solar thermal energy system for renewable desalination by
TRANSCRIPT
Solar Thermal Energy System for Renewable Desalination
by Ryan McLaughlin
A THESIS
submitted to
Oregon State University
Honors College
in partial fulfillment of the requirements for the
degree of
Honors Baccalaureate of Science in Chemical Engineering (Honors Scholar)
Presented June 4, 2020 Commencement June 2020
AN ABSTRACT OF THE THESIS OF
Ryan McLaughlin for the degree of Honors Baccalaureate Science in Chemical Engineering presented on June 4, 2020. Title: Solar Thermal Energy System for Renewable Desalination.
Abstract approved:_____________________________________________________ Nicholas AuYeung
Natural freshwater availability is decreasing as the global population increases.
Advances in desalination technologies aim to produce fresh water in an economical way.
More sustainable energy sources are desired for these desalination plants to limit the carbon
footprint of water production since global carbon dioxide production is exacerbating
freshwater scarcity. Solar thermal energy is desirable because the technology is much more
efficient at producing the heat required for desalination than traditional photovoltaic solar
energy. Dr. Bahman Abbasi, Dr. Nicholas AuYeung, Dr. James Klausner, Dr. Jelena Srebric,
Dr. Chris Hagen, Dr. Behrooz Abbasi, Mohammed Elhashimi, and Deepak Sharma have
been designing a mobile desalination unit that utilizes humidification-dehumidification
cycles to desalinate water. The system is to be powered by a solar thermal system. The
primary objective of this report is to provide a comparison between available heat transfer
fluids and solar collectors used in this solar thermal system as well as provide a preliminary
economic analysis of the system.
Key Words: Desalination, Feasibility Analysis, Economic Analysis, Renewable Energy Corresponding e-mail address: [email protected]
©Copyright by Ryan McLaughlin June 4, 2020
Solar Thermal Energy System for Renewable Desalination
by Ryan McLaughlin
A THESIS
submitted to
Oregon State University
Honors College
in partial fulfillment of the requirements for the
degree of
Honors Baccalaureate of Science in Chemical Engineering (Honors Scholar)
Presented June 4, 2020 Commencement June 2020
Honors Baccalaureate of Science in Chemical Engineering project of Ryan McLaughlin presented on June 4, 2020. APPROVED: _____________________________________________________________________ Nicholas AuYeung, Mentor, representing Chemical Engineering _____________________________________________________________________ Bahman Abbasi, Committee Member, representing Mechanical Engineering _____________________________________________________________________ Mohammed Elhashimi, Committee Member, representing Mechanical Engineering _____________________________________________________________________ Deepak Sharma, Committee Member, representing Mechanical Engineering _____________________________________________________________________ Toni Doolen, Dean, Oregon State University Honors College I understand that my project will become part of the permanent collection of Oregon State University, Honors College. My signature below authorizes release of my project to any reader upon request. _____________________________________________________________________
Ryan McLaughlin, Author
Acknowledgements
I am so grateful for the endless support I have received from faculty, friends,
and family. I would first like to thank my thesis mentor Dr. Nicholas AuYeung. After
my previous mentor had left Oregon State, he had provided me with the opportunity
to join this project that he was working on. He pushed me and gave the support I
needed to navigate the a thesis defense during the Covid-19 pandemic. I am forever
thankful for the opportunity he provided me with to learn more about renewable
energy and desalination, two fields that I have always been passionate about.
I would also like to thank Dr. Bahman Abbasi, Mohammed Elhashimi, and
Deepak Sharma for letting me collaborate with them on this meaningful project as
well as supporting me as committee members. Your support, assistance, and
collaboration along the way was greatly appreciated.
This journey would also not have been possible without my best friend, Kelly
Landreth. She has been the best person to rough life’s rapids with and I could not
imagine life without you. Your love, support, and charisma mean the world to me.
You never fail to put a smile on my face.
I would like to thank my family for helping me get through college. I can’t
imagine how much work it was to raise me—so thank you JR, mom, and dad! I really
appreciate your endless love, support, and dad jokes. It has taken a village to get me
here and I can never begin to express my gratitude to the rest of my grandparents,
aunts, uncles, cousins, and other brother Jackson for helping me get where I am.
Table of Contents
1. Introduction ................................................................................................. 1
2. Background ................................................................................................. 3
Common Desalination Methods ............................................................................. 3
Current Desalination Project ................................................................................. 5
Solar Thermal Collection Technologies ................................................................. 6
Solar Thermal Heat Transfer Fluids ..................................................................... 9
Preliminary Solar Thermal Energy System Design ............................................... 11
3. Methodology ............................................................................................... 14
Solar Collector Comparison Criterion .................................................................. 14
Heat Transfer Fluid Comparison Criterion .......................................................... 16
Heat Exchanger Area ........................................................................................... 18
Economic Analysis ............................................................................................... 19
4. Results and Discussion ................................................................................ 23
Solar Thermal Collector Comparison ................................................................... 23
Heat Transfer Fluid Comparison ......................................................................... 27
Economic Analysis ............................................................................................... 32
References ............................................................................................................ 39
Appendix A – Desalination System ....................................................................... 44
Appendix B – Solar Thermal Collector Decision Matrix ....................................... 45
Appendix C – Heat Transfer Fluid Decision Matrix ............................................. 46
Equation 1: ................................................................................................................. 18
Equation 2: ................................................................................................................. 18
Equation 3: .................................................................................................................. 19
Table 1: Star Diagram Criterion ................................................................................. 17
Table 2: HX Fluid Volume Needed ............................................................................ 32
Table 3: System Cost .................................................................................................. 33
Table 4: Solar Thermal Collector Decision Matrix .................................................... 45
Table 5: Heat Transfer Fluid Decision Matrix ............................................................ 46
Figure 1: Energy Collection and Heat Transfer System ............................................. 12
Figure 2: Maximum Temperature Comparison .......................................................... 23
Figure 3: Power Generation per Radiated Area Comparison ..................................... 25
Figure 4: Collector Number Comparison ................................................................... 26
Figure 5: Heat Transfer Fluid Individual Star Diagrams ............................................ 28
Figure 6: Heat Transfer Fluid Combined Star Diagram ............................................. 29
Figure 7: Heat Transfer Fluid Cost Comparison ......................................................... 31
Figure 8: HT Fluid Temperature Change Sensitivity Analysis .................................. 34
Figure 9: Desalination System .................................................................................... 44
1
1. Introduction
844 million people—about 10% of the global population—do not have access
to clean water [1]. Global water insecurity issues are projected to be exacerbated as
carbon emissions increase, global climate changes and human population increases.
Drought is projected to affect 35% of global land mass this year [2]. More
specifically, Africa is extremely prone to water insecurity issues in the future because
of poor water infrastructure, political instability, and a high percentage of developing
nations prone to rapid population growth as well. Droughts exacerbate a paradox of
poverty in which poor, unstable countries are unable to develop water infrastructure
due to economic stress while water stress produces instability that prevents the
development and economic success. For instance, droughts between 1999 and 2000
dropped Kenya’s GDP a whole 16% [3]. According to the World Health Organization
and UNICEF, at least 44% of the population in Africa do not have access to safe and
reliable fresh water sources as of 2007 [2]. According to the UN, 80% of diseases and
30% of deaths are the result of unsafe drinking water [3]. Without the advanced water
purification technologies that developed countries have, water insecurity issues will
likely continue to plague these developing countries.
Desalination is a method of generating fresh water by removing the salts out
of saltwater. The salt and water are separated through several techniques including
but not limited to filtration, ion exchange, distillation, and humidification-
dehumidification cycles. Desalination helps increase the limited amount of fresh
water available on the planet.
2
Dr. Bahman Abbasi, Dr. Nicholas AuYeung, Dr. James Klausner, Dr. Jelena
Srebric, Dr. Chris Hagen, Dr. Behrooz Abbasi, Mohammed Elhashimi, and Deepak
Sharma have been designing a desalination unit to be deployed in Nigeria. The
desalination unit will purify 3500 liters per hour of fresh water. The system—outlined
in Appendix A—utilizes a humidification-dehumidification cycle to extract the solids
out of a saltwater stream to produce fresh water. Dry air is fed into a converging
nozzle which accelerates and heats it with low-grade solar thermal energy. The hot,
dry air is then used to atomize and vaporize the saltwater, which is fed into a cyclone
for separation. The warm humid air is then fed into a condenser that cools the stream
to condense the water out of the air stream. The air and condensed water stream is fed
into an air-water separator that separates the dry air and fresh, liquid water. The dry
air recycles back into the dry air converging nozzle section while the fresh, liquid
water is fed into a heat recuperator that preheats incoming cool saltwater before it is
fed into the atomizing area.
The purpose of this project is to generate a preliminary design of the solar
thermal collection system used to heat up the air in the compression tubes. The
system will consist of a solar thermal collector, heat transfer fluid, a storage tank,
piping, and a heat exchanger. The primary focus is to review what solar thermal
collectors and heat transfer fluids would be best for this system, but a secondary
analysis of system cost will be used to determine the feasibility of the system.
3
2. Background
Common Desalination Methods
Desalination methods are rapidly evolving as the need to generate more fresh
water increases with changing climate and increasing global population. This section
is meant to be a brief summary of the technologies currently available on the market,
but is not an exhaustive list of the desalination methods available. Between 2008 and
2012, the capacity of desalination plants increased globally from 52,333,950 cubic
meters per day to 79,000,000 cubic meters per day [4]. To be potable drinking water,
the total dissolved solids in the water—a measure of salinity—must be below 1000
milligrams per liter [5]. There are three general desalination methods: thermal
processes, membrane processes, and chemical processes [6].
Some of the most common thermal desalination processes include multi-stage
flash distillation, multi-effect distillation, thermal vapor compression, and mechanical
vapor compression [4]. The processes utilize thermal cycles to extract the solids out
of fresh water through phase separations [5]. Thermal desalination methods typically
require a significantly larger energy input than membrane methods, which causes
undesirably high energy costs of operation [4]. However, these processes are
extremely effective at treating large volumes of saltwater with high levels of salinity
and are desirable because they can utilize heat rather than electricity as an energy
source, which is much cheaper. The primary issue with the high-output thermal and
distillation plants is that most of them emit high levels of carbon dioxide [7]. Carbon
dioxide production is problematic because it further exacerbates climate change,
which is a driver for water insecurity because it increases drought frequency [3].
4
However, renewable sources of energy are used for some thermal and distillation
desalination processes to ensure more sustainable operation [7].
Reverse/forward osmosis, electro-dialysis, and nanofiltration are common
membrane desalination techniques [6]. Membrane desalination techniques work to
remove salt from water by creating a driving force for mass transfer across a
membrane to separate the solids and water [5]. These processes are associated with
large initial investments followed by low energy costs because most of them require
expensive, energy efficient technology [4]. However, many membrane processes
require pre-treatment to prevent the rapid fouling of the membrane used in the
process. Membrane processes usually rely on electrical energy rather than thermal
energy to generate a pressure drop in the system, which is more expensive [8].
Liquid-liquid extraction, adsorption, ion-exchange, and gas hydrate processes
are a few of the more common chemical desalination techniques [5]. As the name
suggests, chemical desalination techniques utilize chemical reactions to extract solids
out of the saltwater [6]. Currently, most of these processes are not considered
commercially feasible to treat highly saline water [5]. Solar thermal energy will be
used in the system as it is a more feasible and efficient off-grid energy source.
Humidification-dehumidification cycles are included in thermal desalination
methods. In these cycles, a hot air stream is humidified using a saltwater stream. The
solids in the saltwater are left behind during humidification or within in a cyclone
section that removes salt in some systems. The air then enters a dehumidifier—or
condenser—where the temperature of the air decreases until fresh water condenses
out of the air. The now dry air is recycled back into the humidification section and the
cycle repeats. This technology has great potential to be used in decentralized
5
applications with freshwater production rates less than several thousand cubic meters
per day [9].
Current Desalination Project
A multi-university team led by Oregon State University is working on
constructing the desalination unit that is projected to be capable of producing 3500
liters of fresh water per day from a water source that has 100,000 ppm of total
dissolved solids. The system—outlined in Appendix A—utilizes humidification-
dehumidification cycles to desalinate the source water. Dry air first enters a
converging nozzle with a heat exchanger powered by solar thermal energy. The dry
air then comes into contact with warm saltwater and atomizes it since the air is
traveling at high speeds. The now humid stream of air enters a cyclone system in
which any salt in the air stream is separated from the air. The humid air then enters a
condenser unit that cools the air stream down to get the water out of the air stream
through condensation. The air and condensed water are fed into an air-water separator
that separates the dry air and fresh, liquid water. The dry air recycles back into the
converging nozzle section while the fresh, liquid water is fed into a heat recuperator
that preheats cool saltwater before the saltwater is fed into the atomizing area.
The system is meant to provide fresh water for off-grid communities with scarce
fresh water sources that are near saltwater sources. The system will primarily be
powered by thermal energy so that the system can be sustainable and self-contained.
The purpose of this project is to review solar thermal collectors, heat transfer fluids,
as well as provide a preliminary design for the energy collection and heat transfer
system that will be used to power the system. The energy collection and heat transfer
system will be used to heat the dry air in the converging nozzles before the air stream
6
atomizes the saltwater. The heat collection and energy transfer system will be
designed to operate around 200 °C.
Solar Thermal Collection Technologies
Solar thermal collectors harvest the light energy from the sun and convert it into
thermal energy. Collector technologies may either be passive or tracking. Unlike
tracking collectors, passive collectors do not track solar movement across the sky
[10]. Most solar thermal technologies are broken into two general categories:
concentrating and non-concentrating. Concentrating technologies work by reflecting
incoming solar radiation by focusing solar onto a small absorption surface while non-
concentrating collectors have large absorption areas and do not concentrate incoming
solar radiation [11].
Concentrating solar thermal collectors are typically used for higher temperature
applications because they are generally able to achieve higher temperatures than non-
concentrating collectors [10]. Common concentrating collector technologies include
parabolic trough collectors, parabolic dish collectors, linear Fresnel collectors, and
heliostat field collector [11].
Parabolic trough collectors are systems which utilize U-shaped mirrors to reflect
solar radiation onto a typically rod-shaped receiver that is the length of the mirror
[12]. Parabolic dish collectors are comprised of a dish shaped mirror that focuses onto
a receiver at the focal point of the dish [10]. Since the parabolic dish collector is a
point focus rather than an axis focus, the parabolic dish collector can usually achieve
higher temperatures than parabolic trough collectors [12]. Linear Fresnel collectors
are comprised of structures of flat mirror strips that focus onto either one or multiple
rod-like receiver(s) that run along the length of the mirrors [10]. Linear Fresnel
7
mirrors mimic parabolic trough collector reflecting patterns, but are comprised of a
series of flat mirrors instead of one U-shaped mirror [13]. Most of these systems are
larger and less portable than parabolic dish and parabolic trough collectors; however,
there have been more recent research in more compact Linear Fresnel collector
systems. Heliostat collector systems are similar to Linear Fresnel collectors in the
sense that both are comprised of multiple reflectors focusing on one or multiple
common absorbers. Heliostat systems are comprised of a system of large mirrors that
direct solar radiation towards a central tower that acts a receiver [12]. Heliostat
collector systems are typically large and capable of producing massive power outputs
but require the largest land area and a substantial water supply [14]. The Ivanpah
Solar Electric Generating System in the United States is capable of producing 392
MW, but utilizes about 3500 acres of land [10].
Non-concentrating solar thermal collection systems are typically used for lower
temperature applications because the systems are unable to reach higher temperatures
without concentrating components. Non-concentrating collectors are desirable
because many have a higher efficiency than concentrating collectors [15]. However,
most non-concentrating collectors can only achieve a maximum temperature of
200 °C and most have poor efficiency at that temperature [11]. Non-concentrating
collectors include flat plate collectors, hybrid PVT collectors, and evacuated tube
collectors [11, 16].
Flat plate collectors generally consist of glazing covers containing tubes filled
with heat transfer fluid fixed on an absorber plate [11]. The collectors need to be
oriented to maximize incoming solar radiation since they are typically permanently
fixed in position [16]. Flat plate collectors are typically used at operating
8
temperatures below 100 °C and one of the cheapest solar thermal collectors [11].
Hybrid PVT (Photovolatic-Thermal) systems are capable of producing both heat and
electrical energy. The hybrid PVT collectors consist of a traditional photovoltaic cell
found in most traditional solar panels as well as an heat absorption plate attached to
the photovoltaic cell to capture heat that would otherwise be lost from the cell.
Hybrid PVT cells are regarded as a more efficient alternative to traditional solar
panels available on the market because Hybrid PVT collectors capture this heat that
would otherwise be lost; however, they are only efficient in low temperature
applications [17]. Evacuated tube collectors (ETCs) are the only non-concentrating
collectors capable of operating efficiently around 200 °C. There are two types of
ETCs: heat pipe and direct flow. Heat pipe ETCs are comprised of a series of hollow
glass cylinders under vacuum with a thermally conductive metal pipe running along
the length of the cylinder. The thermally conductive metal is fixed to an absorber
sheet that transfers incoming solar radiation to the pipe. The pipe is filled with a heat
transfer fluid that undergoes a phase change to store the captured solar energy [11].
Direct flow ETCs are comprised of hollow glass cylinders under vacuum with a flat
or curved absorber plate running along the diameter of the tube. A metal, thermally
conductive pipe containing heat transfer fluid is welded to the absorber plate. The
absorber plate captures incoming solar radiation and transfers to the heat transfer fluid
contained in the metal pipe [11, 18]. Direct flow ETCs are usually more suitable for
high temperature applications because they have lower thermal loss coefficients [18].
The solar collectors primarily researched in this report were parabolic trough
collectors, parabolic dish collectors, and direct flow evacuated tube collectors. The
reason of this selection was that these types of collectors were the most transportable
9
and efficient collectors for operation around 200 °C. The only other collectors
capable of efficient operation around 200 °C were heliostat and Linear Fresnel
collection systems, which were considered too difficult to transport between sites.
Solar Thermal Heat Transfer Fluids
The heat transfer fluids in the system need to be capable of operation between
ambient temperatures and 200 °C, since the solar thermal system will only be capable
of operation during daylight. Common heat transfer fluids for solar thermal collectors
include oils, molten salts, water/glycol mixtures, and pressurized gasses [19].
There are four categories of heat transfer oils used in solar thermal applications:
synthetic hydrocarbon oils, paraffin oils, silicone oils, and aromatic refined mineral
oils [19, 20]. Synthetic hydrocarbon oils are typically associated with higher thermal
conductivity and lower viscosity than mineral oils, which makes them more desirable
heat transfer fluids [19]. Synthetic oils also have a relatively long lifespan of 5 to 10
years and are generally non-toxic [21]. However, mineral oils are a byproduct of the
petroleum industry, which drives down the cost of the heat transfer fluid. Mineral oils
also have low viscosities, low toxicities, high stabilities, and high thermal
conductivities, which makes them a viable and cheaper alternative than synthetic oils
for this solar thermal system [22]. Paraffin oils are petroleum-based heat transfer fluid
with larger temperature ranges and lower viscosities than synthetic and mineral oils,
but are typically toxic and require double-walled heat exchangers [21]. Silicone oils
are an excellent option for solar thermal applications because they freeze at low
temperatures, boil at high temperatures, are non-corrosive, and very resistant to
oxidation. However, silicone oils usually have higher viscosities and low heat
capacities, which greatly increases the pumping power needed [23].
10
Molten salts are salt mixtures primarily composed of nitrates that are used for heat
transfer fluids. These salts are commonly used in high temperature applications
because they have high densities, high heat capacities, high thermal stabilities, and
low vapor pressures [24]. However, most of these molten salts have high melting
points that are problematic for operation because the salts can freeze in heat transfer
piping [25]. The melting points for molten salts typically range between 150 °C and
600 °C [26]. Most solar thermal plants have alternative energy sources during dark
hours to heat the system and prevent freezing salts from destroying heat transfer
piping [27]. Molten salts are not suitable for this solar thermal system because the
system is only operational during the day and the temperature of the system is too
low, which would cause molten salts to freeze.
Water and glycol mixtures are common heat transfer fluids for low to medium
temperature systems. The water and glycol mixtures are extremely desirable heat
transfer fluids because of their large range of operating temperatures, high heat
capacity, low viscosity, and price. However, water and glycol mixtures are only
thermally stable to temperatures up to 175 °C [28]. For this reason, water and glycol
mixtures are not suitable for this solar thermal system since it operates around
200 °C.
Pressurized gases are also commonly used for solar thermal applications.
Commonly used pressurized gases in solar thermal systems include air, carbon
dioxide, helium, hydrogen, and water [16]. Pressurized gasses are desirable heat
transfer fluids because they have much wider operating ranges and they are very
cheap [16, 29]. However, the fluid (e.g. density) and heat transfer properties of gases
limit the efficiency of pressurized gasses in solar thermal applications [16, 25].
11
The primary heat transfer fluids reviewed in this analysis are silicone, aromatic
mineral, paraffin, and synthetic oils. These heat transfer fluids were most suitable for
this solar thermal system because of their fluid, heat transfer, material compatibility,
and toxicology properties. Molten salts were excluded from this analysis because of
their high melting points and low material compatibility. Pressurized gases were
excluded from this analysis because of their unfavorable heat transfer properties.
Water and glycol mixtures were excluded from this analysis because of stability
concerns at the operating temperature of the system. Only non-toxic paraffin oils
were included in this analysis to ensure safe operation of the desalination system.
Preliminary Solar Thermal Energy System Design
The heat transfer and energy collection system will be comprised of four simple
components: the solar thermal collection system, heat transfer fluid storage, heat
transfer fluid pump, and heat exchanger. The system is outlined in Figure 1: Energy
Collection and Heat Transfer System. The solar thermal collection system collects
solar radiation and transfers the energy to a heat transfer fluid. The heat transfer fluid
storage is a tank in which thermal energy will be stored in the heat transfer fluid to
allow for 30 minutes of operation without light. This will help ensure that the process
is capable of running with scattered clouds that would decrease the amount of
incoming solar radiation that the solar thermal collection system can collect. The fluid
is pumped out of the heat transfer fluid storage tank by a pump. The pump will be a
self-priming oil pump capable of withstanding process temperatures exceeding
200 °C. The pump outlet flows into the heat exchanger, which will be used to heat the
air stream that atomizes the saltwater in the desalination unit. The objective of this
report is to provide a preliminary design of the energy collection and heat transfer
12
Heat Transfer Fluid to Air Heat Exchanger
Heat TransferFluid Storage
Heat TransferFluid Pump
Solar Thermal Collection System
Figure 1: Energy Collection and Heat Transfer System
Solar energy is collected and transferred to a heat transfer fluid in the solar thermal collection system. The fluid is then transported to a heat transfer fluid storage tank, which is sized to hold about 30 minutes of heat transfer fluid. The heat transfer pump provides the pressure throughout the system to move the fluid through the piping between components. The outlet of the heat transfer pump goes into the heat exchanger, which heats the process that is used to atomize the saltwater.
system that focuses on the solar thermal collection system and heat transfer fluid used
in the process as well as provide an estimate of the energy cost generated in the
system.
The solar thermal collection system will be designed to provide enough
energy to operate at 200 °C. The system will be designed to produce 400 liters per
hour of fresh water with an energy requirement of 54 kWh/m3 of water. A secondary
goal of the solar thermal collection system is to have it be compact or mountable on a
large bus so that the system may be easily transported to different locations
experiencing water insecurity. Another objective of the solar thermal collection
system is that the system is simple enough that it can be operated easily without
rigorous training. This would allow for a system to be easily deployed, operated, and
managed by local governments in underdeveloped countries.
13
The heat transfer fluid in the system will need to be stable beyond the high
operating temperature of 200 °C. Ideally, the stability and boiling point of the fluid
will be well above the operating temperature (more than 50 °C) so that the heat
transfer fluid would not degrade or cause hazards in the event that the system is out of
specification. Ideally, the heat transfer fluid will be non-toxic so that if the heat
transfer fluid were to enter the air stream or an operator was exposed to it, no adverse
health effects would develop. In addition to that, a non-toxic heat transfer fluid would
decrease the need for complex heat transfer fluid disposal and replacement. Heat
transfer fluid disposal is a very critical factor because most of the areas where the
desalination systems would be deployed would not have a means of treating
hazardous chemicals. In addition to that, the reactivity of the heat transfer fluid
should be low so that there is not a large flammability or corrosion risk. The heat
transfer properties, fluid properties, and cost are also important because they govern
the economic feasibility of the entire energy collection and heat transfer system.
The total cost of the system outlined in Figure 1: Energy Collection and Heat
Transfer System was used to determine a rough estimate for the cost of water
production in the desalination system. The cost of energy for the solar thermal energy
subsystem of the desalination unit was estimated by dividing the installed cost of the
system by the total energy would theoretically produce over the system lifetime. The
levelized cost of water for the energy system was estimated based upon the lifetime
and initial cost of the system and heat transfer fluid.
14
3. Methodology
Solar Collector Comparison Criterion
The solar collectors will be compared based upon the maximum temperature,
energy cost, and power per radiated area. Various solar thermal collectors were
selected based upon performance, ease of transportation, and operating temperature to
compare. The solar collectors compared include the Apricus ETC-20, SunMaxx Solar
VHP 10, SunMaxx Solar VDF 20, Solar Panels Plus SPP-25, Absolicon T160, Artic
Solar XCPC, Norwich Technologies SunTrap, and a parabolic dish collector from
researchers at Oxford University (UK). The Apricus ETC-20 is an evacuated tube,
heat pipe collector with 20 tubes [30]. The SunMaxx Solar VHP 10 and VDF 20 are
heat pipe and direct flow evacuated tube collectors, respectively. The VHP 10 and
VDF 20 have 10 and 20 heat collecting tubes, respectively [31, 32]. The Solar Panels
Plus SPP-25 is a 25 tube evacuated tube collector [33]. The Absolicon T160 is a
parabolic trough solar concentrator [34]. The Artic Solar XCPC is a panel comprised
of a series of small parabolic trough collectors [35]. Norwich Technologies SunTrap
is a parabolic trough receiver optimized for high temperature applications [36]. The
parabolic dish collector from Oxford is a parabolic dish collector still in the
experimental stage that is capable of high temperature operation [37].
The maximum temperature statistic is the stagnation temperature of the
collector. The stagnation temperature is the temperature achieved when the heat
transfer fluid in the collector is not flowing through the system [38]. While this
statistic does not provide specifics about the efficiency at different temperatures for
each collector, it does provide insight as to the temperatures at which the system is
capable of being efficient. Greater stagnation temperatures suggest higher operating
15
temperature ranges and greater efficiencies at higher temperatures since efficiency
generally decreases with temperature under ambient conditions.
The energy cost between solar collectors was compared by dividing the cost of
the unit by the peak output. The peak output of each collector was found from each
collector’s technical specification sheets provided by the company. The peak output is
the maximum power output for the system. The SRCC clear day standard of 2000
BTU/ft2-day or 1000 W/m2 of incoming solar radiation was used, depending on what
information was available for each collector. The cost for each unit was based upon
quotes or information from the company which develops the solar panels. A lower
energy cost indicates that a solar collector is more economically efficient, which
drives the cost of the energy collection and heat transfer system down.
The power per radiated area is calculated by dividing the peak output by the
cross-sectional area at the largest cross-section of the collector. This statistic is meant
to illustrate how much energy each collector can generate per space it takes up. The
power per radiated area is a useful statistic for the solar thermal system because it
provides insight about how portable the unit can be. If the power per radiated area is
greater, the solar thermal collection system will take up less space and be more
transportable. This is important when designing a desalination unit that is meant to be
portable.
A summary of the collectors explored along with the statistics of each collector
may be found in Table 4: Solar Thermal Collector Decision Matrix. The summary
also includes two collectors—a parabolic dish collector from a research team at
Oxford and the SunTrap absorption tube—that have the potential to be a great fit for
the system, but not enough information was available to include them in the report.
16
Heat Transfer Fluid Comparison Criterion
The heat transfer fluids that will be compared were selected based upon their
performance and ability to withstand process temperatures. Only mineral, synthetic,
paraffin, and silicone oils were compared because of the reasons outlined in the Solar
Thermal Heat Transfer Fluids section. The heat transfer fluids compared are
Duratherm S, Duratherm 630, Therminol XP, and Therminol 68. Each heat transfer
fluids compared will be based upon safety, material compatibility, thermodynamic
properties, heat transfer properties, fluid properties, and cost. A star diagram will be
used to compare the safety, material compatibility, thermodynamic properties, heat
transfer properties, and fluid properties while a bar graph will be used to compare the
cost of fluids.
The star diagram criterion is summarized in Table 1: Star Diagram Criterion. The
safety section describes how toxic, flammable and reactive the substance is. This is
quantified by summing the health, flammability, and reactivity section of the NFPA
rating. A lower NFPA score indicates a less hazardous material. The compatibility
section quantifies the corrosivity and fouling/oxidizing tendency of the heat transfer
fluid. The thermodynamic properties illustrate the operating range of the fluid which
includes the freezing point, boiling point, and point at which the substance is
unstable. The heat transfer properties section is a way of illustrating the heat transfer
performance of the fluid. This includes the heat capacity and thermal conductivity.
The fluid properties section includes the density, kinematic viscosity, and thermal
expansion coefficient of the fluid. Greater scores in each category indicate higher
performance in that area. The heat transfer fluid with the greatest area on the star
diagram has the greatest overall performance.
17
1 Combined NFPA score greater than 9 1 Corrosive to most heat
transfer metals
2 Combined NFPA score between 7-9. 2 Meets criteria of above and
below options.
3 Combined NFPA score between 5-7 3
Relatively non-corrosive to most heat transfer metals but prone to fouling and
oxidation.
4 Combined NFPA score between 3-5. 4 Meets criteria of above and
below options.
5 Combined NFPA score less than 3. 5 Non-corrosive and non-
fouling
1Boiling Point < 200 - 250°C
Unstable < 280 - 300°C Freezing Point 5 - > 10°C
1Cp less than 2.2 kJ/kg-K
Thermal Conductivity less than 0.09 W/m-K
1
Kinematic Viscosity > 0.8 cP Density < 700 kg/m3
Thermal Expansion Coefficient >12 %/°C
2 Meets criteria of above and below options. 2 Meets criteria of above and
below options. 2 Meets criteria of above and below options.
3Boiling Pt.: 250 - 310°C
Unstable: 300- 340°C Freezing Pt: -5 - 5°C
3Cp between 2.2 and 2.6
kJ/kg-K Thermal Conductivity between 0.09
and 0.11 W/m-K
3
Kin. Viscosity: 0.8 - 0.7 cP Density: 700 - 800 kg/m3
Thermal Expansion Coefficient: 10-12 %/°C
4 Meets criteria of above and below options. 4 Meets criteria of above and
below options. 4 Meets criteria of above and below options.
5Boiling Point > 310°C
Unstable > 340°C Freezing Point < -5 °C
5Cp greater than 2.6 kJ/kg-K
Thermal Conductivity greater than 0.11 W/m-K
5
Kinematic Viscosity < 0.7 cP Density > 800 kg/m3
Thermal Expansion Coefficient < 10 %/°C
Thermodynamic Properties Heat Transfer Properties Fluid Properties
Star Diagram CriterionSafety Compatibility
Table 1: Star Diagram Criterion
Below is the star diagram criterion for comparing the safety, compatibility, thermodynamic properties, heat transfer properties, and fluid properties. A greater number corresponds to greater performance. The safety section is rated based upon the NFPA safety rating of the chemical. The NFPA score is calculated by adding up all of the numbers in the NFPA safety rating. The compatibility section helps describe the corrosivity and resistance to fouling/oxidation of the heat transfer fluid.
18
The cost of each heat transfer fluid will be calculated based upon an energy
basis. The purpose of this is to take out factors in density when calculating the cost of
each fluid because the cost per unit energy is a more telling parameter of economic
performance. The cost of each fluid is calculated by dividing the cost per unit volume
by the density, heat capacity, and operating temperature change. The operating
temperature change—5 °C—is the temperature change that the heat transfer fluid will
experience in the heat exchanger that heats the air used in the desalination process.
This temperature change will be modified accordingly when optimizing the heat
exchanger in the desalination system. A lower energy cost is desirable because that
indicates less money needs to be spent on heat transfer fluid in the process.
A summary of the heat transfer fluid properties and their performance may be
found in Table 5: Heat Transfer Fluid Decision Matrix.
Heat Exchanger Area
The total heat exchanger area for the process was calculated using the
following equation:
Equation 1:# = %&∆()*
where # is the energy demand, % is the overall heat transfer coefficient, & is the heat
exchanger area, and ∆()* is the log mean temperature difference. # was calculated
using the specified basis of 400 liters of fresh water produced per hour and ceiling
energy use of 54 kW-hr of energy needed per cubic meter of water purified.
% was calculated with the following equation:
Equation 2:+
,=
+
-.+
0
1+
+
-2
where ℎ4 is the convective heat transfer coefficient of the inside fluid (air – assumed
to be 100 W/m2-°C), ℎ5 is the convective heat transfer coefficient of the outside fluid
19
(heat transfer fluid – assumed to be 5000 W//m2-°C), 6 is the thickness of the heat
exchanger wall (assumed to be 1.5 mm), and 7 is the thermal conductivity of the heat
exchanger material (assumed to be 20 W/m-°C, that of stainless steel). This led to an
overall heat transfer coefficient of 97 W/m2-°C.
∆()* was calculated with the following equation:
Equation 3: ∆()* =89:,<=9>,?@=89:,?=9>,<@
ABC8D:,<ED>,?@
8D:,?ED>,<@F
where (G,+ is the temperature of the heat transfer fluid entering the heat exchanger
(200 °C), (G,H is the temperature of the heat transfer fluid leaving the heat exchanger
(195 °C), (I,+ is the temperature of the air entering the heat exchange (70 °C), and
(I,H is the temperature of the air leaving the heat exchanger (125 °C). The log mean
temperature difference is 98 K. The total heat exchanger area needed with these
specifications is 2.3 m2.
Economic Analysis
For the economic analysis, a few assumptions need to be made since this
report focuses primarily on finding the ideal heat transfer fluid and solar collector
rather than completely designing the system. The assumptions for the basis of the 10
year economic analysis are:
• The total heat transfer fluid needed for the system will be that of 30 minutes
of heat transfer fluid moving through the heat exchanger
• The piping, valves, and fittings is 3% of the tank cost [39]
• The electrical work and instrumentation is 7% of the tank cost [39]
• The storage tank will be sized to house 1.5x the heat transfer fluid in the
system
20
• The heat transfer fluid will need to be replaced once every five years
• The system will produce 400 liters of fresh water per hour for 8 hours
• The system will be active 355 days out of the year, with 10 days of downtime
and clouds assumed
• The incoming solar energy during the 8 hours of operation will be 80% of the
SRCC clear sky standard
• Installed costs of equipment are 1.3x higher than the capital cost [39]
• The 2010, 2011 and 2020 CEPCIs are 532.9, 585.7 and 668, respectively [40,
41, 42]
• There is a 10 year life time for the solar collectors
• There is a salvage value of 0 after the 10 year period
The cost per cubic meter of fresh water generated will be calculated over a 10
year period based upon the energy demand of the system. The total cost per cubic
meter of water will be calculated with the following equation:
JKL0MN =JI5AAMO05N ∗ QI5AAMO05N + ∑JI5ST5BMB0U + JVWST +
6XAW4Y6UZU0MS
∗ J[AW4Y
\]L0MN
where JKL0MN is the cost of water per cubic meter, JI5AAMO05N is the cost one collector,
QI5AAMO05N is the number of collectors needed, ^_TMNL045B is the energy needed for
operation, ∑JI5ST5BMB0U is the installed cost of piping, valves, fittings,
instrumentation, storage tanks, storage tank supports, site work, foundations,
electrical work, and instrumentation, JVWST is the installed cost of the pump in the
system, 6XAW4Y is the lifetime of the heat transfer fluid, 6UZU0MS is the lifetime of the
21
system, J[AW4Y is the total cost of heat transfer fluid needed, and \]L0MN is the volume
of water produced over the lifetime of the plant.
JI5AAMO05N was calculated by multiplying collector cost estimates or quotes by
the installation factor (1.3) to account for installation costs. QI5AAMO05N was calculated
dividing the power requirements of the system (54 kWh/m3 water, 400 L/hr of water)
by 80% of the peak output under SRCC clear day conditions. ∑JI5ST5BMB0U was
calculated by summing the installed energy costs for piping, valves, fittings,
instrumentation, storage tanks, storage tank supports, site work, foundations,
electrical work, and instrumentation. The cost of the storage tank and pump were
found based upon the following cost correlation:
J4 = JNMX NMX a4
NMXbc
where J4 is the cost of the storage tank or pump, JNMXis the reference cost per physical
parameter, NMX is the reference physical parameter that the cost is based upon, 4 is
the actual physical parameter that the cost is based upon, and b is an empirically
determined sizing exponent [43]. For the pump, JNMX, NMX, and d were
$357.13/(m3/hr), 0.98 m3/hr, and 0.6, respectively. 4 was the volumetric flow rate of
heat transfer fluid for the pump. For the tank,JNMX, NMX, and d were $3883/m3, 0.32
m3, and 0.5, respectively. 4 was the total volume of heat transfer fluid multiplied by
a factor of 1.5 to allow safe operation with thermal expansion. 6XAW4Y (5 years) and
6UZU0MS (10 years) were assumed values based upon reasonable heat transfer fluid and
system lifetimes [19,39]. J[AW4Y was based upon cost estimates and quotes provided in
Table 5: Heat Transfer Fluid Decision Matrix. \]L0MN was calculated by multiplying
22
the volumetric production of water (400 L/hr) by the daily operational time (8 hours
per day) and by the yearly operation time (355 days).
The levelized cost of energy for the CAPEX of the energy system will be
calculated by dividing the CAPEX of the installed equipment of the energy system by
the energy produced over a 10 year. The levelized cost of water will be calculated for
the two highest performing collectors using the highest performing heat transfer fluid.
This will be calculated by dividing the CAPEX of the installed equipment of the
energy system by the total water produced over 10 years of operation.
23
4. Results and Discussion Solar Thermal Collector Comparison
The solar thermal collectors most viable for the operating temperature of 200 °C
were the parabolic trough (Absolicon T160) and XCPC (Artic Solar XCPC)
technologies. The maximum temperature data along with the energy cost for each
collector may be found in Table 4: Solar Thermal Collector Decision Matrix. The
maximum temperature comparison between the collection technologies is illustrated
in below:
Figure 2: Maximum Temperature Comparison
The maximum temperature of each solar collector is the maximum stagnation temperature of the solar collector. While this does not provide specific performance data at the operating temperature of 200°C, it provides a proxy for the highest temperatures at which the collectors can operate efficiently. The x-axis of this figure is calculated by dividing the unit cost of the system by the peak output under SRCC clear sky conditions. The statistics and full name of each collector may be found in Table 4: Solar Thermal Collector Decision Matrix.
ApricusVHP 10 VDF 20
Absolicon
Artic
SPP
0
100
200
300
400
500
0 500 1000 1500 2000 2500 3000
Max
Tem
pera
ture
(°C)
USD/kW
24
The Absolicon T160 and Artic Solar XCPC can achieve significantly higher
temperatures than the other solar collectors. This was expected as the concentrating
technologies of the two collectors allows for much higher operating temperatures.
The maximum recommended operating temperature for the Absolicon T160 is 175 °C
[34]. However, this maximum operating temperature is based upon pressurized steam
generation rather than a thermal oil as the heat transfer fluid. Other lab studies have
shown that the Absolicon T160 is capable of higher temperature operation (greater
than 200 °C) can achieve stagnation temperatures up to 460 °C [44]. The Artic Solar
XCPC on the other hand, is advertised to have capture efficiencies greater than 50%
when operating around 200 °C and has an estimated stagnation temperature of about
320 °C [35, 45]. While the Artic Solar XCPC maximum operating temperature may
be lower than the Absolicon T160, the Artic Solar XCPC may have greater operating
efficiencies. Power generation statistics need to be requested from both companies to
make a more informed decision about which collector has a greater energy output at
the process conditions since collector efficiency varies so much with temperature.
The collector power generation per amount of space that the collector takes up
is a critical parameter because it describes the transportability of the system. The
transportability of the system is very important because the desalination system will
be based upon a design that is easily moveable between areas with people
experiencing water insecurity. The comparison between power per radiated area—
which compares energy generation—is illustrated in Figure 3: Power Generation per
Radiated Area Comparison.
25
Figure 3: Power Generation per Radiated Area Comparison
The figure above illustrates the comparison between power generated and the space taken up by the solar thermal collector. The power used is the power generated under SRCC clear sky conditions during ideal operation (i.e. 1000 W/m2). The radiated area is the cross-sectional area at the largest cross-section of the collector. The dimensions and power data for each collector can be found in Table 4: Solar Thermal Collector Decision Matrix. The power generation per radiated area comparison further supports that the
Absolicon T160 and Artic Solar XCPC are the most viable solar thermal collector
candidates. The Absolicon T160 and Artic Solar XCPC had a power per radiated area
54% and 24% greater than the next best system (Apricus ETC-20), respectively. The
greater power per radiated area means that the Absolicon T160 and Artic Solar XCPC
would take up the least amount of space per energy generated. This is further shown
when comparing how many units would be needed to meet the energy demand of the
desalination unit (see Economic Analysis section calculations about number of units
needed) as explained in Figure 4: Collector Number Comparison.
Absolicon Artic Apricus SPP VDF 20 VHP 10
Pow
er p
er R
adia
ted
Area
(kW
/m2 )
0.0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
26
Figure 4: Collector Number Comparison
The number of collectors was calculated based upon the energy output of each collector under conditions of 80% SRCC clear day rating for 8 hours of operation. This is plotted against the cost per unit, which is the collector cost. The collector cost along with the power generation of each collector may be found in Table 4: Solar Thermal Collector Decision Matrix. The solar thermal collectors with the smallest rectangular area between the axis and
point are the highest performing collectors in this comparison because the total cost
of the collection system may be calculated by multiplying the axis together. The
lowest total collection system cost of the collectors capable of efficient operation at
process temperatures are the Apricus ETC-20, Artic Solar XCPC, and Absolicon
T160. The total collection system cost of the Apricus ETC-20, Artic Solar XCPC, and
Absolicon T160 are $20,000, $20,700 and $14,000, respectively. The Absolicon T160
is the cheapest option by about $6,000 for the system.
While these statistics appear to point to a clear option, one important detail is
not captured by the statistics presented. Artic Solar XCPC is a passive collection
system while the Absolicon T160 requires a tracking system [34, 35]. The tracking
Apricus
VHP 10
VDF 20
Absolicon
Artic
SPP
0
10
20
30
40
50
60
70
80
$0 $500 $1,000 $1,500 $2,000 $2,500
Colle
ctor
s Nee
ded
at 8
0% P
eak O
utpu
t
Cost per Unit
27
system could pose huge maintenance and installation costs that are not included in
solar collector quotes. The primary advantage of the Artic Solar XCPC technology is
that the system can achieve efficient operation at high temperatures without a tracking
system. More technical information from each company about the cost of tracking
systems along with the power output at the operating temperature is needed before
deciding between the Artic Solar XCPC and Absolicon T160 technologies. In
addition to these solar collecting technologies, further exploration of the parabolic
dish collector from Oxford and parabolic trough SunTrap Receiver from Norwich
technologies is necessary before purchasing a solar thermal collector. Not enough
information was available publicly about these projects to compare them, but each
shows promise for efficient high temperature thermal collector operation. The
Harvard parabolic dish collector and Norwich SunTrap receiver are capable of
achieving temperatures greater than 500 °C and 750 °C, respectively. All information
found regarding these projects is included in Table 4: Solar Thermal Collector
Decision Matrix.
Heat Transfer Fluid Comparison
The heat transfer fluids included in the comparison are Duratherm S (silicone
oil), Duratherm 630 (paraffin oil), Therminol XP (mineral oil), and Therminol 68
(synthetic oil). The first comparison was based upon fluid performance in the
categories of safety, material compatibility, thermodynamic properties, heat transfer
properties, and fluid properties. The star diagram criterion can be found in Table 1:
Star Diagram Criterion. The comparison was made in the form of a star diagram to
compare some of the more qualitative categories in a more quantitative manner.
28
1
2
34
5Safety Rating
CompatibilityRating
ThermodynamicProperties
Rating
HT PropertiesRating
Fluid PropertyRating
Duratherm 630
HT PropertiesRating
Fluid PropertyRating
1
23
45
Safety Rating
CompatibilityRating
ThermodynamicProperties
Rating
HT PropertiesRating
Fluid PropertyRating
Therminol 68
HT PropertiesRating
Fluid PropertyRating
1
2
3
4
5Safety Rating
CompatibilityRating
ThermodynamicProperties
Rating
HT PropertiesRating
Fluid PropertyRating
Therminol XP
Figure 5: Heat Transfer Fluid Individual Star Diagrams
The heat transfer fluids Duratherm S (silicone oil), Duratherm 630 (paraffin oil), Therminol XP (mineral oil), and Therminol 68 (synthetic oil) were compared on the basis of safety, material compatibility, thermodynamic properties, heat transfer properties, and fluid properties. The star diagram criterion for each category may be found in Table 1: Star Diagram Criterion.
All four heat transfer fluids have good safety ratings because that was the
primary concern when designing the system. However, Therminol 68 has a lower
rating than the other three heat transfer fluids because it has an NFPA health rating of
2 rather than 0. For this reason, the other heat transfer fluids were more desirable
because there likely will not be chemical treatment facilities near where the
desalination unit will be deployed. This is a huge concern because improper disposal
of the heat transfer fluid could cause adverse health effects or environmental damage
if the substance is toxic (e.g. Therminol 68). The other somewhat esoteric but very
important category is the compatibility rating. The compatibility rating combines the
material compatibility and resistance to fouling or oxidation of each heat transfer
29
fluid. Duratherm S and Duratherm 630 especially excelled in that category because
both are compatible with standard heat exchanger materials and are very resistant to
fouling. Duratherm S is especially resistant to fouling and may be used in open tank
applications. Therminol XP also has low fouling, but is potentially corrosive to
copper piping since it is a mineral oil. No corrosivity data was available and
Therminol did not respond to an inquiry about the material compatibility of the heat
transfer fluid. Therminol 68 was much more prone to oxidation and required a
carefully monitored inert environment, which caused it to have a lower compatibility
rating. The thermodynamic properties, fluid properties, and heat transfer properties
help indicate which heat transfer fluid has the best overall performance.
Figure 6: Heat Transfer Fluid Combined Star Diagram
The heat transfer fluids Duratherm S (silicone oil), Duratherm 630 (paraffin oil), Therminol XP (mineral oil), and Therminol 68 (synthetic oil) were compared on the basis of safety, material compatibility, thermodynamic properties, heat transfer properties, and fluid properties. The star diagram criterion for each category may be found in Table 1: Star Diagram Criterion. The combined star diagram better illustrates the differences in performance
between Therminol XP, Therminol 68, Duratherm S, and Duratherm 630. Duratherm
630 clearly covers the most area on the star diagram, which indicates that it is a much
better candidate than the other heat transfer fluids as far as performance is concerned.
1
2
3
4
5Safety Rating
Compatibility Rating
ThermodynamicProperties RatingHT Properties Rating
Fluid Property Rating
Therminol 68 Therminol XP
Duratherm S Duratherm 630
30
Duratherm S fell short in the fluid, heat transfer, and thermodynamic properties
because of the general properties of silicone oil. The silicone oil forms vapor near
operating temperatures, has a high viscosity that decreases pumpability, and has a low
heat capacity. Conversely, Duratherm 630 has a high boiling point, very low
viscosity, and high heat capacity which make it the best candidate for a heat transfer
fluid. The specification sheet and NFPA rating state that Duratherm 630 is non-toxic
and non-reportable. However, the manufacturer classified Duratherm 630 as a
paraffin oil which seems unlikely given that most paraffin oils are more toxic. The
toxicology information should be verified with the company before installation. In
addition to the discussed heat transfer fluids, additional research should be conducted
to find out more information about Los Alamos National Labs CX-500 heat transfer
fluid. The fluid is stable up to 570 °C, has a low viscosity, and has a -40 °C gel point
[36]. CX-500 would be a great heat transfer fluid candidate because the fluid would
be capable of withstanding the higher temperatures associated with the Oxford and
Norwich solar thermal collectors. However, minimal information about this fluid was
available online during this review.
The economy of each heat transfer fluid was calculated on a per energy basis
(kJ). The comparison by a per energy basis eliminates the bias of fluid properties
when comparing the heat transfer fluids. A per energy basis provides a proxy for
comparing all fluids with the same basis of energy needed for the desalination
process. The energy cost of each heat transfer fluid was calculated with the same
initial (200 °C) and final operating temperature (195 °C) in the heat exchanger that
transfers energy to the air stream in the desalination process.
31
Figure 7: Heat Transfer Fluid Cost Comparison
The heat transfer fluids Duratherm S (silicone oil), Duratherm 630 (paraffin oil), Therminol XP (mineral oil), and Therminol 68 (synthetic oil) were compared on the basis of the cost per unit energy. The energy basis outlined in the Heat Transfer Fluid Comparison Criterion section was used. Thermal properties are based upon specifications provided by the manufacturers at 200 °C. The performance information for each heat transfer fluid is available in Table 5: Heat Transfer Fluid Decision Matrix. Pricing was not available for Therminol 68, so it was assumed to be that of Therminol XP. Duratherm 630 also outperforms the other heat transfer fluids in energy economy.
Duratherm 630 has an energy cost 25% lower than the next cheapest heat transfer
fluid (Therminol XP). Further comparison was performed to analyze which heat
transfer fluid was the most spatially efficient. The amount of heat transfer fluid
needed for energy demands is outlined in the in Heat Transfer Fluid Comparison
Criterion section. A lower volume of heat transfer fluid is desirable because it will
drive down shipping costs and the tank volume needed for the system. This is
especially important in a mobile desalination unit because space is very limited.
$0.00
$0.50
$1.00
$1.50
$2.00
$2.50
$3.00
Therminol 68 Therminol XP Duratherm S Duratherm 630
Cost
per
kJ o
f Ene
rgy
32
HT Fluid Cp 2.2 J/g°C 2.6 J/g°C 2.034 J/g°C 2.539 J/g°C
HT Fluid Flow Rate 1.964 kg/s 1.662 kg/s 2.124 kg/s 1.701 kg/s
HT Fluid Density 898 kg/m3
761 kg/m3
811 kg/m3
741 kg/m3
Time of Dark Operation 0.5 hr 0.5 hr 0.5 hr 0.5 hr
Mass of Fluid Needed for Storage 3535 kg 2991 kg 3823 kg 3063 kg
Volume of Fluid Needed for Storage 3.94 m3
3.93 m3
4.71 m3
4.13 m3
Total Cost of HT Fluid $30,437 $30,391 $99,622 $22,656
Duratherm S Duratherm 630HX Fluid Volume Needed
Therminol 68 Therminol XP
Table 2: HX Fluid Volume Needed
The table above is a comparison between the heat transfer fluids in regards to mass, volume, and cost. The mass of fluid needed for storage was based upon the heat transfer fluid flow rate, which was based on the energy demand outlined in the Heat Transfer Fluid Comparison Criterion section. The energy demand was calculated based upon water generation. The energy demand was then used to calculate the heat transfer fluid mass flow rate needed by dividing the energy demand by the heat capacity and operating temperature change of the fluid in the heat exchanger (5 °C). All material properties are that at 200 °C and were provided by manufacturers in technical data sheets. The volume of fluid needed was calculated on the basis of running for 30 minutes without light.
Therminol XP is more spatially efficient than Duratherm 630 because it requires 0.2
m3 less of fluid. While this difference may seem trivial, this is the equivalent to about
one 55 gallon drum, which takes up a lot of space. However, Duratherm 630 is
significantly cheaper than Therminol XP and the other heat transfer fluids, which
makes it a more favorable choice for a heat transfer fluid.
Economic Analysis
The solar thermal energy system must be capable of generating fresh water at
a competitive price based upon the energy demand and other assumptions outlined in
the Economic Analysis section. The price of water was calculated for the two most
economical collectors: the Absolicon T160 and Artic Solar XCPC. The heat transfer
fluid used was also the highest performing and most economical option: Duratherm
630. The cost of water for each collector based upon the entirety of the system is in
Table 3: System Cost.
33
Table 3: System Cost
This table is an economic summary of the system over a 10-year period. The pump was sized using methods for a single stage centrifugal pump outlined in Towler et al. [42]. The solar thermal collectors and heat transfer fluids were assumed to have 10 and 5 year lifetimes, respectively. The method for costing the fluid, the method for costing other components, and other assumptions may be found in the Economic Analysis section.
The Absolicon T160 is a more economical option and also occupies less space than
the Artic Solar XCPC system from this analysis. However, the Artic Solar XCPC has
a higher recommended operating temperature, which may indicate that the Artic Solar
XCPC system. More research also needs to be conducted about the supports of each
system, since the Absolicon T160 requires a tracking system and the Artic Solar
XCPC does not.
The energy cost was comparable to that of other solar thermal energy systems.
The levelized CAPEX per unit of energy for the Absolicon T160 and Artic Solar
XCPC systems were $0.049 and $0.055, respectively. The cost for the Absolicon
T160 collector might be higher since the tracking system is not included in the
collector cost. This cost is extremely competitive; however, transportation and
operational costs may lead to an increase in the energy cost. The levelized cost of
water for the energy collection sub-system is $6.34 per cubic meter of water for the
Absolicon T160 and $7.11 per cubic meter of water for the Artic Solar XCPC. This is
Number of Units NeededCost of Collector
Total Cost of Solar CollectorsPump Cost
Total Cost of FluidEnergy Over 10 years (kWh)
Cost of TankCost of piping, valves, and fittings
Cost of electrical and instrumentationTotal Installed Cost
Levelized Energy Cost of Energy System CAPEX per kWh
Levelized Cost of Energy System CAPEX per Cubic Meter of Water
$6.34 $7.11
7 18
$346
$4,938$148
$0.049 $0.055
$72,049 $80,759
System Cost with Duratherm 630
$14,000 $20,700
Absolicon T160 Artic Solar XCPC
$2,000 $1,150
$1,136$45,3111472256
34
$0.00
$1.00
$2.00
$3.00
$4.00
$5.00
$6.00
$7.00
$0
$10,000
$20,000
$30,000
$40,000
$50,000
0 20 40 60
Leve
lized
Cos
t of W
ater
per m
3
HT Fl
uid
Cost
Ove
r Life
time
HT Fluid Temperature Change (°C)
not a very competitive price for water at a mass production scale, but is reasonable for
the smaller desalination system at hand. The primary cost driver of the system was
the heat transfer fluid cost, which accounted for more than 60% of the CAPEX over a
10 year period. The cost of heat transfer fluids may be lower since the cost of heat
transfer fluid is a based upon a 55 gallon basis and the total volume of heat transfer
fluid purchased would be about 1100 gallons.
A sensitivity analysis of the operating temperature difference of the heat
transfer fluid in the heat exchanger was performed to see how the parameter affected
the total cost of heat transfer fluid as well as the levelized cost of water production.
The temperature change was varied between 5 °C and 65 °C for a system using the
Absolicon T160 collectors and Duratherm 630 heat transfer fluid (Figure 8).
Figure 8: HT Fluid Temperature Change Sensitivity Analysis
The temperature change in the heat exchanger of the heat transfer fluid was varied to see the effect on the total cost of heat transfer fluid over the lifetime of the system as well as the levelized cost of water. The system analyzed utilized the Duratherm 630 heat transfer fluid and Absolicon T160 collector. The triangles represent the levelized cost of water and the circles represent the total cost of heat transfer fluid over the lifetime of the system. The costing methodologies may be found in the Economic Analysis section.
35
The operating temperature change of the heat transfer fluid had a profound effect on
the levelized cost of water and heat transfer fluid total cost. Changing the temperature
change from 5 °C to 15 °C dropped the levelized cost of water and heat transfer fluid
cost over the system lifetime by 47% and 67%, respectively. The levelized cost of
water and heat transfer fluid cost at 15 °C is $3.36 and $15,104, respectively.
However, operating temperature changes beyond 15 °C may not be feasible since the
solar thermal collectors may not be able to heat the fluid fast enough during collection
[43]. A more in depth analysis involving the solar thermal collector companies needs
to be performed to assess the feasibility of different operating temperature changes.
36
Conclusions and Recommendations
This analysis was meant to serve as a comparison between available solar
thermal and heat transfer fluid technologies on the market as well as provide a rough
economic analysis of the most optimal combination of technologies. The designed
system will use a paraffin heat transfer oil in combination with parabolic trough
collecting technology.
Out of the solar collectors examined, either the Artic Solar XCPC or
Absolicon T160 should be implemented in the system. The benefits of the Artic Solar
XCPC unit is that it is a passive collector and proven to be efficient at high
temperatures operation. The strengths of the Absolicon T160 is that the system is
more cost and space efficient, which helps drive down the cost and size of the
collection system. Further research needs to be conducted about the cost of the
trackers that the Absolicon T160 would require. In addition to that, more information
about the Oxford parabolic dish collector and SunTrap absorber should be obtained
before making a final decision about the solar collector used in the system.
Two other heat transfer fluids are recommended to further pursue as viable
candidates. These heat transfer fluids are Duratherm G and Los Alamos National
Labs CX-500. Duratherm G is a high temperature glycol mixture capable of operation
up to 260 °C while CX-500 is a nanofluid capable of operation above 500 °C.
Duratherm G could be a viable candidate because glycol mixtures have large fluid
densities, high heat capacities, high resistance to oxidation, high thermal
conductivities, low corrosivity, and are relatively non-toxic. Research about the CX-
500 heat transfer fluid should be pursued if the SunTrap or parabolic trough
concentrator from Oxford are used for solar collection. CX-500 would allow for
37
greater operating temperatures, which has the potential to increase the operating
temperature of the air stream of the desalination system. A greater temperature in the
air stream would increase the amount of water that can be atomized, which would
increase water production. However, Duratherm 630 is currently recommended for
because it was the most economical fluid found in this preliminary analysis.
The optimized energy cost and levelized cost of water were $0.026 per kWh
and $3.36 per cubic meter of fresh water generated, respectively. The cost of water is
likely an overestimate and more research needs to be conducted to determine the
required volume and lifetime of the heat transfer fluid. Once the tank has been sized
for the system and an operating temperature change is determined, a better estimate
for the heat transfer fluid required and the cost of collectors can be obtained to further
drive down the estimated cost of water production. An analysis of the water
generation rate versus the operating temperature should also be conducted. A lower
operating temperature would increase the energy efficiency of the system because
collector efficiency generally decreased as temperatures increased. In addition to that,
a feasibility analysis of the operating temperature difference should be performed to
see what the optimal temperature change of heat transfer fluid is. The amount of heat
transfer fluid had a profound effect on the CAPEX of the project as it accounted for
more than 60% of the installed costs. Finding an optimal operating temperature
change in the desalination heat exchanger can reduce the amount of heat transfer fluid
needed. A typical temperature difference between the inlet and outlet of a collector is
about 15 °C, so heat exchanger operating temperature changes for the heat transfer
fluid between the inlet and outlet should not be significantly greater than that [46]. A
more in depth analysis involving the solar thermal collector distributors will need to
38
be performed to assess system performance at different operating temperature
changes.
A FMEA and operational feasibility analysis should be conducted before the
system design is finalized. One primary objective of the desalination project is to
have local governments in underdeveloped countries to be operating this technology.
Safe and easy operation of the systems is paramount to ensure the safety of operators,
reduce the risk of water contamination with process chemicals, and reduce reliance on
technical aid.
39
References [1] “Global water crisis: Facts, FAQs, and how to help,” World Vision, Mar. 19, 2020.
https://www.worldvision.org/clean-water-news-stories/global-water-crisis-facts (accessed May
20, 2020).
[2] R. C. Calow, A. M. MacDonald, A. L. Nicol, and N. S. Robins, “Ground Water Security and
Drought in Africa: Linking Availability, Access, and Demand,” Groundwater, vol. 48, no. 2, pp.
246–256, Mar. 2010, doi: 10.1111/j.1745-6584.2009.00558.x.
[3] “Water Stress in Sub-Saharan Africa,” Council on Foreign Relations.
https://www.cfr.org/backgrounder/water-stress-sub-saharan-africa (accessed May 21, 2020).
[4] K. Zotalis, E. G. Dialynas, N. Mamassis, and A. N. Angelakis, “Desalination Technologies:
Hellenic Experience,” Water, vol. 6, no. 5, pp. 1134–1150, May 2014, doi: 10.3390/w6051134.
[5] P. Youssef, R. AL-Dadah, and S. Mahmoud, “(PDF) Comparative Analysis of Desalination
Technologies,” Reasearch Gate, Dec. 2014.
https://www.researchgate.net/publication/271724301_Comparative_Analysis_of_Desalination_Te
chnologies (accessed May 23, 2020).
[6] K. E. Tulou, “Overview of Desalination Techniques,” Accessed: May 23, 2020. [Online].
Available: https://core.ac.uk/reader/60532470.
[7] S. Ahmadvand, B. Abbasi, B. Azarfar, M. Elhashimi, X. Zhang, and B. Abbasi, “Looking Beyond
Energy Efficiency: An Applied Review of Water Desalination Technologies and an Introduction
to Capillary-Driven Desalination,” Water, vol. 11, no. 4, p. 696, Apr. 2019, doi:
10.3390/w11040696.
[8] M. Shatat and S. B. Riffat, “Water desalination technologies utilizing conventional and renewable
energy sources,” Int. J. Low-Carbon Technol., vol. 9, no. 1, pp. 1–19, Mar. 2014, doi:
10.1093/ijlct/cts025.
[9] J. Lienhard, “Humidification-Dehumidification Desalination,” in Desalination, J. Kucera, Ed.
Hoboken, NJ, USA: John Wiley & Sons, Inc., 2019, pp. 387–446.
40
[10] M. T. Islam, N. Huda, A. B. Abdullah, and R. Saidur, “A comprehensive review of state-of-the-art
concentrating solar power (CSP) technologies: Current status and research trends,” Renew.
Sustain. Energy Rev., vol. 91, pp. 987–1018, Aug. 2018, doi: 10.1016/j.rser.2018.04.097.
[11] G. Barone, A. Buonomano, C. Forzano, and A. Palombo, “Chapter 6 Solar thermal collectors,” in
Solar Hydrogen Production: Processes, Systems, and Technologies, Academic Press, 2019.
[12] K. Lovegrove and W. Stein, Concentrating Solar Power Technology: Principles, Developments
and Applications. Cambridge, UNITED KINGDOM: Elsevier Science & Technology, 2012.
[13] P. Breeze, Solar Power Generation. San Diego, UNITED KINGDOM: Elsevier Science &
Technology, 2016.
[14] D. Kearney, “Utility-Scale Power Tower Solar Systems: Performance Acceptance Test
Guidelines,” Renew. Energy, p. 53, 2013.
[15] L. Zhou, Y. Li, E. Hu, J. Qin, and Y. Yang, “Comparison in net solar efficiency between the use
of concentrating and non-concentrating solar collectors in solar aided power generation systems,”
Appl. Therm. Eng., vol. 75, pp. 685–691, Jan. 2015, doi: 10.1016/j.applthermaleng.2014.09.063.
[16] Y. Tian and C. Y. Zhao, “A review of solar collectors and thermal energy storage in solar thermal
applications,” Appl. Energy, vol. 104, pp. 538–553, Apr. 2013, doi:
10.1016/j.apenergy.2012.11.051.
[17] T. Matuska, “Performance and Economic Analysis of Hybrid PVT Collectors in Solar DHW
System,” Energy Procedia, vol. 48, pp. 150–156, 2014, doi: 10.1016/j.egypro.2014.02.019.
[18] E. Bellos, C. Tzivanidis, and K. Antonopoulos, “Thermal performance of a direct-flow coaxial
evacuated tube with solidworks flow simulation,” Jul. 2015.
[19] A. Lenert, Y. Nam, and E. Wang, “Heat transfer fluids,” Annu. Rev. Heat Transf., vol. 15, Jan.
2012, doi: 10.1615/AnnualRevHeatTransfer.2012004122.
[20] “5.1. Overview of Solar Thermal Fluids | EME 811: Solar Thermal Energy for Utilities and
Industry.” https://www.e-education.psu.edu/eme811/node/675 (accessed May 25, 2020).
[21] R. H. Plante, Solar Energy, Photovoltaics, and Domestic Hot Water: A Technical and Economic
Guide for Project Planners, Builders, and Property Owners. San Diego, UNITED STATES:
Elsevier Science & Technology, 2014.
41
[22] Y. Al Jasem, H. Pervez Butt, M. Barkhad, M. Al Khazali, and T. Thiemann, “New Heat Transfer
Fluids (HTFs) for Solar Thermal Applications,” in Proceedings of The 3rd World Sustainability
Forum, Sciforum.net, Oct. 2013, p. d002, doi: 10.3390/wsf3-d002.
[23] “Heat Transfer Fluids for Solar Water Heating Systems,” Energy.gov.
https://www.energy.gov/energysaver/solar-water-heaters/heat-transfer-fluids-solar-water-heating-
systems (accessed May 26, 2020).
[24] H. Benoit, L. Spreafico, D. Gauthier, and G. Flamant, “Review of heat transfer fluids in tube-
receivers used in concentrating solar thermal systems: Properties and heat transfer coefficients,”
Renew. Sustain. Energy Rev., vol. 55, pp. 298–315, Mar. 2016, doi: 10.1016/j.rser.2015.10.059.
[25] R. Vutukuru, A. S. Pegallapati, and R. Maddali, “Suitability of various heat transfer fluids for high
temperature solar thermal systems,” Appl. Therm. Eng., vol. 159, p. 113973, Aug. 2019, doi:
10.1016/j.applthermaleng.2019.113973.
[26] R. G. Reddy, “Molten Salts: Thermal Energy Storage and Heat Transfer Media,” J. Phase
Equilibria Diffus., vol. 32, no. 4, p. 269, Jul. 2011, doi: 10.1007/s11669-011-9904-z.
[27] J. Dodaro, “Molten Salt Storage,” Stanford.edu, Dec. 15, 2015.
http://large.stanford.edu/courses/2015/ph240/dodaro2/ (accessed May 26, 2020).
[28] U. Srivastva, R. Malhotra, and S. Kaushik, “Recent Developments in Heat Transfer Fluids Used
for Solar Thermal Energy Applications,” J. Fundam. Renew. Energy Appl., vol. 05, no. 06, 2015,
doi: 10.4172/2090-4541.1000189.
[29] P. Poživil, V. Aga, A. Zagorskiy, and A. Steinfeld, “A Pressurized Air Receiver for Solar-driven
Gas Turbines,” Energy Procedia, vol. 49, pp. 498–503, Jan. 2014, doi:
10.1016/j.egypro.2014.03.053.
[30] “ETC_Collector_Overview_Int.pdf.” Accessed: May 26, 2020. [Online]. Available:
https://www.apricus.com/upload/userfiles/downloads/ETC_Collector_Overview_Int.pdf.
[31] “data-thermopower-vdf-collectors.pdf.” Accessed: May 26, 2020. [Online]. Available:
https://www.sunmaxxsolar.com/data-thermopower-vdf-collectors.
[32] “data-thermopower-vhp-collectors.pdf.” Accessed: May 26, 2020. [Online]. Available:
https://www.sunmaxxsolar.com/data-thermopower-vhp-collectors.
42
[33] “Evacuated Tube Solar Thermal Collectors | Solar Water Heating Systems.”
http://www.solarpanelsplus.com/products/evacuated-tube-collectors/ (accessed May 26, 2020).
[34] “Solar collectors - Absolicon Solar Collector.” http://www.absolicon.com/solar-collectors/
(accessed May 26, 2020).
[35] “Process Heat – Hot Water – Steam – Artic Solar.” http://articsolar.com/applications/process-heat-
hot-water-steam/ (accessed May 26, 2020).
[36] “Collectors AM 02-Obrey_Heat Pipe Linear Receiver.pdf.” Accessed: May 26, 2020. [Online].
Available: https://www.energy.gov/sites/prod/files/2016/08/f33/Collectors%20AM%2002-
Obrey_Heat%20Pipe%20Linear%20Receiver.pdf.
[37] Cryogenics Group at the University of Oxford, “High Temperature Solar Process Heating.
Capabilities of Oxford Concentrator Design,” Jan. 17, 2020.
[38] F. Helminger, “Summary report Stagnation temperature,” p. 12.
[39] G. Glatzmaier, “Developing a Cost Model and Methodology to Estimate Capital Costs for
Thermal Energy Storage,” NREL/TP-5500-53066, 1031953, Dec. 2011. doi: 10.2172/1031953.
[40] “cepci_2011_py.pdf.” Accessed: May 26, 2020. [Online]. Available:
http://folk.ntnu.no/magnehi/cepci_2011_py.pdf.
[41] D. Mignard, “Correlating the chemical engineering plant cost index with macro-economic
indicators,” Chem. Eng. Res. Des., vol. 92, no. 2, pp. 285–294, Feb. 2014, doi:
10.1016/j.cherd.2013.07.022.
[42] G. Towler and R. Sinnott, “Chemical Engineering Design - Principles, Practice and Economics of
Plant and Process Design (2nd Edition) - Knovel,” Feb. 12, 2013.
https://app.knovel.com/web/toc.v/cid:kpCEDPPEP4/viewerType:toc//root_slug:chemical-
engineering/url_slug:chemical-engineering?b-q=towler&sort_on=default&b-group-by=true&b-
sort-on=default&b-content-type=all_references&include_synonyms=no (accessed May 26, 2020).
[43] A. C. Ferreira and Â. Silva, “Application of a Costing Methodology to Estimate Capital Costs of
Solar Thermal Systems in Residential Portuguese Context,” Int. J. Sustain. Energy Plan. Manag.,
vol. 26, pp. 33–46, Apr. 2020, doi: 10.5278/ijsepm.3483.
43
[44] “09_DavidVolkwyn_Energy.pdf.” Accessed: May 26, 2020. [Online]. Available:
http://www.ncpc.co.za/files/Conferences/Conference2019/6_Energy_Presentations/09_DavidVolk
wyn_Energy.pdf.
[45] “Mid-Temperature Thermal XCPC.” Accessed: May 26, 2020. [Online]. Available:
https://cast.ucmerced.edu/sites/cast.ucmerced.edu/files/public/documents/2017Posters/Mid-
Temperature.pdf.
[46] “(PDF) Levelized Cost of Heat for Linear Fresnel Concentrated Solar Systems,” ResearchGate.
https://www.researchgate.net/publication/273413209_Levelized_Cost_of_Heat_for_Linear_Fresn
el_Concentrated_Solar_Systems (accessed May 28, 2020).
[47] O. B. Fernández, “Analysis and dimensioning of a large scale solar cooking system,” p. 87.
[48] “High Temperature Thermal Fluid | Duratherm 630,” Duratherm Fluids.
https://durathermfluids.com/products/duratherm-630/ (accessed May 26, 2020).
[49] “Silicon Based Heat Transfer Fluid | Duratherm S,” Duratherm Fluids.
https://durathermfluids.com/products/duratherm-s/ (accessed May 26, 2020).
[50] “Therminol 68 Heat Transfer Fluid | Therminol | Eastman.”
https://www.therminol.com/product/71093442 (accessed May 26, 2020).
[51] “Therminol XP Heat Transfer Fluid | Therminol | Eastman.”
https://www.therminol.com/product/71093461 (accessed May 26, 2020).
[52] “THERMINOL XP - HTFXP55.”
http://na.dmecompany.com/Catalog/ItemContent.aspx?ItemNumber=10058180&CatalogId=dme
&CatalogDetailId=806&NSM=Y (accessed May 26, 2020).
44
Appendix A – Desalination System Figure 9: Desalination System The system utilizes a humidification-dehumidification cycle to extract the solids out of a saltwater stream to produce fresh water. Dry air is fed into a converging nozzle which compresses while solar thermal energy is used to increase the temperature of the air. The hot, dry air is then used to atom saltwater, which is fed into a cyclone that separates out the salt particles. The warm humid air is then fed into a condenser which is cools the stream to condense water out of the air. The air and condensed water stream is fed into an air-water separator that separates the dry air and fresh, liquid water. The dry air recycles back into the dry air converging nozzle section while the fresh, liquid water is fed into a heat recuperator that preheats cool saltwater before it is fed into the atomizing area.
45
General Specific Model Identifier on Graph Positives Negatives Dimensions/
MaterialRadiated
Area (m2)Performance Cost Peak Output
(kW)
Optimum Operating
Range (°C)
Max Temperatur
e (°C)
Energy Cost $/kW
Power per Radiated Area
(kW/m2)
Evacuated Tube Collector
Company that has many mounting options as well as
solar collection systems. Could purchase manifold then purchase
higher temperature evacuated tubes for the system.
Apricus ETC-20 Apricus Many different options for mounting and systems.
Seems to have a low operating temperature. No specification of
max operating temperature. Could purchase manifold then
buy evacuated tubes separately.
2.005m X 1.496m X 0.136m. High
purity copper pipes with aluminum heat
transfer fins.
3.00
1342 W for the ETC-20 which is 1.89 m2. Max stagnation
temperature of 228°C. Recommended flow rate of 1.4
L/min.
$1,000 1.342 0-120 *** 228 745 0.447
Evacuated Tube Collector
Seems like a cheaper version than Apricus. Seems to be about the same quality of product with
worse customer service.
SunMaxx Solar VHP10 VHP 10Very cheap. Compact.
Different sizes and mounting options.
Max stagnation temperature lower than 250°C.
37.5" X 79". 88 lbs. Water or glycol operating fluid.
1.91
14 kBTU/panel/day SRCC Clear C Rating. Max stagnation
temperature of 220°C. 0.2-3 GPM. Storage tank: 30-40 gal.
$93 0.342 0-100 *** 220 272 0.179
Evacuated Tube Collector
Seems like a cheaper version than Apricus. Seems to be about the same quality of product with worse customer service. Direct
flow pipe.
SunMaxx Solar VDF20 VDF 20Very cheap. Different
sizes and mounting options.
Max stagnation temperature lower than 250°C.
60" X 64.7". 115 lbs. Water operating fluid. Copper pipe and aluminum fins.
2.50
22.8 kBTU/panel/day SRCC Clear C Rating. Max stagnation
temperature of 220°C. 0.2-3 GPM. Storage tank: 30-40 gal.
$1,600 0.567 0-120 *** 220 2822 0.226
Evacuated Tube Collector
10 year warranty. Variety of solar thermal collectors and
storage units. SRCC certified.Solar Panels Plus SPP-25 SPP
Seems like a very reliable company with a long
warranty. Higher stagnation temp.
Not very efficient at 250°C operation. May work better if
different HX fluid used.
81" x 79". 183 lbs. Copper tubing. Stainless steel
frame. Rock wool insulation.
4.13
6000-39000 BTU/ft2/day. Max stagnation temperature of 250
°C. 0.8-1.2 GPM recommended.
$1500 *** 0.95 0-150 *** 250 1579 0.230
Parabolic Trough
Collector
Used in a variety of industries and research
papers. Seems very promising for high
temperature applications. Used in many large scale
thermal plants.
Absolicon T160 Absolicon
Capable of producing steam at 160°C. Likely
can produce 250°C fluid. One of highest efficiency
concentrators.
Not many technical specs. Need more information.
5.49m X 1.056m. 148 lbs. Tyfocor
heat transfer fluid.5.80 430-4200 W per collector from
third party tests. $2000 *** 4 0-175 460 500 0.690
Parabolic Trough
Collector
Seems like a very promising technology. Very organized
company transparent with costs. Excel sheets available with cost
breakdown for installation. Project sizing calculators and
tools available.
Artic Solar XCPC ArticGreater than 50%
efficiency in excess of 200°C.
Not too much specific information about energy
generation I found.
2.208 m x 1.221 m x 0.295 m 2.70
Depends on project set up. Greater than 50% efficiency at
temps upward of 200°C.$1,150 1.5 150-200 320 767 0.556
Parabolic Trough Panel
Collector
Norwich Technologies President, Joes Stettenheim:
[email protected] 802-384-1333
Los Alamos NL x Norwich Technologies x
US Department of Energy
Extremely high temperature application (750°C). Funded project
with department of energy. Collaboration?
Not much information available No information available
No information available No information available No information
availableNo information
availableNo information
available 750 No information available
No information available
Parabolic Dish Collector Harvard project Parabolic Dish Collector
Extremely high temperature application
(greater than 500°C)Not much information available No information
availableNo information
available No information available No information available
No information available
No information available 500 No information
availableNo information
available
Appendix B – Solar Thermal Collector Decision Matrix Table 4: Solar Thermal Collector Decision Matrix
The table above is a summary of the information collected when researching each solar collector. IT also includes the comparison statistics used in the analysis. Any number with “***” indicates that the cost is an estimate based upon similar technologies. All underlined text represents a hyperlink. The technical data may be found from the following sources: [30–37, 44, 45, 47].
46
Appendix C – Heat Transfer Fluid Decision Matrix Table 5: Heat Transfer Fluid Decision Matrix
The star diagram criterion is summarized in Table 1: Star Diagram Criterion. The safety section describes how toxic, flammable and reactive the substance is. This is quantified by summing the health, flammability, and reactivity section of the NFPA rating. A lower NFPA score indicates a less hazardous material. The compatibility section quantifies the corrosivity and fouling/oxidizing tendency of the heat transfer fluid. The thermodynamic properties illustrate the operating range of the fluid which includes the freezing point, boiling point, and point at which the substance is unstable. The heat transfer properties section is a way of illustrating the heat transfer performance of the fluid. This includes the heat capacity and thermal conductivity. The fluid properties section includes the density, kinematic viscosity, and thermal expansion coefficient of the fluid. Greater scores in each category indicate higher performance in that area. The cost of each heat transfer fluid will be calculated based upon an energy basis. The purpose of this is to take out factors in density when calculating the cost of each fluid because the cost per unit energy is a more telling parameter of economic performance. The cost of each fluid is calculated by dividing the cost per unit volume by the density, heat capacity, and operating temperature change. The operating temperature change—5 °C—is the temperature change that the heat transfer fluid will experience in the heat exchanger that heats the air used in the desalination process. A lower energy cost is desirable because that indicates less money needs to be spent on heat transfer fluid in the process. The technical data may be found from the following sources: [48–52].