statesville, nc results of “am” ashrae 110 laboratory fume ... 1... · this report provides...
TRANSCRIPT
Statesville, NC
Results of “AM” ASHRAE 110 Laboratory Fume Hood Performance Evaluations
Venturi Hood
January, 2017
Prepared By:
Exposure Control Technologies Inc.
231-C East Johnson Street Cary, NC 27513 Phone: (919) 319-4290 | Fax: (919) 319-4291
www.exposurecontroltechnologies.com
CONTENTS
EXECUTIVE SUMMARY .............................................................................. 1
RECOMMENDATIONS ............................................................................... 1
METHODOLOGY ........................................................................................ 3
HOOD PERFORMANCE TESTS: STATIC SASH ........................................................ 3
Face Velocity Test ................................................................................... 3
Cross Draft Tests..................................................................................... 4
Airflow Visualization Tests ...................................................................... 4
Tracer Gas Tests ..................................................................................... 5
Periphery Scan Test ................................................................................ 6
Sash Movement Effect (SME) Test .......................................................... 6
RECOMMENDED PERFORMANCE CRITERIA ............................................... 7
TEST RESULTS ............................................................................................ 8
Table I: Laboratory Fume Hood Performance Test Results ...................... 8
STANDARD OPERATING PROCEDURES FOR HOOD USE ............................. 9
APPENDIX A ...................................................... CERTIFICATES OF CALIBRATION
APPENDIX B ............... HOOD INFORMATION AND PERFORMANCE TEST DATA SHEETS
Kewaunee Scientific: Venturi AM Hood Performance Testing January 2017 1
EXECUTIVE SUMMARY
This report provides results of “As Manufactured” (AM) performance tests conducted on one constant air volume (CAV) six-foot Venturi model laboratory fume hood within the Kewaunee Scientific fume hood testing laboratory located in Statesville, North Carolina. Exposure Control Technologies, Inc. performed the tests on January 23-24, 2017. Testing was performed in accordance with guidelines provided in the ANSI/ASHRAE 110-2016 "Method of Testing Performance of Laboratory Fume Hoods." The criteria for performance were adopted from recommendations by the ACGIH, the National Research Council, SEFA, ANSI, and relevant industry standards on laboratory ventilation. The hood was tested “As Manufactured” (AM) at the 28” vertical full open sash height, at 40 fpm face velocity and with the hood both empty and box-loaded.
RECOMMENDATIONS The ASHRAE 110 tests were conducted under a variety of scenarios, as follows:
• ASHRAE 110 test, hood clear, 40 fpm test.
• ASHRAE 110 test, hood box-loaded per NIH standard, 40 fpm test.
Results of testing revealed that the fume hood met acceptance criteria as described herein, with average tracer gas containment results below the industry “AM” standard of 0.05 ppm.
Testing and evaluation were performed by:
Randy Blew Senior Laboratory Services Project Manager
Kewaunee Scientific: Venturi AM Hood Performance Testing January 2017 3
METHODOLOGY
Hood Performance Tests: Static Sash All performance tests were conducted with the sash at the vertical full open height of 28 inches.
• Measurement of Face Velocity
• Measurement of Cross Drafts
• Visualization of Airflow Patterns
• Measurement of Tracer Gas Containment
• Periphery Scan Test
• Sash Movement Effect (SME) Tests
Face Velocity Test The face velocity tests were performed by dividing the opening of the hood into equal area grids of approximately 1 square foot and measuring the velocity at the center of each grid. Air velocities were recorded at one-second intervals for 10 seconds at each grid location. The mean of the grid velocities were averaged for the opening to determine the overall average face velocity. The mean grid velocities can be used to evaluate spatial and temporal variation of velocities across the opening. Refer to Figure 1.
Figure 1: Diagram of hood opening showing face velocity traverse locations
Kewaunee Scientific: Venturi AM Hood Performance Testing January 2017 4
Cross Draft Tests Potentially interfering cross drafts were measured in front of the hood opening with a pair of calibrated thermo-anemometers. Measurements were made with the probes positioned vertically and horizontally parallel to the side edge of the hood approximately 5 feet above the floor and approximately 18 inches from the left, center, and right edge of the hood enclosure. Cross draft velocities were recorded at one-second intervals for 30 seconds and averaged. Velocity of air flowing into the hood due to exhaust flow has negligible effect on cross draft velocities. Refer to Figure 2 for a diagram of cross draft test locations.
Figure 2: Plan and elevation diagram showing location of cross draft measurements.
Airflow Visualization Tests Smoke was generated in the hood and around the periphery of the opening using a Rosco Fog Generator. Smoke patterns were observed to identify escape and reverse flow zones. A low volume of smoke was generated along the periphery of the opening and inside the hood at approximately 6 inches inside the plane of the sash (low-flow). A high volume of smoke was also discharged inside the hood and the clearance time and smoke patterns were noted (high-flow). Observations were rated subjectively based on the table provided in the following section "Recommended Performance Criteria."
Kewaunee Scientific: Venturi AM Hood Performance Testing January 2017 5
Tracer Gas Tests The tracer gas containment tests were conducted to evaluate and quantify the potential for contaminant escape in the presence of a mannequin. A mannequin was used to simulate the presence of a hood user. The mannequin was positioned at the left, center and right of the hood opening with the nose approximately 3 inches in front of the plane of the sash. A tracer gas, Sulfur Hexafluoride, was released from an ASHRAE 110 ejector at 4 liters per minute (lpm) 6 inches behind the plane of the sash directly in front of the mannequin. Breathing zone concentrations were measured every second for 5 minutes in each test location using a calibrated USON Qualichek 200 Trace Gas Leak Detector. The leak detector was calibrated against a calibration gas standard immediately prior to the start of tests and validated after tests were conducted. Average, minimum and maximum breathing zone concentrations were determined from the data. The leak detector has an upper limit of detection of 2.00 parts per million (ppm). Refer to Figure 3 for a diagram of the test configuration.
Figure 3: Configuration of mannequin at hood opening during tracer gas tests.
Kewaunee Scientific: Venturi AM Hood Performance Testing January 2017 6
Periphery Scan Test The Periphery Scan Test was conducted by configuring the sash to the maximum vertical operational opening and positioning the SF6 ejector at the center of the hood opening as described above for the Tracer Gas Test. The periphery of the hood’s opening was then scanned with the USON Qualichek 200 Trace Gas Leak Detector’s probe to determine areas of possible containment loss. While standing away from the face of the hood, the probe was held 1 inch away from the edge of the hood opening and moved slowly around the opening at a rate of approximately 3 inches per second for 120 seconds to identify any potential leakage points. Sash Movement Effect (SME) Test
The Sash Movement Effect Test consisted of recording tracer gas escape data while raising and lowering the sash at a rate of approximately 1.5 feet per second. The sash was closed for approximately 30 seconds and opened for approximately 60 seconds throughout the five-minute test. The values for tracer gas were recorded at a rate of 1 sample per second using a laptop computer and data acquisition system. Refer to Figure 4 for a diagram of the test configuration.
Figure 4: Diagram of typical setup of Sash Movement Effect Test
Kewaunee Scientific: Venturi AM Hood Performance Testing January 2017 7
RECOMMENDED PERFORMANCE CRITERIA The following criteria are assembled from industry consensus standards and are provided as an aid in the evaluation of performance data. The criteria are based on SEFA, ANSI Z9.5, ACGIH, and relevant ventilation standards. The criteria apply to the following tests: Smoke Visibility Test – Hood must provide complete containment of the smoke generated within the hood. Containment was determined visually and in the absence of the mannequin. Results are reported as a qualitative judgment of airflow distribution according to the following rating guide:
RATING DESCRIPTION
FAIL • Smoke was visually observed escaping from the hood
LOW PASS (Poor)
• Reverse flow of smoke is evident near opening • Lazy flow into hood along openings • Slow capture and clearance • Observed potential for escape
PASS (Fair)
• Some Reverse flow in hood not necessarily at opening • Limited turbulent vortex flow inside hood • Smoke is captured and clears readily • No visible escape
HIGH PASS (Good)
• Good capture and quick clearance • Limited vortex flow inside hood • No reverse flow regions • No visible escape
Face Velocity Test – Hood should have a minimum average face velocity of 50-60 fpm at the low volume setting. The face velocity readings should not vary more than 20% of the mean between grid locations. Cross Draft Test – Cross draft velocities should not exceed 50 fpm near the hood opening. Ideally, cross draft velocities should be less than 30 fpm. High cross draft velocities are particularly detrimental to hood performance when sashes are opened beyond the design operational opening. Tracer Gas Challenge Test – Hood should provide containment of tracer gas below an average of 0.10 ppm measured for a period of 5 minutes in the breathing zone of a stationary mannequin positioned directly in front of the ejector location. Periphery Scan Test – Hood should provide containment of tracer gas below an average of 0.10 ppm and peak concentrations should be less than 1.00 ppm measured for a period of 2 minutes while scan is conducted. SME Test – The hood should provide containment of tracer gas below an average of 0.10 ppm measured in the breathing zone of a stationary mannequin positioned directly in front of the ejector location.
Kewaunee Scientific: Venturi AM Hood Performance Testing January 2017 8
TEST RESULTS
Table I: Laboratory Fume Hood Performance Test Results
Average Face
Velocity (fpm)
Exhaust Flow1
(cfm)
Tracer Gas Avg.2; 3 (ppm) Cross Draft Max Avg.
(fpm)
Smoke Visualization Test
Comments Performance
Rating Left Center Right
Per. Scan
SME Horiz. Vert. Low High
41 502
<0.01 <0.01 <0.01 0.01 <0.01
16 20
Pass (Fair)
Pass (Fair)
ASHRAE 110 test, hood clear, 40 fpm test.
Pass
<0.01 <0.01 <0.01 <0.01 <0.01 Pass (Fair)
Pass (Fair)
ASHRAE 110 test, hood box-loaded per NIH standard, 40 fpm test.
Pass
Table I Notes: 1. Calculated Exhaust Flow (cfm) = measured average face velocity (fpm) x face opening area (sq.ft). 2. 5-minute avg. tracer gas concentration in mannequin’s breathing zone. 3. 2 minute avg. tracer gas concentration for periphery scan test (refer to Appendix B – Test Data Sheets for max concentration readings).
Kewaunee Scientific: Venturi AM Hood Performance Testing January 2017 9
STANDARD OPERATING PROCEDURES FOR HOOD USE
The following is a list of guidelines for working in the fume hood:
1. Minimize the sash opening when possible.
2. Do not adjust baffle positions.
3. Elevate contaminants and equipment 1-2 inches above the work surface within the hood(s).
4. If equipment and material storage are necessary, locate along the sidewalls or well away from the point of contaminant generation. Do not store any equipment that restricts the closing of the sash or blocks the bottom slot of the baffle directly in front of the employee.
5. Keep movements in the hood and in front of the hood to a minimum.
6. Keep movements within the lab to a minimum while working in the hood(s). Traffic past the hood(s) can generate considerable cross drafts.
7. Keep head and upper body outside the plane of the hood(s) opening at all times.
8. Always approach and withdraw from hood(s) slowly. Open and close the sash slowly.
APPENDIX A
Certificates of Calibration
APPENDIX B
Hood Information and Performance Test Data Sheets
Datasheet - Laboratory Hood Performance Test ResultsReport printed on 2/9/2017
Company Name:
MainBuilding Name:
Kewaunee Test LabLaboratory:
Hood: Venturi 6 foot
Conditions:
Height
Full open sash Sash Opening:
3Cycle Index:
1/24/2017Date:
28 inches
Baffle Opening:
63 inches
Apparatus In Hood:
12.25 ft^2
Monitor Reading - As Found:
0 ft^2 12.25 ft^2
No Clear for tests.
n/a
DAQCollection Method:
Pass (Fair)Low Volume Rating:
Comments: Lazy and reverse flow along worksurface. Reverse flow in corners of opening. Reverse flow within six inches of opening. Turbulent vortex in top of hood.
Positions: Left
PassCycle Rating:
Width Major Area Additional Area Total Area
Normal
Opening Dimensions:
Test Comments: ASHRAE 110 test, 40 fpm test.
Smoke Visibility Test Results:
Pass (Fair)High Volume Rating:
Cross-Draft Test Results:
Center Right
Horiz.: Max:
Avg: 2 14 16
18 23 23
25 16 21
20 9 7
Vertical Max:
Avg:
Perpend.: Max:
Avg:
DAQCollection Method:Hood Face-Velocity Test Results:
42 42 36 42 43 42
36 37 42 38 36 40
40 45 45 40 40 44
Row 1
Row 2
Row 3
Row 4
Row 5
Row 6
Row 7
Row 8
Col 1 Col 2 Col 3 Col 4 Col 5 Col 6 Col 7 Col 8 Col 9 Col 10 Col 11 Col 12
41Avg:
45Max:
36Min:
502Exhaust
Flow:
fpm
fpm
fpm
cfm
Left Center Right
0.00 0.00 0.00
0.00 0.00 0.00
0.00 0.00 0.00
DAQ
1 2 3 4
Collection Method:Tracer Gas Test Results:
Tested:
Maximum:
Average:
Minimum:
Position:
ppm
ppm
ppm
Max Avg
As Left: n/a
Diff. Pressure Occupied: Un-Occupied:
3Cycle:1/24/2017Date:Venturi 6 footHood:
Average:
Maximum:
Minimum:
Left
.00
.00
.00
Center
.00
.00
.00
Right
.00
.00
.00
0.000.100.200.300.400.500.600.700.800.901.00
Es
ca
pe
-pp
m
30 60 90 120 150 180 210 240 270 300Seconds
0.000.100.200.300.400.500.600.700.800.901.00
Es
ca
pe
-pp
m
30 60 90 120 150 180 210 240 270 300Seconds
0.000.100.200.300.400.500.600.700.800.901.00
Es
ca
pe
-pp
m
30 60 90 120 150 180 210 240 270 300Seconds
0.000.010.020.030.040.050.060.070.080.090.10
Es
ca
pe
-pp
m
30 60 90 120 150 180 210 240 270 300Seconds
Plots of Tracer Gas Containment Report printed on 2/9/2017
3Cycle:
1/24/2017Date:
Venturi 6 footHood: Full open sash Sash Opening:
Other Test Conditions: ASHRAE 110 test, 40 fpm test.
SME Test
1 .. 300 seconds
Average:
Maximum:
Minimum:
3
17
0
1
7
0
0
0
0
Flow Response Cross Draft Tracer Gas Escape
Flow Response Cross Draft Tracer Gas Escape
0.00
50.00
100.00
150.00
200.00
Ve
loc
ity =
fp
m
0.00
0.10
0.20
0.30
0.40
0.50
0.60
0.70
0.80
0.90
1.00
0 300
Seconds
Report printed on 2/9/2017
1# Samples:
300Sample Duration:
1# Samples per Second:
N/ASpeed of Response Rating:
Speed of Response Time:
N/AStability Rating:
Stability Percent Variation:
VAV Comment:
Datasheet - Laboratory Hood Performance Test ResultsReport printed on 2/9/2017
Company Name:
MainBuilding Name:
Kewaunee Test LabLaboratory:
Hood: Venturi 6 foot
Conditions:
Height
Full open sash Sash Opening:
4Cycle Index:
1/24/2017Date:
28 inches
Baffle Opening:
63 inches
Apparatus In Hood:
12.25 ft^2
Monitor Reading - As Found:
0 ft^2 12.25 ft^2
No Clear for tests.
n/a
Collection Method:
Low Volume Rating:
Comments:
Positions:
PassCycle Rating:
Width Major Area Additional Area Total Area
Normal
Opening Dimensions:
Test Comments: Periphery scan, ASHRAE 110 40 fpm test.
Smoke Visibility Test Results:
High Volume Rating:
Cross-Draft Test Results:
Horiz.: Max:
Avg:
Vertical Max:
Avg:
Perpend.: Max:
Avg:
Collection Method:Hood Face-Velocity Test Results:
Row 1
Row 2
Row 3
Row 4
Row 5
Row 6
Row 7
Row 8
Col 1 Col 2 Col 3 Col 4 Col 5 Col 6 Col 7 Col 8 Col 9 Col 10 Col 11 Col 12
Avg:
Max:
Min:
ExhaustFlow:
P-scan
0.05
0.01
0.00
DAQ
1 2 3 4
Collection Method:Tracer Gas Test Results:
Tested:
Maximum:
Average:
Minimum:
Position:
ppm
ppm
ppm
As Left: n/a
Diff. Pressure Occupied: Un-Occupied:
4Cycle:1/24/2017Date:Venturi 6 footHood:
Average:
Maximum:
Minimum:
P-scan
.01
.05
.00
0.000.100.200.300.400.500.600.700.800.901.00
Es
ca
pe
-pp
m
12 24 36 48 60 72 84 96 108 120Seconds
0.000.010.020.030.040.050.060.070.080.090.10
Es
ca
pe
-pp
m
12 24 36 48 60 72 84 96 108 120Seconds
0.000.010.020.030.040.050.060.070.080.090.10
Es
ca
pe
-pp
m
12 24 36 48 60 72 84 96 108 120Seconds
0.000.010.020.030.040.050.060.070.080.090.10
Es
ca
pe
-pp
m
12 24 36 48 60 72 84 96 108 120Seconds
Plots of Tracer Gas Containment Report printed on 2/9/2017
Datasheet - Laboratory Hood Performance Test ResultsReport printed on 2/9/2017
Company Name:
MainBuilding Name:
Kewaunee Test LabLaboratory:
Hood: Venturi 6 foot
Conditions:
Height
Full open sash Sash Opening:
5Cycle Index:
1/24/2017Date:
28 inches
Baffle Opening:
63 inches
Apparatus In Hood:
12.25 ft^2
Monitor Reading - As Found:
0 ft^2 12.25 ft^2
Yes Box-loaded per NIH.
n/a
DAQCollection Method:
Pass (Fair)Low Volume Rating:
Comments: Lazy and reverse flow along worksurface. Reverse flow in corners of opening. Reverse flow within six inches of opening. Turbulent vortex in top of hood.
Positions: Left
PassCycle Rating:
Width Major Area Additional Area Total Area
Normal
Opening Dimensions:
Test Comments: Box-loaded ASHRAE 110, 40 fpm test.
Smoke Visibility Test Results:
Pass (Fair)High Volume Rating:
Cross-Draft Test Results:
Center Right
Horiz.: Max:
Avg: 2 14 16
18 23 23
25 16 21
20 9 7
Vertical Max:
Avg:
Perpend.: Max:
Avg:
DAQCollection Method:Hood Face-Velocity Test Results:
42 42 36 42 43 42
36 37 42 38 36 40
40 45 45 40 40 44
Row 1
Row 2
Row 3
Row 4
Row 5
Row 6
Row 7
Row 8
Col 1 Col 2 Col 3 Col 4 Col 5 Col 6 Col 7 Col 8 Col 9 Col 10 Col 11 Col 12
41Avg:
45Max:
36Min:
502Exhaust
Flow:
fpm
fpm
fpm
cfm
Left Center Right
0.04 0.00 0.00
0.00 0.00 0.00
0.00 0.00 0.00
DAQ
1 2 3 4
Collection Method:Tracer Gas Test Results:
Tested:
Maximum:
Average:
Minimum:
Position:
ppm
ppm
ppm
Max Avg
As Left: n/a
Diff. Pressure Occupied: Un-Occupied:
5Cycle:1/24/2017Date:Venturi 6 footHood:
Average:
Maximum:
Minimum:
Left
.00
.04
.00
Center
.00
.00
.00
Right
.00
.00
.00
0.000.100.200.300.400.500.600.700.800.901.00
Es
ca
pe
-pp
m
30 60 90 120 150 180 210 240 270 300Seconds
0.000.100.200.300.400.500.600.700.800.901.00
Es
ca
pe
-pp
m
30 60 90 120 150 180 210 240 270 300Seconds
0.000.100.200.300.400.500.600.700.800.901.00
Es
ca
pe
-pp
m
30 60 90 120 150 180 210 240 270 300Seconds
0.000.010.020.030.040.050.060.070.080.090.10
Es
ca
pe
-pp
m
30 60 90 120 150 180 210 240 270 300Seconds
Plots of Tracer Gas Containment Report printed on 2/9/2017
5Cycle:
1/24/2017Date:
Venturi 6 footHood: Full open sash Sash Opening:
Other Test Conditions: Box-loaded ASHRAE 110, 40 fpm test.
SME Test
1 .. 300 seconds
Average:
Maximum:
Minimum:
0
0
0
0
0
0
0
1
0
Flow Response Cross Draft Tracer Gas Escape
Flow Response Cross Draft Tracer Gas Escape
0.00
50.00
100.00
150.00
200.00
Ve
loc
ity =
fp
m
0.00
0.10
0.20
0.30
0.40
0.50
0.60
0.70
0.80
0.90
1.00
0 300
Seconds
Report printed on 2/9/2017
1# Samples:
300Sample Duration:
1# Samples per Second:
N/ASpeed of Response Rating:
Speed of Response Time:
N/AStability Rating:
Stability Percent Variation:
VAV Comment:
Datasheet - Laboratory Hood Performance Test ResultsReport printed on 2/9/2017
Company Name:
MainBuilding Name:
Kewaunee Test LabLaboratory:
Hood: Venturi 6 foot
Conditions:
Height
Full open sash Sash Opening:
6Cycle Index:
1/24/2017Date:
28 inches
Baffle Opening:
63 inches
Apparatus In Hood:
12.25 ft^2
Monitor Reading - As Found:
0 ft^2 12.25 ft^2
Yes Box-loaded per NIH.
n/a
Collection Method:
Low Volume Rating:
Comments:
Positions:
PassCycle Rating:
Width Major Area Additional Area Total Area
Normal
Opening Dimensions:
Test Comments: Periphery scan, Box-loaded ASHRAE 110, 40 fpm test.
Smoke Visibility Test Results:
High Volume Rating:
Cross-Draft Test Results:
Horiz.: Max:
Avg:
Vertical Max:
Avg:
Perpend.: Max:
Avg:
Collection Method:Hood Face-Velocity Test Results:
Row 1
Row 2
Row 3
Row 4
Row 5
Row 6
Row 7
Row 8
Col 1 Col 2 Col 3 Col 4 Col 5 Col 6 Col 7 Col 8 Col 9 Col 10 Col 11 Col 12
Avg:
Max:
Min:
ExhaustFlow:
Center
0.11
0.00
0.00
DAQ
1 2 3 4
Collection Method:Tracer Gas Test Results:
Tested:
Maximum:
Average:
Minimum:
Position:
ppm
ppm
ppm
As Left: n/a
Diff. Pressure Occupied: Un-Occupied:
6Cycle:1/24/2017Date:Venturi 6 footHood:
Average:
Maximum:
Minimum:
Center
.00
.11
.00
0.000.100.200.300.400.500.600.700.800.901.00
Es
ca
pe
-pp
m
12 24 36 48 60 72 84 96 108 120Seconds
0.000.010.020.030.040.050.060.070.080.090.10
Es
ca
pe
-pp
m
12 24 36 48 60 72 84 96 108 120Seconds
0.000.010.020.030.040.050.060.070.080.090.10
Es
ca
pe
-pp
m
12 24 36 48 60 72 84 96 108 120Seconds
0.000.010.020.030.040.050.060.070.080.090.10
Es
ca
pe
-pp
m
12 24 36 48 60 72 84 96 108 120Seconds
Plots of Tracer Gas Containment Report printed on 2/9/2017