Super Solution

www.lsis.biz

Vacuum Circuit Breakers

Page 2: Super Solution Vacuum Circuit Breakers - LSIS

Contents

�Rating 03

�Structure 04

�Accessories 04

�Dimensions 05

�Control circuit diagram 08

�Rating 09

�Structure 10

�Accessories 10

�Dimensions 11

�Control circuit diagram 21

�Ordering information 22

15kV VCB (WAPDA)

17.5kV VCB

Page 3: Super Solution Vacuum Circuit Breakers - LSIS

I3

15 kV VCB (WAPDA/NTDC)

Rating

●Rating: 15kV 25kA 630/2500A

●Rated breaking time: 3 cycle

●Rated short-circuit withstand characteristics: 3sec/4sec

●Rated operating sequence: O-0.3s-CO-3min-CO

●CB Compartment available for MCSG

●Control voltage- DC 24~30V, DC 48~60V, DC110V, DC125V, DC220V

- AC 48V, AC100~130V, AC220~250V

●Various accessories- VCB part: Charge switch, UVT, Coil, CTC, Locking Magnet, Plug

Interlock, Lead wire, Low Energy Trip Device Keylock,

Button Cover, Button Padlock, Padlock (H type Door

interlock)

- Cradle part: Temperature Sensor, Earthing s/w & Accessary, Door,

Door Interlock, Door Emergency Button

- Others: Draw-in/out handle, UVT Time Delay Controller,

CTD(Condensor Trip Device), TM

●TEST/SERVICE Automatic Position Indicator

●Standard- CESI Approval [IEC 62271-100/WAPDA/NTDC Standard]

Edited by Foxit ReaderCopyrightⓒ by Foxit Corporation, 2005-2010For Evaluation Only.

Type

Rated voltage Ur (kV)

Rated normal current Ir (A)

Rated frequency fr (Hz)

Rated short-circuit current Isc(kA)

Rated short-time withstand current Ik/tk(kA/s)

Rated short-circuit breaking capacity (MVA)

Rated short-circuit making current Ip (kA)

Rated breaking time (cycle)

Rated withstand Power frequency Ud (kV)

voltage Impulse (1.2×50㎲) Up (kV)

Rated operating sequence

Control voltage Closing coil (V)

Trip coil (V)

Auxiliary contact

Rated opening time (sec)

No-load closing time (sec)

Type test Mechanical

Electrical

Capacitive current switching

Installation Fixed

Draw-out

Phase distance (mm)

Weight Breaker (kg)

Cradle (kg)

Standards

VL-15� 25�06,25

15

630 2500

50

25

25/3(4)*

650

63

3

36

95

O-0.3s-CO-3min-CO

DC 24~30V, DC 48~60V, DC 110V, DC 125V, DC 220V, AC 48V, AC 100~130V, AC 220~250V

DC 24~30V, DC 48~60V, DC 110V, DC 125V, DC 220V, AC 48V, AC 100~130V, AC 220~250V

4a4b, 10a10b

≤ 0.04

≤ 0.06

M2

E2, short circuit life cycle (WAPDA Standard)

C2 (including Single Capacitor)

-

H type (for MCSG)

210 230

125 210

215 255

IEC 62271-100/WAPDA/NTDC Standard

* 4 sec in rated short-time withstand current is possible.

Page 4: Super Solution Vacuum Circuit Breakers - LSIS

4II

Structure

Accessories

Susol series offer various accessories which areproviding simple installation.

VCB Part� Motor (M),

Charge Switch� Closing coil (CC)� Trip coil (TC/TC1)� Counter (C)� Auxiliary conatct (SA)

� Under voltage trip (UVT)� Key lock� Button Padlock� Button Cover� Position Switch� Handle for draw-in and out

� UVT time delay controller� Condenser Trip device (CTD)� Padlock(H type Door Interlock)� Locking Magnet� Plug Interlock� Low Energy Trip Device

CB Compartment Part� Temperature sensor�Door�Door Interlock� Shutter Padlock� Emergency ON/OFF Button

� Earthing s/w & AccessaryKey lock - Earthing s/wLocking Magnet - Earthing s/wPosition s/w - Earthing s/w

� TM(Temperature Monitoring Unit)

Breaker� Insulation rod

� Lower terminal

� Shunt

� Vacuum interrupter

� Upper terminal

� Heat sink

� Tulip contactor

Vacuum Interrupter, VIThe internal components of a typical Vacuum Interrupter are shown in the Fig.

LS Vacuum Interrupter consists of a ceramic insulator, two end plates, arc shield,

bellows, a movable and fixed electrode, and contact set.

The ambient gas pressure within the evacuated tube is approximately 5x10-5 torr.

Fixed electrode

Fixed seal cup

Ceramic

Fixed shield

Contacts

Bellows shield

Bellows

Movable seal cup

Arc shield

Breaker (VI)

Page 5: Super Solution Vacuum Circuit Breakers - LSIS

II5

Dimensions

��15kV, 25kA, 630A, WAPDAWithdrawable (H type unit, phase distance 210mm)

��15kV, 25kA, 2500A, WAPDAWithdrawable (H type unit, phase distance 230mm)

636

640

359.

5

65313

770

53

320 25

383469

358

328

340

76

756

306 Stroke:22064

7594

165

19.54

21.5

210210

10

58

350

310

756

320

46953 383

358

76

301

165

25

230 230790

786

80313

770

361.

5 606

642

90

19.5

21.54

Stroke:220

Page 6: Super Solution Vacuum Circuit Breakers - LSIS

6II

Dimensions

��15kV, 25kA, 630A, WAPDAWithdrawable (H cradle, phase distance 210mm)

26

20

63.4

(Mounting hole)12- 11 (Mounting hole)

6- 11

(Mounting hole)

Tube

8- 11

2- 12

2- 1

2

2-

12

37.5

400

400

212.

5

(Mounting hole)

(Mounting hole)

42.3317

400

400

340

513

212.

5

323.4

725

650

1017.7187.7

210

710

210

10

700.

4

750

1230

65

83.320

5

50

83.3

( 34)

285 150 150 262.7

750

2-M8(DP:18)

14

4- 14

14

2-M 10

(For assembly oflifting hook and LVcompartmentmounting hole)

See Detail A

Detail A

Detail A

Connecting busbar method (with earthing switch)Busbar : 5t×60 (1 sheets) <630A>

Page 7: Super Solution Vacuum Circuit Breakers - LSIS

II7

��15kV, 25kA, 2500A, WAPDAWithdrawable (H cradle, phase distance 230mm)

37.5

4-M12(DP:18)42.3

199.27251016.2

35

860850

65

20

35

71.320

2-M8(DP:18)

71.3

285 150 150 274.2

900

230

23085

0.4

1230

400 45

5

310

535

455

400

900

45

63.4

35(3

0)

10

212.

5

212.

5

See Detail A Detail A

Detail A

14

317 323.4

1112-

89

35

116-(Mounting hole)

118-

122-144-

(Mounting hole)

(Mounting hole)

(Mounting hole)

14(Mounting hole)

(For assembly oflifting hook and LVcompartmentmounting hole)

TUBE

Connecting busbar method (with earthing switch)Busbar : 10t×100 (2 sheets) <2500A>

Page 8: Super Solution Vacuum Circuit Breakers - LSIS

8II

Control circuit diagram

LS

7LS

5LS

4

21

4*

3*

7*

LS

6 8*

65

Po

sitio

n s

witc

h

<1

a1

b(T

ES

T),

1a

1b

(SE

RV

ICE

)>

LS

7LS

5LS

4

21

4*

3*

7*

LS

6 8*

6*5*

Posi

tion s

witc

h<

1a1b(T

ES

T),

2b(S

ER

VIC

E)>

55A6

47

56

58

57

70

59

87

25

3426

23 49

60

61

24

48

22

40

38

74

753941

72

73

10

9

37

36

29

28

71

27

51

53

54

52

50

65

43

21

46

45

A5

A4

44

43

A3

A2

42A1

13

14

D1

D212

11

A6

87

25

3426

23

24

22

38

39

10

9

37

36

29

28

27

51

53

52

50

65

43

21

A5

A4

A3

A2

A1

15

16

D1

D212

111

31

41

51

6

16

15

14

13

12

11

10

9

8

7

6

5

4

3

2

116

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

A B C D

A B C D

<C

onn

ecto

r Te

rmin

al C

onf

igur

atio

n>

A t

ype

B t

ype

LS

7

22

23

A2

10

M

MOTOR POWER SOURCE

N

TRIP POWER SOURCE

A6

52a

N

CLOSE POWER SOURCE

A4

N1

2

A1

9

P

A5

P

11A

3

P

39

37

51

25

27

41

29

43

LS

5

24

LS

4

21

43

68

7L

S6 8

65

53

57

55

50

34

36

384

b

42

40

26

28

24

10

a

4a

57

31

TE

ST

SE

RV

ICE

54

56

52

Clo

sing

Sp

ring

Co

ntac

t(C

harg

e co

mp

lete

ind

icat

ing

co

ntac

t)

14

D1

D2

13

45

49

47

61

60

48

44

46

59

71

75

73

58

72

74

70

10

b

C

UV

TT

C1

TC

52a

CS

LS

2

LOCKING MAGNET POWER SOURCE

NP

LM

16

15

22

42

40

26

28

24

60

48

44

46

23

25

27

41

29

43

45

49

47

61

50

34

36

38

54

56

52

58

72

74

70

39

37

51

53

57

55

59

71

75

73

35

Posi

tion

switc

h <2

a(TE

ST),2

a(SE

RVI

CE)

>

Se

con

da

ry t

rip

co

il w

ith T

CM

Co

nta

ct

(9a

)(9

b)

Auxi

liary

sw

itch

Trip c

oil

monito

ring c

onta

ct

Cur

rent

Trip

Coi

l(1A

,5A

) ind

icat

ing

cont

act

CT

C2

Not

e1)

Not

e3)

Not

e4)

Not

e4)

Not

e4)

Not

e5)

Not

e2)

Not

e) 1

. CTC

2 : C

urre

nt T

rip C

oil(1

A,5

A) (

Term

inal

NO

: 13

,14)

2. P

ositi

on S

/W -

TES

T 2a

, SE

RV

ICE

2a(

Term

inal

No.

1, 2

, 3, 4

, 5, 6

, 7, 8

)- T

ES

T po

sitio

n 1a

1b, S

ER

VIC

E p

ositi

on 1

a1b/

2b a

re a

vaila

ble.

(*

mar

ked

cont

act i

s b

cont

act.)

3. U

VT

- Und

er V

olta

ge T

rip (T

erm

inal

No.

D1,

D2)

4. T

C1

- Sec

onda

ry T

rip C

oil (

Term

inal

No.

11,

12)

In c

ase

TC1

is s

elec

ted

and

auxi

liary

sw

itch

is 1

0a10

b, S

ome

'a' c

onta

ct.

(Ter

min

al N

o.: 4

0,41

) and

'b' c

onta

ct(T

erm

inal

No.

:54,

55)

are

not

ava

ilabl

e.5.

Sec

onda

ry T

rip C

oil M

onito

ring

Con

tact

(Ter

min

al N

O.:3

6)In

cas

e S

econ

dary

Trip

Coi

l TC

M C

onta

ct is

sel

ecte

d an

d au

xilia

ry s

witc

h is

9a8

b, S

ome

'a' c

onta

ct(T

erm

inal

No.

: 40,

41) a

nd 'b

' con

tact

(Ter

min

al N

o.:3

6, 3

7) a

re n

ot a

vaila

ble.

6. C

TC -

Cur

rent

Trip

Coi

l (Te

rmin

al N

o.: A

5,A

6)C

TC1

- Sec

onda

ry C

urre

nt T

rip C

oil (

Term

inal

No.

: 11,

12)

CTC

2 - C

urre

nt T

rip C

oil (

Term

inal

No.

: 13,

14)

CTC

3 - C

urre

nt T

rip C

oil (

Term

inal

No.

: D1,

D2)

7. L

ET

- Low

Ene

rgy

Trip

Dev

ice

(Ter

min

al N

o.: 1

3,14

)8.

LM

- Lo

ckin

g M

agen

t (Te

rmin

al N

o.:1

5, 1

6), I

n ca

se o

f B ty

pe c

onne

ctor

is a

vaila

ble

9. C

lose

and

Trip

coi

l is

One

Pul

se ty

pe, e

xclu

ding

Trip

coi

l (D

C11

0, 2

20V

)10

. In

abov

e op

tiona

l acc

esso

ries,

UV

T,C

TC a

nd T

C1

can

not b

e se

lect

ed s

imul

tane

ousl

y.11

. Abo

ve c

ircui

t dia

gram

is b

ased

on

"OFF

" sta

te o

f VC

B a

nd c

losi

ng s

prin

g is

cha

rged

.

Opt

ion

∅: E

xter

nal t

erm

inal

of V

CB

52 :

Vac

uum

circ

uit b

reak

erM

: S

prin

g ch

argi

ng m

otor

TC :

Trip

coi

l(SH

T)TC

1 : S

econ

dary

Trip

coi

l(SH

T1)

C

: Clo

sing

coil(

CC

)U

VT :

Und

er V

olta

ge T

rip52

a : A

uxilia

ry s

witc

h (N

O)

52b

: Aux

iliary

sw

itch

(NC

)LS

2 :

Mot

or s

top

limit

switc

hC

TC :

Cur

rent

Trip

coi

l(3A)

CTC

1 : S

econ

dary

Cur

rent

Trip

coi

l(3A)

CTC

2 : C

urre

nt T

rip c

oil(1

A,5A

)C

TC3

: Cur

rent

Trip

coi

l(1A,

5A)

LET

: Low

Ene

rgy

Trip

Dev

ice(2

5mJ,

100m

J)C

S :

Clo

sing

sprin

g ch

arge

d in

dica

tion

limit

switc

hLS

4, L

S5 :

Posit

ion

S/W

(TES

T po

sitio

n)LS

6, L

S7 :

Posit

ion

S/W

(SER

VIC

E po

sitio

n)

LM :

Lock

ing

mag

net(o

nly

with

draw

able

type

)

CT

C213

D1

14D

2

CT

C3

S/W

TE

ST

: 1a

1bT

ES

T :

2aT

ES

T :

1a1b

No.

SE

RV

ICE

: 2b

SE

RV

ICE

: 2a

SE

RV

ICE

: 1a

1bA

3 A

4 A

5LS

4 C

lose

at T

ES

T p

ositi

on

Clo

se a

t TE

ST

pos

ition

C

lose

at T

ES

T p

ositi

on

LS5

OP

EN

at T

ES

T p

ositi

on

Clo

se a

t TE

ST

pos

ition

O

PE

N a

t TE

ST

pos

ition

LS6

OP

EN

at S

ER

VIC

E p

ositi

onC

lose

at S

ER

VIC

E p

ositi

onC

lose

at S

ER

VIC

E p

ositi

onLS

7 O

PE

N a

t SE

RV

ICE

pos

ition

C

lose

at S

ER

VIC

E p

ositi

on

OP

EN

at S

ER

VIC

E p

ositi

on

Page 9: Super Solution Vacuum Circuit Breakers - LSIS

II9

Rating

●Rating: 17.5kV 20/25kA 630/1250/2000A

●Rated breaking time: 3 cycle

●Rated short-circuit withstand characteristics: 3sec/4sec

●●Rated operating sequence: O-0.3s-CO-15s-CO

●●Type test level: M2, E2(List3), C2

●●Various cradle type: E, F and H type

●●CB Compartment available (Box type cradle) for MCSG

●●Control voltage- DC 24~30V, DC 48~60V, DC 110V, DC 125V, DC 220V- AC 48V, AC 100~130V, AC 220~250V

●●Various accessories- VCB part: Charge switch, UVT, Second Latch Checking switch,Position switch, Locking magnet, Plug interlock, Key lock, Button cover,Button padlock, Padlock(H type Door interlock), MOC

- Cradle part: MOC(Mechanical Operating Cell switch), TOC(TruckOperating Cell switch), Temperature sensor, Earthing switch &accessaries, Door, Door interlock, Door emergency button

- Others: Draw-in/out handle, UVT Time delay controller,CTD(Condensor Trip Device), Temperature module

●●Draw-in/out indication

●●Standard and certification- IEC 62271-100 [M2, C2, E2(List3)]- KEMA & KERI certified

Type

Rated voltage Ur (kV)

Rated normal current Ir (A)

Rated frequency fr (Hz)

Rated short-circuit current Isc(kA)

Rated short-time withstand current Ik/tk(kA/s)

Rated short-circuit breaking capacity (MVA)

Rated short-circuit making current Ip (kA)

Rated breaking time (cycle)

Rated withstand Power frequency Ud (kV)

voltage Impulse (1.2×50㎲) Up (kV)

Rated operating sequence

Control voltage Closing coil (V)

Trip coil (V)

Auxiliary contact

Rated opening time (sec)

No-load closing time (sec)

Type test Mechanical

Electrical

Capacitive current switching

Installation Fixed

Draw-out

Phase distance * (mm)

Weight Breaker (kg)

Cradle (kg)

Standards

VL-17� 20/25�06/13/20

17.5

630 1250 2000

50/60

20/25

20/3, 25/3

600/750

2.5*lsc(50Hz)/2.6*lsc(60Hz)

3

38

95

O-0.3s-CO-15s-CO

DC 24~30V, DC 48~60V, DC 110V, DC 125V, DC 220V, AC 48V, AC 100~130V, AC 220~250V

DC 24~30V, DC 48~60V, DC 110V, DC 125V, DC 220V, AC 48V, AC 100~130V, AC 220~250V

4a4b, 10a10b

≤ 0.04

≤ 0.06

M2

E2 (List3)

C2 (including Single Capacitor)

P type

E, F type (for MESG), H type (for MCSG)

150 (210)

115 (120) 115 (120) 130 (140)

170 (200) 170 (200) 180 (200)

IEC 62271-100

* ( ) displays option of phase distance.

17.5kV VCB Edited by Foxit ReaderCopyrightⓒ by Foxit Corporation, 2005-2010For Evaluation Only.

Page 10: Super Solution Vacuum Circuit Breakers - LSIS

10II

Structure

Accessories

Susol series offer various accessories which areproviding simple installation.

Breaker� Insulation rod

� Lower terminal

� Shunt

� Vacuum interrupter

� Upper terminal

� Heat sink (over 2000A)

� Tulip contactor

Vacuum Interrupter, VIThe internal components of a typical Vacuum Interrupter are shown in the Fig.

LS Vacuum Interrupter consists of a ceramic insulator, two end plates, arc shield,

bellows, a movable and fixed electrode, and contact set.

The ambient gas pressure within the evacuated tube is approximately 5x10-5 torr.

Fixed electrode

Fixed seal cup

Ceramic

Fixed shield

Contacts

Bellows shield

Bellows

Movable seal cup

��

Arc shield

Breaker (VI)

VCB Part� Motor (M),

Charge Switch� Closing coil (CC)� Trip coil (TC/TC1)� Counter (C)� Auxiliary conatct (SA)

� Under voltage trip (UVT)� Key lock� Button Padlock� Button Cover� Position Switch� Handle for draw-in and out

� UVT time delay controller� Condenser Trip device (CTD)� MOC� Padlock(H type Door Interlock)� Locking Magnet� Plug Interlock

CB Compartment Part� TOC (Truck Operating Cell s/w)�MOC (Mechanical Operating Cell s/w)� Temperature sensor�Door�Door Interlock� Shutter Padlock

� Emergency ON/OFF Button� Earthing s/w & Accessary

Key lock - Earthing s/wLocking Magnet - Earthing s/wPosition s/w - Earthing s/w

� TM(Temperature Monitoring Unit)

Page 11: Super Solution Vacuum Circuit Breakers - LSIS

II11

Dimensions

��17.5kV, 20/25kA, 630/1250AFixed (P type, phase distance 150mm)

��17.5kV, 20/25kA, 630/1250AFixed (P type, phase distance 210mm)

96.5

46.8

M12(Earthing hole)

96.5

46.8

M12(Earthing hole)

Page 12: Super Solution Vacuum Circuit Breakers - LSIS

12I

Dimensions

��17.5kV, 20/25kA, 630/1250AWithdrawable (F type unit, phase distance 210mm)

��17.5kV, 20/25kA, 630/1250AWithdrawable (E type unit, phase distance 210mm)

Page 13: Super Solution Vacuum Circuit Breakers - LSIS

I13

��17.5kV, 20/25kA, 630/1250AWithdrawable (H type unit, phase distance 150mm)

��17.5kV, 20/25kA, 630/1250AWithdrawable (H type unit, phase distance 210mm)

Racking in/out Stroke:200

Racking in/out Stroke:220

Page 14: Super Solution Vacuum Circuit Breakers - LSIS

14II

��17.5kV, 20/25kA, 2000AWithdrawable (E type unit, phase distance 210mm)

��17.5kV, 20/25kA, 2000AFixed (P type, phase distance 210mm)

46.8

96.5

M12(Earthing hole)

Dimensions

Page 15: Super Solution Vacuum Circuit Breakers - LSIS

II15

��17.5kV, 20/25kA, 2000AWithdrawable (E type unit, phase distance 210mm)

��17.5kV, 20/25kA, 2000AWithdrawable (H type unit, phase distance 150mm)

Racking in/out Stroke:220

Page 16: Super Solution Vacuum Circuit Breakers - LSIS

16II

��17.5kV, 20/25kA, 2000AWithdrawable (H type unit, phase distance 210mm)

Racking in/out Stroke:220

Dimensions

Page 17: Super Solution Vacuum Circuit Breakers - LSIS

II17

��17.5kV, 20/25kA, 630/1250AWithdrawable (H cradle, phase distance 150mm)

See Detail A

42.3

M12 (DP:25)

600 650 560

317 323.4

1017.7725 183.7

150

15055

011

20

400

400

205

445

400

400

212.

5

212.

5

Detail A

2-M8 (DP:18)

65 285 150 150 258.7

550

87.320

43.4

87.320

87.320

(Mounting hole)

(Mounting hole)

(Mounting hole)(Mounting hole)

(Mounting hole)

TUBE TUBE

Detail ADetail A

10.0

3030

(For assembly of lifting hook and LV compartment mounting hole)

Connecting busbar method (with earthing switch)Busbar : 8t×40 (2 sheets) <1250A>

Connecting busbar method (with earthing switch)Busbar : 8t×40 (1 sheet) <630A>

Page 18: Super Solution Vacuum Circuit Breakers - LSIS

18II

��17.5kV, 20/25kA, 1250AWithdrawable (H cradle, phase distance 210mm)

Detail A

Detail A

See Detail A

M12 (DP:25)317

700 21

021

0

725 183.71017.7

323.4 42.3

TUBE TUBE

2-M8(DP:18)

Detail A

65 285 150 150 258.7

700

10.0

87.320

63.4

2087.3 87.3

20

(Mounting hole)(Mounting hole)

(Mounting hole)

(Mounting hole)

(Mounting hole)

30 30

(For assembly of lifting hook and LV compartment mounting hole)

Connecting busbar method (with earthing switch)Busbar : 8t×40 (2 sheets) <1250A>

Connecting busbar method (with earthing switch)Busbar : 8t×40 (1 sheet) <630A>

Dimensions

Page 19: Super Solution Vacuum Circuit Breakers - LSIS

II19

��17.5kV, 20/25kA, 2000AWithdrawable (H cradle, phase distance 150mm)

See Detail A

2-M12 (DP:25)

317

550 15

015

0

725 202.71017.7

323.4 42.325

277.7150150285

TUBE

Detail A

2-M8 (DP:18)

Detail A

65

550

2068.3

10.0

68.3

20

86.8

(Mounting hole)

(Mounting hole)

(Mounting hole) (Mounting hole)

(Mounting hole)

25 30

(For assembly of lifting hook and LV compartment mounting hole)

Connecting busbar method (with earthing switch)Busbar : 10t×75 (2 sheets)

Page 20: Super Solution Vacuum Circuit Breakers - LSIS

20II

��17.5kV, 20/25kA, 2000AWithdrawable (H cradle, phase distance 210mm)

2-M12 (DP:25)

317 42.3

183.77251017.7

210

25

210

323.4

700

65 285 150 150

700

258.7

TUBE

Detail A

2-M8(DP:18)

Detail A

10.0

2087.3

See Detail A

127

87.320

(Mounting hole)

(Mounting hole)

(Mounting hole) (Mounting hole)

(Mounting hole)

2530

(For assembly of lifting hook and LV compartment mounting hole)

Connecting busbar method (with earthing switch)Busbar : 10t×75 (2 sheets)

Dimensions

Page 21: Super Solution Vacuum Circuit Breakers - LSIS

II21

Control circuit diagram

LS

7LS

5LS

4

21

4*

3*

7*

LS

6 8*

65

Po

sitio

n s

witc

h

<1

a1

b(T

ES

T),

1a

1b

(SE

RV

ICE

)>

LS

7LS

5LS

4

21

4*

3*

7*

LS

6 8*

6*5*

Posi

tion s

witc

h<

1a1b(T

ES

T),

2b(S

ER

VIC

E)>

55A6

47

56

58

57

70

59

87

25

3426

23 49

60

61

24

48

22

40

38

74

753941

72

73

10

9

37

36

29

28

71

27

51

53

54

52

50

65

43

21

46

45

A5

A4

44

43

A3

A2

42A1

13

14

D1

D212

11

A6

87

25

3426

23

24

22

38

39

10

9

37

36

29

28

27

51

53

52

50

65

43

21

A5

A4

A3

A2

A1

15

16

D1

D212

111

31

41

51

6

16

15

14

13

12

11

10

9

8

7

6

5

4

3

2

116

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

A B C D

A B C D

<C

onn

ecto

r Te

rmin

al C

onf

igur

atio

n>

A t

ype

B t

ype

LS

7

22

23

A2

10

M

MOTOR POWER SOURCE

N

TRIP POWER SOURCE

A6

52a

N

CLOSE POWER SOURCE

A4

N1

2

A1

9

P

A5

P

11A

3

P

39

37

51

25

27

41

29

43

LS

5

24

LS

4

21

43

68

7L

S6 8

65

53

57

55

50

34

36

384

b

42

40

26

28

24

10

a

4a

57

31

TE

ST

SE

RV

ICE

54

56

52

Clo

sing

Sp

ring

Co

ntac

t(C

harg

e co

mp

lete

ind

icat

ing

co

ntac

t)

14

D1

D2

13

45

49

47

61

60

48

44

46

59

71

75

73

58

72

74

70

10

b

C

UV

TT

C1

TC

52a

CS

LS

2

LOCKING MAGNET POWER SOURCE

NP

LM

16

15

22

42

40

26

28

24

60

48

44

46

23

25

27

41

29

43

45

49

47

61

50

34

36

38

54

56

52

58

72

74

70

39

37

51

53

57

55

59

71

75

73

35

Posi

tion

switc

h <2

a(TE

ST),2

a(SE

RVI

CE)

>

Se

con

da

ry t

rip

co

il w

ith T

CM

Co

nta

ct

(9a

)(9

b)

Auxi

liary

sw

itch

Trip c

oil

monito

ring c

onta

ct

Cur

rent

Trip

Coi

l(1A

,5A

) ind

icat

ing

cont

act

CT

C2

Not

e1)

Not

e3)

Not

e4)

Not

e4)

Not

e4)

Not

e5)

Not

e2)

Not

e) 1

. CTC

2 : C

urre

nt T

rip C

oil(1

A,5

A) (

Term

inal

NO

: 13

,14)

2. P

ositi

on S

/W -

TES

T 2a

, SE

RV

ICE

2a(

Term

inal

No.

1, 2

, 3, 4

, 5, 6

, 7, 8

)- T

ES

T po

sitio

n 1a

1b, S

ER

VIC

E p

ositi

on 1

a1b/

2b a

re a

vaila

ble.

(*

mar

ked

cont

act i

s b

cont

act.)

3. U

VT

- Und

er V

olta

ge T

rip (T

erm

inal

No.

D1,

D2)

4. T

C1

- Sec

onda

ry T

rip C

oil (

Term

inal

No.

11,

12)

In c

ase

TC1

is s

elec

ted

and

auxi

liary

sw

itch

is 1

0a10

b, S

ome

'a' c

onta

ct.

(Ter

min

al N

o.: 4

0,41

) and

'b' c

onta

ct(T

erm

inal

No.

:54,

55)

are

not

ava

ilabl

e.5.

Sec

onda

ry T

rip C

oil M

onito

ring

Con

tact

(Ter

min

al N

O.:3

6)In

cas

e S

econ

dary

Trip

Coi

l TC

M C

onta

ct is

sel

ecte

d an

d au

xilia

ry s

witc

h is

9a8

b, S

ome

'a' c

onta

ct(T

erm

inal

No.

: 40,

41) a

nd 'b

' con

tact

(Ter

min

al N

o.:3

6, 3

7) a

re n

ot a

vaila

ble.

6. C

TC -

Cur

rent

Trip

Coi

l (Te

rmin

al N

o.: A

5,A

6)C

TC1

- Sec

onda

ry C

urre

nt T

rip C

oil (

Term

inal

No.

: 11,

12)

CTC

2 - C

urre

nt T

rip C

oil (

Term

inal

No.

: 13,

14)

CTC

3 - C

urre

nt T

rip C

oil (

Term

inal

No.

: D1,

D2)

7. L

ET

- Low

Ene

rgy

Trip

Dev

ice

(Ter

min

al N

o.: 1

3,14

)8.

LM

- Lo

ckin

g M

agen

t (Te

rmin

al N

o.:1

5, 1

6), I

n ca

se o

f B ty

pe c

onne

ctor

is a

vaila

ble

9. C

lose

and

Trip

coi

l is

One

Pul

se ty

pe, e

xclu

ding

Trip

coi

l (D

C11

0, 2

20V

)10

. In

abov

e op

tiona

l acc

esso

ries,

UV

T,C

TC a

nd T

C1

can

not b

e se

lect

ed s

imul

tane

ousl

y.11

. Abo

ve c

ircui

t dia

gram

is b

ased

on

"OFF

" sta

te o

f VC

B a

nd c

losi

ng s

prin

g is

cha

rged

.

Opt

ion

∅: E

xter

nal t

erm

inal

of V

CB

52 :

Vac

uum

circ

uit b

reak

erM

: S

prin

g ch

argi

ng m

otor

TC :

Trip

coi

l(SH

T)TC

1 : S

econ

dary

Trip

coi

l(SH

T1)

C

: Clo

sing

coil(

CC

)U

VT :

Und

er V

olta

ge T

rip52

a : A

uxilia

ry s

witc

h (N

O)

52b

: Aux

iliary

sw

itch

(NC

)LS

2 :

Mot

or s

top

limit

switc

hC

TC :

Cur

rent

Trip

coi

l(3A)

CTC

1 : S

econ

dary

Cur

rent

Trip

coi

l(3A)

CTC

2 : C

urre

nt T

rip c

oil(1

A,5A

)C

TC3

: Cur

rent

Trip

coi

l(1A,

5A)

LET

: Low

Ene

rgy

Trip

Dev

ice(2

5mJ,

100m

J)C

S :

Clo

sing

sprin

g ch

arge

d in

dica

tion

limit

switc

hLS

4, L

S5 :

Posit

ion

S/W

(TES

T po

sitio

n)LS

6, L

S7 :

Posit

ion

S/W

(SER

VIC

E po

sitio

n)

LM :

Lock

ing

mag

net(o

nly

with

draw

able

type

)

CT

C213

D1

14D

2

CT

C3

S/W

TE

ST

: 1a

1bT

ES

T :

2aT

ES

T :

1a1b

No.

SE

RV

ICE

: 2b

SE

RV

ICE

: 2a

SE

RV

ICE

: 1a

1bA

3 A

4 A

5LS

4 C

lose

at T

ES

T p

ositi

on

Clo

se a

t TE

ST

pos

ition

C

lose

at T

ES

T p

ositi

on

LS5

OP

EN

at T

ES

T p

ositi

on

Clo

se a

t TE

ST

pos

ition

O

PE

N a

t TE

ST

pos

ition

LS6

OP

EN

at S

ER

VIC

E p

ositi

onC

lose

at S

ER

VIC

E p

ositi

onC

lose

at S

ER

VIC

E p

ositi

onLS

7 O

PE

N a

t SE

RV

ICE

pos

ition

C

lose

at S

ER

VIC

E p

ositi

on

OP

EN

at S

ER

VIC

E p

ositi

on

Page 22: Super Solution Vacuum Circuit Breakers - LSIS

22II

Ordering information

Note)1. If A2 (UVT), A4 (Position S/W 2a2b) and A7 (Keylock) are selected, A147 is the type name in the ordering.2. Unable to select A1(Secondary trip coil), U1~U8(UVT) simultaneously.3. A3(Position S/W 1a3b), A4(Position S/W 2a2a), A5(Position S/W 2a2b)can not be selected simultaneously. 4. A8 (Button Padlock) and A9 (Button Cover) can not be selected simultaneously.5. When A1 (Secondary Trip coil) is selected the maximum available auxiliary contacts are 9a9b.6. When A2(Secondary trip coil with TCS Contact) is selected the maximum available auxiliary contacts are 4a3b, 9a8b.7. AC (Plug interlock), AD (H type Door interlock), AE (MOC) and AF (Locking magnet) are available only for H type.8. In case of B-type connector the flame retardant wire is applicable to auxiliary contacts 4a4b, not to 10a10b.9. A-type connector is applicable to P/E/F type and B-type connector to H type.10. Lead wire special color (blue) is applicable to A-type connector.11. Locking magnet can be applied only to H type VCB - breaker and cradle.12. Locking magnet of H type breaker use the same control power supply as motor.13. Flame retardant type blue wire is not available.14. M0, C0 and T0 are selectable only for ordering Dummy VCB. Please contact us before ordering.15. When current Trip Coil AV(CTC 1A) or AW(CTC 5A) is selected, A1(Secondary Trip Coil), U1~U8(UVT) cannot be selected

simultaneously and the maximum auxiliary contact is 4a4b.

VL

1 Secondary Trip coil

2 Secondary Trip Coil with TCM Contact

3 Position S/W (Test: 1a1b, Service: 2b)

4 Position S/W (Test: 2a, Service: 2a)

5 Position S/W (Test: 1a1b, Service: 1a1b)

7 Key lock

8 Button Padlock

9 Button Cover

A Lead Wire

B User Plug (Part)

C Plug Interlock

D Padlock (H type Door Interlock)

E MOC (Mechanical Operating Cell S/W)

F Locking Magnet

O Lead Wire special color (Blue)

V CT operated coil 1A

W CT operated coil 5A

U Low Energy Trip Device 100mJ

Accessories Note 1)

20 06B

Note) Types of phase distance1. In case of 15kV VCB- 210mm for 630A of H type- 230mm for 2500A of H type

2. In case of 17.5kV VCB- 150 and 210mm for H type- 150 and 210mm for 630/1250A of P type- 210mm available for E and F type

Note) 15kV: 630A, 2500A17.5 : 630A, 1250A, 2000A

Note) 1. A is written only once in case of more than one.2. 17.5kV be applicable 3. Low Energy Trip Device in case apply to 2500A

Note) 15kV: SB2, SB4, SB6 be applicable

H

Other options

CTD1 Condenser Trip Device(AC 110V)

CTD2 Condenser Trip Device(AC 220V)

UDC1 UVT Time Delay Controller(ADC 110V)

UDC2 UVT Time Delay Controller(ADC 220V)

UDC3 UVT Time Delay Controller(ADC 48V)

CTU Coil Test Unit

VC Vacuum Checker

15

■ Breaker

Type

VL Susol VCB

Rated voltage (kV)

15 15

17 17.5

Installation type

HDraw-out type

(for MCSG)

Breaking current (kA)

20 20

25 25

Compatibility

A 150 mm

B 210 mm

H 230 mm

Rated current (A)

06 630

13 1250

20 2000

25 2500

Motor control voltage

M0 N.A. (manual)

M1 DC 110V

M2 DC 220V

M3 DC 125V

M4 DC 24V~30V

M5 DC 48V~60V

M6 AC 48V

M7 AC 100V~130V

M8 AC 200V~250V

Closing coil voltage

C0 N.A. (without Coil)

C1 DC 110V

C2 DC 220V

C3 DC 125V

C4 DC 24V~30V

C5 DC 48V~60V

C6 AC 48V

C7 AC 100V~130V

C8 AC 200V~250V

Trip coil voltage

T0 N.A. (without Coil)

T1 DC 110V

T2 DC 220V

T3 DC 125V

T4 DC 24V~30V

T5 DC 48V~60V

T6 AC 48V

T7 AC 100V~130V

T8 AC 200V~250V

T9 Current trip coil

UVT

U0 N.A. (without UVT)

U1 DC 110V

U2 DC 220V

U3 DC 125V

U4 DC 24V~30V

U5 DC 48V~60V

U6 AC 48V

U7 AC 100V~130V

U8 AC 200V~250V

Connector and wireSA2 A type connector, 4a4bSA4

StandardA type connector, 10a10b

SB2 B type connector, 4a4bSB4 B type connector, 10a10bSA6 A type connector, 4a4bSA8

FlameA type connector, 10a10b

SB6retardant

B type connector, 4a4b

M1 C1 T1 U1 1 4 7SB2VL-15H25A06 A

Note 2)

Note 2)

Note 2)

Note 2)

Note 2)

Note 3)

Page 23: Super Solution Vacuum Circuit Breakers - LSIS

II23

Note) Types of phase distance1. In case of 15kV VCB- 210mm for 630A of H type- 230mm for 2500A of H type

2. In case of 17.5kV VCB- 150 and 210mm for H type- 210mm available for E and F type

■ Cradle

Note) 1.These accessories for cradle and TM can be applied only to H type.2.AJ and AK can not be selected without door (AH).3.TM (Temperature Monitoring) should be used with AL (Temperature Sensor).4.H type lead wire - one of AM, AN or AO is required for cradle in case of H type breaker.5.Unable to select AK at the cradle in the case of selecting A8(Button Padlock), A9(Button Cover) for body of breakere.6.When Earthing Switch(A1) is selected, Keylock(A5) is included as standard.

Note) A is written only once in case of more than one.

Note) 17.5kV: F(TOC), G (MOC) be applicable

Accessories

TM Temperature Monitoring

VCL 20 06CH12 1 4 7A

1 ES(Earthing Switch) without option

2 ES(Earthing Switch) with position S/W

(2a2b)

4ES(Earthing Switch) with position S/W

(6a6b)

5 ES(Earthing Switch) with Keylock

6 ES with Locking magnet: DC110V

7 ES with Locking magnet: DC220V

8 ES with Locking magnet: DC125V

9 ES with Locking magnet: DC24V

A ES with Locking magnet: DC48V

B ES with Locking magnet: AC48V

C ES with Locking magnet: AC110V

D ES with Locking magnet: AC220V

E Shutter padlock

F TOC (Truck Operating Cell S/W)

G MOC (Mechanical Operating Cell S/W)

H Door

J Door Interlock

K Door Emergency Push Button

L Temperature Sensor

MH type Lead Wire 4a4b

(Flame retardant wire)

N H type Lead Wire 10a10b

(Flame retardant wire)

O H type Lead Wire 4a4b

(Rated short time current)

P ES(Earthing Switch) with making

Accessories

Type

VCSusol VCB

cradle

Installation type

HDraw-out type

(for MCSG)

Breaking current (kA)

20 20

25 25

Compatibility

A 150 mm

B 210 mm

H 230 mm

Rated current (A)

06 630

13 1250

20 2000

25 2500

Rated voltage (kV)

12 12

17 17.5

Page 24: Super Solution Vacuum Circuit Breakers - LSIS

www.lsis.bizⓒ 2013.5 LSIS Co.,Ltd. All rights reserved.

Specifications in this catalog are subject to change without notice due to continuous product development and improvement.

� HEAD OFFICELS Tower 1026-6, Hogye-dong, Dongan-gu, Anyang-si, Gyeonggi-do 431-848, Korea

Tel. (82-2)2034-4887, 4873, 4918, 4148Fax. (82-2)2034-4648

� CHEONG-JU PLANTCheong-Ju Plant #1, Song Jung Dong, Hung Duk Ku,Cheong Ju, 361-720, Korea

2013. 05 Vacuum Circuit Breakers (E) 2013. 05 / (01) 2013. 05 Printed in Korea STAFF

�LSIS (Middle East) FZE ��Dubai, U.A.E. Address: LOB 19 JAFZA VIEW TOWER Room 205, Jebel Ali Freezone P.O. Box 114216, Dubai, United Arab EmiratesTel: 971-4-886 5360 Fax: 971-4-886-5361 e-mail: [email protected] �Dalian LSIS Co., Ltd. ��Dalian, China

Address: No.15, Liaohexi 3-Road, Economic and Technical Development zone, Dalian 116600, ChinaTel: 86-411-8273-7777 Fax: 86-411-8730-7560 e-mail: [email protected]�LSIS (Wuxi) Co., Ltd. ��Wuxi, China

Address: 102-A , National High & New Tech Industrial Development Area, Wuxi, Jiangsu, 214028, P.R.ChinaTel: 86-510-8534-6666 Fax: 86-510-522-4078 e-mail: [email protected]�LSIS-VINA Co., Ltd. ��Hanoi, Vietnam

Address: Nguyen Khe - Dong Anh - Ha Noi - Viet NamTel: 84-4-882-0222 Fax: 84-4-882-0220 e-mail: [email protected]�LSIS-VINA Co., Ltd. ��Hochiminh , Vietnam

Address: 41 Nguyen Thi Minh Khai Str. Yoco Bldg 4th Floor, Hochiminh City, VietnamTel: 84-8-3822-7941 Fax: 84-8-3822-7942 e-mail: [email protected]�LSIS Shanghai Office ��Shanghai, China

Address: Room 32 floors of the Great Wall Building, No. 3000 North Zhongshan Road, Putuo District, Shanghai, ChinaTel: 86-21-5237-9977 Fax: 89-21-5237-7189 e-mail: [email protected]�LSIS Beijing Office ��Beijing, China

Address: B-Tower 17FL.Beijing Global Trade Center B/D. No.36, BeiSanHuanDong-Lu, DongCheng-District,Beijing 100013, P.R. ChinaTel: 86-10-5825-6025,7 Fax: 86-10-5825-6026 e-mail: [email protected]�LSIS Guangzhou Office ��Guangzhou, China

Address: Room 1403, 14/F, New Poly Tower, No.2 Zhongshan Liu Road, Guangzhou 510180, P.R. ChinaTel: 020-8326-6754 Fax: 020-8326-6287 e-mail: [email protected]�LSIS Chengdu Office ��Chengdu, China

Address: Room 1701 17Floor, huamin hanjun internationnal Building, No1 Fuxing Road Chengdu, 610016, P.R. ChinaTel: 86-28-8670-3201 Fax: 86-28-8670-3203 e-mail: [email protected]�LSIS Qingdao Office ��Qingdao, China

Address: Room 2001,20/F,7B40, Galaxy Building, No.29 Shandong Road, Shinan District, Qingdao 266071, P.R. ChinaTel: 86-532-8501-6058 Fax: 86-532-8501-6057 e-mail: [email protected]�LSIS NETHERLANDS Co.Ltd ��Schiphol-Rijk, Netherlands

Address: 1st. Floor, Tupolevlaan 48, 1119NZ,Schiphol-Rijk, The NetherlandsTel: 31-20-654-1420 Fax: 31-20-654-1429 e-mail: [email protected]�LSIS Gurgaon Office ��Gurgaon ,India

Address: 109 First Floor, Park Central, Sector-30, Gurgaon- 122 002, Haryana, India e-mail: [email protected]

�Global Network

� For your safety, please read user's manual thoroughly before operating.

� Contact the nearest authorized service facility for examination, repair, or adjustment.

� Please contact a qualified service technician when you need maintenance.Do not disassemble or repair by yourself!

� Any maintenance and inspection shall be performed by the personnel having expertise concerned.Safety Instructions