    Fans - BasicDefinitions

    Fan SystemCalculation and Design

    Important Standards

    Practical Examples

    Important Standards

    IMPORTANT BUILDING VENTILATION STANDARDS

    C.T.E. (replaces: NBE-CPI/96)

    DESCRIPTION:

    ROYAL DECREE 314/2006, 17th March, approving the Spanish Te chnical Building Code.

    PURPOSE:

    It is a regulation that lays down the basic quality requirements for buildings and

    facilities. This regulation covers specific basic building requireme nts related to the safety and

    wellbe ing of people. These refer to bo th structural safety and fire protection, and hea lth andsafety, noise protection, energy saving and disabled access.

    DETAILS:

    Article 11. Basic fire safety requirements (SI in Spanish) Article 13. Basic health and

    safety requirements (HS)

    Article 13. Basic hea lth and sa fety requiremen ts (HS)

    RITE

    DESCRIPCIN:

    Regulation on building heating installations.

    PURPOSE:

    To set the energy efficiency and safety requirements for these installations that are

    designed to ensure the wellbeing and health of people, during the design and calculation

    process and during execution, maintenance and use, as well as establish the procedures to

    prove this fulfilment. He ating installations will include permane nt climate control installations

    (heating, cooling and ventilation). It will apply to heating installations in new or refurbished

    buildings. It will not apply to heating installations in the part of industrial, agricultural or

    other processes that is not aimed at ensuring the wellbeing and health and safety of people

    through heating.

    REBT

    DESCRIPTION:

    Low voltage electrotechnical regulation (2002).

    PURPOSE:

    This regulation aims to set the technical conditions and guarantees for electrical installations

    Air extraction in carparks (pdf inSpanish)

    Air extraction inkitchen extractorhoods (pdf inSpanish)

    Air extraction inhouses (pdf inSpanish)

    Stairwellove rpressure (pdf inSpanish)

    http://www.sodeca.com/downloads/Ej-practicos-escaleras.pdfhttp://www.sodeca.com/downloads/Ej-practicos-escaleras.pdfhttp://www.sodeca.com/downloads/Ej-practicos-escaleras.pdfhttp://www.sodeca.com/downloads/Ej-practicos-viviendas.pdfhttp://www.sodeca.com/downloads/Ej-practicos-campanas.pdfhttp://www.sodeca.com/downloads/Ej-practicos-aparcamientos.pdfhttp://www.sodeca.com/en/tecnica4.html#arribahttp://www.sodeca.com/en/tecnica3.html#arribahttp://www.sodeca.com/en/tecnica2.html#arribahttp://www.sodeca.com/en/tecnica.html#arribahttp://www.sodeca.com/en/interes.htmlhttp://www.sodeca.com/en/sat.htmlhttp://www.sodeca.com/catalogos/http://www.sodeca.com/catalogos/?fl=nhttp://www.sodeca.com/en/software.htmlhttp://www.sodeca.com/en/tecnica.htmlhttp://85.152.24.154:8080/Sodeca/action/SodecaAction?method=list&bundle=ResourcesEnhttp://www.sodeca.com/en/empresa.htmlhttp://www.sodeca.com/en/index.htmlhttp://www.sodeca.com/pt/index.htmlhttp://www.sodeca.com/de/index.htmlhttp://www.sodeca.com/en/tecnica3.html#http://www.sodeca.com/en/tecnica3.html#http://www.sodeca.com/ca/index.htmlhttp://www.sodeca.com/index.html
  • 7/30/2019 SODECA7 Sodeca Fans, Industrial Ventilation

    2/6

    /9/12 ::: SODECA ::: Sodeca Fans, Industrial Ventilation

    ww.sodeca.com/en/tecnica3.html#arriba

    connected to a power supply regarding low voltage limits.

    DETAILS:

    PURPOSE: a) To ensure the he alth and safety of pe ople and property. b) To guarantee

    the operating of these installations and prevent disturbance in other installations and

    services. c) To contribute to the technical reliability and economic efficiency of the

    installations.

    SCOPE OF APPLICATION:

    1. The present regulation will apply to the installations that distribute electrical energy,

    gene rators for internal consumption and receivers, with the following nom inal voltage limits:

    a) Alternating current: equal to or less than 1,000 volts.

    b) Continuous current: equal to o r less than 1,500 volts.

    2. This regulation will apply:

    a) To new installations and changes and extensions to these.

    b) To existing installations before they enter into force that undergo major changes or

    repairs and to extensions to these.

    c) To existing installations before they enter into force regarding the inspection system,

    although the technical criteria applicable for these inspections will be those relating to the

    regulations under which they were approved.

    UNE-EN 13779:2005 (replaces: UNE 100011:1991)

    DESCRIPTION:

    Non-residential building ventilation. Requirements regarding features of buildingventilation and air conditioning systems.

    PURPOSE:

    This document applies to the design of ventilation and air conditioning systems for non-

    residential buildings used for human occupation. It focuses on the definition of relevant

    parameters for these systems. Naturally ventilated buildings are not included under the

    purpose and scope of application of this document.

    The classification system in this regulation uses different categories. Examples are given

    for some values and the typical ranges with default values are given for the requirements.

    The default values provided in this document must be used when other values are not

    specified. The classification should always be suitable for the building type and its use, and

    the classification criteria should be explained if the examples given in the regulation are not

    used. National regulations must always be fulfilled, even when outside the ranges given in

    this document.

    DETAILS:

    To provide the guidelines for ventilation systems in order to ensure a comfortable and

    health indoor environment.

  • 7/30/2019 SODECA7 Sodeca Fans, Industrial Ventilation

    3/6

    /9/12 ::: SODECA ::: Sodeca Fans, Industrial Ventilation

    ww.sodeca.com/en/tecnica3.html#arriba

    UNE 100165:2004 (replaces: UNE 100165:1992)

    DESCRIPTION:

    Climate control. Smoke extraction and ventilation in kitchens.

    PURPOSE:

    The purpose of this regulation is to set the criteria for the calculation and design of

    mechanical ventilation systems in industrial kitchens. This regulation does not establish the

    design criteria for different types of extractor hoods in order to increase their intake

    efficiency. The regulation applies to commercial kitchens that run on electricity or any other

    fuel.

    DETAILS:

    The extraction airflow of an extractor hood is the most important aspect of industrial

    kitchen ventilation.

    UNE 100166:2004 (replaces: UNE 100166:1992)

    DESCRIPTION:

    Clima te control. Car park ventilation.

    PURPOSE:

    This regulation lays down the criteria for the calculation and design of mechanical

    ventilation systems in underground car parks and natural ventilation in aboveground car

    parks. The regulation applies to public car parks.

    DETAILS:

    The ventilation airflow must under no circumstances be less than 18 m3/h * m2.

    UNE-EN 12101-3:2002

    DESCRIPTION:

    Smoke and heat control systems. Part 3: Specifications for mechanical smoke and heat

    ex tractor vents.

    PURPOSE:

    This part specifies the necessary elements and provides the testing methods for

    mechanical smoke and heat extractor vents that are installed as part of an air inlet and heat

    and smoke extraction system. It also describes the procedures to approve a range of

    mechanical heat and smok e a ir vents and their motors base d on a limited number of tests.

    DETAILS:

    Classification by fan temperature and operating time. Class F400 (400C/2hours).

    UNE-EN 12101-6:2006 (replaces: UNE 100040:1996)

  • 7/30/2019 SODECA7 Sodeca Fans, Industrial Ventilation

    4/6

    /9/12 ::: SODECA ::: Sodeca Fans, Industrial Ventilation

    ww.sodeca.com/en/tecnica3.html#arriba

    DESCRIPTION:Smoke and heat control systems. Part 6: Specifications for pressure differential systems.

    Equipment.

    PURPOSE:

    This regulation covers the information and requirements for design, calculation methods,

    installation and testing of the systems designed to limit the spreading of smoke through

    pressure differentials.

    DETAILS:

    To supply outside a ir to a p ressurised space me chanical fans with the right ducts must be

    used where necessary.

    IMPORTANT REGULATIONS REGARDING POTENTIALLY EXPLOSIVEATMOSPHERES

    UNE-EN 60079-10:2004 (replaces: UNE-EN 60079-10:1997)

    DESCRIPTION:

    Electrical equipment for explosive gas atmospheres. Part 10: Hazardous site

    classification.

    PURPOSE:

    In sites in which hazardous quantities and concentrations of flammable gas or steam

    might appear, preventive measures must be taken to reduce the risk of explosion. The

    purpose of this part of the CEI 79 is to explain the fundamental criteria to assess the risk of

    explosion and provide guidelines so that the design and operating parameters reduce this

    risk. In the case of electrical apparatus, this regulation is the basis for the right selection

    and installation of the appa ratus to be used o n hazardous sites.

    ATEX

    DESCRIPTION:

    This is the abbreviation for "Explosive Atmospheres" and is the term on which two

    European Directives are based:

    PURPOSE:

    Product Directive 94/9/EC

    It focuses on equipment manufacturer obligations. It describes the Essential Health and

    Safety Requirements (EHSRs) for products with regard to design, manufacturing, testing,

    documentation and maintainability.

    http://www.sodeca.com/en/tecnica3.html#arriba
  • 7/30/2019 SODECA7 Sodeca Fans, Industrial Ventilation

    5/6

    /9/12 ::: SODECA ::: Sodeca Fans, Industrial Ventilation

    ww.sodeca.com/en/tecnica3.html#arriba

    Workers Directive 1999/92/EC

    It focuses on user or employer obligations. Risk analysis and description. Definition of

    areas and maintenance practices in relation to factory safety. It describes the minimum

    requiremen ts to improve health and sa fety protection for workers at a potential risk.

    PrEN 14986:2006

    DESCRIPTION:

    Design of fans to work in potentially explosive atmospheres.

    PURPOSE:

    This regulation only deals with the prevention of ignition in an explosive atmosphere for

    fans.

    DETAILS:

    4.8 Materials for fan rotating and static parts.

    4.15 Safety distance between rotating elements and the fan casing.

    IMPORTANT REGULATIONS FOR SMOKE EVACUATION IN INDUSTRIALPREMISES

    ROYAL DECREE 2267/2004

    DESCRIPTION:

    ROYAL DECREE 2267/2004, 3rd December, approving the Fire Safety Regulation in

    industrial premises.

    UNE 23585:2004

    DESCRIPTION:

    Fire safety. Smoke temperature and evacuation control systems (SCTEH in Spanish).

    Calculation and design requirements and methods to design a smoke temperature and

    evacuation control system in case of fire.

    PURPOSE:

    The purpose of this regulation is to provide those in charge of designing a building with a

    suitable analysis and calculation method to e stablish the nee ds and requirements of one or

    several Air Inlet and Heat and Smoke Extraction System or Systems (SCTEH in Spanish) for

    this building, in order to properly control combustion smoke and gases generated in the

    worst case scenarios foreseeable regarding fires, as well as the their temperature. A SCTEH

    consists of a set of vents or mechanical extraction units (fans) to extract combustion smoke

    and hot gases during a fire and, where applicable, clean air inlet vents, with the right

    http://www.sodeca.com/en/tecnica3.html#arriba
  • 7/30/2019 SODECA7 Sodeca Fans, Industrial Ventilation

    6/6

    ::: SODECA ::: Sodeca Fans, Industrial Ventilation

    ww.sodeca.com/en/tecnica3.html#arriba

    measurements so that in the event of a fire, as well as keeping the average smoke

    temperature at an acceptable level, the health and safety conditions when evacuating and/or

    rescuing people and animals are improved and the contents and structural elements of the

    building are protected, allowing the fire to be fought while keeping the building in a similar

    state as it was in when the fire started.

    DETAILS:

    CTE SI3-8.2 states the following: The system design, calculation, installation andmaintenance can be completed in accordance with the standards UNE 23585:2004 (in which

    the exclusion of mechanical or forced evacuation systems described in the last paragraph of

    section "0.3 Applications" should not be taken into consideration).

    IMPORTANT BOILER ROOM REGULATIONS

    UNE 60601:2006 (annuls: UNE 60601:2000)

    DESCRIPTION:

    This covers stand-alone machines and equipment that generate heat or cold or

    cogene ration ma chines that use gas fuels.

    PURPOSE:

    This regulation lays down a) the requirements applicable to premises or buildings that

    contain generators used to produce heat and cold used a heat-carrying fluid, excluding the

    air and including the steam at a maximum working pressure lower than or equal to 0.5 bar,

    with an overall nominal working power of above 70 kW , or b) cogene ration equipme nt with a

    nominal hea t consumption of above 70 kW that use gas fuels. This regulation also app lies

    to outdoor stand-alone equipment, either heat- or cold-producing or cogeneration.

    DETAILS:

    Extractors must consist of a centrifugal air extractor installed outside the building. The

    casing-wheel assembly must be made from materials that do not produce mechanical

    sparks and must be driven by an electric motor outside the assembly.