Technical Information Sheet SL36-NPT
Novaris Pty Ltd ABN: 33 065 427 232 72 Browns Road, Kingston, TAS. 7050 TEL: +61 3 6229 7233 AUSTRALIA FAX: +61 3 6229 9245
Copyright 2000 Novaris E-mail: [email protected]
SURGE PROTECTORS FOR PROCESS TRANSMITTERS
SL36-NPT3/4 SL36-NPT1/2
Product Description
Novaris SL36-NPT signal line protectors are designed
for the effective protection against lightning and other
transient overvoltages on process control 4/20mA
transmitters. These units can be readily fitted to field
mounted instruments whilst still maintaining explosion
proof integrity where applicable. All components in
the SL36-NPT series are passive and the whole unit
may be defined as simple apparatus.
For the protection of the remote end of the circuit at
the RTU Novaris SL1-36 DINsafe signal line
protectors are recommended.
Operation
The SL36-NPT is a shunt-connected device. It
therefore inserts no series impedance and does not
effect device calibration or operation. The unit
provides protection against common mode and
transverse mode disturbances. Common mode
disturbances are typical of lightning induced voltages.
These voltages exist between each signal line and
ground and can have high energy content. For commonmode protection the protector comprises a fast acting,
high-energy, three-element gas arrester connected
between each line and ground. Most instruments can
withstand common mode voltages of up to 500V.
Transverse mode protection is provided in the first
instance by the gas arrester as primary protection plusa fast acting transient clamping diode, which limits line
to line voltage to 36V, well within the limits of 12V
and 24V instruments.
Installation
Screw the protector into a spare conduit entry on the
instrument body. Connect the flying leads as follows:
Red to +ve terminal
Black to –ve terminal
Green/Yellow to earth terminal (frame).
ALL LEADS MUST BE AS SHORT AS POSSIBLE.Do not coil leads, cut them to the minimum length
required.
Specifications
Description: Shunt connected surge protector for4/20mA process instruments.
Protection modes: Transverse and commonmode
Protection stages: Gas arrester/Transorb
Surge withstand: IEEE C62.41 cat, A, B, C AS1768-1991 cat. A, B, C
Surge rating: 20kA for 8/20µs pulse
Transverse mode clamp voltage:36V peak
Arrester firing voltage: 230V peak
Arrester residual voltage: 20V peak
Material: nickel plated brass, epoxy filled
Dimensions:
¾” NPT 30 long x 32 diameter, hex 27AF½” NPT 70 long x 39 diameter, hex 34AF
Approval: AUS Ex2428UEx d ia IIC T4 Class 1 Zone 1
Options
Cat No. Clamp DescriptionSL36-NPT3/4 36V ¾” NPT threadSL36-NPT1/2 36V ½” NPT thread
Note: Other clamping voltages available on request