (Usable by adjusting flaring dimension)
: Prepare a new tool. (Use the new tool as the tool exclusive for R410A.) : Tools for other refrigerants can be used under certain conditions.: Tools for other refrigerants can be used.
DimensionA
DimensionB
OCH582B
7
3 FEATURES
CHARGELESS SYSTEMPRE-CHARGED REFRIGERANT IS SUPPLIED FOR PIPING LENGTH AT SHIPMENTMaximum 30 m (PUHZ-P200/250)
TherefrigerantcircuitwithLEV(LinearExpansionValve)andaccumulatoralwayscontroltheoptimalrefrigerantlevelregardlessofthelength(30mmaximumand5mminimum)ofpiping.Theadditionalrefrigerantchargingworkduringinstal-lationoftencausesproblems.Itiscompletelyeliminatedbychargelesssystem.Thisuniquesystemimprovesthequalityandreliabilityoftheworkdone.Italsohelpstospeeduptheinstallationtime.
PUHZ-P200YKAPUHZ-P250YKA
OCH582B
8
4 SPECIFICATIONS
5860
A
kW
W
kWK/min(CFM)
dBdB
mm (in)mm (in)mm (in)kg (lb)
kg (lb)L
mm (in)mm (in)
Power supply (phase, cycle, voltage) Max. currentExternal finish Refrigerant control Compressor Model Motor output Starter type Protection devices
Crankcase heaterHeat exchanger Fan Fan (drive) o No. Fan motor output AirflowDefrost method Noise level Dimensions
Weight Refrigerant Charge Oil (Model)Pipe size O.D.
Connection method
Between the indoor & outdoor unit
CoolingHeating
WDH
LiquidGas
Indoor sideOutdoor sideHeight differencePiping length
Service Ref. PUHZ-P250YKA.UKPUHZ-P250YKAR1.UK
PUHZ-P200YKA.UKPUHZ-P200YKAR1.UK
Munsell 3Y 7.8/1.1Linear Expansion Valve
Hermetic
Line start
—Plate fin coil
Propeller fan o 20.200 + 0.200140 (4,940)
Reverse cycle
1,050 (41-5/16)330 + 40 (13+1-9/16)
1,338 (52-11/16)
R410A
FlaredFlared & BrazingMaximum 30 mMaximum 70 m
21
5.5
HP switchComp. surface thermo
3 phase 50 Hz, 400 V
OU
TDO
OR
UN
ITRE
FRIGE
RANT
PIPIN
G
4.7
19
127 (281)
6.5
9.52 (3/8)25.4 (1)
135 (298)
7.7
12.7 (1/2)25.4 (1)
ANB52FRNMT
2.30 (FVC68D)
5962
OCH582B
9
5 DATA
5-1. REFILLING REFRIGERANT CHARGE (R410A: kg) PUHZ-P200/250
ANB52FRNMT
Service Ref.
Compressor model
(at 20°C)
U-V
U-W
W-V
WindingResistance
( " )
0.30
0.30
0.30
PUHZ-P200/250YKA.UKPUHZ-P200/250YKAR1.UK
Additionalchargeisrequiredforpipeslongerthan30m.
Service Ref.Pipinglength(oneway) Initial
charged10m 20m 30m 40m 50m 60m 70m
PUHZ-P200YKA.UKPUHZ-P200YKAR1.UK
5.9 6.2 6.5 +0.9(7.4) +1.8(8.3) +2.7(9.2) +3.6(10.1) 6.5
PUHZ-P250YKA.UKPUHZ-P250YKAR1.UK
6.9 7.3 7.7 +1.2(8.9) +2.4(10.1) +3.6(11.3) +4.8(12.5) 7.7
5-3. COMPRESSOR TECHNICAL DATA
5-2. ADJUSTING THE AMOUNT OF REFRIGERANT PUHZ-P200/250Amount of additional refrigerant charge (kg)
30 m and less 31–40 m and less 41–50 m and less 51–60 m and less 61–70 m and less
0.9 kg 1.8 kg 2.7 kg 3.6 kg
1.2 kg 2.4 kg 3.6 kg 4.8 kg
Service Ref. Permittedpipe length
PUHZ-P200YKA.UKPUHZ-P200YKAR1.UK
PUHZ-P250YKA.UKPUHZ-P250YKAR1.UK
70 m or less
Initial charge(kg)
6.5
7.7
No additionalcharge necessary
OCH582B
10
5-4. NOISE CRITERION CURVES
1.5m
1mMICROPHONE
UNIT
GROUND
90
80
70
60
50
40
30
20
1063 125 250 500 1000 2000 4000 8000
APPROXIMATETHRESHOLD OFHEARING FORCONTINUOUSNOISE
OC
TAVE
BA
ND
SO
UN
D P
RES
SUR
E LE
VEL,
dB
(0 d
B =
0.0
002
µbar
)
BAND CENTER FREQUENCIES, Hz
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
PUHZ-P200YKA.UKPUHZ-P200YKAR1.UK COOLING
MODE
HEATING58
SPL(dB)
60
LINE
90
80
70
60
50
40
30
20
1063 125 250 500 1000 2000 4000 8000
APPROXIMATETHRESHOLD OFHEARING FORCONTINUOUSNOISE
OC
TAVE
BA
ND
SO
UN
D P
RES
SUR
E LE
VEL,
dB
(0 d
B =
0.0
002
µbar
)
BAND CENTER FREQUENCIES, Hz
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
PUHZ-P250YKA.UKPUHZ-P250YKAR1.UK COOLING
MODE
HEATING59
SPL(dB)
62
LINE
OCH582B
11
5-5. STANDARD OPERATION DATA
PLA-RP125BAR4.UKPLA-RP100BAR4.UK
PLA-RP125BAR4.UKPLA-RP100BAR4.UK
1, 501, 50
230230
0.150.14
1.000.94
PUHZ-P250YKA.UKPUHZ-P250YKAR1.UK
PUHZ-P200YKA.UKPUHZ-P200YKAR1.UK
3, 503, 50
400400
HeatingCoolingHeatingCooling
11.7810.578.637.77
19,000 22,400 22,000 27,000
5.92 6.36 7.83 8.41
79.274.568.866.8
50.250.345.048.8
−2.05.6−2.17.6
7.57.57.57.5
20272027
15191519
45.312.441.613.3
735735
624624
0.710.74
0.180.21
—
—
—
—
2.993.032.97 2.81
0.630.830.89 0.63
0.13
0.87
0.14
0.94
Ele
ctric
al c
ircui
tR
efrig
eran
t circ
uit
Indo
or s
ide
Out
door
side
Representative matching
SHF
BF
Mode
Capacity
InputTota
l
Phase , Hz
Voltage
Input
Current
Outdoor unit
Phase , Hz
Voltage
Current
Discharge pressure
Suction pressure
Discharge temperature
Condensing temperature
Suction temperature
Ref. pipe length
Intake air temperature
Discharge air temperature
Intake air temperature
V
kW
A
V
A
MPa
MPa
°C
°C
°C
m
°C
°C
°C
°C
°C
Indoor unit
D.B.
W.B.
D.B.
D.B.
W.B.
W
kW
OCH582B
12
Unit: mm
6 OUTLINES AND DIMENSIONS
PUHZ-P200YKA.UKPUHZ-P200YKAR1.UKPUHZ-P250YKA.UKPUHZ-P250YKAR1.UK
OCH582B
13
7 WIRING DIAGRAM
PUHZ-P200YKA.UK PUHZ-P250YKA.UKPUHZ-P200YKAR1.UK PUHZ-P250YKAR1.UK
Terminal Block <Power Supply>Terminal Block <Indoor/Outdoor>Motor for CompressorFan MotorSolenoid Valve (Four-Way Valve)High Pressure SwitchThermistor <Liquid>Thermistor <2-Phase Pipe>Thermistor <Ambient>Thermistor <Heat Sink>Thermistor <Comp. Surface>Linear Expansion ValveReactorReactorRush Current Protect ResistorFuse <T15AL250V>Capacitor
P.B.
N.F.
C.B.
TB-U/V/WTB-L1/L2/L3TB-P1/P3X52CA/B
LI1/LI2/LI3/NILO1/LO2/LO3GD1, GD2
SW1
SW4SW5SW6SW7SW8
Power Circuit BoardConnection Terminal <U/V/W-Phase>Connection Terminal <L1/L2/L3-Power Supply>Connection Terminal52C RelayNoise Filter Circuit BoardConnection Terminal <L1/L2/L3/N-Power Supply>Connection Terminal <L1/L2/L3-Power Supply>Connection Terminal <Ground>Controller Circuit BoardSwitch <Manual Defrost, Defect History,Record Reset, Refrigerant Address>Switch <Test Operation>Switch <Function Switch, Model Select>Switch <Model Select>Switch <Function Switch>Switch <Function Switch>
SW9SWPCN31CN3SCNDMCN51SV1SSCNM
CNMNT
CNVMNT
LED1, LED2F3, F4X51, X52, X54
Switch <Function Switch>Switch <Pump Down>Connector <Emergency Operation>Connector <Connection for Option>Connector <Connection for Option>Connector <Connection for Option>Connector <Connection for Option>Connector <Connection for Option>Connector <Connection for Option>Connector <Connect to Optional M-NET Adapter Board>Connector <Connect to Optional M-NET Adapter Board>LED <Operation Inspection Indicators>Fuse <T6.3AL250V>Relay
SYMBOLTB1TB2MCMF1, MF221S463HTH3TH6TH7TH8TH32LEV-AACL4DCLRSFUSE1, FUSE2CY1, CY2
SYMBOL SYMBOLNAME NAME NAME
CNDC(PNK)
3
1
MF1
CNF1(WHT)1
7
MS3~
MF2
CNF2(WHT)1
7
2
MS3~
TRANS
X54
31
P.B.
U
POWER SUPPLY3N ~400V 50Hz
TB1
V W
RED
WHT
BLK
MC
7
L 1
L 2
L 3
N
N.F.
CNDC(PNK)
31 CNL(BLU)
13
CNAC2(RED)31
CNCT(RED) 1 2
LO3
GD1
NI
LI1
LI2
LI3
GD2
S1
S2
S3
2
2ACL4
RED
WHT
BLK
BLU
RED
WHT
BLK
TB2
X52CA RED
BLK
WHT
BLK
YLW
ORN
BRN
TB-P
1
TB-P
3
RED
GRN/
YLW
BLK
BLK
WHT
WHT
INDOORUNIT
1 2CN6
(WHT)
1 2CN5
(RED)CN2
(RED)
1 7 1 2CN4
(WHT)
TB-U TB
-VTB
-W
L3IN
TB-L
2
TB-L1
TH8
t°
RSRED
MS3~
22
CY1
CY2
C. B. TH6TH7 TH3
21S4
t° t° t°
LEV-A
CNS(WHT)
CNAC(WHT)
F3
F4 21S4(GRN)
CN2(RED)
CN4(WHT)
SW5TH7/6
(RED)TH3
(WHT)CNVMNT
(WHT)CNMNT(WHT)
SW8
SW6
SW1
SW7
SW9
CN31
X52
63H(YLW)
2
7
* 11 4 1 2
1 3
31 1 5
1 21 7
13
1 2
3 431 SV1
(GRY)
LEV-A(WHT)
51
SS(WHT)
X51
31
63H
M
CN3S(WHT)
31
CNDM(WHT)
CN51(WHT)
31
51
1 2TH32(BLK)
TH32
t°
When M-NET adapter is connected
CN2M(WHT)
CN5(WHT)
CND(WHT)
M-NET
M-NET ADAPTER
TB7A B S
51
5
1
2
13
3
3 5
CNM(WHT)
1 14LE
D1
LED2
SWP
SW4
* 1
TB-L3
X52CB
L3OUT
FUSE
1
FUSE
2
WHT
RED
WHT
RED
DCL
CNAC1(WHT) 31
LO1
LO2
1 2 3 4 5 6 7 8OFFON
1 2 3 4 5 6OFFON
1 2 3 4 5 6 7 8OFFON
1 2 3 4 5 6OFFON
SW6MODEL SW5-6 *2
200Y
250Y
The black square (■) indicates a switch position.*1. MODEL SELECT
*2. SW5-1 to 5: Function switch
TB7 Terminal Block <M-NET connection>SYMBOL NAME
CN5 Connector <Transmission>CND Connector <Power Supply>CN2M Connector <M-NET communication>
M-NET ADAPTER
OCH582B
Outdoorunitmodel P200/250YOutdoorunitpowersupply 3N~(3ph4-wires),50Hz,400VOutdoorunitinputcapacitymainswitch(Breaker) *1 32A
Wiring
WireNo.×
size(m
m²) Outdoorunitpowersupply 5×Min.4
Indoorunit-Outdoorunit *2 Cablelength50m:3×4(Polar)/Cablelength80m:3×6(Polar)
Indoorunit-Outdoorunitearth *2 1×Min.2.5
Remotecontroller-Indoorunit *3 2×0.3(Non-polar)
Circuit
rating
OutdoorunitL1-N,L2-N,L3-N(3phase) *4 230VACIndoorunit-OutdoorunitS1-S2 *4 230VACIndoorunit-OutdoorunitS2-S3 *4 24VDCRemotecontroller-Indoorunit *4 12VDC
*1.Abreakerwithatleast3.0mmcontactseparationineachpoleshallbeprovided.Useearthleakagebreaker(NV). Makesurethatthecurrentleakagebreakerisonecompatiblewithhigherharmonics. Alwaysuseacurrentleakagebreakerthatiscompatiblewithhigherharmonicsasthisunitisequippedwithaninverter. Theuseofaninadequatebreakercancausetheincorrectoperationofinverter.*2.Maximum80m.Totalmaximumincludingallindoor/indoorconnectionis80m.
•UseonecableforS1andS2andanotherforS3asshowninthepicture. •Maximum50m.TotalmaximumforPEA.Wiringsize3×1.5(Polar).*3.The10mwireisattachedintheremotecontrolleraccessory.*4.ThefiguresareNOTalwaysagainsttheground. S3terminalhas24VDCagainstS2terminal.HoweverbetweenS3andS1,theseterminalsareNOTelectricallyinsulatedbythetransformerorotherdevice.
Caution: Be sure to install N-Line. Without N-Line, it could cause damage to the unit.
14
8 WIRING SPECIFICATIONS8-1. FIELD ELECTRICAL WIRING (power wiring specifications)
B
B Earth leakage breakerC wiring circuit breaker or isolating switch
C
LN
12
12
S1
Indoor unit
S2S3
S1S2S3
S1S2S3
Unitpowersupply Indoor/outdoor
unit connection cable
Indoor unit
Outdoor unit
Remote controller B
B Earth leakage breakerC wiring circuit breaker or isolating switch
C
12
12
12
S1S2S3
S1S2S3
S1S2S3
S1S2S3
Indoor/outdoorconnection cable
Indoor unit
Unitpowersupply
Indoor unit
Indoor unit
Outdoor unit
Remote controller
LN
Synchronized twin and triple system Electrical wiring•Synchronizedtwin •Synchronizedtriple
Notes: 1. Wiring size must comply with the applicable local and national code..2. Power supply cables and Indoor/Outdoor unit connecting cables shall not be lighter than polychloroprene sheathed flexible cable.
3. Install an earth longer than other cables.
Warning: In case of A-control wiring, there is high voltage potential on the S3 terminal caused by electrical circuit design that has no electrical insulation between power line and communication signal line. Therefore, please turn off the main power supply when servicing. And do not touch the S1, S2, S3 terminals when the power is energized. If isolator should be used between indoor unit and outdoor unit, please use 3-pole type.
(Design 60245 IEC 57)
S1
S2
S3
S1
S2
S3
A-ControlOutdoor Unit
3 poles isolator
Power supply
Isolator
A-ControlIndoor Unit
Neversplicethepowercableortheindoor-outdoorconnectioncable,otherwiseitmayresultinasmoke,afireorcommunicationfailure.
S1S2S3
Indoor/outdoor unit connection cable
Indoor unit
Unitpowersupply
Unitpowersupply
Outdoor unit
L1
L2
L3B
N
S1S2S3
L1
L2
L3
N
C BC
12
Remote controller
B Earth leakage breakerC wiring circuit breaker or isolating switch
1:1 System (Indoor: PEA-200, 250) 1:2 System (Indoor: PEA-400, 500)
S1S2S3
Indoor/outdoor unit connection cable
Indoor unit
Unitpowersupply
Unitpowersupply
Outdoor unit No.1
L1
L2
L3B
N
S1S2S3
L1
L2
L3
N
B Earth leakage breakerC wiring circuit breaker or isolating switch
C BC
S1S2S3
Indoor/outdoor unit connection cable
TB4-1
TB4-2
Unitpowersupply
Outdoor unit No.2
L1
L2
L3B
N
S1S2S3
C
12
Remote controller
OCH582B
15
8-2. SEPARATE INDOOR UNIT/OUTDOOR UNIT POWER SUPPLIESThe following illustrations show available connection patterns.The outdoor unit power supply patterns vary on models.
Simultaneous twin/triple system
Affix a label B that is included with the manuals near each wiring diagram for the indoor and outdoor units.
<For models without heater>The optional indoor power supply terminal kit is required.
A
B
C
D
E
F
G
H
J
Outdoor unit power supplyEarth leakage breakerWiring circuit breaker or isolating switchOutdoor unitIndoor unit/outdoor unit connecting cablesRemote controllerIndoor unitOptionIndoor unit power supply
K Indoor unit earth
If the indoor and outdoor units have separate power supplies, refer to the table below.If the optional indoor power supply terminal kit is used, change the indoor unitelectrical box wiring referring to the figure in the right and the DIP switch settings of the outdoor unit control board.
Indoor power supply terminal kit (option)Indoor unit electrical box connector con-nection changeLabel affixed near each wiring diagramfor the indoor and outdoor unitsOutdoor unit DIP switch settings (whenusing separate indoor unit/outdoor unitpower supplies only)
Indoor unit specificationsRequired
Required
Required
Electric heater(For models withheater)
Connectors (connections when shippedfrom the factory are for indoor unit powersupplied from outdoor unit)
Indoor unit power supplied from outdoor unit(when shipped from factory)
If the indoor andoutdoor units haveseparate powersupplies, change theconnections of theconnectors as shownin the followingfigure.
Connectors
Indoor unitcontrol board
Separate indoor unit/outdoor unit powersupplies
Electric heater(For models withheater)
S1S2S3
LN
BLUEBLUE
YELLOWYELLOW
CND
CN01ORANGE
CN01ORANGE
S1S2S3
LN
YELLOWBLUE
BLUEYELLOW
CND
Indoor unitcontrol board
Note: There are 3 types of labels; A, B, and C. Affix the appropriate label to the units according to the wiring method.
ONOFF
Set the SW8-3 to ON.1 2 (SW8)
3
E
F
D G
K K
HG
HG
H
LN
LN
S1S2S3
S1S2S3
12
LN
S1S2S3
12
LN
S1S2S3
12
A B C B CJ
*1. A breaker with at least 3 mm contact separation in each pole shall be provided. Use earth leakage breaker (NV). The breaker shall be provided to ensure disconnection of all active phase conductor of the supply.*2. Maximum 120 m*3.The 10 m wire is attached in the remote controller accessory. Maximum 500 m*4.The figures are NOT always against the ground.
Notes: 1. Wiring size must comply with the applicable local and national code.2. Power supply cables and indoor unit/outdoor unit connecting cables shall not be lighter than polychloroprene sheathed flexible cable. (Design 60245 IEC 57)3. Install an earth longer than other cables.
Indoor unit modelIndoor unit power supplyIndoor unit input capacity *1Main switch (Breaker)
Indoor unit power supplyIndoor unit power supply earthIndoor unit-Outdoor unit *2Indoor unit-Outdoor unit earthRemote controller-Indoor unit *3Indoor unit L-N *4Indoor unit-Outdoor unit S1-S2 *4Indoor unit-Outdoor unit S2-S3 *4Remote controller-Indoor unit *4
RP35–140~/N (single), 50 Hz, 230 V
16 A
3 o Min. 1.51 o Min. 1.52 o Min. 0.3
–2 o 0.3 (Non-polar)
230 V AC –
24 V DC12 V DC
Circ
uit
ratin
g
Wiri
ngW
ire N
o. o
size
(mm2 )
OCH582B
16
8-3. INDOOR – OUTDOOR CONNECTING CABLE
Be sure to connect the indoor-outdoor connecting cables directly to the units (no intermediate connections).Intermediate connections can lead to communication errors if water enters the cables and causes insufficient insulation to earth or a poor electrical contact at the intermediate connection point.
Indoor unit-Outdoor unit
Indoor/Outdoor separatepower supply Max. 120m
2 o Min. 0.3
—Indoor unit-Outdoor unit earth
Wire No. o Size (E)
Note: The optional indoor power supply terminal kit is necessary.
WIRING SPECIFICATIONS FOR 220−240 V, 50 Hz(INDOOR-OUTDOOR CONNECTING CABLE)
Cross section of cable Wire size (mm2) Number of wires Polarity L (m)*5Round
2.5 3Clockwise : S1-S2-S3(Pay attention to stripe of yellow and green.)
(30)*1
Flat2.5 3
Not applicable(Because center wire has no cover finish)
Not applicable*4
Flat1.5 4
From left to right : S1-Open-S2-S3 (18)*2
Round2.5 4
Clockwise : S1-S2-S3-Open(Connect S1 and S3 to the opposite angle.)
(30)*3
Note: Power supply cords of appliances shall not be lighter than design 60245 IEC or 227 IEC.
*1 In case that cable with stripe of yellow and green is available.*2 In case of regular polarity connection (S1-S2-S3), wire size is 1.5 mm².*3 In case of regular polarity connection (S1-S2-S3).*4 In case that flat cables are connected as this picture, they can be used up to 30 m.*5 Mentioned cable length is just a reference value.
It may be different depending on the condition of installation, humidity or materials, etc.
-
(3C Flat cable × 2)
OCH582B
17
8-4. M-NET WIRING METHODPoints to note:(1)Outsidetheunit,transmissionwiresshouldstayawayfromelectricwiresinordertopreventelectromagneticnoisefrom
makinganinfluenceonthesignalcommunication.Placethematintervalsofmorethan5cm.Donotputtheminthesameconduittube.
(2)Terminalblock(TB7)fortransmissionwiresshouldneverbeconnectedto220–240Vpowersupply.Ifitisconnected,electronicpartsonM-NETP.C.boardmayburnout.
(3)Use2-core×1.25mm²shieldwire(CVVS,CPEVS)forthetransmissionwire.Transmissionsignalsmaynotbesentorreceivednormallyifdifferenttypesoftransmissionwiresareputtogetherinthesamemulti-conductorcable.Neverdothisbecausethismaycauseamalfunction.
ItisacceptableifM-NETwire(non-polar,2-cores)isarrangedinadditiontothewiringforA-control.
(4)EarthonlyoneofanyappliancesthroughM-NETtransmissionwire(shieldwire).Communicationerrormayoccurduetotheinfluenceofelectromagneticnoise.
“Ed”errorwillappearontheLEDdisplayofoutdoorunit. “0403”errorwillappearonthecentral-controlremotecontroller.
Iftherearemorethan2earthingspotsontheshieldwire,noisemayenterintotheshieldwirebecausetheearthwireandshieldwireform1circuitandtheelectricpotentialdifferenceoccursduetotheimpedancedifferenceamongearthingspots.Incaseofsinglespotearthing,noisedoesnotenterintotheshieldwirebecausetheearthwireandshieldwiredonotform1circuit.
Toavoidcommunicationerrorscausedbynoise,makesuretoobservethesinglespotearthingmethoddescribedintheinstallationmanual.
Centralized controller
Refrigerantaddress 00M-NETaddress 01
A-controlremotecontroller
A-controlremotecontroller
A-controlremotecontroller
Refrigerantaddress 00M-NETaddress 02
Refrigerantaddress 00M-NETaddress 03Power
supply unit
Centralizedcontroller
M-NET transmission wire
O Bad example (Multi spot earthing of shield wire)
Good example 1 (Single spot earthing of shield wire)
Power supply unit
M-NET typeoutdoor unit
M-NET typeoutdoor unit
M-NET typeoutdoor unit
M-NET typeoutdoor unit
M-NET transmission wire
M-NET typeoutdoor unit
M-NET typeoutdoor unit
M-NET typeoutdoor unit
M-NET transmission wire
M-NET typeoutdoor unit
M-NET typeoutdoor unit
Good example 2 (Single spot earthing of shield wire)
Centralizedcontroller
Centralizedcontroller
Power supply unit
Power supply unit
OCH582B
18
8-4-3. Regulations in address settingsInthecaseofmultiplegroupingsystem,M-NETandrefrigerantaddresssettingsshouldbedoneasexplainedintheabovesection.Setthelowestnumberinthegroupfortheoutdoorunitwhoserefrigerantaddressis“00”asitsM-NETaddress.
Refrigerantaddressescanbeoverlappediftheyareinthedifferentgroup.
Note:IngroupB,M-NETaddressoftheoutdoorunitwhoserefrigerantaddressis“00”isnotsettotheminimuminthegroup.As“3”isrightforthissituation,thesettingiswrong.TakinggroupAasagoodsample,settheminimumM-NETaddressinthegroupfortheoutdoorunitwhoserefrigerantaddressis“00”.
8-4-1. M-NET address settingInA-controlmodels,M-NETaddressandrefrigerantaddressshouldbesetonlyfortheoutdoorunit.SimilartoCITYMULTIsystem,thereisnoneedtosettheaddressofoutdoorunitandremotecontroller.Toconstructacentralcontrolsystem,thesettingofM-NETaddressshouldbeconductedonlyupontheoutdoorunit.Thesettingrangeshouldbe1to50(thesameasthatoftheindoorunitinCITYMULTIsystem),andtheaddressnumbershouldbeconsecutivelysetinasamegroup.
Addressnumbercanbesetbyusingrotaryswitches(SW11for1stdigitandSW12for2nddigit),whichislocatedontheM-NETboardofoutdoorunit.(Initialsetting:alladdressesaresetto“0”.)
8-4-2. Refrigerant address settingInthecaseofmultiplegroupingsystem(multiplerefrigerantcircuitsin1group),indoorunitsshouldbeconnectedbyremotecontrollerwiring(TB5)andtherefrigerantaddressneedstobeset.Leavetherefrigerantaddressesto“00”ifthegroupset-tingisnotconducted.SettherefrigerantaddressbyusingDIPSW1-3to-6ontheoutdoorcontrollerboard.[Initialsetting:allswitchesareOFF.(Allrefrigerantaddressesare“00”.)]
1234567890 1234567890
1234567890 1234567890
1234567890
1234567890
1 2
~
50M-NET Address No.<Setting example>
Switchsetting
SW111stdigitSW122nddigit
OFF
ON
1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6
1 2 3 4 5 61 2 3 4 5 61 2 3 4 5 61 2 3 4 5 61 2 3 4 5 61 2 3 4 5 61 2 3 4 5 61 2 3 4 5 6
0Refrigerant address
OFF
ON
8
OFF
ON
1
OFF
ON
9
OFF
ON
10
OFF
ON
11
OFF
ON
12
OFF
ON
13
OFF
ON
14
OFF
ON
15
OFF
ON
2
OFF
ON
3
OFF
ON
4
OFF
ON
5
OFF
ON
6
OFF
ON
7
A-controlremotecontroller
Group A Group B Group C
A-controlremotecontroller
TB5
A-controlremotecontroller
Refrigerantaddress 00M-NETaddress 01
Refrigerantaddress 00M-NETaddress 02
Refrigerantaddress 01M-NETaddress 03
Refrigerantaddress 00M-NETaddress 04Power
supply unit
Centralizedcontroller
Power supply unit
A-controlremotecontroller
A-controlremotecontroller
TB5
Group A Group B
Refrigerantaddress 00M-NETaddress 01
Refrigerantaddress 01M-NETaddress 02
Refrigerantaddress 00M-NETaddress 04
Refrigerantaddress 01M-NETaddress 03
Refrigerantaddress 02M-NETaddress 05
Centralizedcontroller
M-NET wiring(1)Use2-core×1.25mm²shieldwireforelectricwires. (Excludingthecaseconnectingtosystemcontroller.)(2)ConnectthewiretotheM-NETterminalblock.Connectonecoreofthetransmission
wire(non-polar)toAterminalandtheothertoB.Peeltheshieldwire,twisttheshieldparttoastringandconnectittoSterminal.
(3)Inthesystemwhichseveraloutdoorunitsarebeingconnected,theterminal(A,B,S)onM-NETterminalblockshouldbeindividuallywiredtotheotheroutdoorunit’sterminal,i.e.AtoA,BtoBandStoS.Inthiscase,chooseoneofthoseoutdoorunitsanddriveascrewtofixanearthwireontheplateasshownontherightfigure.
Transmissionwire
Shield part
M-NET terminal block Earth
wire
A B S
OCH582B
19
Unit: mm (in)
9 REFRIGERANT SYSTEM DIAGRAM
PUHZ-P200YKA.UK PUHZ-P250YKA.UKPUHZ-P200YKAR1.UK PUHZ-P250YKAR1.UK
Heat exchangerThermistor TH6(2-phase pipe)
Thermistor TH7(Ambient)
Distributor
Accumulator
Compressor
Refrigerant GAS pipeconnection [25.4([1 inch)
Refrigerant LIQUID pipeP200 : connection [9.52([3/8 inch)P250 : connection [12.7([1/2 inch)
Stop valve(with service port)
4-way valve
Linear expansion valve A
Thermistor TH32(Comp, surface)
Muffler
Ball valve
#50Strainer
Oil return hole with strainer #40
Strainer#100
Strainer#100
Strainer#100
Refrigerant flow in coolingRefrigerant flow in heating
Charge plug(High pressure)
<Blazing>
Thermistor TH8(Control protection)
HEX
Stop valve
Thermistor TH3(Liquid)
LEV-A
High pressureswitch 63H
Charge plug(Low pressure)
OCH582B
20
9-2. START AND FINISH OF TEST RUN • Operationfromtheindoorunit Executethetestrunusingtheinstallationmanualfortheindoorunit. • OperationfromtheoutdoorunitByusingtheDIPswitchSW4onthecontrolboardofoutdoorunit,testruncanbestartedandfinished,anditsoperationmode(cooling/heating)canbesetup.
1Settheoperationmode(cooling/heating)usingSW4-2. 2TurnonSW4-1tostarttestrunwiththeoperationmodesetbySW4-2. 3TurnoffSW4-1tofinishthetestrun. • Theremaybeafaintknockingsoundaroundthemachineroomafterpowerissupplied.However, thisisnotaproblemwithproductbecausethelinearexpansionpipeisjustmovingtoadjust openingpulse. • Theremaybeaknockingsoundaroundthemachineroomforseveralsecondsaftercompressorstartsoperating.However,thisisnotaproblemwithproductbecauseitisgeneratedbythecheckvalveitselfduetoasmallpressuredifferenceintherefrigerantcircuit.
Note:The operation mode cannot be changed by SW4-2 during test run. (To change test run mode, stop the unit by SW4-1, change the operation mode and restart the test run by SW4-1.)
OFF1 2
ON
<SW4>
A B
C D
A Stop C OperationB Cooling D Heating
9-1. REFRIGERANT COLLECTING (PUMP DOWN)Whenrelocatingordisposingoftheindoor/outdoorunit,pumpdownthesystemfollowingtheprocedurebelowsothatnorefrig-erantisreleasedintotheatmosphere.1Turnoffthepowersupply(circuitbreaker).2Connectthelow-pressurevalveonthegaugemanifoldtothechargeplug(low-pressureside)ontheoutdoorunit.3Closetheliquidstopvalvecompletely.4Supplypower(circuitbreaker).
•Whenpowerissupplied,makesurethat“CENTRALLYCONTROLLED”isnotdisplayedontheremotecontroller.If“CEN-TRALLYCONTROLLED”isdisplayed,therefrigerantcollecting(pumpdown)cannotbecompletednormally.
•Start-upoftheindoor-outdoorcommunicationtakesabout3minutesafterthepower(circuitbreaker)isturnedon.Startthepump-downoperation3to4minutesafterthepower(circuitbreaker)isturnedon.
5Performtherefrigerantcollectingoperation(coolingtestrun).•Pushthepump-downSWPswitch(push-buttontype)onthecontrolboardoftheoutdoorunit.Thecompressorandventi-lators(indoorandoutdoorunits)startoperating(refrigerantcollectingoperationbegins).(LED1andLED2onthecontrolboardoftheoutdoorunitarelit.)
•Onlypushthepump-downSWPswitchiftheunitisstopped.However,eveniftheunitisstoppedandthepump-downSWPswitchispushedlessthan3minutesafterthecompressorstops,therefrigerantcollectingoperationcannotbeperformed.Waituntilthecompressorhasbeenstoppedfor3minutesandthenpushthepump-downSWPswitchagain.
6Fullyclosetheballvalveonthegaspipesideoftheoutdoorunitwhenthepressuregaugeonthegaugemanifoldshows0.05to0MPa[Gauge](approx.0.5to0kgf/cm²)andquicklystoptheairconditioner.•Becausetheunitautomaticallystopsinabout3minuteswhentherefrigerantcollectingoperationiscompleted(LED1off,LED2lit),besuretoquicklyclosethegasballvalve.However,ifLED1islit,LED2isoff,andtheunitisstopped,opentheliquidstopvalvecompletely,closethevalvecompletelyafter3minutesormorehavepassed,andthenrepeatstep5.(Openthegasballvalvecompletely.)
•Iftherefrigerantcollectingoperationhasbeencompletednormally(LED1off,LED2lit),theunitwillremainstoppeduntilthepowersupplyisturnedoff.
•Notethatwhentheextensionpipingisverylongwithalargerefrigerantamount,itmaynotbepossibletoperformapumpdownoperation.Inthiscase,userefrigerantrecoveryequipmenttocollectalloftherefrigerantinthesystem.
7Turnoffthepowersupply(circuitbreaker),removethegaugemanifold,andthendisconnecttherefrigerantpipes.
Warning:When pumping down the refrigerant, stop the compressor before disconnecting the refrigerant pipes.• If the refrigerant pipes are disconnected while the compressor is operating and the stop valve (ball valve) is open, the
pressure in the refrigeration cycle could become extremely high if air is drawn in, causing the pipes to burst, per-sonal injury, etc.
OCH582B
21
10 TROUBLESHOOTING
<Check code displayed by self-diagnosis and actions to be taken for service (summary)>Presentandpastcheckcodesarelogged,andtheycanbedisplayedonthewiredremotecontrollerandcontrolboardofout-doorunit.Actionstobetakenforservice,whichdependsonwhetherornotthetroubleisreoccurringinthefield,aresumma-rizedinthetablebelow.Checkthecontentsbelowbeforeinvestigatingdetails.
10-1. TROUBLESHOOTING
Unit conditions at service Check code Actions to be taken for service (summary)
The trouble is reoccurring.
Displayed
Not displayed
Judge what is wrong and take a corrective action according to “10-4. SELF-DIAGNOSIS ACTION TABLE”.
Conduct trouble shooting and ascertain the cause of thetrouble according to “10-5. TROUBLESHOOTING OF PROBLEMS”.
The trouble is not reoccurring.
Logged
Not logged
1Consider the temporary defects such as the work of protection devices in the refrigerant circuit including compressor, poor connection of wiring, noise, etc. Re-check the symptom, and check the installation environment, refrigerant amount, weather when the trouble occurred, matters related to wiring, etc. 2Reset check code logs and restart the unit after finishing service.3There is no abnormality in electrical component, controller board, remote controller, etc.
1Re-check the abnormal symptom.2Conduct trouble shooting and ascertain the cause of the trouble according to “10-5. TROUBLESHOOTING OF PROBLEMS”.3Continue to operate unit for the time being if the cause is not ascertained.4There is no abnormality concerning of parts such as electrical component, controller board, remote controller, etc.
10-2. CHECK POINT UNDER TEST RUN10-2-1. Before test run• Afterinstallationofindoorandoutdoorunits,pipingworkandelectricwiringwork,re-checkthatthereisnorefrigerantleak-age,loosenedconnectionsandincorrectpolarity.
• Measureimpedancebetweenthegroundandthepowersupplyterminalblock(L,N)ontheoutdoorunitby500VMeggerandcheckthatitis1.0M"orover.
• Donotuse500VMeggertoindoor/outdoorconnectingwireterminalblock(S1,S2,S3)andremotecontrollerterminalblock (1,2).Thismaycausemalfunction.• Makesurethattestrunswitch(SW4)issettoOFFbeforeturningonpowersupply.• Turnonpowersupply12hoursbeforetestruninordertoprotectcompressor.• Forspecificmodelswhichrequirehigherceilingsettingsorauto-recoveryfeaturefrompowerfailure,makeproperchangesofsettingsreferringtothedescriptionof“11.FUNCTIONSETTING”.Makesuretoreadoperationmanualbeforetestrun.(Especiallyitemstosecuresafety.)
OCH582B
22
F1 F2 F3 F4
unem ecivreS
rosruC:unem niaM
Test runInput maintenance info.Function settingCheckSelf check
F1 F2 F3 F4
Test run menu
CursorService menu:
Test runDrain pump test run
1Select"Service"fromtheMainmenu,andpressthe button.
2Select"Testrun"withthe F1 or F2 button,andpressthe button.
Select"Testrun"withthe F1 or F2 button,andpressthe button.
F1 F2 F3 F4
CoolPipe
AutoSwitch disp.
Mode Fan
RemainTest run
F1 F2 F3 F4
Remain
Vane
Coolmode:Checkthecoldairblowsout.Heatmode:Checkthewarmairblowsout.
Press the F1 button togo throughtheoperationmodes in theorderof "CoolandHeat".
Checktheautovanewiththe F1 F2 buttons.
Pressthe buttontoreturnto“Testrunoperation”.
Pressthe button.
Whenthetestruniscompleted,the“Testrunmenu”screenwillappear.Thetestrunwillautomaticallystopafter2hours.
Test run operation
Auto vane check
Pressthe buttonandopentheVanesettingscreen.
Functionbuttons
F1 F2 F3 F4
MENU RETURN SELECT ON/OFF
10-2-2. Test run for wired remote controller <PAR-30MAA> <PAR-31MAA>
Checktheoperationoftheoutdoorunit’sfan.
OCH582B
23
F1 F2 F3 F4
Error informationError codeError unit IURef. address Unt#Model nameSerial No.
ResetPage
Error informationContact informationDealer Tel
ResetPage
Reset error: Reset button
Reset error: Reset button
blinks
1 Checkcode,errorunit,refrigerantaddress,unitmodelname,andserialnumberwillappear.Themodelnameandserialnumberwillappearonlyif theinformationhasbeenregistered.
Pressthe F1 or F2 buttontogotothenextpage.
When an error occurs, the following screen will appear.Check the error status, stop the operation, and consult your dealer.
Contactinformation(dealer'sphonenumber)willappeariftheinformationhavebeenregistered.
F1 F2 F3 F4
F1 F2 F3 F4
Error information
Error reset
Error reset
Error codeError unit IURef. address Unt#Model nameSerial No.
ResetPage
Reset current error?
Error reset
OKCancel
Main menu:
Reset error: Reset button
blinks
2 Pressthe F4 buttonorthe buttontoresettheerrorthatisoccurring.
Errors cannot be reset while the ON/OFF operation is prohibited.
Select"OK"withthe F4 button.
Navigating through the screens•TogobacktotheMainmenu.......... button
<Error information>
OCH582B
24
F1 F2 F3 F4
Main
Main display:Cursor Page
Main menuRestrictionEnergy savingNight setbackFilter informationError information
blinks
Whilenoerrorsareoccurring,page2/2oftheerrorinformationcanbeviewedbyselecting"Errorinformation"fromtheMainmenu.Errorscannotberesetfromthisscreen.
<Checking the error information>
<Error history>
F1 F2 F3 F4
unem ecivreS
rosruC:unem niaM
Test runInput maintenance info.Function settingCheckSelf check
F1 F2 F3 F4
Check menu
CursorService menu:
Error historyRefrigerant volume checkRefrigerant leak checkSmooth maintenanceRequest code
F1 F2 F3 F4
Error history
Page DeleteCheck menu:
Error Unt# dd/mm/yy
Error history
Cancel OK
Delete error history?
Error history
Check menu:
Error history deleted
2 Select"Errorhistory"withthe F1 or F2 button,andpressthe button.
Select"Check"withthe F1 or F2 button,andpressthe button.
3Select"Errorhistory"fromtheCheckmenu,andpressthe buttontoviewupto16errorhistoryrecords.
4recordsareshownperpage,andthetoprecordonthefirstpageindicatesthelatesterrorrecord.
Error history
4Todeletetheerrorhistory,pressthe F4 button(Delete)onthescreenthatshowserrorhistory.
Aconfirmationscreenwillappearaskingifyouwanttodeletetheerrorhistory.
Pressthe F4 button(OK)todeletethehistory.
"Errorhistorydeleted"willappearonthescreen.
Pressthe buttontogobacktotheCheckmenuscreen.
Deleting the error history
1 Select"Service"fromtheMainmenu,andpressthe button.
OCH582B
25
ON/OFF TEMP
FAN
VANEMODE
CHECK LOUVER
TEST RUN
AUTO STOP
AUTO START
h
min
TEST RUN
RESETSET CLOCK
7
5
6
2
3,4
10-2-3. Test run for wireless remote controller Measureanimpedancebetweenthepowersupplyterminalblockontheoutdoorunitandgroundwitha500VMeggerandcheckthatitisequaltoorgreaterthan1.0M".1Turnonthemainpowertotheunit.2Pressthebuttontwicecontinuously. (Startthisoperationfromthestatusofremotecontrollerdisplayturnedoff.)
Aandcurrentoperationmodearedisplayed.3Pressthe()buttontoactivatemode,thencheckwhethercoolairblowsoutfromtheunit.
4Pressthe()buttontoactivatemode,thencheckwhetherwarmairblowsoutfromtheunit.
5Pressthebuttonandcheckwhetherstrongairblowsoutfromtheunit.
6Pressthebuttonandcheckwhethertheautovaneoperatesproperly.
7PresstheON/OFFbuttontostopthetestrun.
Note:• Point the remote controller towards the indoor unit receiver
while following steps 2 to 7.• It is not possible to run in FAN, DRY or AUTO mode.
MODE
MODECOOL
HEAT
TEST RUN
FAN
VANE
TEST RUN
OCH582B
26
F1 F2 F3 F4
unem ecivreS
rosruC:unem niaM
Test runInput maintenance info.Function settingCheckSelf check
F1 F2 F3 F4
kcehc fleS
:tceleS
Ref. address
sserddA
F1 F2 F3 F4
kcehc fleSRef. address
Return:teseR
Error Unt # CI.prG
F1 F2 F3 F4
Self check
Return:Reset
Ref. address
Error Grp.-- -Unt# --
When there is no error history
F1 F2 F3 F4
Self check
Delete error history?
Ref. address
Cancel OK
F1 F2 F3 F4
Self check
Return:
Ref. address
Error history deleted
2 Withthe F1 or F2 button,entertherefrigerantaddress,andpressthe button.
Select"Selfcheck"withthe F1 or F2 button,andpressthe button.
1 Select"Service"fromtheMainmenu,andpressthe button.
3 Checkcode,unitnumber,attributewillappear."-"willappearifnoerrorhistoryisavailable.
4 Resettingtheerrorhistory.
Pressthe F4 button(Reset)onthescreenthatshowstheerrorhistory.
Aconfirmationscreenwillappearaskingifyouwanttodeletetheerrorhistory.
Pressthe F4 button(OK)todeletetheerrorhistory.
Ifdeletionfails,"Requestrejected"willappear."Unitnotexist"willappearifnoindoorunitsthatarecorrespondtotheenteredaddressarefound.
Navigating through the screens•TogobacktotheMainmenu.......... button
•Toreturntothepreviousscreen....... button
10-3. HOW TO PROCEED "SELF-DIAGNOSIS"10-3-1. Self-diagnosis <PAR-30MAA> <PAR-31MAA>
OCH582B
27
Ifoperationscannotbecompletedwiththeremotecontroller,diagnosetheremotecontrollerwiththisfunction.
F1 F2 F3 F4
unem ecivreS
rosruC:unem niaM
Maintenance passwordRemote controller check
F1 F2 F3 F4
Remote controller check
:nigeB
Start checking?
F1 F2 F3 F4
Remote controller check
:nigeB
Start checking?
1 Select"Service"fromtheMainmenu,andpressthe button.
Select "Remotecontroller check"with the F1 or F2 button,andpressthe button.
2 Select"Remotecontrollercheck"fromtheServicemenu,andpressthe but-tontostarttheremotecontrollercheckandseethecheckresults.
Tocancel theremotecontrollercheckandexit theRemotecontrollercheckmenuscreen,pressthe orthe button.
Theremotecontrollerwillnotrebootitself.
Check the remote controller display and see if anything is displayed (including lines). Nothing will appear on the remote controller display if the correct voltage (8.5–12 V DC) is not supplied to the remote control-ler. If this is the case, check the remote controller wiring and indoor units.
OK: Noproblemsare foundwith the remotecontroller.Checkotherpartsforproblems.
E3,6832:Thereisnoiseonthetransmissionline,ortheindoorunitoranotherremotecontroller is faulty.Check the transmission lineand theotherremotecontrollers.
NG(ALL0,ALL1):Send-receivecircuitfault.Remotecontrollerneedsreplacing.ERC: Thenumberofdataerrorsisthediscrepancybetweenthenumberof
bits inthedatatransmittedfromtheremotecontrollerandthatofthedatathatwasactually transmittedover thetransmission line. Ifdataerrorsarefound,checkthetransmission lineforexternalnoise inter-ference.
Remote controller check results screen
If the button ispressedafter the remotecontrollercheck resultsaredis-played,remotecontrollercheckwillend,andtheremotecontrollerwillautomati-callyrebootitself.
10-3-2. Remote controller check <PAR-30MAA> <PAR-31MAA>
3
OCH582B
28
•"CHECK"lights,andrefrigerantaddress"00"flashes.
•Checkthattheremotecontroller'sdisplayhasstoppedbeforecontinuing.
•Selecttherefrigerantaddressoftheindoorunitfortheself-diagnosis.
Note:Setrefrigerantaddressusingtheoutdoorunit’sDIPswitch(SW1).(Formoreinformation,seetheoutdoorunitinstallationmanual.)
•Ifanairconditionererroroccurs,theindoorunit'ssensoremitsanintermittentbuzzersound,theoperationlightflashes,andthecheckcodeisoutput.(Ittakes3secondsatmostforcheckcodetoappear.)
•Thecheckmodeiscancelled.
[Procedure]1.PresstheCHECKbuttontwice.
2.PresstheTEMPbuttons.
3.PointtheremotecontrolleratthesensorontheindoorunitandpresstheHOURbutton.
4.PointtheremotecontrolleratthesensorontheindoorunitandpresstheON/OFFbutton.
<Malfunction-diagnosis method at maintenance service>
10-3-3. Self-diagnosis <Wireless remote controller> <In case of trouble during operation>Whenamalfunctionoccurstoairconditioner,bothindoorunitandoutdoorunitwillstopandoperationlampblinkstoinformunusualstop.
ON/OFF TEMP
FAN
VANEMODE
CHECK LOUVER
TEST RUN
AUTO STOP
AUTO START
h
min
RESETSET CLOCK
CHECKCHECKdisplay
Temperaturebutton
CHECKbutton
Refrigerantaddressdisplay
HOURbutton
ON/OFFbutton
OCH582B
29
[Output pattern A] Errors detected by indoor unit
[Output pattern B]
E9
1. If the beeper does not sound again after the initial 2 beeps to confirm the self-check start signal was received and the OPERATION INDICATOR lamp does not come on, there are no error records.2. If the beeper sounds 3 times continuously “beep, beep, beep (0.4 + 0.4 + 0.4 seconds)” after the initial 2 beeps to confirm the self-check start signal was received, the specified refrigerant address is incorrect.
OPERATIONINDICATORlamp flashpattern
Beep Beep Beep Beep Beep Beep Beep
OffApprox. 2.5 s
OnApprox. 3 s
On0.5 s
On0.5 s
On0.5 s
On0.5 s
OffApprox. 2.5 s
OnApprox. 3 s
On0.5 s
On0.5 s
· · · Repeated
Number of blinks/beeps in pattern indicates the checkcode in the following table (i.e., n=5 for “U2”)
Number of blinks/beeps in pattern indicatesthe check code in the following table
nth1st 2nd 3rd 1st 2nd
Self-checkstarts(Start signalreceived)
Beeper sounds[Output pattern B]
OPERATIONINDICATORlamp flashpattern
Beep Beep Beep Beep Beep Beep Beep
OffApprox. 2.5 s
On0.5 s
On0.5 s
On0.5 s
On0.5 s
OffApprox. 2.5 s
On0.5 s
On0.5 s
· · · Repeated
Number of blinks/beeps in pattern indicates the checkcode in the following table (i.e., n=5 for “P5”)
Number of blinks/beeps in pattern indicatesthe check code in the following table
nth1st 2nd 3rd 1st 2nd
Self-checkstarts(Start signalreceived)
Beeper sounds
• Refer to the following tables for details on the check codes.[Output pattern A]
Notes:
*The check code in the parenthesis indicates PAR-30/31MAA model.
Beeper sounds/OPERATIONINDICATOR lamp flashes Check code
Symptom Remark
(Number of times)
Wireless remote controller Wired remote controller
Beeper sounds/OPERATIONINDICATOR lamp flashes Check code
(Number of times)
Wireless remote controller Wired remote controller
1 P1 Intake sensor error
P9 Pipe (TH5) sensor error2 P2 Pipe (TH2) sensor error
3 E6,E7 Indoor/outdoor unit communication error4 P4 Drain sensor error/Float switch connector (CN4F) open
5P5 Drain pump errorPA Forced compressor stop (due to water leakage abnormality)
6 P6 Freezing/Overheating protection operation7 EE Communication error between indoor and outdoor units8 P8 Pipe temperature error9 E4, E5 Remote controller signal receiving error
10 –
11 –––
Errors detected by unit other than indoor unit (outdoor unit, etc.)
Symptom
1 Indoor/outdoor unit communication error
2(Transmitting error) (Outdoor unit)
3 Open/short of outdoor unit thermistors4 Compressor overcurrent interruption (When compressor locked)5 Abnormal high discharging temperature/insufficient refrigerant
6 Abnormal high pressure (63H operated)/Overheating protection operation
7 Abnormal temperature of heat sink8 Outdoor unit fan protection stop9 Compressor overcurrent interruption/Abnormal of power module10
11 Abnormality such as overvoltage or voltage shortage and abnormal synchronous signal to main circuit/Current sensor error
1213
U2
U5
UPU3,U4UF
U1,Ud (UD)*
U8U6
U9,UH
Others
––
––
14 Other errors (Refer to the technical manual for the outdoor unit.)
1214
Fb (FB)*PL
Indoor unit control system error (memory error, etc.)
– E0, E3– E1, E2 Remote controller control board error
Remote controller transmission errorAbnormality of refrigerant circuit
Compressor overcurrent interruption
As for indoor unit, refer to indoor unit's service manual.
– –
OCH582B
30
10-4. SELF-DIAGNOSIS ACTION TABLE<Abnormalities detected when the power is put on>
Note:RefertoindoorunitsectionforcodesstartingwithPandE. Check Code Abnormal points and detection method Case Judgment and action
None ―
1Novoltageissuppliedtoterminalblock(TB1)ofoutdoorunit.a)Powersupplybreakeristurnedoff.
b)Contactfailureordisconnectionofpowersupplyterminal
c)Openphase(L2orNphase)
2Electricpowerisnotsuppliedtopowersupplyterminalofoutdoorpowercircuitboard.a)Contactfailureofpowersupplyterminal
b)Openphaseontheoutdoorpowercircuitboard
(Disconnectionofterminalonoutdoorpowercircuitboard)
3Electricpowerisnotsuppliedtooutdoorcontrollercircuitboard.a)Disconnectionofconnector(CNDC)
4Disconnectionofreactor(DCLorACL4)
5Disconnectionofoutdoornoisefil-tercircuitboardorpartsfailureinoutdoornoisefiltercircuitboard.
6Defectiveoutdoorpowercircuitboard
7Openofrushcurrentprotectresis-tor(RS)
8Defectiveoutdoorcontrollercircuitboard
1Checkfollowingitems.
a)Powersupplybreaker
b)Connectionofpowersupplyterminalblock.(TB1)
c)Connectionofpowersupplyterminalblock.(TB1)
2Checkfollowingitems.
a)Connectionofpowersupplyterminalblock.(TB1)
b)Connectionofterminalonoutdoorpowercircuitboard
3 Check connectionoftheconnector(CNDC)ontheoutdoorcontrollercircuitboard.
Check connectionoftheconnectorCNDC onthenoisefiltercircuitboard.Referto"10-9.TESTPOINTDIAGRAM".
4 Check connectionofreactor.(DCLorACL4)Referto"8.WIRINGDIAGRAM".
5a)Checkconnectionofoutdoornoisefiltercircuitboard.b)Replaceoutdoornoisefiltercircuit
board.Referto"10-9.TESTPOINTDIAGRAM".
6Replaceoutdoorpowercircuitboard.
7Replacerushcurrentprotectresistor(RS). Powercircuitboardmightbeshort-circuit.Checkthepowercircuitboard.(Referto"10-9.TESTPOINTDIAGRAM".)
8Replacecontrollerboard(Whenitemsabovearecheckedbuttheunitscannotberepaired.)
F5(5201)
63H connector openAbnormalif63Hconnectorcircuitisopenfor3minutescontinuouslyafterpowersupply.63H:High-pressureswitch
1Disconnectionorcontactfailureof63Hconnectoronoutdoorcontrol-lercircuitboard
2Disconnectionorcontactfailureof63H
363Hisworkingduetodefectiveparts.
4Defectiveoutdoorcontrollercircuitboard
1Checkconnectionof63Hconnectoronoutdoorcontrollercircuitboard.
Referto"10-9.TESTPOINTDIAGRAM".2Checkthe63Hsideofconnectingwire.
3Checkcontinuitybytester. Replacethepartsifthepartsaredefec-tive.
4Replaceoutdoorcontrollercircuitboard.
OCH582B
31
Check Code Abnormal points and detection method Case Judgment and action
EA(6844)
Miswiring of indoor/outdoor unit connecting wire1.Outdoorcontrollercircuitboardcanautomaticallycheckthenumberofconnectedindoorunits.Abnormalifthenumbercannotbecheckedautomaticallyduetomiswiringofindoor/outdoorunitconnectingwire,etc.afterpoweristurnedonfor4minutes.
2.Abnormalifoutdoorcontrollercircuitboardrecognizesexcessivenumberofindoorunits.
1Contactfailureormiswiringofindoor/outdoorunitconnectingwire
2Diameterorlengthofindoor/out-doorunitconnectingwireisoutofspecifiedcapacity.
3Excessivenumberofindoorunitsareconnectedto1outdoorunit.(4unitsormore)
4Defectivetransmittingreceivingcircuitofoutdoorcontrollercircuitboard
5Defectivetransmittingreceivingcircuitofindoorcontrollerboard
6Defectiveindoorpowerboard72ormoreoutdoorunitshaverefrigerantaddress“0”.
(Incaseofgroupcontrol)8Noisehasenteredintopowersup-plyorindoor/outdoorunitconnect-ingwire.
1Checkdisconnectionorloosenessorpolarityofindoor/outdoorunitconnectingwireofindoorandoutdoorunits.
2Checkdiameterandlengthofindoor/out-doorunitconnectingwire.
Totalwiringlength:80m(includingwiringconnectingeachindoorunitandbetweenindoorandoutdoorunit)AlsocheckiftheconnectionorderofflatcableisS1,S2,S3.
3Checkthenumberofindoorunitsthatareconnectedtooneoutdoorunit.(IfEAisdetected)
4–6Turnthepoweroffonce,andonagaintocheck.
Replaceoutdoorcontrollercircuitboard,indoorcontrollerboardorindoorpowerboardifabnormalityoccursagain.
7Checkifrefrigerantaddresses(SW1-3toSW1-6onoutdoorcontrollercircuitboard)areoverlappingincaseofgroupcontrolsystem.
8Checktransmissionpath,andremovethecause.
Note:Thedescriptionsabove,1–8,areforEA,EbandEC.
Eb(6845)
Miswiring of indoor/outdoor unit connecting wire (converse wiring or disconnection)Outdoorcontrollercircuitboardcanautomaticallysettheunitnumberofindoorunits.Abnormaliftheindoorunitnumbercannotbesetwithin4minutesafterpoweronbecauseofmiswiring(conversewiringordisconnection)ofindoor/outdoorunitconnectingwire.
1Contactfailureormiswiringofindoor/outdoorunitconnectingwire
2Diameterorlengthofindoor/out-doorunitconnectingwireisoutofspecifiedcapacity.
4Defectivetransmittingreceivingcircuitofoutdoorcontrollercircuitboard
5Defectivetransmittingreceivingcir-cuitofindoorcontrollerboard
6Defectiveindoorpowerboard72ormoreoutdoorunitshaverefrigerantaddress“0”.
(Incaseofgroupcontrol)8Noisehasenteredintopowersup-plyorindoor/outdoorunitconnect-ingwire.
EC(6846)
Start-up time overTheunitcannotfinishstart-upprocesswithin4minutesafterpoweron.
1Contactfailureofindoor/outdoorunitconnectingwire
2DiameterorlengthofIndoor/out-doorunitconnectingwireisoutofspecifiedcapacity.
72ormoreoutdoorunitshaverefrigerantaddress“0”.
(Incaseofgroupcontrol)8Noisehasenteredintopowersup-plyorindoor/outdoorunitconnect-ingwire.
OCH582B
32
<Abnormalities detected while unit is operating> Check Code Abnormal points and detection method Case Judgment and action
U1(1302)
High pressure (High-pressure switch 63H operated)Abnormalifhigh-pressureswitch63H(4.15MPa)operatedduringcompressoroperation.
1Shortcycleofindoorunit2Cloggedfilterofindoorunit3Decreasedairflowcausedbydirtofindoorfan
4Dirtofindoorheatexchanger5Lockedindoorfanmotor6Malfunctionofindoorfanmotor7Defectiveoperationofstopvalve(Notfullopen)
8Cloggedorbrokenpipe9Lockedoutdoorfanmotor0 Malfunctionofoutdoorfanmotor1Shortcycleofoutdoorunit2Dirtofoutdoorheatexchanger3Decreasedairflowcausedbydefectiveinspectionofoutsidetemperaturethermistor
(Itdetectslowertemperaturethanactualtemperature.)
4Disconnectionorcontactfailureofconnector(63H)onoutdoorcon-trollerboard
5Disconnectionorcontactfailureof63Hconnection
6 Defectiveoutdoorcontrollerboard7Defectiveactionoflinearexpan-sionvalve
8Malfunctionoffandrivingcircuit
1–6Checkindoorunitandrepairdefect.
7Checkifstopvalveisfullyopen.
8Checkpipingandrepairdefect.9–2Checkoutdoorunitandrepairdefect.
3CheckthedetectedtemperatureofoutsidetemperaturethermistoronLEDdisplay.
(SW2onA-ControlServiceTool:Referto "10-10.FUNCTIONOFSWITCHES,CONNECTORSANDJUMPERS".)
4–6TurnthepoweroffandcheckifF5isdisplayedwhenthepoweristurnedonagain.
WhenF5isdisplayed,referto“Judgmentandaction”forF5.
7Checklinearexpansionvalve. Referto"10-6.HOWTOCHECKTHEPARTS".
8Replaceoutdoorcontrollerboard.
U2
(TH32:1132)
High comp. surface temperature1.Abnormalifcomp.surfacetemperature
thermistor(TH32)exceeds125°C or110°Ccontinuouslyfor5minutes.Abnormalifcondenser/evaporatortemperaturethermistor(TH5)exceeds40°Cduringdefrostingandcomp.surfacetemperaturethermistor(TH32)exceeds110°C.
2.Abnormalifdischargesuperheat(Cooling:TH32−TH5/Heating:TH32−TH6)increases.AlltheconditionsinAorBaredetectedsimultaneouslyfor10minutescontinuous-lyafter6minutespastfromcompressorstart-up(includingthethermostatindica-tionorrecoveryfromdefrosting).<ConditionA>•Heatingmode•Whendischargesuperheatislessthan70°C.•WhentheTH6tempismorethanthevalueobtainedbyTH7−5:.
•WhenthecondensingtempofTH5islessthan35:.
<ConditionB>•Duringcompressoroperation(CoolingandHeating)
•Whendischargesuperheatislessthan80°CinCooling.
•Whendischargesuperheatislessthan90°CinHeating.
•WhencondensingtempofTH6ismorethan−40:.(InCoolingonly.)
3.Abnormalifcomp.surfacetemperaturethermistor(TH32)exceeds125°Cor110°Ccontinuouslyfor5minutes.
1Overheatedcompressoroperationcausedbyshortageofrefrigerant
2Defectiveoperationofstopvalve3Defectivethermistor4Defectiveoutdoorcontrollerboard
5Defectiveactionoflinearexpan-sionvalve
1Checkintakesuperheat. Checkleakageofrefrigerant. Chargeadditionalrefrigerant.2Checkifstopvalveisfullyopen.34TurnthepoweroffandcheckifU3is
displayedwhenthepowerisonagain. WhenU3isdisplayed,referto“Judgment
andaction”forU3.5Checklinearexpansionvalve. Referto"10-6.HOWTOCHECKTHEPARTS".
U3(TH32:5132)
Open/short circuit of comp. surface thermistor (TH32)Abnormalifopen(−20°Corless)orshort(217°Cormore)isdetectedduringcompressoroperation.(Detectionisinoperativefor10minutesofcompressorstartingprocessandfor10minutesafterandduringdefrosting.)
1Disconnectionorcontactfailureofconnector(TH32)ontheoutdoorcontrollercircuitboard
2Defectivethermistor3Defectiveoutdoorcontrollercircuitboard
1 Checkconnectionofconnector(TH32)ontheoutdoorcontrollercircuitboard.Checkbreakingoftheleadwireforthermistor(TH32).Referto"10-9.TESTPOINTDIAGRAM".
2 Checkresistancevalueofthermistor(TH32)ortemperaturebymicroprocessor.(Thermistor/TH32:Referto"10-6.HOWTOCHECKTHEPARTS".)(SW2onA-ControlServiceTool:Referto"10-10.FUNCTIONOFSWITCHES,CONNECTORSANDJUMPERS".)
3Replaceoutdoorcontrollerboard.
OCH582B
33
Check Code Abnormal points and detection method Case Judgment and action
U4(TH3:5105)(TH6:5107)(TH7:5106)(TH8:5110)
Open/short of outdoor unit thermistors (TH3, TH6, TH7, and TH8)Abnormalifopenorshortisdetectedduringcompressoroperation.OpendetectionofthermistorsTH3andTH6isinoperativefor10secondsto10minutesaftercompressorstartingand10minutesafterandduringdefrosting.Note:Checkwhichunithasabnormalityin
itsthermistorbyswitchingthemodeofSW2.(PAC-SK52ST)
(Referto"10-10.FUNCTIONOFSWITCHES,CONNECTORSANDJUMPERS".)
1Disconnectionorcontactfailureofconnectors
Outdoorcontrollercircuit board:TH3,TH6/TH7 Outdoorpowercircuitboard:CN32Defectivethermistor3Defectiveoutdoorcontrollercircuitboard
1 Checkconnectionofconnector(TH3,TH6/TH7)ontheoutdoorcontrollercircuitboard.Checkconnectionofconnector(CN3)ontheoutdoorpowercircuitboard.Checkbreakingoftheleadwireforthermistor(TH3,TH6,TH7,TH8).Referto"10-9.TESTPOINTDIAGRAM"
2 Checkresistancevalueofthermistor(TH3,TH6,TH7,TH8)orchecktemperaturebymicroprocessor.(ThermistorTH3,TH6,
TH7,TH8:Referto"10-6.HOWTOCHECKTHEPARTS".)
(SW2onA-ControlServiceTool:Referto"10-10.FUNCTIONOFSWITCHES,CONNECTORSANDJUMPERS.)
3Replaceoutdoorcontrollercircuitboard.Note: Emergencyoperationisavailable
incaseofabnormalitiesofTH3,TH6andTH7.Referto"10-8.EMERGENCYOPERATION".
U5(4230)
Temperature of heat sinkAbnormalifheatsinkthermistor(TH8)detectstemperatureindicatedbelow.P200/250Y ········································90:
1Theoutdoorfanmotorislocked.2Failureofoutdoorfanmotor3Airflowpathisclogged.4Riseofambienttemperature5Defectivethermistor6Defectiveinputcircuitofoutdoorpowercircuitboard
7Failureofoutdoorfandrivecircuit
12Checkoutdoorfan.3Checkairflowpathforcooling.4Checkifthereissomethingwhichcauses
temperaturerisearoundoutdoorunit.(Upperlimitofambienttemperatureis46°C.)Turnoffpower,andonagaintocheckifU5isdisplayedwithin30minutes.IfU4isdisplayedinsteadofU5,followtheactiontobetakenforU4.
5Checkresistancevalueofthermistor(TH8)ortemperaturebymicrocomputer.(Thermistor/TH8:Referto"10-6.HOWTOCHECKTHEPARTS".)(SW2onA-ControlServiceTool:Referto "10-10.FUNCTIONOFSWITCHES,CONNECTORSANDJUMPERS".)
6Replaceoutdoorpowercircuitboard.7Replaceoutdoorcontrollercircuitboard.
U6(4250)
Power moduleCheckabnormalitybydrivingpowermoduleincaseovercurrentisdetected.(UForUPerrorcondition)
1Outdoorstopvalveisclosed.2Decreaseofpowersupplyvoltage3Looseness,disconnectionorconverseofcompressorwiringconnection
4Defectivecompressor
5Defectiveoutdoorpowercircuitboard
1Openstopvalve.2Checkfacilityofpowersupply.3Correctthewiring(U•V•Wphase)tocompressor.Referto"10-9.TESTPOINTDIAGRAM".(Outdoorpowercircuitboard).
4Checkcompressorreferringto"10-6.HOWTOCHECKTHEPARTS".
5Replaceoutdoorpowercircuitboard.
U8(4400)
Outdoor fan motorAbnormalifrotationalfrequencyofthefanmotorisnotdetectedduringDCfanmotoroperation.Fanmotorrotationalfrequencyisabnormalif;•100rpmorbelowdetectedcontinuouslyfor15secondsat20:ormoreoutsideairtemperature.
•50rpmorbelowor1500rpmormoredetectedcontinuouslyfor1minute.
1FailureintheoperationoftheDCfanmotor2Failureintheoutdoorcircuitcontrollerboard
1CheckorreplacetheDCfanmotor.
2Checkthevoltageoftheoutdoorcircuitcontrollerboardduringoperation.3 Replacetheoutdoorcircuitcontrollerboard.
(whenthefailureisstillindicatedevenafterperformingtheaction1above.)
Thermistors Open detection Short detectionSymbol NameTH3TH6TH7TH8
−40: or below−40: or below−40: or below−27: or below
90: or above90: or above90: or above
Thermistor <Liquid>Thermistor <2-phase pipe>
Thermistor <Ambient>Thermistor <Heat sink> 102: or above
( )
OCH582B
34
Check Code Abnormal points and detection method Case Judgment and action
U9(4220)
Detailedcodes
Tofindoutthedetailhistory(latest)aboutU9error,turnONSW2-1,2-2and2-6.Referto"10-10.FUNCTIONOFSWITCHES,CONNECTORSANDJUMPERS".
01
Overvoltage error•IncreaseinDCbusvoltagetoP200/250Y:760V
1Abnormalincreaseinpowersourcevoltage
2Disconnectionofcompressorwiring
3Defectiveoutdoorpowercircuitboard4Compressorhasagroundfault.
1Checkthefieldfacilityforthepowersupply.
2Correctthewiring(U.V.Wphase)tocompressor.Referto"10-9.TESTPOINTDIAGRAM"(Outdoorpowercircuitboard).
3Replaceoutdoorpowercircuitboard.4Checkcompressorforelectricalinsula-
tion.Replacecompressor.
02
Undervoltage error•InstantaneousdecreaseinDCbusvoltagetoP200/250Y:400V
1Decreaseinpowersourcevoltage,instantaneousstop.
2Defective52Cdrivecircuitinoutdoorpowercircuitboard
3DisconnectionorlooseconnectionofrushcurrentprotectresistorRS
4DefectiverushcurrentprotectresistorRS
1Checkthefieldfacilityforthepowersupply.2Replaceoutdoorpowercircuitboard.
3CheckRSwiring.
4ReplaceRS.
04
Input current sensor error/L1-phase open error•Decreaseininputcurrentthroughoutdoorunitto0.1Aonlyifoperationfrequencyismorethanorequalto40Hzorcompressorcurrentismorethanorequalto6A.
1L1-phaseopen2Disconnectionorlooseconnection
betweenTB1andoutdoornoisefiltercircuitboard
3 DisconnectionorlooseconnectionofCN5ontheoutdoorpowercircuitboard/CNCTontheoutdoornoisefilterboard
4DefectiveACCT(ACcurrenttrans)ontheoutdoornoisefiltercircuitboard
5Defectiveinputcurrentdetectioncircuitinoutdoorpowercircuitboard
6Defectiveoutdoorcontrollercircuitboard
1 Checkthefieldfacilityforthepowersupply.2CheckthewiringbetweenTB1andoutdoornoisefiltercircuitboard. 3CheckCN5/CNCTwiring.
4 Replaceoutdoornoisefiltercircuitboard.
5Replaceoutdoorpowercircuitboard.
6Replaceoutdoorcontrollercircuitboard.
08
Abnormal power synchronous signal•Noinputofpowersynchronoussignaltopowercircuitboard
•Powersynchronoussignalof44Hzorless,or65Hzormoreisdetectedonpowercircuitboard.
1Distortionofpowersourcevoltage,noisesuperimposition.
2Disconnectionorlooseconnectionofearthwiring
3DisconnectionorlooseconnectionofCN2ontheoutdoorpowercircuitboard/controllercircuitboard
4Defectivepowersynchronoussignalcircuitinoutdoorcontrollercircuitboard
5Defectivepowersynchronoussignalcircuitinoutdoorpowercircuitboard
1 Checkthefieldfacilityforthepowersupply.2Checkearthwiring.
3CheckCN2wiring.
4Replaceoutdoorcontrollercircuitboard.
5Replaceoutdoorpowercircuitboard.
10
PFC error (Overvoltage/Undervoltage/Overcurrent)•PFCdetectedanyofthefol-lowing:a)IncreaseofDCbusvoltageto420V.
b)DecreaseinPFCcontrolvoltageto12VDCorlower.
c)Increaseininputcurrentto50Apeak.(Formodelsequippedwithsingle-phasePFConly)
NotapplicableforP200/250Ymodel. ChecktheswitchsettingforModelSelectontheoutdoorcontrollercircuitboard.
20
PFC/IGBT error (Undervoltage)•WhenCompressorisrunning,DCbusvoltagestaysat310Vorlowerforconsecutive10seconds
NotapplicableforP200/250Ymodel. ChecktheswitchsettingforModelSelectontheoutdoorcontrollercircuitboard.
Continuetothenextpage
OCH582B
35
Check Code Abnormal points and detection method Case Judgment and action
Ud(UD)*(1504)
Over heat protectionAbnormalifoutdoorpipethermistor(TH3)detects70: ormoreduringcompressoroperation.
1Defectiveoutdoorfan(fanmotor)orshortcycleofoutdoorunitduringcoolingoperation
2Defectiveoutdoorpipethermistor(TH3)
3Defectiveoutdoorcontrollerboard
1Checkoutdoorunitairpassage.
23Turnthepoweroffandonagaintocheckthecheckcode.IfU4isdisplayed,followtheU4processingdirection.
*ThecheckcodeintheparenthesisindicatesPAR-30/31MAAmodel.
UF(4100)
Compressor overcurrent interruption (When compressor locked)AbnormalifovercurrentofDCbusorcompressorisdetectedwithin30secondsaftercompressorstartsoperating.
1Stopvalveisclosed.2Decreaseofpowersupplyvoltage3Looseness,disconnectionorcon-verseofcompressorwiringcon-nection
4Defectivecompressor
5Defectiveoutdoorpowerboard6DIPswitchsettingdifferenceofoutdoorcontrollercircuitboard
1Openstopvalve.2Checkfacilityofpowersupply.3Correctthewiring(U•V•Wphase)tocompressor.Referto"10-9.TESTPOINTDIAGRAM"(Outdoorpowercircuitboard).
4Checkcompressor. Referto"10-6.HOWTOCHECKTHE
PARTS".5Replaceoutdoorpowercircuitboard.6ChecktheDIPswitchsettingofoutdoorcontrollercircuitboard.Referto"ModelSelect"in"(1)Functionofswitches"in"10-10.FUNCTIONOFSWITCHES,CONNECTORSANDJUMPERS".
UH(5300)
Current sensor error or input current error• Abnormalifcurrentsensordetects−1.0Ato1.0Aduringcompressoroperation.(Thiserrorisignoredincaseoftestrunmode.)
1Disconnectionofcompressorwiring
2Defectivecircuitofcurrentsensoronoutdoorpowercircuitboard
3Decreaseofpowersupplyvoltage
1Correctthewiring(U•V•Wphase)tocompressor.Referto"10-9.TESTPOINTDIAGRAM"(Outdoorpowercircuitboard).
2Replaceoutdoorpowercircuitboard.
3Checkthefacilityofpowersupply.
UL(1300)
Low pressureAbnormalifthefollowingconditionsaredetectedforcontinuously3minutesaftercompressorstartsheatingoperatingfor10minutes.1.HeatingmodeDetectionmode1TH7−TH3[4°CandTH5−Indoorroomtemperature[2°CDetectionmode2TH7−TH3[2°CandTH5−Indoorroomtemperature[4°CandTH2−Indoorroomtemperature[4°C
2.CoolingmodeTH6−TH7[2°CandTH3−TH7[2°CandIndoorroomtemperature−Indoorliquidpipetemperature(TH2)[5°C
ThermistorTH3:OutdoorliquidpipetemperatureTH5:Indoorcond./eva.temperatureTH6:Outdoor2-phasepipetemperatureTH7:Ambienttemperature
1Stopvalveofoutdoorunitisclosedduringoperation.
2Leakageorshortageofrefrigerant
3Malfunctionoflinearexpansionvalve
4Cloggingwithforeignobjectsinrefrigerantcircuit
Note:Cloggingoccursinthepartswhichbecomebelowfreezingpointwhenwaterentersinrefrigerantcircuit.
1Checkstopvalve.
2Checkintakesuperheat.Checkleakageofrefrigerant.Checkadditionalrefrigerant.
3Checklinearexpansionvalve.Referto"10-6.HOWTOCHECKTHEPARTS".
4Afterrecoveringrefrigerant,removewaterfromentirerefrigerantcircuitundervacu-ummorethan1hour.
UP(4210)
Compressor overcurrent interruptionAbnormalifovercurrentDCbusorcompres-sorisdetectedaftercompressorstartsoper-atingfor30seconds.
1Stopvalveofoutdoorunitisclosed.
2 Decreaseofpowersupplyvoltage3Looseness,disconnectionorcon-verseofcompressorwiringcon-nection
4Defectivefanofindoor/outdoorunits
5Shortcycleofindoor/outdoorunits6Defectiveinputcircuitofoutdoorcontrollerboard
7Defectivecompressor8Defectiveoutdoorpowercircuitboard
9DIPswitchsettingdifferenceofoutdoorcontrollercircuitboard
1Openstopvalve.2Checkfacilityofpowersupply.3Correctthewiring(U•V•Wphase)tocom-pressor.Referto"10-9.TESTPOINTDIAGRAM".(Outdoorpowercircuitboard).
4Checkindoor/outdoorfan.5Solveshortcycle.6Replaceoutdoorcontrollercircuitboard.7Checkcompressor.Referto"10-6.HOWTOCHECKTHEPARTS".
Beforethereplacementoftheoutdoorcontrollercircuitboard,disconnectthewiringtocompressorfromtheoutdoorpowercircuitboardandchecktheoutputvoltageamongphases,U,V,W,duringtestrun.Nodefectonboardifvoltageamongphases(U-V,V-WandW-U)issame.Makesuretoperformthevoltagecheckwithsameperformingfrequency.8Replaceoutdoorpowercircuitboard9ChecktheDIPswitchsettingofoutdoorcontrollercircuitboard
OCH582B
36
Check Code Abnormal points and detection method Case Judgment and action
E0orE4
Remote controller transmission error (E0)/signal receiving error (E4)1Abnormalifmainorsubremotecontrollercannotreceivenormallyanytransmissionfromindoorunitofrefrigerantaddress“0”for3minutes.
(Checkcode:E0)2Abnormalifsubremotecontrollercouldnotreceiveanysignalfor2minutes.(Checkcode:E0)
1Abnormalifindoorcontrollerboardcannotreceivenormallyanydatafromremotecontrollerboardorfromotherindoorcon-trollerboardfor3minutes.(Checkcode:E4)
2Indoorcontrollerboardcannotreceiveanysignalfromremotecontrollerfor2min-utes.(Checkcode:E4)
1Contactfailureattransmissionwireofremotecontroller
2Allremotecontrollersaresetas“sub”remotecontroller.Inthiscase,E0isdisplayedonremotecontroller,andE4isdisplayedatLED(LED1,LED2)ontheoutdoorcontrollercircuitboard.
3Miswiringofremotecontroller4Defectivetransmittingreceivingcircuitofremotecontroller
5Defectivetransmittingreceivingcircuitofindoorcontrollerboardofrefrigerantaddress“0”
6Noisehasenteredintothetrans-missionwireofremotecontroller.
1Checkdisconnectionorloosenessofindoorunitortransmissionwireofremotecontroller.
2Setoneoftheremotecontrollers“main”ifthereisnoproblemwiththeactionabove.
3Checkwiringofremotecontroller.•Totalwiringlength:maximum500m(Donotusecableo3ormore.)•Thenumberofconnectingindoorunits:maximum16units
•Thenumberofconnectingremotecon-troller:maximum2units
Ifthecauseoftroubleisnotanyof1–3above,4Diagnoseremotecontrollers.
a)When“RCOK”isdisplayed,remotecontrollershavenoproblem.Turnthepoweroff,andonagaintocheck.Ifabnormalitygeneratesagain,replaceindoorcontrollerboard.
b)When“RCNG”isdisplayed,replaceremotecontroller.
c)When“RCE3”or“ERC00–66”isdis-played,noisemaybecausingabnor-mality.
Note:Iftheunitisnotnormalafterreplacingindoorcontrollerboardingroupcontrol,indoorcon-trollerboardofaddress“0”maybeabnormal.
E1orE2
Remote controller control board1Abnormalifdatacannotbenormallyreadfromthenonvolatilememoryoftheremotecontrollercontrolboard.
(Checkcode:E1)2Abnormaliftheclockfunctionofremotecontrollercannotbenormallyoperated.
(Checkcode:E2)
1Defectiveremotecontroller 1Replaceremotecontroller.
E3orE5
Remote controller transmission error (E3)/signal receiving error (E5)1Abnormalifremotecontrollercouldnotfindblankoftransmissionpathfor6secondsandcouldnottransmit.(Checkcode:E3)
2Remotecontrollerreceivestransmitteddataatthesametime,comparesthedata,andwhendetectingit,judgesdifferentdatatobeabnormal30continuoustimes.(Checkcode:E3)
1Abnormalifindoorcontrollerboardcouldnotfindblankoftransmissionpath.
(Checkcode:E5)2Indoorcontrollerboardreceivestransmitteddataatthesametime,comparesthedata,andwhendetectingit,judgesdifferentdatatobeabnormal30continuoustimes.(Checkcode:E5)
12remotecontrollersaresetas“main.”(Incaseof2remotecontrollers)
2Remotecontrollerisconnectedwith2indoorunitsormore.
3Repetitionofrefrigerantaddress4Defectivetransmittingreceivingcircuitofremotecontroller
5Defectivetransmittingreceivingcircuitofindoorcontrollerboard
6Noisehasenteredintotransmissionwireofremotecontroller.
1Setaremotecontrollertomain,andtheothertosub.
2Remotecontrollerisconnectedwithonly1indoorunit.
3Theaddresschangestoaseparatesetting.
4−6Diagnoseremotecontroller.a)When“RCOK”isdisplayed,remotecontrollershavenoproblem.
Turnthepoweroff,andonagaintocheck.
Whenbecomingabnormalagain,replaceindoorcontrollerboard.
b)When“RCNG”isdisplayed,replaceremotecontroller.
c)When“RCE3”or“ERC00–66”isdisplayed,noisemaybecausingabnormality.
OCH582B
37
Check Code Abnormal points and detection method Case Judgment and action
E6(6840
Indoor/outdoor unit communication error (Signal receiving error)1Abnormalifindoorcontrollerboardcouldnotreceiveanysignalnormallyfor6minutesafterturningthepoweron.
2Abnormalifindoorcontrollerboardcouldnotreceiveanysignalnormallyfor3minutes.
3Considertheunitasabnormalunderthefollowingcondition.When2ormoreindoorunitsareconnectedtoanoutdoorunit,indoorcontrollerboardcouldnotreceiveasignalfor3minutesfromoutdoorcontrollercircuitboard,asignalwhichallowsoutdoorcontrollercircuitboardtotransmitsignals.
1Contactfailure,shortcircuitormiswiring(conversewiring)ofindoor/outdoorunitconnectingwire
2Defectivetransmittingreceivingcircuitofoutdoorcontrollercircuitboard.
3Defectivetransmittingreceivingcircuitofindoorcontrollerboard.
4Noisehasenteredintoindoor/outdoorunitconnectingwire.
5Defectivefanmotor6Defectiverushcurrentresistorofoutdoorpowercircuitboard
CheckLEDdisplayonoutdoorcontrollercircuitboard.(ConnectA-Controlservicetool(PAC-SK52ST)) RefertoEA−ECitemifLEDdisplaysEA−AC.1Checkdisconnectingorloosenessofindoor/outdoorunitconnectingwireofindoorunitoroutdoorunit.
Checkalltheunitsincaseoftwin/triple/quadrupleindoorunitsystem.
2–4 Turnthepoweroff,andonagaintocheck.Ifabnormalitygeneratesagain,replaceindoorcontrollerboardoroutdoorcontroller circuitboard.Note: Otherindoorcontrollerboardmayhave
defectinthecaseoftwin/triple/quadrupleindoorunitsystem.
5Turnthepoweroff,anddetachfanmotorfromconnector(CNF1,2).Thenturnthepoweronagain.
Ifabnormalityisnotdisplayed,replacefanmotor.
Ifabnormalityisdisplayed,replaceoutdoorcontrollercircuitboard.
6Checktherushcurrentresistoronoutdoorpowercircuitboardwithtester.Ifopenisdetected,replacethepowercircuitboard.
E7
Indoor/outdoor unit communication error (Transmitting error)Abnormalif“1”receivingisdetected30timescontinuouslythoughindoorcontrollerboardhastransmitted“0”.
1Defectivetransmittingreceivingcircuitofindoorcontrollerboard
2Noisehasenteredintopowersupply.
3Noisehasenteredintooutdoorcontrolwire.
1–3Turnthepoweroff,andonagaintocheck.Ifabnormalitygeneratesagain,replaceindoorcontrollerboard.
E8(6840)
Indoor/outdoor unit communication error (Signal receiving error)(Outdoor unit)Abnormalifoutdoorcontrollercircuitboardcouldnotreceiveanythingnormallyfor3minutes.
1Contactfailureofindoor/outdoorunitconnectingwire
2Defectivecommunicationcircuitofoutdoorcontrollercircuitboard
3Defectivecommunicationcircuitofindoorcontrollerboard
4NoisehasenteredintoIndoor/outdoorunitconnectingwire.
1CheckdisconnectionorloosenessofIndoor/outdoorunitconnectingwireofindoororoutdoorunits.
2–4 Turnthepoweroff,andonagaintocheck.Replaceindoorcontrollerboardoroutdoorcontrollercircuitboardifabnormalityisdisplayedagain.
E9(6841)
Indoor/outdoor unit communication error (Transmitting error) (Outdoor unit)1Abnormalif“0”receivingisdetected30timescontinuouslythoughoutdoorcon-trollercircuitboardhastransmitted“1”.
2Abnormalifoutdoorcontrollercircuitboardcouldnotfindblankoftransmissionpathfor3minutes.
1Indoor/outdoorunitconnectingwirehascontactfailure.
2Defectivecommunicationcircuitofoutdoorcontrollercircuitboard
3Noisehasenteredpowersupply.4NoisehasenteredIndoor/outdoorunitconnectingwire.
1Checkdisconnectionorloosenessofindoor/outdoorunitconnectingwire.
2–4 Turnthepoweroff,andonagaintocheck.Replaceoutdoorcontrollercir-cuitboardifabnormalityisdisplayedagain.
EF(6607or
6608)
Non defined check codeThiscodeisdisplayedwhennondefinedcheckcodeisreceived.
1Noisehasenteredtransmissionwireofremotecontroller.
2NoisehasenteredIndoor/outdoorunitconnectingwire.
3Outdoorunitisnotaseriesofpower-inverter.
12Turnthepoweroff,andonagaintocheck.Replaceindoorcontrollerboardoroutdoorcontrollercircuitboardifabnormalityisdisplayedagain.
3Replaceoutdoorunitwithpower-invertertypeoutdoorunit.
OCH582B
38
Check Code Abnormal points and detection method Case Judgment and action
Ed(0403)
Serial communication error1Abnormalifserialcommunicationbetweenoutdoorcontrollercircuitboardandout-doorpowercircuitboardisdefective.
1BreakingofwireorcontactfailureofconnectorCN2betweentheoutdoorcontrollercircuitboardandtheoutdoorpowercircuitboard
2BreakingofwireorcontactfailureofconnectorCN4betweentheoutdoorcontrollercircuitboardandtheoutdoorpowercircuitboard
3Defectivecommunicationcircuitofoutdoorpowercircuitboard
4Defectivecommunicationcircuitofoutdoorcontrollercircuitboardforoutdoorpowercircuitboard
12CheckconnectionofeachconnectorCN2andCN4betweentheoutdoorcontrollercircuitboardandtheoutdoorpowercir-cuitboard.
3Replaceoutdoorpowercircuitboard.
4Replaceoutdoorcontrollercircuitboard.
2AbnormalifcommunicationbetweenoutdoorcontrollercircuitboardandM-NETboardisnotavailable.
1Breakingofwireorcontactfail-ureofconnectorbetweenout-doorcontrollercircuitboardandM-NETboard
2ContactfailureofM-NETboardpowersupplyline
3NoisehasenteredintoM-NETtransmissionwire.
1Checkdisconnection,looseness,orbreakingofconnectionwirebetweenoutdoorcontrol-lercircuitboard(CNMNT)andM-NETboard(CN5).
2Checkdisconnection,looseness,orbreakingofconnectionwirebetweenoutdoorcontrol-lercircuitboard(CNMNT)andM-NETboard(CND).
3CheckM-NETtransmissionwiringmethod.
P8
Pipe temperature<Coolingmode>Detectedasabnormalwhenthepipetemperatureisnotinthecoolingrange3minutesaftercompressorstartand6minutesaftertheliquidorcondenser/evaporatorpipeisoutofcoolingrange.Note1:Ittakesatleast9minutestodetect.Note2:AbnormalityP8isnotdetectedin
dryingmode.Coolingrange: Indoorpipetemperature(TH2or
TH5)−intaketemperature(TH1)[−3:TH:Lowertemperaturebetweenliquidpipe
temperatureandcondenser/evaporatortemperature
<Heatingmode>When10secondshavepassedafterthecompressorstartsoperationandthehotadjustmentmodehasfinished,theunitisdetectedasabnormalwhencondenser/evaporatorpipetemperatureisnotinheatingrangewithin20minutes.Note3:Ittakesatleast27minutestodetect
abnormality.Note4:Itexcludestheperiodofdefrosting
(Detectionrestartswhendefrostingmodeisover)
Heatingrange:3: [(Condenser/Evaporatortemperature(TH5)−intaketemperature(TH1))
1Slighttemperaturedifferencebetweenindoorroomtemperatureandpipe<liquidorcondenser/evaporator>temperaturethermistor•Shortageofrefrigerant•Disconnectedholderofpipe<liquidorcondenser/evaporator>thermistor
•Defectiverefrigerantcircuit2Converseconnectionofextensionpipe(onpluralunitsconnection)
3Conversewiringofindoor/outdoorunitconnectingwire(onpluralunitsconnection)
4Defectivedetectionofindoorroomtemperatureandpipe<condenser/evaporator>temperaturethermistor
5Stopvalveisnotopenedcompletely.
1–4Checkpipe<liquidorcondenser/evaporator>temperaturewithroomtemperaturedisplayonremotecontrollerandoutdoorcontrollercircuitboard.Pipe<liquidorcondenser/evaporator>temperaturedisplayisindicatedbyset-tingSW2ofoutdoorcontrollercircuitboardasfollows.
Conducttemperaturecheckwithoutdoorcontrollercircuitboardafterconnecting‘A-ControlServiceTool(PAC-SK52ST)’.
23Checkconverseconnectionofextensionpipeorconversewiringofindoor/outdoorunitconnectingwire.
PL
Abnormal refrigerant circuitDuringCooling,Dry,orAutoCoolingoperation,thefollowingconditionsareregardedasfailureswhendetectedfor1second.a)Thecompressorcontinuestorunfor30ormoreseconds.
b)Theliquidpipetemperatureorthecondenser/evaporatortemperatureis75°Cormore.
These detected errors will not be cancelled until the power source is reset.
1Abnormaloperationof4-wayvalve2Disconnectionoforleakageinrefrigerantpipes
3Airintorefrigerantpiping4Abnormaloperation(norotation)ofindoorfan
·Defectivefanmotor ·Defectiveindoorcontrolboard 5Defectiverefrigerantcircuit(clogging)
1 When this error occurs, be sure to replace the 4-way valve.
2Checkrefrigerantpipesfordisconnectionorleakage.
3Aftertherecoveryofrefrigerant,vacuumdrythewholerefrigerantcircuit.
4Referto"10-6.HOWTOCHECKTHEPARTS".
5Checkrefrigerantcircuitforoperation. To avoid entry of moisture or air into refrigerant circuit which could cause abnormal high pressure, purge air in refrigerant circuit or replace refrigerant.
( )1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6ON
OFF
1 2 3 4 5 6ON
OFF
1 2 3 4 5 6ON
OFF
A-Control Service Tool SW2 setting
Temperature display of indoor liquid pipeIndoor 1
Temperature display of indoor liquid pipeIndoor 2
Temperature display of indoor condenser/evaporator pipe Indoor 1
Temperature display of indoor condenser/evaporator pipe Indoor 2
OCH582B
39
<M-NET communication error> Note:“Indoorunit”inthetextindicatesM-NETboardinoutdoorunit. Check Code Abnormal points and detection method Case Judgment and action
A0(6600)
Address duplicate definitionThiserrorisdisplayedwhentransmissionfromtheunitsofsameaddressisdetected.Note:Theaddressandattributedisplayed
atremotecontrollerindicatethecontrollerthatdetectedabnormality.
1Thereare2ormoresameaddressofcontrollerofoutdoorunit,indoorunit,FRESHMASTER,orLOSSNAY.
2Noisehasenteredintotransmissionsignalandsignalwastransformed.
Searchtheunitwithsameaddressasabnormalityoccurred.Ifthesameaddressisfound,shutthepowersupplyofoutdoorunitandindoorunitandFRESHMASTERorLOSSNAYatthesametimefor2minutesormoreaftertheaddressiscorrected,andturnthepoweronagain.Checktransmissionwaveformornoiseontransmissionwire.
A2(6602)
Hardware error of transmission processorTransmissionprocessorintendedtotransmit“0”,but“1”appearedontransmissionwire.Note:Theaddressandattributedisplayat
remotecontrollerindicatethecontrollerthatdetectedabnormality.
1 Errorisdetectedifwaveformistransformedwhenwiringworksoftransmissionwireofoutdoorunit,indoorunit,FRESHMASTERorLOSSNAYaredone,orpolarityischangedwiththepoweronandtransmissiondatacollideeachother.
2 Defectivetransmittingreceivingcircuitoftransmissionprocessor
3Transmissiondataischangedbythenoiseontransmission
1Iftheworksoftransmissionwireisdonewiththepoweron,shutoffthepowersupplyofoutdoorunitandindoorunitandFRESHMASTERorLOSSNAYatthesametimefor2minutesormore,andturnthepoweronagain.
2Checktransmissionwaveformornoiseontransmissionwire.
A3(6603)
BUS BUSY1.Overtimeerrorbycollisiondamage Abnormaliftransmittingisnotpossiblefor8to 10minutescontinuouslybecauseofcollisionoftransmission.
2.Datacouldnotreachtransmissionwirefor8to10minutescontinuouslybecauseofnoise,etc.
Note:Theaddressandattributedisplayedatremotecontrollerindicatethecontrollerthatdetectedabnormality.
1Transmissionprocessorcouldnottransmitsignalbecauseshortcyclevoltageofnoiseandthelikehaveenteredintotransmissionwirecontinuously.
2 Transmissionquantityhasincreasedandtransmissionisnotpossiblebecausetherewaswiringmistakeofterminalblockfortransmissionwire(TB3)andterminalblockforcentralcontrol(TB7)inoutdoorunit.
3Transmissionaremixedwithothersandoccupationrateontransmissionwirerosebecauseofdefectiverepeater(afunctiontoconnectorordisconnecttransmissionofcontrolandcentralcontrolsystem)ofoutdoorunit,thenabnormalityisdetected.
1Checkiftransmissionwireofindoorunit,FRESHMASTER,LOSSNAY,orremotecontrollerisnotconnectedtoterminalblockforcentralcontrol(TB7)ofoutdoorunit.
2Checkiftransmissionwireofindoorunit,FRESHMASTERorLOSSNAYisnotconnectedtoterminalblockfortransmissionwireofoutdoorunit.
3Checkifterminalblockfortransmissionwire(TB3)andterminalblockforcentralcontrol(TB7)isnotconnected.
4Checktransmissionwaveformornoiseontransmissionwire.
A6(6606)
Communication error with communication processorDefectivecommunicationbetweenunitprocessorandtransmissionprocessorNote:Theaddressandattributedisplayat
remotecontrollerindicatethecontrollerthatdetectedabnormality.
1Dataoftransmissionprocessororunitprocessorisnottransmittednormallybecauseofaccidentaltroublesuchasnoiseorthundersurge.
2Addressforwardingfromunitprocessorisnottransmittednormallybecauseofdefectivetransmissionprocessorhardware.
Turnoffthepowersupplyofoutdoorunit,indoorunitandFRESHMASTERorLOSSNAYatthesametimefor2minutesormore,andturnthepoweronagain.Systemreturnsnormallyifabnormalitywasaccidentalmalfunction.Ifthesameabnormalitygeneratesagain,abnormality-generatedcontrollermaybedefective.
OCH582B
40
Check Code Abnormal points and detection method Case Judgment and action
A7(6607)
NO ACK signal1.Transmittingsidecontrollerdetectsabnormalifamessagewastransmittedbutthereisnoreply(ACK)thatamessagewasreceived.Transmittingsidedetectsabnormalityevery30seconds,6timescontinuously.
Note:Theaddressandattributedisplayedatremotecontrollerindicatethecontrollerthatdidnotreply(ACK).
Commonfactorthathasnorelationwithabnormalitysource1Theunitofformeraddressdoesnotexistasaddressswitchhaschangedwhiletheunitwasenergized.
2Extinctionoftransmissionwirevoltageandsignaliscausedbyover-rangetransmissionwire.•Maximumdistance.......200m•Remotecontrollerline..(12m)
3Extinctionoftransmissionwirevoltageandsignaliscausedbytype-unmatchedtransmissionwire.Type......Withshieldwire- CVVS, CPEVSWithnormalwire(noshield)- VCTF,VCTFK,CVV CVS,VVR,VVF,VCT
Diameter.....1.25mm2ormore4Extinctionoftransmissionwirevoltageandsignaliscausedbyover-numberedunits.
5Accidentalmalfunctionofabnormality-detectedcontroller(noise,thundersurge)
6Defectiveofabnormality-generatedcontroller
Always try the following when the error “A7” occurs.
1Turnoffthepowersupplyofoutdoorunit,indoorunitandFRESHMASTERorLOSSNAYatthesametimefor2minutesormore,andturnthepoweronagain.Ifmalfunctionwasaccidental,theunitreturnstonormal.
2Checkaddressswitchofabnormality-generatedaddress.
3Checkdisconnectionorloosenessofabnormality-generatedorabnormality-detectedtransmissionwire(terminalblockandconnector)
4Checkiftolerancerangeoftransmissionwireisnotexceeded.
5Checkiftypeoftransmissionwireiscorrectornot.
Ifthecauseoftroubleisin1–5above,repairthedefect,thenturnoffthepowersupplyofoutdoorunit,indoorunitandFRESHMASTERorLOSSNAYatthesametimefor2minutesormore,andturnthepoweronagain.•Ifthecauseoftroubleisnotin1–5aboveinsinglerefrigerantsystem(oneoutdoorunit),controllerofdisplayedaddressorattributeisdefective.
•Ifthecauseoftroubleisnotin1–5aboveindifferentrefrigerantsystem(2ormoreoutdoorunits),judgewith6.
6Ifaddressofabnormalitysourceistheaddressthatshouldnotexist,thereistheunitthatmemorizesnonexistentaddressinformation.Deleteuselessaddressinformationwithmanualsettingfunctionofremotecontroller.
ThisappliesonlytothesystemFRESHMASTERorLOSSNAYisconnectedto,orthesystemthatisequippedwithgroupsettingofdifferentrefrigerantsystem.
Ifthecauseoftroubleisnotanyof1–6 above,replacethecontrollerboardofdisplayedaddressorattribute.Iftheunitdoesnotreturnnormally,multicontrollerboardofoutdoorunitmaybedefective(repeatercircuit).Replacemulticontrollerboardonebyonetocheckiftheunitreturnsnormally.
2.Ifdisplayedaddressorattributeisoutdoorunit,indoorunitdetectsabnormalitywhenindoorunittransmitssignaltooutdoorunitandtherewasnoreply(ACK).
1Contactfailureoftransmissionwireofoutdoorunitorindoorunit
2Disconnectionoftransmissionconnector(CN2M)ofoutdoorunit
3Defectivetransmittingreceivingcircuitofoutdoorunitorindoorunit
3.Ifdisplayedaddressorattributeisindoorunit,remotecontrollerdetectsabnormalitywhenremotecontrollertransmitssignaltoindoorunitandtherewasnoreply(ACK).
1Duringgroupoperationwithindoorunitofmulti-refrigerantsystem,ifremotecontrollertransmitssignaltoindoorunitwhileoutdoorunitpowersupplyofonerefrigerantsystemisturnedofforwithin2minutesofrestart,abnormalityisdetected.
2Contactfailureoftransmissionwireofremotecontrollerorindoorunit
3Disconnectionoftransmissionconnector(CN2M)ofindoorunit
4Defectivetransmittingreceivingcircuitofindoorunitorremotecontroller
Continuetothenextpage
OCH582B
41
Check Code Abnormal points and detection method Case Judgment and action
A7(6607)
4.Ifdisplayedaddressorattributeisremotecontroller,indoorunitdetectsabnormal-itywhenindoorunittransmitssignaltoremotecontrollerandtherewasnoreply(ACK).
1Duringgroupoperationwithindoorunitofmulti-refrigerantsystem,ifindoorunittransmitssignaltoremotecontrollerwhileoutdoorunitpowersupplyofonerefrigerantsystemisturnedofforwithin2minutesofrestart,abnor-malityisdetected.
2Contactfailureoftransmissionwireofremotecontrollerorindoorunit
3Disconnectionoftransmissionconnector(CN2M)ofindoorunit
4Defectivetransmittingreceivingcircuitofindoorunitorremotecontroller
Same as mentioned in “A7” of the previ-ous page.
5.IfdisplayedaddressorattributeisFRESHMASTER,indoorunitdetectsabnormal-itywhenindoorunittransmitssignaltoFRESHMASTERandtherewasnoreply(ACK).
1DuringsequentialoperationofindoorunitandFRESHMASTERofotherrefrigerantsystem,ifindoorunittransmitssignaltoFRESHMASTERwhileout-doorunitpowersupplyofsamerefrigerantsystemwithFRESHMASTERisturnedofforwithin2minutesofrestart,abnormalityisdetected.
2ContactfailureoftransmissionwireofindoorunitorFRESHMASTER
3Disconnectionoftransmissionconnector(CN2M)ofindoorunitorFRESHMASTER
4DefectivetransmittingreceivingcircuitofindoorunitorFRESHMASTER
6.IfdisplayedaddressorattributeisLOSSNAY,indoorunitdetectsabnormal-itywhenindoorunittransmitssignaltoLOSSNAYandtherewasnoreply(ACK).
1IfthepowersupplyofLOSSNAYisoff,indoorunitdetectsabnor-malitywhenittransmitssignaltoLOSSNAY.
2DuringsequentialoperationofindoorunitandLOSSNAYofotherrefrigerantsystem,ifindoorunittransmitssignaltoLOSSNAYwhileoutdoorunitpowersupplyofsamerefrigerantsystemwithLOSSNAYisturnedofforwithin2minutesofrestart,abnormalityisdetected.
3ContactfailureoftransmissionwireofindoorunitofLOSSNAY
4Disconnectionoftransmissionconnector(CN2M)ofindoorunit
5DefectivetransmittingreceivingcircuitofindoorunitorLOSSNAY
7.Ifdisplayedaddressorattributeisnonex-istent.
1Theunitofformeraddressdoesnotexistasaddressswitchhaschangedwhiletheunitwasener-gized.
2AbnormalityisdetectedwhenindoorunittransmitssignalbecausetheaddressofFRESHMASTERandLOSSNAYarechangedaftersequentialopera-tionofFRESHMASTERandLOSSNAYbyremotecontroller.
OCH582B
42
10-5. TROUBLESHOOTING OF PROBLEMS
Check Code Abnormal points and detection method Case Judgment and action
A8(6608)
M-NET NO RESPONSEAbnormalifamessagewastransmittedandtherewerereply(ACK)thatmessagewasreceived,butresponsecommanddoesnotreturn.Transmittingsidedetectsabnormalityevery30seconds,6timescontinuously.Note:Theaddressandattributedisplayedat
remotecontrollerindicatethecontrol-lerthatdidnotreply(ACK).
1Transmittingconditionisrepeatedfaultbecauseofnoiseandthelike.
2Extinctionoftransmissionwirevoltageandsignaliscausedbyover-rangetransmissionwire.•Maximumdistance......200m•Remotecontrollerline (12m)
3Extinctionoftransmissionwirevoltageandsignaliscausedbytype-unmatchedtransmissionwire.Type.........Withshieldwire- CVVS, CPEVSWithnormalwire(noshield)- VCTF,VCTFK,CVV CVS,VVR,VVF,VCT
Diameter.....1.25mm2ormore
4Accidentalmalfunctionofabnor-mality-generatedcontroller
1Checktransmissionwaveformornoiseontransmissionwire.
2TurnoffthepowersupplyofoutdoorunitandindoorunitandFRESHMASTERorLOSSNAYatthesametimefor2minutesormore,andturnthepoweronagain.Ifmalfunctionwasaccidental,theunitreturnstonormal.Ifthesameabnormalitygener-atesagain,controllerofdisplayedaddressandattributemaybedefective.
Phenomena Factor Countermeasure
1.Remotecontrollerdisplaydoesnotwork.
112VDCisnotsuppliedtoremotecontroller.(PowersupplydisplayisnotindicatedonLCD.)
2 12–15VDCissuppliedtoremotecontroller,however,nodisplayisindicated.
• “PLEASEWAIT”isnotdisplayed.• “PLEASEWAIT”isdisplayed.
1CheckLED2onindoorcontrollerboard.(1)WhenLED2islit.
Checktheremotecontrollerwiringforbreakingorcontactfailure.
(2)WhenLED2isblinking.Checkshortcircuitofremotecontrollerwiring.
(3)WhenLED2isnotlit.RefertophenomenaNo.3below.
2Checkthefollowing.• Failureofremotecontrollerif“PLEASEWAIT”isnotdisplayed
• RefertophenomenaNo.2belowif“PLEASEWAIT”isdisplayed.
2.“PLEASEWAIT”displayisremainedontheremotecontroller.
1Atlongest2minutesafterthepowersupply“PLEASEWAIT”isdisplayedtostartup.
2Communicationerrorbetweentheremotecontrollerandindoorunit
3 Communicationerrorbetweentheindoorandoutdoor unit
4Outdoorunitprotectiondeviceconnectorisopen.
1Normaloperation2Self-diagnosisofremotecontroller3“PLEASEWAIT”isdisplayedfor6min-utesatmostincaseofindoor/outdoorunitcommunicationerror.CheckLED3onindoorcontrollerboard.(1)WhenLED3isnotblinking.
Checkindoor/outdoorconnectingwireformiswiring.(ConversewiringofS1andS2,orbreakofS3wiring.)
(2)WhenLED3isblinking.Indoor/outdoorconnectingwireisnormal.
4CheckLEDdisplayonoutdoorcontrollercircuitboard.Referto"10-10.FUNCTIONOFSWITCHES,CONNECTORSANDJUMPERS".Checkprotectiondeviceconnector(63H)forcontactfailure.Referto"10-9.TESTPOINTDIAGRAM".
3.Whenpressingtheremotecontrolleroperationswitch,theOPERATIONdisplayisappearedbutitwillbeturnedoffsoon.
1Aftercancellingtoselectfunctionfromtheremotecontroller,theremotecontrolleroperationswitchwillbenotacceptedforapprox.30seconds.
1Normaloperation
OCH582B
43
Phenomena Factor Countermeasure
4.Evencontrollingbythewirelessremotecontroller,nobeepisheardandtheunitdoesnotstartoperating.Operationdisplayisindicatedonwirelessremotecontroller.
1Thepairnumbersettingsofthewirelessremotecontrollerandindoorcontrollerboardaremismatched.
1Checkthepairnumbersettings.
5.Whenoperatingbythewirelessremotecontroller,beepsoundisheard,however,unitdoesnotstartoperating.
1Nooperationfor2minutesatmostafterthepowersupplyON.
2Localremotecontrolleroperationisprohibited.•RemotecontrollingadaptorisconnectedtoCN32ontheindoorcontrollerboard.
•Localremotecontrolleroperationisprohibitedbycentralizedcontroller,etc.sinceitisconnectedtoMELANS.
3PhenomenaofNo.2.
1Normaloperation
2Normaloperation
3CheckthephenomenaNo.2.
6.Remotecontrollerdisplayworksnormallyandtheunitperformscoolingoperation,however,thecapacitycannotbefullyobtained.(Theairdoesnotcoolwell.)
1Refrigerantshortage2Filterclogging3Heatexchangerclogging4Airductshortcycle
1 • Ifrefrigerantleaks,dischargingtemperaturerisesandLEVopeningincreases.Inspectleakagebycheckingthetemperatureandopening.
• Checkpipeconnectionsforgasleakage.2Openintakegrilleandcheckthefilter.
Cleanthefilterbyremovingdirtordustonit.3 • Ifthefilterisclogged,indoorpipe
temperaturerisesanddischargingpressureincreases.Checkifheatexchangeriscloggedbyinspectingdischargingpressure.
• Cleantheheatexchanger.4Removetheblockage.
7.Remotecontrollerdisplayworksnormallyandtheunitperformsheatingoperation,however,thecapacitycannotbefullyobtained.
1LinearexpansionvalvefaultOpeningcannotbeadjustedwellduetolinearexpansionvalvefault.
2Refrigerantshortage3Lackofinsulationforrefrigerantpiping4Filterclogging5Heatexchangerclogging6Airductshortcycle7Bypasscircuitofoutdoorunitfault
1 • Dischargingtemperatureandindoorheatexchangertemperaturedoesnotrise.Inspectthefailurebycheckingdischargingpressure.
• Replacelinearexpansionvalve.2 • Ifrefrigerantleaks,discharging
temperaturerisesandLEVopeningincreases.Inspectleakagebycheckingthetemperatureandopening.
• Checkpipeconnectionsforgasleakage.3Checktheinsulation.4Openintakegrilleandcheckthefilter.
Cleanthefilterbyremovingdirtordustonit.
5 • Ifthefilterisclogged,indoorpipetemperaturerisesanddischargingpressureincreases.Checkifheatexchangeriscloggedbyinspectingdischargingpressure.
• Cleantheheatexchanger.6Removetheblockage.7 Checkrefrigerantsystemduringoperation.
8.1For3minutesaftertemperatureadjusterturnsoff,thecompressorwillnotstartoperatingeveniftemperatureadjusteristurnedon.
2For3minutesaftertemperatureadjusterturnson,thecompressorwillnotstopoperatingeveniftemperatureadjusteristurnedoff.(Compressorstopsoperatingimmediatelywhenturningoffbytheremotecontroller.)
12Normaloperation(Forprotectionofcompressor)
12Normaloperation
OCH582B
44
How long is “PLEASE WAIT” kept being displayed on the
remote controller?
6 minutes or more
2 minutes or less
2 to 6 minutes
NO
NO
YES
YES
Are any check codes displayed on the remote controller?
Are any check codes displayed on the LED?
Symptoms: “PLEASE WAIT” is kept being displayed on the remote controller.
Check the display time of “PLEASE WAIT” after turning on the main power.
• “PLEASE WAIT” will be displayed during the start-up diagnosis after turning on the main power.
• Normal The start-up diagnosis will be over in around 2 minutes.
• Miswiring of indoor/ outdoor connecting wire• Breaking of indoor/ outdoor connecting wire (S3)• Defective indoor controller board• Defective outdoor controller circuit board
• Refer to “Self-diagnosis action table” in order to solve the trouble.
• In case of communication errors, the display of remote controller may not match the LED display of the outdoor unit.
• Defective indoor controller board• Defective remote controller
Check the LED display of the outdoor controller circuit board.
Diagnosis flow Cause Inspection method and troubleshooting
OCH582B
45
198 to 264 V AC?
198 to 264 V AC?
198 to 264 V AC?
12 to 16 V DC?
12 to 16 V DC?
NO
YES
NO
YES
NO
YES
YES
NO
YES
NO
Check the voltage between S1 and S2 on the terminal block (TB4) of the indoor unit which is used to connect the indoor unit and the outdoor unit.
Check the voltage among L(L3) and N on the terminal block (TB1) of the outdoor power circuit board.
Check the voltage of indoor controller board (CN2D).
Check the voltage of the unit after removing the indoor power board (CN2S).
Check the voltage between S1 and S2 on the terminal block (TB1) of the outdoor unit which is used to connect the indoor unit and the outdoor unit.
• Troubles concerning power supply.
• Check the power wiring to the outdoor unit.• Check the breaker.
• Bad wiring of the outdoor controller board.• The fuses on the outdoor controller circuit board are blown.
• Check the wiring of the outdoor unit.• Check if the wiring is bad. Check if the fuses are blown. The fuses on the outdoor controller circuit board will be blown when the indoor /outdoor connecting wire short-circuits.
• Bad wiring of the outdoor controller board.• The fuses on the outdoor controller circuit board are blown.
• Check if miswiring, breaking or poor contact is causing this problem. Indoor/outdoor connecting wire is polarized 3-core type. Connect the indoor unit and the outdoor unit by wiring each pair of S1, S2 and S3 on the both side of indoor/outdoor terminal blocks.
• Defective indoor power board
• Replace the indoor power board.
• Defective indoor controller board
• Replace the indoor controller board.
• Miswiring, breaking or poor connection of indoor/outdoor connecting wire
• Check if there is miswiring or breaking of wire.
Symptoms: Nothing is displayed on the remote controller. 1
Diagnosis flow Cause Inspection method and troubleshooting
LED display of the indoor controller boardLED1 :LED2 : LED3 :
OCH582B
46
198 to 264 V AC?
Are there looseness or disconnection of the indoor/outdoor connecting wire?
Is anything displayed?
17 to 28 V DC?
Is “E8” displayed?
Can all the indoor unit be operated?
Check the voltage between S2 and S3 on the terminal block of the outdoor unit.
NO
YES
Not lighting.
Blinking.
NO
YES
NO
YES
Not displayed.
Displayed.
YES
NO
YES
NO
Check the voltage between S1 and S2 on the terminal block (TB4) of the indoor unit which is used to connect the indoor unit and the outdoor unit.
Check the refrigerant address of the outdoor unit. (SW1-3 to 1-6)
Check the looseness or disconnection of the indoor/outdoor connecting wire.
Check the LED display of the outdoor unit after turning on the main power again.
Can the unit be restarted?
• Breaking or poor contact of the indoor/outdoor connecting wire
• Fix the breaking or poor contact of the indoor/outdoor connecting wire.
• Defective outdoor controller circuit board
• Replace the outdoor controller circuit board.
• Normal Only the unit which has the refrigerant address “0” supplies power to the remote controller.
• Set the refrigerant address to “0”. In case of the multiple grouping system, recheck the refrigerant address again.
• Defective indoor power board
• Replace the indoor power board.
• Defective outdoor power circuit board
• Replace the outdoor power circuit board.
• Defective indoor controller board
• Replace the indoor controller board of the indoor unit which does not operate.
• Defective outdoor controller circuit board
• Replace the outdoor controller circuit board.
• Influence of electromagnetic noise
• Not abnormal There may be the influence of electromagnetic noise. Check the transmission wire and get rid of the causes.
Symptoms: Nothing is displayed on the remote controller. 2
Diagnosis flow CauseInspection method and troubleshooting
LED display of the indoor controller boardLED1 :LED2 : LED3 : or
Check the status of the indoor controller board LED3 display.
Is the refrigerant address “0”?
NO
YES
NO
YES
Is “EA” or “Eb” displayed?
OCH582B
47
Diagnosis flow Cause Inspection method and troubleshooting
Symptoms: Nothing is displayed on the remote controller. 3
LED display of the indoor controller boardLED1 :LED2 : or LED3 : —
10 to 16 V DC?YES
NO
Lighting
Blinking
Lighting
Blinking
Check the voltage of the terminal block (TB6) of the remote controller.
Check the status of the LED2 after disconnecting the remote controller wire from the terminal block (TB5) of the indoor unit.
• Defective remote controller
• Replace the remote controller.
• Breaking or poor contact of the remote controller wire
• Check if there is breaking or poor contact of the remote controller wire. Check the voltage of the terminal block (TB5) connecting the remote controller wire. If it is not between 10 and 16 V DC, the indoor controller board must be defective.
• The remote controller wire short-circuits
• Check if the remote controller wire is short-circuited.
• Defective indoor controller board
• Replace the indoor controller board.
Check the status of the LED2.
Check the status of the LED2.
OCH582B
48
1 The operating display of remote controller does not come on.
Phone Calls From Customers How to Respond Note1 Check if power is supplied to air conditioner. Nothing appears on the display unless power is supplied.
2 Unit cannot be restarted for a while after it’s stopped.
2 Wait around 3 minutes to restart unit. The air conditioner is in a state of being protected by the microcomputer’s directive. Once the compressor is stopped, the unit cannot be restarted for 3 minutes. This control is also applied when the unit is turned on and off by remote controller.
3 Check code appears and blinkson the display of remotecontroller.
Refer to “SELF-DIAGNOSIS ACTION TABLE”. Check if servicing is required for the error.
Display time of “FILTER” depends on the model. Long life filter: 2500 hrs.Standard filter: 100 hrs.
3 Check code will be displayed if any protection devices of the air conditioner are actuated. What is check code?
1 “PLEASE WAIT” is displayed on the screen.
1 Wait around 2 minutes. An automatic startup test will be conducted for 2 minutes when power is supplied to the air conditioner. “PLEASE WAIT” will be kept displayed while that time.
2 “FILTER” is displayed on the screen.
2 This indicates that it is time to clean the air filters. Clean the air filters. Press the FILTER button on the remote controller twice to clear “FILTER” from the display. See the operation manual that came with the product for how to clean the filters.
3 “STANDBY” is displayed on the screen.
3 This is displayed when the unit starts HEAT operation, when the thermostat puts the compressor in operation mode, or when the outdoor unit ends DEFROST operation and returns to HEAT operation. The display will automatically disappear around 10 minutes later. While “STANDBY” is displayed on the remote controller, the airflow amount will be restricted because the indoor unit’s heat exchanger is not fully heated up. In addition to that, the up/down vane will be automatically set to horizontal blow in order to prevent cold air from directly blowing out to human body. The up/down vane will return to the setting specified by the remote controller when “STANDBY” is released.
4 “DEFROST” is displayed on the screen. (No air comes out of the unit.)
4 The outdoor unit gets frosted when the outside temperature is low and the humidity is high. “DEFROST” indicates the DEFROST operation is being performed to melt this frost. The DEFROST operation ends in around 10 minutes (at most 15 minutes). During the DEFROST operation, the indoor unit’s heat exchanger becomes cold, so the fan is stopped. The up/down vane will be automatically set to horizontal blow in order to prevent cold air from directly blowing out to human body. The display will turn into “STANDBY” when DEFROST operation ends.
Unit does not operate at all.
Remote controller
• Before repair Frequent calling from customers
OCH582B
49
Phone Calls From Customers How to Respond Note1 Check the set temperature of remote controller. The outdoor unit cannot be operated if the set temperature is not appropriate. The outdoor unit operates in the following modes.
COOL: When the set temperature is lower than the room temperature. HEAT: When the set temperature is higher than the room temperature.
2 Check if filters are not dirty and clogged. If filters are clogged, the airflow amount will be reduced and the unit capacity will be lowered. See the instruction manual that came with the product for how to clean the filters.3 Check there is enough space around the air conditioner. If there are any obstacles in the air intake or air outlet of indoor/outdoor units, they block the airflow direction so that the unit capacity will be lowered.
1 A gas escaping sound is heard sometimes.
1 This is not a malfunction. This is the sound which is heard when the flow of refrigerant in the air conditioner is switched.
2 A cracking sound is heard sometimes.
2 This is not a malfunction. This is the sound which is heard when internal parts of units expand or contract when the temperature changes.
3 A buzzing sound is heard sometimes.
3 This is not a malfunction. This is the sound which is heard when the outdoor unit starts operating.
4 A ticking sound is heard from the outdoor unit sometimes.
4 This is not a malfunction. This is the sound which is heard when the fan of the outdoor unit is controlling the airflow amount in order to keep the optimum operating condition.
5 A sound, similar to water flowing, is heard from the unit.
5 This is not a malfunction. This is the sound which is heard when the refrigerant is flowing inside the indoor unit.
2 The fan speed does not match the setting of the remote controller in HEAT operation.
The up/down vane will be automatically set to horizontal blow in these cases listed up on the left (1–3). After a while, the up/down vane will be automatically moved according to the setting of the remote controller.
2 This is not a malfunction. 1) When the HEAT operation starts, to prevent the unit from blowing cold air, the fan speed is gradually increased from zero to the set speed, in proportion to the temperature rise of the discharged air. 2) When the room temperature reaches the set temperature and the outdoor unit stops, the unit starts the LOW AIR operation. 3) During the HEAT operation, the DEFROST operation is performed to defrost the outdoor unit. During the DEFROST operation, the blower is stopped to prevent cold air coming out of the indoor unit.
Sound comes out from the air conditioner.
1 The fan speed does not match the setting of the remote controller during DRY operation.(No air comes out sometimes during DRY operation.)
1 This is not a malfunction. During the DRY operation, the blower’s ON/OFF is controlled by the microcomputer to prevent overcooling and to ensure efficient dehumidification. The fan speed cannot be set by the remote controller during DRY operation.
Something is wrong with the blower…..
The room cannot be cooled or heated sufficiently.
OCH582B
50
3 Air blows out for a while after HEAT operation is stopped.
Phone Calls From Customers How to Respond Note
3 This is not a malfunction. The blower is operating just for cooling down the heated-up air conditioner. This will be done within 1 minute. This control is conducted only when the HEAT operation is stopped with the electric heater ON.
However, this control is also applied to the models which has no electric heater.
“STANDBY” will be displayed on the remote controller in case of 1 and 2. “DEFROSTING” will be displayed on the screen in case of 3.
1 The airflow direction is changed during COOL operation.
1 If the up/down vane is set to downward in COOL operation, it will be automatically set to horizontal blow by the microcomputer in order to prevent water from dropping down. “1 Hr.” will be displayed on the remote controller if the up/down vane is set to downward with the fan speed set to be less than “LOW”.
2 The airflow direction is changed during HEAT operation. (The airflow direction cannot be set by remote controller.)
2 In HEAT operation, the up/down vane is automatically controlled according to the temperature of the indoor unit’s heat exchanger. In the following cases written below, the up/down vane will be set to horizontal blow, and the setting cannot be changed by remote controller. 1) At the beginning of the HEAT operation 2) While the outdoor unit is being stopped by thermostat or when the outdoor unit gets started to operate. 3) During DEFROST operation The airflow direction will be back to the setting of remote controller when the above situations are released.
3 The airflow direction does not change. (Up/down vane, left/right louver)
3 1) Check if the vane is set to a fixed position. (Check if the vane motor connector is removed.) 2) Check if the air conditioner has a function for switching the air direction. 3) If the air conditioner does not have that function, “NOT AVAILABLE” will be displayed on the remote controller when “AIR DIRECTION” or “LOUVER” button is pressed.
Something is wrong with the blower…..
Something is wrong with the airflow direction….
1 Check if you set ON/OFF timer. The air conditioner starts operating at the time designated if ON timer has been set before.
2 Check if any operations are ordered by distant control system or the central remote controller. While “CENTRALLY CONTROLLED INDICATOR” is displayed on the remote controller, the air conditioner is under the control of external directive.
The air conditioner starts operating even though any buttons on the remote controller are not pressed.
1 Check if you set ON/OFF timer. The air conditioner stops operating at the time designated if OFF timer has been set before.
The air conditioner stops even though any buttons on the remote controller are not pressed.
There might be a case that “CENTRALLY CONTROLLED INDICATOR” will not be displayed.
There might be a case that “CENTRALLY CONTROLLED INDICATOR” will not be displayed.
3 Check if power is recovered from power failure (black out). The units will automatically start operating when power is recovered after power failure (black out) occurs. This function is called “auto recovery feature from power ”.
2 Check if any operations are ordered by distant control system or the central remote controller. While “CENTRALLY CONTROLLED INDICATOR” is displayed on the remote controller, the air conditioner is under the control of external directive.
OCH582B
51
Phone Calls From Customers How to Respond Note
This is not a malfunction.This may occur when the operation gets started in the room of high humidity.
A white mist is expelled from the indoor unit.
COOL: when pipes or piping joints are cooled, they get sweated and water drips down.HEAT: water drips down from the heat exchanger.Note: Make use of optional parts “Drain Socket” and
“Drain pan” if these water needs to be collected and drained out for once.
Water or moisture is expelled from the outdoor unit.
Batteries are being exhausted. Replace them and press the reset button of remote controller.
The display of wireless remote controller gets dim or does not come on.The indoor unit does not receive a signal from remote controller at a long distance.
OCH582B
52
12345
MGray
Orange
Red
Yellow
Black
Parts name Check points
Disconnect the connector then measure the resistance with a tester. (At the ambient temperature 10 to 30°C)
Thermistor (TH3)<Liquid>Thermistor (TH6)<2-phase pipe>Thermistor (TH7)<Ambient> Thermistor (TH8)<Heat sink>Thermistor (TH32)<Comp. Surface>
Normal160 to 410 k"
4.3 to 9.6 k"
39 to 105 k"
TH32TH3TH6TH7TH8
Abnormal
Open or short
Measure the resistance between the terminals with a tester. (At the ambient temperature 20°C)
Solenoid valve coil<4-way valve> (21S4)
Motor for compressor(MC)
Linear expansion valve(LEV-A)
Normal Abnormal
Open or short
Abnormal
Open or shortRefer to “5-3. COMPRESSOR TECHNICAL DATA”.
Disconnect the connector then measure the resistance with a tester. (Winding temperature 20°C)
Normal
Gray - Black Gray - Red Gray - Yellow Gray - Orange
Abnormal
46 ± 3 "Open or short
Refer to the next page.Fan motor(MF1,MF2)
Measure the resistance between the terminals with a tester. (Winding temperature 20°C)
Normal
W
V
U
P200/250
1215 ± 122 "
10-6. HOW TO CHECK THE PARTSPUHZ-P200YKA.UK PUHZ-P250YKA.UKPUHZ-P200YKAR1.UK PUHZ-P250YKAR1.UK
OCH582B
53
Notes · High voltage is applied to the connecter (CNF1, 2) for the fan motor. Pay attention to the service. · Do not pull out the connector (CNF1, 2) for the motor with the power supply on. (It causes trouble of the outdoor controller circuit board and fan motor.)Self checkSymptom : The outdoor fan cannot rotate.
1
2
Check method of DC fan motor (fan motor/outdoor controller circuit board)
Fail
Fail
Wiring contact checkContact of fan motor connector (CNF1, 2)
Fuse checkCheck the fuse (F5) on outdoorcontroller circuit board.
Power supply check (Remove the connector (CNF1, 2))Measure the voltage in the outdoor controller circuit board.TEST POINT 1 : VDC (between 1 (+) and 4 (−) of the fan connector): VDC 250–330 V DCTEST POINT 2 : VCC (between 5 (+) and 4 (−) of the fan connector): VCC 15 V DC
Recover wiring.
Replace the outdoor controller circuit board.
Replace the fan motor.
Replace the outdoor controller circuit board (C.B) and fan motor (MF1, 2).
Replace the outdoor controller circuit board.
Replace the fan motor.
Is the voltage normal?
Is there contact failure?
Yes
No
Did the fuse blow?
No
Yes
Check the operation of fan. END
Yes OK
Check the operation. END
OK
Yes
No
OCH582B
54
10-7. HOW TO CHECK THE COMPONENTS<Thermistor feature chart>Low temperature thermistors
•Thermistor<Liquid>(TH3)•Thermistor<2-phasepipe>(TH6)•Thermistor<Ambient>(TH7)
0: 15k"10: 9.6k"20: 6.3k"25: 5.2k"
0: 180k"25: 50k"50: 17k"70: 8k"90: 4k"
30: 4.3k"40: 3.0k"
ThermistorR0=15k"±3%Bconstant=3480±2%
Rt=15exp{3480(273+t– 273)}
1 1
ThermistorR50=17k"±2%Bconstant=4150±3%
Rt=17exp{4150(273+t–323)}1 1
ThermistorR120=7.465k"±2%Bconstant=4057±2%
Rt=7.465exp{4057(273+t–393)}1 1
Medium temperature thermistor
•Thermistor<HeatSink>(TH8)
20: 250k"30: 160k"40: 104k"50: 70k"60: 48k"
70: 34k"80: 24k"90: 17.5k"100: 13.0k"110: 9.8k"
High temperature thermistor
•Thermistor<Comp.Surface>(TH32)
0
10
20
30
40
50
−20 −10 0 10 20 30 40 50Temperature (:)
Res
ista
nce
(k"
)
200
150
100
50
025 50 75 100 125
Temperature (:)
Res
ista
nce
(k"
)
500
400
300
200
100
025 50 75 100 120
Temperature (:)
Res
ista
nce
(k"
)
OCH582B
55
<Output pulse signal and the valve operation>
(2) Linear expansion valve operation
A
B
C
Open
Extra tightening (about 32 pulse)
Pulse number
500 pulseOpening a valveall the way
CloseValv
e po
sitio
n (c
apac
ity)
Openingavalve:8→7→6→5→4→3→2→1→8Closingavalve:1→2→3→4→5→6→7→8→1Theoutputpulseshiftsinaboveorder.
·Whenlinearexpansionvalveoperationstops,alloutputphasesbecomeOFF.
·Whenthepoweristurnedon,700pulseclosingvalvesignalwillbesenttillitgoestoApointinordertodefinethevalveposition.
(Thepulsesignalisbeingsentforabout20seconds.)
Whenthevalvemovessmoothly,thereisnosoundorvibrationoccurringfromthelinearexpansionvalve:however,whenthepulsenumbermovesfromB to Aorwhenthevalveislocked,moresoundcanbeheard.
NosoundisheardwhenthepulsenumbermovesfromB to Aincasecoilisburntoutormotorislockedbyopen-phase.
·Soundcanbedetectedbyplacingtheearagainstthescrewdriv-erhandlewhileputtingthescrewdrivertothelinearexpansionvalve.
LEV
M
16
[4 [4
[3
[2
[1
1Gray
Orange
Red
Yellow
Black
2
3
4
5
Connector LEV-ALEV-BLEV-C
12 V DC
Outdoor controller board
Drive circuit
[3
[2
[1
3
2
54
Linearexpansionvalve(1) Operation summary of the linear expansion valve•Linearexpansionvalveopens/closesthroughsteppingmotorafterreceivingthepulsesignalfromtheoutdoorcontrollercir-cuitboard.•Valvepositioncanbechangedinproportiontothenumberofpulsesignal.<Connectionbetweentheoutdoorcontrollerboardandthelinearexpansionvalve>
1
ON
OFF
OFF
OFF
ON
ON
OFF
OFF
OFF
ON
OFF
OFF
OFF
ON
ON
OFF
[1
Output(Phase)
Output
[2
[3
[4
2 3 4 5 6 7 8
OFF
OFF
ON
OFF
OFF
OFF
ON
ON
OFF
OFF
OFF
ON
ON
OFF
OFF
ON
OCH582B
56
Main body
Lead wire
StopperCoil
Be sure to attach the stopper.
A
(3) How to attach and detach the coil of linear expansion valve<Composition>Linearexpansionvalveisseparableintothemainbodyandthecoilasshowninthediagrambelow.
<How to detach the coil> Holdthelowerpartofthemainbody(shownasA)firmlysothatthemainbodydoesnotmoveanddetachthecoilbypullingitupward.Besuretodetachthecoilholdingmainbodyfirmly.Otherwisepipescanbendduetopressure.
<How to attach the coil> Holdthelowerpartofthemainbody(shownasA)firmlysothatthemainbodydoesnotmoveandattachthecoilbyinsertingitdownwardintothemainbody.Thensecurelyattachthecoilstop-pertomainbody.(Atthistime,becarefulthatstressisnotaddedtoleadwireandmainbodyisnotwoundbyleadwire.)Ifthestopperisnotfirmlyattachedtomainbody,coilmaybedetachedfromthemainbodyandthatcancausedefectiveoperationoflin-earexpansionvalve.Topreventpipingstress,besuretoattachthecoilholdingthemainbodyoflinearexpansionvalvefirmly.Otherwisepipemaybreak.
A
OCH582B
57
(4) Releasing emergency operation 1Turnthemainpowersupplyoff.2Settheemergencyoperationswitch(SWE)onindoorcontrollerboardtoOFF.3Settheshortingpinsofemergencyoperationconnector(CN31)onoutdoorcontroller
boardtoOFF.4SetSW4-2onoutdoorcontrollerboardasshownintheright.
Note:Ifshortingpinsarenotsetonemergencyoperationconnector(CN31),thesettingremainsOFF.
SW4
1 2 Cooling
HeatingON
10-8. EMERGENCY OPERATION (1)Whenanycheckcodesshownbelowisdisplayedonoutdoorunit,ormicrocomputerforwiredremotecontrollerorindoor unithasafailurewhilenootherproblemsarefound,emergencyoperationwillbeavailablebysettingtheemergencyopera-
tionswitch(SWE)ONandshort-circuitingtheconnector(CN31)onoutdoorcontrollerboard.
(2) Check the following items and cautions for emergency operation 1Makesurethatthereisnoabnormalityinoutdoorunitotherthantheaboveabnormalities.(Emergencyoperationwillnot
beavailablewhencheckcodeotherthantheaboveareindicated.)2Foremergencyoperation,itisnecessarytosettheemergencyoperationswitch(SWE)onindoorcontrollerboard.Refer
totheelectricalwiringdiagramofindoorunitforhowtosettheindoorunit.3Duringemergencyoperation,theair-conditionerwillcontinuouslybeoperatedbysupplyingpowerandstoppingit:Itcan
notbeturnedonoroffbyremotecontrol,andtemperaturecontrolisnotpossible.4Donotperformemergencyheatingoperationforanextendedperiodoftime:Iftheoutdoorunitstartsdefrostingduring
thisperiod,coldairwillblowoutfromtheindoorunit.5Donotperformemergencycoolingoperationformorethan10hours:Neglectingthiscouldresultinfreezingtheheat
exchangerinindoorunit.
(3) Emergency operation procedure 1Turnthemainpowersupplyoff.2Turnontheemergencyoperationswitch(SWE)onindoorcontrollerboard.3Settheshortingpinsofemergencyoperationconnector(CN31)onoutdoorcontrollerboardtoON.4UseSW4-2onoutdoorcontrollerboardtosettheoperationmode(coolingorheating).(SW4-1isnotused.)
5Turningthemainpowersupplyonwillstarttheemergencyoperation.
SW4
1 2 Cooling
HeatingON ON
OFF
CN31 Shorting pins
Inspected contentOpen/short of outdoor unit thermistor (TH3/TH6/TH7/TH8)Indoor/outdoor unit communication error • Signal receiving error (Outdoor unit)Indoor/outdoor unit communication error • Transmitting error (Indoor unit)Communication error other than outdoor unitCommunication error between outdoor controller board and M-NET board (Serial communication error)
Check codeU4E8E9
E0–E7Ed
●When following abnormalities occur, emergency operation will be available.
OCH582B
58
(5) Operation data during emergency operationDuringemergencyoperation,nocommunicationisperformedwiththeindoorunit,sothedataitemsneededforoperationaresettothefollowingvalues:
Operation data
Intake temperature (TH1)
Indoor pipe temperature (TH2)
Indoor 2-phase pipe temperature (TH5)
Set temperature
Outdoor liquid pipe temperature (TH3)
Outdoor comp. surface temperature (TH32)
Outdoor 2-phase pipe temperature (TH6)
Outdoor ambient temperature (TH7)
Temperature difference code(room temperature - set temperature) (∆Tj)Discharge superheat (SHd)
Sub-cool (SC)
Operation mode
COOL
27:
5:
5:
25:
45:
80:
50:
35:
5
30:
5:
HEAT
20.5:
45:
50:
22:
5:
80:
5:
7:
5
30:
5:
(*1)
(*1)
(*1)
(*1)
(*2)
(*2)
Remarks
*1. If the thermistor temperature data is normal (not open/short), that data is loaded into the control as valid data. When the unit enters emergency operation and TH values are mismatched, set the thermistors to open/short. And the unit runs emergency operation with the values listed above.*2. If one thermistor is set to open/short, the values for SHd/SC will be different from the list above. [Example] When liquid temperature thermistor (TH3) has an open or short circuit.
COOL
45:
Ta
Tc
5:
5:
HEAT
5:
Tb
Td
50:
45:
Thermistor
TH3
TH6
TH32
TH5
TH2
Regard normal figure as effective data.
Regard normal figure as effective data.
Discharge superheat (SHd) Cooling = TH32−TH6 = Tc−Ta Heating = TH32−TH5 = Td−50
Degree of subcooling (SC) Cooling = TH6−TH3 = Ta−45 Heating = TH5−TH2 = 50−45 = 5:
—
—
—
—
—
OCH582B
CNSS1–S2:230VAC
CNAC2 to 4: Powersupplyforout-
doorcontrollercircuitboard(230VAC)
1 to 3: Powersupplyforindoorandoutdoorunitconnectionwire(230VAC)
CN4Transmissiontoout-doorpowercircuitboard(CN4)
CN51Externalsignaloutput•Compressoroperatingsignal•Abnormalsignal
CN2Connecttotheoutdoorpowercircuitboard(CN2)1–5:Receptionfrom
powercircuitboard2–5:Zerocrosssignal
(0–5VDC)3,4:Notused6–5:16VDC7–5:16VDC
SW1Forceddefrost,detecthistoryrecordreset,refrigerantaddress
CNDM1–2:Inputoflow-levelsoundprioritymode1–3:Inputofexternalcontactpoint
SW7Demandcontrolsetting
63HHighpressureswitch
SW4Testoperation
SW6Modelselect
SW5Functionswitch
TH3Thermistor<Liquid>
TH7/6Thermistor<Ambient/2-phasepipe>
VFG
(VoltagebetweenrightpinsofPC5CandPC5D,pin3andpin4)(Sameas(CNF17(+)–4(−))
VSP(VoltagebetweenpinsofC5A,C5B):0VDC(whenstopped),1–6.5VDC(whenoperated)
LEV-ALinearexpansionvalve
SWPPumpdown
SW8PipereplaceWiringreplace
CNMConnecttoAcontrolservicetool
CNMNTConnecttoM-NETadapter(CN5)
CNVMNTConnecttoM-NETadapter(CND)
TH32Thermistor<Comp.Surface>
CommunicationpowersupplyD71Voltage24VDC
CNF1,CNF2Connecttothefanmotor1–4:250–330VDC5–4:15VDC6–4:0–6.5VDC7–4:15VDC(Whenstopped) 7.5VDC(Whenoperated) (0–15Vpulse)
CNDC250–330V DC(1+, 3−)(Noisefiltercircuitboard)
+−
21S44-wayvalve
59
<CAUTION>TESTPOINT1ishighvoltage.10-9. TEST POINT DIAGRAMOutdoor controller circuit boardPUHZ-P200YKA.UK PUHZ-P250YKA.UKPUHZ-P200YKAR1.UK PUHZ-P250YKAR1.UK
OCH582B
LI1,LI2,LI3,NIPOWER SUPPLYLI1-LI2/LI-LI3/LI3-LI1:400VACinputLI1-NI/LI2-NI/LI3-NI:230VACinput(Connecttotheterminalblock(TB1))
GD1Connecttotheearth
CNAC1,CNAC2230VAC(Connecttotheoutdoorcontrollercircuitboard(CNAC))
CNDC(Connecttotheoutdoorcontrollercircuitboard(CNDC))
LO1,LO2,LO3POWER SUPPLYLO1-LO2/LO2-LO3/LO3-LO1:400VACOUTPUT(Connecttotheoutdoorpowercircuitboard(TB-L1,L2,L3))
CNCTPrimarycurrent(Connecttotheoutdoorpowercircuitboard(CN5))
CNLConnecttotheACL4
60
Outdoor noise filter circuit boardPUHZ-P200YKA.UK PUHZ-P250YKA.UKPUHZ-P200YKAR1.UK PUHZ-P250YKAR1.UK
GD2Connecttotheearth
OCH582B
61
Outdoor power circuit boardPUHZ-P200YKA.UKPUHZ-P250YKAR1.UKPUHZ-P200YKA.UKPUHZ-P250YKAR1.UK
Brief Check of POWER MODULEUsually,theyareinastateofbeingshort-circuitediftheyarebroken.Measuretheresistanceinthefollowingpoints(connectors,etc.).Iftheyareshort-circuited,itmeansthattheyarebroken.1.CheckofDIODE MODULEL1-P1,L2-P1,L3-P1,L1-N1,L2-N1,L3-N12.CheckofDIP-IPMP2-U,P2-V,P2-W,N2-U,N2-V,N2-W
Note:ThemarksL1,L2,L3,N1,N2,P1,P2,U,VandWshowninthediagramarenotactuallyprintedontheboard.
CN5Detectionofprimarycurrent(Connecttotheoutdoornoisefiltercircuitboard(CNCT))
CN4Connecttotheoutdoorcontrollercircuitboard(CN4)
CN2Connecttotheoutdoorcontrollercircuitboard(CN2)1–5:Powercircuitboard→Transmittingsignaltothecontrollerboard(0–5VDC)2–5:Zerocrosssignal(0–5VDC)3–4:Notused6–5:16VDC7–5:16VDC
TB-U, TB-V, TB-WConnecttothecompressor(MC)Voltageamongphases:10–400VAC
Diodemodule
U P2VWN2
L3 N1L1P1 L2
DIP-IPM
TABconnectoronX52CAConnecttotheRSresistor
CN6Thermistor<Heatsink>(TH8)
TB-L1,TB-L2,TB-L3Connecttotheoutdoornoisefiltercircuitboard(LO1,LO2,LO3)400VAC
L3OUT-L3INLeadconnect
TB-P3ConnecttotheDCL
TB-P1ConnecttotheDCL
5:– 1, 2, 6, 7 : +
OCH582B
62
SwitchType
ofswitch
Dipswitch
Pushswitch
SW1
1
2
No. Function Effective timingAction by the switch operation
Forced defrost *1 Start Normal When compressor is working in heating operation. *1
Abnormal history clear
Refrigerant address setting When power supply ON
Clear Normal off or operating
SWP
6
5
4
3
Under suspensionPump down Start Normal
SW412
Test run Operating OFFUnder suspension
Test run mode setting Heating Cooling
ON OFF
1 2 30 1 2 3
4 5 6
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
1 2 34 5 6 7
4 5 6
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
1 2 38 9 10 11
4 5 6
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
1 2 312 13 14 15
4 5 6
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
10-10. FUNCTION OF SWITCHES, CONNECTORS AND JUMPERS (1) Function of switches
*1Forceddefrostshouldbedoneasfollows.1ChangetheDIPSW1-1ontheoutdoorcontrollerboardfromOFFtoON.2Forceddefrostwillstartbytheaboveoperation1ifalltheseconditionswrittenbelowaresatisfied.•Heatmodesetting•10minuteshavepassedsincecompressorstartedoperatingorpreviouscompulsorydefrostingfinished.•Pipetemperatureislessthanorequalto8°C.
Forceddefrostwillfinishifcertainconditionsaresatisfied. ForceddefrostcanbedoneifaboveconditionsaresatisfiedwhenDIPSW1-1ischangedfromOFFtoON. AfterDIPSW1-1ischangedfromOFFtoON,thereisnoproblemifDIPSW1-1isleftONorchangedtoOFFagain. Thisdependsontheserviceconditions.
Continuetothenextpage
Theblacksquare( )indicatesaswitchposition.
Outdoor M-NET board (optional)
LED2EnergizingdisplayofM-NETboard(5Vpowersupply)
CN2MConnecttoM-NET
LED13Receiving
LED11Outdoorunitconnectingdisplay
CN5Serialcommunicationwithoutdoorboard
SW11M-NETaddress(1sdigit)
SW12M-NETaddress(10sdigit)
SW1SwitchforcommunicationdisplaybetweenM-NETandoutdoorboard
CNDPowersupply(5V/12V)input2 to 35VDCInput1 to 312VDCInput))
1, 2 : + 3:– ][
LED12Transmitting
LED1EnergizingdisplayofM-NETboard(12Vpowersupply)
OCH582B
63
*2 ‘Powerfailureautomaticrecovery’canbesetbyeitherremotecontrollerorthisDIPSW.IfoneofthemissettoON,‘Autorecovery’activates.Pleaseset“Autorecovery”basicallybyremotecontrollerbecauseallunitsdonothaveDIPSW.
Pleaserefertotheindoorunitinstallationmanual.*3SW7-1issettingchangeoverofDemand/Lownoise.Itiseffectiveonlyincaseofexternalinput. (Localwiringisnecessary.Refertothenextpage:Specialfunction)*4PleasedonotuseSW7-3to7-6usually.Troublemightbecausedbytheusagecondition.*5SW5-1to5:Functionswitch
Type ofSwitch Switch No. Function
Action by the switch operationEffective timing
ON OFF
DIP switch
SW5
1 Nofunction — — —
2 Powerfailureautomaticrecovery*2 Autorecovery Noautorecovery WhenpowersupplyON
3,4,5 Nofunction — — —6 Modelselect FollowingSW5-6reference
SW7*4
1 Modeselect*3 Demandfunction Lownoisemode Always2 Nofunction — — —3 MaxHzsetting(cooling) MaxHz(cooling)o0.8 Normal Always4 MaxHzsetting(heating) MaxHz(heating)o0.8 Normal Always5 Nofunction — — —6 Defrostsetting Forhighhumidity Normal Always
SW81 Nofunction — — —2 Nofunction — — —3 Nofunction — — —
SW91 Nofunction — — —2 Functionswitch Valid Normal Always3,4 Nofunction — — —
SW6
1
Modelselect
2
3
4
5
6
7
8
SW5 6
1 2 3 4 5 6 7 8OFFON
1 2 3 4 5 6OFFON
1 2 3 4 5 6 7 8OFFON
1 2 3 4 5 6OFFON
SW6MODEL SW5-6*5
200Y
250Y
The black square (■) indicates a switch position.
OCH582B
64
Special function(a)Low-levelsoundprioritymode(Localwiring)
CN31
Types Connector Function Effective timing
Connector Start
Short Open
Action by open/ short operation
Emergency operation When power supply ONNormal
(2) Function of connector
(b)Ondemandcontrol(Localwiring)
Byperformingthefollowingmodification,operationnoiseoftheoutdoorunitcanbereducedbyabout3-4dB.ThelownoisemodewillbeactivatedwhenacommerciallyavailabletimerorthecontactinputofanON/OFFswitchisaddedtotheCNDMconnector(option)onthecontrolboardoftheoutdoorunit.• Theabilityvariesaccordingtotheoutdoortemperatureandconditions,etc.1Completethecircuitasshownwhenusingtheexternalinputadapter(PAC-SC36NA-E).(Option)2SW7-1(Outdoorunitcontrolboard):OFF3SW1ON:Lownoisemode SW1OFF:Normaloperation
ACircuitdiagramexample (lownoisemode)BOn-sitearrangementCExternalinputadapter (PAC-SC36NA-E)
X:RelayDOutdoorunitcontrolboardEMaximum10mFPowersupplyforrelay
A
SW1
Orange1
3
Brown
Red
EB
F
CNDM
XX
C D
ACircuitdiagramexample (Demandfunction)BOn-sitearrangementX,Y:Relay
CExternalinputadapter (PAC-SC36NA-E)DOutdoorunitcontrolboardEMaximum10mFPowersupplyforrelay
Byperformingthefollowingmodification,energyconsumptioncanbereducedto0–100%ofthenormalconsumption.ThedemandfunctionwillbeactivatedwhenacommerciallyavailabletimerorthecontactinputofanON/OFFswitchisaddedtotheCNDMconnector(option)onthecontrolboardoftheoutdoorunit.1Completethecircuitasshownwhenusingtheexternalinputadapter(PAC-SC36NA-E).(Option)2BysettingSW7-1onthecontrolboardoftheoutdoorunit,theenergyconsumption(comparedtothenormalconsumption)canbelimitedasshownbelow.
SW7-1 SW2 SW3 Energyconsumption
Demandfunction ON
OFF OFF 100%ON OFF 75%ON ON 50%OFF ON 0%(Stop)
A
SW2 SW3
Orange1
3
Brown
Red
CNDM
Y
XX Y
F
B E
C D
OCH582B
65
<Display function of inspection for outdoor unit>TheblinkingpatternsofbothLED1(green)andLED2(red)indicatethetypesofabnormalitywhenitoccurs.Typesofabnormalitycanbeindicatedindetailsbyconnectinganoptionalpart‘A-ControlServiceTool(PAC-SK52ST)’toconnectorCNMonoutdoorcontrollerboard.
1Be sure to replace the 4-way valve.2Check refrigerant pipes for disconnection or leakage.3After the recovery of refrigerant, vacuum dry the whole refrigerant circuit.4Refer to “10-6.HOW TO CHECK THE PARTS”.5Check refrigerant circuit for operation.
F5
—
—
—E6
E7
—
—
E0
E3
E4
E5
EF
PL
Ed
A0–A8
[Display] (1)Normal condition
(2)Abnormal condition
Unit conditionOutdoor controller board A-Control Service Tool
LED1 (Green) LED2 (Red) Check code
When the power is turned onWhen unit stopsWhen compressor is warming upWhen unit operates
Lighted LightedLightedLightedLighted
Not lighted
Indication of the displayAlternately blinking display
Operation modeNot lighted
Lighted
00, etc.08, etc.
C5, H7, etc.
Indication ErrorCheck code
*1
Outdoor controller boardContents Inspection method
LED1 (Green) LED2 (Red)1 blinking 2 blinking
2 blinking 1 blinking
2 blinking
3 blinking
4 blinking
5 blinking
Connector (63H) is open.
Startup time over
Check code is not defined.
Miswiring of indoor/outdoor unit conne-cting wire, excessive number of indoor units (4 units or more)Miswiring of indoor/outdoor unit co-nnecting wire (converse wiring or di-sconnection)
Indoor/outdoor unit communication error(signal receiving error) is detected by in-door unit. Indoor/outdoor unit communication error(transmitting error) is detected by indoorunit.Indoor/outdoor unit communication error(signal receiving error) is detected by outdoor unit.Indoor/outdoor unit communication error (transmitting error) is detected by outdoorunit.Remote controller signal receiving error is detected by remote controller.
Remote controller transmitting error is detected by remote controller.
Remote controller signal receiving error is detected by indoor unit.
Remote controller transmitting error is detected by indoor unit.
Serial communication error<Communication between outdoor controller board and outdoor power board><Communication between outdoor controller board and M-NET P.C. board>Communication error of M-NETsystem
*1.Check code displayed on remote controller
1Check if indoor/outdoor connecting wire is connected correctly.2Check if 4 or more indoor units are connected to outdoor unit.3Check if noise entered into indoor/outdoor connecting wire or power supply.4Re-check error by turning off power, and on again.
1Check if connector (63H) on the outdoor controller board is not disconnected. 2Check continuity of pressure switch (63H) by tester.
1Check if connector (CN4) on outdoor controller board and outdoor power board is not disconnected.2Check if there is poor connection of connector on outdoor controller board(CNMNT and CNVMNT).3Check M-NET communication signal.
1Check if remote controller is MA remote controller(PAR-21MAA).2Check if noise entered into transmission wire of remote controller.3Check if noise entered into indoor/outdoor connecting wire.4Re-check error by turning off power, and on again.
1Check if connecting wire of indoor unit or remote controller is connected correctly.2Check if noise entered into transmission wire of remote controller.3Re-check error by turning off power, and on again.
1Check if indoor/outdoor connecting wire is connected correctly.2Check if noise entered into indoor/outdoor connecting wire or power supply.3Check if noise entered into indoor/outdoor controller board.4Re-check error by turning off power, and on again.
P.30
P.31(EA)P.31(Eb)P.31(EC)P.37
P.37
P.37(E8)P.37(E9)P.36
P.36
P.36
P.36
P.37
P.38
P.38
P.39 toP.42
Detailedreference
page
OCH582B
66
U2
U1
U8
UdUF
UPUHU6U3
U4
U5
U9
P1P2P9
P4
P5
P6
P8
Indication ErrorCheckcode*1
Outdoor controller boardContents Inspection method
LED1 (Green) LED2 (Red)3 blinking 1 blinking
2 blinking
3 blinking
*1 Check code displayed on remote controller*2 Refer to the indoor unit’s service manual.
4 blinking
5 blinking
6 blinking
7 blinking
1 blinking
2 blinking
3 blinking
4 blinking
4 blinking
Abnormality of comp. surfacethermistor(TH32)
1Check if stop valves are open.2Check if connectors (TH32 and LEV-A) on outdoor controller board are not disconnected.3Check if unit is filled with specified amount of refrigerant.4Measure resistance values among terminals on indoor valve and outdoor linear expansion valve using a tester.
Abnormal high pressure (High pressure switch 63H operated.)
Abnormality of outdoor fan motor rotational speed
1Check if indoor/outdoor units have a short cycle on their air ducts.2Check if connector (63H) on outdoor controller board is not disconnected.3Check if heat exchanger and filter is not dirty.4Measure resistance values among terminals on linear expansion valve using a tester.
1Check if stop valves are open.2Check looseness, disconnection, and converse connection of compressor wiring.3Measure resistance values among terminals on compressor using a tester.4Check if outdoor unit has a short cycle on its air duct.
Compressor overcurrent breaking(Start-up locked)Compressor overcurrent breakingAbnormality of current sensor (P.B.)Abnormality of power moduleOpen/short of comp. surface thermistor (TH32)Open/short of outdoor thermistors(TH3, TH6, TH7 and TH8)
1Check if connectors(TH3, TH6 ,TH7 and TH32)on outdoor controller board and connector (CN3) on outdoor power board are not disconnected.2Measure resistance value of outdoor thermistors.
Abnormality of heat sinktemperature
1Check if indoor/outdoor units have a short cycle on their air ducts.2Measure resistance value of outdoor thermistor(TH8).
1Check the outdoor fan motor.2Check if connector (TH3) on outdoor controller board is disconnected.
Abnormality of voltage 1Check looseness, disconnection, and converse connection of compressor wiring.2Measure resistance value among terminals on compressor using a tester.3Check if power supply voltage decreases.4Check the wiring of CN52C.
Abnormality of room temperature thermistor (TH1)Abnormality of pipe temperature thermistor /Liquid (TH2)Abnormality of pipe temperature thermistor/Condenser-Evaporator
1Check if connectors (CN20, CN21, CN29 and CN44) on indoor controller board are not disconnected.2Measure resistance value of indoor thermistors.
Abnormality of drain sensor (DS)Float switch(FS) connector openIndoor drain overflow protection
1Check if connector (CN31)(CN4F) on indoor controller board is not disconnected.2Measure resistance value of indoor thermistors.3Measure resistance value among terminals on drain pump using a tester.4Check if drain pump works.5Check drain function.
Freezing (cooling)/overheating (heating) protection
1Check if indoor unit has a short cycle on its air duct.2Check if heat exchanger and filter is not dirty.3Measure resistance value on indoor and outdoor fan motors.4Check if the inside of refrigerant piping is not clogged.
Abnormality of pipe temperature
1Check if indoor thermistors(TH2 and TH5) are not disconnected from holder.2Check if stop valve is open.3Check converse connection of extension pipe. (on plural units connection)4Check if indoor/outdoor connecting wire is connected correctly. (on plural units connection)
P.32
P.32
P.33
P.35P.35
P.35P.35P.33P.32
P.33
P.33
P.34
*2*2*2
*2
*2
*2
Detailedreference
page
Protection from overheat operation(TH3)
OCH582B
67
<Outdoor unit operation monitor function>[When optional part ‘A-Control Service Tool (PAC-SK52ST)’ is connected to outdoor controller board (CNM)]DigitalindicatorLED1displays2digitnumberorcodetoinformoperationconditionandthemeaningofcheckcodebycontrollingDIPSW2on‘A-ControlServiceTool’.OperationindicatorSW2:Indicatorchangeofselfdiagnosis
SW2setting
1
ON
2 3 4 5 6
Displaydetail Explanationfordisplay Unit
<Digital indicator LED1 working details>(Besurethatthe1to6intheSW2aresettoOFF.)(1)DisplaywhenthepowersupplyON
WhenthepowersupplyON,blinkingdisplaysbyturns.Waitfor4minutesatthelongest.
(2)Whenthedisplaylights(Normaloperation)1Operationmodedisplay.
1
ON
2 3 4 5 6
(Initialsetting)
SW2
1 secondinterval
LED1(Lighting)
Display Operation ModelThe tens digit: Operation mode The ones digit: Relay output
OCHd
Display
012345678A
CompressorWarming-upCompressor 4-way valve Solenoid valve
————ONONONON——
————————ONON
——ONON——ONON—ON
—ON—ON—ON—ON——
OFF/FANCOOLING/DRY *
HEATINGDEFROSTING
2DisplayduringerrorpostponementPostponementcodeisdisplayedwhencompressorstopsduetotheworkofprotectiondevice.Postponementcodeisdisplayedwhileerrorisbeingpostponed.
*C5isdisplayedduringreplacementoperation.
(3)WhenthedisplayblinksInspectioncodeisdisplayedwhencompressorstopsduetotheworkofprotectiondevices.
Display Contents to be inspected (When power is turned on)F5E8E9EAEbEC
E0–E7
63H connector(yellow) is open.Indoor/outdoor communication error (Signal receiving error) (Outdoor unit)Indoor/outdoor communication error (Transmitting error) (Outdoor unit)Miswiring of indoor/outdoor unit connecting wire, excessive number of indoor units (4 units or more)Miswiring of indoor/outdoor unit connecting wire(converse wiring or disconnection)Startup time overCommunication error except for outdoor unit
Display Inspection unit01234
Outdoor unitIndoor unit 1Indoor unit 2Indoor unit 3Indoor unit 4
Display Contents to be inspected (During operation)U1U2U3U4U5U6U8UdUFUHULUPPL
P1–P8A0–A7
Abnormal high pressure (63H operated)Abnormal comp. surface thermistor, shortage of refrigerantOpen/short circuit of comp. surface thermistor(TH32)Open/short of outdoor unit thermistors (TH3, TH6, TH7 and TH8)Abnormal temperature of heat sinkAbnormality of power moduleAbnormality in outdoor fan motorOverheat protectionCompressor overcurrent interruption (When Comp. locked)Current sensor errorAbnormal low pressureCompressor overcurrent interruptionAbnormality of refrigerantAbnormality of indoor unitsCommunication error of M-NET system
OCH582B
68
SW2setting
1
ON
2 3 4 5 6
Displaydetail Explanationfordisplay UnitPipetemperature/Liquid(TH3)−40to90
−40to90(Whenthecoilthermistordetects0:orbelow,“–”andtemperaturearedisplayedbyturns.)(Example)When−10:;0.5s0.5s2s
:
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
Comp.surfacetemperature(TH32)−52to221
OutputstepofoutdoorFAN0to10
ThenumberofON/OFFtimesofcom-pressor0to9999
Compressorintegratingoperationtimes0to9999
−52to221(Whenthecomp.surfacethermistordetects100:ormore,hundredsdigit,tensdigitandonesdigitaredisplayedbyturns.)(Example)When105:;0.5s0.5s2s
:
Step
100times
10hours
0to10
0to9999(Whenthenumberoftimesis100ormore,hundredsdigit,tensdigitandonesdigitaredisplayedbyturns.)(Example)When42500times(425×100times);0.5s0.5s2s
0to9999(Whenitis100hoursormore,hundredsdigit,tensdigitandonesdigitaredisplayedbyturns.)(Example)When2450hours(245×10hours);0.5s0.5s2s
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
Compressoroperatingcurrent0to50
LEV-Aopeningpulse0to480
0to50(Omitthefiguresafterthedecimalfractions.)
0to480(Whenitis100pulseormore,hundredsdigit,tensdigitandonesdigitaredisplayedbyturns.(Example)When150pulse;0.5s0.5s2s
A
Pulse
Errorpostponementcodehistory(1)ofoutdoorunit
PostponementcodedisplayBlinking:DuringpostponementLighting:Cancellationofpostponement“00”isdisplayedincaseofnopostponement.
Codedisplay
Codedisplay
Operationmodeonerroroccurring OperationmodeofwhenoperationstopsduetoerrorisdisplayedbysettingSW2likebelow.
1
ON
2 3 4 5 6
(SW2)
10
1
ON
2 3 4 5 6
Compressoroperatingfrequency0to255
0to255(Whenitis100 Hzormore,hundredsdigit,tensdigitandonesdigitaredisplayedbyturns.(Example)When125Hz;0.5s0.5s2s
Hz
1 05
4 25
2 45
1 25
1 50
1
ON
2 3 4 5 6
Theblacksquare( )indicatesaswitchposition.
OCH582B
69
SW2setting
1
ON
2 3 4 5 6
Displaydetail Explanationfordisplay UnitPipetemperature/Liquid(TH3)onerroroccurring−40to90
−40to90(Whenthecoilthermistordetects0:orbelow,“–”andtemperaturearedisplayedbyturns.)(Example)When−15:;0.5s0.5s2s
:
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
Comp.surfacetemperature(TH32)onerroroccurring−52to221
Compressoroperatingcurrentonerroroccurring0to50
Errorhistory(1)(latest)Alternatedisplayofabnormalunitnumberandcode
Errorhistory(2)Alternatedisplayoferrorunitnumberandcode
−52to221(Whenthetemperatureis100:ormore,thehundredsdigit,tensdigitandonesdigitaredisplayedbyturns.)(Example)When130:;0.5s0.5s2s
:
A
Codedisplay
Codedisplay
0to50
Whennoerrorhistory,“0”and“––”aredisplayedbyturns.
Whennoerrorhistory,“0”and“––”aredisplayedbyturns.
1
ON
2 3 4 5 6
ThermostatONtime0to999
Testrunelapsedtime0to120
0to999(Whenitis100minutesormore,thehundredsdigit,tensdigitandonesdigitaredisplayedbyturns.)(Example)When245minutes;0.5s0.5s2s
0to120(Whenitis100minutesormore,thehundredsdigit,tensdigitandonesdigitaredisplayedbyturns.)(Example)When105minutes;0.5s0.5s2s
Minute
Minute
15
1 30
2 45
1 05
Theblacksquare( )indicatesaswitchposition.
OCH582B
70
SW2setting
1
ON
2 3 4 5 6
Displaydetail Explanationfordisplay Unit
Capacitysettingdisplay Displayedasanoutdoorcapacitycode.
Codedisplay
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
Outdoorunitsettinginformation
Indoorpipetemperature/Liquid(TH2(1))Indoor1−39to88
Codedisplay
:
−39to88(Whenthetemperatureis0:orless,“–”andtemperaturearedisplayedbyturns.)
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
Indoorroomtemperature(TH1)8to39
Capacity CodeP200YKA 40P250YKA 50
Setting details• The tens digit (Total display for applied setting)
• The ones digit
H·P / Cooling onlySingle phase / 3 phase
Display details
0 : H·P 1 : Cooling only0 : Single phase 2 : 3 phase
Setting details
Defrosting switch
Display details
0 : Normal 1 : For high humidity
(Example)Whenheatpump,3phaseanddefrosting(normal)aresetup,“20”isdisplayed.
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
Indoorpipetemperature/Cond./Eva.(TH5(1))Indoor1−39to88
−39to88(Whenthetemperatureis0:orless,“–”andtemperaturearedisplayedbyturns.)
:
−39to88(Whenthetemperatureis0:orless,“–”andtemperaturearedisplayedbyturns.)
−39to88(Whenthetemperatureis0:orless,“–”andtemperaturearedisplayedbyturns.)
:
:
:
8to39
Indoorpipetemperature/Liquid(TH2(2))Indoor2−39to88
Indoorpipetemperature/Cond./Eva.(TH5(2))Indoor2−39to88
1
ON
2 3 4 5 6
Thenumberofconnectedindoorunits
Unit
0to4(Thenumberofconnectedindoorunitsaredis-played.)
Theblacksquare( )indicatesaswitchposition.
OCH582B
71
1
ON
2 3 4 5 6
°C
DischargesuperheatSHd0to255
Cooling=TH32−TH6Heating=TH32−TH5
0to255(Whenthetemperatureis100°Cormore,hundredsdigit,tensdigitandonesdigitaredisplayedbyturns.)
0.1A
Inputcurrentofoutdoorunit 0to500(Whenitis100ormore,hundredsdigit,tensdigitandonesdigitaredisplayedbyturns.)
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
SW2setting
1
ON
2 3 4 5 6
Displaydetail Explanationfordisplay Unit
°C
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
Indoorsettingtemperature17to30
Outdoorpipetemperature/2-phase(TH6)−39to88
OutdoorHeatsinktemperature(TH8)−40to200
17to30
°C
°C
°C
−39to88(Whenthetemperatureis0:orless,“–”andtemperaturearedisplayedbyturns.)
−40to200(Whenthetemperatureis0:orless,“–”andtemperaturearedisplayedbyturns.)(Whenthethermistordetects100:ormore,hundredsdigit,tensdigitandonesdigitaredisplayedbyturns.)
OutdoorAmbienttemperature(TH7)−39to88
−39to88(Whenthetemperatureis0:orless,“–”andtemperaturearedisplayedbyturns.)
NormalOvervoltage errorUndervoltage errorInput current sensor errorL1-phase open errorAbnormal power synchronous signal
Display examples for multiple errors: Overvoltage (01) + Undervoltage (02) = 03 Undervoltage (02) + Power-sync signal error (08) = 0A
Description Display000102
04
08
U9errordetailhistory(latest)
Codedisplay
1
ON
2 3 4 5 6
Numberofdefrostcycles0toFFFE
2cycles
0toFFFE(inhexadecimalnotation)(WhenmorethanFFinhex(255indecimal),thenumberisdisplayedinorderof163'sand162's,and161'sand160'splaces.(Example)When5000cycles;0.5s0.5s2s
C49
Theblacksquare( )indicatesaswitchposition.
DCbusvoltage300to750
300to750(Whenitis100Vormore,hundredsdigit,tensdigitandonesdigitaredisplayedbyturns.)
V1
ON
2 3 4 5 6
OCH582B
72
SW2setting Displaydetail Explanationfordisplay Unit
1
ON
2 3 4 5 6
%
Capacitysave0to100WhenairconditionerisconnectedtoM-NETandcapacitysavemodeisdemanded,avaluefrom“0”to“100”isdisplayed.Whenthereisnosettingofcapacitysave,“100”isdisplayed.
0to100(Whenthecapacityis100%hundredsdigit,tensdigitandonesdigitaredisplayedbyturns.)(Example)When100%;0.5s0.5s2s
Codedisplay
Errorpostponementcodehistory(2)ofoutdoorunit
PostponementcodedisplayBlinking:DuringpostponementLighting:Cancellationofpostponement“00”isdisplayedincaseofnopostponement.
Codedisplay
Errorpostponementcodehistory(3)ofoutdoorunit
PostponementcodedisplayBlinking:DuringpostponementLighting:Cancellationofpostponement“00”isdisplayedincaseofnopostponement.
Codedisplay
Errorhistory(3)(Oldest)Alternatedisplayofabnormalunitnum-berandcode.
Whennoerrorhistory,“0”and“––“aredisplayedbyturns.
3:Outdoorpipetemperature/Liquid(TH3)6:Outdoorpipetemperature/2-phase(TH6)7:OutdoorAmbienttemperature(TH7)8:OutdoorHeatsink(TH8)
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
Errorthermistordisplay
Whenthereisnoerrorthermistor,“–“isdisplayed. Code
display
Operationfrequencyonerroroccurring0to255
0to255(Whenitis100Hzormore,hundredsdigit,tensdigitandonesdigitaredisplayedbyturns.)(Example)When125Hz;0.5s0.5s2s
1
ON
2 3 4 5 6Hz
Fansteponerroroccurring0to10
0to10
1
ON
2 3 4 5 6Step
001
251
Theblacksquare( )indicatesaswitchposition.
:
Indoorroomtemperature(TH1)onerroroccurring8to39
8to39
1
ON
2 3 4 5 6
OCH582B
73
SW2setting Displaydetail Explanationfordisplay Unit
:
Indoorpipetemperature/Liquid(TH2)onerroroccurring−39to88
−39to88(Whenthetemperatureis0°Corless,“–”andtemperaturearedisplayedbyturns.)(Example)When−15°C;0.5s0.5s2s
Indoorpipetemperature/Cond./Eva.(TH5)onerroroccurring−39to88
−39to88(Whenthetemperatureis0°Corless,“–”andtemperaturearedisplayedbyturns.)(Example)When−15°C;0.5s0.5s2s
Outdoortemperature/2-phasepipe(TH6)onerroroccurring−39to88
−39to88(Whenthetemperatureis0°Corless,“–”andtemperaturearedisplayedbyturns.)(Example)When−15°C;0.5s0.5s2s
Outdoortemperature/Ambient(TH7)onerroroccurring−39to88
−39to88(Whenthetemperatureis0°Corless,“–”andtemperaturearedisplayedbyturns.)(Example)When−15°C;0.5s0.5s2s
Outdoortemperature/Heatsink(TH8)onerroroccurring−40to200
−40to200(Whenthetemperatureis0°Corless,“–”andtemperaturearedisplayedbyturns.)(Whenthetemperatureis100°Cormore,hundredsdigit,tensdigitandonesdigitaredisplayedbyturns.)
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
15
15
15
15
:
:
:
:
Theblacksquare( )indicatesaswitchposition.
:
0to255(Whenthetemperatureis100°Cormore,hundredsdigit,tensdigitandonesdigitaredisplayedbyturns.)(Example)When150°C;0.5s0.5s2s
SubcoolonerroroccurringSC0to130
Cooling=TH6−TH3Heating=TH5−TH2
0to130(Whenthetemperatureis100°Cormore,hundredsdigit,tensdigitandonesdigitaredisplayedbyturns.)(Example)When115°C;0.5s0.5s2s
5011
ON
2 3 4 5 6
DischargesuperheatonerroroccurringSHd0to255
Cooling=TH32−TH6Heating=TH32−TH5
1
ON
2 3 4 5 6
:
151
154
Thermo-ONtimeuntilerrorstops0to999
0to999(Whenitis100minutesormore,hundredsdigit,tensdigitandonesdigitaredisplayedbyturns.)(Example)When415minutes;0.5s0.5s2s1
ON
2 3 4 5 6 Minute
OCH582B
74
SW2setting Displaydetail Explanationfordisplay Unit
Indoorpipetemperature/Liquid(TH2(3))Indoor3−39to88
−39to88(Whenthetemperatureis0°Corless,“–”andtemperaturearedisplayedbyturns.)
Indoorpipetemperature/Cond./Eva.(TH5(3))Indoor3−39to88
−39to88(Whenthetemperatureis0°Corless,“–”andtemperaturearedisplayedbyturns.)
Whenthereisnoindoorunit,“00”isdisplayed.
:
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
:
Seconds
1
ON
2 3 4 5 6 Code
Theblacksquare( )indicatesaswitchposition.
Timetocurrentlimitactivatesfromcom-pressorturnsON.0to180
0to180
DetailedcodeofcheckcodeU9
NormalOvervoltage errorUndervoltage errorT open-phaseAbnormal power synchronous signalDefective power boardQ1 current, overvoltage
Description Display0001020408
10
Detected at—
Power boardPower board
Controller boardPower board
Power board
Controllingstatusofcompressoroperatingfrequency
1
ON
2 3 4 5 6 Codedisplay
Thefollowingcodewillbeahelptoknowtheoperatingstatusofunit.
Display Compressor operating frequency control
Display Compressor operating frequency control
Primary current controlSecondary current control
12
1
4
8
2
•The tens digit
•The ones digit (In this digit, the total number of activated control is displayed.)
Preventive control for excessive temp-erature rise of discharge temperaturePreventive control for excessive temp-erature rise of condensing temperatureFrosting preventing controlPreventive control for excessive temp-erature rise of heat sink
(Example)The following controls are activated.• Primary current control• Preventive control for excessive tempe- rature rise of condensing temperature• Preventive control for excessive tempe- rature rise of heat sink
1a
LED
OCH582B
75
11 FUNCTION SETTING
Function Settings Mode No. Setting No. : Initial setting (when sent from the factory) Remarks
Power failure automatic recoveryIndoor temperature detecting
LOSSNAY connectivity
Power supply voltageAuto operation mode
Frost prevention temperatureHumidifier control
Change of defrosting controlRefrigerant leakagesetting (%)
OFFONAverage data from each indoor unitData from the indoor unit with remote controllerData from main remote controller*Not supportedSupported (Indoor unit does not intake outdoor air through LOSSNAY)Supported (Indoor unit intakes outdoor air through LOSSNAY)240V220V, 230VSingle set pointDual set point2: (Normal)3:When the compressor operates, the humidifier also operates.When the fan operates, the humidifier also operates.StandardFor high humidity80%60%
12123123121212121212
01
02
03
04
06
15
16
17
21
The setting is applied to all the units in the same refrigerant system.
Meaning of "Function setting"mode02:indoor temperature detecting
No Indoor temperature(ta)=
No.1 Average data of the sensor on all the indoor units
Initialsetting
ta=(A+B)/2 ta=(A+B)/2 ta=A ta=A
No.2 The data of the sensoron the indoor unit thatconnectedwith remote controller
ta=A ta=B ta=A ta=A
No.3 The data of the sensoron main remote controller
ta=C ta=C ta=C ta=C
OUTDOOR
INDOOR
REMOTE(MAIN)
REMOTE(SUB)
INDOOR
OUTDOOR
INDOOR
REMOTE(MAIN)
REMOTE(SUB)
OUTDOOR
INDOOR
REMOTE(MAIN)
OUTDOOR
INDOOR
REMOTE(MAIN)
REMOTE(SUB)
INDOOR
11-1. UNIT FUNCTION SETTING BY THE REMOTE CONTROLLEREachfunctioncanbesetasnecessaryusingtheremotecontroller.Thesettingoffunctionforeachunitcanonlybedonebytheremotecontroller.Selectfunctionavailablefromthetable1.
<Table1>Functionselections(1)Functionsavailablewhensettingtheunitnumberto00(Select00referringto4settingtheindoorunitnumber.)
*Thefunctionisavailableonlywhenthewiredremotecontrollerisused.Thefunctionisnotavailableforfloorstandingmodels.
OCH582B
76
Floorstanding
PSA-KA
———————————————
Function Settings No.Mode
No.Setting
: Initial setting (Factory setting)- : Not available
4-Waycassette
Ceiling suspended Wall mounted
PLA-BA
Filter sign 100h 12500h 07 2No filter sign indicator 3
Air flow Quiet 1(Fan speed) Standard 08 2
High ceiling 3No.of air outlets 4 directions 1
3 directions 09 22 directions 3
Optional high efficiency Not supported 10 1filter Supported 2Vane setting No vanes (Vane No.3 setting : PLA only) 1
Vane No.1 setting 11 2Vane No.2 setting 3
Optional humidifier Not supported 13 1(PLA only) Supported 2Vane differential setting No.1 setting (TH5: 24–28°C) 1in heating mode No.2 setting (Standard, TH5:28–32°C) 14 2(cold wind prevention) No.3 setting (TH5: 32–38°C) 3Swing Not available Swing 23 1
Available Wave air flow 2Set temperature in heating Available 24 1mode (4 deg up) *
* PKA-HAL/KAL: 2 deg up
Not available 2Fan speed during the Extra low 1heating thermo OFF Stop 25 2
Set fan speed 3Fan speed during the Set fan speed 27 1cooling thermo OFF Stop 2Detection of abnormality of Available 28 1the pipe temperature (P8) Not available 2
}PLA-BA
PKA-HAL PKA-KAL
—
——————————
———————————
PSA-KA
———————————————
PCA-KAQ
———
——
Ceiling concealed
PEA-GA
—
—
—
—
—
—
—
—
—
——
—
(2)Functionsavailablewhensettingtheunitnumberto01–03orAL(07incaseofwirelessremotecontroller)•Whensettingfunctionsforanindoorunitinanindependentsystem,settheunitnumberto01referringto4settingtheindoorunitnumberofOperatingProcedure.
•Whensettingfunctionsforasimultaneous-TwinTripleindoorunitsystem,settheunitnumberto01to03foreachindoorunitincaseofselectingdifferentfunctionsforeachunitreferringto4settingtheindoorunitnumberofOperatingProcedure.
•WhensettingthesamefunctionsforanentiresimultaneousTwinTriple-indoorunitsystem,setrefrigerantaddresstoAL(07incaseofwirelessremotecontroller)referringto4settingtheindoorunitnumberofOperatingProcedure.
PEAD-RP•JA(L)Q
Function Settings No.Mode
No.Setting : Initial setting
(Factory setting)Filter sign 100h 1
2500h 07 2No filter sign indicator 3
External static pressure 35/50/70/100/150Pa 0810
12
Extra low
3
Fan speed during theheating thermo OFF Stop 25
1
Set fan speed2
27 12
Detection of abnormalityof the pipe
128 2
Set temperature in heating24mode (4 deg up)
Refer to the right tableExternal static pressure 35/50/70/100/150Pa Refer to the right table
AvailableNot available
Fan speed during thecooling thermo OFF
Set fan speedStopAvailableNot available
External static pressure
Setting No. Initial setting (Factory setting)
35Pa50Pa70Pa100Pa150Pa
23123
Mode No. 08 Mode No. 1011222
Mode No.11Setting No. Settings PLA-BA PCA-KAQ
1 No VanesVane No.3 setting
( Downward position than the standard )Less smudging No vane function
2 Vane No.1 setting Standard Standard3 Vane No.2 setting Less draft * (Upward position than the standard) Less draft * (Upward position than the standard)
* Be careful of the smudge on ceiling.
OCH582B
77
F1 F2 F3 F4
Main
Main display:Cursor Page
Main menuMaintenanceInitial settingService
F1 F2 F3 F4
Service menu
CursorSelect:
Enter maintenance password
unem ecivreS
unem ecivreS
rosruC
rosruC
:unem niaM
:unem niaM
Test runInput maintenance info.Function settingCheckSelf check
Maintenance passwordRemote controller check
Service menu
Service menu:
Not available.Please stop the unit.
2 WhentheServicemenuisselected,awindowwillappearaskingforthepass-word.
Toenter thecurrentmaintenancepassword(4numericaldigits),move thecursortothedigityouwanttochangewiththe F1 or F2 button.
Seteachnumber(0through9)withthe F3 or F4 button.
Then,pressthe button.
1 Select"Service"fromtheMainmenu,andpressthe button.
Atthemaindisplay,themenubuttonandselect"Service"tomakethemaintenancesetting.
Maintenance password is required
Note: The initial maintenance password is "9999". Change the default password as necessary to prevent unauthorized access. Have the password available for those who need it.
: If you forget your maintenance password, you can initialize the password to the default password "9999" by pressing and holding the F1 and F2 buttons simultaneously for three seconds on the maintenance password setting screen.
3 Ifthepasswordmatches,theServicemenuwillappear.
Thetypeofmenuthatappearsdependsontheconnectedindoorunits’type.
Note: Air conditioning units may need to be stopped to make certain set-tings. There may be some settings that cannot be made when the system is centrally controlled.
Ascreenwillappearthatindicatesthesettinghasbeensaved.
Navigating through the screens•TogobacktotheMainmenu.................. button
•Toreturntothepreviousscreen............... button
11-1-1. Selecting functions using the wired remote controller <PAR-30MAA> <PAR-31MAA>
<Service menu>
OCH582B
78
F1 F2 F3 F4
unem ecivreS
rosruC:unem niaM
Test runInput maintenance info.Function settingCheckSelf check
F1 F2 F3 F4
Function setting
Cursor AddressMonitor:
Ref. addressUnit No. Grp./1/2/3/4/All
F1 F2 F3 F4
Function setting
Cursor CursorRequest:
Ref. addressMode 1Mode 2Mode 3Mode 4
Grp.
F1 F2 F3 F4
Function setting
Cursor CursorRequest:
Ref. addressMode 1Mode 2Mode 3Mode 4
Grp.
2 Settheindoorunitrefrigerantaddressesandunitnumberswiththe F1through F4 buttons,andthenpressthe buttontoconfirmthecurrentsetting.
Select"Functionsetting"withthe F1 or F2 button,andpressthe button.
3 Whendatacollectionfromtheindoorunitsiscompleted,thecurrentsettingofthesystemappearshighlighted.
Non-highlighteditemsindicatethatnofunctionsettingsaremade.Screenappearancevariesdependingonthe"UnitNo."setting.
4 Usethe F1 or F2 button tomove thecursor toselect themodenumber,andchangethesettingnumberwiththe F3 or F4 button.
1 Select"Service"fromtheMainmenu,andpressthe button.
<Checking the indoor unit No.>Whenthe buttonispressed,thetargetindoorunitwillstartfanoperation.Iftheunitiscommonorwhenrunningallunits,allindoorunitsfortheselectedrefrigerantaddresswillstartfanoperation.
F1 F2 F3 F4
Function settingRef. address
Sending data
5 Whenthesettingsarecompleted,press the button tosend thesettingdatafromtheremotecontrollertotheindoorunits.Whenthetransmissionissuccessfullycompleted,thescreenwillreturntotheFunctionsettingscreen.
Note: • Make the above settings only on Mr. Slim units as necessary.• The above function settings are not available for the City Multi units.• Table 1 summarizes the setting options for each mode number. Refer to
the indoor unit Installation Manual for the detailed information about ini-tial settings, mode numbers, and setting numbers for the indoor units.
• Be sure to write down the settings for all functions if any of the initial settings has been changed after the completion of installation work.
<Function setting>
OCH582B
79
ON/OFF TEMP
FAN
VANEMODE
CHECK LOUVER
TEST RUN
AUTO STOP
AUTO START
h
min
CHECK
RESETSET CLOCK
Flow of function selection procedureThe flow of the function selection procedure is shown below. This example shows how to turn off the function that raises the set temperature by 4 degrees during HEAT operation. (Mode 24: 2) The procedure is given after the flow chart.
1 Check the function selection setting.
2 Switch to function selection mode. (Enter address "50" in check mode, then press the button.)
Check mode is the mode entered whenyou press the CHECK button twice to display"CHECK".
3 Specify unit No. "01" (since the function applies to unit 01). (Set address "01" while still in check mode, then press the button.)Note: You cannot specify the refrigerant address.
4 Select mode No. "24" (function that raises set temperature by 4 degrees during HEAT operation). (Set address "24" while still in check mode, then press the button.)
6
Finished
8 End function selection mode. (End check mode.)
YES
NO
Note: When you switch to function selection mode on the wireless remote controller's operation area, the unit ends function selection mode automatically if nothing is input for 10 minutes or longer.
5 Select setting No. "02" (OFF). (Set address "02" while still in check mode, then press the button.)
Change unit No.
YES
NO
7
h
min
h
h
[Flow of function selection procedure]
11-1-2. Selecting functions using the wireless remote controller (Type C)Functionscanbeselectedwiththewirelessremotecontroller.Functionselectionusingwirelessremotecontrollerisavailableonlyforrefriger-antsystemwithwirelessfunction.Refrigerantaddresscannotbespecifiedbythewirelessremotecontroller.
Bysettingunitnumberwiththebutton,specifiedindoorunitstartsperformingfanoperation.Detectwhichunitisassignedtowhichnumberusingthisfunction.IfunitnumberissettoAL,alltheindoorunitsinsamerefrigerantsystemstartperformingfanoperationsimultaneously.
[Operating instructions]1Checkthefunctionsettings.2Pressthebuttontwicecontinuously.→CHECKislitand“00”blinks. PresstheTEMPbuttononcetoset“50”.Directthewirelessremotecontrollertowardthereceiveroftheindoorunitandpress thebutton.3Settheunitnumber. PresstheTEMPbuttontosettheunitnumber.(Press“01”tospecifytheindoorunitwhoseunitnumberis01.) Directthewirelessremotecontrollertowardthereceiveroftheindoorunitandpressthebutton.
Notes: 1.Ifaunitnumberthatcannotberecognizedbytheunitisentered,3beepsof0.4secondswillbeheard.Reentertheunitnumbersetting. 2.Ifthesignalwasnotreceivedbythesensor,youwillnothearabeepora“doublebeep”maybeheard.Reentertheunitnumbersetting.4Selectamode. PresstheTEMPbuttontosetamode.Press“24”toturnonthefunctionthatraisesthesettemperatureby4degrees duringheatoperation.Directthewirelessremotecontrollertowardthesensoroftheindoorunitandpressthebutton. →Thesensor-operationindicatorwillflashandbeepswillbeheardtoindicatethecurrentsettingnumber. Currentsettingnumber: 1=1beep(1second) 2=2beeps(1secondeach) 3=3beeps(1secondeach) Notes: 1.Ifamodenumberthatcannotberecognizedbytheunitisentered,3beepsof0.4secondswillbeheard.Reenterthemodenumber. 2.Ifthesignalwasnotreceivedbythesensor,youwillnothearabeepora“doublebeep”maybeheard.Reenterthemodenumber.5Selectthesettingnumber. PresstheTEMPbuttontoselectthesettingnumber.(02:Notavailable) Directthewirelessremotecontrollertowardthereceiveroftheindoorunitandpressthebutton. →Thesensor-operationindicatorwillflashandbeepswillbeheardtoindicatethethesettingnumber. Settingnumber:1=2beeps(0.4secondseach) 2=2beeps(0.4secondseach,repeatedtwice) 3=2beeps(0.4secondseach,repeated3times) Notes: 1.Ifasettingnumberthatcannotberecognizedbytheunitisentered,thesettingwillturnbacktotheoriginalsetting. 2.Ifthesignalwasnotreceivedbythesensor,youwillnothearabeepora“doublebeep”maybeheard.Reenterthesettingnumber.6Repeatsteps4and5tomakeanadditionalsettingwithoutchangingunitnumber.7Repeatsteps3 to 5tochangeunitnumberandmakefunctionsettingsonit.8Completethefunctionsettings Press button.
Do not use the wireless remote controller for 30 seconds after completing the function setting.
h
CHECK
min
h
h
min
OCH582B
80
Functionbuttons
F1 F2 F3 F4
PresstoturnON/OFFtheindoorunit.
ON/OFF button
When the backlight is off, pressing any button turns the backlight on and does not perform its function. (except for the (ON/OFF) button)
Thefunctionsofthefunctionbuttonschangedependingonthescreen.RefertothebuttonfunctionguidethatappearsatthebottomoftheLCDforthefunctionstheyserveonagivenscreen.Whenthesystemiscentrallycontrolled,thebuttonfunctionguidethatcorrespondstothelockedbuttonwillnotappear.
Presstosavethesetting.
SELECT button
Presstoreturntothepreviousscreen.
RETURN button
PresstobringuptheMainmenu.
MENU button
Operationsettingswillappear.Whenthebacklight isoff,pressinganybuttonturnsthebacklightonanditwillstaylitforacertainperiodoftimedependingonthescreen.
Backlit LCD
Thislamplightsupingreenwhiletheunitisinoperation.Itblinkswhiletheremotecontrollerisstartinguporwhenthereisanerror.
ON/OFF lamp
Maindisplay :Presstochangetheoperationmode.Mainmenu :Presstomovethecursordown.
Function button F1
Maindisplay :Presstodecreasetemperature.Mainmenu :Presstomovethecursorup.
Function button F2
Maindisplay :Presstoincreasetemperature.Mainmenu :Presstogotothepreviouspage.
Function button F3
Maindisplay :Presstochangethefanspeed.Mainmenu :Presstogotothenextpage.
Function button F4
Fri
Room
Set temp.
Mode Temp. Fan
Cool Auto
Main
Main display:Cursor Page
Main menuVane·Louver·Vent. (Lossnay)High powerTimerWeekly timerOU silent mode
<Main display> <Main menu>
Functionguide
11-2. FUNCTION SELECTION OF REMOTE CONTROLLER11-2-1. PAR-30MAA/PAR-31MAA
OCH582B
81
Menu structure <PAR-30MAA><PAR-31MAA>
Not all functions are available on all models of indoor units.
Energy saving
Auto returnSchedule
Night setback
Main menuPress the MENU button.Move the cursor to the desired item with the F1 and F2 buttons, and press the SELECT button.
Vane · Louver · Vent. (Lossnay)
High power
Weekly timer
Restriction
Maintenance
Initial setting
ON/OFF timerAuto-Off timer
Temp. rangeOperation lock
Manual vane angle
Main/Sub
Timer
Main display
Contrast
Display details
Auto mode
Administrator password
Language selection
Service
Input maintenance info.
Function settingLossnay (City Multi only)
CheckSelf checkMaintenance password
Remote controller check
Test run
Clock
Auto descending panel
Filter Information
Error Information
OCH582B
82
Main menu list <PAR-30MAA><PAR-31MAA>
Setting and display items Setting detailsVane · Louver · Vent. (Lossnay) Use to set the vane angle.
•Selectadesiredvanesettingfromfivedifferentsettings.Use to turn ON/OFF the louver.•Selectadesiredsettingfrom"ON"and"OFF."Use to set the amount of ventilation.•Selectadesiredsettingfrom"Off,""Low,"and"High."
High power Use to reach the comfortable room temperature quickly.•UnitscanbeoperatedintheHigh-powermodeforupto30minutes.
Timer ON/OFF timer* Use to set the operation ON/OFF times.•Timecanbesetin5-minuteincrements.
Auto-Off timer Use to set the Auto-Off time.•Timecanbesettoavaluefrom30to240in10-minuteincrements.
Weekly timer* Use to set the weekly operation ON/OFF times.•Upto8operationpatternscanbesetforeachday.(NotvalidwhentheON/OFFtimerisenabled.)
Restriction Temp. range Use to restrict the preset temperature range.•Differenttemperaturerangescanbesetfordifferentoperationmodes.
Operation lock Use to lock selected functions.•Thelockedfunctionscannotbeoperated.
Energy saving Auto return Use to get the units to operate at the preset temperature after performing energy-save operation for a specified time period.•Timecanbesettoavaluefrom30and120in10-minuteincrements.(Thisfunctionwillnotbevalidwhenthepresettemperaturerangesarerestricted.)
Schedule* Set the start/stop times to operate the units in the energy-save mode for each day of the week, and set the energy-saving rate.•Upto4energy-saveoperationpatternscanbesetforeachday.•Timecanbesetin5-minuteincrements.•Energy-savingratecanbesettoavaluefrom0%or50to90%in10%increments.
Night setback* Use to make Night setback settings.•Select"Yes"toenablethesetting,and"No"todisablethesetting.Thetemperaturerangeandthestart/stoptimescanbeset.
Filter information Use to check the filter status.•Thefiltersigncanbereset.
Error information Use to check error information when an error occurs.•Checkcode,errorsource,refrigerantaddress,unitmodel,manufacturingnumber,contactinformation(dealer'sphonenumber)canbedisplayed.(Theunitmodel,manufacturingnumber,andcontactinformationneedtoberegisteredinadvancetobedisplayed.)
Maintenance Auto descending panel Auto descending panel (Optional parts) Up/Down you can do.
Manual vane angle Use to set the vane angle for each vane to a fixed position.
Initial setting Main/Sub When connecting two remote controllers, one of them needs to be designated as a sub controller.
Clock Use to set the current time.
Main display Use to switch between "Full" and "Basic" modes for the Main display.•Theinitialsettingis"Full."
Contrast Use to adjust screen contrast.
Display details Make the settings for the remote controller related items as necessary.Clock: Theinitialsettingsare"Yes"and"24h"format.Temperature: SeteitherCelsius(°C)orFahrenheit(°F).Room temp. : SetShoworHide.Auto mode: SettheAutomodedisplayorOnlyAutodisplay.
Auto mode Whether or not to use the Auto mode can be selected by using the button.This setting is valid only when indoor units with the Auto mode function are connected.
Administrator password The administrator password is required to make the settings for the following items.•Timersetting•Energy-savesetting•Weeklytimersetting•Restrictionsetting•Outdoorunitsilentmodesetting•Nightsetback
Language selection Use to select the desired language.Service Test run Select "Test run" from the Service menu to bring up the Test run menu.
•Testrun•DrainpumptestrunInput maintenance Select "Input maintenance Info." from the Service menu to bring up the Maintenance information screen.
The following settings can be made from the Maintenance Information screen.•Modelnameinput•SerialNo.input•Dealerinformationinput
Function setting Make the settings for the indoor unit functions via the remote controller as necessary.Check Error history: Displaytheerrorhistoryandexecute“deleteerrorhistory”.
Refrigerant leak check: Refrigerantleakscanbejudged.Smooth maintenance: Theindoorandoutdoormaintenancedatacanbedisplayed.Request code: Detailsoftheoperationdataincludingeachthermistortemperatureanderrorhistorycanbechecked.
Self check Error history of each unit can be checked via the remote controller.Maintenance password Use to change the maintenance password.Remote controller check When the remote controller does not work properly, use the remote controller checking function to trouble-
shoot the problem.
Main menu list
*Clocksettingisrequired.
OCH582B
83
12 MONITORING THE OPERATION DATA BY THE REMOTE CONTROLLER
Detailsontheoperationdataincludingeachthermistortemperatureanderrorhistorycanbeconfirmedwiththeremotecontroller.
F1 F2 F3 F4
Check menu
CursorService menu:
Error historyRefrigerant volume checkRefrigerant leak checkSmooth maintenanceRequest code
Select"Requestcode"withthe F1 or F2 button,andpressthe button.
Select"Check"withthe F1 or F2 button,andpressthe button.
2 SettheRefrigerantaddressandRequestcode.
Selecttheitemtobechangedwiththe F1 or F2 button.
Selecttherequiredsettingwiththe F3 or F4 button.
■<Ref.address>setting[0]–[15]■<Requestcode>setting
Pressthe button,Datawillbecollectedanddisplayed.
F1 F2 F3 F4
Request code
Request:
Request:
Request code
Ref.addressRequest code
Cursor - +
Ref.addressRequest code
Cursor - +
Request code: 004Discharge temperature: 69˚C
1 Select"Service"fromtheMainmenu,andpressthe button.
12-1. HOW TO "MONITOR THE OPERATION DATA"12-1-1. PAR-30MAA/PAR-31MAA
OCH582B
84
Certain indoor/outdoor combinations do not have the request code function; therefore, no request codes are displayed.
Req
uest
cod
e
Request contentDescription
(Display range)Unit Remarks
0123456789101112131415161718
19
20
2122232425262728293031
32
33
34
35
3637383940414243444546474849
Operation stateCompressor-Operating current (rms)Compressor-Accumulated operating timeCompressor-Number of operation timesComp. surface temperature (TH32)Outdoor unit -Liquid pipe 1 temperature (TH3)
Outdoor unit-2-phase pipe temperature (TH6)
Outdoor unit-Outside air temperature (TH7)Outdoor unit-Heat sink temperature (TH8)
Discharge superheat (SHd)Sub-cool (SC)
Compressor-Operating frequencyCompressor-Target operating frequencyOutdoor unit-Fan output stepOutdoor unit-Fan 1 speed(Only for air conditioners with DC fan motor)Outdoor unit-Fan 2 speed(Only for air conditioners with DC fan motor)
LEV (A) opening
Primary currentDC bus voltage
Number of connected indoor unitsIndoor unit-Setting temperatureIndoor unit-Intake air temperature <Measured by thermostat>Indoor unit-Intake air temperature (Unit No. 1)<Heat mode-4-deg correction>Indoor unit-Intake air temperature (Unit No. 2)<Heat mode-4-deg correction>Indoor unit-Intake air temperature (Unit No. 3)<Heat mode-4-deg correction>Indoor unit-Intake air temperature (Unit No. 4)<Heat mode-4-deg correction>
Indoor unit -Liquid pipe temperature (Unit No. 1)Indoor unit -Liquid pipe temperature (Unit No. 2)Indoor unit -Liquid pipe temperature (Unit No. 3)Indoor unit -Liquid pipe temperature (Unit No. 4)
Indoor unit-Cond./Eva. pipe temperature (Unit No. 1)Indoor unit-Cond./Eva. pipe temperature (Unit No. 2)Indoor unit-Cond./Eva. pipe temperature (Unit No. 3)Indoor unit-Cond./Eva. pipe temperature (Unit No. 4)
Thermostat ON operating timeTest run elapsed time
Refer to 12-2-1. Detail Contents in Request Code.0–50 0–9999 0–9999 3–217 −40–90
−39–88
−39–88 −40–200
0–255 0–130
0–255 0–255 0–10
0–9999
0–9999
0–500
0–50
0–4 17–30 8–39 8–39
8–39
8–39
8–39
−39–88 −39–88 −39–88 −39–88
−39–88 −39–88 −39–88 −39–88
0–999 0–120
180–370
–A
10 hours100 times:
:
:
:
:
:
:
HzHz
Step
rpm
rpm
Pulses
AV
Units:
:
:
:
:
:
:
:
:
:
:
:
:
:
MinutesMinutes
"0" is displayed if the air conditioner is a single-fantype.
"0" is displayed if the target unit is not present.
"0" is displayed if the target unit is not present.
"0" is displayed if the target unit is not present.
Not possible to activate maintenance mode during the test run.
12-2. Request code list
OCH582B
85
Req
uest
cod
e
Request contentDescription
(Display range)Unit Remarks
50515253545556575859606162636465666768697071727374757677787980818283
84
85868788
89
90
91
9293949596979899
100
101
102
Indoor unit-Control stateOutdoor unit-Control stateCompressor-Frequency control stateOutdoor unit-Fan control stateActuator output stateError content (U9)
Signal transmission demand capacityContact demand capacityExternal input state (silent mode, etc.)
Outdoor unit-Capacity setting displayOutdoor unit-Setting information
M-NET adapter connection (presence/absence)
Display of execution of replace/wash operation
Outdoor unit-Microprocessor version information
Outdoor unit-Microprocessor version information (sub No.)
Outdoor unit - Error postponement history 1 (latest)
Outdoor unit - Error postponement history 2 (previous)
Outdoor unit - Error postponement history 3 (last but one)
0–255
"0000": Not connected
Examples) Ver 5.01 →Auxiliary information (displayed afterversion information)Examples) Ver 5.01 A000 →
Displays postponement code. (" - - " isdisplayed if no postponement code is present)Displays postponement code. (" - - " isdisplayed if no postponement code is present)Displays postponement code. (" - - " isdisplayed if no postponement code is present)
––––––
%––
––
–
–
Ver
–
Code
Code
Code
Refer to 12-2-1.Detail Contents in Request Code.
Refer to 12-2-1.Detail Contents in Request Code.Refer to 12-2-1.Detail Contents in Request Code.
Refer to 12-2-1.Detail Contents in Request Code.
Refer to 12-2-1.Detail Contents in Request Code.
Refer to 12-2-1.Detail Contents in Request Code.
Refer to 12-2-1.Detail Contents in Request Code.
Refer to 12-2-1.Detail Contents in Request Code.
Refer to 12-2-1.Detail Contents in Request Code.
Refer to 12-2-1.Detail Contents in Request Code.
"0001": Connected
"0000": Not washed"0001": Washed
"0501"
"A000"
OCH582B
86
Req
uest
cod
e
Request contentDescription
(Display range)Unit Remarks
103104105
106
107108109110111112113114115116117118119120
121
122
123
124125126127128129130131
132
133
134
135136137138139140~
146147148149150151152
Displays error history. (" --" is displayed if no history is present.)Displays error history. (" --" is displayed if no history is present.)Displays error history. (" --" is displayed if no history is present.)
: TH36 : TH67 : TH78 : TH80 : No thermistor error
Displayed in the same way as request code "0".0–50 0–9999 0–9999 3–217 −40–90
−40–200
−39–88
−39–88
0–255 0–130 0–255
0–10
0–9999
0–9999
0–500
0–999
−39–88
−39–88
−39–88
−39–88 −39–88 −39–88
CodeCodeCode
Sensornumber
–A
10 hours100 times:
:
:
:
:
:
:
Hz
Step
rpm
rpm
Pulses
Minutes
:
:
:
:
:
:
"0" is displayed if the air conditioner is a single-fan type.
Average value of all indoor units is displayed if the air condi-tioner consists of 2 or more indoor units (twin, triple, quad).Average value of all indoor units is displayed if the air condi-tioner consists of 2 or more indoor units (twin, triple, quad).
Error history 1 (latest)Error history 2 (second to last)Error history 3 (third to last)
Abnormal thermistor display(TH3/TH6/TH7/TH8)
Operation mode at time of errorCompressor-Operating current at time of errorCompressor-Accumulated operating time at time of errorCompressor-Number of operation times at time of errorComp. surface temperature (TH32) at time of errorOutdoor unit -Liquid pipe 1 temperature (TH3) at time of error
Outdoor unit-2-phase pipe temperature (TH6) at time of error
Outdoor unit-Outside air temperature (TH7) at time of errorOutdoor unit-Heat sink temperature (TH8) at time of errorDischarge superheat (SHd) at time of errorSub-cool (SC) at time of errorCompressor-Operating frequency at time of errorOutdoor unit at time of error• Fan output stepOutdoor unit at time of error• Fan 1 speed (Only for air conditioners with DC fan)Outdoor unit at time of error• Fan 2 speed (Only for air conditioners with DC fan)
LEV (A) opening at time of error
Thermostat ON time until operation stops due to error
Indoor -Liquid pipe temperature at time of error
Indoor -Cond/Eva. pipe temperature at time of error
Indoor at time of error• Intake air temperature <Thermostat judge temperature>
Indoor -Actual intake air temperatureIndoor -Liquid pipe temperatureIndoor -Cond/Eva. pipe temperature
3
OCH582B
87
Req
uest
cod
e
Request contentDescription
(Display range)Unit Remarks
153
154
155
156157
158
159160161162163164165166167~
189190191
192~
764765766
767
0–9999
0–9999
0–255 Fan control data
00 **" "**" indicates fan control data.
"00 **" "**" indicates fan control data.
Refer to 12-2-1. Detail Contents in Request Code.UndefinedRefer to 12-2-1. Detail Contents in Request Code.
Undefined
Examples) Ver 5.01 → "0501"Auxiliary information (displayed after version information)Examples) Ver 5.01 A000 → "A000"
1 hour
10 hours
–
–
–
–––––
Ver
–
For indoor fan phase control
For indoor fan pulsation control
For indoor DC brushless motor control
Indoor-Fan operating time(After filter is reset)Indoor-Total operating time(Fan motor ON time)
Indoor fan output value (Sj value)Indoor fan output value(Pulsation ON/OFF)Indoor fan output value (duty value)
Indoor unit-Model setting informationIndoor unit-Capacity setting informationIndoor unit-SW3 informationWireless pair No. (indoor control board side) settingIndoor unit-SW5 information
Indoor unit-Microprocessor version informationIndoor unit-Microprocessor version information (sub No.)
Stable operation (Heat mode)Stable operation (Cool mode)
Stable operation cancellation
This request code is not provided to collect data. It is used to fix the operation state.This request code is not provided to collect data. It is used to fix the operation state.This request code is not provided to collect data. It is used to cancel the operation state that has beenfixed by request codes "765" and "766".
"
Refer to 12-2-1. Detail Contents in Request Code.
OCH582B
88
Frequency control state 2
Display Discharge temperature Condensation temperature Anti-freeze Heat sink temperatureoverheat prevention overheat prevention protection control overheat prevention
01 Controlled2 Controlled3 Controlled Controlled4 Controlled5 Controlled Controlled6 Controlled Controlled7 Controlled Controlled Controlled8 Controlled9 Controlled ControlledA Controlled Controlledb Controlled Controlled ControlledC Controlled Controlledd Controlled Controlled ControlledE Controlled Controlled ControlledF Controlled Controlled Controlled Controlled
[Operation state] (Request code :" 0")
Data display
C 4Relay output stateOperation mode
[Indoor unit – Control state] (Request code :"50 ")
Data display
Operation mode
Display Operation mode0 STOP • FANC COOL • DRYH HEATd DEFROST
Relay output state
Display Power currently Compressor Four-way valve Solenoid valvesupplied to compressor
Unit No. 4 stateUnit No. 3 state
Unit No. 2 state
Unit No. 1 state
Display State0 Normal1 Preparing for heat operation2 –3 –4 Heater is ON.5 Anti-freeze protection is ON.6 Overheat protection is ON.7 Requesting compressor to turn OFFF There are no corresponding units.
[Outdoor unit – Control state] (Request code :" 51")
Data display State0 0 0 0 Normal0 0 0 1 Preparing for heat operation0 0 0 2 Defrost
[Compressor – Frequency control state] (Request code :" 52")
Data display
0 0Frequency control state 2
Frequency control state 1
Frequency control state 1
Display Current limit control0 No current limit1 Primary current limit control is ON.2 Secondary current limit control is ON.
–
ONON
012345678A
–
ONONONON
–
ONON
ONON
ON
–ON
ON
ON
ON
12-2-1. Detail Contents in Request Code
OCH582B
89
[Fan control state] (Request code :"53")
Data display
Fan step correction value by heat sink temperature overheat prevention controlFan step correction value by cool condensation temperature overheat prevention control
0 0
Display Correction value− (minus) − 1
0 0
2
[Actuator output state] (Request code :"54")
Data displayActuator output state 1Actuator output state 2
0 0
Actuator output state 1
Display SV1 Four-way valve Compressor
0123456789AbCdEF
ON
ON
ON
ON
ON
ON
ON
ON
ONON
ONON
ONON
ONON
ONONONON
ONONONON
ONONONONONONONON
Actuator output state 2
Display 52C SV2 SS
01234567
ON
ON
ON
ON
ONON
ONON
ONONONON
[Error content (U9)] (Request code :"55")
Data display
Error content 1Error content 2
0 0
Error content 1 : Detected
Display Overvoltage Undervoltage L1-phase Power synchronizingerror error open error signal error
0123456789AbCdEF
Error content 2 : Detected
Display Converter Fo PAM errorerror
0123
Compressor iswarming up
1 +1+2
OCH582B
90
[Contact demand capacity] (Request code : " 61")
Data display 0 0 0Setting content
[External input state] (Request code : "62")
Data display 0 0 0Input state
Input state : Input present
Display Contact demand Silent mode Spare 1 Spare 2input input input input
0123456789AbCdEF
[Outdoor unit -– Capacity setting display] (Request code : "70")
Data display Capacity
10 50 9 35
11 6014 7120 10025 12528 14040 20050 250
[Outdoor unit – Setting information] (Request code : "71")
Data displaySetting information 1Setting information 2
0 0Setting information 1
Display Defrost mode0 Standard1 For high humidity
Setting information 2
Display Single-/ Heat pump/3-phase cooling only
0 Single-phase Heat pump1 Cooling only2 3-phase Heat pump3 Cooling only
Setting content
Display Setting value
01 50%2 75%
0%
3 100%
OCH582B
91
[Indoor unit – Model setting information] (Request code : "162" )
Data display
0 0
See the table on the right.
[Indoor unit – Capacity setting information] (Request code : "163")
Data display
0 0
See the table on the right.
Display Capacity setting state Display Capacity setting state
00 12 10 11201 16 11 12502 22 12 14003 25 13 16004 28 14 20005 32 15 22406 35, 36 16 25007 40 17 28008 45 1809 50 190A 56 1A0b 63 1b0C 71 1C0d 80 1d0E 90 1E0F 100 1F
Display Pair No. setting state
00 No. 001 No. 1 J41 disconnected02 No. 2 J42 disconnected03 No. 3 J41, J42 disconnected
[Wireless pair No. (indoor control board side) setting] (Request code :" 165")
Data display
0 0
See the table on the right.
Display Model setting state Display Model setting state
00 2001 2102 2203 2304 2405 2506 2607 2708 2809 290A 2A0b 2b0C 2C0d 2d0E 2E0F 2F10 3011
PEA-RP200/250GAQ
3112 3213 3314 3415 3516 3617 3718 3819 391A 3A1b 3b1C 3C1d 3d1E 3E1F 3F
Display Model setting state
A0A1
PCA-RP•KAQ
A2A3A4A5A6A7A8A9AAAbACAdAEAFB0B1
PKA-RP•HAL/KALPEAD-RP•JA(L)Q
B2B3B4B5B6B7B8B9BABBBCBDBEBF
PLA-RP•BA
PSA-RP•KA
OCH582B
92
13-1. SMOOTH MAINTENANCE13-1-1. PAR-30MAA/PAR-31MAA
Maintenancedata,suchasthe indoor/outdoorunit’sheatexchangertemperatureandcompressoroperationcurrentcanbedisplayedwith“Smoothmaintenance”.This cannot be executed during test operation.Depending on the combination with the outdoor unit, this may not be supported by some models.
F1 F2 F3 F4
Check menu
CursorService menu:
Error historyRefrigerant volume checkRefrigerant leak checkSmooth maintenanceRequest code
Smooth maintenance
Begin:
Smooth maintenance
Exit:
Ref.addressStable mode
Cursor -Address+
Ref.addressStable mode
Stabilization→Collecting
Cool / Heat/ Normal
Cool / Heat/ Normal
Select "Smoothmaintenance"with the F1 or F2 button,andpress thebutton.
Select"Check"withthe F1 or F2 button,andpressthe button.
Select"Service"fromtheMainmenu,andpressthe button.
Seteachitem.
Selecttheitemtobechangedwiththe F1 or F2 button.
Selecttherequiredsettingwiththe F3 or F4 button.
■<Ref.address>setting[0]−[15]■<Stablemode>setting[Cool]/[Heat]/[Normal]
Pressthe button,Fixedoperationwillstart.Stablemodewilltakeapprox.20minutes.
1
2
13 EASY MAINTENANCE FUNCTION
Smooth maintenance
Return:Page
Ref.address CoolSub coolOU TH4 temp.OU TH6 temp.OU TH7 temp.
● Reduces maintenance work drastically. ● Enables you to check operation data of the indoor and outdoor units by remote controller.
Furthermore, use of maintenance stable-operation control that fixes the operating frequency, allows smooth inspection, even forinverter models.
Remove theservice panel.
Measurethe intake airtemperature.
Measure the dischargetemperature.
Measure the outside air temperature.
●Indoor unit ●●Outdoor unit ●
Smooth Mainte-nance Function ● Conventional inspection work
Easy maintenance information (unit)Compressor Outdoor unit Indoor unit
Accumulated operating Heat exchanger7
Intake airtime (o10 hours) temperature (:) temperature (:)Number of ON/OFF Discharge
8
4
5
1
2
963
Heat exchangertimes (o10 times) temperature (:) temperature (:)Operating Outside air Filter operatingcurrent (A) temperature (:) time* (Hours)
* The filter operating time is the time that has elapsed since the filter was reset.
Discharge temperature 60°C
ContinuetothenextpageOCH582B
93
Smooth maintenance
Return:
Smooth maintenance
Return:
Smooth maintenance
Return:
Page
Page
Page
COMP. currentCOMP. run timeCOMP. On / OffCOMP. frequency
A
Hz
Hrtimes
Hr
Ref. address Cool
Ref.address Cool
Ref.address Cool
Sub coolOU TH4 temp.OU TH6 temp.OU TH7 temp.
IU air temp.IU HEX temp.IU filter time
TheCompressor-Accumulatedoperating(COMP.run) time is10-hourunit,andtheCompressor-Numberofoperationtimes(COMP.ON/OFF) isa100-timeunit(fractionsdiscarded).
Navigating through the screens•TogobacktotheMainmenu.......... button
•Toreturntothepreviousscreen....... button
3Theoperationdatawillappear.
[1:1]Refrigerantaddress=00
[Twin]Refrigerantaddress=00
Outdoorunit
Indoor unit02
Indoor unit01
Outdoorunit
Remotecontroller
Remotecontroller
Indoor unit01
■ Refrigerant addressSingle refrigerant systemIn the case of single refrigerant system, the refrigerant addressis "00" and no operation is required.Simultaneous twin, triple units belong to this category(single refrigerant system).
Multi refrigerant system (group control)Up to 16 refrigerant systems (16 outdoor units) can be con-nected as a group by 1 remote controller. To check or set therefrigerant addresses.
Refrigerantaddress00
Refrigerantaddress01
Refrigerantaddress02
Refrigerantaddress15
Outdoorunit
Indoor unit01
Outdoorunit
Indoor unit01
Outdoorunit
Indoor unit01
Outdoorunit
Indoor unit01
Remotecontroller
OCH582B
94
<Guide for operation condition>Inspection item Result
Pow
er s
uppl
y
Loos
e co
n-ne
ctio
n
Breaker Good RetightenedTerminal block Outdoor Unit Good Retightened
Indoor Unit Good Retightened(Insulation resistance) M"(Voltage) V1 Accumulated operating time Time2 Number of ON/OFF times Times3 Current A4 Refrigerant/heat exchanger temperature COOL : HEAT :5 Refrigerant/discharge temperature COOL : HEAT :6 Air/outside air temperature COOL : HEAT : (Air/discharge temperature) COOL : HEAT :Appearance Good Cleaning requiredHeat exchanger Good Cleaning requiredSound/vibration None Present
Air/intake air temperature COOL : HEAT : (Air/discharge temperature) COOL : HEAT :8
7
9
Refrigerant/heat exchanger temperature COOL : HEAT :Filter operating time* Time
Decorative panel Good Cleaning requiredFilter Good Cleaning requiredFan Good Cleaning requiredHeat exchanger Good Cleaning requiredSound/vibration None Present
Com-pressor
Tem
pera
ture
Cle
anli-
ness
Out
door
Uni
t
Tem
pera
ture
Cle
anlin
ess
Indo
or U
nit
* The filter operating time is the time that has elapsed since the filter was reset.
Check PointsEnter the temperature differences between 5 , 4 , 7 and 8 intothe graph given below.Operation state is determined according to the plotted areas onthe graph.For data measurements, set the fan speed to "Hi" before activat-ing maintenance mode.
Is "D000" displayed stably on the remotecontroller?(5 Discharge temperature) – (4 Outdoorheat exchanger temperature)(7 Indoor intake air temperature) – (8Indoor heat exchanger temperature)Is "D000" displayed stably on the remotecontroller?(5 Discharge temperature) – (8 Indoorheat exchanger temperature)(8 Indoor heat exchanger temperature) –(7 Indoor intake air temperature)
Coo
l
Classification Item Result
Inspection
Temperaturedifference
Hea
tInspection
Temperaturedifference
Stable Unstable
:
:
Stable Unstable
:
:
Notes:Fixed Hz operation may not be possible under the following tempera-ture ranges.A)In cool mode, outdoor intake air temperature is 40 :or higher or
indoor intake air temperature is 23 : or lower.B)In heat mode, outdoor intake air temperature is 20 : or higher or
indoor intake air temperature is 25 : or lower.
1.
If the air conditioner is operated at a temperature range other than theones above but operation is not stabilized after 30 minutes or more haveelapsed, carry out inspection.
3. In heat mode, the operation state may vary due to frost forming on theoutdoor heat exchanger.
:45
40
35
30
25
20
15
10
5
0 10 20 30 40 50 60 70 80
NormalFilter inspection
Inspection C
Inspection A
Inspection B
:45
40
35
30
25
20
15
10
5
0 10 20 30 40 50 60 70 80 ::
Normal
Filter inspectionInspection C
Inspection A
Inspection B
Cool mode Heat mode
( 7 In
door
inta
ke a
ir te
mpe
ratu
re)—
( 8In
door
heat
exc
hang
er te
mpe
ratu
re)
( 8 In
door
hea
t exc
hang
er te
mpe
ratu
re) —
( 7 In
door
inta
ke a
ir te
mpe
ratu
re)
[5 Discharge temperature] – [4 Outdoorheat exchanger temperature)
[5 Discharge temperature] – [8 Indoorheat exchanger temperature)
Res
ult
Normal operation stateFilter may be clogged.*Performance has dropped. Detailed in-spection is necessary.Refrigerant amount is dropping.Filter or indoor heat exchanger may beclogged.
Area Check itemJudgement
Cool Heat
NormalFilter inspectionInspection A
Inspection BInspection C
Note: The above judgement is just guide based on Japanese standardconditions.It may be changed depending on the indoor and outdoor temperature.
* It may be judged as "Filter inspection" due to the outdoor and indoor temperature, even though it is not clogged.
2.
OCH582B
Coverpanel(rear)
Coverpanel(front)
OPERATING PROCEDURE PHOTOS
95
14 DISASSEMBLY PROCEDURE
1. Removing the service panel and top panel (1)Removetheservicepanelfixingscrews(4forfront/5x
12),thenslidetheservicepaneldownwardtoremoveit. (Theservicepanelisfixedtothesidepanel(R)witha
hookontherightside.) (2)Removethetoppanelfixingscrews(3forfrontand3for
rear/5x12)toremovethetoppanel.
Note: When removing service panel and top panel at the same time, count one less screw since they share a screw.
2. Removing the fan motor (MF1, MF2) (1)Removetheservicepanel.(SeePhoto1)
(2)Removethewiregrillefixingscrews(4forfront/5x12),thenslidethewiregrilleupwardtoremoveit.(SeePhoto1)
(Fortheeachfanmotorontopandunder)(3)Removethescrewofnut(1forfront/M6),thenslidethe
propellerfanforwardtoremoveit. (Fortheeachfanmotorontopandunder)(4)Disconnecttheconnectors,CNF1(WHT)andCNF2(WHT)onthecontrollercircuitboardintheelectricalpartsbox.(SeePhoto4)
(5)Loosentheclampfortheleadwireonmotorsupportandseparator.
(6)Releasetheleadwirefromtheholeonseparator. (7)Removethefanmotorfixingscrews(4forfront/5x20)to
removethefanmotor.(Fortheeachfanmotorontopandunder)
Photo 2
Photo 3
Photo 1
ToppanelfixingscrewsToppanel
Servicepanelfixingscrews
ServicepanelWiregrillefixingscrews
Wiregrillefixingscrews
Slide
PUHZ-P200YKA.UK PUHZ-P250YKA.UKPUHZ-P200YKAR1.UK PUHZ-P250YKAR1.UK
Coverpanel(front)fixingscrews
Fanmotorfixingscrews
Fanmotor
Fanmotorfixingscrews
Frontpanel
Propeller
Nut
Sidepanel(R)
OCH582B
OPERATING PROCEDURE PHOTOS
96
3. Removing the electrical parts box (1)Removetheservicepanel.(SeePhoto1) (2)Removethetoppanel.(SeePhoto1) (3)Disconnectthepowersupplycablefromterminalblock. (4)Disconnecttheindoor/outdoorconnectingwirefrom
terminalblock. (5)DisconnecttheconnectorCNF1(WHT),CNF2(WHT),
TH3(WHT),TH7/6(RED),TH32(BLK),63H(YLW),21S4(GRN),LEV-A(WHT)fromthecontrollercircuitboard.<Symbolsontheboard>•Fanmotor(CNF1,CNF2)•Thermistor<Liquid>(TH3)•Thermistor<Ambient/2-PhasePipe>(TH7/6)•Thermistor<Comp.Surface>(TH32)•Highpressureswitch(63H)•4-wayvalve(21S4)•LEV(LEV-A)
(6)Loosentheclamps,fastenersandcablestrapforthelead wireintheelectricalpartsboxandseparator.(7)Loosentheleadwiresfixedtothepipeswithbands.(8)TodisconnecttheCOMPleadwire,removetheterminal
cover,thenremovetheCOMPleadwirefixingscrews(4forfront/5x12).
(9)Removetheelectricalpartsboxfixingscrews(2forfront/4x10),thenslidetheelectricalpartsboxupwardtoremoveit.
(Theelectricalpartsboxisfixedtothesidepanel(R)withahookontherightside,andtotheseparatorductwithahookontheleftside.)
Photo 4 Electricalpartsbox
Electricalpartsboxfixingscrews
Controllercircuitboard
Valvebed
Terminalcover
Compressor
Sidepanel(R)
Terminalblock(Indoor/Outdoor)Terminalblock
(Powersupply)
Valvebedfixingscrew
Valvebedfixingscrews
OCH582B
PHOTOS 4. Disassembling the electrical parts box
(1)Disconnectalltheconnectorsonthecontrollercircuitboard.(2)Toremovethecontrollercircuitboard,releaseitfromthe
support.(3)Removecontbasefixingscrews(2forfront/4x10).(Photo5)
(Thecont.baseisfixedtothecontbasepiecewithahookontheleftside.)
(4)Disconnectalltheconnectorsonthenoisefiltercircuitboard.(Photo6)
(5)Toremovethenoisefiltercircuitboard,releaseitfromthesupport.(6)RemoveN.F.basefixingscrews(2forfront/4x10).(Photo7)(7)Disconnectalltheconnectorsonthepowercircuitboard.(8)Toremovethepowercircuitboard,removepowerboardfixing
screws(4forfront/4x12),thenreleasetheboardfromthesupport.(Photo8)
(9)Thereactorisattachedtotherearsideoftheelectricalpartsbox.(Photo9)(Toremovethereactor,theelectricalpartsboxmustbeseparatedfromtheoutdoorunit.)
Note: When reassembling the electrical parts box, make sure the wirings are correct.
Photo 5
Photo 6
Photo 8
Photo 7
Photo 9
Controllercircuitboard(C.B.)
Screw
Screw
Screws
Screws Screws
Screws
Screw
Noisefilterbase
Reactor
Contbase
Powercircuitboard(P.B)
OPERATING PROCEDURE
Noisefiltercircuitboard(N.F.)
Screw
97
Photo 10
Electricalpartsbox
Thermistor<2-phasepipe>(TH6)
Cont.boxtop
5. Removing the thermistor <2-Phase Pipe> (TH6) (1)Removetheservicepanel.(SeePhoto1) (2)Removethetoppanel.(SeePhoto1) (3)DisconnecttheconnectorTH7/6(RED)onthecontrollercircuitboardintheelectricalpartsbox.(SeePhoto4) (4)Loosenthefastenerfortheleadwireintheelectricalpartsbox. (5)Loosentheclampfortheleadwireonthetopofelectricalpartsbox. (6)Pulloutthethermistor<2-phasepipe>(TH6)fromthermistorclip.
Note: When replacing thermistor <2-phase pipe> (TH6), replace it together with thermistor <Ambient> (TH7) since they are combined together. Refer to procedure No.5 on the next page to remove the thermistor <Ambient> (TH7).
OCH582B
OPERATING PROCEDURE PHOTOS
98
6. Removing the thermistor <Ambient> (TH7) (1)Removetheservicepanel.(SeePhoto1) (2)Removethetoppanel.(SeePhoto1) (3)DisconnecttheconnectorTH7/6(RED)onthecontroller
circuitboardintheelectricalpartsbox.(SeePhoto4) (4)Loosenthefastenerfortheleadwireintheelectricalparts
box. (5)Loosentheclampsfortheleadwireontopoftheelectrical partsbox.
(6)Pulloutthethermistor<Ambient>(TH7)fromthermistorholder.
Photo 11
Leadwireofthermistor<Ambient>(TH7) Sensorholder
Photo 12
ValvebedThermistor<Comp.Surface>(TH32)
Compressor
Note: When replacing thermistor <Ambient> (TH7), replace it together with thermistor <2-phase pipe> (TH6), since they are combined together. Refer to procedure No.4 in the previous page to remove the thermistor <2-phase pipe>(TH6).
Damper Thermistor <Liquid>(TH3)
7. Removing the thermistor <Liquid> (TH3), and thermistor <Comp. surface> (TH32).
(1)Removetheservicepanel.(SeePhoto1)(2)Disconnecttheconnector,TH3(WHT)andTH32(BLK)on
thecontrollercircuitboardintheelectricalpartsbox.(SeePhoto4)
(3)Loosenthefastener,cablestrapandbandfortheleadwireonthecontrollercircuitboardintheelectricalpartsbox.
(4)Loosentheclampfortheleadwireonseparator.(5)Pulloutthethermistor<Liquid>(TH3)fromthermistorclip.(6)Removethetopdamper,thenpulloutthethermistor
<Comp.surface>(TH32)fromthermistorholder.
OCH582B
OPERATING PROCEDURE PHOTOS
99
8. Removing the 4-way valve coil (21S4), LEV coil (LEV (A))and lead wire for high pressure switch.
(1)Removetheservicepanel.(SeePhoto1) (2)Removethetoppanel.(SeePhoto1) (3)Removetheelectricalpartsbox.(SeePhoto4) (4)Loosentheclampfortheleadwireonseparator. [Removing the lead wire for high pressure switch] (5)Disconnecttheleadwirefromthehighpressureswitch. [Removing the 4-way valve coil]
(5)Removethe4-wayvalvecoilfixingscrew(1forfront/M5)toremovethe4-wayvalvecoil.
(6)Slidethe4-wayvalvecoilforwardtoremoveit.
[Removing the LEV coil] (5)Loosentheleadwiresfixedtothepipeswithbands. (6)SlidetheLEVcoilupwardtoremoveit.
Photo 13
9. Removing the 4-way valve, LEV (LEV (A)) and high pressure switch.
(1)Removetheservicepanel.(SeePhoto1) (2)Removethetoppanel.(SeePhoto1) (3)Removetheelectricalpartsbox.(SeePhoto4) (4)Removethecoverpanel(front).(SeePhoto1) (5)Removethecoverpanel(rear).(SeePhoto1) (6)Removethevalvebed.(SeePhoto14) (7)Removethesidepanel(R). (8)Recoverrefrigerant. [Removing the 4-way valve]
(9)Removethe4-wayvalvecoil.(Seephoto13)(10)Removetheweldedpartof4-wayvalve(4positions)to
removethe4-wayvalve.
[Removing the LEV] (9)RemovetheLEVcoil.(Seephoto13)
(10)Removetheweldedpartof4-wayvalve(4positions)toremovethe4-wayvalve.
[Removing the high pressure switch]
(9)Disconnecttheleadwirefromthehighpressureswitch.(10)Removetheweldedpartofhighpressureswitch (1position)toremovethehighpressureswitch.
Note 1: Recover refrigerant without spreading it in the air.Note 2: The welded part can be removed easily by
removing the side panel (R).Note 3: When installing the following parts, cover it with
a wet cloth to prevent it from heating as the temperature below, then braze the pipes so that the inside of pipes are not oxidized;
• 4-way valve, 120°C or more • LEV, 120°C or more • High pressure switch, 100°C or more
4-wayvalvecoil(21S4)
Accumulator
LEVcoil(LEVA)
Highpressureswitch
OCH582B
OPERATING PROCEDURE PHOTOS
Valvebedfixingscrew
100
Compressor(MC)
Valvebed
Separator
Separatorfixingscrew
Valvebedfixingscrews
Compressorfixingnut
Receiverlegfixingscrews Receiver
leg
Outlet
Inlet
Compressor(MC)
10. Removing the compressor (MC) (1)Removetheservicepanel.(SeePhoto1) (2)Removethetoppanel.(SeePhoto1) (3)Removetheelectricalpartsbox.(SeePhoto4) (4)Removethecoverpanel(front).(SeePhoto1) (5)Removethecoverpanel(rear).(SeePhoto1) (6)Removethevalvebed.(Seephoto14) (7)Removethesidepanel(R).(SeePhoto1) (8)Removethefrontpanelfixingscrews(5forfront/5x12
and2forfront/4x10),thenslidethefrontpanelupwardtoremoveit.
(Thefrontpanelisfixedwith4hooks;3ontheleftsidefixingtothesidepanel(L),andtheotherontherightsidefixingtotheseparator.)
(9)ReleasetheleadwireforFM1andFM2fromtheholeonseparator.
(10)Removetheseparatorfixingscrews(4forfront/4x10), thenslidetheseparatorupwardtoremoveit. (Theseparatorisfixedtoahookofthesideplate.) (11)Recoverrefrigerant. (12)Removetheweldedpartofcompressor(2positions). (13)Removethe3compressorfixingnuts(M6)toremovethe compressor.
Note 1: Recover refrigerant without spreading it in the air. Note 2: The compressor can be easily removed by removing separator.
Photo 14
Photo 15 11. Removing the power receiver (1)Removetheservicepanel.(SeePhoto1) (2)Removethetoppanel.(SeePhoto1) (3)Removetheelectricalpartsbox.(Seephoto4) (4)Removethecoverpanel(front).(SeePhoto1) (5)Removethecoverpanel(rear).(SeePhoto1) (6)Removethevalvebed.(SeePhoto14) (7)Removethesidepanel(R).(SeePhoto1) (8)Recoverrefrigerant.
(9)Removetheweldedpartoftheaccumulator(2positions)toremovetheaccumulator.
(10)Removereceiverlegfixingscrews(2forfront/4x10),thenslidethepowerreceiverforwardtoremoveit.
(Thepowerreceiverisfixedtothebasewithahookonthebottom.)
Note: Recover refrigerant without spreading it in the air.
Accumulator
Accumulator
OCH582B
101OCH582B
HEADOFFICE:TOKYOBLDG.,2-7-3,MARUNOUCHI,CHIYODA-KU,TOKYO100-8310,JAPAN
CCopyright2014MITSUBISHIELECTRICCORPORATIONDistributedinJun.2015No.OCH582REVISEDEDITION-BDistributedinJan.2015No.OCH582REVISEDEDITION-ADistributedinOct.2014No.OCH582MadeinJapan
Newpublication,effectiveJun.2015Specificationsaresubjecttochangewithoutnotice.