structural calculations

Upload: soleb

Post on 02-Jun-2018

250 views

Category:

Documents


5 download

TRANSCRIPT

  • 8/11/2019 Structural Calculations

    1/54

    PROPOSED RESIDENTIAL

    HOUSE IN KYANJA

    PLOT 3318 - BLOCK 195, KYANJA

    STRUCTURAL CALCULATIONS

    CLIENT STRUCTURAL DESIGNER

    MR. TONNY SAKAAZA

    P.O.BOX 10109, KAMPALA

    UGANDA

    SOLOMON N. BALEMEZI

    BSc. CIV. ENG. MUK; M.U.I.P.E

    P.O. BOX 8493 KAMPALA

    EMAIL: [email protected]

    PHONE: 0779-918-103

  • 8/11/2019 Structural Calculations

    2/54

    STRUCTURAL SUMMARY SHEET

    Client : MR TONNY SAKAAZA

    Project: PROPOSED RESIDENTIAL HOUSE IN KYANJA

    Regulations and Design 1. Kampala Capital City Authority RegulationsCodes: 2. BS 6399, Part 1 1985 Design Loadings

    3. CP3 Chapter V, Part 2 1978 Wind Loadings4. BS 8110, Parts 1 & 3 1991 Structural Use of Concrete

    Loading Conditions: 1. Roof Imposed load = 0.6KN/m 2

    Dead load (Tiles, timber, ceiling, e.t.c) = 1.0KN/m 2

    2. Floor Imposed load (office or bedroom) = 1.5KN/m 2

    3 Wind Basic SpeedS 1=1.0 S 2 = 0.9 S 3 =1.0

    Foundations: 1. Reinforced concrete Strip Footings

    Walls: 200mm Thick Load Bearing walls

    Roof: IT4 sheets on Timber purlins, Timber trusses

    Sub-Soil Conditions: Evaluated soil bearing pressures = 180k N /m 2

    Materials: CONCRETE1. Blinding Concrete Grade 15 (1:3:6) Max 20mm aggregate.

    2. Structural Concrete

    Grade 20 (1:2:4)

    Max 20mm aggregate2. Structural Concrete Grade 25 (1:1.5:3) Max 20mm aggregate

    REINFORCEMENT1. T & Y high yield (f y) Grade 460 N/mm 2 2. R Low yield Grade 250N/mm 2

    MASONRY WALLSolid concrete blocks of compressive strength 5N/mm 2

    TIMBER

    Pine - strength class C14

    Fire Resistance: 1 hour fire resistance for all elements

    Purpose of Building: Residential

  • 8/11/2019 Structural Calculations

    3/54

  • 8/11/2019 Structural Calculations

    4/54

  • 8/11/2019 Structural Calculations

    5/54

    REFERENCE PARTICULARS OUTPUT

    Eurocode 5(ENV 1995-1-1)

    Eurocode 5(ENV 1995-1-1)

    PROPOSED SAKAZA'S RESIDENCE IN KUNGU

    DESIGN OF THE TIMBER PURLINS

    Design Assumptions and Details;

    Angle of inclination of the roof to horizontal is 4

    75x50mm Pine Timber Purlins Iron Sheets as Roof Covering (weight = 4.8kg/m 2) No wind load considered because roof is surrounded by parapet wall

    Note: The Design output is to determine the span of purlins that shall preventultimate failure of purlins and to limit excessive deflection.

    Timber properties Pine; Strength Class C14/ SG4

    Grade Stresses

    Loading;

    Permanent Load Due to;

    1. Corrugated Iron Sheets, F sheets :

    2. Purlins, F purlins :

    Total Permanent Load

    Variable Load;

    For Roof without access, Live load Hence, Design Load, F d;

  • 8/11/2019 Structural Calculations

    6/54

    REFERENCE PARTICULARS OUTPUT

    Eurocode 5(ENV 1995-1-1)

    Eurocode 5(ENV 1995-1-1)

    Eurocode 5(ENV 1995-1-1)

    Resolving the LoadNormal to the roof;

    Tangential to the roof;

    Determine Maximum Span of Purlins using Bending Criterion

    Moments Due to applied Loads ;

    Ignore bending about y-y axis because it is negligible

    Moment Capacity of a 75x50mm Pine Timber Section ;

    f b.allow - Allowable Bending Stress

    Ixx - Moment of Inertia about the x-x axis

    y - Distance to neutral axis

    Allowable Bending Stress f b.allow :

    Where:

    f m,k - Characteristic Bending Stress kmod - Modification factor for Load Duration and Service Class

    kh - Modification factor for Member Size Effect

    k sys - Modification factor for System Strength = 1.1

    m - Material Safety Factor = 1.3

    Moment of Inertia about x-x axis I xx:

    Distance to Neutral Axis y: ;

    Hence;

  • 8/11/2019 Structural Calculations

    7/54

    REFERENCE PARTICULARS OUTPUTEquating moment due to applied load to moment capacity of the timber section

    L = 1389mm

    Determine Maximum Span of Purlins using Limiting Deflection CriterionDeflection Criterion:

    L = 1600mm

    Bending Criterion governs the Maximum Span for Purlins.

    Therefore place Trusses at 1300mm c/c

    L = 1389mm Due toBending Criterion

    L = 1600mm Due toDeflection Criterion

    Bending governs

  • 8/11/2019 Structural Calculations

    8/54

    REFERENCE PARTICULARS OUTPUT

    PROPOSED SAKAZA'S RESIDENCE IN KUNGU

    DESIGN OF THE MAIN TRUSS

    Loading;

    Permanent Load Due to;

    1. Purlins, F purlins :

    2. Corrugated Iron Sheets, F sheets :

    3. Ceiling, F ceiling (Assume 0.15kN/m2

    ):

    4. Services, F services (Assume 0.1kN/m 2):

    Total Permanent Load

    Variable Load;

    For Roof without access, Live load Hence, Design Load, F d;

  • 8/11/2019 Structural Calculations

    9/54

    REFERENCE PARTICULARS OUTPUT

    Eurocode 5

    (ENV 1995-1-1)

    Eurocode 5(ENV 1995-1-1)

    Design of the Tie Beam

    Timber properties Pine; Strength Class C14/ SG4Grade Stresses

    Results of Truss Analysis for the Tie Beam;From the Analysis of the main truss for the Ultimate Limit State using PROKONStructural Analysis software, the following maximum forces have been obtainedfrom PROKON Structural Analysis software.

    Maximum Compressive Force = 4.87kN

    Design of Tie Beam to Resist Maximum Compressive Force

    Member Geometric Properties

    Try a 50x75mm Timber Section

    Since the slenderness ratio is greater than 0.3, the member will fail by bucklingand hence clause 6.3.2(3) applies.

    Buckling Resistance Condition:

  • 8/11/2019 Structural Calculations

    10/54

    REFERENCE PARTICULARS OUTPUT

    Eurocode 5(ENV 1995-1-1)

    Clause 6.3.2 (3)

    Eurocode 5(ENV 1995-1-1)

    Eurocode 5(ENV 1995-1-1)

    Factor k; EC5, equation (6.28))

    Instability factor, k c; (EC5, equation (6.26))

    Design Buckling Strength f c.design :

    Where:

    f c,design - Design Buckling Strength

    f c,k - Characteristic Compression strength parallel to grain

    kmod - Modification factor for Load Duration and Service Class

    kc - Instability Factor

    m - Material Safety Factor = 1.3

    Applied Compression Stress, f c.applied

    Section is Adequate.Hence provide 50x75mm Section for the Tie Beam

  • 8/11/2019 Structural Calculations

    11/54

    REFERENCE PARTICULARS OUTPUT

    Results of Truss Analysis for the Rafter;

    From the Analysis of the main truss for the Ultimate Limit State using PROKONStructural Analysis software, the following maximum forces have been obtainedfrom PROKON Structural Analysis software.

    Maximum Force = 4.93kN Compressive

    Design of Rafter to Resist Maximum Compressive Force

    Member Geometric Properties

    Try a 50x75mm Timber Section

    Since the slenderness ratio is greater than 0.3, the member will fail by buckling

    and hence clause 6.3.2(3) applies.Buckling Resistance Condition:

    Factor k; EC5, equation (6.28))

  • 8/11/2019 Structural Calculations

    12/54

    REFERENCE PARTICULARS OUTPUT

    Instability factor, k c; (EC5, equation (6.26))

    Design Buckling Strength f c.design :

    Where:

    f c,design - Design Buckling Strength

    f c,k - Characteristic Compression strength parallel to grain kmod - Modification factor for Load Duration and Service Class

    kc - Instability Factor

    m - Material Safety Factor = 1.3

    Applied Compression Stress, f c.applied

    Section is Adequate.

    Hence provide 50x75mm Section for the Rafter

  • 8/11/2019 Structural Calculations

    13/54

    REFERENCE PARTICULARS OUTPUT

    Results of Truss Analysis for the Struts & Ties;

    From the Analysis of the main truss for the Ultimate Limit State using PROKONStructural Analysis software, the following maximum forces have been obtainedfrom PROKON Structural Analysis software.

    Maximum Force = 6.69kN Compressive

    Design of Rafter to Resist Maximum Compressive Force

    Member Geometric Properties

    Try a 50x75mm Timber Section

    Since the slenderness ratio is greater than 0.3, the member will fail by bucklingand hence clause 6.3.2(3) applies.

    Buckling Resistance Condition:

    Factor k; EC5, equation (6.28))

  • 8/11/2019 Structural Calculations

    14/54

    REFERENCE PARTICULARS OUTPUT

    Instability factor, k c; (EC5, equation (6.26))

    Design Buckling Strength f c.design :

    Where:

    f c,design - Design Buckling Strength

    f c,k - Characteristic Compression strength parallel to grain

    kmod - Modification factor for Load Duration and Service Class kc - Instability Factor

    m - Material Safety Factor = 1.3

    Applied Compression Stress, f c.applied

    Section is Adequate.

    Hence provide 50x75mm Section for the Ties & Struts

  • 8/11/2019 Structural Calculations

    15/54

  • 8/11/2019 Structural Calculations

    16/54

    DESIGN OF PLYWOOD WEBBED BEAM 01REFERENCE CALCULATIONS OUPUT

    Illustration

    Section PropertiesFirst Moment of Area, QQ = Q flange + Q web

    = A + a = ((100mm*50mm)*(200-25))+(200*12*2)= 875,000 + 4,800

    Q = 879,900mm 3

    Second Moment of Area, QI = (1/12)*(BH 3-bh 3))

    = (1/12)*((100*400 3) - (100*300 3))= (1/12)*((6,400,000,000)-( 2,700,000,000))

    I = 308,333,333mm 4

    Zziwa, A.

    Ziraba, Y.K.& Mwakali,J.A (2010)15 th NTCMay 20-21,2010

    BS5268-2:2002 Table8

    Timber properties Local/Trade name; Flanges from Pine

    Strength Class C14/ SG4

    Grade Stresses

    Bending parallel to grain; m = 14 N/mm 2

    Tension parallel to grain; t = 8 N/mm 2

    Compression parallel to grain; c = 16 N/mm 2

    Compression perpendicular to grain (no wane); cp1 = 2 N/mm 2

    Shear parallel to grain; = 1.7 N/mm 2

    Mean modulus of elasticity; Emean = 7000 N/mm 2

    Characteristic density; char = 290 kg/m 3

    Average density; = 350 kg/m 3

    3200mm

  • 8/11/2019 Structural Calculations

    17/54

    Loading Characteristic Permanent Loads

    Ceramic Tiles - 0.5kN/m 2

    Screed - 1.2kN/m 2

    Plywood Decking - 0.2kN/m 2

    Plaster - 0.5kN/m 2 Self Weight - 0.7kN/m 2

    Miscellaneous - 0.5kN/m 2

    Ceiling - 0.5kN/m 2

    Services - 1.0kN/m 2

    Partitions Walls - 2.5kN/m 2 Total 7.6kN/m 2

    Characteristic Variable Loads

    Category A; Areas for Domestic and Residential Activities

    Imposed Loads = 2.0kN/m 2

    Design LoadingFd = 1.35F k.perm + 1.5F k.varFd = (1.35*7.6) + (1.5*2.0)kN/m 2

    F d = 13.26kN/m2

    Fk.perm = 7.6kN/m 2

    F k.var = 2.0kN/m 2

    F d = 13.26kN/m 2

  • 8/11/2019 Structural Calculations

    18/54

    Determine Joist Spacing using Bending Criterion

    Mallow Mapplied

    Mallow = (1/y)*( f b.allow * I): y = 200mm; I = 308,333,333mm 4

    f b.allow = (1/ m) * kmod * kh* ksys * f m,k

    Where:

    f b.allow - Allowable Bending Stress f m,k - Characteristic Bending Stress kmod - Modification factor for Load Duration and Service Class kh - Modification factor for Member Size Effect ksys - Modification factor for System Strength = 1 .1

    m - Material Safety Factor = 1.3

    f b.allow = (0.769)*0.6 *1.1*14N/mm2

    = 7.106N/mm 2

    Mallow = 0.005mm-1 x 7.106N/mm 2 x 308,333,333mm 4

    M allow = 10,955,083Nmm (or 10.955kNm)

    Mapplied = (1/8)* *L2; L=3.2m Assume M applied = M allow;

    allow = Mallow x 8/L 2 allow = 10.955kNm x 8/(3.2m) 2

    allow = 8.559kN/m

    Let z = joist spacing centre to centre

    Fd (kN/m2)* z = allow (kN/m)

    13.26kN/m 2* z = 8.559kN/mz = 8.559/13.26

    z = 0.645m

    K mod = 0.6 for serviceclass 1, long termduration

    m = 1.3 for Timberand Timber products

    M al low = 9.959kNm

    allow = 7.7805kN/m

    To limit failure due tobending, placePlywebbed BoxJoists at a distanceless than 645mm c/capart.

  • 8/11/2019 Structural Calculations

    19/54

    Determine Joist Spacing using Shear Criterion

    Vallow Vapplied

    Vallow = (1/Q)*(2 * t * I * f v.allow ):

    Q = 879,800mm 3; I = 308,333,333mm 4; t = 12mm

    f v.allow = (1/ m) * kmod * ksys * f v,k

    Where:

    f b.allow - Allowable Bending Stress f m,k - Characteristic Bending Stress kmod - Modification factor for Load Duration and Service Class ksys - Modification factor for System Strength = 1 .1

    m - Material Safety Factor = 1.3

    f v.allow = 0.769* 0.6 *1.1 * 5N/mm 2 = 2.438N/mm 2

    Vallow = (1.13710-6)*(2 * 12 * 308,333,333 * 2.538)

    V allow = 21,347N (or 21.347kN)

    Vapplied = L/2; L=3.2m

    Assume V applied = V allow;

    Hence,

    allow = V allow * 2/L

    allow = 21.347kN * 2/3.2 allow = 13.342kN/m

    Let z = joist spacing centre to centre

    Fd (kN/m2)* z = allow (kN/m)

    13.26kN/m 2* z = 13.342kN/mz = 13.342/13.26

    z = 1.000m

    V al low = 21.347kN

    allow = 13.342kN/m

    To limit failure due toPanel shear, placePlywebbed BoxJoists at a distanceless than 1000mmc/c apart.

  • 8/11/2019 Structural Calculations

    20/54

    Determine Joist Spacing using Deflection Criterion

    allow loads

    allow = L/200

    allow = 3200mm/200

    allow = 16mm

    loads = [((5L4(1+k def,f )/384EI) + (L 2/8)((1+k def,w )/G w Aw))]

    Where:

    kdef,f - Deformation Factor for flange material kdef,w - Deformation Factor for web material E - Modulus of Elasticity for Transformed Section

    I - Second Moment of Area for transformed section

    Aw - Total Cross Section Area of the web Gw - Mean Shear Modulus of the web

    loads = [((5*32004(1+0.6)/384*7000*453,942,476) +

    (3200 2/8)((1+0.8)/578*12*400*2))]

    loads = (0.687 + 0.415) = 16

    = 14.519kN/m

    Let z = joist spacing centre to centre

    Fd (kN/m2)* z = allow (kN/m)

    13.26kN/m 2* z = 14.519kN/m

    z = 14.519/13.26

    z = 1.095mTo satisfyserviceabilityrequirements due todeflection, placePlywebbed BoxJoists at a distanceless than 1095mmc/c apart.

    Bending cr i te r ion go verns . Therefore , p lace Plywebbed Box Beams @ 600mm c/c

  • 8/11/2019 Structural Calculations

    21/54

  • 8/11/2019 Structural Calculations

    22/54

    BEAM 02

  • 8/11/2019 Structural Calculations

    23/54

  • 8/11/2019 Structural Calculations

    24/54

  • 8/11/2019 Structural Calculations

    25/54

    Project RESIDENTIAL HOUSE IN KYANJJA REINFORCED CONCRETE COUNCIL

    Client TONY SAKAZA Made by Date Page Location FIRST FLOOR, from grid 1 to 3 SNB 8-Sep-14 3

    CONTINUOUS BEAM (Analysis & Design) to BS 8110:1997 Checked Revision Job No

    Originated from RCC41.xls on CD 1999 BCA for RCC SNB - 1

    SPAN 1 LEFT CENTRE RIGHT ACTIONS M kNm 82.3 113.0 82.3

    b 0.70 1.60 0.70DESIGN d mm 327.0 343.0 327.0

    As mm 673 945 673 As' mm 351 164 351

    TOP STEEL Layer 1 3 T 16 2 T 12 3 T 16Layer 2 1 T 16 1 T 16

    As prov mm 804 As' prov 226 As prov 804BTM STEEL Layer 1 2 T 16 3 T 16 2 T 16

    Layer 2 2 T 16 As' prov mm 402 As prov 1005 As' prov 402

    DEFLECTION L/d 19.067 Allowed 28.109 SHEAR V kN 108.6 Link 108.6

    v N/mm 1.661 8 1.661

    vc N/mm 0.565 Nominal 0.565LINKS R8 @ 105 for 1575 R8 @ 125 R8 @ 105 for 1575

    legs No 2 2 2

    CHECKS % As ok ok okCover ok ok okmin S ok ok ok

    max S ok ok okLinks

    Main barsmax V ok ok

    Deflection ok

    SPAN 2 LEFT CENTRE RIGHT ACTIONS M kNm

    b 1.00 ~ 1.00DESIGN d mm -81.0 -45.5 -57.0

    As mm #DIV/0! #DIV/0! #DIV/0! As' mm #DIV/0! #DIV/0! #DIV/0!

    TOP STEEL Layer 1 #DIV/0! T 32 #DIV/0! T 25 #DIV/0! T 16#DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0!

    As prov mm #DIV/0! As' prov #DIV/0! As prov #DIV/0!BTM STEEL Layer 1 #DIV/0! T 25 #DIV/0! T 25 #DIV/0! T 16

    #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0! As' prov mm #DIV/0! As prov #DIV/0! As' prov #DIV/0!

    DEFLECTION L/d Allowed #DIV/0!SHEAR V kN #VALUE! Link #VALUE!

    v N/mm #VALUE! 8 #VALUE!vc N/mm #DIV/0! Nominal #DIV/0!

    LINKS #VALUE! #DIV/0! #VALUE!legs No 2 2 2

    CHECKS % As #DIV/0! #DIV/0! #DIV/0!Cover ok ok okmin S #DIV/0! #DIV/0! #DIV/0!

    max S #DIV/0! #DIV/0! #DIV/0!Links

    Main barsmax V #VALUE! #VALUE!

    Deflection #DIV/0!

    okok

    #DIV/0!#DIV/0!

    #DIV/0!#DIV/0!

    okok

    okok

    #DIV/0!#DIV/0!

  • 8/11/2019 Structural Calculations

    26/54

    BEAM 05

  • 8/11/2019 Structural Calculations

    27/54

    Project RESIDENTIAL HOUSE IN KYANJJA

    Client TONY SAKAZA Made by Date Sheet No Location FIRST FLOOR from grid 1 to 3 SNB 8-Sep-14 1

    CONTINUOUS BEAM (Analysis & Design) to BS 8110:1997 Checked Revision Job NoOriginated from RCC41.xls on CD 1999 BCA for RCC SNB - 1

    LOCATION Supports from grid 1 to grid 3

    MATERIALS COVERS (to all steel)fcu 25 N/mm h agg 20 mm Top cover 25 mmfyl 460 N/mm gs 1.05 Btm cover 25 mm

    fyv 250 N/mm gc 1.50 Side cover 25 mm

    SPANS L (m) H (mm) bw (mm) hf (mm) Type bf (mm) LOADING PATTERNSPAN 1 5.01 400 200 R 200 min maxSPAN 2 DEAD 1 1.4SPAN 3 IMPOSED 0 1.6

    SPAN 4 REBAR LAYERINGSPAN 5 Support steelSPAN 6 in alt layer ? Y

    SUPPORTS ABOVE (m) H (mm) B (mm) End Cond BELOW (m) H (mm) B (mm) End CondSupport 1 0.40 400 4550 F 0.40 400 4550 F

    Support 2 0.40 400 4550 F 0.40 400 4550 FSupport 3Support 4Support 5Support 6Support 7

    LOADING UDLs (kN/m) PLs (kN) Position (m)Dead Imposed Position Loaded Dead Imposed Position Loaded

    Span 1 Load Load from left Length Span 4 Load Load from left LengthUDL 20.2 2.0 ~~~~~ ~~~~~ UDL ~~~~~ ~~~~~PL 1 ~~~~~ PL 1 ~~~~~PL 2 ~~~~~ PL 2 ~~~~~

    Part UDL Part UDL

    Span 2 Span 5UDL ~~~~~ ~~~~~ UDL ~~~~~ ~~~~~PL 1 ~~~~~ PL 1 ~~~~~PL 2 ~~~~~ PL 2 ~~~~~

    Part UDL Part UDLSpan 3 Span 6

    UDL ~~~~~ ~~~~~ UDL ~~~~~ ~~~~~PL 1 ~~~~~ PL 1 ~~~~~PL 2 ~~~~~ PL 2 ~~~~~

    Part UDL Part UDL

    LOADING DIAGRAM

    1 3

    REACTIONS (kN)SUPPORT 1 2

    ALL SPANS LOADED 79.0 79.0ODD SPANS LOADED 79.0 79.0

    EVEN SPANS LOADED 50.7 50.7Characteristic Dead 50.7 50.7

    Characteristic Imposed 5.0 5.0

    REINFORCED CONCRETE

    COUNCIL

  • 8/11/2019 Structural Calculations

    28/54

    Project RESIDENTIAL HOUSE IN KYANJJA REINFORCED CONCRETE COUNCIL

    Client TONY SAKAZA Made by Date Page Location FIRST FLOOR, from grid 1 to 3 SNB 8-Sep-14 2

    CONTINUOUS BEAM (Analysis & Design) to BS 8110:1997 Checked Revision Job No

    Originated from RCC41.xls on CD 1999 BCA for RCC SNB - 1

    BENDING MOMENT DIAGRAMS (kNm)

    1 Elastic Moments 3 1 Redistributed Envelope 3

    SUPPORT No 1 2Elastic M 65.9 65.9 ~ ~ ~ ~ kNm/m

    Redistributed M 56.0 56.0 ~ ~ ~ ~ kNm/mb 0.850 0.850 ~ ~ ~ ~ ~Redistribution 15.0% 15.0%

    SPAN No 1Elastic M 33.04 ~ ~ ~ ~ ~

    Redistributed M 42.93 ~ ~ ~ ~ ~b 1.299 ~ ~ ~ ~ ~

    SHEARS (kN)

    1 Elastic Shears 3 1 Redistributed Shears 3

    SPAN No 1Elastic V 79.0 79.0 ~ ~ ~ ~

    Redistributed V 79.0 79.0 ~ ~ ~ ~

    Elastic V ~ ~ ~ ~ ~ ~

    Redistributed V ~ ~ ~ ~ ~ ~

    1 2 ALL SPANS Above 33.0 -33.0

    LOADED Below 33.0 -33.0ODD SPANS Above 33.0 -33.0

    LOADED Below 33.0 -33.0EVEN SPANS Above 21.1 -21.1

    LOADED Below 21.1 -21.1

    COLUMN MOMENTS(kNm)

    -100

    -80

    -60

    -40

    -200

    20

    40

    60

    80

    100

    0 1 2 3 4 5 6-100

    -80

    -60

    -40

    -200

    20

    40

    60

    80

    100

    0 1 2 3 4 5 6

    -40

    -20

    0

    20

    40

    60

    80

    0 1 2 3 4 5 6-60

    -40

    -20

    0

    20

    40

    60

    80

    0 1 2 3 4 5 6

  • 8/11/2019 Structural Calculations

    29/54

    Project RESIDENTIAL HOUSE IN KYANJJA REINFORCED CONCRETE COUNCIL

    Client TONY SAKAZA Made by Date Page Location FIRST FLOOR, from grid 1 to 3 SNB 8-Sep-14 3

    CONTINUOUS BEAM (Analysis & Design) to BS 8110:1997 Checked Revision Job No

    Originated from RCC41.xls on CD 1999 BCA for RCC SNB - 1

    SPAN 1 LEFT CENTRE RIGHT ACTIONS M kNm 40.9 42.9 40.9

    b 0.85 1.30 0.85DESIGN d mm 349.0 361.0 349.0

    As mm 291 295 291 As' mm

    TOP STEEL Layer 1 3 T 12 2 T 12 3 T 12Layer 2

    As prov mm 339 As' prov 226 As prov 339BTM STEEL Layer 1 2 T 12 3 T 12 2 T 12

    Layer 2 As' prov mm 226 As prov 339 As' prov 226

    DEFLECTION L/d 13.878 Allowed 40.967 SHEAR V kN 61.7 Link 61.7

    v N/mm 0.884 8 0.884

    vc N/mm 0.408 Nominal 0.408LINKS R8 @ 250 for 750 R8 @ 250 R8 @ 250 for 750

    legs No 2 2 2

    CHECKS % As ok ok okCover ok ok okmin S ok ok ok

    max S ok ok okLinks

    Main barsmax V ok ok

    Deflection ok

    SPAN 2 LEFT CENTRE RIGHT ACTIONS M kNm

    b 1.00 ~ 1.00DESIGN d mm -81.0 -45.5 -57.0

    As mm #DIV/0! #DIV/0! #DIV/0! As' mm #DIV/0! #DIV/0! #DIV/0!

    TOP STEEL Layer 1 #DIV/0! T 32 #DIV/0! T 25 #DIV/0! T 16#DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0!

    As prov mm #DIV/0! As' prov #DIV/0! As prov #DIV/0!BTM STEEL Layer 1 #DIV/0! T 25 #DIV/0! T 25 #DIV/0! T 16

    #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0! As' prov mm #DIV/0! As prov #DIV/0! As' prov #DIV/0!

    DEFLECTION L/d Allowed #DIV/0!SHEAR V kN #VALUE! Link #VALUE!

    v N/mm #VALUE! 8 #VALUE!vc N/mm #DIV/0! Nominal #DIV/0!

    LINKS #VALUE! #DIV/0! #VALUE!legs No 2 2 2

    CHECKS % As #DIV/0! #DIV/0! #DIV/0!Cover ok ok okmin S #DIV/0! #DIV/0! #DIV/0!

    max S #DIV/0! #DIV/0! #DIV/0!Links

    Main barsmax V #VALUE! #VALUE!

    Deflection #DIV/0!

    okok

    #DIV/0!#DIV/0!

    okok

    #DIV/0!#DIV/0!

    #DIV/0!#DIV/0!

    okok

  • 8/11/2019 Structural Calculations

    30/54

    BEAM 07

  • 8/11/2019 Structural Calculations

    31/54

    Project RESIDENTIAL HOUSE IN KYANJJA

    Client TONY SAKAZA Made by Date Sheet No Location FIRST FLOOR from grid 1 to 3 SNB 8-Sep-14 1

    CONTINUOUS BEAM (Analysis & Design) to BS 8110:1997 Checked Revision Job NoOriginated from RCC41.xls on CD 1999 BCA for RCC SNB - 1

    LOCATION Supports from grid 1 to grid 3

    MATERIALS COVERS (to all steel)fcu 25 N/mm h agg 20 mm Top cover 25 mmfyl 460 N/mm gs 1.05 Btm cover 25 mm

    fyv 250 N/mm gc 1.50 Side cover 25 mm

    SPANS L (m) H (mm) bw (mm) hf (mm) Type bf (mm) LOADING PATTERNSPAN 1 5.38 400 200 R 200 min maxSPAN 2 DEAD 1 1.4SPAN 3 IMPOSED 0 1.6

    SPAN 4 REBAR LAYERINGSPAN 5 Support steelSPAN 6 in alt layer ? Y

    SUPPORTS ABOVE (m) H (mm) B (mm) End Cond BELOW (m) H (mm) B (mm) End CondSupport 1 0.40 400 4550 F 0.40 400 4550 F

    Support 2 0.40 400 4550 F 0.40 400 4550 FSupport 3Support 4Support 5Support 6Support 7

    LOADING UDLs (kN/m) PLs (kN) Position (m)Dead Imposed Position Loaded Dead Imposed Position Loaded

    Span 1 Load Load from left Length Span 4 Load Load from left LengthUDL 11.1 2.0 ~~~~~ ~~~~~ UDL ~~~~~ ~~~~~PL 1 ~~~~~ PL 1 ~~~~~PL 2 ~~~~~ PL 2 ~~~~~

    Part UDL Part UDL

    Span 2 Span 5UDL ~~~~~ ~~~~~ UDL ~~~~~ ~~~~~PL 1 ~~~~~ PL 1 ~~~~~PL 2 ~~~~~ PL 2 ~~~~~

    Part UDL Part UDLSpan 3 Span 6

    UDL ~~~~~ ~~~~~ UDL ~~~~~ ~~~~~PL 1 ~~~~~ PL 1 ~~~~~PL 2 ~~~~~ PL 2 ~~~~~

    Part UDL Part UDL

    LOADING DIAGRAM

    1 3

    REACTIONS (kN)SUPPORT 1 2

    ALL SPANS LOADED 50.4 50.4ODD SPANS LOADED 50.4 50.4

    EVEN SPANS LOADED 29.9 29.9Characteristic Dead 29.9 29.9

    Characteristic Imposed 5.4 5.4

    REINFORCED CONCRETE

    COUNCIL

  • 8/11/2019 Structural Calculations

    32/54

  • 8/11/2019 Structural Calculations

    33/54

    Project RESIDENTIAL HOUSE IN KYANJJA REINFORCED CONCRETE COUNCIL

    Client TONY SAKAZA Made by Date Page Location FIRST FLOOR, from grid 1 to 3 SNB 8-Sep-14 3

    CONTINUOUS BEAM (Analysis & Design) to BS 8110:1997 Checked Revision Job No

    Originated from RCC41.xls on CD 1999 BCA for RCC SNB - 1

    SPAN 1 LEFT CENTRE RIGHT ACTIONS M kNm 32.6 29.4 32.6

    b 0.85 1.30 0.85DESIGN d mm 349.0 361.0 349.0

    As mm 228 196 228 As' mm

    TOP STEEL Layer 1 3 T 12 2 T 12 3 T 12Layer 2

    As prov mm 339 As' prov 226 As prov 339BTM STEEL Layer 1 2 T 12 2 T 12 2 T 12

    Layer 2 As' prov mm 226 As prov 226 As' prov 226

    DEFLECTION L/d 14.889 Allowed 47.478 SHEAR V kN 40.1 Link 40.1

    v N/mm 0.575 8 0.575

    vc N/mm 0.408 Nominal 0.408LINKS R8 @ 250 for 500 R8 @ 250 R8 @ 250 for 500

    legs No 2 2 2

    CHECKS % As ok ok okCover ok ok okmin S ok ok ok

    max S ok ok okLinks

    Main barsmax V ok ok

    Deflection ok

    SPAN 2 LEFT CENTRE RIGHT ACTIONS M kNm

    b 1.00 ~ 1.00DESIGN d mm -81.0 -45.5 -57.0

    As mm #DIV/0! #DIV/0! #DIV/0! As' mm #DIV/0! #DIV/0! #DIV/0!

    TOP STEEL Layer 1 #DIV/0! T 32 #DIV/0! T 25 #DIV/0! T 16#DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0!

    As prov mm #DIV/0! As' prov #DIV/0! As prov #DIV/0!BTM STEEL Layer 1 #DIV/0! T 25 #DIV/0! T 25 #DIV/0! T 16

    #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0! As' prov mm #DIV/0! As prov #DIV/0! As' prov #DIV/0!

    DEFLECTION L/d Allowed #DIV/0!SHEAR V kN #VALUE! Link #VALUE!

    v N/mm #VALUE! 8 #VALUE!vc N/mm #DIV/0! Nominal #DIV/0!

    LINKS #VALUE! #DIV/0! #VALUE!legs No 2 2 2

    CHECKS % As #DIV/0! #DIV/0! #DIV/0!Cover ok ok okmin S #DIV/0! #DIV/0! #DIV/0!

    max S #DIV/0! #DIV/0! #DIV/0!Links

    Main barsmax V #VALUE! #VALUE!

    Deflection #DIV/0!

    okok

    #DIV/0!#DIV/0!

    okok

    #DIV/0!#DIV/0!

    #DIV/0!#DIV/0!

    okok

  • 8/11/2019 Structural Calculations

    34/54

    BEAM 09

  • 8/11/2019 Structural Calculations

    35/54

    Project RESIDENTIAL HOUSE IN KYANJJA

    Client TONY SAKAZA Made by Date Sheet No Location FIRST FLOOR from grid 1 to 3 SNB 8-Sep-14 1

    CONTINUOUS BEAM (Analysis & Design) to BS 8110:1997 Checked Revision Job NoOriginated from RCC41.xls on CD 1999 BCA for RCC SNB - 1

    LOCATION Supports from grid 1 to grid 3

    MATERIALS COVERS (to all steel)fcu 25 N/mm h agg 20 mm Top cover 25 mmfyl 460 N/mm gs 1.05 Btm cover 25 mm

    fyv 250 N/mm gc 1.50 Side cover 25 mm

    SPANS L (m) H (mm) bw (mm) hf (mm) Type bf (mm) LOADING PATTERNSPAN 1 3.35 400 200 200 R 200 min maxSPAN 2 4.95 400 200 200 R 200 DEAD 1 1.4SPAN 3 4.55 400 200 200 R 200 IMPOSED 0 1

    SPAN 4 REBAR LAYERINGSPAN 5 Support steelSPAN 6 in alt layer ? Y

    SUPPORTS ABOVE (m) H (mm) B (mm) End Cond BELOW (m) H (mm) B (mm) End CondSupport 1 1.00 950 200 K

    Support 2 1.00 950 200 KSupport 3 1.00 950 200 KSupport 4 1.00 950 200 KSupport 5Support 6Support 7

    LOADING UDLs (kN/m) PLs (kN) Position (m)Dead Imposed Position Loaded Dead Imposed Position Loaded

    Span 1 Load Load from left Length Span 4 Load Load from left LengthUDL 2.8 ~~~~~ ~~~~~ UDL ~~~~~ ~~~~~PL 1 130.0 2.98 ~~~~~ PL 1 ~~~~~PL 2 ~~~~~ PL 2 ~~~~~

    Part UDL Part UDL

    Span 2 Span 5UDL 2.8 ~~~~~ ~~~~~ UDL ~~~~~ ~~~~~PL 1 130.0 3.08 ~~~~~ PL 1 ~~~~~PL 2 ~~~~~ PL 2 ~~~~~

    Part UDL Part UDLSpan 3 Span 6

    UDL 2.8 ~~~~~ ~~~~~ UDL ~~~~~ ~~~~~PL 1 130.0 1.53 ~~~~~ PL 1 ~~~~~PL 2 ~~~~~ PL 2 ~~~~~

    Part UDL Part UDL

    LOADING DIAGRAM

    1 3

    REACTIONS (kN)SUPPORT 1 2 3 4

    ALL SPANS LOADED 6.7 188.9 200.1 44.7ODD SPANS LOADED 6.7 141.9 111.6 44.7

    EVEN SPANS LOADED 0.3 61.5 106.9 2.8Characteristic Dead 4.6 11.7 13.4 6.3

    Characteristic Imposed 0.2 172.5 181.4 35.9

    REINFORCED CONCRETE

    COUNCIL

  • 8/11/2019 Structural Calculations

    36/54

  • 8/11/2019 Structural Calculations

    37/54

    Project RESIDENTIAL HOUSE IN KYANJJA REINFORCED CONCRETE COUNCIL

    Client TONY SAKAZA Made by Date Page Location FIRST FLOOR, from grid 1 to 3 SNB 8-Sep-14 3

    CONTINUOUS BEAM (Analysis & Design) to BS 8110:1997 Checked Revision Job No

    Originated from RCC41.xls on CD 1999 BCA for RCC SNB - 1

    SPAN 1 LEFT CENTRE RIGHT ACTIONS M kNm 7.6 5.4 18.2

    b 0.85 0.70 1.30DESIGN d mm 349.0 361.0 349.0

    As mm 52 36 125 As' mm

    TOP STEEL Layer 1 2 T 12 2 T 12 2 T 12Layer 2

    As prov mm 226 As' prov 226 As prov 226BTM STEEL Layer 1 2 T 12 2 T 12 2 T 12

    Layer 2 As' prov mm 226 As prov 226 As' prov 226

    DEFLECTION L/d 9.280 Allowed 56.917 SHEAR V kN 3.4 Link 133.2

    v N/mm 0.049 8 1.909

    vc N/mm 0.356 Nominal 0.356LINKS R8 @ 250 for 500 R8 @ 250 R8 @ 75 for 525

    legs No 2 2 2

    CHECKS % As ok ok okCover ok ok okmin S ok ok ok

    max S ok ok okLinks

    Main barsmax V ok ok

    Deflection ok

    SPAN 2 LEFT CENTRE RIGHT ACTIONS M kNm 30.7 87.7 41.2

    b 0.85 1.16 0.85DESIGN d mm 349.0 343.0 349.0

    As mm 213 738 294 As' mm

    TOP STEEL Layer 1 2 T 12 2 T 12 3 T 12Layer 2

    As prov mm 226 As' prov 226 As prov 339BTM STEEL Layer 1 2 T 16 3 T 16 2 T 16

    Layer 2 1 T 16 As' prov mm 402 As prov 804 As' prov 402

    DEFLECTION L/d 14.431 Allowed 27.829 SHEAR V kN 49.2 Link 93.8

    v N/mm 0.704 8 1.343vc N/mm 0.356 Nominal 0.408

    LINKS R8 @ 250 for 750 R8 @ 250 R8 @ 125 for 1500legs No 2 2 2

    CHECKS % As ok ok okCover ok ok okmin S ok ok ok

    max S ok ok okLinks

    Main barsmax V ok ok

    Deflection ok

    okok

    okok

    okok

    okok

    okok

    okok

  • 8/11/2019 Structural Calculations

    38/54

    Project RESIDENTIAL HOUSE IN KYANJJA REINFORCED CONCRETE COUNCIL

    Client TONY SAKAZA Made by Date Page Location FIRST FLOOR, from grid 1 to 3 SNB Sep-2014 4

    CONTINUOUS BEAM (Analysis & Design) to BS 8110:1997 Checked Revision Job No

    Originated from RCC41.xls on CD 1999 BCA for RCC SNB - 1

    SPAN 3 LEFT CENTRE RIGHT ACTIONS M kNm 38.3 66.3 30.2

    b 0.91 1.07 1.00DESIGN d mm 349.0 359.0 349.0

    As mm 271 485 210 As' mm

    TOP STEEL Layer 1 3 T 12 2 T 12 2 T 12Layer 2

    As prov mm 339 As' prov 226 As prov 226BTM STEEL Layer 1 2 T 16 3 T 16 2 T 16

    Layer 2 As' prov mm 402 As prov 603 As' prov 402

    DEFLECTION 12.674 Allowed 32.448 SHEAR V kN 99.9 Link V 41.5

    v N/mm 1.431 8 v 0.595vc N/mm 0.408 Nominal vc 0.356

    LINKS R8 @ 115 for 1150 R8 @ 250 R8 @ 250 for 750legs No 2 2 2

    CHECKS % As ok ok okCover ok ok okmin S ok ok ok

    max S ok ok okLinks

    Main barsmax V ok ok

    Deflection ok

    SPAN 4 LEFT CENTRE RIGHT ACTIONS M kNm

    b 1.00 ~ 1.00DESIGN d mm -53.0 -43.0 -59.0

    As mm #DIV/0! #DIV/0! #DIV/0! As' mm #DIV/0! #DIV/0! #DIV/0!

    TOP STEEL Layer 1 #DIV/0! T 12 #DIV/0! T 16 #DIV/0! T 16#DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0!

    As prov mm #DIV/0! As' prov #DIV/0! As prov #DIV/0!BTM STEEL Layer 1 #DIV/0! T 16 #DIV/0! T 16 #DIV/0! T 16

    #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0! As' prov mm #DIV/0! As prov #DIV/0! As' prov #DIV/0!

    DEFLECTION Allowed #DIV/0!SHEAR V kN #VALUE! Link #VALUE!

    v N/mm #VALUE! 10 #VALUE!vc N/mm #DIV/0! Nominal #DIV/0!

    LINKS #VALUE! #DIV/0! #VALUE!legs No 2 2 2

    CHECKS % As #DIV/0! #DIV/0! #DIV/0!Cover ok ok okmin S #DIV/0! #DIV/0! #DIV/0!

    max S #DIV/0! #DIV/0! #DIV/0!Links

    Main barsmax V #VALUE! #VALUE!

    Deflection #DIV/0!

    okok

    #DIV/0!#DIV/0!

    #DIV/0!#DIV/0!

    okok

    okok

    #DIV/0!#DIV/0!

  • 8/11/2019 Structural Calculations

    39/54

    BEAM 10

  • 8/11/2019 Structural Calculations

    40/54

    Project RESIDENTIAL HOUSE IN KYANJJA

    Client TONY SAKAZA Made by Date Sheet No Location FIRST FLOOR from grid 1 to 3 SNB 8-Sep-14 1

    CONTINUOUS BEAM (Analysis & Design) to BS 8110:1997 Checked Revision Job NoOriginated from RCC41.xls on CD 1999 BCA for RCC SNB - 1

    LOCATION Supports from grid 1 to grid 3

    MATERIALS COVERS (to all steel)fcu 25 N/mm h agg 20 mm Top cover 25 mmfyl 460 N/mm gs 1.05 Btm cover 25 mm

    fyv 250 N/mm gc 1.50 Side cover 25 mm

    SPANS L (m) H (mm) bw (mm) hf (mm) Type bf (mm) LOADING PATTERNSPAN 1 6.54 400 200 R 200 min maxSPAN 2 DEAD 1 1.4SPAN 3 IMPOSED 0 1.6

    SPAN 4 REBAR LAYERINGSPAN 5 Support steelSPAN 6 in alt layer ? Y

    SUPPORTS ABOVE (m) H (mm) B (mm) End Cond BELOW (m) H (mm) B (mm) End CondSupport 1 0.40 400 4550 F 0.40 400 4550 F

    Support 2 0.40 400 4550 F 0.40 400 4550 FSupport 3Support 4Support 5Support 6Support 7

    LOADING UDLs (kN/m) PLs (kN) Position (m)Dead Imposed Position Loaded Dead Imposed Position Loaded

    Span 1 Load Load from left Length Span 4 Load Load from left LengthUDL 26.0 2.0 ~~~~~ ~~~~~ UDL ~~~~~ ~~~~~PL 1 ~~~~~ PL 1 ~~~~~PL 2 ~~~~~ PL 2 ~~~~~

    Part UDL Part UDL

    Span 2 Span 5UDL ~~~~~ ~~~~~ UDL ~~~~~ ~~~~~PL 1 ~~~~~ PL 1 ~~~~~PL 2 ~~~~~ PL 2 ~~~~~

    Part UDL Part UDLSpan 3 Span 6

    UDL ~~~~~ ~~~~~ UDL ~~~~~ ~~~~~PL 1 ~~~~~ PL 1 ~~~~~PL 2 ~~~~~ PL 2 ~~~~~

    Part UDL Part UDL

    LOADING DIAGRAM

    1 3

    REACTIONS (kN)SUPPORT 1 2

    ALL SPANS LOADED 129.5 129.5ODD SPANS LOADED 129.5 129.5

    EVEN SPANS LOADED 85.0 85.0Characteristic Dead 85.0 85.0

    Characteristic Imposed 6.5 6.5

    REINFORCED CONCRETE

    COUNCIL

  • 8/11/2019 Structural Calculations

    41/54

  • 8/11/2019 Structural Calculations

    42/54

    Project RESIDENTIAL HOUSE IN KYANJJA REINFORCED CONCRETE COUNCIL

    Client TONY SAKAZA Made by Date Page Location FIRST FLOOR, from grid 1 to 3 SNB 8-Sep-14 3

    CONTINUOUS BEAM (Analysis & Design) to BS 8110:1997 Checked Revision Job No

    Originated from RCC41.xls on CD 1999 BCA for RCC SNB - 1

    SPAN 1 LEFT CENTRE RIGHT ACTIONS M kNm 82.3 113.0 82.3

    b 0.70 1.60 0.70DESIGN d mm 327.0 343.0 327.0

    As mm 673 945 673 As' mm 351 164 351

    TOP STEEL Layer 1 3 T 16 2 T 12 3 T 16Layer 2 1 T 16 1 T 16

    As prov mm 804 As' prov 226 As prov 804BTM STEEL Layer 1 2 T 16 3 T 16 2 T 16

    Layer 2 2 T 16 As' prov mm 402 As prov 1005 As' prov 402

    DEFLECTION L/d 19.067 Allowed 28.109 SHEAR V kN 108.6 Link 108.6

    v N/mm 1.661 8 1.661

    vc N/mm 0.565 Nominal 0.565LINKS R8 @ 105 for 1575 R8 @ 125 R8 @ 105 for 1575

    legs No 2 2 2

    CHECKS % As ok ok okCover ok ok okmin S ok ok ok

    max S ok ok okLinks

    Main barsmax V ok ok

    Deflection ok

    SPAN 2 LEFT CENTRE RIGHT ACTIONS M kNm

    b 1.00 ~ 1.00DESIGN d mm -81.0 -45.5 -57.0

    As mm #DIV/0! #DIV/0! #DIV/0! As' mm #DIV/0! #DIV/0! #DIV/0!

    TOP STEEL Layer 1 #DIV/0! T 32 #DIV/0! T 25 #DIV/0! T 16#DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0!

    As prov mm #DIV/0! As' prov #DIV/0! As prov #DIV/0!BTM STEEL Layer 1 #DIV/0! T 25 #DIV/0! T 25 #DIV/0! T 16

    #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0! As' prov mm #DIV/0! As prov #DIV/0! As' prov #DIV/0!

    DEFLECTION L/d Allowed #DIV/0!SHEAR V kN #VALUE! Link #VALUE!

    v N/mm #VALUE! 8 #VALUE!vc N/mm #DIV/0! Nominal #DIV/0!

    LINKS #VALUE! #DIV/0! #VALUE!legs No 2 2 2

    CHECKS % As #DIV/0! #DIV/0! #DIV/0!Cover ok ok okmin S #DIV/0! #DIV/0! #DIV/0!

    max S #DIV/0! #DIV/0! #DIV/0!Links

    Main barsmax V #VALUE! #VALUE!

    Deflection #DIV/0!

    okok

    #DIV/0!#DIV/0!

    #DIV/0!#DIV/0!

    okok

    okok

    #DIV/0!#DIV/0!

  • 8/11/2019 Structural Calculations

    43/54

    BEAM 11

  • 8/11/2019 Structural Calculations

    44/54

  • 8/11/2019 Structural Calculations

    45/54

  • 8/11/2019 Structural Calculations

    46/54

    Project RESIDENTIAL HOUSE IN KYANJJA REINFORCED CONCRETE COUNCIL

    Client TONY SAKAZA Made by Date Page Location FIRST FLOOR, from grid 1 to 3 SNB 8-Sep-14 3

    CONTINUOUS BEAM (Analysis & Design) to BS 8110:1997 Checked Revision Job No

    Originated from RCC41.xls on CD 1999 BCA for RCC SNB - 1

    SPAN 1 LEFT CENTRE RIGHT ACTIONS M kNm 1.0 1.8 2.0

    b 0.85 1.00 1.15DESIGN d mm 349.0 361.0 349.0

    As mm 7 12 14 As' mm

    TOP STEEL Layer 1 2 T 12 2 T 12 2 T 12Layer 2

    As prov mm 226 As' prov 226 As prov 226BTM STEEL Layer 1 2 T 12 2 T 12 2 T 12

    Layer 2 As' prov mm 226 As prov 226 As' prov 226

    DEFLECTION L/d 4.515 Allowed 56.917 SHEAR V kN 3.6 Link 5.4

    v N/mm 0.051 8 0.078

    vc N/mm 0.356 Nominal 0.356LINKS R8 @ 250 for 500 R8 @ 250 R8 @ 250 for 500

    legs No 2 2 2

    CHECKS % As ok ok okCover ok ok okmin S ok ok ok

    max S ok ok okLinks

    Main barsmax V ok ok

    Deflection ok

    SPAN 2 LEFT CENTRE RIGHT ACTIONS M kNm 39.1 39.7 39.2

    b 0.85 1.30 0.85DESIGN d mm 349.0 361.0 349.0

    As mm 277 271 278 As' mm

    TOP STEEL Layer 1 3 T 12 2 T 12 3 T 12Layer 2

    As prov mm 339 As' prov 226 As prov 339BTM STEEL Layer 1 2 T 12 3 T 12 2 T 12

    Layer 2 As' prov mm 226 As prov 339 As' prov 226

    DEFLECTION L/d 15.374 Allowed 43.895 SHEAR V kN 52.9 Link 52.9

    v N/mm 0.758 8 0.758vc N/mm 0.408 Nominal 0.408

    LINKS R8 @ 250 for 500 R8 @ 250 R8 @ 250 for 500legs No 2 2 2

    CHECKS % As ok ok okCover ok ok okmin S ok ok ok

    max S ok ok okLinks

    Main barsmax V ok ok

    Deflection ok

    okok

    okok

    okok

    okok

    okok

    okok

  • 8/11/2019 Structural Calculations

    47/54

    Project RESIDENTIAL HOUSE IN KYANJJA REINFORCED CONCRETE COUNCIL

    Client TONY SAKAZA Made by Date Page Location FIRST FLOOR, from grid 1 to 3 SNB Sep-2014 4

    CONTINUOUS BEAM (Analysis & Design) to BS 8110:1997 Checked Revision Job No

    Originated from RCC41.xls on CD 1999 BCA for RCC SNB - 1

    SPAN 3 LEFT CENTRE RIGHT ACTIONS M kNm 27.9 13.2 23.5

    b 1.15 0.85 1.00DESIGN d mm 349.0 361.0 349.0

    As mm 193 88 162 As' mm

    TOP STEEL Layer 1 2 T 12 2 T 12 2 T 12Layer 2

    As prov mm 226 As' prov 226 As prov 226BTM STEEL Layer 1 2 T 12 2 T 12 2 T 12

    Layer 2 As' prov mm 226 As prov 226 As' prov 226

    DEFLECTION 13.019 Allowed 56.917 SHEAR V kN 31.3 Link V 29.2

    v N/mm 0.448 8 v 0.419

    vc N/mm 0.356 Nominal vc 0.356LINKS R8 @ 250 for 500 R8 @ 250 R8 @ 250 for 500

    legs No 2 2 2

    CHECKS % As ok ok okCover ok ok okmin S ok ok ok

    max S ok ok okLinks

    Main barsmax V ok ok

    Deflection ok

    okok

    okok

    okok

  • 8/11/2019 Structural Calculations

    48/54

    REFERENCE PARTICULARS OUTPUT

    BS 5628; Part 11978

    PROPOSED SAKAZA'S RESIDENCE IN KUNGU

    DESIGN OF LOAD BEARING MASONRY WALLS

    Assume a 200mm thick wall

  • 8/11/2019 Structural Calculations

    49/54

    REFERENCE PARTICULARS OUTPUT

    Loading (per m-run of wall);

    Load from: DLkN/m

    LLkN/m

    1. Roof Trusses 2.2 4.3

    2. Ring Beams 5.63. Wall from ringbeam to 1 s floor 11.44. Concrete Beams on 1 st Floor 9.35. Timber Beams on 1 s Floor 11.4 36. Wall from 1 st floor to GL 11.4

    Total 51.3 7.3

    Slenderness ratio;

    Since there are no intersecting walls, the effective height of the wall will govern theslenderness ratio.

    Vertical Design Strength f d ;

    Where;

    Critically loaded wall is 600mm Length

    Design Philosophy;

    Thus;

    From which

  • 8/11/2019 Structural Calculations

    50/54

  • 8/11/2019 Structural Calculations

    51/54

    REFERENCE PARTICULARS OUTPUT

    PROPOSED SAKAZA'S RESIDENCE IN KUNGU

    DESIGN OF THE STRIP FOOTINGS

    Loading (kN/m run) Characteristic Permanent Loads

    Slab : 7.6kN/m 2 * 3.2m = 24.32kN/m

    Concrete Beam: 25kN/m 3 * 0.2m*0.4m = 2.00kN/m

    Masonry Walling: 22kN/m 3 * 8.2m*0.2m = 36.08kN/m

    Roofing (Assumed) 2.5kN/m 2 * 3.2m = 8.00kN/m

    Total Dead Load = 70.4kN/m

    Characteristic Variable Load

    Single Family Dwellings : = 2.00kN/m2

    Maximum TributaryLength = 3.2m

    UDL variable load 2kN/m2 * 3.2m = 6.4kN/m

    Sizing of Strip Width (B)

    From Geotechnical Investigation Report, at 900mm depthTest Pit 1 Test pit 2 Average

    Cohesion, C (kN/mm 2) 39 36 37.5Angle of Friction, (degrees) 19 24 22

    Bulk Density, (kN/m3

    )17.99 18.15 18.07

    Using Terzaghi's Bearing Capacity Equations for strip Footings;

    B

  • 8/11/2019 Structural Calculations

    52/54

  • 8/11/2019 Structural Calculations

    53/54

    REFERENCE PARTICULARS OUTPUT

    54.4kN

    54.4kN

    108.8kN

    0.6m

    181.333kN/m

  • 8/11/2019 Structural Calculations

    54/54

    REFERENCE PARTICULARS OUTPUT Assume R6 bars at a spacing S

    For a 1-m run;

    Hence Provide R8 at 200mm centre to centre