starter and motor protection trip class t c 20 / 20e 10a, 10 / 10e 10a, 10 / 10e, 20 / 20e, 30 / 30e...
TRANSCRIPT
![Page 1: Starter and motor protection Trip class T C 20 / 20E 10A, 10 / 10E 10A, 10 / 10E, 20 / 20E, 30 / 30E Tripping time T P 3 … 30 s 1) 1) Some frames sizes and current ratings have limited](https://reader035.vdocuments.net/reader035/viewer/2022081401/5ad1a5227f8b9aff738beadf/html5/thumbnails/1.jpg)
Unrestricted / © Siemens AG 2015. All Rights Reserved. siemens.com/3VA
3VA molded case circuit breaker Starter and motor protection
Totally Integrated Power - SENTRON
![Page 2: Starter and motor protection Trip class T C 20 / 20E 10A, 10 / 10E 10A, 10 / 10E, 20 / 20E, 30 / 30E Tripping time T P 3 … 30 s 1) 1) Some frames sizes and current ratings have limited](https://reader035.vdocuments.net/reader035/viewer/2022081401/5ad1a5227f8b9aff738beadf/html5/thumbnails/2.jpg)
Unrestricted / © Siemens AG 2015. All Rights Reserved.
3VA molded case circuit breaker
Starter and motor protection
3VA1 MCCB 3VA2 MCCB
Applications Starter protection Starter and motor protection
Frame sizes 60 A 250 A 160 A 250 A 400 A 630 A
Rated currents 32 A – 200 A 25 A - 500 A
Trip Unit AM I / LSI; LSIG
IEC breaking capacity Icu 415 V 50/60 Hz 55kA , 70kA 55kA, 110kA
Communication Not available Available
Metering Not available Available
![Page 3: Starter and motor protection Trip class T C 20 / 20E 10A, 10 / 10E 10A, 10 / 10E, 20 / 20E, 30 / 30E Tripping time T P 3 … 30 s 1) 1) Some frames sizes and current ratings have limited](https://reader035.vdocuments.net/reader035/viewer/2022081401/5ad1a5227f8b9aff738beadf/html5/thumbnails/3.jpg)
Unrestricted / © Siemens AG 2015. All Rights Reserved.
3VA molded case circuit breaker
Starter protection vs. motor protection
Starter protection Motor protection
Overload relay
(3RB; 3UF7)
Overload
protection
Contactor
Functional
switching
MCCB (3VA)
Instantaneous
protection
Motor
Contactor
Functional
switching
MCCB (3VA)
Instantaneous
protection
Overload protection
… and more
Motor
MCCB (3VA)
Instantaneous
protection
Overload protection
Functional switching
… and more
Motor
![Page 4: Starter and motor protection Trip class T C 20 / 20E 10A, 10 / 10E 10A, 10 / 10E, 20 / 20E, 30 / 30E Tripping time T P 3 … 30 s 1) 1) Some frames sizes and current ratings have limited](https://reader035.vdocuments.net/reader035/viewer/2022081401/5ad1a5227f8b9aff738beadf/html5/thumbnails/4.jpg)
Unrestricted / © Siemens AG 2015. All Rights Reserved.
3VA molded case circuit breaker
Starter protection and motor protection
3VA1 3VA2 3VA2 3VA2
TM120M ETU310M ETU350M ETU860M
Starter
protection
Starter
protection
Motor
protection
Motor
protection
Protection
L overload (long time) Ir
Thermal memory
S short time delay short circuit Isd
I instantaneous short circuit Ii
G ground fault Ig
Additional features
Prepared for higher inrush currents from IE3 motors
Phase unbalance protection available * *
Blocking protection * *
Idle running protection
Power metering integrated
Communication as option
* Function can be achieved with the overload relay (3RB; 3UF7)
![Page 5: Starter and motor protection Trip class T C 20 / 20E 10A, 10 / 10E 10A, 10 / 10E, 20 / 20E, 30 / 30E Tripping time T P 3 … 30 s 1) 1) Some frames sizes and current ratings have limited](https://reader035.vdocuments.net/reader035/viewer/2022081401/5ad1a5227f8b9aff738beadf/html5/thumbnails/5.jpg)
Unrestricted / © Siemens AG 2015. All Rights Reserved.
3VA molded case circuit breaker
IE3 standard (1/2)
January 1st 2015 The IE3 standard
is mandatory in
Europe since
In the power range
0.75 7.5 375 kW
from 2017 on from 2015 on
• Newly installed motors
• Motors in continuous operation
It applies to
![Page 6: Starter and motor protection Trip class T C 20 / 20E 10A, 10 / 10E 10A, 10 / 10E, 20 / 20E, 30 / 30E Tripping time T P 3 … 30 s 1) 1) Some frames sizes and current ratings have limited](https://reader035.vdocuments.net/reader035/viewer/2022081401/5ad1a5227f8b9aff738beadf/html5/thumbnails/6.jpg)
Unrestricted / © Siemens AG 2015. All Rights Reserved.
3VA molded case circuit breaker
IE3 standard (2/2)
Nominal
current
Starting
current
Inrush
current
Before Motors according
to IE3 standard
IE3 Premium Efficiency
motors
• Higher efficiency factor
because of less ohmic loss
• Reduced nominal current
Less ohmic loss
• Lower resistance
• Increase of starting
current
A fact that you won‘t find in
data sheets - but what we
have analyzed for you:
The inrush current rises
enormously!
![Page 7: Starter and motor protection Trip class T C 20 / 20E 10A, 10 / 10E 10A, 10 / 10E, 20 / 20E, 30 / 30E Tripping time T P 3 … 30 s 1) 1) Some frames sizes and current ratings have limited](https://reader035.vdocuments.net/reader035/viewer/2022081401/5ad1a5227f8b9aff738beadf/html5/thumbnails/7.jpg)
Unrestricted / © Siemens AG 2015. All Rights Reserved.
3VA molded case circuit breaker
Inrush current and instantaneous short circuit
3VA1 3VA2 3VA2 3VA2
TM120M ETU310M ETU350M ETU860M
Starter protection Starter protection Motor protection Motor protection
Protection
Ii 7 … 16 x In2) 3 … 15 x In
1) 15 x In1) 3 …15 x In
1)
Ii Default setting Minimum rotary
switch setting
Minimum rotary
switch setting
Minimum rotary
switch setting
Minimum setting
1) Some frames sizes and current ratings have limited adjustment setting. For more information, please refer to the device manual/FAQ@ SIOS.
2) Up to 125 A, In: 200 A Ii = 7….14 x In
All our 3VA molded case
circuit breakers are
prepared for increased
inrush current generated
by IE3 motors.
![Page 8: Starter and motor protection Trip class T C 20 / 20E 10A, 10 / 10E 10A, 10 / 10E, 20 / 20E, 30 / 30E Tripping time T P 3 … 30 s 1) 1) Some frames sizes and current ratings have limited](https://reader035.vdocuments.net/reader035/viewer/2022081401/5ad1a5227f8b9aff738beadf/html5/thumbnails/8.jpg)
Unrestricted / © Siemens AG 2015. All Rights Reserved.
3VA molded case circuit breaker
Overload parameter settings
3VA2 3VA2
ETU350M ETU860M
Motor protection Motor protection
Protection
Ir 0,4 … 1 x In 0,4 … 1 x In
Setting time delay
@ overload Trip class TC
Trip class Tc or
Tripping time TP
Trip class TC
10A, 10 / 10E
20 / 20E
10A, 10 / 10E,
20 / 20E, 30 / 30E
Tripping time TP 3 … 30 s 1)
1) Some frames sizes and current ratings have limited adjustment setting. For more information, please refer to the device manual/FAQ@ SIOS.
Using the mode „Trip class TC“ to set the time delay @ overload means always to select a time range
for overload protection.
Example: TC = 20 6s < TP ≤ 20s according to IEC 60947-4-1
A more precise way to set the tripping time is to directly edit the TP with the ETU860M.
![Page 9: Starter and motor protection Trip class T C 20 / 20E 10A, 10 / 10E 10A, 10 / 10E, 20 / 20E, 30 / 30E Tripping time T P 3 … 30 s 1) 1) Some frames sizes and current ratings have limited](https://reader035.vdocuments.net/reader035/viewer/2022081401/5ad1a5227f8b9aff738beadf/html5/thumbnails/9.jpg)
Unrestricted / © Siemens AG 2015. All Rights Reserved.
3VA molded case circuit breaker
Tripping time, trip class acc. to IEC 60947-4-1
Tripping classes of overload protection devices in acc. with IEC 60947-4-
1
100
50
20
10
5
2
1 50
20
10
5
2
1
0,7 1 2 5 8
t
x Ie
120
CLASS 30 CLASS 25 CLASS 20 CLASS 15 CLASS 10 CLASS 5
Tripping characteristic curve
for 3-pole sym. load
30 and 30E
2 s < tA < 10 s 10 A
10 and 10E
20 and 20E
4 and 5 s < tA < 10 s
6 and 10 s < tA < 20 s
9 and 20 s < tA < 30 s
CLASS Tripping time
The tripping classes are based on the tripping time
(tA) at 7.2-times the set current Ie from cold state.
Suffix “E” in class means narrower tolerance
available in solid-state OLR
The overload protection device has to
trip within these times!
![Page 10: Starter and motor protection Trip class T C 20 / 20E 10A, 10 / 10E 10A, 10 / 10E, 20 / 20E, 30 / 30E Tripping time T P 3 … 30 s 1) 1) Some frames sizes and current ratings have limited](https://reader035.vdocuments.net/reader035/viewer/2022081401/5ad1a5227f8b9aff738beadf/html5/thumbnails/10.jpg)
Unrestricted / © Siemens AG 2015. All Rights Reserved.
The average current and the unbalance ratio are calculated based on:
3VA molded case circuit breaker
Phase unbalance protection
If one of the 3 phases fail, a three-phase motor continues to run like a single-phase motor with an
enormous decrease of load torque. There is a high risk that the motor stops rotating.
With the feature „phase unbalance protection“ the 3VA molded case circuit breaker trips by exceeding
the phase unbalance values for the time tunbalance.
3VA2 3VA2
ETU350M ETU860M
Motor protection Motor protection
Protection
Unbalance Ratio 40% fix 5 … 50% (default 40%)
Phase unbalance protection availability ON ON / OFF (default ON)
Delay time tunbalance
0,7s during start up
4s during normal operation
0,7s during start up
4s during normal operation
![Page 11: Starter and motor protection Trip class T C 20 / 20E 10A, 10 / 10E 10A, 10 / 10E, 20 / 20E, 30 / 30E Tripping time T P 3 … 30 s 1) 1) Some frames sizes and current ratings have limited](https://reader035.vdocuments.net/reader035/viewer/2022081401/5ad1a5227f8b9aff738beadf/html5/thumbnails/11.jpg)
Unrestricted / © Siemens AG 2015. All Rights Reserved.
3VA molded case circuit breaker
Blocking protection
• Stone crusher (stone too hard / large)
• Conveyer belt (transport goods wedged)
Motor blocking (or falling back behind breakdown torque) generates high motor
current (close to starting current). But it‘s still not as high as a short circuit
current!
Without the blocking protection feature it might take up to 30s or more
(depending on current and TP setting) until the breaker trips
unnecessary thermal stress
Application examples for blocking protection
3VA2
ETU860M
Motor protection
Protection
Ib 1,2 … 10 x In in A (default 10)
Delay time tb 1 … 10s (default 1s)
Blocking protection availability ON / OFF (default ON)
During the start up phase (ramp up), blocking protection is automatically disabled
until the motor reaches the operating speed (tstart). tstart equals tb.
![Page 12: Starter and motor protection Trip class T C 20 / 20E 10A, 10 / 10E 10A, 10 / 10E, 20 / 20E, 30 / 30E Tripping time T P 3 … 30 s 1) 1) Some frames sizes and current ratings have limited](https://reader035.vdocuments.net/reader035/viewer/2022081401/5ad1a5227f8b9aff738beadf/html5/thumbnails/12.jpg)
Unrestricted / © Siemens AG 2015. All Rights Reserved.
3VA molded case circuit breaker
Idle running protection
• Load transmission between motor and application was lost
(belt rupture, broken chain …)
• Pump, compressor
With the accessory for idle running protection the motor can be switched off by
tripping the circuit breaker.
Application examples for idle running protection
3VA2
ETU860M
Motor protection
Protection
I<< 0,3 … 0,9 x Ir (default 0,9)
Delay time t<< 1 … 200s (default 1s)
Idle running protection availability ON / OFF (default OFF)
![Page 13: Starter and motor protection Trip class T C 20 / 20E 10A, 10 / 10E 10A, 10 / 10E, 20 / 20E, 30 / 30E Tripping time T P 3 … 30 s 1) 1) Some frames sizes and current ratings have limited](https://reader035.vdocuments.net/reader035/viewer/2022081401/5ad1a5227f8b9aff738beadf/html5/thumbnails/13.jpg)
Unrestricted / © Siemens AG 2015. All Rights Reserved.
3VA1 molded case circuit breaker
Starter protection – TM120M (3VA11/12)
Front view Characteristic curve
Size In Ii
Class
M, H
160 A
(3VA11)
32 A 220 … 510 A
40 A 280 … 640 A
50 A 350 … 800 A
63 A 440 … 1010 A
80 A 560 ... 1280 A
100 A 700 ... 1600 A
125 A 875 … 2000 A
250 A
(3VA12)
160 A 1120 ... 2560 A
200 A 1400 … 2800 A
Ii
![Page 14: Starter and motor protection Trip class T C 20 / 20E 10A, 10 / 10E 10A, 10 / 10E, 20 / 20E, 30 / 30E Tripping time T P 3 … 30 s 1) 1) Some frames sizes and current ratings have limited](https://reader035.vdocuments.net/reader035/viewer/2022081401/5ad1a5227f8b9aff738beadf/html5/thumbnails/14.jpg)
Unrestricted / © Siemens AG 2015. All Rights Reserved.
3VA2 molded case circuit breaker
Starter protection – ETU310M I
Front view Characteristic curve
Size In Ii
Class
C, L
160 A
(3VA21)
25 A 75 … 375 A
40 A 120 … 600 A
63 A 189 … 945 A
100 A 300 … 1.500 A
250 A
(3VA22)
160 A 480 … 2.400 A
200 A 600 … 3.000 A
400 A
(3VA23) 250 A 750 … 3.750 A
630 A
(3VA24)
400 A 1.200 … 6.000 A
500 A 1.500 … 7.500 A
Ii
![Page 15: Starter and motor protection Trip class T C 20 / 20E 10A, 10 / 10E 10A, 10 / 10E, 20 / 20E, 30 / 30E Tripping time T P 3 … 30 s 1) 1) Some frames sizes and current ratings have limited](https://reader035.vdocuments.net/reader035/viewer/2022081401/5ad1a5227f8b9aff738beadf/html5/thumbnails/15.jpg)
Unrestricted / © Siemens AG 2015. All Rights Reserved.
3VA2 molded case circuit breaker
Motor protection – ETU350M LSI
Front view Characteristic curve
Size In Ir Tc
Isd tsd Ii 10A 10 / 10E 20 / 20E
Class
M, C
160 A
(3VA21)
25 A 10 … 25 A
4 8
17
3 …15 Ir 30 ms
375 A
40 A 16 … 40 A 17 600 A
63 A 25 … 63 A 17 945 A
100 A 40 … 100 A 17 1.500 A
250 A
(3VA22)
160 A 63 … 160 A 17 2.400 A
200 A 100 … 200 A 15 3.000 A
400 A
(3VA23) 250 A 100 … 250 A 17 3.750A
630 A
(3VA24)
400 A 160 … 400 A 17 6.000 A
500 A 250 … 500 A 15 7.500 A
![Page 16: Starter and motor protection Trip class T C 20 / 20E 10A, 10 / 10E 10A, 10 / 10E, 20 / 20E, 30 / 30E Tripping time T P 3 … 30 s 1) 1) Some frames sizes and current ratings have limited](https://reader035.vdocuments.net/reader035/viewer/2022081401/5ad1a5227f8b9aff738beadf/html5/thumbnails/16.jpg)
Unrestricted / © Siemens AG 2015. All Rights Reserved.
3VA2 molded case circuit breaker
Motor protection – ETU860M LSIG (1/2)
Front view Characteristic curve
Size In Ir Isd tsd Ii Ig tg
Class
M, C
160 A
(3VA21)
25 A 10 … 25 A
1,2 … 15 x In 30 ms
75 … 375 A 5 … 25 A, OFF
50 … 800 ms
40 A 16 … 40 A 120 … 600 A 8 … 40 A, OFF
63 A 25 … 63 A 189 … 945 A 13 … 63 A,
OFF
100 A 40 … 100 A 300 … 1.500 A 20 … 100 A,
OFF
250 A
(3VA22)
160 A 63 … 160 A 480 … 2.400 A 32 … 160 A,
OFF
200 A 80 … 200 A 600… 3.000 A 50 … 250 A,
OFF
400 A
(3VA23) 250 A 100 … 250 A 750… 3.750 A
50 … 250 A,
OFF
630 A
(3VA24)
400 A 160 … 400 A 1.200 … 6.000 A 80 … 400 A,
OFF
500 A 250 … 500 A 1.500 … 7.500 A 100 … 500 A,
OFF
![Page 17: Starter and motor protection Trip class T C 20 / 20E 10A, 10 / 10E 10A, 10 / 10E, 20 / 20E, 30 / 30E Tripping time T P 3 … 30 s 1) 1) Some frames sizes and current ratings have limited](https://reader035.vdocuments.net/reader035/viewer/2022081401/5ad1a5227f8b9aff738beadf/html5/thumbnails/17.jpg)
Unrestricted / © Siemens AG 2015. All Rights Reserved.
3VA2 molded case circuit breaker
Motor protection – ETU860M LSIG (2/2)
Front view Characteristic curve
Size In
TC Tp I Ib tb I<< t<<
10A 10 / 10E 20 / 20E 30 30E
Class
M, C
160 A
(3VA21)
25 A
4 8
17 24 24 3 … 30 s
OFF, 5 … 50%
30 … 250 A, OFF
1 … 10s 0,3 … 0,9 x Ir 1 … 200s
40 A 17 24 24 3 … 30 s 48 … 400 A, OFF
63 A 17 24 24 3 … 30 s 76 … 630 A, OFF
100 A 17 24 24 3 … 25 s 120 … 1000 A, OFF
250 A
(3VA22)
160 A 17 20 – 3 … 20 s 162 … 1600 A, OFF
200 A 12 15 – 3 … 15 s 240 … 2000 A, OFF
400 A
(3VA23)
250 A 17 24 24 3 … 30 s 300 … 2500 A, OFF
630 A
(3VA24)
400 A 17 24 24 3 … 25 s 480 … 4000 A, OFF
500 A 12 15 – 3 … 15 s 600 … 5000 A, OFF
Tc: Tripping Class I: unsymmetrie of the current I<<: pick up current idle protection Ib: pick up time blocking protection
Tp: Tripping Time t<<: delay time idle protection tb: pick up current blocking protection
![Page 18: Starter and motor protection Trip class T C 20 / 20E 10A, 10 / 10E 10A, 10 / 10E, 20 / 20E, 30 / 30E Tripping time T P 3 … 30 s 1) 1) Some frames sizes and current ratings have limited](https://reader035.vdocuments.net/reader035/viewer/2022081401/5ad1a5227f8b9aff738beadf/html5/thumbnails/18.jpg)
Unrestricted / © Siemens AG 2015. All Rights Reserved.
3VA tables with IE3 motors – motor protection
breaker
SENTRON 3VA circuit breaker for motor protection
In this case, the 3VA circuit breaker for motor protection is also doing the functional
switching
![Page 19: Starter and motor protection Trip class T C 20 / 20E 10A, 10 / 10E 10A, 10 / 10E, 20 / 20E, 30 / 30E Tripping time T P 3 … 30 s 1) 1) Some frames sizes and current ratings have limited](https://reader035.vdocuments.net/reader035/viewer/2022081401/5ad1a5227f8b9aff738beadf/html5/thumbnails/19.jpg)
Unrestricted / © Siemens AG 2015. All Rights Reserved.
3VA molded case circuit breaker
Starter protection/motor protection – tested combinations
Starter protection Motor protection Coordination tests
Tested combinations can be
found in the shape of an FAQ in
SIOS.
The corresponding factory
certificate can also be found in
SIOS.
Please note for these
combinations:
Functional switching is done
by the contactor
Mounting rules have to be
heeded
Unless otherwise indicated,
the combinations are IE3ready
Overload relay
Overload
protection
Contactor
Functional
switching
MCCB (3VA)
Instantaneous
protection
Motor
Contactor
Functional
switching
MCCB (3VA)
Instantaneous
protection
Overload protection
… and more
Motor
![Page 20: Starter and motor protection Trip class T C 20 / 20E 10A, 10 / 10E 10A, 10 / 10E, 20 / 20E, 30 / 30E Tripping time T P 3 … 30 s 1) 1) Some frames sizes and current ratings have limited](https://reader035.vdocuments.net/reader035/viewer/2022081401/5ad1a5227f8b9aff738beadf/html5/thumbnails/20.jpg)
Unrestricted / © Siemens AG 2015. All Rights Reserved.
3VA tables with IE3 motors – motor protection
breaker-contactor-combination
SENTRON 3VA motor protection breaker – device combinations
![Page 21: Starter and motor protection Trip class T C 20 / 20E 10A, 10 / 10E 10A, 10 / 10E, 20 / 20E, 30 / 30E Tripping time T P 3 … 30 s 1) 1) Some frames sizes and current ratings have limited](https://reader035.vdocuments.net/reader035/viewer/2022081401/5ad1a5227f8b9aff738beadf/html5/thumbnails/21.jpg)
Unrestricted / © Siemens AG 2015. All Rights Reserved.
3VA tables with IE3 motors – starter protection
breaker-contactor-overload relay-combination
SENTRON 3VA1 starter protection breakers – device combinations
![Page 22: Starter and motor protection Trip class T C 20 / 20E 10A, 10 / 10E 10A, 10 / 10E, 20 / 20E, 30 / 30E Tripping time T P 3 … 30 s 1) 1) Some frames sizes and current ratings have limited](https://reader035.vdocuments.net/reader035/viewer/2022081401/5ad1a5227f8b9aff738beadf/html5/thumbnails/22.jpg)
Unrestricted / © Siemens AG 2015. All Rights Reserved.
3VA tables with IE3 motors – starter protection
breaker-contactor-overload relay-combination
SENTRON 3VA starter protection breakers – device combinations with overload relay 3RB20/21
![Page 23: Starter and motor protection Trip class T C 20 / 20E 10A, 10 / 10E 10A, 10 / 10E, 20 / 20E, 30 / 30E Tripping time T P 3 … 30 s 1) 1) Some frames sizes and current ratings have limited](https://reader035.vdocuments.net/reader035/viewer/2022081401/5ad1a5227f8b9aff738beadf/html5/thumbnails/23.jpg)
Unrestricted / © Siemens AG 2015. All Rights Reserved.
3VA tables with IE3 motors – starter protection
breaker-contactor-overload relay-combination
SENTRON 3VA starter protection breakers – device combinations with overload relay 3RB22/23
and SIMOCODE pro 3UF7
![Page 24: Starter and motor protection Trip class T C 20 / 20E 10A, 10 / 10E 10A, 10 / 10E, 20 / 20E, 30 / 30E Tripping time T P 3 … 30 s 1) 1) Some frames sizes and current ratings have limited](https://reader035.vdocuments.net/reader035/viewer/2022081401/5ad1a5227f8b9aff738beadf/html5/thumbnails/24.jpg)
Unrestricted / © Siemens AG 2015. All Rights Reserved.