special program for technical-vocational...
TRANSCRIPT
-
Special Program for
Technical-Vocational
Education Industrial Technology
Electrical Installation and
Maintenance NC II
Quarter 1 – Module 3:
Layout and Install Flexible Non-
Metallic Conduit
9
________________________________________________________________________________________________________________________________________________________________Subject to further validation for IP compliance, this material is for first quarter use only. Circulation shall be limited to public schools within the jurisdiction of the Division of Cebu Province. LR-PIPCV
1ST G
ENER
ATION
MODU
LES -
VERS
ION 2.0
-
Special Program Technical Vocational Education Grade - 9
Alternative Delivery Mode
Quarter 1 - Module 3: Layout and Install Flexible Non-Metallic Conduit
First Edition, 2020
Republic Act 8293 section 176 states that: No copyright shall subsist in any work of the Government of the Republic of the Philippines. However, prior approval of the government agency or office wherein the work is created shall be necessary for the exploitation of such work for a profit. Such an agency or office may, among other things, impose as a condition the payment of royalties. Borrowed materials (i.e., songs, stories, poems, photos, brand names, trademarks, etc.) included in this book are owned by their respective copyright holders. Every effort has been exerted to locate and seek permission to use these materials from their respective copyright owners. The publisher and authors do not represent nor claim ownership over them. Published by the Department of Education Secretary: Leonor Magtolis Briones Undersecretary: Diosdado M. San Antonio
DEVELOPMENT TEAM OF THE MODULE
Writer : Andrez Melchor G. Zozobrado
Editor : Jose Garry R. Napoles
Reviewers : Analogie D. Destacamento
Chito R. Villacampa
Illustrator : Maribell J. Fuentes
Layout Artist : Maribell J. Fuentes
Management Team:
Schools Division Superintendent : Marilyn S. Andales
Assistant Schools Div. Superintendent : Leah B. Apao
Cartesa M. Perico
Ester A. Futalan
Chief Education Supervisor, CID : Mary Ann P. Flores
Education Program Supervisor, LRMDS : Isaiash T. Wagas
Education Program Supervisor, TLE : Jose Garry R. Napoles
Department of Education – Regional Office 7
Division of Cebu Province
Office Address : IPHO Bldg., Sudlon, Lahug, Cebu City, Philippines
Telefax : (032) 520-3216 – 520-3217; SDS Office: (032) 255 - 6405
E-mail Address : [email protected]
Bitoon National Vocational High School
Address : Bitoon, Dumanjug, Cebu
Telephone : (032) 471-8001
E-mail Address : [email protected]
________________________________________________________________________________________________________________________________________________________________Subject to further validation for IP compliance, this material is for first quarter use only. Circulation shall be limited to public schools within the jurisdiction of the Division of Cebu Province. LR-PIPCV
1ST G
ENER
ATION
MODU
LES -
VERS
ION 2.0
-
9
Special Program for
Technical-Vocational
Education Industrial Technology
Electrical Installation and
Maintenance NC II
Quarter 1 – Module 3:
Layout and Install Flexible Non-
Metallic Conduit
________________________________________________________________________________________________________________________________________________________________Subject to further validation for IP compliance, this material is for first quarter use only. Circulation shall be limited to public schools within the jurisdiction of the Division of Cebu Province. LR-PIPCV
1ST G
ENER
ATION
MODU
LES -
VERS
ION 2.0
-
Key Message
For Educators:
Learning is a constant process. Amidst inevitable circumstances, the Department of
Education extends its resources and looks for varied ways to cater to your needs and to
adapt to the new system of Education as a fortress of the Learning Continuity Plan. One of
the probable solutions is the use of Teacher-Made Educational Modules in teaching.
You are reading the Electrical Installation and Maintenance for Grade 9: First
Quarter Alternative Delivery Mode (ADM) Module on “Layout and Install Flexible Non-
Metallic Conduit” as written and found in the Competency-Based Curriculum –
Strengthened Technical-Vocational Education Program.
The creation of this module is an effort of competent trainers from Bitoon National
Vocational High School of the Department of Education-Cebu Province during this
pandemic period. In addition, this module is meticulously planned, organized, checked, and
verified by knowledgeable educators to assist you in imparting the lessons to the learners
while considering the physical, social, and economic restraints in the teaching process.
The use of the Teacher-Made Educational Module aims to surpass the challenges of
teaching in a new normal education set-up. Through this module, the students are given
independent learning activities, which embodies in the Most Essential Learning
Competencies based on the K-12 Curriculum Competencies, to work on in accordance with
their capability, efficiency, and time. Thus, helping the learners acquire the prerequisite 21st
Century skills needed with an emphasis on utmost effort in considering the whole well-being
of the learners.
As the main source of learning, it is your top priority to explain clearly how to use this
module to the learners. While using this module, learner’s progress and development should
be recorded verbatim to assess their strengths and weaknesses while doing the activities
presented independently in the safety of their homes. Moreover, you are anticipated to
persuade learners to comply and to finish the modules on or before the scheduled time.
For the Learners:
As a significant stakeholder of learning, the Department of Education researched and
explored innovative ways to address your needs with high consideration on social,
economic, physical, and emotional aspects of your well-being. To continue the learning
process, DepEd comes up with an Alternative Delivery mode of teaching using Teacher-
Made Educational Modules.
You are reading the Electrical Installation and Maintenance for Grade 9: First
Quarter Alternative Delivery Mode (ADM) Module on “Layout and Install Flexible Non-
Metallic Conduit” as written and found in the Competency-Based Curriculum –
Strengthened Technical-Vocational Education Program.
________________________________________________________________________________________________________________________________________________________________Subject to further validation for IP compliance, this material is for first quarter use only. Circulation shall be limited to public schools within the jurisdiction of the Division of Cebu Province. LR-PIPCV
1ST G
ENER
ATION
MODU
LES -
VERS
ION 2.0
-
This module is specially crafted for you to grasp the opportunity to continue learning
even at home. Using guided and independent learning activities, rest assured that you will
be able to take pleasure as well as to deeply understand the contents of the lesson
presented, recognizing your capacity and capability in acquiring knowledge.
This module has the following parts and corresponding icons:
LEARNING OUTCOME
The first part of the module will keep you
on track on the Competencies,
Objectives, and Skills expected for you to
be developed and mastered. Some
reminders about the module are found in
here too.
This part aims to check your prior
knowledge of the lesson to take. If you
can get a perfect score and perform
competently the competency, you can
skip the module and proceed to the next
module. If not, continue to the next part.
This part helps you link the previous
lesson to the current one through a short
exercise/drill.
A brief discussion of the lesson can be
read in this part. It guides and helps you
unlock the lesson presented.
A comprehensive activities for
independent practice is in this part to
solidify your knowledge and skills of the
given topic. This can be a drill or
exercise or an activity.
This part of the module is used to
process your learning and understanding
of the given topic. It can be a series of
questions or an activity.
A transfer of newly acquired knowledge
and skills to a real-life situation is present
in this part of the module. This can be a
task sheet (used when doing simple
tasks), operation sheet (used when doing
or operating devices or a job sheet (used
in doing series of task for a specific job).
GENERALIZATION
REVIEW LESSON
INFORMATION SHEET
ACTIVITY SHEET
PERFORMANCE TASKS
PRE - ASSESSMENT
________________________________________________________________________________________________________________________________________________________________Subject to further validation for IP compliance, this material is for first quarter use only. Circulation shall be limited to public schools within the jurisdiction of the Division of Cebu Province. LR-PIPCV
1ST G
ENER
ATION
MODU
LES -
VERS
ION 2.0
-
This activity assesses your level of
mastery towards the topic.
This contains answers to all activities in
the module.
At the end of this module you will also find:
In using this module, keep a note of the fundamental reminders below.
1. The module is government-owned. Handle it with care. Unnecessary marks
are prohibited. Use a separate sheet of paper in answering all the given
exercises.
2. This module is organized according to the level of understanding. Skipping
one part of this module may lead you to confusion and misinterpretation.
3. The instructions are carefully laden for you to understand the given lessons.
Read each item cautiously.
4. This is a Home-Based class; your reliability and honor in doing the tasks and
checking your answers are a must.
5. This module helps you attain and learn lessons at home. Make sure to
comprehend the first activity before proceeding to the next one.
6. This module should be returned in good condition to your teacher/facilitator
once you completed it.
7. Answers should be written on a separate sheet of paper or notebook
especially prepared for TVE subjects.
If you wish to talk to your teacher/educator, do not hesitate to keep in touch with
him/her for further discussion. Know that even if this is a home-based class, your teacher is
only a call away. Good communication between the teacher and the student is our priority to
flourish your understanding of the given lessons.
We do hope that in using this material, you will gain ample knowledge and skills for
you to be fully equipped and ready to answer the demands of the globally competitive world.
We are confident in you! Keep soaring high!
References Printed in this part is a list of all reliable and valid
resources used in crafting and designing this module.
SELF – CHECK
ANSWER KEYS
________________________________________________________________________________________________________________________________________________________________Subject to further validation for IP compliance, this material is for first quarter use only. Circulation shall be limited to public schools within the jurisdiction of the Division of Cebu Province. LR-PIPCV
1ST G
ENER
ATION
MODU
LES -
VERS
ION 2.0
-
1
Good day, dear learner!
This module is solely prepared for you to access and to acquire lessons befitted in
your grade level. The exercises, drills and assessments are carefully made to suit your level
of understanding. Indeed, this learning resource is for you to fully comprehend the “Layout
and Install Flexible Non-Metallic Conduit” independently, you are going to go through this
module following its proper sequence. Although you are going to do it alone, this is a guided
lesson and instructions/directions on how to do every activity is plotted for your convenience.
Using this learning resource, you are ought to “Layout and Install Flexible Non-
Metallic Conduit” as inculcated in the Competency-Based Curriculum – Strengthened
Technical-Vocational Education Program.
This module is composed of set of instructions for you to be guided in the activities
that you will perform later. Read and follow instructions properly, do not skip any parts and
perform each activity honestly. This module is intended for you finish within a week.
At the end of this module, you are expected to achieve the following objectives for
this session:
Identify flexible non-metallic conduit to be used in exposed or concealed in a certain condition
Describe the property of materials of the flexible non-metallic conduit.
Display responsibility and accountability by all times.
Perform for social responsibility.
Directions: Write TRUE if the statement is correct and FALSE if it is not. Write your
answer in a separate sheet of paper.
1. PEC provisions in installing flexible non-metallic conduit are strictly followed.
2. Uses and application of flexible non-metallic conduit are discussed according to
the PEC.
3. Electrical flexible non-metallic conduits are leveled horizontally and vertically aligned
to the structure specified in job requirements.
4. Workplace is not cleaned and made not safe upon the completion of work according to
the established standard.
5. Tools, materials and equipments needed for the installation are prepared in line with
job requirements.
LEARNING OUTCOME
PRE- ASSESSMENT
________________________________________________________________________________________________________________________________________________________________Subject to further validation for IP compliance, this material is for first quarter use only. Circulation shall be limited to public schools within the jurisdiction of the Division of Cebu Province. LR-PIPCV
1ST G
ENER
ATION
MODU
LES -
VERS
ION 2.0
-
2
6 Flexible non-metallic conduit must installed not line with job requirements.
7. Flexible non-metallic conduit is installed in line with the job requirements
8. Final report is prepared upon the completion of job.
Directions: Write Permitted if is to be used in allowable exposed or concealed locations
and Not Permitted if it is not in a certain condition. Write your answer in a
separate sheet of paper.
1. Where flexibility is required for installation, operation, or maintenance.
2. Where subject to physical damage.
3. Where protection of the contained is required from vapors, liquids, or solids.
4. Where any combination of ambient and conductor temperature is in excess of that for
which the liquid tight flexible non-metallic conduit is approved.
5. For outdoor locations where listed and marked as suitable for the purpose. FFN: For
marking requirements, see Section 110.1.21.
Flexible Non-metallic Conduit
This portion of information sheet is lifted from Philippine Electrical Code, 2000, Part I.
Definition. Liquid tight flexible non-metallic conduit is a listed raceway of circular cross
section of various types as follows:
1. A smooth seamless inner core and cover bonded together and having one or more
reinforcement layers between the core and cover designated as Type LFNC-A.
2. A smooth inner surface with integral reinforcement within the conduit wall,
designated as Type LFNC-B.
3. A corrugated internal and external surface without integral reinforcement within the
conduit wall, designated as Type LFNC-C.
This conduit is flame resistant and, with fittings, is approved for the installation of
electrical conductors.
Disclaimer: The contents above are borrowed from STVEP - CBC/CBLM – Electrical Installation and Maintenance (EIM) by Mr. Marino C. Cueto;
Ms. Gina C, delos Santos; Dr. Corazon Echano; and Mr. Lemuel C. Valles, funded by the Department of Education.
REVIEW LESSON
INFORMATION SHEET
________________________________________________________________________________________________________________________________________________________________Subject to further validation for IP compliance, this material is for first quarter use only. Circulation shall be limited to public schools within the jurisdiction of the Division of Cebu Province. LR-PIPCV
1ST G
ENER
ATION
MODU
LES -
VERS
ION 2.0
-
3
Uses.
(a) Permitted. Listed liquid tight flexible nonmetallic conduit shall be permitted to be
used in exposed or concealed locations for the following purposes. FPN: Extreme
cold may cause some types of nonmetallic conduits to become brittle and
therefore more susceptible to damage from physical contact.
(1) Where flexibility is required for installation, operation, or maintenance.
(2) Where protection of the contained conductors is required from vapors, liquids,
or solids.
(3) For outdoor locations where listed and marked as suitable for the purpose.
FFN: For marking requirements, see Section 110.1.21
(4) For direct burial where listed and marked for the purpose.
(5) Liquid tight flexible nonmetallic conduit as defined in Section 3.51.2.1(2) shall
be permitted to be installed in lengths longer than 1 800 mm where secured in
accordance with Section 3.51.2.6.
(6) As a listed manufactured prewired assembly, 15, mm (20mm) through 25 mm
(32 mm) conduit, as defined in Section 3.51 .2.1(2).
(b) Not Permitted. Liquid tight flexible non-metallic conduit shall not be used in the
following:
(1) `Where subject to physical damage
(2) Where any combination of ambient and conductor temperature is in excess of
that for which the liquid tight flexible non-metallic conduit is approved
(3) In lengths longer than 1 800 mm, except as permitted by Section 3.51
.2.2(a)(5) or where a longer length is approved as essential for a required
degree of flexibility..
(4) Where voltage of the contained conductors is in excess of 600 volts, nominal
Exception. As permitted in Section 6.0.2.3(a) for electric signs over 600 volts.
Size. The electrical trade sizes of liquid tight flexible nonmetallic conduit shall be in
accordance with (a) or (b):
(a) 15mm (20 mm) to 100mm (110mm) inclusive
(b) 10 mm (15 mm) as permitted below
(1) For enclosing the leads of motors as permitted in Section 4.30.13.5(b) (2) In
lengths not exceeding 1 800 mm as part of a listed assembly for tap
connections to lighting fixtures as required in Section 4.10.13.4(c), or for
utilization equipment (3) for electric sign conductors in accordance with
Section 6.0 .2 .3 (a)
Disclaimer: The contents above are borrowed from STVEP - CBC/CBLM – Electrical Installation and Maintenance (EIM) by Mr. Marino C. Cueto;
Ms. Gina C, delos Santos; Dr. Corazon Echano; and Mr. Lemuel C. Valles, funded by the Department of Education.
________________________________________________________________________________________________________________________________________________________________Subject to further validation for IP compliance, this material is for first quarter use only. Circulation shall be limited to public schools within the jurisdiction of the Division of Cebu Province. LR-PIPCV
1ST G
ENER
ATION
MODU
LES -
VERS
ION 2.0
-
4
Number of Conductors. The number of conductors permitted in a single conduit shall be in
accordance with the percentage fill specified.
Fittings. Liquid tight flexible non - metallic conduit shall be used only with listed terminal
fittings. Angle connectors shall not be used for concealed raceway installations.
Securing and Supporting. Liquid tight flexible nonmetallic conduit, as defined in Section
3.51.2.1(2), shall be securely fastened and supported in accordance with one of the
following.
(a) The conduit shall be securely fastened at intervals not exceeding 900 mm and
within 300 mm on each side of every outlet box, junction box, cabinet, or
fitting.
(b) Securing and supporting of the conduit shall not be required where it is fished,
installed in lengths not exceeding 900 mm at terminals where flexibility is
required, or where installed in lengths not exceeding 1 800 mm from a fixture
terminal connection for tap conductors to lighting fixtures as permitted in
Section 4.10.13.4(c)
(c) Horizontal runs of liquid tight flexible nonmetallic conduit supported by openings
through framing members at intervals not exceeding 900 mm and securely
fastened within 300 mm of termination points shall be permitted.
3.51.2.7 Equipment Grounding. When an equipment grounding conductor is required for
the circuits installed in liquid tight flexible nonmetallic conduit, it shall be permitted to be
installed on the inside or outside of the conduit. When installed on the outside, the
length of the equipment grounding conductor shall not exceed 1 800 mm and shall be
routed with the raceway or enclosure. Fittings and boxes shall be bonded or grounded
in accordance with Article 2.50.
Splices and Taps. Splices and taps shall be made in accordance with Section 3.0.1 13. See
Article 3.70 for rules on the installation and use of boxes and conduit bodies.
Bends-Number in One Run. There shall not be more than the equivalent of four quarter
bends (360 degrees total) between pull points, e.g., conduit bodies and boxes.
Flexible Nonmetallic Conduit Fittings
Coupling
Flexible Nonmetallic Conduit
Disclaimer: The contents above are borrowed from STVEP - CBC/CBLM – Electrical Installation and Maintenance (EIM) by Mr. Marino C.
Cueto; Ms. Gina C, delos Santos; Dr. Corazon Echano; and Mr. Lemuel C. Valles, funded by the Department of Education.
________________________________________________________________________________________________________________________________________________________________Subject to further validation for IP compliance, this material is for first quarter use only. Circulation shall be limited to public schools within the jurisdiction of the Division of Cebu Province. LR-PIPCV
1ST G
ENER
ATION
MODU
LES -
VERS
ION 2.0
-
5
Liquid tight angle connector Liquid tight straight connector
Directions: Read the procedure below in installing conduit and electrical wiring from indoor
unit to outdoor using flexible non-metallic tubing. Write your remarks/comments
in every step by following the given table format below. Use a separate sheet of
paper.
1. Wear appropriate PPE.
2. Measure the required length of flexible non-metallic conduit from the outdoor unit to the
indoor unit.
3. Cut the flexible non-metallic tubing
4. Insert the wires first before laying out the tubing permanently.
5. Use guide wires to facilitate easy pulling of conductors.
ACTIVITY SHEET
Adapter
Disclaimer: The contents above are borrowed from STVEP - CBC/CBLM – Electrical Installation and Maintenance (EIM) by Mr. Marino C.
Cueto; Ms. Gina C, delos Santos; Dr. Corazon Echano; and Mr. Lemuel C. Valles, funded by the Department of Education.
________________________________________________________________________________________________________________________________________________________________Subject to further validation for IP compliance, this material is for first quarter use only. Circulation shall be limited to public schools within the jurisdiction of the Division of Cebu Province. LR-PIPCV
1ST G
ENER
ATION
MODU
LES -
VERS
ION 2.0
-
6
6. Prepare the required length of the conductor.
7. Tie the conductors securely to the guide wires.
8. Pull the guide wires at the other end of the tubing.
9. Seek assistance from other person. The conductors should be push from the other end
while being pulled from the other end.
10. Lay out the tubing with conductors permanently
11. Just simply lay the electrical tubing on the path where the refrigeration system tubing is
installed.
.
12. Secure the flexible non-metallic tubing wrapping it with cable tie.
Wire
allowanc
e
Disclaimer: The contents above are borrowed from STVEP - CBC/CBLM – Electrical Installation and Maintenance (EIM) by Mr. Marino C.
Cueto; Ms. Gina C, delos Santos; Dr. Corazon Echano; and Mr. Lemuel C. Valles, funded by the Department of Education.
________________________________________________________________________________________________________________________________________________________________
Subject to further validation for IP compliance, this material is for first quarter use only. Circulation shall be limited to public schools within the jurisdiction of the Division of Cebu Province. LR-PIPCV
1ST G
ENER
ATION
MODU
LES -
VERS
ION 2.0
-
7
13. Insert the connector.
14. Secure the tubing to the raceway on the indoor unit.
15. Put the lock nut and tighten it.
16. Prepare the conductor for termination. Strip off at least 5 mm of insulation.
17. Terminate the conductors.
18. Be sure that the connections are tightened correctly.
Assessment Criteria
Dimensions VS
S
NI
1. Quality: Quality, workmanship, appearance
2. Accuracy: Dimension, horizontality and verticality of conduits
Disclaimer: The contents above are borrowed from STVEP - CBC/CBLM – Electrical Installation and Maintenance (EIM) by Mr. Marino C.
Cueto; Ms. Gina C, delos Santos; Dr. Corazon Echano; and Mr. Lemuel C. Valles, funded by the Department of Education.
________________________________________________________________________________________________________________________________________________________________Subject to further validation for IP compliance, this material is for first quarter use only. Circulation shall be limited to public schools within the jurisdiction of the Division of Cebu Province. LR-PIPCV
1ST G
ENER
ATION
MODU
LES -
VERS
ION 2.0
-
8
3. Method: Observance of the safety measures.
4. Speed: Submission on time +1, before the expected time +2, after the expected time – 2.
Rating Scale:
VS – Very Satisfactory = 15 – 11
S – Satisfactory = 10 – 5
NI – Needs Improvement = 6 and below
Observation: (Table Format)
Steps
Remarks / Comments
First Step
Second Step
Third Step
Fourth step
Fifth step – up to the last step
``
Directions: Read carefully and answer the statement below. Write your answer on a
separate sheet of paper.
Disclaimer: The contents above are borrowed from STVEP - CBC/CBLM – Electrical Installation and Maintenance (EIM) by Mr. Marino C.
Cueto;Ms. Gina C, delos Santos; Dr. Corazon Echano; and Mr. Lemuel C. Valles, funded by the Department of Education.
GENERALIZATION
________________________________________________________________________________________________________________________________________________________________Subject to further validation for IP compliance, this material is for first quarter use only. Circulation shall be limited to public schools within the jurisdiction of the Division of Cebu Province. LR-PIPCV
1ST G
ENER
ATION
MODU
LES -
VERS
ION 2.0
-
9
1. Why flexible non-metallic conduit shall be permitted to be used in exposed or concealed
in a certain condition?
2. Why flexible non-metallic conduit shall not be used in a certain condition?
3. What is liquid tight flexible non-metallic conduit?
Rubrics:
Criteria Score Rate
Exceptionally clear, thorough and comprehend explanation. 4
Generally clear and substantial explanation. 3
Lacks of clarity, partial or not comprehensive explanation. 2
Unclear, misunderstanding or serious misconception on the explanation. 1
Directions: Draw the different types of Flexible Non-metallic Conduit Fittings. Label it. Use a
separate sheet of paper.
1. Coupling
2. Flexible Non-Metallic Conduit
3. Adapter
4. Liquid Tight Angle Connector
5. Liquid Tight Straight Connector
Rubrics:
Excellent (4) Good (3) Satisfactory
(2)
Needs
Improvement ((1)
Following
Project
Direction
all directions were
followed
you followed
most
directions
you followed
some
directions
none of the
directions were
followed
Use Of
Creativty
you used your own
ideas and imagination
as reflected on you
observation/comments
you used
your own
ideas most
of the time
you used
some
imagination
you did not use
your own
ideas/imagination
Effort Put
Into Project
you took your time
and work hard on the
project
you worked
hard for
most of the
time
you put a
small effort
into the project
you rushed
through and did
not work hard
PERFORMANCE TASKS
Disclaimer: The contents above are borrowed from STVEP - CBC/CBLM – Electrical Installation and Maintenance (EIM) by Mr. Marino C.
Cueto; Ms. Gina C, delos Santos; Dr. Corazon Echano; and Mr. Lemuel C. Valles, funded by the Department of Education.
________________________________________________________________________________________________________________________________________________________________Subject to further validation for IP compliance, this material is for first quarter use only. Circulation shall be limited to public schools within the jurisdiction of the Division of Cebu Province. LR-PIPCV
1ST G
ENER
ATION
MODU
LES -
VERS
ION 2.0
-
10
I. Directions: Label the different types of Flexible Non-metallic Conduit Fittings. Write
your answer on a separate answer sheet.
II. Directions: Inside Box A are jumbled letters. Arrange the letters to form words pertaining
to Flexible Non-metallic Conduit. Then write the words inside Box B. Use a
separate sheet of paper for your answer.
Box A
1. gculinop
2. teradpa
3. connorect
4. tcoduin
5. xfeiblel
1.
2.
3.
4
5.
Disclaimer: The contents above are borrowed from STVEP - CBC/CBLM – Electrical Installation and Maintenance (EIM) by Mr. Marino C. Cueto;
Ms. Gina C, delos Santos; Dr. Corazon Echano; and Mr. Lemuel C. Valles, funded by the Department of Education
SELF – CHECK
Box B
________________________________________________________________________________________________________________________________________________________________Subject to further validation for IP compliance, this material is for first quarter use only. Circulation shall be limited to public schools within the jurisdiction of the Division of Cebu Province. LR-PIPCV
1ST G
ENER
ATION
MODU
LES -
VERS
ION 2.0
-
11
ANSWER KEYS
________________________________________________________________________________________________________________________________________________________________Subject to further validation for IP compliance, this material is for first quarter use only. Circulation shall be limited to public schools within the jurisdiction of the Division of Cebu Province. LR-PIPCV
1ST G
ENER
ATION
MODU
LES -
VERS
ION 2.0
-
12
REFERENCES:
Johnston, Larry et.al., Better Homes and Gardens Wiring 1st Edition, Meredith Books; 2007,pp.
Mulin, R.C., Smith R.L. Electrical Wiring-Commercial, Six Ed., New York: Delmar’s Publishing Inc.; 1984, pp.
Agpoa, Feleciano. Interior and Exterior Wiring Troubleshooting ; National Bookstore: 1991
________________________________________________________________________________________________________________________________________________________________Subject to further validation for IP compliance, this material is for first quarter use only. Circulation shall be limited to public schools within the jurisdiction of the Division of Cebu Province. LR-PIPCV
1ST G
ENER
ATION
MODU
LES -
VERS
ION 2.0
-
13
For inquiries or feedback, please write or call: Department of Education: DepEd-Cebu Province Office Address : IPHO Bldg., Sudlon, Lahug, Cebu City, Philippines Telefax : (032) 520-3216 – 520-3217; SDS Office: (032) 255 - 6405 E-mail Address : [email protected] Bitoon National Vocational High School Office Address : Bitoon, Dumanjug, Cebu Telefax : (032) 471-8001 E-mail Address : [email protected]
________________________________________________________________________________________________________________________________________________________________Subject to further validation for IP compliance, this material is for first quarter use only. Circulation shall be limited to public schools within the jurisdiction of the Division of Cebu Province. LR-PIPCV
1ST G
ENER
ATION
MODU
LES -
VERS
ION 2.0