t5n400
TRANSCRIPT
242 ABB SACE - Protection and control devices
5 Special applications
5.2 Networks at particular frequencies
Trip curvesthermomagnetic release
T5N 400/630
In 320 to 630 ATMG
Table 9: Tmax performance T5N 320-630 A TMG
Km = Multiplier factor of I3 due to the induced magnetic fields
I1 (400Hz) I3 setting (2.5…5xIn)
T5N 400/630 MIN MED MAX I3 @ 2.5..5xIn (50Hz) I3 @ 2.5..5xIn (400Hz)In320 201 244 288 800...1600 1.5 1200...2400In400 252 306 360 1000...2000 1.5 1500...3000In500 315 382 450 1250...2500 1.5 1875...3750In630 397 482 567 1600...3150 1.5 2400...4725
Km
I1
t [s]
10.01
100
0.1
0.1 10
1
10
100
1000
10000
In=320 to 630 I3=3.75..7.5xIn