switchgear and circuit breakers failures and case · pdf fileswitchgear and circuit breakers...
TRANSCRIPT
![Page 1: Switchgear and Circuit Breakers Failures and Case · PDF fileSwitchgear and Circuit Breakers Failures and ... Switchgear and Circuit Breaker Failure ... –Ground fault protection](https://reader033.vdocuments.net/reader033/viewer/2022052208/5a98635d7f8b9adb5c8d3cc5/html5/thumbnails/1.jpg)
FM Global
Switchgear and Circuit
Breakers Failures and
Case Studies
UE Systems 2015 Reliable Asset Conference June 4th
Dan Crawford, Group Manager Field Engineering, FM Global
![Page 2: Switchgear and Circuit Breakers Failures and Case · PDF fileSwitchgear and Circuit Breakers Failures and ... Switchgear and Circuit Breaker Failure ... –Ground fault protection](https://reader033.vdocuments.net/reader033/viewer/2022052208/5a98635d7f8b9adb5c8d3cc5/html5/thumbnails/2.jpg)
FM Global
180 years of expertise
Mutuality
Single focus
– commercial property
![Page 3: Switchgear and Circuit Breakers Failures and Case · PDF fileSwitchgear and Circuit Breakers Failures and ... Switchgear and Circuit Breaker Failure ... –Ground fault protection](https://reader033.vdocuments.net/reader033/viewer/2022052208/5a98635d7f8b9adb5c8d3cc5/html5/thumbnails/3.jpg)
FM Global
FM Global-Engineering
~1,800 engineers
148 countries
Loss Prevention Solutions
- Consistent
- Practical and cost effective
- Scientific proven
![Page 4: Switchgear and Circuit Breakers Failures and Case · PDF fileSwitchgear and Circuit Breakers Failures and ... Switchgear and Circuit Breaker Failure ... –Ground fault protection](https://reader033.vdocuments.net/reader033/viewer/2022052208/5a98635d7f8b9adb5c8d3cc5/html5/thumbnails/4.jpg)
FM Global
Switchgear and Circuit Breaker Failure
What can happen?
Switchgear/circuit breakers fail to operate with
severe consequences
![Page 5: Switchgear and Circuit Breakers Failures and Case · PDF fileSwitchgear and Circuit Breakers Failures and ... Switchgear and Circuit Breaker Failure ... –Ground fault protection](https://reader033.vdocuments.net/reader033/viewer/2022052208/5a98635d7f8b9adb5c8d3cc5/html5/thumbnails/5.jpg)
FM Global
Switchgear and Circuit Breaker Failure
What can happen -
![Page 6: Switchgear and Circuit Breakers Failures and Case · PDF fileSwitchgear and Circuit Breakers Failures and ... Switchgear and Circuit Breaker Failure ... –Ground fault protection](https://reader033.vdocuments.net/reader033/viewer/2022052208/5a98635d7f8b9adb5c8d3cc5/html5/thumbnails/6.jpg)
FM Global
Switchgear and Circuit Breaker Failure
What can happen -
![Page 7: Switchgear and Circuit Breakers Failures and Case · PDF fileSwitchgear and Circuit Breakers Failures and ... Switchgear and Circuit Breaker Failure ... –Ground fault protection](https://reader033.vdocuments.net/reader033/viewer/2022052208/5a98635d7f8b9adb5c8d3cc5/html5/thumbnails/7.jpg)
FM Global
Switchgear and Circuit Breaker Failure
What can happen – worst case
![Page 8: Switchgear and Circuit Breakers Failures and Case · PDF fileSwitchgear and Circuit Breakers Failures and ... Switchgear and Circuit Breaker Failure ... –Ground fault protection](https://reader033.vdocuments.net/reader033/viewer/2022052208/5a98635d7f8b9adb5c8d3cc5/html5/thumbnails/8.jpg)
FM Global
Switchgear and Circuit Breaker Failure
Beyond the loss of the CBs and Switchgear
– Ignition source
– Catastrophic failure of controlled equipment
– Business Interruption
![Page 9: Switchgear and Circuit Breakers Failures and Case · PDF fileSwitchgear and Circuit Breakers Failures and ... Switchgear and Circuit Breaker Failure ... –Ground fault protection](https://reader033.vdocuments.net/reader033/viewer/2022052208/5a98635d7f8b9adb5c8d3cc5/html5/thumbnails/9.jpg)
FM Global
Switchgear and Circuit Breaker Failure
FM experience
![Page 10: Switchgear and Circuit Breakers Failures and Case · PDF fileSwitchgear and Circuit Breakers Failures and ... Switchgear and Circuit Breaker Failure ... –Ground fault protection](https://reader033.vdocuments.net/reader033/viewer/2022052208/5a98635d7f8b9adb5c8d3cc5/html5/thumbnails/10.jpg)
FM Global
Risk Factors
Environment
Operating
conditions
Age/history
Maintenance
Operator training
SEVERITY
Low
Very High
Very
Severe
F
R
E
Q
U
E
N
C
Y
Operator training, contingency plan, safety device
![Page 11: Switchgear and Circuit Breakers Failures and Case · PDF fileSwitchgear and Circuit Breakers Failures and ... Switchgear and Circuit Breaker Failure ... –Ground fault protection](https://reader033.vdocuments.net/reader033/viewer/2022052208/5a98635d7f8b9adb5c8d3cc5/html5/thumbnails/11.jpg)
FM Global
Contingency Plan – What to ask yourself.
Is a needed spare on hand and ready to install─ Critical equipment
─ Long lead time
─ Obsolete
Is re-configuring the electrical system possible
Is redundant equipment installed
double-ended substation
Has an alternative supply been identified
Rental diesel engine-driven generator units
![Page 12: Switchgear and Circuit Breakers Failures and Case · PDF fileSwitchgear and Circuit Breakers Failures and ... Switchgear and Circuit Breaker Failure ... –Ground fault protection](https://reader033.vdocuments.net/reader033/viewer/2022052208/5a98635d7f8b9adb5c8d3cc5/html5/thumbnails/12.jpg)
FM Global
Safety Device
![Page 13: Switchgear and Circuit Breakers Failures and Case · PDF fileSwitchgear and Circuit Breakers Failures and ... Switchgear and Circuit Breaker Failure ... –Ground fault protection](https://reader033.vdocuments.net/reader033/viewer/2022052208/5a98635d7f8b9adb5c8d3cc5/html5/thumbnails/13.jpg)
FM Global
Preventive Maintenance Program
Electrical protection - a system of many components
– Instrument
– Relay
– Control wire
– Trip coil
– Battery
– Etc.
![Page 14: Switchgear and Circuit Breakers Failures and Case · PDF fileSwitchgear and Circuit Breakers Failures and ... Switchgear and Circuit Breaker Failure ... –Ground fault protection](https://reader033.vdocuments.net/reader033/viewer/2022052208/5a98635d7f8b9adb5c8d3cc5/html5/thumbnails/14.jpg)
FM Global
Preventive Maintenance Program Examples
Frequency Flooded Lead Acid Flooded Ni-Cd Sealed Lead
Acid (VRLA)Monthly Check and record charger
voltage and current,
electrolyte levels and for
evidence of corrosion and
leaks,…
Check and record
charger voltage and
current, electrolyte
levels,…
Check and record
charger voltage and
current, ambient
temperature, and for
evidence of corrosion,
leaks, overheating …
Quarterly Check the specific gravity
for lead-antimony
batteries*, and the
temperature of 10% of the
cells…
Check the pilot cell
electrolyte
temperature
Check the internal
ohmic values and
negative terminal
temperature of 10% of
the cells…
Annually Check the specific gravity
of all the cells for lead-
antinomy batteries as well
as all inter-cell
resistances …
check all inter-cell
resistances …
Check the inter-cell
resistance and the
amount of AC ripple in
the charger waveform,
charger alarm
accuracy…
![Page 15: Switchgear and Circuit Breakers Failures and Case · PDF fileSwitchgear and Circuit Breakers Failures and ... Switchgear and Circuit Breaker Failure ... –Ground fault protection](https://reader033.vdocuments.net/reader033/viewer/2022052208/5a98635d7f8b9adb5c8d3cc5/html5/thumbnails/15.jpg)
FM Global
Preventive Maintenance Program Examples
2.1.3.4.2 Perform a capacity test ( also
called performance test or discharge test)
every 5 years for flooded lead acid and
flooded Ni-Cd batteries, and every 2 years
for sealed lead acid (VRLA) batteries.
Sources:
DS 5-19: Switchgear and Circuit Breakers
DS 5-20: Electrical Testing
![Page 16: Switchgear and Circuit Breakers Failures and Case · PDF fileSwitchgear and Circuit Breakers Failures and ... Switchgear and Circuit Breaker Failure ... –Ground fault protection](https://reader033.vdocuments.net/reader033/viewer/2022052208/5a98635d7f8b9adb5c8d3cc5/html5/thumbnails/16.jpg)
FM Global
Case Study #1
Site Information
– A simple manufacturing facility
– 24/7 operation
– Utility power is the single electric powere source
![Page 17: Switchgear and Circuit Breakers Failures and Case · PDF fileSwitchgear and Circuit Breakers Failures and ... Switchgear and Circuit Breaker Failure ... –Ground fault protection](https://reader033.vdocuments.net/reader033/viewer/2022052208/5a98635d7f8b9adb5c8d3cc5/html5/thumbnails/17.jpg)
FM Global
Case Study #1
480 V
12 kV
Utility line 69 kV
![Page 18: Switchgear and Circuit Breakers Failures and Case · PDF fileSwitchgear and Circuit Breakers Failures and ... Switchgear and Circuit Breaker Failure ... –Ground fault protection](https://reader033.vdocuments.net/reader033/viewer/2022052208/5a98635d7f8b9adb5c8d3cc5/html5/thumbnails/18.jpg)
FM Global
Case Study #1
Damage Investigation
– Explosion & fire involving
480V cabinets
– Tank rupture of the mineral
oil-filled 12 kV/480V
transformer
– Minimum business
interruption: contingency
plan in place
![Page 19: Switchgear and Circuit Breakers Failures and Case · PDF fileSwitchgear and Circuit Breakers Failures and ... Switchgear and Circuit Breaker Failure ... –Ground fault protection](https://reader033.vdocuments.net/reader033/viewer/2022052208/5a98635d7f8b9adb5c8d3cc5/html5/thumbnails/19.jpg)
FM Global
Case Study #1
Damage investigation
– Key contributing factor: Lack of adequate maintenance
• 12 kV switchgear’s battery - discharged
• 480 V circuit breaker: seized
• 12 kV fuse for transformer had a known problem
![Page 20: Switchgear and Circuit Breakers Failures and Case · PDF fileSwitchgear and Circuit Breakers Failures and ... Switchgear and Circuit Breaker Failure ... –Ground fault protection](https://reader033.vdocuments.net/reader033/viewer/2022052208/5a98635d7f8b9adb5c8d3cc5/html5/thumbnails/20.jpg)
FM Global
Case Study #1
Conclusion
– Overall maintenance program needs
improvement
– Contingency plan minimized the BI
– No fire following: no combustible load in the
electrical room
![Page 21: Switchgear and Circuit Breakers Failures and Case · PDF fileSwitchgear and Circuit Breakers Failures and ... Switchgear and Circuit Breaker Failure ... –Ground fault protection](https://reader033.vdocuments.net/reader033/viewer/2022052208/5a98635d7f8b9adb5c8d3cc5/html5/thumbnails/21.jpg)
FM Global
Case Study #2
Site Information
– A simple manufacturing facility
– 24/7 operation
– Utility power is the single electric power source
![Page 22: Switchgear and Circuit Breakers Failures and Case · PDF fileSwitchgear and Circuit Breakers Failures and ... Switchgear and Circuit Breaker Failure ... –Ground fault protection](https://reader033.vdocuments.net/reader033/viewer/2022052208/5a98635d7f8b9adb5c8d3cc5/html5/thumbnails/22.jpg)
FM Global
Case Study #2
Site Electrical system:
– Utility power: 69 kV
– 480V feeder
• Solid grounded system
• Fused switch with ground fault protection
• >100 ft. bus bar above the production area
• 40 years old
![Page 23: Switchgear and Circuit Breakers Failures and Case · PDF fileSwitchgear and Circuit Breakers Failures and ... Switchgear and Circuit Breaker Failure ... –Ground fault protection](https://reader033.vdocuments.net/reader033/viewer/2022052208/5a98635d7f8b9adb5c8d3cc5/html5/thumbnails/23.jpg)
FM Global
Case Study #2
Electrical PM
– Annual IR scan
– Annual transformer oil sample – screen & DGA
– 3 year switchgear PM
![Page 24: Switchgear and Circuit Breakers Failures and Case · PDF fileSwitchgear and Circuit Breakers Failures and ... Switchgear and Circuit Breaker Failure ... –Ground fault protection](https://reader033.vdocuments.net/reader033/viewer/2022052208/5a98635d7f8b9adb5c8d3cc5/html5/thumbnails/24.jpg)
FM Global
Case Study #2
The incident
– Bus bar failed (close to the plug-in)
– Auminum bus & enclosure steel frame vaporized
– Suspended ceiling above blew off
– Hot particles from the bus duct explosion ignited the combustible material above the ceiling and a fire followed
![Page 25: Switchgear and Circuit Breakers Failures and Case · PDF fileSwitchgear and Circuit Breakers Failures and ... Switchgear and Circuit Breaker Failure ... –Ground fault protection](https://reader033.vdocuments.net/reader033/viewer/2022052208/5a98635d7f8b9adb5c8d3cc5/html5/thumbnails/25.jpg)
FM Global
![Page 26: Switchgear and Circuit Breakers Failures and Case · PDF fileSwitchgear and Circuit Breakers Failures and ... Switchgear and Circuit Breaker Failure ... –Ground fault protection](https://reader033.vdocuments.net/reader033/viewer/2022052208/5a98635d7f8b9adb5c8d3cc5/html5/thumbnails/26.jpg)
FM Global
Case Study #2
Damage investigation
– Ground fault protection did not operate
– Fuses of two phases melted
– Entire bus damaged
– Significant smoke/water damage to food product
– 100% production shutdown
![Page 27: Switchgear and Circuit Breakers Failures and Case · PDF fileSwitchgear and Circuit Breakers Failures and ... Switchgear and Circuit Breaker Failure ... –Ground fault protection](https://reader033.vdocuments.net/reader033/viewer/2022052208/5a98635d7f8b9adb5c8d3cc5/html5/thumbnails/27.jpg)
FM Global
Case Study #2
Damage investigation
─ GFP
• Unknown setting of GFP
• No electrical study to identify setting
• No recorded testing/maintenance
─ The 480 V bus bar
• No documented maintenance activities
![Page 28: Switchgear and Circuit Breakers Failures and Case · PDF fileSwitchgear and Circuit Breakers Failures and ... Switchgear and Circuit Breaker Failure ... –Ground fault protection](https://reader033.vdocuments.net/reader033/viewer/2022052208/5a98635d7f8b9adb5c8d3cc5/html5/thumbnails/28.jpg)
FM Global
Conclusion
– Coordination study needed for GFP
– Test GFP during 3 year PM
– Improve bus PM
– Fire related issues
• Automatic sprinkler installation
• FD pre incident planning
Case Study #2
![Page 29: Switchgear and Circuit Breakers Failures and Case · PDF fileSwitchgear and Circuit Breakers Failures and ... Switchgear and Circuit Breaker Failure ... –Ground fault protection](https://reader033.vdocuments.net/reader033/viewer/2022052208/5a98635d7f8b9adb5c8d3cc5/html5/thumbnails/29.jpg)
FM Global
Questions