Summary of MEP Equipment serving the Raised Floor Computer Room. The 825sf raised floor computer room in suite 100 is equipped with an Uninterruptible Power Supply (UPS) backed up by a diesel generator with two fully redundant transfer switches, distribution boards and APC racks with in-row cooling utilizing two (2) redundant 30 Ton Carrier Air-Cooled Chillers. The computer room is protected above and below floor by a FM200 fire suppression system, backed up by a pre-action dry pipe sprinkler system. The generator is a 300KW Cummings Diesel Generator with a 400A 3P 480V output circuit breaker; a 300 Gallon belly tank (for a run time of approximately 13.75 hours at full load) and Remote Annunciator. Nameplate System Display Engine Block Remote Announcitor (In Computer Room) Snip from fuel consumption chart

Upload: others

Post on 08-Jan-2022

4 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Summary of MEP Equipment serving the Raised Floor Computer

Summary of MEP Equipment

serving the

Raised Floor Computer Room.

The 825sf raised floor computer room in suite 100 is equipped with an Uninterruptible Power

Supply (UPS) backed up by a diesel generator with two fully redundant transfer switches,

distribution boards and APC racks with in-row cooling utilizing two (2) redundant 30 Ton Carrier

Air-Cooled Chillers. The computer room is protected above and below floor by a FM200 fire

suppression system, backed up by a pre-action dry pipe sprinkler system.

The generator is a 300KW Cummings Diesel Generator with a 400A 3P 480V output circuit

breaker; a 300 Gallon belly tank (for a run time of approximately 13.75 hours at full load) and

Remote Annunciator.

Nameplate System Display

Engine Block Remote Announcitor

(In Computer Room)

Snip from fuel consumption chart

Page 2: Summary of MEP Equipment serving the Raised Floor Computer

The generator feeds a Generator distribution panel with two (2) 400A/3P Breakers feeding two

(2) 400A Automatic Transfer Switches (one Cummings and one Cutler Hammer). Each of these

feeds a 400A distribution board with Current Technology TG100 TVSS feeding a PDU, Chiller,

and 277/480V Lighting and Appliance Panelboard, Transformer and 120/208V Lighting and

Appliance Panelboard.

Generator Distribution Board ATS/Distribution #1 ATS/Distribution #2

ATS#1 Distribution Board #1

ATS#2 Distribution Board #2

TVSS (Typical Both Systems)

Page 3: Summary of MEP Equipment serving the Raised Floor Computer

The UPS is an APC Symmetra 75KW N+1 unit that was completely overhauled in 2017. Feeding

the two (2) MGE Power Management Modules Power Distribution units (PDU) PDUs Input:

480V,150A,60Hz,3Ph,3W+GND and Output: 208V,347A,60Hz,3Ph,4W+GND

UPS Lineup UPS Display

PDU PDU Distribution

PDU Nameplate PDU Display

Page 4: Summary of MEP Equipment serving the Raised Floor Computer

Each PDUs feeds a row of six (6) APC Computer Cabinets with In-row Cooling which remain (Air Cooled

Chillers on Roof) as well as the open frame racks which remain within the raised floor computer room:

Computer Cabinet Lineup In-Row Cooling Display

Carrier Chillers on Roof Chiller Nameplate (Typical Both)

Typical Open Racks Typical Open Racks

Page 5: Summary of MEP Equipment serving the Raised Floor Computer

The Computer room is protected above and below floor by a FM200 Fire Suppression system

backed up by a Dry Pipe Pre-action Sprinkler System:

Control Panel, Abort/Manual Release

Buttons, Alarm strobe and

Generator Remote Announciator

FM 200 Bottles FM200 Control Panel

Preaction System Piping Air Compressor

Control Panel