Surge Impedance and Loading Power

44

Remember: Surge Impedance

Lossless Line is assumedIf a load is purely resistive equal to the surge impedanceThe, Load Current is given by (where VL is line-to-line voltage)

ckim
Typewritten Text
WWW.MWFTR.COM
Page 2: Surge Impedance and Loading Power - MWFTR - … · Surge Impedance Loading. 46. aAt SIL, Receiving End Voltage is the same in magnitude as Sending End voltage . a. a

Surge Impedance and Loading Power

45

If a load is purely resistive equal to the surge impedanceThe, Power (3-phase) delivered to the load:

Page 3: Surge Impedance and Loading Power - MWFTR - … · Surge Impedance Loading. 46. aAt SIL, Receiving End Voltage is the same in magnitude as Sending End voltage . a. a

Surge Impedance Loading

46

At SIL, Receiving End Voltage is the same in magnitude as Sending End voltage

Page 4: Surge Impedance and Loading Power - MWFTR - … · Surge Impedance Loading. 46. aAt SIL, Receiving End Voltage is the same in magnitude as Sending End voltage . a. a

Surge Impedance and Loading Power

47

Role of Transmission Line

Practical use of SIL(Surge Impedance Loading)A permissible loading of a transmission may be expressed by a fraction of its SILSIL may provide a comparison of load carrying capability of lines

Page 5: Surge Impedance and Loading Power - MWFTR - … · Surge Impedance Loading. 46. aAt SIL, Receiving End Voltage is the same in magnitude as Sending End voltage . a. a

Surge Impedance Loading

48

Role of Transmission LIne

Page 6: Surge Impedance and Loading Power - MWFTR - … · Surge Impedance Loading. 46. aAt SIL, Receiving End Voltage is the same in magnitude as Sending End voltage . a. a

Hyperbolic Form or the equations

49

Page 7: Surge Impedance and Loading Power - MWFTR - … · Surge Impedance Loading. 46. aAt SIL, Receiving End Voltage is the same in magnitude as Sending End voltage . a. a

Hyperbolic Form or the equations

50

Page 8: Surge Impedance and Loading Power - MWFTR - … · Surge Impedance Loading. 46. aAt SIL, Receiving End Voltage is the same in magnitude as Sending End voltage . a. a

Hyperbolic Form or the equations

51

Page 9: Surge Impedance and Loading Power - MWFTR - … · Surge Impedance Loading. 46. aAt SIL, Receiving End Voltage is the same in magnitude as Sending End voltage . a. a

What if your calculator does not do Hyperbolic?

52

Page 10: Surge Impedance and Loading Power - MWFTR - … · Surge Impedance Loading. 46. aAt SIL, Receiving End Voltage is the same in magnitude as Sending End voltage . a. a

Hyperbolic Form or the equations

53

Page 11: Surge Impedance and Loading Power - MWFTR - … · Surge Impedance Loading. 46. aAt SIL, Receiving End Voltage is the same in magnitude as Sending End voltage . a. a

Example 5.1

54

A single-circuit 60-Hz transmission line is 370 km (or 230 mi) long. The conductor’s outside diameter is 0.977in. And the flat horizontal spacing is 7.25 m (or 23.8 ft)between conductors. The resistance of the conductor is 0.1603 ohm/mile. The load on the line is 125 MW at 215kV with 1 unity power factor. (a) Find the voltage, current, and power at the sending end. (b)Find the voltage regulation of the line. (c) Determine the wavelength and velocity of propagation of the line.

Page 12: Surge Impedance and Loading Power - MWFTR - … · Surge Impedance Loading. 46. aAt SIL, Receiving End Voltage is the same in magnitude as Sending End voltage . a. a

Example 5.1

55

A single-circuit 60-Hz transmission line is 370 km (or 230 mi) long. The conductor’s outside diameter is 0.977in. And the flat horizontal spacing is 7.25 m (or 23.8 ft)between conductors. The resistance of the conductor is 0.1603 ohm/mile. The load on the line is 125 MW at 215kV with 1 unity power factor. (a) Find the voltage, current, and power at the sending end. (b)Find the voltage regulation of the line. (c) Determine the wavelength and velocity of propagation of the line.

Page 13: Surge Impedance and Loading Power - MWFTR - … · Surge Impedance Loading. 46. aAt SIL, Receiving End Voltage is the same in magnitude as Sending End voltage . a. a

Example 5.1

56

A single-circuit 60-Hz transmission line is 370 km (or 230 mi) long. The conductor’s outside diameter is 0.977in. And the flat horizontal spacing is 7.25 m (or 23.8 ft)between conductors. The resistance of the conductor is 0.1603 ohm/mile. The load on the line is 125 MW at 215kV with 1 unity power factor. (a) Find the voltage, current, and power at the sending end. (b)Find the voltage regulation of the line. (c) Determine the wavelength and velocity of propagation of the line.

Page 14: Surge Impedance and Loading Power - MWFTR - … · Surge Impedance Loading. 46. aAt SIL, Receiving End Voltage is the same in magnitude as Sending End voltage . a. a

Example 5.1

57

A single-circuit 60-Hz transmission line is 370 km (or 230 mi) long. The conductor’s outside diameter is 0.977in. And the flat horizontal spacing is 7.25 m (or 23.8 ft)between conductors. The resistance of the conductor is 0.1603 ohm/mile. The load on the line is 125 MW at 215kV with 1 unity power factor. (a) Find the voltage, current, and power at the sending end. (b)Find the voltage regulation of the line. (c) Determine the wavelength and velocity of propagation of the line.

Page 15: Surge Impedance and Loading Power - MWFTR - … · Surge Impedance Loading. 46. aAt SIL, Receiving End Voltage is the same in magnitude as Sending End voltage . a. a

Example 5.1

58

A single-circuit 60-Hz transmission line is 370 km (or 230 mi) long. The conductor’s outside diameter is 0.977in. And the flat horizontal spacing is 7.25 m (or 23.8 ft)between conductors. The resistance of the conductor is 0.1603 ohm/mile. The load on the line is 125 MW at 215kV with 1 unity power factor. (a) Find the voltage, current, and power at the sending end. (b)Find the voltage regulation of the line. (c) Determine the wavelength and velocity of propagation of the line.

Page 16: Surge Impedance and Loading Power - MWFTR - … · Surge Impedance Loading. 46. aAt SIL, Receiving End Voltage is the same in magnitude as Sending End voltage . a. a

Example 5.1

59

A single-circuit 60-Hz transmission line is 370 km (or 230 mi) long. The conductor’s outside diameter is 0.977in. And the flat horizontal spacing is 7.25 m (or 23.8 ft)between conductors. The resistance of the conductor is 0.1603 ohm/mile. The load on the line is 125 MW at 215kV with 1 unity power factor. (a) Find the voltage, current, and power at the sending end. (b)Find the voltage regulation of the line. (c) Determine the wavelength and velocity of propagation of the line.

Page 17: Surge Impedance and Loading Power - MWFTR - … · Surge Impedance Loading. 46. aAt SIL, Receiving End Voltage is the same in magnitude as Sending End voltage . a. a

Example 5.1

60

A single-circuit 60-Hz transmission line is 370 km (or 230 mi) long. The conductor’s outside diameter is 0.977in. And the flat horizontal spacing is 7.25 m (or 23.8 ft)between conductors. The resistance of the conductor is 0.1603 ohm/mile. The load on the line is 125 MW at 215kV with 1 unity power factor. (a) Find the voltage, current, and power at the sending end. (b)Find the voltage regulation of the line. (c) Determine the wavelength and velocity of propagation of the line.

Page 18: Surge Impedance and Loading Power - MWFTR - … · Surge Impedance Loading. 46. aAt SIL, Receiving End Voltage is the same in magnitude as Sending End voltage . a. a

Class Activity

61

Class Activity on Transmission Parameters

Page 19: Surge Impedance and Loading Power - MWFTR - … · Surge Impedance Loading. 46. aAt SIL, Receiving End Voltage is the same in magnitude as Sending End voltage . a. a

What if your calculator does not do Hyperbolic?

62

Page 20: Surge Impedance and Loading Power - MWFTR - … · Surge Impedance Loading. 46. aAt SIL, Receiving End Voltage is the same in magnitude as Sending End voltage . a. a

Equivalent Circuit of a Long Line

63

Can we use Pi-circuit even for a long line?

Page 21: Surge Impedance and Loading Power - MWFTR - … · Surge Impedance Loading. 46. aAt SIL, Receiving End Voltage is the same in magnitude as Sending End voltage . a. a

Equivalent Circuit of a Long Line

64

Can we use Pi-circuit even for a long line?

Page 22: Surge Impedance and Loading Power - MWFTR - … · Surge Impedance Loading. 46. aAt SIL, Receiving End Voltage is the same in magnitude as Sending End voltage . a. a

Equivalent Circuit of a Long Line

65

Can we use Pi-circuit even for a long line?

Page 23: Surge Impedance and Loading Power - MWFTR - … · Surge Impedance Loading. 46. aAt SIL, Receiving End Voltage is the same in magnitude as Sending End voltage . a. a

Equivalent Circuit of a Long Line

66

Can we use Pi-circuit even for a long line?

Page 24: Surge Impedance and Loading Power - MWFTR - … · Surge Impedance Loading. 46. aAt SIL, Receiving End Voltage is the same in magnitude as Sending End voltage . a. a

Nominal to long-line

From Nominal Pi-ckt equation ( 50 < l < 150 )

Lon-line equivalent pi-ckt equation ( l > 150 miles)

67

Page 25: Surge Impedance and Loading Power - MWFTR - … · Surge Impedance Loading. 46. aAt SIL, Receiving End Voltage is the same in magnitude as Sending End voltage . a. a

Example 5.3

68

Find the equivalent pi-circuit for the line described in Example 5.1 and compare it with the nominal pi.

Page 26: Surge Impedance and Loading Power - MWFTR - … · Surge Impedance Loading. 46. aAt SIL, Receiving End Voltage is the same in magnitude as Sending End voltage . a. a

Example 5.3

69

Find the equivalent pi-circuit for the line described in Example 5.1 and compare it with the nominal pi.

Page 27: Surge Impedance and Loading Power - MWFTR - … · Surge Impedance Loading. 46. aAt SIL, Receiving End Voltage is the same in magnitude as Sending End voltage . a. a

Power Flow

70

Power Flow (P & Q)Expressed by V, I, and pfExpressed by ABCD circuit constants⌧Focus: How VR and IR affects VS⌧ABCD Constants: All Complex Numbers

Page 28: Surge Impedance and Loading Power - MWFTR - … · Surge Impedance Loading. 46. aAt SIL, Receiving End Voltage is the same in magnitude as Sending End voltage . a. a

Power Flow

71

Page 29: Surge Impedance and Loading Power - MWFTR - … · Surge Impedance Loading. 46. aAt SIL, Receiving End Voltage is the same in magnitude as Sending End voltage . a. a

Power Flow

72

Page 30: Surge Impedance and Loading Power - MWFTR - … · Surge Impedance Loading. 46. aAt SIL, Receiving End Voltage is the same in magnitude as Sending End voltage . a. a

Power Flow: Origin Shift

73

Page 31: Surge Impedance and Loading Power - MWFTR - … · Surge Impedance Loading. 46. aAt SIL, Receiving End Voltage is the same in magnitude as Sending End voltage . a. a

Power Flow: Origin Shift

74

Page 32: Surge Impedance and Loading Power - MWFTR - … · Surge Impedance Loading. 46. aAt SIL, Receiving End Voltage is the same in magnitude as Sending End voltage . a. a

Power Flow

75

ObservationsPoint n is not dependent on IRPoint n will not change if VR is constant: (A*VR^2)/BDistance between n and kis constant for fixed value of VS and VR: (VS*VR)/BDistance between o and kchanges with changing load (IR)

Page 33: Surge Impedance and Loading Power - MWFTR - … · Surge Impedance Loading. 46. aAt SIL, Receiving End Voltage is the same in magnitude as Sending End voltage . a. a

Power Flow

76

ObservationsBecause the distance between n and k is constant, the distance between o and k is constrained to move in a circle whose center is at n.If VR is held constant, a different circle can be drawn for different values of VS’s

Page 34: Surge Impedance and Loading Power - MWFTR - … · Surge Impedance Loading. 46. aAt SIL, Receiving End Voltage is the same in magnitude as Sending End voltage . a. a

Power Flow for Max Power

77

If VR is held constant, a different circle can be drawn for different values of VS’s

Page 35: Surge Impedance and Loading Power - MWFTR - … · Surge Impedance Loading. 46. aAt SIL, Receiving End Voltage is the same in magnitude as Sending End voltage . a. a

Power Flow for Max Power

78

Page 36: Surge Impedance and Loading Power - MWFTR - … · Surge Impedance Loading. 46. aAt SIL, Receiving End Voltage is the same in magnitude as Sending End voltage . a. a

Power Flow: Impact of Vs and Var

79

When PR has to be maintained, moving from a to b involves:

Sending end voltage reduces from VS4 to VS3(To keep the VR intact), due to the VS decrease, the Var has to be decreased, which means negative reactive power must be supplied by parallel capacitors

Page 37: Surge Impedance and Loading Power - MWFTR - … · Surge Impedance Loading. 46. aAt SIL, Receiving End Voltage is the same in magnitude as Sending End voltage . a. a

Reactive Compensation of Transmission Line

80

Reactive Compensation by:Series Compensation: Capacitor placed in each conductor reduces the series impedanceShunt Compensation: Placement of inductors between conductor and neutral reduces the susceptance(admittance)

Pi-Circuit Case

Page 38: Surge Impedance and Loading Power - MWFTR - … · Surge Impedance Loading. 46. aAt SIL, Receiving End Voltage is the same in magnitude as Sending End voltage . a. a

Reactive Compensation of Transmission Line

81

Pi-Circuit CaseMaximum Power Equation

Page 39: Surge Impedance and Loading Power - MWFTR - … · Surge Impedance Loading. 46. aAt SIL, Receiving End Voltage is the same in magnitude as Sending End voltage . a. a

Reactive Compensation

of Transmission

Line

82

Page 40: Surge Impedance and Loading Power - MWFTR - … · Surge Impedance Loading. 46. aAt SIL, Receiving End Voltage is the same in magnitude as Sending End voltage . a. a

EXAMPLE 5.4: Reactive Compensation of Transmission Line

83

In order to show the relative changes in the B constant with respect to the change of the A, C, and D constants of a line when series compensation is applied, find the constants for the line of Example 5.1 uncompensated and for a series compensation factor of 70%

Page 41: Surge Impedance and Loading Power - MWFTR - … · Surge Impedance Loading. 46. aAt SIL, Receiving End Voltage is the same in magnitude as Sending End voltage . a. a

EXAMPLE 5.4: Reactive Compensation of Transmission Line

84

In order to show the relative changes in the B constant with respect to the change of the A, C, and D constants of a line when series compensation is applied, find the constants for the line of Example 5.1 uncompensated and for a series compensation factor of 70%

Page 42: Surge Impedance and Loading Power - MWFTR - … · Surge Impedance Loading. 46. aAt SIL, Receiving End Voltage is the same in magnitude as Sending End voltage . a. a

EXAMPLE 5.4: Reactive Compensation of Transmission Line

85

In order to show the relative changes in the B constant with respect to the change of the A, C, and D constants of a line when series compensation is applied, find the constants for the line of Example 5.1 uncompensated and for a series compensation factor of 70%

Page 43: Surge Impedance and Loading Power - MWFTR - … · Surge Impedance Loading. 46. aAt SIL, Receiving End Voltage is the same in magnitude as Sending End voltage . a. a

EXAMPLE 5.4: Reactive Compensation of Transmission Line

86

In order to show the relative changes in the B constant with respect to the change of the A, C, and D constants of a line when series compensation is applied, find the constants for the line of Example 5.1 uncompensated and for a series compensation factor of 70%

Page 44: Surge Impedance and Loading Power - MWFTR - … · Surge Impedance Loading. 46. aAt SIL, Receiving End Voltage is the same in magnitude as Sending End voltage . a. a

EXAMPLE 5.4: Reactive Compensation of Transmission Line

87

In order to show the relative changes in the B constant with respect to the change of the A, C, and D constants of a line when series compensation is applied, find the constants for the line of Example 5.1 uncompensated and for a series compensation factor of 70%

Page 45: Surge Impedance and Loading Power - MWFTR - … · Surge Impedance Loading. 46. aAt SIL, Receiving End Voltage is the same in magnitude as Sending End voltage . a. a

Shunt Compensation

88

Charging Current Reduction with Shunt Compensation