smart building automation systems - vİko by...
TRANSCRIPT
SMART BUILDING AUTOMATION SYSTEMS
TECHNICAL
CATALOQUEwww.theaiq.com.tr
15
Product overview of the KNX range from Thea IQ
An overview of building solutions
Heating Control
Push Buttons
Light Control
Binary input
Touch Panels
Thea IQ Digital Room ThermostatPage 58
Thea IQ Push Buttons 2x1, 4x2, 6x3, 8x4Page 56 - 57
Thea IQ Presence DetectorsPage 59 - 62
Binary Inputs for Flush-Mounted Sockets 2/4/6 WayPage 55
Thea IQ Touch Panels 7”, 10”, 15”, 19”Page 69 - 78
Heating/Cooling
Heating Actuators, Fan Coil ActuatorsPage 32 - 33 / 47 - 49
Sensors
Blinds/Shutters
Switching/Dimming
Dimming
Intercomries
System devices
Weather Station, Brightness Sensor Page 63 - 64
Blind ActuatorsPage 20 - 24 / 44
Switching Actuators, Switching Actuators C-LoadPage 11 - 19 / 41 -43
Dimming Actuators, Control UnitsPage 25 - 31 / 45 - 46
Thea IQ Outdoor Unit, Videophone Box, VOIP ServerPage 81 - 83
Thea IQ Power Sup-plies, Line Coupler, USB Interface, Time SwitchPage 5 - 8
SMART BUILDING AUTOMATION SYSTEMS
15
SMART BUILDING AUTOMATION SYSTEMS
SYSTEMCOMPONENTS
SMART BUILDING AUTOMATION SYSTEMS
Power Supply Units
Line Coupler
USB Data
Yearly Time Switch
SMART BUILDING AUTOMATION SYSTEMS
theaiq.com.tr
• ForsupplyingKNXdeviceswithbusvoltage• Onenon-chokedandonechokedoutputeach.• Thenon-chokedoutputcanbeusedforthesupplyofanother lineorforfunctiondevices(smartsensoretc.)whichrequirean auxiliaryvoltage• AKNXbuslinecanbesuppliedfromtwopowersupplyunits. Theremustbeatleast200mofbuslinebetweentheinfeed points
• Nominalvoltagecanbesubdividedtooutputs(chokedornon- choked)asdesired.• Withresetswitchforbuslines• Withshortcircuitprotection• Withovervoltageprotection
Power Supply Units
Main Features
PSU 640 90992201PSU 320 90992202
Order Number
5
Connection
PSU 640 PSU 320
LEDdisplay,red :busresetLEDdisplay,yellow :overvoltageLEDdisplay,red :overloadLEDdisplay,green :operation
Technical Data Status Display
PSU 640 PSU 320
OperatingvoltageAC
OperatingvoltageDC
Powerloss
Dimensions
Outputcurrent
Outputvoltage
Ambienttemperature
Protectionrating
161...264VAC,50/60Hz
176...270VDC
5Wmax.
7modules
640mA
4modules
320mA
30VDC
-5°C...+45°C
IP20
PSU 320 Power Supply Unit 320mAPSU 640 Power Supply Unit 640mA
SYSTEM COMPONENTSPower Supply Units
SMART BUILDING AUTOMATION SYSTEMSArea / Line CouplerSYSTEM COMPONENTS
• Reducedbusloadduetofilterfunction(filtertable)• Forwardingofgrouptelegramscanbeparameterised• Telegramrepetitionsincaseoftransmissionerrorsadjustable• Telegramconfirmationcanbeparameterised
• Expansionofalineintoamaximumof4line segmentswithupto64devicespersegment• Telegramrepetitionsincaseoftransmissionerrors adjustable
Area / Line Coupler
Main Features
Technical Data Functions
Used as area/line coupler
Used as line repeater
Line Coupler 90992203
Order Number
Line Coupler
OperatingvoltageKNX
Operatingvoltage
Width
Currentconsumptionsuperordinateline
Currentconsumptionsubordinateline
Ambienttemperature
Protectionrating
Busvoltage
230VAC
2modules
6mA
8mA
-5°C...+45°C
IP20
Connection
6
• ForconnectingtwoKNX/EIBdatalinesandensuringthe electricalseparationoftheselinesfromoneanother• Canbeusedasanareaoralinecoupleroralternativelyasa linerepeaterdependingontheassignmentofthephysical addressandontheparameterizationofthedevice• Withamaximumof3linerepeatersinparallelperline,the highestmax.numberof256devicesinalinecanthenbe realized• Aseparatepowersupplyisrequiredforeachlineoreachline
segment• LEDstatusindication
Line Coupler
As Line Coupler/Line RepeaterAs Area/Line Coupler
SMART BUILDING AUTOMATION SYSTEMS
theaiq.com.tr
USB Interface 90992231
SYSTEM COMPONENTS
USB Data Interface
Main Features
Technical Data
Order Number
USB Data Interface
USB Interface
OperatingvoltageKNX
Powersupply
Powerconsumption
Width
LengthofUSBcable
Transmissionprotocol
PCport(USB)
Rateoftransmission
Ambienttemperature
Protectionrating
Busvoltage
ViaPCUSB-port
150mWmax.
2modules
5mmax.
CompatiblewithUSBstandards1.1and2.0
USBconnectingsockettypeB
typically9.6kbaud
-5°C...+45°C
IP20
Connection
7
• PermitstheconnectionofaPCtotheinstabusKNX/EIB• EnablesInstabusdevicestobeaddressed,programmedand diagnosedbymeansoftheETS• Thedeviceelectronicsgettheirpowersupplycompletelyfrom theUSBinterfaceoftheconnectedPC
• ThefirmwareoftheUSBdatainterfacecanbeupdatedwith thelocalPCsothatthedevicecaneasilybeadaptedtofuture standards
USB Interface
USB Interface
SMART BUILDING AUTOMATION SYSTEMS
SYSTEM COMPONENTS
TSR 644S 4-Channel Yearly Time Switch Module
TSR 644S 90990154
Order Number
• Withdaily,weekly,yearly,random,pulseandpriorityprograms• Timedependentswitchingoflighting,heating,blinds,alarm systemsetc.• Time-dependentspecificationofdifferenttemperaturelevelsfor individualroomcontrol• Timeanddatesynchronisationfromotherbusparticipants
• Movablepublicholidayscanbeautomaticallyadjustedannually• Automaticsummer/wintertimechange• SwitchingtimesarepermanentlystoredinEEPROM
Main Features
Yearly Time Switch
8
Scale Drawings
TSR 644S
Oneachofthe4channelsyoucanchoosebetweenthefollowingmessagetypes:
• Switchingmessage(1Bit)• Prioritymessage(2Bit)• Dimmingorvaluemessage(8Bit)• Temperaturemessage(16Bit)• AnymessageintheEIS5form(16Bit)• Cyclicsendingselectable• Timeswitchcanbesetsynchronisedviabusbyreceiving thetimeanddatemessage
Technical Data Functions
TSR 644S
OperatingvoltageKNX
Operatingvoltage
Numberofchannels
Numberofmemorycells
Timeaccuracy
Shortestswitchingtime
Dimensions
Display
Ambienttemperature
Protectionrating
Busvoltage,(<10mA)
230VAC,50-60Hz
4
324
≤±1s/day(Quartz)
1s
6modules
LCD
-5°C...+45°C
IP20
15
SMART BUILDING AUTOMATION SYSTEMS
STANDARTSERIES
Switch Actuators
Blind Actuators
Dimming Actuators
Control Units
Heating Actuator
Fan Coil Actuator
Binary Inputs
Dali Gateway
Room Actuator
SMART BUILDING AUTOMATION SYSTEMS
theaiq.com.tr
• Forswitching16independentloadsofmax.16Aperchannelor 8electricallydrivenblinds/shuttersfor230VACmainssupply• Mixedoperationofthesetwomodesofoperationisalso possible• OutputscanbeconfiguredasNOcontactsorNCcontacts• Upto5differentsafetyfunctions(3windalarms,1rainalarm, 1frostalarm)• Extensivesunprotectionfunctionwithfixedandvariableblind orslatpositions• LEDstatusindicationforeachoutput
• Switchingfunctionse.g.On/Off,pulse,On/Offdelay,staircase lightwithwarning• Logicaloperationse.g.Disable,AND,enable,OR• Manualoperation(alsowithoutbusvoltage)
STANDART SERIES
Switch Actuators 16 Channels / Blind Actuators 8 Channels
Main Features
SBA 16 16-Channel Module
SBA 16 90992214
Order Number
Switch Actuators
11
Connection
SBA 16
Resistiveload :3000WCapacitiveload :max.140µFIncandescentlampload :3000WHalogenlampload :2500WFluorescentlamploaduncompensated :1000WFluorescentlamploadparallelcompensated :1160W(140µF)Fluorescentlamploadduocircuit :2300W(140µF)Motors :1380VA
Technical Data Switching Capacity
SBA 4
OperatingvoltageKNX
Operatingvoltage
PowerConsumptionKNX
Powerloss
Dimensions
Outputs
Min.switchingcurrent
Ambienttemperature
Protectionrating
Busvoltage,(<10mA)
230/240VAC,50/60Hz
150mW
4,5Wmax.
8modules
Relay,16A(at250VAC,cosϕ=1),
10A(at250VAC,cosϕ=0,6)
100mA
-5°C...+45°C
IP20
SMART BUILDING AUTOMATION SYSTEMS
Resistiveload :3000WCapacitiveload :max.140µFIncandescentlampload :3000WHalogenlampload :2500WFluorescentlamploaduncompensated :1000WFluorescentlamploadparallelcompensated :1160W(140µF)Fluorescentlamploadduocircuit :2300W(140µF)Motors :1380VA
STANDART SERIES
Switch Actuators 8 Channels / Blind Actuators 4 Channels
Main Features
Technical Data Switching Capacity
SBA 8 90992215
Order Number
Switch Actuators
SBA 8
OperatingvoltageKNX
Operatingvoltage
PowerConsumptionKNX
Powerloss
Dimensions
Outputs
Min.switchingcurrent
Ambienttemperature
Protectionrating
Busvoltage,(<10mA)
230/240VAC,50/60Hz
150mW
3Wmax.
4modules
Relay,16A(at250VAC,cosϕ=1),
10A(at250VAC,cosϕ=0,6)
100mA
-5°C...+45°C
IP20
Connection
12
• Forswitching8independentloadsofmax.16Aperchannelor 4electricallydrivenblinds/shuttersfor230VACmainssupply• Mixedoperationofthesetwomodesofoperationisalso possible• OutputscanbeconfiguredasNOcontactsorNCcontacts• upto5differentsafetyfunctions(3windalarms,1rainalarm, 1frostalarm)• extensivesunprotectionfunctionwithfixedandvariableblind orslatpositions• LEDstatusindicationforeachoutput
• Switchingfunctionse.g.On/Off,pulse,On/Offdelay,staircase lightwithwarning• Logicaloperationse.g.Disable,AND,enable,OR• Manualoperation(alsowithoutbusvoltage)
SBA 8 8-Channel Module
SBA 8
SMART BUILDING AUTOMATION SYSTEMS
theaiq.com.tr
• Forswitching4independentloadsofmax.16Aperchannelor 2electricallydrivenblinds/shuttersfor230VACmainssupply• Mixedoperationofthesetwomodesofoperationisalso possible• OutputscanbeconfiguredasNOcontactsorNCcontacts• upto5differentsafetyfunctions(3windalarms,1rainalarm, 1frostalarm)• extensivesunprotectionfunctionwithfixedandvariableblind orslatpositions• LEDstatusindicationforeachoutput
• Switchingfunctionse.g.On/Off,pulse,On/Offdelay,staircase lightwithwarning• Logicaloperationse.g.Disable,AND,enable,OR• Manualoperation(alsowithoutbusvoltage)
STANDART SERIES
Switch Actuators 4 Channels / Blind Actuators 2 Channels
Main Features
SBA 4 4-Channel Module
SBA 4 90992216
Order Number
Switch Actuators
13
Connection
SBA 4
Resistiveload :3000WCapacitiveload :max.140µFIncandescentlampload :3000WHalogenlampload :2500WFluorescentlamploaduncompensated :1000WFluorescentlamploadparallelcompensated :1160W(140µF)Fluorescentlamploadduocircuit :2300W(140µF)Motors :1380VA
Technical Data Switching Capacity
SBA 4
OperatingvoltageKNX
Operatingvoltage
PowerConsumptionKNX
Powerloss
Dimensions
Outputs
Min.switchingcurrent
Ambienttemperature
Protectionrating
Busvoltage,(<10mA)
230/240VAC,50/60Hz
150mW
2Wmax.
4modules
Relay,16A(at250VAC,cosϕ=1),
10A(at250VAC,cosϕ=0,6)
100mA
-5°C...+45°C
IP20
SMART BUILDING AUTOMATION SYSTEMS
Resistiveload :3600WCapacitiveload :max.140µFIncandescentlampload :2500WHalogenlampload :2500WFluorescentlamploaduncompensated :2500WFluorescentlamploadparallelcompensated :1300W(140µF)Fluorescentlamploadlead-lagcircuit :2300W(140µF)
STANDART SERIES
Switch Actuators 4 Channels
Main Features
Technical Data Switching Capacity
SA 4 90992217
Order Number
Switch Actuators
SA 4
OperatingvoltageKNX
PowerConsumptionKNX
Powerloss
Dimensions
Switchingcurrent230VAC
Switchingcurrent400VAC
SwitchingcurrentDC
Min.switchingcurrent
Ambienttemperature
Protectionrating
Busvoltage,(<10mA)
150mW
4Wmax.
4modules
16A(cosϕ=1),10A(cosϕ=0,6)
10A(cosϕ=1),6A(cosϕ=0,6)
16A,24VDC
100mA
-5°C...+45°C
IP20
Connection
14
• Forswitching4independentloadsofmax.16Aperchannel• Switchingof230VACor24VAC/DCelectricalloadswith floatingcontacts• OutputscanbeconfiguredasNOcontactsorNCcontacts• Operatinghourscountercanbeactivatedindependentlyfor eachoutput• Inputmonitoringforcyclicalupdateswithsafetycircuit• LEDstatusindicationforoperation
• Switchingfunctionse.g.On/Off,pulse,On/Offdelay,staircase lightwithwarning• Logicaloperationse.g.Disable,AND,enable,OR• Manualoperation(alsowithoutbusvoltage)• Noadditionalpowersupplynecessary
SA 4 4-Channel Module
SA 4
SMART BUILDING AUTOMATION SYSTEMS
theaiq.com.tr
Resistiveload :3600WCapacitiveload :max.140µFIncandescentlampload :2500WHalogenlampload :2500WFluorescentlamploaduncompensated :2500WFluorescentlamploadparallelcompensated :1300W(140µF)Fluorescentlamploadlead-lagcircuit :2300W(140µF)
STANDART SERIES
Switch Actuators 8 Channels
Main Features
Technical Data Switching Capacity
SA 8 90992218
Order Number
Switch Actuators
SA 8
OperatingvoltageKNX
PowerConsumptionKNX
Powerloss
Dimensions
Switchingcurrent230VAC
Switchingcurrent400VAC
SwitchingcurrentDC
Min.switchingcurrent
Ambienttemperature
Protectionrating
Busvoltage,(<10mA)
150mW
8Wmax.
8modules
16A(cosϕ=1),10A(cosϕ=0,6)
10A(cosϕ=1),6A(cosϕ=0,6)
16A,24VDC
100mA
-5°C...+45°C
IP20
Connection
15
• Forswitching8independentloadsofmax.16Aperchannel• Switchingof230VACor24VAC/DCelectricalloadswith floatingcontacts• OutputscanbeconfiguredasNOcontactsorNCcontacts• Operatinghourscountercanbeactivatedindependentlyfor eachoutput• Inputmonitoringforcyclicalupdateswithsafetycircuit• LEDstatusindicationforoperation
• Switchingfunctionse.g.On/Off,pulse,On/Offdelay,staircase lightwithwarning• Logicaloperationse.g.Disable,AND,enable,OR• Manualoperation(alsowithoutbusvoltage)• Noadditionalpowersupplynecessary
SA 8 8-Channel Module
SA 8
SMART BUILDING AUTOMATION SYSTEMS
• Forswitching4independentcapacitiveloadsofmax.16Aper channel• Switchingof230VACor24VAC/DCelectricalloadswith floatingcontacts• OutputscanbeconfiguredasNOcontactsorNCcontacts• Currentdetection:measurementoftheloadcurrentforeach output
• Switchingfunctionse.g.On/Off,pulse,On/Offdelay,staircase lightwithwarning• Logicaloperationse.g.Disable,AND,enable,OR• Manualoperation(alsowithoutbusvoltage)• Noadditionalpowersupplynecessary
STANDART SERIES
Switch Actuators 4 Channels for C Load
Main Features
SAC 4 4-Channel C-Load Module
SAC 4 90992219
Order Number
Switch Actuators
16
Connection
SAC 4
Resistiveload :3680WCapacitiveload :max.200µFIncandescentlampload :3680WHalogenlampload :3680WFluorescentlamploaduncompensated :3680WFluorescentlamploadparallelcompensated :2500W(200µF)Fluorescentlamploadduocircuit :3680W(200µF)
Technical Data Switching Capacity
SAC 4
OperatingvoltageKNX
PowerConsumptionKNX
Powerloss
Dimensions
Switchingcurrent230VAC
Switchingcurrent400VAC
SwitchingcurrentDC
Min.switchingcurrent
Ambienttemperature
Protectionrating
Busvoltage,(<10mA)
240mW
4Wmax.
4modules
16A(cosϕ=1),10A(cosϕ=0,6)
10A(cosϕ=1),6A(cosϕ=0,6)
16A,12–24VDC
100mA
-5°C...+45°C
IP20
SMART BUILDING AUTOMATION SYSTEMS
theaiq.com.tr
Resistiveload :3680WCapacitiveload :max.200µFIncandescentlampload :3680WHalogenlampload :3680WFluorescentlamploaduncompensated :3680WFluorescentlamploadparallelcompensated :2500W(200µF)Fluorescentlamploadduocircuit :3680W(200µF)
STANDART SERIES
Switch Actuators 8 Channels for C Load
Main Features
Technical Data Switching Capacity
SAC 8 90992220
Order Number
Switch Actuators
SAC 8
OperatingvoltageKNX
PowerConsumptionKNX
Powerloss
Dimensions
Switchingcurrent230VAC
Switchingcurrent400VAC
SwitchingcurrentDC
Min.switchingcurrent
Ambienttemperature
Protectionrating
Busvoltage,(<10mA)
240mW
8Wmax.
8modules
16A(cosϕ=1),10A(cosϕ=0,6)
10A(cosϕ=1),6A(cosϕ=0,6)
16A,12–24VDC
100mA
-5°C...+45°C
IP20
Connection
17
• Forswitching8independentcapacitiveloadsofmax.16Aper channel• Switchingof230VACor24VAC/DCelectricalloadswith floatingcontacts• OutputscanbeconfiguredasNOcontactsorNCcontacts• Currentdetection:measurementoftheloadcurrentforeach output• Monitoringofthresholdvaluesforloadmonitoring• LEDstatusindicationforoperation
• Switchingfunctionse.g.On/Off,pulse,On/Offdelay,staircase lightwithwarning• Logicaloperationse.g.Disable,AND,enable,OR• Manualoperation(alsowithoutbusvoltage)• Noadditionalpowersupplynecessary
SAC 8 8-Channel C-Load Module
SAC 8
L1L2L3N
A1 A2 A3 A4OFF
ON
OFF
ON
OFF
ON
OFF
ON
A1 A2 A3 A4
A5 A6 A7 A8OFF OFF
ON
OFF
ON
OFF
ON
A5 A6 A7 A8
ON
rot
schwarz
EIB
SMART BUILDING AUTOMATION SYSTEMS
• Forswitching2independentloadsofmax.16Aperchannel• Switchingof230VACor24VAC/DCelectricalloadswith floatingcontacts• OutputscanbeconfiguredasNOcontactsorNCcontacts• Operatinghourscountercanbeactivatedindependentlyfor eachoutput• Inputmonitoringforcyclicalupdateswithsafetycircuit• LEDstatusindicationforoperation
• Switchingfunctionse.g.On/Off,pulse,On/Offdelay,staircase lightwithwarning• Logicaloperationse.g.Disable,AND,enable,OR• Manualoperation(alsowithoutbusvoltage)• Noadditionalpowersupplynecessary
STANDART SERIES
Switch Actuators 2 Channels
Main Features
SA 2 2-Channel Module
SA 2 90992221
Order Number
Switch Actuators
18
Connection
SA 2
Resistiveload :3600WCapacitiveload :max.140µFIncandescentlampload :2500WHalogenlampload :2500WFluorescentlamploaduncompensated :2500WFluorescentlamploadparallelcompensated :1300W(140µF)Fluorescentlamploadlead-lagcircuit :2300W(140µF)
Technical Data Switching Capacity
SA 2
OperatingvoltageKNX
PowerConsumptionKNX
Powerloss
Dimensions
Switchingcurrent230VAC
Switchingcurrent400VAC
SwitchingcurrentDC
Min.switchingcurrent
Ambienttemperature
Protectionrating
Busvoltage,(<10mA)
150mW
2Wmax.
4modules
16A(cosϕ=1),10A(cosϕ=0,6)
10A(cosϕ=1),6A(cosϕ=0,6)
16A,24VDC
100mA
-5°C...+45°C
IP20
SMART BUILDING AUTOMATION SYSTEMS
theaiq.com.tr
• Forswitching6independentloadsofmax.6Aperchannel• OutputscanbeconfiguredasNOcontactsorNCcontacts• Multi-phaseconnectionispossible• Switchingfunctionse.g.On/Off,pulse,On/Offdelay, time-switch• Logicaloperationse.g.Disable,AND,enable,OR• Noadditionalpowersupplynecessary
STANDART SERIES
Switch Actuators 6 Channels 6A w/o manual control
Main Features
SA 6 6-Channel Switch Actuator Module
SA 6 90992205
Order Number
Switch Actuators
19
Connection
SA 6
Resistiveload :1380WCapacitiveload :max.14µFIncandescentlampload :1200WHalogenlampload :1200WFluorescentlamploaduncompensated :500VAFluorescentlamploadparallel-compensated :2x58VAFluorescentlamploaddualswitching :1000VA
Technical Data Switching Capacity
SA 6
OperatingvoltageKNX
Outputvoltage
PowerConsumption
Dimensions
Typeofcontact
Min.switchingcurrent
Ambienttemperature
Protectionrating
Busvoltage,(<10mA)
250VAC,50Hz
150mW
4modules
NO/NCcontact,6A
100mA
-5°C...+45°C
IP20
SMART BUILDING AUTOMATION SYSTEMS
• Forcontrolling8electricallydrivenblinds,shutters,awnings, ventilationflapsetc.foramainsvoltageof230VAC• Canbeconfiguredto4channeloperationfordirectcontrolof four12…48VDCdrives• Upto5differentsafetyfunctions(3windalarms,1rainalarm, 1frostalarm)• Extensivesunprotectionfunctionwithfixedandvariableblind orslatpositions• LEDstatusindicationforoperation
• Integrationintothetemperaturemanagementofthebuilding• Blind/shutterpositiondirectlycontrollable• Slatpositiondirectlycontrollable• Manualoperation(alsowithoutbusvoltage)• Mixedoperationof230Vand12…48VDCmotorsisnot possible
STANDART SERIES
Blind Actuators 8 Channels 230V AC / 4 Channels 12 – 48V DC
Main Features
BA 8 8-Channel Module
BA 8 90992224
Order Number
Blind Actuators
20
Connection
BA 8
• Busoperation :Operationviapush-button sensorsorotherbusdevices• Short-termmanualoperation :Manualoperationlocally withbuttonfield,automatic returntobusoperation.• Continuousmanualmode :Exclusivelymanual operationonthedevice
• Highestpriority :manualmode• 2ndpriority :forcedposition• 3rdpriority :safetyfunction• 4thpriority :sunprotection• Lowestpriority :busmode
Technical Data Operation modes
Priorities
BA 8
OperatingvoltageKNX
Operatingvoltage
PowerConsumptionKNX
Powerloss
SwitchingVoltageAC
SwitchingVoltageDC
Switchingcurrent230VAC
SwitchingcurrentDC
Min.switchingcurrent
Dimensions
Ambienttemperature
Protectionrating
Busvoltage,(<10mA)
230VAC,50/60Hz
150mW
6Wmax.
230VAC,50/60Hz
12...48VDC
6A
6A(24VDC),3A(48VDC)
100mA
8modules
-5°C...+45°C
IP20
SMART BUILDING AUTOMATION SYSTEMS
theaiq.com.tr
STANDART SERIES
Blind Actuators 4 Channels 230V AC / 2 Channels 12 – 48V DC
Main Features
BA 4 90992211
Order Number
Blind Actuators
• Busoperation :Operationviapush-button sensorsorotherbusdevices• Short-termmanualoperation :Manualoperationlocallywith buttonfield,automaticreturn tobusoperation.• Continuousmanualmode :Exclusivelymanualoperation onthedevice
• Highestpriority :manualmode• 2ndpriority :forcedposition• 3rdpriority :safetyfunction• 4thpriority :sunprotection• Lowestpriority :busmode
Technical Data Operation modes
Priorities
BA 4
OperatingvoltageKNX
Operatingvoltage
PowerConsumptionKNX
Powerloss
SwitchingVoltageAC
SwitchingVoltageDC
Switchingcurrent230VAC
SwitchingcurrentDC
Min.switchingcurrent
Dimensions
Ambienttemperature
Protectionrating
Busvoltage,(<10mA)
230VAC,50/60Hz
150mW
4,5Wmax.
230VAC,50/60Hz
12...48VDC
6A
6A(24VDC),3A(48VDC)
100mA
4modules
-5°C...+45°C
IP20
Connection
21
• Forcontrolling4electricallydrivenblinds,shutters,awnings, ventilationflapsetc.foramainsvoltageof230VAC• Canbeconfiguredto2channeloperationfordirectcontrolof two12…48VDCdrives• Upto5differentsafetyfunctions(3windalarms,1rainalarm, 1frostalarm)• Extensivesunprotectionfunctionwithfixedandvariableblind orslatpositions• LEDstatusindicationforoperation
• Integrationintothetemperaturemanagementofthebuilding• Blind/shutterpositiondirectlycontrollable• Slatpositiondirectlycontrollable• Manualoperation(alsowithoutbusvoltage)• Mixedoperationof230Vand12…48VDCmotorsisnot possible
BA 4 4-Channel Module
BA 4 for 24V DC BA 4 for 230V AC
SMART BUILDING AUTOMATION SYSTEMS
• Forcontrolling2electricallydrivenblinds,shutters,awnings, ventilationflapsetc.foramainsvoltageof230VAC• Canbeconfiguredto1channeloperationfordirectcontrolofa 12…48VDCdrive• Upto5differentsafetyfunctions(3windalarms,1rainalarm, 1frostalarm)• Extensivesunprotectionfunctionwithfixedandvariableblind orslatpositions• LEDstatusindicationforoperation
• Integrationintothetemperaturemanagementofthebuilding• Blind/shutterpositiondirectlycontrollable• Slatpositiondirectlycontrollable• Manualoperation(alsowithoutbusvoltage)
STANDART SERIES
Blind Actuators 2 Channels 230V AC / 1 Channel 12 – 48V DC
Main Features
BA 2 2-Channel Module
BA 2 90992212
Order Number
Blind Actuators
22
Connection
BA 2 for 24V DC BA 2 for 230V AC
• Busoperation :Operationviapush-button sensorsorotherbusdevices• Short-termmanualoperation :Manualoperationlocallywith buttonfield,automaticreturn tobusoperation.• Continuousmanualmode :Exclusivelymanualoperation onthedevice
• Highestpriority :manualmode• 2ndpriority :forcedposition• 3rdpriority :safetyfunction• 4thpriority :sunprotection• Lowestpriority :busmode
Technical Data Operation modes
Priorities
BA 2
OperatingvoltageKNX
Operatingvoltage
PowerConsumptionKNX
Powerloss
SwitchingVoltageAC
SwitchingVoltageDC
Switchingcurrent230VAC
SwitchingcurrentDC
Min.switchingcurrent
Dimensions
Ambienttemperature
Protectionrating
Busvoltage,(<10mA)
230VAC,50/60Hz
150mW
4,5Wmax.
230VAC,50/60Hz
12...48VDC
6A
6A(24VDC),3A(48VDC)
100mA
4modules
-5°C...+45°C
IP20
SMART BUILDING AUTOMATION SYSTEMS
theaiq.com.tr
STANDART SERIES
Blind Actuators 4 Channels 12 – 48V DC
Main Features
BAD 4 90992209
Order Number
Blind Actuators
• Busoperation :Operationviapush-button sensorsorotherbusdevices• Short-termmanualoperation :Manualoperationlocallywith buttonfield,automaticreturn tobusoperation.• Continuousmanualmode :Exclusivelymanualoperation onthedevice
• Highestpriority :manualmode• 2ndpriority :forcedposition• 3rdpriority :safetyfunction• 4thpriority :sunprotection• Lowestpriority :busmode
Technical Data Operation modes
Priorities
BAD 4
OperatingvoltageKNX
Operatingvoltage
PowerConsumptionKNX
Powerloss
SwitchingVoltageDC
Switchingcurrent
Min.switchingcurrent
Dimensions
Ambienttemperature
Protectionrating
Busvoltage,(<10mA)
12...48VDC,50/60Hz
150mW
1Wmax.
12...48VDC
6A(24VDC),3A(48VDC)
100mA
4modules
-5°C...+45°C
IP20
Connection
23
• Forcontrolling4electricallydrivenblinds,shutters,awnings, ventilationflapsetc.foramainsvoltageof12…48VDC• Upto5differentsafetyfunctions(3windalarms,1rainalarm, 1frostalarm)• Extensivesunprotectionfunctionwithfixedandvariableblind orslatpositions• LEDstatusindicationforoperation
• Integrationintothetemperaturemanagementofthebuilding• Blind/shutterpositiondirectlycontrollable• Slatpositiondirectlycontrollable• Manualoperation(alsowithoutbusvoltage)
Blind Actuators
BAD 4
SMART BUILDING AUTOMATION SYSTEMS
• Forcontrolling4electricallydrivenblinds,shutters,awnings, ventilationflapsetc.foramainsvoltageof230VAC• Upto5differentsafetyfunctions(3windalarms,1rainalarm, 1frostalarm)• Extensivesunprotectionfunctionwithfixedandvariableblind orslatpositions• LEDstatusindicationforoperation
• Integrationintothetemperaturemanagementofthebuilding• Blind/shutterpositiondirectlycontrollable• Slatpositiondirectlycontrollable• Manualoperation(alsowithoutbusvoltage)
STANDART SERIES
Blind Actuators 4 Channels 230V AC
Main Features
BAA 4 4-Channel Module
BAA 4 90992213
Order Number
Blind Actuators
24
Connection
BAA 4
• Busoperation :Operationviapush-button sensorsorotherbusdevices• Short-termmanualoperation :Manualoperationlocally withbuttonfield,automatic returntobusoperation.• Continuousmanualmode :Exclusivelymanualoperation onthedevice
• Highestpriority :manualmode• 2ndpriority :forcedposition• 3rdpriority :safetyfunction• 4thpriority :sunprotection• Lowestpriority :busmode
Technical Data Operation modes
Priorities
BAA 4
OperatingvoltageKNX
Operatingvoltage
PowerConsumptionKNX
Powerloss
SwitchingVoltageAC
Switchingcurrent
Min.switchingcurrent
Dimensions
Ambienttemperature
Protectionrating
Busvoltage,(<10mA)
230VAC,50/60Hz
150mW
4,5Wmax.
230VAC,50/60Hz
6A
100mA
4modules
-5°C...+45°C
IP20
SMART BUILDING AUTOMATION SYSTEMS
theaiq.com.tr
Incandescentlampload :500WHalogenlampload :500WInductivetransformers :500VATronictransformers :500WMixedloadresistive-inductive :500VAMixedloadresistive-capacitive :500W
Incandescentlampload :250WHalogenlampload :250WInductivetransformers :250VATronictransformers :250WMixedloadresistive-inductive :250VAMixedloadresistive-capacitive :250W
STANDART SERIES
Dimming Actuators 1 Channel 500W
Main Features
Technical Data Switching Capacity at 230V AC
Switching Capacity at 110V AC
DA 1 90992225
Order Number
Dimming Actuators
DA 1
OperatingvoltageKNX
Operatingvoltage
PowerConsumptionKNX
Powerloss
Dimensions
Min.Switchingcapacity
Max.Switchingcapacity
Switchingcurrentmotors
Ambienttemperature
Protectionrating
Busvoltage,(<10mA)
110V...230VAC,50/60Hz
150mW
4Wmax.
4modules
20W
500W
2,3A
-5°C...+45°C
IP20
Connection
25
• ForswitchinganddimmingofHVincandescentlamps,HV halogenlampsandLVhalogenlampswithinductive transformersorTronictransformers• Parameterizableswitch-onanddimmingbehaviour• Softswitch-onandsoftswitch-offfunction• Timefunctions:switch-ondelay,switch-offdelay,staircase lightingtimerwithrun-ontime• Protectedagainstno-load,short-circuitandoverheating• LEDstatusindicationforoperation
• Canbeusedasaspeedcontrollerofsingle-phaseelectric motors• Logicaloperationse.g.Disable,AND,enable,OR• Manualoperation(alsowithoutbusvoltage)
DA 1 1-Channel Module
DA 1
SMART BUILDING AUTOMATION SYSTEMS
Incandescentlampload :300WHalogenlampload :300WInductivetransformers :300VATronictransformers :300WMixedloadresistive-inductive :300VAMixedloadresistive-capacitive :300W
Incandescentlampload :150WHalogenlampload :150WInductivetransformers :150VATronictransformers :150WMixedloadresistive-inductive :150VAMixedloadresistive-capacitive :150W
DA 2 90992226
STANDART SERIES
Dimming Actuators 2 Channels 300W
Main Features
Technical Data Switching Capacity at 230V AC
Switching Capacity at 110V AC
Order Number
Dimming Actuators
DA 2
OperatingvoltageKNX
Operatingvoltage
PowerConsumptionKNX
Powerloss
Dimensions
Min.Switchingcapacity
Max.Switchingcapacity
Ambienttemperature
Protectionrating
Busvoltage,(<10mA)
110V...230VAC,50/60Hz
150mW
4Wmax.
4modules
20W
300W
-5°C...+45°C
IP20
Connection
26
• ForswitchinganddimmingofHVincandescentlamps,HV halogenlampsandLVhalogenlampswithinductive transformersorTronictransformers• Parameterizableswitch-onanddimmingbehaviour• Softswitch-onandsoftswitch-offfunction• Timefunctions:switch-ondelay,switch-offdelay,staircase lightingtimerwithrun-ontime
• Protectedagainstno-load,short-circuitandoverheating• LEDstatusindicationforoperation• Logicaloperationse.g.Disable,AND,enable,OR• Manualoperation(alsowithoutbusvoltage)
DA 2 2-Channel Module
DA 2
SMART BUILDING AUTOMATION SYSTEMS
theaiq.com.tr
DA 4 90992227
STANDART SERIES
Dimming Actuators 4 Channels 250W
Main Features
Order Number
Dimming Actuators
Incandescentlampload :250WHalogenlampload :250WInductivetransformers :250VATronictransformers :250WMixedloadresistive-inductive :250VAMixedloadresistive-capacitive :250W
Incandescentlampload :120WHalogenlampload :120WInductivetransformers :120VATronictransformers :120WMixedloadresistive-inductive :120VAMixedloadresistive-capacitive :120W
Technical Data Switching Capacity at 230V AC
Switching Capacity at 110V AC
DA 4
OperatingvoltageKNX
Operatingvoltage
PowerConsumptionKNX
Powerloss
Dimensions
Min.Switchingcapacity
Max.Switchingcapacity
Ambienttemperature
Protectionrating
Busvoltage,(<10mA)
110V...230VAC,50/60Hz
150mW
8Wmax.
8modules
20W
250W
-5°C...+45°C
IP20
Connection
27
• ForswitchinganddimmingofHVincandescentlamps,HV halogenlampsandLVhalogenlampswithinductive transformersorTronictransformers• Parameterizableswitch-onanddimmingbehaviour• Softswitch-onandsoftswitch-offfunction• Timefunctions:switch-ondelay,switch-offdelay,staircase lightingtimerwithrun-ontime• Protectedagainstno-load,short-circuitandoverheating
• LEDstatusindicationforoperation• Increaseinoutputpowerpossiblethroughparallelswitchingof multipleoutputs• Logicaloperationse.g.Disable,AND,enable,OR• Manualoperation(alsowithoutbusvoltage)
DA 4 4-Channel Module
DA 4 Parallel wiring
SMART BUILDING AUTOMATION SYSTEMS
DA 4 4-Channel Module
• ForswitchinganddimmingofHVincandescentlamps,HV halogenlampsandLVhalogenlampswithinductive transformersorTronictransformers• Parameterizableswitch-onanddimmingbehaviour• Softswitch-onandsoftswitch-offfunction• Timefunctions:switch-ondelay,switch-offdelay,staircase lightingtimerwithrun-ontime• Protectedagainstno-load,short-circuitandoverheating• LEDstatusindicationforoperation
• Thepowercanbeincreasedwithexternalboosters.The boostersmustbeselectedtomatchthedimmersandtheload outputs• Logicaloperationse.g.Disable,AND,enable,OR• Manualoperation(alsowithoutbusvoltage)
STANDART SERIES
Dimming Actuators 4 Channels 210W
Main Features
DA 4S 90992210
Order Number
Dimming Actuators
28
Connection
DA 4S
Incandescentlampload :210W/VAHalogenlampload :210W/VAInductivetransformers :210W/VATronictransformers :210W/VAMixedloadresistive-inductive :210W/VAMixedloadresistive-capacitive :210W/VA
Technical Data Switching Capacity
DA 4S
OperatingvoltageKNX
Operatingvoltage
PowerConsumptionKNX
Powerloss
Dimensions
Min.Switchingcapacity
Max.Switchingcapacity
Ambienttemperature
Protectionrating
Busvoltage,(<10mA)
190V...230VAC,50/60Hz
150mW
8,5Wmax.
8modules
20W
210W
-5°C...+45°C
IP20
SMART BUILDING AUTOMATION SYSTEMS
theaiq.com.tr
DA 2S 2-Channel Module
• ForswitchinganddimmingofHVincandescentlamps,HV halogenlampsandLVhalogenlampswithinductive transformersorTronictransformers• Parameterizableswitch-onanddimmingbehaviour• Softswitch-onandsoftswitch-offfunction• Timefunctions:switch-ondelay,switch-offdelay,staircase lightingtimerwithrun-ontime• Protectedagainstno-load,short-circuitandoverheating• LEDstatusindicationforoperation
• Thetotalconnectedloadis600W/VAwithamax.single- channelloadof400W/VA• Thepowercanbeincreasedwithexternalboosters.• Logicaloperationse.g.Disable,AND,enable,OR• Multi-phaseconnectionispossible
STANDART SERIES
Dimming Actuators 2 Channel 300W w/o manual control
Main Features
DA 2S 90992206
Order Number
Dimming Actuators
29
Connection
DA 2S
Resistiveload :300WIncandescentlampload :300WHalogenlampload :300WInductivetransformers :300VATronictransformers :300WMixedloadresistive-inductive :300VAMixedloadresistive-capacitive :300W
Technical Data Switching Capacity
DA 2S
OperatingvoltageKNX
Operatingvoltage
PowerConsumptionKNX
Powerloss
Dimensions
Min.Switchingcapacity
Ambienttemperature
Protectionrating
Busvoltage,(<10mA)
230VAC,50/60Hz
150mW
4,5Wmax.
4modules
50W
-5°C...+45°C
IP20
SMART BUILDING AUTOMATION SYSTEMS
DA 1S 1-Channel Module
• ForswitchinganddimmingofHVincandescentlamps,HV halogenlampsandLVhalogenlampswithinductive transformersorTronictransformers• Parameterizableswitch-onanddimmingbehaviour• Softswitch-onandsoftswitch-offfunction• Timefunctions:switch-ondelay,switch-offdelay,staircase lightingtimerwithrun-ontime• Protectedagainstno-load,short-circuitandoverheating• LEDstatusindicationforoperation
• Thepowercanbeincreasedwithexternalboosters.The boostersmustbeselectedtomatchthedimmersandtheload outputs• Logicaloperationse.g.Disable,AND,enable,OR
STANDART SERIES
Dimming Actuators 1 Channel 500W w/o manual control
Main Features
DA 1S 90992208
Order Number
Dimming Actuators
30
Connection
DA 1S
Resistiveload :500WIncandescentlampload :500WHalogenlampload :500WInductivetransformers :500VATronictransformers :500WMixedloadresistive-inductive :500VAMixedloadresistive-capacitive :500W
Technical Data Switching Capacity
DA 1S
OperatingvoltageKNX
Operatingvoltage
PowerConsumptionKNX
Powerloss
Dimensions
Min.Switchingcapacity
Ambienttemperature
Protectionrating
Busvoltage,(<10mA)
230VAC,50/60Hz
150mW
4,5Wmax.
4modules
50W
-5°C...+45°C
IP20
SMART BUILDING AUTOMATION SYSTEMS
theaiq.com.tr
Minimumload :5WResistiveload :2500WCapacitiveload :1100W(max.140µF)Incandescent/halogenlampload :2500WType-dependentfluorescentlampswithEVG(duetovaryingswitch-onpeaks)
STANDART SERIES
Control Units for 1-10V EVG 3 Channels
Main Features
Technical Data Switching Capacity
CU 3 90992207
Order Number
Control Units
CU 3
OperatingvoltageKNX
Signalvoltage
Signalcurrent
PowerConsumption
Dimensions
Typeofcontact
Ambienttemperature
Protectionrating
Busvoltage,(<10mA)
1–10V
100mA(perchannel)
240mWmax.
4modules
Relaycontact,16A(at250VAC,cosϕ=1),10A(at250VAC,cosϕ=0,6)
-5°C...+45°C
IP20
Connection
31
• Forswitchinganddimmingoflightingcircuitsincombination withelectronicballastsorotherdimmable1-10Vdevices• “Soft-ON”,“Soft-OFF”andtimedimmerareconfigurable• Time-delayedswitch-offwhenbrightnessvaluedropsbelow theswitch-offbrightnessispossible• Multi-phaseconnectionispossible
• 1-10Voutputandoneswitchoutput(relaycontact)perchannel• Slideswitchesformanualcontroloftherelays(alsowithout busvoltage)• Noadditionalpowersupplyrequired
CU 3 3-Channel Module
CU 3
SMART BUILDING AUTOMATION SYSTEMS
HA 6 6-Channel Module
• Forswitchingofthermalactuatorsforheatersorcooling ceilings• Cancontrolupto6roomsusingthermalactuatorsforevery channel• Upto4thermalvalvedrivescanbeconnectedperchannel• Theoutputscanbecontrolledeitherwithswitchingorwith PWM
• Overload-protected,shortcircuit-protected• Protectionagainstjammingvalves
STANDART SERIES
Heating Actuator 6 Channels
Main Features
HA 6 90992204
Order Number
Heating Actuator
32
Connection
HA 6
• Summerandwinteroperationmode• Emergencyoperationincaseofbusfailure• Cyclicalmonitoringoftheinputsignalscanbeparameterized• Incaseofoverloadthedevicedetermineswhichoutputis involvedandswitchesitoff.Non-overloadedoutputs continuetowork,whichmeansthattheroomsinquestion arestillheated.
Technical Data Functions
HA 6
OperatingvoltageKNX
Operatingvoltage
Powerconsumption
Width
Typeofcontact
Voltageoutput
Switchingcurrentoutput
Switch-oncurrent
Ambienttemperature
Protectionrating
Busvoltage
230VAC,50/60Hz
125mWmax.
4modules
Triac
230VAC
5...50mA
1,5Amax.(2sec)
-5°C...+45°C
IP20
SMART BUILDING AUTOMATION SYSTEMS
theaiq.com.tr
Upto5differentfancoilsystemscanbeset:
• 2-pipesystemonlyheating (in1-channeland2-channeloperation)• 2-pipesystemonlycooling (in1-channeland2-channeloperation)• 2-pipesystemheating/coolingviachange-overobject (in1-channeland2-channeloperation)• 4-pipesystemheating/coolingviachange-overobject (onlyin1-channeloperation)• 4-pipesystemheating/coolingviacommandvalue specification(onlyin1-channeloperation)
STANDART SERIES
FCA 1 Fan Coil Actuator
Technical Data Functions
FCA 90992222
Order Number
Fan Coil Actuator
FCA
OperatingvoltageKNX
Operatingvoltage
PowerConsumptionKNX
PowerLoss
Dimensions
Typeofcontact
Switchingvoltage
Switchingcurrent
MinimumswitchingcurrentAC
Ambienttemperature
Protectionrating
Busvoltage,(<10mA)
230VAC,50–60Hz
150mW
3Wmax.
4modules
µcontact,potential-freeNOcontact
250VAC
10A
100mAmin.
-5°C...+45°C
IP20
Connection
33
Main Features
• Foroperationofventilatorconvectors(fancoilunits) implementedforroomairconditioning• Fancoilactuatorfor2-pipeand4-pipesystems• Connectionofonefancoilunitwithupto6fanlevelsor connectionoftwofancoilunitswithupto3fanlevelseach• Operatingmodesforheating,coolingorcombinedheating/ coolingoperation• LEDstatusindicationforoperation
• Freechannelscanbeusedforswitchingfunctionse.g.for roomlighting• Cyclicalorevent-orientedtransmission• Manualoperationondevice(fanstages,valveandswitching outputs)• Limitvaluescanbeset
Fan Coil Actuator
FCA 1-Channel operation FCA 2-Channel operation
SMART BUILDING AUTOMATION SYSTEMS
• Binaryinputsfortheconnectionof230VcontactstoKNX• Inputscanbeassignedvariousfunctionsorblocked independentlyofeachother• Freeassignmentofthefunctionsforswitching,dimming, shutterandvaluetransmittertoallinputsorpulsecountersand switchingcounterfunctionstoinputs1and2• LEDstatusindicationforeachchannel
• Multi-phaseconnectionispossible• Allinputscanbeoperatedwithdifferentvoltages• SeparatereferencepotentialsNforeachinput
STANDART SERIES
Binary Inputs 4 Channels for 230V
Main Features
BI 4 4-Channel Module
BI 4 90992228
Order Number
Binary Inputs
34
Connection
BI 4
Bymeansofparametersettings,thefollowingfunctionsarepossibleforeachinput:
• Switch/keyinput• Dimmercontrol• Controlofblinds• Valuator• Counter
Technical Data Switching Capacity
BI 4
OperatingvoltageKNX
Operatingvoltage
Inputcurrent
PowerConsumptionKNX
Powerlossmax.
Dimensions
Inputlinelength
Ambienttemperature
Protectionrating
Busvoltage,(<10mA)
110V...230VAC,50/60Hz
7mAat230VACperinput
150mW
1,7W
2modules
100mmax.
-5°C...+45°C
IP20
SMART BUILDING AUTOMATION SYSTEMS
theaiq.com.tr
• Binaryinputsfortheconnectionof230VcontactstoKNX• Inputscanbeassignedvariousfunctionsorblocked independentlyofeachother• Freeassignmentofthefunctionsforswitching,dimming, shutterandvaluetransmittertoallinputsorpulsecountersand switchingcounterfunctionstoinputs1and2• LEDstatusindicationforeachchannel
• Multi-phaseconnectionispossible• Allinputscanbeoperatedwithdifferentvoltages• SeparatereferencepotentialsNforeachinput
STANDART SERIES
Binary Inputs 8 Channels for 230V
Main Features
BI 8 8-Channel Module
BI 8 90992230
Order Number
Binary Inputs
35
Connection
BI 8
Bymeansofparametersettings,thefollowingfunctionsarepossibleforeachinput:
• Switch/keyinput• Dimmercontrol• Controlofblinds• Valuator• Counter
Technical Data Switching Capacity
BI 8
OperatingvoltageKNX
Operatingvoltage
Inputcurrent
PowerConsumptionKNX
Powerlossmax.
Dimensions
Inputlinelength
Ambienttemperature
Protectionrating
Busvoltage,(<10mA)
110V...230VAC,50/60Hz
7mAat230VACperinput
240mW
3,4W
4modules
100mmax.
-5°C...+45°C
IP20
SMART BUILDING AUTOMATION SYSTEMS
BI 6 90992229
STANDART SERIES
Binary Inputs 6 Channels for 24V
Main Features
Order Number
Binary Inputs
Connection
BI 6
36
• Switch/keyinput• Dimmercontrol• Controlofblinds• Valuator• Counter
By means of parameter settings, the following functions are possible for each input:
Technical Data Switching Capacity
BI 6
OperatingvoltageKNX
Operatingvoltage
Inputcurrent
PowerConsumptionKNX
Powerlossmax.
Dimensions
Inputlinelength
Ambienttemperature
Protectionrating
Busvoltage,(<10mA)
8V...42VAC/DC,50/60Hz
4mAat24VAC/DCperinput
225mW
2W
2modules
100mmax.
-5°C...+45°C
IP20
• Binaryinputsfortheconnectionof24VAC/DCcontactstoKNX• Inputscanbeassignedvariousfunctionsorblocked independentlyofeachother• Freeassignmentofthefunctionsforswitching,dimming, shutterandvaluetransmittertoallinputsorpulsecountersand switchingcounterfunctionstoinputs1and2• LEDstatusindicationforeachchannel
• ACandDCvoltagescanbeconnected• Separatereferencepotentialsforinputs1–3and4–6• Allinputscanbeoperatedwithdifferentvoltages
BA 2 2-Channel Module
SMART BUILDING AUTOMATION SYSTEMS
theaiq.com.tr
• ForcontrollingofluminariesandotherapplicationswithDALI operatingdeviceinKNXinstallationse.g.electronicballast• Eachgroupfeaturesthefullscopeoffunctionswithoutany restrictions.Functionscanbeparameterizedseparatelyfor eachgroup.Thisfeaturepermitsindependentandmulti- functionalcontroloftheDALIdevices• Adjustingthelimitvaluesforbrightnessispossible• Dimmingresponsecanbeparameterized
• AnindividualDALIdevicecanbeexchangedduringoperation withoutsoftware• TheconfigurationandcommissioningoftheDALIGateway takesplaceviaaplug-inthatisintegratedintotheETS3• Withshortcircuit,surgeandoverloadprotection
STANDART SERIES
DALI Gateway
Main Features
DALI Gateway 90992232
Order Number
DALI GATEWAY
37
Connection
DALI Gateway
• Controlofamaximumof64DALI devicesinamax.of32groups• Incorporationofthegroupsintoupto 16light-scenespossible• Centralswitchingfunction• Manualcontrolofthegroupsindependentofthebus (siteoperationwithbroadcastcontrol)• FeedbackofDALIerrorstatusorshort-circuit andsupplyvoltagefailuremessage• Soft-OnorSoft-Offfunction• Timerfunctions(ON-delay,OFF-delay,staircaselighting function,alsowithpre-warningfunction)
Technical Data Functions
DALI Gateway
OperatingvoltageKNX
Powerconsumption
Width
Operatingvoltage
NumberofDALIsubscribers
DALIratedvoltage
DALIratedcurrent
DALItransmissionrate
DALIprotocol
Ambienttemperature
Protectionrating
Busvoltage
150mWmax.
4modules
110V...240VAC,50Hz
64max.
16VDC
200mAmax.
1.2kbit/s
EN60929AnnexE4
-5°C...+45°C
IP20
SMART BUILDING AUTOMATION SYSTEMS
• OperationasNOorNCcontacts• Timefunctions,feedbackfunction,logicandrestraint function,extendedfeedback• Upto8internalscenesparameterizableperoutput
• Controlselectricallyoperatedblinds,shutters,awnings etc.withamainsvoltageof230VAC• Blind/shutterpositiondirectlycontrollable,slatposition directlycontrollable• Safetyfunctions,sunprotectionfunction,extended feedbackfunctions• Integrationinscenesandrestraints
Room Actuator 90992223
STANDART SERIES
Room Actuator
Main Features
Technical Data Functions
Order Number
Switching function
Blind function
Room Actuator
Room Actuator
OperatingvoltageKNX
Operatingvoltage
PowerConsumptionKNX
PowerLoss
Dimensions
Relaycontacts
Heatingoutputs
Ohmicload
Blind,fanmotors
Ambienttemperature
Protectionrating
Busvoltage,(<10mA)
230VAC,50–60Hz
150mW
6Wmax.
4modules
NOcontact,16A(at250VAC,cosϕ=1),
6A(at250VAC,cosϕ=0,6)
Triac0,05A(250VAC)
3000W
1380VA
-5°C...+45°C
IP20
Connection
38
• Forcontrollingthreefunctionssimultaneouslyinonedevice suchaslighting,blindsandheating• Fourrelayoutputscanbeseteitherforblindoperationor alternativelyforswitchingoperation.• Mixedoperationispossible• Twoadditionaltriacoutputsallowsilentcontrolofelectro thermalvalvedrivesforheatingorcoolingsystems• LEDstatusindicationforoperation
• Bycombiningthefunctionsoftheroomactuator’soutputs,in manycasesitispossibletoplanandexecuteelectrical installationsonaroom-specificbasis• SwitchingoperationorPWMoperation• Short-circuitandoverloadprotection• Manualoperationondevice• Emergencyoperation
Room Actuator
15
SMART BUILDING AUTOMATION SYSTEMS
MIXSERIES
Switch Actuators
Blind Actuators
Dimming Actuators
Control Units
Heating Actuator
Fan Coil Actuator
Binary Inputs
SMART BUILDING AUTOMATION SYSTEMS
theaiq.com.tr
• Forswitching8independentloadsofmax.16Aperchannel• Extendableto16channelswithonebaseandoneextension moduleor24channelswithonebaseandtwoextension modules.• RemovableKNXbusmoduleenablesdevicestobechanged withoutreprogramming• Adjustablecharacteristics:e.g.switching,delayedswitching, pulsefunction• Links,typeofcontact(NCcontact/NOcontact)and participationincentralcommandssuchaspermanentOn, permanentOff,centralswitchingandsave/callupscene• Switchingfunctions:e.g.On/Off,pulse,On/Offdelay,staircase lightwithwarning
• Logicaloperationse.g.Disable,AND,enable,OR• Manualset-upanduseofswitchactuatorsispossiblewithout KNXbusmodule• Manualoperationondevice(alsowithoutbusvoltage)• LEDstatusindicationforeachchannel
MIX SERIES
Switch Actuators 8/16/24 Channels
Main Features
RSA 8S 8-Channel Base Module RSE 8S 8-Channel Extension Module
RSA 8S 90990017RSE 8S 90990018
Order Number
Switch Actuators
41
Connection
RSA 8S RSE 8S
Resistiveload :3680WIncandescentlampload :1000WHVhalogenlampload :2300WFluorescentlampload(conventional)parallel-corrected :2x58W(7µF),3x36W(4,5µF), max.120W(14µF)Fluorescentlampload(conventional)notcorrected :14x58W,20x36W, max.1000VAFluorescentlampload(electronicballast) :3x36W,2x58W,max.120WHigh-pressuremetalvapourlamps :1x70WEnergysavinglamps :6x7W,4x11W,2x15W, 2x20W,2x23WLEDlamp :<2W:5W|>2W<8W:15W
Technical Data Switching Capacity
RSA 8S RSE 8S
OperatingvoltageKNX
Operatingvoltage
PowerConsumption
Dimensions
Typeofcontact
Voltageoutput
Ambienttemperature
Protectionrating
110–240VAC,45–65Hz
Busvoltage,(<10mA) -
3,6VA 3VA
4modules
NOcontact,16A(at250VAC,cosϕ=1),3A(at250VAC,cosϕ=0,6)
250VAC,0–65Hz
-5°C...+45°C
IP20
C1 C4
L N
3 4
NLL
C2
5 6 9 10
C3
7 8
C6 C8
13 14
C5
11 12 17 18
C7
15 16
KNX
C1 C4
3 4
NLL
C2
5 6 9 10
C3
7 8
C6 C8
13 14
C5
11 12 17 18
C7
15 16
SMART BUILDING AUTOMATION SYSTEMS
• Forswitching4independentloadsofmax.16Aperchannel• Extendableto8channelswithonebaseandoneextension moduleor12channelswithonebaseandtwoextension modules.• Freecombinationofswitches,dimming,blinds,heatingcontrol andbinaryinputswithonebaseandtwoextensionmodules• LEDstatusindicationforeachchannel• Switchingfunctionse.g.On/Off,pulse,On/Offdelay,staircase lightwithwarning
• Logicaloperationse.g.Disable,AND,enable,OR• ManualswitchwithOn/Off/Bussettings(alsowithoutbus voltage)
Resistiveload :3680WCapacitiveload :max.42µFIncandescentlampload :2300WHalogenlampload :2300WFluorescentlampload(conventional)lead-lagcircuit :10x(2x58W),5x(2x100W)Fluorescentlampload(conventional)parallel-corrected :10x40W(4.7µF),20x58W(7µF),2x100W(18µF)Fluorescentlampload(conventional)notcorrected :26x40W,20x58W,10x100W
RSA 4S 90990001RSE 4S 90990002
MIX SERIES
Switch Actuators 4/8/12 Channels
Main Features
Technical Data Switching Capacity
Order Number
RSA 4S 4-Channel Base Module RSE 4S 4-Channel Extension Module
Switch Actuators
RSA 4S RSE 4S
OperatingvoltageKNX
Operatingvoltage
PowerConsumption
Dimensions
Typeofcontact
Ambienttemperature
Protectionrating
230VAC,50Hz
2,5VA
4modules
NOcontact,16A(at250VAC,cosϕ=1),10A(at250VAC,cosϕ=0,6)
-5°C...+45°C
IP20
Busvoltage,(<10mA)
Connection
RSA 4S RSE 4S
42
C1
L N
3 4 5 6 7 8
N
KNX
LL
C2 C3 C4
9 10
C1
L N
3 4 5 6 7 8
NLL
C2 C3 C4
9 10
SMART BUILDING AUTOMATION SYSTEMS
theaiq.com.tr
• Forswitching4independentcapacitiveloadsofmax. 16Aperchannel• Extendableto8channelswithonebaseandoneextension moduleor12channelswithonebaseandtwoextension modules.• Freecombinationofswitches,dimming,blinds,heatingcontrol andbinaryinputswithonebaseandtwoextensionmodules• LEDstatusindicationforeachchannel• Switchingfunctionse.g.On/Off,pulse,On/Offdelay,staircase lightwithwarning
• Logicaloperationse.g.Disable,AND,enable,OR• ManualswitchwithOn/Off/Bussettings(alsowithoutbus voltage)
Resistiveload :3680WCapacitiveload :max.200µFIncandescentlampload :3680WHalogenlampload :3680WFluorescentlampload(conventional)lead-lagcircuit :3680WFluorescentlampload(conventional)parallel-corrected :2500W(200µF)Fluorescentlampload(conventional)notcorrected :3680W
RSA 4C-Load 90990005RSE 4C-Load 90990006
MIX SERIES
Switch Actuators C-Load 4/8/12 Channels
Main Features
Technical Data Switching Capacity
Order Number
RSA 4C-Load 4-Channel Base Module RSE 4C-Load 4-Channel Extension Module
Switch Actuators
RSA 4C-Load RSE 4C-Load
OperatingvoltageKNX
Operatingvoltage
PowerConsumption
Dimensions
Typeofcontact
Ambienttemperature
Protectionrating
230VAC,50Hz
2,5VA
4modules
NOcontact,16A(at250VAC,cosϕ=1),10A(at250VAC,cosϕ=0,6)
-5°C...+45°C
IP20
Busvoltage,(<10mA) -
Connection
RSA 4C-Load RSE 4C-Load
43
C1
L N
3 4 5 6 7 8
N
KNX
LL
C2 C3 C4
9 10
C1
L N
3 4 5 6 7 8
NLL
C2 C3 C4
9 10
SMART BUILDING AUTOMATION SYSTEMS
• Forcontrollingdevicesforblinds,shutters,sunandvision protectiondevices,skylightsandventilationflaps• Extendableto8channelswithonebaseandoneextension moduleor12channelswithonebaseandtwoextension modules.• Freecombinationofswitches,dimming,blinds,heatingcontrol andbinaryinputswithonebaseandtwoextensionmodules• Copyfunctionforfastconfiguration
• FloatingcontactsforUpandDownperchannel• LEDUpandDownswitchingstatusdisplayforeachchannel• Manualoperationondevice(evenwithoutbusconnection)
• Controllingawnings,blinds,shuttersandvarioussun andvisibilityprotectiondevices• Controllingskylightsandventilationflaps(withlimitswitches)• Shadingforgreenhouses,conservatoriesetc.
JSA 4S 90990015JSE 4S 90990016
MIX SERIES
Blind Actuators 4/8/12 Channels
Main Features
Technical Data Functions
Order Number
JSA 4S 4-Channel Base Module JSE 4S 4-Channel Extension Module
Blind Actuators
JSA 4S JSE 4S
OperatingvoltageKNX
Operatingvoltage
PowerConsumption
Dimensions
Typeofcontact
Ambienttemperature
Protectionrating
Busvoltage,(<8mA)
230VAC,50Hz
2,5VA
4modules
NOcontact,3A(at250VAC,cosϕ=1)
-5°C...+45°C
IP20
-
44
Connection
JSA 4S JSE 4S
NL1L2
C3
M
M M
C1 C2
LN
C4
M
KNX
NL
C3
M
M M
C1 C2
LN
C4
M
SMART BUILDING AUTOMATION SYSTEMS
theaiq.com.tr
• Forswitching2independentloadsofmax.16Aperchannel• Extendableto4channelswithonebaseandoneextension moduleor6channelswithonebaseandtwoextension modules.• Freecombinationofswitches,dimming,blinds,heatingcontrol andbinaryinputswithonebaseandtwoextensionmodules• LEDstatusindicationforeachchannel• Withboostermoduletheoutputofbaseandextensiondimming actuatorsmodulescanbedoubledto:2x600W/VA(2channels) or1x1000W/VA(1channel)
• Switchingfunctionse.g.On/Off,pulse,On/Offdelay,staircase lightwithwarning• Logicaloperationse.g.Disable,AND,enable,OR• ManualswitchwithOn/Off/Bussettings(alsowithoutbus voltage)
DSA 2 90990007DSE 2 90990008DSB 2 90990045
MIX SERIES
Dimming Actuators 2/4/6 Channels
Main Features
Order Number
DSA 2 2-Channel Base Module DSE 2 2-Channel Extension Module DSB 2 2-Channel Booster Module
Dimming Actuators
Connection
DSA 2
45
DSE 2 DSB 2
Ohmicload :3680WCapacitiveload :max.42µFIncandescentlampload :2300WHVhalogenlampload :2300WFluorescentlightsuncompensated :26x40W,20x58W,10x100WParallelcompensated :10x40W(4,7µF),20x58W (7,0µF),2x100W(18µF)Dualswitch(KVG) :10x(2x58W),5x(2x100W)
Technical Data Switching Capacity
DSA DSE DSB
OperatingvoltageKNX
Operatingvoltage
PowerConsumption
Dimensions
Min.Switchingcapacity
Max.symmetricalswitchingcapacity
Max.asymmetricalswitchingcapacity
Ambienttemperature
Protectionrating
Busvoltage,(<10mA)
230VAC,50Hz
4modules
-5°C...+45°C
IP20
1VA
10W/VA
2x300W/VA
1x500W/VA
0,5VA
300W
Upgradeto2x300W/VA
Upgradeto1x500W/VA
--
C1
≤600 W ≤600 W
1 2
N
KNX
DMG 2 KNX DMB 2 KNX
LL
C2
3 4
C1
1 2
C2
3L L L L
4
C1
≤300 W ≤300 W
1L
2
N
KNX
LL
C2
3L
4
C1
≤300 W ≤300 W
1 2
NLL
C2
3L L
4
SMART BUILDING AUTOMATION SYSTEMS
• Forswitchinganddimmingoflightingcircuitsincombination withelectronicballasts• Extendableto4channelswithonebaseandoneextension moduleor6channelswithonebaseandtwoextension modules.• Freecombinationofswitches,dimming,blinds,heatingcontrol andbinaryinputswithonebaseandtwoextensionmodules• LEDstatusindicationforeachchannel
• 1-10Voutputandoneswitchoutput(relaycontact)perchannel• Withzero-crossswitchingforswitchingwithoutrelays• ManualswitchwithOn/Off/Bussettings(alsowithoutbus voltage)
Minimumload :5WResistiveload :3680WCapacitiveload :1100W(max.140µF)Incandescent/halogenlampload :2500WType-dependentfluorescentlampswithEVG(duetovaryingswitch-onpeaks)
MIX SERIES
Control Units for 1-10V EVG 2/4/6 Channels
Main Features
Technical Data Switching Capacity
SSA 2 2-Channel Base Module
SSA 2 90990009SSE 2 90990010
Order Number
SSE 2 2-Channel Extension Module
Control Units
SSA 2 SSE 2
OperatingvoltageKNX
Operatingvoltage
Signalcurrent
PowerConsumption
Dimensions
Typeofcontact
Ambienttemperature
Protectionrating
230VAC,50Hz
100mA(perchannel)
2VA
4modules
NOcontact,16A(at250VAC,cosϕ=1),10A(at250VAC,cosϕ=0,6)
-5°C...+45°C
IP20
Busvoltage,(<10mA)
46
Connection
SSA 2 SSE 2
C1
L N
31
EVG2
3
4
–
+
L1
N
4 + – + –7 8
N
KNX
LL
C1 C2 C2
–
LED Controller1-10 V DIM
+–
+
L1
N
C1
L N
31
EVG2
3
4
–
+
L1
N
4 + – + –7 8
NLL
C1 C2 C2
–
LED Controller1-10 V DIM
+–
+
L1
N
SMART BUILDING AUTOMATION SYSTEMS
theaiq.com.tr
• Forcontrollingthermalactuators• Extendableto8channelswithonebaseandoneextension moduleor12channelswithonebaseandtwoextension modules.• Freecombinationofswitches,dimming,blinds,heatingcontrol andbinaryinputswithonebaseandtwoextensionmodules• LEDstatusindicationforeachchannel• Heatingactuatorfor24Vor230Vactuators• Cancontrolupto4roomsusingthermalactuatorsforevery channel
• Upto5positioningactuatorsperchannel• Silentsemiconductorswitch(triac)• ManualswitchwithOn/Off/Bussettings(alsowithoutbus voltage)
• Channel-wiseselectionoftheoperatingmodebetween switchingandcontinuouscontrol.• Monitoringthe“Controlvariable”object:Anemergency programisstartedifacontrolvariablefails.• Overridingoptionofthecontrolvariableusingthe “Compulsoryoperationmode”object.• Aheatingactuatorcanbedeactivatedusingthe“Summer mode”object.• Avalveprotectionprogramcanbeexecutedifdesired.• Determiningthemaximumcontinuouscontrolvariablefor theadvancecontrolofaboiler.
HSA 4 90990013HSE 4 90990014
MIX SERIES
Heating Actuators 4/8/12 Channels
Main Features
Technical Data Functions
Order Number
HSA 4 4-Channel Base Module HSE 4 4-Channel Extension Module
Heating Actuators
HSA 4 HSE 4
OperatingvoltageKNX
Operatingvoltage
PowerConsumption
Dimensions
Typeofcontact
Voltageoutput
Ambienttemperature
Protectionrating
230VAC,50Hz
2,5VA
4modules
Triac0,5A
24VAC,250VAC
-5°C...+45°C
IP20
Busvoltage,(<10mA)
47
Connection
HSA 4 HSE 4
H1
L N
3 4 5 6 7 8
NLL
H2 H3 H4
9 10
KNX
H1
L N
3 4 5 6 7 8
NLL
H2 H3 H4
9 10
SMART BUILDING AUTOMATION SYSTEMS
MIX SERIES
Heating Actuators with triacs 6/12 Channels
HST 6 6-Channel Module HST 12 12-Channel Module
Heating Actuators
Connection
HST 6
48
• Forcontrollingthermalactuators(24V)• Channel-wiseselectionofthemodebetweenON/OFFand continuouscontrol• Theheatingactuatorisdeactivatedusingthe“Summermode” object• Inthesummermode,avalveprotectionprogramcanbe implementedifdesired• Automaticreleaseofthethermalconnectedvalveafter switch-on• Canbeinstalleddirectlyonawallorarailintheheatingcircuit distributor• Mainsplugontransformerforeasyinstallation
• Calculationofthemaximumcontinuousactuatingvalueforthe flowcontrolofaboiler• Emergencyprogramincaseoftimeoutoftheactuatingvalue• Integratedpowersupplyforamaximumof13thermalactuators• Silentswitchingthankstotriacoutputs
Main Features
HST 6 90990046HST 12 90990047
Order Number
TheHST6cancontrolupto6roomsthroughamaximumof4thermalconnectedvalvesperchannel.
TheHST12cancontrolupto12roomswithamaximumof2connectedvalveseach.
ThetotalnumberofconnectedvalvesfortheHST6aswellastheHST12amountstomaximum13.
Technical Data Functions
HST 6 HST 12
OperatingvoltageKNX
Operatingvoltage
PowerConsumption
Dimensions
Typeofcontact
Ambienttemperature
Protectionrating
Busvoltage,(<10mA)
230VAC,50-60Hz
2,5VA
70x75x302mm
Triac2A
-5°C...+50°C
IP20
1
NL
2 3 4 5 6
KNX
SMART BUILDING AUTOMATION SYSTEMS
theaiq.com.tr
• Fancoilactuatorfor2-pipeand4-pipesystems• Controlsafancoilwithheatingorcoolingvalveandupto3fan steps.• Suitablefor2-wayand3-wayvalves• 2inputsforwindowcontactorremotetemperaturesensorand driptraymonitoring• Anadditionalrelayenablestheactuationofanelectricalheater bankoralternativelyanelectricalcoolerbank• Adjustmentofset-pointvalueforcoolinginrelationtoexternal temperature• LEDstatusindicationforoperation
• Optionalinternalorexternaltemperaturecontrols• TheinternalcontrollercanbeusedasaPoraPIcontroller• TheintegratedcontrollerhasfouroperatingmodesofComfort, Standby,NightmodeandFrostprotectionmode• Manualoperationondevice(fanstages,switchingbetween heatingandcooling)• Withemergencyprogram
• 3redLEDsfordisplayingthefanstep(S1...S3)• 1redLEDforheatingoperation• 1blueLEDforcoolingoperation• 1redLEDfortheauxiliaryrelay(C1)• 2redLEDsforinputs1and2(E1,E2)• 1redLEDfortestmode• 1pushbuttonforthefansteps• 1pushbuttonforheating/coolingoperation
FCA 1 90990025
MIX SERIES
FCA 1 Fan Coil Actuator
Main Features
Technical Data Operation and Display
Order Number
FCA 1 Fan Coil Actuator
Fan Coil Actuator
FCA 1
OperatingvoltageKNX
Operatingvoltage
PowerConsumption
StandbyConsumption
Dimensions
Typeofcontact
SwitchingCapacityvalves(triacs)
SwitchingCapacity,additionalrelay
SwitchingCapacity,ventilatorrelay
Ambienttemperature
Protectionrating
Busvoltage,(<10mA)
230VAC,50–60Hz
3VA
1,9W
4modules
Triac
0,5A(24–230VAC)
16A
8A
-5°C...+45°C
IP20
49
Connection
FCA 1
C-
+C°
C+ LC LH H+ H-
L
M
N S1 S2
NLL
L C1
S3 LS
E1 E2
M
SMART BUILDING AUTOMATION SYSTEMS
• Binaryinputmodulewithawiderangeofinputvoltage• Extendableto12channelswithonebaseandone extensionmoduleor18channelswithonebaseandtwo extensionmodules.• Freecombinationofswitches,dimming,blinds,heating controlandbinaryinputswithonebaseandtwo extensionmodules• LEDstatusindicationforeachchannel
• Multi-voltageinput8-250AC/DCorauxiliarysupplyfrom device(approx.18VAC/20mA)• Allinputscanbeoperatedwithdifferentvoltages
Bymeansofparametersettings,thefollowingfunctionsarepossibleforeachinput:
• Switch/keyinput• Dimmercontrol• Controlofblinds• Valuator• Counter• Send2telegrams
BSA 6 90990011BSE 6 90990012
MIX SERIES
Binary Inputs 6/12/18 Channels
Main Features
Technical Data Switching Capacity
Order Number
BSA 6 6-Channel Base Module BSE 6 6-Channel Extension Module
Binary Inputs
BSA 6 BSE 6
OperatingvoltageKNX
Operatingvoltage
PowerConsumption
Dimensions
Voltage/powerconsumptioninputs
Output(auxiliary)
Ambienttemperature
Protectionrating
Busvoltage,(<10mA)
230VAC,50Hz
2,5VA
4modules
8–250VAC/DC3mA
18VAC/20mA
-5°C...+45°C
IP20
-
50
Connection
BSA 6 BSE 6
I1 I2 I3
L N
7 8
I4 I5 I6
9
1413 1615 1817
10
N
8 V AC/DC
LL
11 12
5 643
KNX
I1 I2 I3
L N
7 8
I4 I5 I6
9
1413 1615 1817
10
N
8 V AC/DC
LL
11 12
5 643
SMART BUILDING AUTOMATION SYSTEMS
theaiq.com.tr
MIX SERIES COMBINATION EXAMPLES
MIX SERIESCombination Examples
51
SMART BUILDING AUTOMATION SYSTEMS
MIX SERIES COMBINATION EXAMPLES
COMBINATION EXAMPLES
4XSwitching+4xDimming
8xSwitching+4xCLoad
6xBinaryInput+4xSwitching+2xDimming
2x1-10vDimming+6xBinaryInput+4xSwitching
4xHeating+6xBinaryInput+4xSwitching
4xBlind+4xSwitching+4xCLoad
4xBlind+2Dimming+6BinaryInput
12xSwitching
12xCLoad
6xDimming
6x1-10vDimming
18xBinaryInput
12xHeating
12xBlind
BASEMODULE
RSA4S
RSA4S
BSA6
SSA2
HSA4
JSA4S
JSA4S
RSA4S
RSA4C
DSA2
SSA2
BSA6
HSA4
JSA4S
EXTENSION
DSE2
RSE4S
RSE4S
BSE6
BSE6
RSE4S
DSE2
RSE4S
RSE4C
DSE2
SSE2
BSE6
HSE4
JSE4S
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
EXTENSION
DSE2
RSE4C
DSE2
RSE4C
RSE4C
RSE4C
BSE6
RSE4S
RSE4C
DSE2
SSE2
BSE6
HSE4
JSE4S
52
SMART BUILDING AUTOMATION SYSTEMS
theaiq.com.tr 15
SMART BUILDING AUTOMATION SYSTEMS
FIELDEQUIPMENTS
SMART BUILDING AUTOMATION SYSTEMS
Binary Inputs
Push Buttons
Room Thermostat
Presence Detectors
Brightness Sensor
Weather Station
SMART BUILDING AUTOMATION SYSTEMS
theaiq.com.tr
• Binaryinputmoduleswith2,4or6inputsforfloatingswitch/ pushbuttoncontacts• Canbeinstalledincombinationwithconventionalpush buttons/switchesinflush-mountedsockets• Inputscanbereconfiguredtooutputs:binaryinput: potential-freecontact/binaryoutput:1mA(lowcurrent) (LED1mAtypes)• Adjustableresponsetorestorationofthebussupply
Thefollowingfunctionscanbeconfigured:• Switch/pushbuttoninput• Dimmercontrol• Controlofblinds• Value• Upto4CommandLED(WithBI6-way,onlyC1...C4)
BI 2-way 90990035BI 4-way 90990036BI 6-way 90990037
FIELD EQUIPMENTS
Binary Inputs for flush-mounted sockets 2/4/6 way
Main Features
Technical Data Input Functions
Order Number
BI 2-way Binary Input BI 6-way Binary InputBI 4-way Binary Input
Binary Inputs
BI 2-way BI 4-way BI 6-way
OperatingvoltageKNX
OutputconfigurationLED
Contactvoltage
Contactcurrent
InterfaceExtensionmax.
Ambienttemperature
Protectionrating
Busvoltage,(<10mA)
Lowcurrent1mA(LED1mAtypes)withoutseriesresistor
3,3V
0,5mA
5m
-5°C...+45°C
IP20
Connection
BI 2-way BI 4-way BI 6-way
C1 C2
KNX
C1 C2 C3 C4
KNX
C1 C2 C3 C4 C5 C6
KNX
55
SMART BUILDING AUTOMATION SYSTEMS
FIELD EQUIPMENTS
Push Buttons
TSA 2x1 TSA 4x2 TSA 6x3
Push Buttons
• Foroperatingswitching,dimming,blindsandrecall/savelight scenefunctionsindividually• Canbeusedtosendtemperature,priority,percentage,HVAC operationmodevalue• Scenefunctionscanbesavedbypressing3-4secondsiffoldis programmedasrecall/savelightscene• Settingofdesiredbehaviourvialongandshortkeydepression ispossible• WithLEDstatusindication
• CanbelocatedintoallframesofTheaModularSeries;Optima, SistemaandUltima
• Switching• Dimming• Blinds• Recall/savelightscene
TSA 2x1 9099XY19*TSA 4x2 9099XY20*TSA 6x3 9099XY24*
Main Features
Technical Data Functions
Order Number
TSA 2x1 TSA 4x2 TSA 6x3
OperatingvoltageKNX
Dimensions(mm)
Ambienttemperature
Protectionrating
Busvoltage,(<10mA)
-5°C...+45°C
IP20
44,4x49,1x37,9(2M) 67,1x49,6x37,9(3M)
Scale Drawings
TSA 2x1 TSA 4x2 TSA 6x3
(*) see page 65 for XY colour code equivalents and frame alternatives
66.6
56
SMART BUILDING AUTOMATION SYSTEMS
theaiq.com.tr
• Foroperatingswitching,dimming,blindsandrecall/savelight scenefunctionsindividually• Canbeusedtosendtemperature,priority,percentage,HVAC operationmodevalue• Scenefunctionscanbesavedbypressing3-4secondsiffoldis programmedasrecall/savelightscene• Settingofdesiredbehaviourvialongandshortkeydepression ispossible• WithLEDstatusindication
• CanbelocatedintoallframesofTheaModularSeries;Optima, SistemaandUltima
FIELD EQUIPMENTS
Push Buttons
Main Features
TSA 8x4 (2M) 9099XY21*TSA 8x4 (4M) 9099XY59*
Order Number
Push Buttons
Scale Drawings
TSA 8x4 (2M) TSA 8x4 (4M)
• Switching• Dimming• Blinds• Recall/savelightscene
Technical Data Functions
TSA 8x4 (2M) TSA 8x4 (4M)
OperatingvoltageKNX
Dimensions(mm)
Ambienttemperature
Protectionrating
Busvoltage,(<10mA)
44,4x49,1x37,9(2M)
-5°C...+45°C
IP20
89,5x49,2x37,9(4M)
(*) see page 65 for XY colour code equivalents and frame alternatives
TSA 8x4 (2M) TSA 8x4 (4M)
88.9
57
SMART BUILDING AUTOMATION SYSTEMS
• Individualroomthermostatforcontrollingheatingactuators andfancoilunits• Canbeusedascontinuousortwopointcontrol.• ContinuousPIcontrolcanbeconfiguredfortwostageorfor heatingandcooling• Cansupporttheoperatingmodesascomfort,night/standby, frostprotection,presence,windowstatus• LCDfordisplayingallfunctions,actualtemperatureandalso date• Operationmodeandtemperaturesetvaluecanbechangedby
userviabuttons• CanbelocatedintoallframesofTheaModularSeries;Optima, SistemaandUltima
FIELD EQUIPMENTS
Digital Room Thermostat
Main Features
Room Thermostat 9099XY23*
Order Number
Room Thermostat
Scale Drawings
Room Thermostat
• Heatingonly• Heatingandcooling• 2-stageheatingwithswitchingadditionalstage• 2-stageheatingwithcontinuousadditionalstage
Technical Data Functions
Room Thermostat
OperatingvoltageKNX
SettingRange
Measurabletemperaturerange
Dimensions(mm)
Ambienttemperature
Protectionrating
Busvoltage,(<10mA)
6°C...42°C
-20°C...+60°C
44,4x49,1x37,9(2M)
-5°C...+45°C
IP20
(*) see page 65 for XY colour code equivalents and frame alternatives
58
SMART BUILDING AUTOMATION SYSTEMS
theaiq.com.tr
FIELD EQUIPMENTS
Presence Detector for wall installation
Main Features
PSD 180 9099XY22*(*) see page 65 for XY colour code equivalents and frame alternatives
Order Number
Presence Detectors
• AutomaticcontroloflightingandHVAC• PresenceoutputforHVACcontrolwithswitch-offdelay• Lightingcontrolwithlightthresholdvalueandself-learning switch-offdelay
Technical Data Function
PSD 180
OperatingvoltageKNX
Recommendedinstallationheight
Brightnesssettingrange
Detectionangle
Lightswitch-offdelay
Presenceswitch-offdelay
Dimensions
Ambienttemperature
Protectionrating
Busvoltage
1,2–2m
100–1600lx
180°
30s–20min
30s–60min
44,4x49,2x49,4(2M)
0°C...+45°C
IP20
Scale Drawings
59
• Passiveinfraredpresencedetector• Forcontrollinglightning,ventilationetc.particularlyinoffices andhallways• Thesquaredetectionareaallowsaccurateandsimpleplanning• Thelightingswitchesonwithdarknessandpresenceandoff withsufficientlightorabsence• Theself-learningswitch-offdelayadjuststooccupants’ behaviour• Masterorslaveoperatingmodeisselectedviaconfiguration• Testoperationmodechecksthedetectionareaand
configuration• Choiceoffullyorsemiautomaticoperation• TheparametersaresetbyETSorpotentiometer
PSD 180 Presence Detector
PSD 180
SMART BUILDING AUTOMATION SYSTEMS
FIELD EQUIPMENTS
Presence Detectors for Ceiling Installation
PSD 360 PSD 2-IR DUAL EIB
• Passiveinfraredpresencedetector• Forcontrollinglightning,ventilationetc.particularlyinoffices andhallways• Thepresencedetectorhas“Genuinedaylightmeasurement” andisonlysuitableforswitchingfluorescentlamps(FL/PL)• Thesquaredetectionareaallowsaccurateandsimpleplanning• Thelightingswitchesonwithdarknessandpresenceandoff withsufficientlightorabsence• Theself-learningswitch-offdelayadjuststooccupants’ behaviour
• Masterorslaveoperatingmodeisselectedviaconfiguration• Testoperationmodechecksthedetectionareaand configuration• Choiceoffullyorsemiautomaticoperation• TheparametersaresetbyETSorpotentiometer
PSD 360 90990031PSD 2-IR DUAL EIB 90990032
Main Features
Order Number
Presence Detectors
60
Scale Drawings
PSD 360 PSD 2-IR DUAL EIB
• AutomaticcontroloflightingandHVAC• PresenceoutputforHVACcontrolwithswitch-offdelay• Lightingcontrolwithlightthresholdvalueandself-learning switch-offdelay
• Automaticcontrolfortwolightingzones• Lightingcontrolwithtwolightthresholdvaluesandself- learningswitch-offdelay• Twobrightnessmeasurements
Technical Data Functions
PSD 360
PSD 2-IR DUAL EIB
PSD 360 PSD 2-IR DUAL EIB
OperatingvoltageKNX
Recommendedinstallationheight
Brightnesssettingrange
Detectionangle
Lightswitch-offdelay
Presenceswitch-offdelay
Lightmeasurement
Ambienttemperature
Protectionrating
2–3,5m
100–1600lx
360°
30s–20min
Busvoltage
30s–60min
Genuinedaylightmeasurement
0°C...+45°C
IP40
-
(*) KNX bus coupler (90090954) required
SMART BUILDING AUTOMATION SYSTEMS
theaiq.com.tr
• Theswitchingbehaviourofthepresencedetectoriscontrolled bypresenceandlight,orasrequiredinswitchingorconstant lightcontroloperationmodes• Inthe“switching”operationmode,lightingswitchesonwith darknessandpresenceandoffwithsufficientlightorwhen nobodyispresent.Inthe“constantlightcontrol”operation modethesensorcontrolstheartificiallightdaylight-dependent onaconstantlightinglevel.• In“Fullyautomatic”mode,thelightingswitchesonandoff automaticallyaccordingtopresenceandlight;in“Semi- automatic”mode,itmustbeswitchedonmanuallyandit switchesoffautomatically• Squaredetectionareaforcorridors
• PresenceoutputforHVACcontrolwithswitch-ondelayand switch-offdelay• Theself-learningswitch-offdelaytimeadjuststooccupants’ behaviour• Manualoverride:Lightingordimmingcanbemanually controlledatanytime• Testoperationmodechecksthedetectionareaandconfiguration• Amaximumof10detectorscanbeswitchedatthesametime• Integratedbuscoupling
• Master/slaveparallelswitching:Severaldetectorscanbe connectedwitheachothertoincreasethedetectionarea.The mastercontrolslightingandHVAC.Allotherdetectorsmerely providepresenceinformationasslaves• Master/masterparallelswitching:Severaldetectorscanbe connectedwitheachothertocontrolseverallightinggroups.Every mastercontrolsitslightinggroupaccordingtoitsownbrightness measurements.Presenceisdetectedbyallthedetectors• Masterorslaveoperatingmodeisselectedviaconfiguration
Motion Detector 90990057
FIELD EQUIPMENTS
Presence Detector Compact Passage
Main Features
Technical Data Functions
Order Number
Presence Detectors
Motion Detector
OperatingvoltageKNX
Recommendedinstallationheight
Detectionangle
Installationtype
Brightnessmeasuringrange
Lightswitch-offdelay
Lightstand-bytime
Presenceswitch-offdelay
Presenceswitch-ondelay
Ambienttemperature
Protectionrating
Busvoltage
2–3m
360°
Ceilinginstallation
10–1500lx
30s–20min
0s–60min
30s–120min
0s–30min
0°C...+50°C
IP40
Scale Drawings
Motion Detector
61
SMART BUILDING AUTOMATION SYSTEMS
FIELD EQUIPMENTS
Presence Detector Compact Passage
Presence Detectors
PSD 360 / PSD 2-IR DUAL
Mounting height (A) Walking (C)Sitting (B)
2m
2,5m
3m
3,5m
4m
20m2|4,5mx4,5m
36m2|6mx6m
49m2|7mx7m
64m2|8x8m
-
36m2|6mx6m±0,5m
64m2|8mx8m±0,5m
81m2|9mx9m±0,5m
100m2|10mx10m±1m
121m2|11mx11m±1m
Compact Passage
Mounting height (A) Diagonally (t)Head on to (r)
2m
2,5m
3m
3,5m
56m2|16mx3,5m±1m
72m2|18mx4m±1m
90m2|20mx4,5m±1m
100m2|20x5m±1m
105m2|30mx3,5m±1m
120m2|30mx4m±1m
135m2|30mx4,5m±1m
150m2|30mx5m±1m
PSD 180
Mounting height (A) Walking (C)Sitting (B)
2,2m 25m2|7mx3,5m 100m2|8m
62
SMART BUILDING AUTOMATION SYSTEMS
theaiq.com.tr
• Forbrightnessdependentcontrolling• Thresholdvalues,dimminglevelsandswitchdelayadjustable• 3thresholdswitchesintegrated• Thresholdcanbesetbetween1and20000Lux• Behaviouradjustableifthresholdsareexceededornotmet• Choiceof1–100luxor100–20000luxmeasuringranges• 3configurablethresholds
• Upto4differentbrightnesslevelscanbemonitored• Eachsectioncanbeallocatedonelightsettingconsistingof3 switchingobjectsand1dimmingobject• Surfacemountedlightsensorincludedindelivery
FIELD EQUIPMENTS
Brightness Sensor 3 Channels
Main Features
GIS 1
GIS 1 90990058
Order Number
Brightness Sensor
63
Technical Data
GIS 1
OperatingvoltageKNX
Numberofchannels
On/offswitchingdelay
Width
Brightnessmeasuringrange
Max.cablelengthtosensor
Ambienttemperature
Protectionrating
Busvoltage(≤10mA)
3
8s–240min
2modules
1–20000lux
100m
-5°C...+45°C
IP20
SMART BUILDING AUTOMATION SYSTEMS
• Combinationsensorformeasuringwind,rain,brightnessand temperature• Rainsensorwithheater(withconnectionat230VAC)• Measurementandevaluationdirectlyondevice• Adelaycanbesetforafterrainhasstoppedtoprevent unnecessarymovementofblinds• Sunprotectionforuptothreefacadespossible
• 2differentchanneltypesareuniversalchannelsandthesun protectionchannels• Theautomatedsunprotectionmechanismindependently controlstheblinds(shutter/awning)duringthedaywithout manualintervention.
• Thebrightnessisabove/belowthethreshold• Thetemperatureisabove/belowthethreshold• Thewindspeedisabove/belowthethreshold• Therainispresent/notpresent
• Adawn/duskthreshold• 3brightnessthresholds• 3objectsforactuatingthedrive(up/down,slats%,height%)• 1suncontrolobject(morning/evening)• 1teachinobject• 1safetyobject
Weather Station 90990056
FIELD EQUIPMENTS
Weather Station
Main Features
Technical Data Universal channels
Sun protection channel
Order Number
Weather Station
Weather Station
OperatingvoltageKNX
Operatingvoltage
Brightnessmeasuringrange
Measuringtemperaturerange
Measuringwindspeedrange
Ambienttemperature
Protectionrating
Busvoltage,(<10mA)
230VAC
1–100000lx
-20°C...+55°C
2–20m/s
-20°C...+55°C
IP44
Scale Drawings
Weather Station
64
SMART BUILDING AUTOMATION SYSTEMS
theaiq.com.tr
Optima Frames
opak white
anthracite
cream
fume
white
black
bronze
Sistema Frames
inox
gold
inox Matt
antique
chrome
una
chrome Matt
Push Button Frame and Cover Color Alternatives
Cover Color Alternatives
opaque white cream metallic whitedore anthracite fume black
65
SMART BUILDING AUTOMATION SYSTEMS
Multiple Frames
Ultima Frames
Glass
Metallic
Wood
Eloxal
white
chrome
bamboo
silver
light green
inox
walnut
bronze
burgundy
gold
wenge
black
black
una
2M
3M 2X2M
4M 3X2M
7M 4X2M
66
SMART BUILDING AUTOMATION SYSTEMS
theaiq.com.tr 15
SMART BUILDING AUTOMATION SYSTEMS
TOUCHPANELS
SMART BUILDING AUTOMATION SYSTEMS
Touch Zone
KNX Superio
Superio
Home
Domus
Mirror
KNX Server
SMART BUILDING AUTOMATION SYSTEMS
theaiq.com.tr
TOUCH PANELS
Touch Zone 7” Touch Panel
Touch Zone
69
• Combinesthefunctionsofasmartphonewithbuildingsecurity functionsformorecomfortandsecurityineverybuilding• 7“glassmultiTouchpanelforanintuitivehandlinginresidential andcommercialbuildings• Multi-roomcontrolpanelwithfunctionssuchasbuttonfor controllingtemperature,lighting,shadingandforenergyand securitymanagementofthebuilding• Canbeusedaselegantinteriorintercomstation
• Canbeinstalledhorizontallyorvertically• TheGooglePlay(AndroidMarket)offersahostofpracticaland usefulapps
Touch Zone 7” Black 90992300Touch Zone 7” White 90992301
Main Features
Technical Data
Order Number
Touch Zone
Operatingvoltage
PowerConsumption
Processor
Memory
StorageExtension
Storagemedium
Interfaces
Compatibleoperating
systems
Userinterface
Browsercompatibility
Multimedia
Sensors
FrontUnit
Resolution(inPixel)
DimensionsCut-OutwithMTZ[mm]
ProductSize[mm]
Ambienttemperature
Relativehumidity
Protectionrating
9...36VDC
7Wmax.
Fanlessultralowconsumption1GHzSitara™ARM®Cortex™A8Corewithintegratedgraphicscontroller
512MBRAM
MicroSDHC
highspeedFlashmemory4GB
1x10/100MbpsLANwithPoE,1xWLAN(opt.),1xRS232/RS485,2xUSB2.0,1xminiUSBOTG,4xDI/4xDO,IRReceiver,Bluetooth(opt.)
Android2.3(Android4.xcompatibilityisgoingtobeverified),Linux(Kernel2.6.32)-optional,MOQ500pcs,MicrosoftWindowsC7-optional,
MOQ500pcs
Web/HTML5(Alloperatingsystems)Appsupport(iOS/Android)
GoogleChrome,AppleSafari,MozillaFirefox
Microphone(ext)/Loudspeaker2WattRMS(ext)
Temperaturesensor,Lightsensor
7,0”-17,78cmwidescreen-LEDbacklightTFT
WVGA800x480
129x210x75
136x213
0°C...+30°C
5%to80%at25°C(nohumidity/condense)
IP20
(*) wall mount boxes are required
SMART BUILDING AUTOMATION SYSTEMS
• Integratesthefunctionsofhomeautomationandbecomesthe centralpointofthehomeforbothinformationand entertainment• Multi-roomcontrolpanelwithfunctionssuchasbuttonfor controllingtemperature,lighting,shadingandforenergyand securitymanagementofthebuilding• Additionalfunctionscanalsobeusedviaintegratedplug-ins, includingIPcameraintegration,callingupweatherreports, newstickersandwebsites,generatingmessages,callingup energyusedisplaysandmuchmore
• CanconnecttheKNXnetworkdirectly• Operatingelementsareeitherautomaticallyassignedtoagrid oraredraggedtothebackgroundimage• Canbeusedaselegantinteriorintercomstation
TOUCH PANELS
KNX Superio 10”/19” Touch Panel
Main Features
KNX Superio
KNX Superio 10” 90992310 KNX Superio 19” 90992311
Order Number
KNX Superio
70
Technical Data
KNXSuperio 10” KNXSuperio 19”
Operatingvoltage
PowerConsumption
Processor
Memory
StorageExtension
Storagemedium
Interfaces
Operatingsystem
KNXGroupaddresses
Multimedia
FrontUnit
Resolution(inPixel)
Methodofoperating
DimensionsCut-OutwithMTZ[mm]
ProductSize[mm]
Typeofdesign
Ambienttemperature
Relativehumidity
Protectionrating
100–240VDC
15Wmax.
10,1”-25,6cmwidescreenLEDbacklightTFT
Projectedcapacitivetouchscreenwith3mmglassfront,multitouchcapable
Resistivetouchscreen,5-wiretechnology
WSVGA1024x600
315x200x80 582x327x80
333x200 600x345
18,5”-47,0cmwidescreenTFT,LEDbacklightTFT
fanlesslowconsumptionATOMN4501,66GHzCPUwithintegratedGMA3150graphicscontroller
2GBDDR2SDRAM
SDSlot
highspeedCFC4GB
2x10/100/1000MbpsLAN,1xRS232/422/485,3xUSB2.0
proprietaryoperatingsystemwithKNXsupervision
Upto1000
speakerandmicrophoneincludedwithechocancellation
homogeneoussmoothglasssurfacewithaluminiumsideborder
0°C...+30°C
5%to80%at25°C(nohumidity/condense)
IP20
35Wmax.
(*) wall mount boxes are required
SMART BUILDING AUTOMATION SYSTEMS
theaiq.com.tr
• Integratesthefunctionsofhomeautomationandbecomesthe centralpointofthehomeforbothinformationand entertainment• Multi-roomcontrolpanelwithfunctionssuchasbuttonfor controllingtemperature,lighting,shadingandforenergyand securitymanagementofthebuilding• Additionalfunctionscanalsobeusedviaintegratedplug-ins, includingIPcameraintegration,callingupweatherreports, newstickersandwebsites,generatingmessages,callingup energyusedisplaysandmuchmore
• Operatingelementsareeitherautomaticallyassignedtoagrid oraredraggedtothebackgroundimage• Canbeusedaselegantinteriorintercomstation
TOUCH PANELS
Superio 10”/15”/19” Touch Panel
Main Features
Superio
Superio 10” 90992315Superio 15” 90992317Superio 19” 90992318
Order Number
Superio
71
Technical Data
Superio 10” Superio 15” Superio 19”
Operatingvoltage
PowerConsumption
Processor
Memory
StorageExtension
Storagemedium
Interfaces
Operatingsystem
Multimedia
FrontUnit
Resolution(inPixel)
Methodofoperating
DimensionsCut-OutwithMTZ[mm]
ProductSize[mm]
Typeofdesign
Ambienttemperature
Relativehumidity
Protectionrating
100–240VDC
15Wmax.
10,1”-25,6cmwidescreenLEDbacklightTFT
Projectedcapacitivetouchscreenwith3mmglassfront,multitouchcapable
WSVGA1024x600 WXGA(1366x768) WXGA(1366x768)
315x182x80 492x288x80 582x327x80
333x200 510x306 600x345
15,6”-39,6cmwidescreenTFT,LEDbacklightTFT
18,5”-47,0cmwidescreenTFT,LEDbacklightTFT
Resistivetouchscreen,5-wiretechnology
25Wmax.
fanlesslowconsumptionATOMN4501,66GHzCPUwithintegratedGMA3150graphicscontroller
2GBDDR2SDRAM
SDSlot
highspeedCFC4GB(900MBavailableonsystem/1900MBonsecondarypartition)
1x10/100/1000MbpsLAN,1xWLAN(opt.),1xRS232/422/485,3xUSB2.0,4xDI/4xDO,IRReceiver,
Analogvideoinput,Bluetooth(opt.),2MPixelCMOSWebcamera(opt.)
MicrosoftWindowsEmbedded
speakerandmicrophoneincludedwithechocancellation
homogeneoussmoothglasssurfacewithaluminiumsideborder
0°C...+30°C
5%to80%at25°C(nohumidity/condense)
IP20
35Wmax.
(*) wall mount boxes are required
SMART BUILDING AUTOMATION SYSTEMS
TOUCH PANELS
Home 10”/15” Touch Panel
Home
72
• Integratesthefunctionsofhomeautomationandbecomesthe centralpointofthehomeforbothinformationandentertainment• Multi-roomcontrolpanelwithfunctionssuchasbuttonfor controllingtemperature,lighting,shadingandforenergyand securitymanagementofthebuilding• Additionalfunctionscanalsobeusedviaintegratedplug-ins, includingIPcameraintegration,callingupweatherreports,news tickersandwebsites,generatingmessages,callingupenergyuse displaysandmuchmore
• Operatingelementsareeitherautomaticallyassignedtoagridor aredraggedtothebackgroundimage• Highqualityanodizedaluminiumframes• Canbeusedasinteriorintercomstation
Main Features
Technical Data
Home 10” Home 15”
Operatingvoltage
PowerConsumption
Processor
Memory
StorageExtension
Storagemedium
Interfaces
Operatingsystem
KNXGroupaddresses
Multimedia
FrontUnit
Resolution(inPixel)
Methodofoperating
DimensionsCut-OutwithMTZ[mm]
ProductSize[mm]withframe
Typeofdesign
Ambienttemperature
Relativehumidity
Protectionrating
90-260VACautorangefanless
30Wmax.
HDTVresolutionupto1080icapable/1freeVGAport(dualdisplayarchitecture),AC’97audio
resistivetouchscreenwithUSBtouchcontroller,6-wiretechnology
IntelAtomProcessor-1,2GHz,533MHz,512KL2Cache
2GBDDR2SDRAM
313x258x80
340x285x20
10,4”
XGA1024x768
15”
XGA1024x768
399x336x90
425x365x25
highspeedDOM2GB(550MBavailableonsystem/970MBonsecondarypartition)
2x10/100/1000MbpsLAN,1xRS232/422/485,5xRS232,5xUSB2.0,2xPS/2
MicrosoftWindowsXPembedded
Upto1000
ultracompactembeddedPCforwallmount;noiselessandwithoutanyrotatingpart
0°C...+30°C
5%to80%at25°C(nohumidity/condense)
IP20
40Wmax.
1PCI-Slot-
Home 10” 90990093Home 15” 90990094
Order Number
(*) wall mount boxes are required
SMART BUILDING AUTOMATION SYSTEMS
theaiq.com.tr
• Integratesthefunctionsofhomeautomationandbecomesthe centralpointofthehomeforbothinformationand entertainment• Multi-roomcontrolpanelwithfunctionssuchasbuttonfor controllingtemperature,lighting,shadingandforenergyand securitymanagementofthebuilding• Additionalfunctionscanalsobeusedviaintegratedplug-ins, includingIPcameraintegration,callingupweatherreports, newstickersandwebsites,generatingmessages,callingup energyusedisplaysandmuchmore
• Operatingelementsareeitherautomaticallyassignedtoagrid oraredraggedtothebackgroundimage• Canbeusedasinteriorintercomstation
TOUCH PANELS
Domus 19” Touch Panel
Main Features
Domus
73
Technical Data
Domus
Operatingvoltage
PowerConsumption
Processor
Memory
StorageExtension
Storagemedium
Interfaces
Operatingsystem
Multimedia
FrontUnit
Resolution(inPixel)
Methodofoperating
DimensionsCut-OutwithMTZ[mm]
ProductSize[mm]withframe
Ambienttemperature
Relativehumidity
Protectionrating
90-260VACautorangefanless
50Wmax.
IntelAtomProcessor-1,2GHz,533MHz,512KL2Cache
2GBDDR2SDRAM
1PCI-Slot
highspeedDOM4GB(900MBavailableonsystem/1900MBonsecondarypartition)
2x10/100/1000MbpsLAN,5xRS232,1xRS232/422/485,5xUSB2.0,2xPS/2
MicrosoftWindowsEmbedded
HDTVresolutionupto1080icapable,1freeVGAport(dualdisplayarchitecture),AC’97audio
19”-48,3cm
SXGA1280x1024
resistivetouchscreenwithUSBtouchcontroller,6-wiretechnology
472x410x90
497x435x25
0°C...+30°C
5%to80%at25°C(nohumidity/condense)
IP20
Domus 19” 90992352
Order Number
(*) wall mount boxes are required
SMART BUILDING AUTOMATION SYSTEMS
TOUCH PANELS
Mirror 15”/19” Touch Panel
Mirror
74
• Innovativecombinationofatouchpanelforbuildingautomation andahigh-qualitymirror,whichmeetsthehigheststandardsof designandtechnology• Multi-roomcontrolpanelwithfunctionssuchasbuttonfor controllingtemperature,lighting,shadingandforenergyand securitymanagementofthebuilding• Additionalfunctionscanalsobeusedviaintegratedplug-ins, includingIPcameraintegration,callingupweatherreports,news tickersandwebsites,callingupenergyusedisplaysandmuch more• Thespecialmountingofthemirrorprotectsthetouchpanel
fromhumidityandmakesitparticularlysuitablefortheusein wetlocationslikebathroomsorwellnessareas• Instandbymode,whichisautomaticallyactivatedafterone minutewithoutactiveinput,justlookslikeaconventionalmirror• Atouchonthemirroractivatesthedisplayofthe15”or19” Panel• Canbeusedaselegantinteriorintercomstation
Mirror 15” 90992330Mirror 19” 90992331
Main Features
Technical Data
Order Number
Mirror 15” Mirror 19”
Operatingvoltage
PowerConsumption
Processor
Memory
StorageExtension
Storagemedium
Interfaces
Operatingsystem
KNXGroupaddresses
Multimedia
FrontUnit
Resolution(inPixel)
Methodofoperating
DimensionsCut-OutwithMTZ[mm]
ProductSize[mm]withframe
Typeofdesign
Ambienttemperature
Relativehumidity
Protectionrating
90-260VACautorangefanless
25Wmax.
HDTVresolutionupto1080icapable/onboardAC’97audio/1xfreeVGAport-DUALDisplayarchitecture
ProjectedcapacitivetouchgrantsoperationbeyondglassorTHEAIQMIRRORFrame
IntelAtomProcessor-1,2GHz,533MHz,512KL2Cache
2GBDDR2SDRAM
1PCI-Slot
highspeedDOM4GB(900MBavailableonsystem/1900MBonsecondarypartition)
2x10/100/1000MbpsLAN,1xRS232/422/485,5xRS232,5xUSB2.0,2xPS/2
MicrosoftWindowsEmbedded
Upto1000
399x336x90
425x365x25
10,4”
XGA1024x768
15”
XGA1024x768
472x410x90
497x435x25
ultracompactMIRRORembeddedPCforwallmount;noiselessandwithoutanyrotatingpart
0°C...+30°C
5%to80%at25°C(nohumidity/condense)
IP20
50Wmax.
(*) wall mount boxes are required
SMART BUILDING AUTOMATION SYSTEMS
theaiq.com.tr
• Web-basedvisualisationsystemforhomeandbuilding automationbasedonKNX• AllowsthefullcontroloftheconnectedmodulesthroughPC/ MAC,TouchPanels,smartphones,tablets• Offersalsoadditionalfunctionssuchasscenariosandprovides accesstowebcontent,weatherreports,newstickers,and messageboards
• Complicatedobjectscanbecontrolledthroughspecialpop-up windows• FromtheKNXM-SERVERtotheKNXE-SERVERscalable visualisationsolutions
• Illumination• Heating/Cooling• Doorandwindowcontacts• Irrigation/sprinkling• Thermo-control• Alarmsystems• Energymanagement• Loadcontrol• Weatherstations• IPcameras• Intercom*• Burglarprotection*• Multiroom* (*)Requiresadditionalmodule
KNX M-Server 90992370KNX H-Server 90992371KNX A-Server 90992372KNX E-Server 90992373
TOUCH PANELS
KNX Server
Main Features
Technical Data Functions
Order Number
KNX Server
KNX Server
Operatingvoltage
PowerConsumption
StorageExtension
Interfaces
Compatibleoperatingsystems
Userinterface
Browsercompatibility
Dimensions
Ambienttemperature
Protectionrating
75
12...24VDC
3W
SD/SDHCupto32GB
KNX,1xRS232,2xUSB2.0,1xRJ45
MicrosoftWindows,Apple,Mac,OSX,Linux,
AppleiOS,GoogleAndroid
Web/HTML5(Alloperatingsystems)
Appsupport(iOS/Android)
GoogleChrome,AppleSafari,MozillaFirefox
8modules
0°C...+50°C
IP20
SMART BUILDING AUTOMATION SYSTEMS
TOUCH PANELS
KNX Server
KNX Server
76
VERSION KNX GROUPADDRESSES
SCENARIOS LOGICS / CONDITIONS
ROOMS / PAGES
VERSION CODEENERGY-MANAGEMENT
IP CAMERAS
MINI
HOME
ADVANCED
ENTERPRISE
100
500
1500
UNLIMITED
5
30
100
UNLIMITED
5
30
100
UNLIMITED
10
UNLIMITED
UNLIMITED
UNLIMITED
4
12
UNLIMITED
UNLIMITED
-
UNLIMITED
UNLIMITED
UNLIMITED
KNXM-SERVER
KNXH-SERVER
KNXA-SERVER
KNXE-SERVER
KNXSERVER Video surveillance
Alarm system
Intercom / VOIP
Audio/Video KNX system
GSM modem
CLIENT
Touchpanel (DIVA, MIRROR, SUPERIO, DOMUS, HOME, TOUCHZONE)
PC / MAC
iPhone / Android
12-24 VDC
BUS
+ - + -
LAN
RESET
RS232 USB
Alarm central
IP camera
Analogue camera
IP videoserver
IR receiver
IR
1 2 34 5 67 8 9
* 0 #
VOIP external unit
VOIP internal unit
LAN / USB
LAN / USB
LAN
LAN
LAN
RS232
LANLAN
LAN
WIFI / UMTS
Audio/Video sources
Audio/Video multiroom
Zone terminals
KNX
LAN
SMART BUILDING AUTOMATION SYSTEMS
theaiq.com.tr
APPLICATION EXAMPLE
KNX-H/A/E-SERVER: Residential
KNX Server
1
KNX‐H/A/E‐SERVER:Residential
Upto180residentialapartments
apartment3:TZ+SUPERIO+KNXSERVER+optionalOPENDOOR&
UP‐INTERCOM‐SW
Tablet/smartphoneOPTIMA‐App,
Videophone‐App(Androidonly!!)WLAN
OPTIMA‐App,
Videophone‐AppOPENDOOR
OPTIMAinGoogleChrome,
OPTIMAIntercomplugin
apartment2:TZ+SUPERIO+KNXSERVER+optionalOPENDOOR&
UP‐INTERCOM‐SW
Tablet/smartphoneOPTIMA‐App,
Videophone‐App(Androidonly!!)WLAN
OPENDOOR
OPTIMAinGoogleChrome,
OPTIMAIntercomplugin
apartment1:TZ+SUPERIO+KNXSERVER+optionalOPENDOOR
Tablet/smartphoneOPTIMA‐App,
Videophone‐App(Androidonly!!)WLAN
OPTIMA‐App,
Videophone‐AppOPENDOOR
Concierge Mainentrance
OPENDOOR
VoIP‐Server(DB100)
!!max.about280concurrentcalls!!
Internet
Tablet/smartphone/PCOPTIMA‐App/Google
Chrome(KNX)only!!
Backentrance
OPENDOOR
!!KNX‐H/A/E‐SERVERIntercombaselicensefortheusageofPCClients(SUPERIO,Laptop,
Desktop):1externalunit,3internalunits!!
77
SMART BUILDING AUTOMATION SYSTEMS
APPLICATION EXAMPLE
KNXSUPERIO: Single villa
KNXSUPERIO
1
KNXSUPERIO:Singlevilla
Mainentrance
2ndfloor:TZ
1st
floor:TZ
groundfloor:KNXSUPERIO
+optionalUP‐INTERCOM‐SW
Tablet/smartphoneOPTIMA‐App,Videophone‐App(Androidonly!!)
WLAN
Internet
Tablet/smartphoneOPTIMA‐App(KNX)only!!
OPENDOOR
OPTIMA‐App,Videophone‐App
!!KNXSUPERIOIntercombaselicense:1externalunit,3internalunits!!
!!KNXSUPERIOsupportsonlymobiledeviceclients(TOUCHZONE,tablets,smartphones)!!
OPTIMAinGoogleChrome,
OPTIMAIntercomplugin
OPTIMA‐App,Videophone‐App
78
SMART BUILDING AUTOMATION SYSTEMS
theaiq.com.tr 15
SMART BUILDING AUTOMATION SYSTEMS
INTERCOMSYSTEMS
SMART BUILDING AUTOMATION SYSTEMS
Opendoor Units
Voip Server
VideoPhone
SMART BUILDING AUTOMATION SYSTEMS
theaiq.com.tr
INTERCOM SYSTEMS
10.2.2 Opendoor Units
Opendoor Units
81
Technical Data
OD Compact Audio OD Compact Video
Powersupply
Powerconsumption
Controls
Configuration
Audio
Camera
Dooropener
Externalcallkeys
Interfaces
Connections
PoEpowersupply
Material
Dimension[mm]
Ambienttemperature
Protectionrating
24VDC(20-36VDC)
LCDdisplay,2lineswithbacklight,3buttonsforscrollingandcalling
throughabrowser
Integratedloudspeaker2Watt,Integratedmicrophone
-20°C...+50°C
IP54
4inputsforadditionalexternalringbuttons,withbinaryencoderupto15externalringbuttonspossible
Sabotagesurveillanceoveradditionalmodule
1xEthernetRJ45,Powersupply24VDC,Directcallkeys,2Relays(dooropener+Light)
PowersupplythroughPoweroverEthernet(PoE/Endspan);Attention!NoMid-spanforPoEpowersupply
Aluminiumhousing
4Wmax.
99,0x198,5x38,3 99,0x298,0x38,3
Relaycontact24V,2A
9Wmax.
OD-Camintegratedinflatdesign(VGAColourCMOSImageSensor)-
• Networkbasedintercomsolution• Productrangecontainsfinishedstandalonesolutions (AudioCompact,VideoCompact)asalsocompactmodules, whichcanbemountedintotheowndesign• OPENDOORFramesareavailablefor1,2,3or4modulesfor combinationdesign• SupportsthesustainableSIPprotocol
Main Features
OD Compact Audio 90992001OD Compact Video 90992002
Order Number
(*)Outdoor Units combinations for your requirements please contact us
SMART BUILDING AUTOMATION SYSTEMS
INTERCOM SYSTEMS
VOIP SERVER
Voip Server
82
• TransformsKNXSERVERintoatelephonecentralforprivate buildingsandoffices• PossibilitytointegrateIPphones,IPintercomsystems, touchpanels,tabletsandsmartphonesthatsupporttheSIP standard• Theaudio/videocallistransferredoverthenetwork(LANor WLAN),inwhichKNXSERVERisinstalled• Possibilitytoconnectwithanalogue(PSTN)ordigital(ISDN) telephonelineswithoptionalconvertermodules• InternalunitsobjectpermitstoconfigureanIPphone,a softphone,atablet/smartphoneoratouchpanel/PC/MACwitha JAVAcompatiblebrowserasinternalVoIPunit
• ExternalunitsobjectpermitstoconfigureanIPintercomunit andtoconfigureactions(e.g.dooropener)whichcanbe controlledduringVoIPcommunication.Evenoneormore camerasignalscanbeconnected.• Callgroupsobjectpermitstoredirectincomingcallstomore thanoneinternalunit;thedeviceansweringthecallasfirstwill takecontroloverthecommunication• Avirtualdialpadcanbeusedtostartcallstootherinternalunits ortoanexternalphoneline
VOIP Server 90992380
Main Features
Technical Data
Order Number
VoIP Server
Requirements
VOIPServer
Supportedprotocols
Supportedaudiocodecs
Supportedvideocodecs
Configuration
Supportedhardware
Supportedsoftware
Integrationwiththevisualisation
Internalunits
Parallelcalls
KNXServerofnewestgeneration
Asteriskversion1.8
SIP,IAX2
G.711/G.729/GSM
H.263/H.263+/H.264
ThroughcorrespondingobjectsinthewebconfigurationareaofKNXSERVER
TheaIQtouchpanels
IPphones*
IPintercomsystems*
Analogue-digitalconverters*
Tabletsandsmartphones*
Freeandcommercialsoftphones*
JAVAcompatiblewebbrowseroflastgeneration
• AutomaticstartoftheJAVAappletsinthebrowserwhenaccessingKNXSERVER
• Automaticpop-upwindowatincomingcalls
• Interphonefunctionforcallsbetweeninternalunits
• Displayofcamerasignalatincomingcalls
• Executionoffunctionsatincomingcalls
• Automaticstartingofcallsthroughevents/KNXalerts
Upto20
Upto3
SMART BUILDING AUTOMATION SYSTEMS
theaiq.com.tr
• Thesolutionthatallowsyoutocontrolyourvideointercom comfortablyoveryourtouchpanel• Compatibilitywithallcommonintercomsupportinga/bsignals• Possibilitytointegrateupto10externalintercomunits, expandableonrequest• Upto20clientpanelsconfigurable,expandableonrequest• Interphonefunctionalityforcommunicationbetweenclient panels(audioonly)• ConfigurablebuttonsforsendingDTMFtones• Outstandingaudioandvideoqualitywithpowerfulhardware
• Extendedsupportofintercomfunctions,likee.g.accept/reject call,show/hidevideosignal,volumeregulationwithmute function,audiorecording,quickdialbuttons,fullnum-pad, additionalbuttons• Statusbarwithsysteminformation(serverstate,callerID)• Graphicalinterfacefullycustomizable• Freering-toneselection• Interfaceautomaticallypopsupinfrontofanincomingcall
INTERCOM SYSTEMS
VideoPhone Box
Main Features
VideoPhone Box 90990041
Order Number
VideoPhone
83
Technical Data
Videophone Box
PowerSupply
PowerConsumption
Storagemedium
VoIP-Controller
Video-Controller
Interfaces
OutsideDimensions[mm]
Typeofdesign
Ambienttemperature
Relativehumidity
Protectionrating
2x5VDCoverexternal110–240VACpowersupplies
10Wmax.
highspeedCFC4GB(900MBavailableonsystem/1900MBonsecondarypartition)
2x10/100MbpsLAN(1forconvertedvideosignal,1foraudiosignal),
2xRJ11(1forintercoma/b,1foradditionalphone),4xvideoinputforanaloguecamerasignal
178x105x36
ultracompactembeddedsystemforaudio/videodigitalization
0°C...+45°C
10%to90%at25°C(nohumidity/condense)
IP20
•intercomsupport•simultaneousringing•voiceencodingaccordingtoG.711(64kbit/s)•echocancellation(G.165)•configurationandmaintenanceviawebinterface(localorremote)•4videoinputsformulti-videosourcefromdifferentarea•supportsround-robin-see4videosignalsinscreenoutput•motiondetection•resolution-true640x480,352x288,320x240,176x144•quality:low,high,medium,clarity,motion•coloursetup:brightness,contrast,hueandsaturation•videoscreen:1x1,2x2,3x3,4x4•supportsActiveXcontrol•builtinJPEGdecoder•configurationandmaintenanceviawebinterface