Page 1: TECHNICAL MANUAL - EURAPO · a modulating signal with 0-10Vdc tension in order to regulate the fan speed. OMNIBUS regulators give the possibility to fully control the fan speed (0-100%)

HIG

H P

RESS

URE

UN

IT E

ST E

BH

TECHNICAL MANUAL

EN

Page 2: TECHNICAL MANUAL - EURAPO · a modulating signal with 0-10Vdc tension in order to regulate the fan speed. OMNIBUS regulators give the possibility to fully control the fan speed (0-100%)

2

Page 3: TECHNICAL MANUAL - EURAPO · a modulating signal with 0-10Vdc tension in order to regulate the fan speed. OMNIBUS regulators give the possibility to fully control the fan speed (0-100%)

3

INDEX

EN

1

2

3

4

5

6

7

8

9

1. GENERAL INFORMATION 1.1 Applications .............................................................................. 4 1.2 Operation.................................................................................. 4 1.3 Performances ......................................................................... 4 1.4 Product range.......................................................................... 4 1.5 Selection software ................................................................ 4

2. DIMENSIONS AND WEIGHTS .................................................. 5

3. COMPONENTS 3.1 Structure .................................................................................... 6 3.2 Coils ............................................................................................ 7 3.3 Fan deck .................................................................................... 7 3.4 Condensate tray .................................................................... 8 3.5 Air filter ...................................................................................... 8 3.6 Standard electrical panel IP30 ........................................ 8 3.6.1 Optional electrical panel IP55 ...................................... 8 3.7 Packing ....................................................................................... 9

4. ELECTRICAL ACCESSORIES 4.1 Electric box CBL10 ................................................................ 10 4.2 Electrical heater - KREL....................................................... 10 4.3 AS - Air sensor ........................................................................ 10 4.4 CS - Check Sensor ................................................................ 10 4.5 WS - Water sensor ................................................................ 10 4.6 PC - Condensate pump ..................................................... 10 4.7 EDCR - Electronic regulator ............................................... 11 4.8 OMNIBUS digital control .................................................... 12 4.8.1 Power Omnibus card for BMS - OBT10 .................. 12 4.8.2 Display Console - ODC236 .......................................... 12 4.8.3 Analogue Plus Console - ODC736 ........................... 12 4.8.4 Infrared receiver (OC516) and remote control (OIR30) ........................................ 12 4.9 OMNIBUS Supervision........................................................ 13 4.9.1 OTouch - OCB30 ............................................................... 13 4.9.2 ONet - OCB50 Webserver ............................................ 13

5. HYDRAULIC ACCESSORIES 5.1 J3B2 ........................................................................................... 14 5.2 J3C2 .......................................................................................... 14 5.3 J3BM ......................................................................................... 14 5.4 J3CM ......................................................................................... 14 5.5 J2B2 ............................................................................................ 14 5.6 J2C2 ............................................................................................ 14

6. OTHER ACCESSORIES 6.1 PM - Air delivery plenum .................................................. 17 6.2 PA - Air intake plenum ....................................................... 17 6.4 F5 - Filter ................................................................................. 17 6.5 RAL Painting ........................................................................... 17

7. TECHNICAL DATA 7.1 Air volumes ............................................................................... 18 7.2 Cooling capacities ................................................................. 19 7.3 Heating capacities ................................................................. 20 7.4 Electrical data .......................................................................... 21 7.5 Working operation limits .................................................... 21

8. NOISE LEVELS 8.1 Sound power........................................................................... 22 8.2 Sound pressure in a closed enviroment ..................... 22

9. ELECTRICAL CONNECTIONS ................................................... 24

Page 4: TECHNICAL MANUAL - EURAPO · a modulating signal with 0-10Vdc tension in order to regulate the fan speed. OMNIBUS regulators give the possibility to fully control the fan speed (0-100%)

1

2

3

4

5

6

7

8

9

1. GENERAL INFORMATION1.1 APPLICATIONS

ESTEBH high pressure ducted fan coils with energy saving motors, are specifically designed for ducted installations, with external static pressure up to 300 Pa.Their high pressure fan decks permit to satisfy every request of heating and cooling application in big environments.

1.2 OPERATION

The effectiveness of a fan coil is due to the large surface area of the finned heat exchanger (coil) where the air drawn from the room by the fan passes through.Heating operation: the hot water circulating in the finned coil supplies heat to the air passing through the heat exchanger.Cooling operation: the chilled water circulating in the finned coil removes heat from the air passing through the heat exchanger.The air is also dehumidified and the condensed water vapor must be discharged from the unit: suitable drains must therefore be provided to drain the condensed water that collects in the condensate tray.

1.3 PERFORMANCES

The performance of a fan coil can vary greatly with changes in the temperature and in the amount of water circulating through the coil, as well as with changes in the temperature and in the amount of air circulating through the coil.The air volume is determined by selecting the proper fan speed through continuous regulation (0-100%) by using electronicor digital (OMNIBUS) regulators (also for BMS system) while the water flow rate is determined by the specifications of the system and of the pump.Thermal performances of the unit can be optimized by controlling the inlet flow rate of the water with proper regulating valves (ON/OFF or modulating), which can be supplied as accessories and which are necessary in case of cooling operation.For each model, thermal performances in heating and cooling depend on the number of rows of the coil installed, which gives the opportunity to make the air treatment suit every condition required.In cooling function, under the same operating conditions, the more rows the heat exchanger has, the more it will dehumidify.

1.4 PRODUCT RANGE

The ESTEBH high pressure fan coil units are available in 5 sizes (020÷060) for concealed horizontal installation, in 2 and 4 pipe systems.

1.5 SELECTION SOFTwARE

To facilitate choosing the correct size of a fan coil for any operating condition (including those differing from the standard ones), EURAPO offers a dedicated computer program which can be downloaded from the ftp address http://ftp.eurapo.it/ and can be updated with automatic upload through internet.

Installation and Operation instructions concerning the software for selection are provided with the software itself.

4

Page 5: TECHNICAL MANUAL - EURAPO · a modulating signal with 0-10Vdc tension in order to regulate the fan speed. OMNIBUS regulators give the possibility to fully control the fan speed (0-100%)

2. DIMENSIONS AND wEIGHTS

5

EN

1

2

3

4

5

6

7

8

9

C

E

91,5

30,5

31,5

40

H

15

31,5

D21

2120

20BF

134

G

ø 20

134

A

3532

,5

020 030 040 050 060A [mm] 407,6 407,6 407,6 407,6 517,6B [mm] 902 902 902 902 1160C [mm] 989,6 989,6 1239,6 1239,6 1634,6D [mm] 365,6 365,6 365,6 365,6 475,6E [mm] 926,6 926,6 1176,6 1176,6 1571,6F [mm] 634 634 634 634 892G [mm] 418,5 418,5 418,5 418,5 446,5H [mm] 1019,6 1019,6 1269,6 1269,6 1664,6Weight (3R - 3 rows) [kg] 64,3 64,3 79,3 79,3 126,0

(2-3-4 rows) (2-3-4 rows) (2-3-4 rows) (2-3-4 rows) (2-3-4-5 rows)Weight of the coil [kg] 1,2-2,0-2,6 1,2-2,0-2,6 1,9-2,9-3,7 1,9-2,9-3,7 3,4-4,6-6,3-9,0Water connection G1/2” F G1/2” F G1/2” F G1/2” F G1” M

(2-3-4 rows) (2-3-4 rows) (2-3-4 rows) (2-3-4 rows) (2-3-4-5rows)Water content [I] 1,4-2,2-2,9 1,4-2,2-2,9 1,9-2,8-3,8 1,9-2,8-3,8 3,4-5,0-6,7-8,4

Page 6: TECHNICAL MANUAL - EURAPO · a modulating signal with 0-10Vdc tension in order to regulate the fan speed. OMNIBUS regulators give the possibility to fully control the fan speed (0-100%)

1

2

3

4

5

6

7

8

9

6

3. COMPONENTS

3.1 STRUCTURE

The structure is made of galvanized steel. A particular manufacturing process gives stiffness to the structure: in this way all risks of vibration (which causes unpleasant noise) are strongly reduced. All the inner elements that could be cooled are completely lined with insulating material based on polyolefins, chemically reticulated and closed cell foam, which is not only a thermal insulation material but also a good sound attenuator. Self-extinguishing grade in accordance to norms: Class 1 - Italy, Class M1 - France, UNI 8457 and UNI 9174.In order to facilitate all maintenance operations, the structure is divided in 3 separate and independent sections:

• Fandeck• Condensatetray• Filter

The air intake and outlet are provided with a 21 mm flange for an easy connection to the air duct.The ESTEBH fan coils can be installed on the ceiling by using the four fixing brackets always supplied with every unit.

LEGEND

1. Structure

2. Fixing support

3. Filter

4. Fan deck

5. Standard coil

6. Heat exchangers(2 or 3 rows)

7. Condensate tray

8. Access panel to fan deck

9. Access panel to condensate tray

10. Access panel to filter

11. Water discharge fixing supports

12. Electric box

13. Inverter

Page 7: TECHNICAL MANUAL - EURAPO · a modulating signal with 0-10Vdc tension in order to regulate the fan speed. OMNIBUS regulators give the possibility to fully control the fan speed (0-100%)

1

2

3

4

5

6

7

8

9

7

EN

3.2 COILS

For each unit size there are 2, 3 and 4 row coils available; for 4 pipe systems it is possible to install a 2 or 3 row coil. It is therefore possible to have a combination of maximum 7 rows (4 row cooling + 3 row heating). For models 060 are also 5 row coils available, which can be combined with additional 2 or 3 row coils. All coils consist of 3/8” external diameter copper pipes mechanically expanded to the aluminum fin packs, provided with copper headers and brass soldering connections. Max. operating pressure 1,6 MPa, testing pressure 2,8 MPa. For the sizes 020, 030, 040 e 050 each header is provided with a very handy air valve, to allow air venting or water drainage from the coil. The air valve can be easily reached from the outside of the unit. For the sizes 060 the air vent valve are not present, therefore it is necessary to provide in the pipe connection a system for the water discharge and air venting of the coil. ESTEBH units are also available for District Cooling applications: the water coils (4 rows for size 020÷050 and 5 rows for size 060) are designed with a reduced number of circuits, suitable for functioning with high water temperature difference.ESTEBH units can be ordered with right (standard) or left water connections, so defined when facing the air outlet. If necessary, however the coils can be easily removed and reversed on site. Water connections are 1/2” F (female threaded) for sizes 020, 030, 040, 050 1” M (male threaded) for size 060.

MAXIMUM OPERATING PRESSURE wITH vALvES: 16 BAR.

3.3 FAN DECk

The fan deck is composed by a motor and 2 centrifugal galvanized steel scrolls. The brushless motor is a component of the EST technology (Energy Saving Technology) applied to the Eurapo product range. It is combined to a dedicated electronic device (inverter), which is provided with DIP SWITCH that can be set on site accordingly to the pressure drop in the system. The inverter can be managed by specific regulators (Omnibus, for example) which use a modulating signal with 0-10Vdc tension in order to regulate the fan speed. OMNIBUS regulators give the possibility to fully control the fan speed (0-100%) and/or to manually select three fan steps (high, med and low speed): it is actually possible to set in every moment and very easily the three different levels of motor’s rotation, in order to fulfil specific thermal or acoustical requirements. The motor and the scrolls are fixed on a rigid galvanized steel 1,5 mm thick basement: the motor is located in a proper cradle and fixed with elastic ribbon supports. All motors operate at 50/60Hz and for all sizes the power supply is 230V± 6%. Each fan assembly is dynamically balanced, to reduce noise and wear of the components to minimum levels; it can easily be removed for maintenance operation.

Page 8: TECHNICAL MANUAL - EURAPO · a modulating signal with 0-10Vdc tension in order to regulate the fan speed. OMNIBUS regulators give the possibility to fully control the fan speed (0-100%)

1

2

3

4

5

6

7

8

8

3.4 CONDENSATE TRAy

The condensate tray is made of galvanized steel and it is completely insulated by a 12 mm thick closed cell polyurethane foam layer. The condensed water is discharged from both sides (left or right) through a 20 mm diameter header.Stainless Steel (AISI 316) condensate tray is also available upon request.

3.5 AIR FILTER

The air filter consists of a washable polyester acrylic fiber, filtration class G3. A filter with higher filtering grade (F5) is also available upon request for each model.The particular pleated shape of the filter, protected by a metal frame, allows having a big filtering surface with only 45 mm thickness. The filter section can be easily removed for cleaning and maintenance operation. Filters are not washable.

3.6 STANDARD ELECTRICAL PANEL IP30

All models are provided with a 12 pole terminal board with screw terminals contained in a self-extinguishing (class V0) plastic box (IP30).The electric box is fixed on the same side of the water connection.

Every ESTEBH model is supplied with an electric wiring diagram showing all the electrical components, accessories factory fitted and/or remote controllers ordered together with the unit. Everything must be correctly wired in accordance to the diagram, to obtain the requested working conditions of the unit.

3.6.1 OPTIONAL ELECTRICAL PANEL IP55 (Gw00)

Electrical panel composed by a terminal board with screw terminals contained in a high protection box (IP55). Available on request.

3.7 PACkING

Every unit is packed in a carton box and lays on a wooden pallet.

LEGEND

1. Label on packing

2. Label on internal structure

3. Box with fixing brackets and accessories

4 Valve Kit (optional)

1

2

4

3

9

Standard electrical panel ESTCBL00

Page 9: TECHNICAL MANUAL - EURAPO · a modulating signal with 0-10Vdc tension in order to regulate the fan speed. OMNIBUS regulators give the possibility to fully control the fan speed (0-100%)

1

2

3

4

5

6

7

8

9

EN

9

4. ELECTRICAL ACCESSORIES4.1 ELECTRIC BOX CBL10

Self-extinguishing plastic box (class V0), which contains a 12 pole terminal board and a double insulated transformer (230/24 V~10 VA), for the electrical connection of the modulating valves. It can be used in combination to EDCR and Omnibuscontrols (OBTxx).

4.2 ELECTRICAL HEATER - kREL

Additional module for Electrical heater supplied with 2 safety thermostats, one with automatic resetting and the other one with manual resetting, a power relay card and a terminal board for the electrical connection.The table shows the power of the electric heater for each unit size.

EBH P [kw] P/S[v-ph-Hz] A B C

020030

3,0 230-1-50 1068,1 954,6402,1

040050

6,0 380-3-50 1318,1 1204,6

060 9,0 380-3-50 1713,1 1599,6 512,1

4.3 AS - AS - AIR SENSOR

1 m long NTC sensor fixed on the air inlet of the ducted unit. It is optional, on request, with the following regulators:

It is optional, on request, with the following regulators: EDCR and OMNIBUS (OBTXX).

4.4 CS - CHECk SENSOR

1m long NTC sensor, to be installed on the air outlet of the ducted unit. In combination with OMNIBUS card, it allows highlighting any faults in the functioning of the ducted unit, by reporting an alarm signal.

4.5 wS - wATER SENSOR

3m long NTC sensor (10K, 25°C), requested for the automatic S/W switch when a ducted unit is controlled by a regulator with microprocessor or OMNIBUS, in a 2 pipe system, for both heating and cooling operation. The Summer/Winter changeover works as follows:

WS combined to EDCR Summer: water temperature < 18 °C ± 1K = cooling on water temperature > 20 °C ± 1K = cooling off Winter: water temperature > 36 °C = heating on water temperature < 34 °C = heating off

The water sensor is not compatible with 2 way valves (J2B2 or J2C2, for example).

228

B

C

A

WS

Page 10: TECHNICAL MANUAL - EURAPO · a modulating signal with 0-10Vdc tension in order to regulate the fan speed. OMNIBUS regulators give the possibility to fully control the fan speed (0-100%)

4.6 PC - CONDENSATE PUMP

The condensate pump is necessary when the traditional water discharge is not allowed. It is supplied already mounted on the unit. The power of the pump is different for the different models where it has to be installed.Functions:

• forcedevacuationofthecondensedwater.

PC Technical features for sizes 020 and 030

Max flow rate 10 l/h

Max suction head 2 m

Max discharge head 6 m

Electric power 18 W

Electric voltage 230 V~ 50/60 Hz

Alarm contact NC 8 A - 250 V

Detection levels in mm ON: 16, OFF: 11, Alarm: 19

Sound level at 1 m 25,1 dBA

Protection IP20

Detection remote

Thermal protection (overheating) 90 °C

Safety standards CE

RhOS and WEEE directives Complies

PC Technical features for sizes 040÷060:

Max flow rate 20 l/h

Max suction head 3 m

Max discharge head 10 m (flow= 4 l/h)

Electric power 14 W

Electric voltage 230 V~ 50/60 Hz

Alarm contact NC 8 A resistive - 250 V

Detection levels in mm ON: 16, OFF: 11, Alarm: 19

Sound level at 1 m < 20 dBA

Protection IP20

Detection remote

Thermal protection (overheating) 90 °C

Safety standards CE

RhOS and WEEE directives Complies

1

2

3

4

5

6

7

8

10

9

ALTEZZA DI MANDATA MASSIMA RACCOMANDATA

PORTATA (l/h)

MAN

DATA

(m)

20181614121086420

1

2

3

4

5

6

7

8

9

10

ALTEZZA DI MANDATA MASSIMA RACCOMANDATA

PORTATA (l/h)

ALTE

ZZA

DI M

ANDA

TA (m

)

20181614121086420

2

4

6

8

10

12

14

DIS

CH

ARG

E H

EAD

(m

)

FLOW RATE (l/h)

RECOMMENDED MAX DISCHARGE HEAD

DIS

CH

ARG

E H

EAD

(m

)

FLOW RATE (l/h)

RECOMMENDED MAX DISCHARGE HEAD

Page 11: TECHNICAL MANUAL - EURAPO · a modulating signal with 0-10Vdc tension in order to regulate the fan speed. OMNIBUS regulators give the possibility to fully control the fan speed (0-100%)

1

2

3

4

5

6

7

8

11

EN

9

4.7 ELECTRONIC REGULATORS EDCR

Microprocessor control designed for water terminal units equipped with brushless motors (EST Inverter Technology).It permits to control the type of ventilation (fan thermostated or fan continuously running), the fan speeds (0-10V or Auto),SUMMER/WINTER changeover and room temperature thermostat.

For more information please refer to the TECHNICAL MANUAL FOR EDCR CONTROLLERS.

EDCR

EDCR CONTROLS FUNCTIONS TABLE

Functions EDCR

Ventilation mode (Thermostated - Continuous) •

Manual (0-10V) or Auto speed selector •

Automatic S/W changeover (2 pipe system, with WS) •

Automatic (with dead band) or external (centralized) S/W changeover •

Room temperature thermostat setting •

Temperature setting range limitation •

De-stratification function •

Economy/occupancy contact* •

Window contact* •

Frost protection (only with heating valve) •

Operating mode LED (Summer - Winter) •

Dirty filter alarm LED •

* not optoinsulated from 230 V~ power supply net

EDCR CONTROL COMPATIBILITy TABLE

Compatibility Rif. EURAPO EDCR

2 and 4 pipe system •

ON/OFF 230V cooling and heating valve, 2/4 pipe system J3B2-J3C2 •

Modulating 24V cooling and heating valve, 2/4 pipe system J3BM-J3CM •

NTC water sensor for automatic S/W (2 pipe system) and min. water temp. thermostat wS •

Electric heater (in alternative to the heating valve) kREL •

Page 12: TECHNICAL MANUAL - EURAPO · a modulating signal with 0-10Vdc tension in order to regulate the fan speed. OMNIBUS regulators give the possibility to fully control the fan speed (0-100%)

1

2

3

4

5

6

7

8

12

4.8 OMNIBUS DIGITAL CONTROL

The OMNIBUS digital control system permits a complete and integrated management of several fancoil units installed in thesame building. It is designed either for a stand-alone operating mode, or to be integrated, at different levels, to a centralizedBuilding Automation System, with a serial communication protocol RS-485 (Modbus RTU).The digital regulator can control many fancoils at the same time (Master/Slave solution), which are connected together in alocal BUS network by two twisted wires (AWG 24).

4.8.1 POwER OMNIBUS CARD - OBT10

The Power Omnibus card mounted on the unit is designed to fully regulate (directly or via Modbus) the water terminal units.The card can provide:• 6 ON/OFF outputs: 3 speeds for an auxiliary fan; Electric heater/Dehumidification;

Hot water valve, Cold water valve• 3 Analogue 0-10V outputs: EST fan, Heating modulating valve, Cooling

modulating valve• 5 Outputs on the additional multitask card OBT50 (optional): On/off heating valve 24V; On/off cooling valve 24V; Auxiliary

fan for fresh air and/or free cooling; Alarm contact; External air damper• 5 Analogue inputs: Room temperature sensor (AS), Water sensor (WS), Air outlet sensor (CS), External air temperature sensor

and relative humidity sensor• 3 Digital inputs: Economy contact; Window contact; contact for the thermal protection of the motor• 2 Serial communication ports (RS485): Network “Local Bus” for the connection of the Console (built-in the unit or for

remote installation); Network Modbus for the connection to a Supervision System (BMS)

4.8.2 DISPLAy CONSOLE - ODC236

The Console is connected to the Power Omnibus card by a phone cable (4 wires), from which it is energized (15 Vcc) and it receives information from the Local-bus network. The Display Console is provided with four buttons for setting the parameters and the operating modes of the water terminal unit:

• Status: OFF-Comfort-Economy• Fan:Low,Med,High,Auto• Mode:Cool-Heat-Fan-Dry• RoomtemperatureSet-point

The Display Console can be used as Service Tool:• identification by code of possible alarms• setting or variation of the Modbus address• visualization of the I/O status

4.8.3 ANALOGUE PLUS CONSOLE - ODC736

The Console is connected to the Power Omnibus card by a phone cable (4 wires), from which it is energized (15 Vcc) and it receives information from the Local-bus network. The Analogue Plus Console is composed by:One LED showing the operating mode and operating status of the Power Omnibus card• Four LEDs to visualize the fan speed status and warnings, in case• Two buttons: one for setting the operating mode of the terminal unit (Cooling/Heating) and one for the selection of the fan speed• Roomtemperaturesensor• Oneknobforsettingtheroomtemperatureset-pointvalueandOFFposition

9

ODC736

ODC236

OBT10

Page 13: TECHNICAL MANUAL - EURAPO · a modulating signal with 0-10Vdc tension in order to regulate the fan speed. OMNIBUS regulators give the possibility to fully control the fan speed (0-100%)

1

2

3

4

5

6

7

8

13

EN

4.8.4 INFRARED RECEIvER (OC516) AND REMOTE CONTROL (OIR30)

The end user has the possibility to regulate the fan coil unit through the Infrared remote control (OIR30). The IR receiver is connected to the Power Omnibus card by a flat phone cable from which it takes the power supply (15 Vcc) and by which it exchanges information on the RS485 “Local bus” network. The IR console has a built-in air sensor and one LED showing the Status of the unit, in particular: • fixed green: cooling mode• fixed red: heating mode• flashing yellow: alarm or warning status

4.9 OMNIBUS SUPERvISION

4.9.1 OTOUCH - OCB30 (up to 100 units)

• Modbus/RTU Protocol• Differentaccesslevels(user/supervisor/service)• Centralizedoperation• Set-upparametersconfiguration• INPUT/OUTPUTstatusmonitoring• Daily,weeklyandspecialeventsprogram• Alarmsmanagement• 7inchestouchscreen• OptionalmodemforremotemanagementviaGSM• Boost function for a period set by the user• LANinterfacewithTCP/IPprotocol• Suitableforthemostcommonwebbrowsers• RemotemanagementviaInternet• Boilerroommanagement(pumps,boiler,heatpump)• Scenariosmanagement• MultilanguageOTOUCH is a 7-inch touch screen supervisor that allows centralizing the managing of power OMNIBUS cards, up to a maximum of 100 cards connected to the same network. Each Omnibus card can also be managed individually with different options.OTouch allows the management of complex scenarios and seasonal programming of the system. It runs in a rational way all the different components of a heating and cooling installation, granting the communication and interaction between the several elements of a plant: Energy production (boiler/chiller) - Circulation pumps - Zone valves - Dehumidifiers - Fan Coil Units. It can communicate via Bus, via SMS with GSM line, via Internet. It is arranged for Wi-Fi connection.

4.9.2 ONET - OCB50 wEBSERvER (up to 480 units)

• Modbus/RTU protocol• Differentaccesslevels(user/supervisor/service)• Centralizedoperation• Set-upparametersconfiguration• INPUT/OUTPUTstatusmonitoring• Daily,weeklyandspecialeventsprogram• Alarmsmanagement• Boost function for a period set by the user• Suitableforconnectingupto2linesof240unitseach• LANinterfacewithTCP/IPprotocol• Suitableforthemostcommonwebbrowsers• RemotemanagementviaInternet

9

OTOUCH

OCB50

OIR30OC516

For more information please refer to the TECHNICAL MANUAL FOR OMNIBUS CONTROLLERS

Page 14: TECHNICAL MANUAL - EURAPO · a modulating signal with 0-10Vdc tension in order to regulate the fan speed. OMNIBUS regulators give the possibility to fully control the fan speed (0-100%)

1

2

3

4

5

6

7

8

14

5. HyDRAULIC ACCESSORIES

5.1 J3B2 – ON/OFF 3-wAy vALvES wITH 4 wATER CONNECTIONS, 3/4”, FOR 2 OR 4 PIPE SySTEMS, 230v

The ON/OFF 3-way regulating valves with bypass are provided with thermoelectric actuator and connection tubes. The direct water flow is closed by not supplying power to the actuator. They are suitable for fan coils size 020÷050 and available also with 24V. They are always supplied loose together with their proper insulating shell.

5.2 J3C2 – ON/OFF 3-wAy vALvES wITH 4 wATER CONNECTIONS, 1”, FOR 2 OR 4 PIPE SySTEMS, 230v

The ON/OFF 3-way regulating valves with bypass are provided with thermoelectric actuator and connection tubes. The direct water flow is closed by not supplying power to the actuator. They are suitable for fan coils size 060÷070 and available also with 24V. They are always supplied loose together with their proper insulating shell.

5.3 J3BM – MODULATING (24v) 3-wAy vALvES wITH 4 wATER CONNECTIONS, 3/4”, FOR 2 OR 4 PIPE SySTEMS

The modulating 3-way regulating valves with bypass are provided with modulating actuator and connection tubes. The direct water flow is closed by not supplying power to the actuator. They are suitable for fan coils size 020÷050.They are always supplied loose together with their proper insulating shell.

5.4 J3CM – MODULATING (24v) 3-wAy vALvES wITH 4 wATER CONNECTIONS, 1”, FOR 2 OR 4 PIPE SySTEMS

The modulating 3-way regulating valves with bypass are provided with modulating actuator and connection tubes. The directwater flow is closed by not supplying power to the actuator. They are suitable for fan coils size 060.They are always supplied loose together with their proper insulating shell.

5.5 J2B2 – ON/OFF 2-wAy vALvES, 3/4”, FOR 2 OR 4 PIPE SySTEMS, 230v

The ON/OFF 2-way regulating valves with bypass are provided with thermoelectric actuator and connection tubes. They are suitable for fan coils size 020÷050 and available also with 24V. They are not supplied with insulation shell. They need to be insulated on site.

5.6 J2C2 – ON/OFF 2-wAy vALvES, 1”, FOR 2 OR 4 PIPE SySTEMS, 230v

The ON/OFF 2-way regulating valves with bypass are provided with thermoelectric actuator and connection tubes. They are suitable for fan coils size 060÷070 and available also with 24V. They are not supplied with insulation shell. They need to be insulated on site.

9

Page 15: TECHNICAL MANUAL - EURAPO · a modulating signal with 0-10Vdc tension in order to regulate the fan speed. OMNIBUS regulators give the possibility to fully control the fan speed (0-100%)

1

2

3

4

5

6

7

8

15

EN

ESTEBH with J3B2

TECHNICAL FEATURES OF THE vALvES

Nominal pressure PN16 Cod.: J3B2, J3BM, J3C2, J3CM, J2B2, J2C2

FluidHot or cold water for HVAC system, according to VDI standard quality or equivalent

Cod.: J3B2, J3BM, J3C2, J3CM, J2B2, J2C2

Hydraulic connection 1” GF 3/4” GF

Cod.: J3C2, J3CM, J2C2Cod.: J3B2, J3BM, J2B2

Max close-off pressure62 kPa70 kPa150 kPa

Cod.: J2C2Cod.: J3C2, J3CMCod.: J3B2, J3BM, J2B2

Kvs

2,52,64,55,5

Cod.: J3B2, J3BMCod.: J2B2Cod.: J3C2, J3CMCod.: J2C2

Material Brass Cod.: J3B2, J3BM, J3C2, J3CM, J2B2, J2C2

Flow temperature limit 2÷95 °C2÷110 °C

Cod.: J2C2Cod.: J3B2, J3BM, J3C2, J3CM, J2B2

Room temperature limit 2÷50 °C Cod.: J3B2, J3BM, J3C2, J3CM, J2B2, J2C2

Actuator On/OffModulating

Cod.: J3B2, J3C2, J2B2, J2C2Cod.: J3CM, J3BM

Voltage supply 230V~ ±15% 50/60 Hz24V ~ ±15% 50/60 Hz

Cod.: J3B2, J3C2, J2B2, J2C2Cod.: J3CM, J3BM

Control signal 0÷10 Vcc Cod.: J3BM, J3CM

Absorption 2,5 VA Cod.: J3B2, J3BM, J3C2, J3CM

Opening time 20° C ~ 180s Cod.: J3B2, J3C2, J2C2

Closing time 20° C ~ 260s Cod.: J3B2, J3C2, J2C2

Protection grade IP44 (EN 60529)IP43 (EN 60529)

Cod.: J3B2, J3C2, J2B2Cod.: J3CM, J3BM, J2C2

9

Page 16: TECHNICAL MANUAL - EURAPO · a modulating signal with 0-10Vdc tension in order to regulate the fan speed. OMNIBUS regulators give the possibility to fully control the fan speed (0-100%)

1

2

3

4

5

6

7

8

16

9

MAXIMUM OPERATING PRESSURE wITH vALvES: 16 BAR.

In order to choose the correct type of valve it is necessary to know the system’s technical specifications; for this reason the consultant should take full responsibility for this choice.

GRAPHIC PRESSURE DROP vALvES

0

20

40

60

80

100

120

140

160

0 1 2 3 4 5 6

Pres

sure

dro

p [k

Pa]

Water flow [mc/h]

kvs=4,5kvs=5,5

0

20

40

60

80

100

120

140

160

0 0,5 1 1,5 2 2,5 3 3,5

Pres

sure

dro

p [k

Pa]

Water flow [mc/h]

kvs=2,5kvs=2,6

Page 17: TECHNICAL MANUAL - EURAPO · a modulating signal with 0-10Vdc tension in order to regulate the fan speed. OMNIBUS regulators give the possibility to fully control the fan speed (0-100%)

6. OTHER ACCESSORIES6.1 PM – AIR DELIvERy PLENUM

The air delivery plenum is made of galvanized steel sheet, insulated inside with polyurethane foam, 12 mm thick, provided with spigots for the connection to the air ducts and with fixing supports. It must be installed on the air outlet of the unit.

6.2 PA – AIR INTAkE PLENUM

The air intake plenum is made of galvanized steel sheet, insulated inside with polyurethane foam, 12 mm thick, provided with spigots for the connection to the air ducts and with fixing supports. It must be installed on the air inlet of the unit.

6.3 FILTER F5

High filtering grade air filter consisting of a polyester acrylic fiber foam, filtration class F5.

6.4 RAL PAINTING

The complete structure of the unit can be painted with oven dried epoxy powders. The standard colour is white (RAL 9001) but the full range of RAL colours is available upon request, with possible delays in the delivery time.

1

2

3

4

5

6

7

8

17

EN

PM-PASize 020 030 040 050 060

N. Collars 3 3 4 4 5

A 403,6 403,6 513,6

B 962,6 1212,6 1607,6

C 306,5 300 311

9

Filter F5 (on request)

B

C

A

350

78,2 Ø200

Page 18: TECHNICAL MANUAL - EURAPO · a modulating signal with 0-10Vdc tension in order to regulate the fan speed. OMNIBUS regulators give the possibility to fully control the fan speed (0-100%)

1

2

3

4

5

6

7

8

18

7. TECHNICAL DATA

7.1 AIR vOLUMES [m3/h] AT DIFFERENT EXTERNAL STATIC PRESSURES [PA]

9

Nominal values (m3/h)0 25 50 75 100

Size020

1V - - - - -2V 165 - - - -3V 439 - - - -4V 749 - - - -5V 956 - - - -6V 1197 849 - - -7V 1360 1108 728 - -8V 1580 1387 1100 - -9V 1892 1697 1430 1329 849

Size030

1V - - - - -2V 323 - - - -3V 689 - - - -4V 914 - - - -5V 1200 786 - - -6V 1573 1094 615 - -7V 1829 1517 1205 - -8V 2059 1790 1470 1444 9149V 2478 2249 1981 1978 1606

Size040

1V 289 - - - -2V 644 - - - -3V 1018 - - - -4V 1363 - - - -5V 1897 - - - -6V 2117 1415 713 - -7V 2559 2220 1820 1658 16688V 2839 2565 2239 2031 20059V 3191 2973 2712 2800 2879

Size050

1V 310 - - - -2V 797 - - - -3V 1215 - - - -4V 1664 972 - - -5V 2099 1721 1164 - -6V 2536 2357 1893 1330 -7V 2984 3021 2737 2335 19078V 3398 3507 3260 2918 30479V 3862 3977 3772 3539 3619

Size060

1V 494 - - - -2V 1046 - - - -3V 1587 - - - -4V 1912 894* 220 - -5V 2769 2107* 1615 - -6V 3189 2791* 2476 2496 15767V 3550 3304* 3101 3238 28518V 3996 3749* 3559 3910 35959V - - 4306 4544 4311

* measured at 30Pa The air volume refers to standard fan coils, with clean air filter, 20 °C room temperature, at sea level and without plenum.

Page 19: TECHNICAL MANUAL - EURAPO · a modulating signal with 0-10Vdc tension in order to regulate the fan speed. OMNIBUS regulators give the possibility to fully control the fan speed (0-100%)

1

2

3

4

5

6

7

8

19

9

7.2 COOLING CAPACITIES, 4 ROwS, AT 25 Pa (*Size 060 at 30 Pa)

ROOM TEMPERATURE: 27 °C d.b. - 48% r.h. - TEMPERATURE wATER: 7/12 °C

Speed 020 030 040 050 060*

1V

Total cooling capacity kW - - - - -

Sensible cooling capacity kW - - - - -

Water flow l/h - - - - -

Pressure drop kPa - - - - -

2V

Total cooling capacity kW - - - - -

Sensible cooling capacity kW - - - - -

Water flow l/h - - - - -

Pressure drop kPa - - - - -

3V

Total cooling capacity kW - - - - -

Sensible cooling capacity kW - - - - -

Water flow l/h - - - - -

Pressure drop kPa - - - - -

4V

Total cooling capacity kW - - - 5,86 7,11

Sensible cooling capacity kW - - - 4,49 4,84

Water flow l/h - - - 1005 1220

Pressure drop kPa - - - 8,1 3,0

5V

Total cooling capacity kW - 4,84 - 9,11 14,71

Sensible cooling capacity kW - 3,68 - 7,47 10,55

Water flow l/h - 830 - 1563 2523

Pressure drop kPa - 9,1 - 18,2 10,8

6V

Total cooling capacity kW 5,48 6,31 8,08 11,44 17,89

Sensible cooling capacity kW 4,07 4,95 6,37 9,85 13,33

Water flow l/h 941 1082 1386 1963 3069

Pressure drop kPa 11,9 14,7 13,9 27,6 16,2

7V

Total cooling capacity kW 6,53 8,07 10,71 13,81 18,55

Sensible cooling capacity kW 5,07 6,61 9,04 11,93 14,75

Water flow l/h 1120 1385 1838 2370 3182

Pressure drop kPa 16,0 23,1 25,6 37,7 20,2

8V

Total cooling capacity kW 7,74 8,85 11,86 15,28 20,77

Sensible cooling capacity kW 6,02 7,11 9,77 13,62 16,64

Water flow l/h 1328 1518 2036 2622 3564

Pressure drop kPa 21,8 26,1 29,2 45,3 23,9

9V

Total cooling capacity kW 8,98 10,4 13,14 16,63 -

Sensible cooling capacity kW 6,95 8,33 10,81 14,8 -

Water flow l/h 1540 1784 2255 2854 -

Pressure drop kPa 28,7 35,1 35,2 53,0 -

10V

Total cooling capacity kW - - - - -

Sensible cooling capacity kW - - - - -

Water flow l/h - - - - -

Pressure drop kPa - - - - -

EN

Page 20: TECHNICAL MANUAL - EURAPO · a modulating signal with 0-10Vdc tension in order to regulate the fan speed. OMNIBUS regulators give the possibility to fully control the fan speed (0-100%)

1

2

3

4

5

6

7

8

20

9

7.3 HEATING CAPACITIES, 4 ROwS, AT 25 Pa (* Size 060 at 30 Pa)

ROOM TEMPERATURE: 20 °C d.b. - 50% r.h. - water temperature: 70/60 °C

Speed 020 030 040 050 060*

1V

Heating capacity [kW] kW - - - - -

Water flow [l/h] l/h - - - - -

Pressure drop [kPa] kPa - - - - -

2V

Heating capacity [kW] kW - - - - -

Water flow [l/h] l/h - - - - -

Pressure drop [kPa] kPa - - - - -

3V

Heating capacity [kW] kW - - - - -

Water flow [l/h] l/h - - - - -

Pressure drop [kPa] kPa - - - - -

4V

Heating capacity [kW] kW - - - 13,62 16,38

Water flow [l/h] l/h - - - 1005 1220

Pressure drop [kPa] kPa - - - 7,1 1,4

5V

Heating capacity [kW] kW - 10,36 - 21,76 34,95

Water flow [l/h] l/h - 830 - 1563 2523

Pressure drop [kPa] kPa - 7,7 - 16,0 5,2

6V

Heating capacity [kW] kW 11,94 13,59 17,43 27,71 43,85

Water flow [l/h] l/h 941 1082 1386 1963 3069

Pressure drop [kPa] kPa 10,1 12,6 12,1 24,3 7,8

7V

Heating capacity [kW] kW 15,01 17,57 24,43 33,33 50,06

Water flow [l/h] l/h 1120 1385 1838 2370 3182

Pressure drop [kPa] kPa 13,6 19,9 22,3 33,5 9,8

8V

Heating capacity [kW] kW 17,95 18,99 27,24 38,15 55,74

Water flow [l/h] l/h 1328 1518 2036 2622 3564

Pressure drop [kPa] kPa 18,7 22,4 25,0 40,4 11,7

9V

Heating capacity [kW] kW 20,96 24,93 30,33 41,68 -

Water flow [l/h] l/h 1540 1784 2255 2854 -

Pressure drop [kPa] kPa 24,5 30,2 30,1 47,2 -

10V

Heating capacity [kW] kW - - - - -

Water flow [l/h] l/h - - - - -

Pressure drop [kPa] kPa - - - - -

Page 21: TECHNICAL MANUAL - EURAPO · a modulating signal with 0-10Vdc tension in order to regulate the fan speed. OMNIBUS regulators give the possibility to fully control the fan speed (0-100%)

1

2

3

4

5

6

7

8

21

9

7.4 ELECTRICAL DATA

Electrical data refer to standard fan coils with clean filter and with 50 Pa of external static pressure. A dirty filter or an external air pressure drop will lower the absorbed power level. The installation of electric accessories increases the absorbed power level.

Absorbed current[A]

Power input[w]

Power supply[v ph-Hz]

Speed 9V 9V

020 1,38 185 230-1-50/60

030 1,04 232 230-1-50

040 1,32 296 230-1-50

050 2,74 617 230-1-50

060 3,37 762 230-1-50

7.5 wORkING OPERATION LIMITS

Each high pressure ducted unit can work properly only if the operating limits listed below are respected:

• Max.operatingpressure(waterside):1,6Mpa• Min.inletcoldwatertemperature:5°C• Max.inletcoldwatertemperature:20°C• Min.inlethotwatertemperature:35°C• Max.inlethotwatertemperature:85°C

In order to select the ESTEBH ducted fancoil with calculating conditions differing form the standard ones or with DISTRICT COOLING coils, please use the EURAPO software for selection.

Note. Some units can present the risk of condensing water sprays if selected under particular calculating conditions in water temperature and relative humidity. In this case it is necessary to modify the calculating parameters or select a different ESTEBH model.

Unit size 060 can be used only with external static pressure >30Pa. For a correct selection of the units, pls use the EURAPO software for selection.

EN

Page 22: TECHNICAL MANUAL - EURAPO · a modulating signal with 0-10Vdc tension in order to regulate the fan speed. OMNIBUS regulators give the possibility to fully control the fan speed (0-100%)

1

2

3

4

5

6

7

8

22

9

8. NOISE LEvELS

8.1 SOUND POwER

The acoustic emission characteristics of any noise source is defined as its «sound power» (SWL). This typical measurement indicates the total radiated energy which does not vary for a given noise source; that is, it does not depend on the observer, location, distance or any other factor which is not part of the source. Following please find the values of the sound power level.

8.2 SOUND PRESSURE IN A CLOSED ENvIRONMENT

The perceived noise radiated from a sound source is something quite different: noise perception is indicated by its «sound pressure» (SPL). Even though it is caused by the emission of a sound energy, it greatly depends on the environment through which the sound travels, on the distance from the source and on all other circumstances that are not directly related to the primary noise source.Besides the distance from the source, the most important factor that influences the «sound pressure» (and, as a result, the perceived noise) in a closed environment is the amount of sound energy reflected off surfaces that have a greater or lesser reflection capacity: it depends, therefore, on the re-transmission of sound energy (power) acting upon reflecting surfaces.Covering the walls with sound absorbing material (i.e. material with a low sound reflecting capacity) is the most effective way to reduce the noise level in a closed environment.The following values indicate the sound pressure emitted by high pressure unit, calculated in open field at 1,5 meter distance and with a reverberation time of 0,3 seconds. By using the EURAPO software for selection it is possible to calculate the new sound pressure level obtained by changing the parameters: room volume, distance from the noise source and reverberation time.The reverberation time measures the sound characteristics of a room: it increases as the room dimensions increase and decreases as the sound absorption capacity of the structure increases.

Page 23: TECHNICAL MANUAL - EURAPO · a modulating signal with 0-10Vdc tension in order to regulate the fan speed. OMNIBUS regulators give the possibility to fully control the fan speed (0-100%)

1

2

3

4

5

6

7

8

23

EN

9

TOTAL SOUND POwER LEvEL (at 25 Pa)

dB(A)Size 020 1V -

2V -3V -4V -5V -6V 58,47V 64,68V 67,69V 66,310V -

Size 030 1V -2V -3V -4V -5V 45,36V 52,07V 59,48V 63,19V 67,410V -

Size 040 1V -2V -3V -4V -5V -6V 56,57V 66,68V 69,59V 71,910V -

Size 050 1V -2V -3V -4V 57,85V 61,36V 64,37V 67,48V 69,79V 7210V -

Size 060* 1V -2V -3V -4V 63,25V 69,46V 73,37V 76,58V 79,49V -10V -

*Measured at 30 Pa

TOTAL SOUND PRESSURE LEvEL

dB(A)Size 020 1V -

2V -3V -4V -5V -6V 44,37V 50,58V 53,49V 52,210V -

Size 030 1V -2V -3V -4V -5V 31,26V 37,97V 45,38V 499V 53,310V -

Size 040 1V -2V -3V -4V -5V -6V 42,47V 52,58V 55,49V 57,810V -

Size 050 1V -2V -3V -4V 43,65V 47,26V 50,27V 53,38V 55,69V 57,810V -

Size 060 1V -2V -3V -4V 49,15V 55,26V 59,27V 62,48V 65,39V -10V -

Page 24: TECHNICAL MANUAL - EURAPO · a modulating signal with 0-10Vdc tension in order to regulate the fan speed. OMNIBUS regulators give the possibility to fully control the fan speed (0-100%)

1

2

3

4

5

6

7

8

24

9

9. ELECTRICAL CONNECTIONSMost frequently used wiring diagrams:

LEGEND (for all the electric diagrams)

M Fan motor X Terminal board

N NeutralEV Regulating valve: EVC for cooling; EVH for heating

L Phase PC Condensate pump

PE Earth Summer/Winter switch

PR Power Relay card

EST - CBL00

EST - CBL00 - EvC- EvH

Page 25: TECHNICAL MANUAL - EURAPO · a modulating signal with 0-10Vdc tension in order to regulate the fan speed. OMNIBUS regulators give the possibility to fully control the fan speed (0-100%)

1

2

3

4

5

6

7

8

25

EN

9

EST - CBL10 - EvCM - EvHM

EST - CBL00 - EvC - EvH - MASTER/SLAvE

Page 26: TECHNICAL MANUAL - EURAPO · a modulating signal with 0-10Vdc tension in order to regulate the fan speed. OMNIBUS regulators give the possibility to fully control the fan speed (0-100%)

1

2

3

4

5

6

7

8

26

9

EST - CBL00 - EvC - EvH - PC

EDCR - EST - CBL00 - EvC - EvH

Page 27: TECHNICAL MANUAL - EURAPO · a modulating signal with 0-10Vdc tension in order to regulate the fan speed. OMNIBUS regulators give the possibility to fully control the fan speed (0-100%)

1

2

3

4

5

6

7

8

27

EN

9

OBT50 - EvC

Page 28: TECHNICAL MANUAL - EURAPO · a modulating signal with 0-10Vdc tension in order to regulate the fan speed. OMNIBUS regulators give the possibility to fully control the fan speed (0-100%)

Eurapo SrlVia A. Malignani, 1233170 Pordenone - ItalyT +39 0434 572552F +39 0434 [email protected]

As programs and technologies are always improving, description, data and drawings must be intended as merely indicative and can be modified without any notice.

6MT0

310

- EN