temperature analysis for earth air heat exchanger
TRANSCRIPT
Temperature analysis for Earth air heat exchanger
Baljit Singh #1, Arun Kumar Asati *2 Rakesh Kumar#3 #1Ph.D Research Scholar, Department of Mechanical Engineering IKGPTU Kapurthala, Punjab, India.
#3IET Bhaddal, Ropar Punjab, India 1 [email protected] [email protected]
*Department of Mechnaical Engineering, SBSSTC, Ferozepur, Punjab, India. SBSSTC, Ferozepur, Punjab, India.
Abstract—Now a days save electricity is major concern for societal needs. Various Conventional methods used for to save environment. To make comfort environment many techniques used like thermal comfort. The use of geothermal energy is the best way to make environment healthy for mankind and to reduce the demand of electricity which is increasing day by day. The Earth Air Heat Exchanger system is a best passive technology to the use of geothermal energy. The investigation shows the major temperature drop of 8.9 °C corresponding to inlet temperature (Tin) 41.9 °C on date 31 March 2017, minor drop of 1.1 °C corresponding to inlet temperature (Tin) 26.2 °C on date 5 April 2017. In this research paper efforts will be made to study the accomplishment of low cost cooling system for hot-dry climate.
Keyword - Geothermal energy, Passive, climate.
I. INTRODUCTION
This type of heat exchanger is good for making environment comfort for human beings. It uses the undisturbed temperature of earth for cooling the room. The undisturbed temperature remains constant. It consists of group of buried pipes under the earth through which the air passed through a fan or blower. The material of the pipe may be Poly Vinyl Chloride (PVC), Mild Steel and Concrete. The design parameters that impact the evaluation of this system are: pipe depth, pipe length, pipe diameter, air velocity, air flow rate, pipe material, pipe arrangement [1]. In this paper the Earth Air Heat Exchanger (EAHE) system is studied for hot-dry climate. Air-conditioning systems is the largest energy consumer that is the biggest challenge which arisesnow days. This problem can be overcome by the use of ground coupled heat exchanger in air conditioning system [2]. It suitably meets heating and cooling energyloads of a building. Its performance is based uponthe seasonally varying inlet temperature, and out lettemperature which further depends on the groundtemperature [3].
This heat exchanger built by burying in the ground at a particular depth so that the required cooling and heating can be achieved from system. This air is often outside air for ventilation, but also useful for partially or totally managing thermal loads of construction [4]. In present research study efforts will be made to save electricity by proper set-up of EAHE in spite of using other conventional systems in houses.
The climatic conditions and parameters used strongly affect this system. The modifications of the system depend upon the variation in the parameters used [5]. The set up is free from any dust particles enter into the pipe of heat exchanger which block the passage of air through the pipe.
A large amount of the primary energy is consumed by space heating and cooling in buildings/houses. The requirement of huge renewable energy in the building sector and industrial establishments is the demand for sustainable energy and environments. Geothermal energy is one of the renewable energy sources that we utilised for supplying air at low expense of energy and with a low impact on the environment [6]. The utilizing styles and exploring methods are various, geothermal electricity, ground source heat pump, earth to air heat exchanger (EAHE), etc. are the main application measures. Among them, an EAHE has the advantages of simple system, easy implementation and low operation cost [7].
The use of earth as a component of energy system can be accomplished through three primary methods: direct, indirect and isolated. In direct system, the building is in contact with the earth through the pipes and fresh air form the environment maintains the comfort temperature. In the indirect system, the building interior is cooled by a low cost cooling system or by an earth air tunnel heat exchanger. The isolated system uses the geothermal temperature of earth to enhance the effectiveness of a heat pump by moderating temperatures [8].
The ground temperatures at several depths can be measured, the overall heat transfer coefficient (overall HTC) can be determined; the heat exchange rate quantified. The HGHE consists of 50 m of length buried at 1 m of depth. The energy and exergy analysis of horizontal ground heat exchanger (HGHE) for hot climatic conditions can be determined [9]. The objective of this study is to found a low cost cooling system with the help of this passive method of cooling for ho-dry climate.
ISSN (Print) : 2319-8613 ISSN (Online) : 0975-4024 Baljit Singh et al. / International Journal of Engineering and Technology (IJET)
DOI: 10.21817/ijet/2017/v9i5/170905188 Vol 9 No 5 Oct-Nov 2017 3958
II. EXPERIMENTAL SET-UP AND INSTRUMENTATIONS
It consists of burial concrete pipe of diameter 0.224 m and is buried in the soil at a distance of 1.5 m. The one end of buried pipe is open to the fields and other end is in the room for testing. A blower is connected to the open end of pipes which deliever air to the room for study. The temperature will be measured with the help RTDs of 0.5°C accuracy and least count 0.1°C, range 0-100°C. The RTDs are connected at two different points. One at the inlet to the pipe and other is at the outlet of the pipe. The arrangement of different instruments used for the investigation of the complete system shown in fig 1.
Fig 1.Schematic Diagram of the experimental set-up
III. METHODOLOGY
The EAHE system is switch on and air is flows through the pipes from inlet to outlet from time 7.30 am to 4.00 pm on eight days i.e 29 March 2017 to 5 April 2017. The temperature reading is noted for every half hour. The dry bulb temperature is noted at two points. The buried pipes and temperature indicators are shown in Fig 2.
Fig 2.the buried pipes and temperature indicator used for study.
IV. RESULTS & DISCUSSIONS
A. EFFECT OF TEMPERATURE
In the study of earth air heat exchanger temperature difference between the inlet temperature (Tin) and outlet temperature (Tout) plays an important role. The temperature drop of 2.1 °C is observed at 8.00 am which is caused by minor difference in inlet temperature and soil temperature. The inlet temperature line rapidly goes on increasing after 9.00 am due to rise in Tin temperature from value 30.6 °C to 32.3 °C. The drop of only 0.2 °C is available from time 11.00 am to 11.30 pm which is because of less heat transfer between air and soil at that time. The major drop of temperature is 7.4 °C experienced after 1.30 pm because of excess rise in Tin to value 36.4 °C. The maximum temperature drop is available because of maximum difference in inlet temperature and soil temperature which increasing the rate of heat transfers from air in the pipe and the soil. The lines of temperatures Tin and Tout come closer and closer after 3.00 pm and the fall is equal to 5.4 °C due to decrease in inlet temperature and undisturbed temperature of earth. The undisturbed temperature of the earth is that temperature which remains almost constant throughout the year.
ISSN (Print) : 2319-8613 ISSN (Online) : 0975-4024 Baljit Singh et al. / International Journal of Engineering and Technology (IJET)
DOI: 10.21817/ijet/2017/v9i5/170905188 Vol 9 No 5 Oct-Nov 2017 3959
The dropThe fall temperatu°C of theof 2:00 pmaximumshows thsets in ev
The inletat that timoutdoor ctemperatuMinimumand the presistance
p of temperatuof temperaturure 36.3 °C at
e summer daypm is 8.1 °C. Tm heat transfehat difference vening. Also d
t temperature me and fall isclimatic condure of environ
m temperaturepipe surface ie.
Fig
ure is low aftre is constant t that time. A. Therefore froTherefore thiser depends upis reducing af
difference in te
Fig
line after 10.3s equal to 5.5ditions. The Tnment. Maxime difference atis calculated
g 3.Variation of ti
er 8.30 am caand equal to
As we know thom the figures study is compon the differefter 2.00 pm aemperature ob
g 4.Variation of ti
30 suddenly b °C. The perf
Tin curve of temum temperatt the time 8.0using the gen
me vs. temperatu
aused by hot 7.4 °C from
he maximum o 4 it is found
mpletely validaence of two tas the environmbserved at the
me vs. temperatu
ends downwaformance of eemperature exture difference00 am is 2.5 °neral heat tran
ure on 29 March 2
waves passingtime 1.00 pm
outdoor tempethat the maximating the resuemperatures. ment temperatime of 4.00 p
ure on 30 March 2
ards which is bearth air heat xtends upwarde on this day C. The heat tnsfer equation
2017
g near blowerm to 1.30 pm erature at the tmum drop of lts obtained frThe trends of
ature goes on pm is 6.5 °C.
2017
because of woexchanger is
ds after 12.00 at the time oftransfer at then, assuming t
r during mornthis is due totime of 2:00 ptemperature a
from the experf two lines Ti
decreasing wh
orse climatic cgreatly affectpm because
f 2.00 pm is 8e interface betthat there is n
ning time. o same Tin pm is 36.6 at the time riment the in and Tout hen sun is
conditions ted by the of rise in
8.9 °C and tween soil no contact
ISSN (Print) : 2319-8613 ISSN (Online) : 0975-4024 Baljit Singh et al. / International Journal of Engineering and Technology (IJET)
DOI: 10.21817/ijet/2017/v9i5/170905188 Vol 9 No 5 Oct-Nov 2017 3960
The variaFerozepuEAHE reworse enand dropdifferencas shownthe air flo
differencam as scontinuou°C is avadrop of that that timThe inlet6.7 °C wThe drop
ation in two cur. Therefore eveals that thenvironmental cp of temperatuce after the timn in Figure 6. ow direction (
The temperatce (Tin-Tout) ofhown figure usly shows inailable at timehe day is avaime. This maxt temperature
which occurs bp of 5.5 °C is o
Fig
curves of Tin athe inlet tem
e performanceconditions anure varies fromme of 1.30 pm
The temperatu(inside the hea
Fi
ture observatif 2.2 °C is obs
7. The diffencreasing trene 10.30 am belable at 1.30 p
ximum fall of(Tin) of 3.00 p
because of decobserved at th
g 5.Variation of ti
and Tout on thmperature variee of system cand passing awm 5.6 °C to 6
m is 8.2 °C andures of soil, aat exchanger).
ig 6.Variation of t
ions on 2 Apserved becauseerence of inlds with increa
ecause of inletpm is 8.4 °C cf temperature pm shows varcrease in inlet
he time of 4.00
me vs. temperatu
hat day showses and corres
an be improveway of clouds 6.9 °C from 1d minimum temair and heat ex
time vs. temperat
pril 2017 aree of morning tlet temperatuase in environt temperature correspondingobserved due
riation in downt temperature
0 pm.
ure on 31 March 2
s abrupt changsponding outled by making
the temperatu1.00 am to 12mperature difxchanger and
ture on 1 April 20
e shown in fitime at the inlre (Tin) and nment temperis reaches to to maximum
e to excess henward directioto value 37.1
2017
ges caused byet temperatursystem compure after 10.32.00 pm. The fference at the the heat trans
017
igure 7. The let and outlet temperature
ature. The fal35.9 °C at thenvironment
eat transfer beon with tempe1 °C and there
y rain in somere varies. Theletely dust fre0 am changesmaximum tem time 8.00 amfer rate also v
minimum temof the pipe at of tested ro
ll of temperatuhat time. The m
temperature oetween the airerature drop oefore less hea
e areas of e study of ee. Due to s abruptly mperature
m is 2.9 °C vary along
mperature time 8.00 om (Tout) ure of 6.0 maximum of 39.3 °C r and soil. of equal to at transfer.
ISSN (Print) : 2319-8613 ISSN (Online) : 0975-4024 Baljit Singh et al. / International Journal of Engineering and Technology (IJET)
DOI: 10.21817/ijet/2017/v9i5/170905188 Vol 9 No 5 Oct-Nov 2017 3961
is suddenoutlet tem33.3 °C icurve is bmaximumconstructconcrete.fall is incthe differand beco
increasinThis is duis observtemperatuand less change ienvironmconsidera
The time vs. nly deflected mperature (Tou
instead of 31.bending to dowm drop of thetion of earth a. The inlet tecreasing continrence in inlet
omes almost co
Figure 9 showng in continue ue morning tim
ved from 9.00 ure is changechange in env
in the inlet ament temperatuably.
Fi
temperature pupwards at 9
ut) is 29.1 °C. .5 °C at 9.00 wnward direc
e day availablair heat exchanemperature reanuously as thetemperature
onstant to valu
Fi
ws the tempemanner. The me and differam to 9.30 ams from 4.4 °Cvironment temand outlet valure of the day
ig 7.Variation of t
plots on date 39.00 am due t
The fall is 1.am. The temp
ction at time 1le at 2.30 pmnger as other raches to 40.3 e day reaches (hot) and soilue 7.5 °C to 7
ig 8.Variation of t
erature variatiminimum temence in soil tem is because oC to 5.4 °C fromperature. Thlues of temp
y is 37.2 °C at
time vs. temperat
3 April 2017 ato rise in inle7 °C more thaperature fall o.30 pm is bec
m is 8.5 °C anresearchers us°C at 3.00 pmto peak heati
l temperature 7.0 °C from tim
time vs. temperat
ions on 4 Apmperature dropemperature anof small rise inom time 10.0
he reading of terature at the
t 2.00 pm. The
ture on 2 April 20
are shown in ft temperaturean 2 April 201of 7.5 °C is obause of cool a
nd increases bsed the PVC pm and correspng of the day.(cold) is incr
me of 3.30 pm
ture on 3 April 20
ril 2017. Thep of 2.3 °C is
nd environmenn environmen0 am to 10.30two temperatue time of 2.0e environment
017
fig 8. The cure (Tin) is 33.3 17 as the envibserved after air prevailing because of usepipes whose cponding fall o. The increasereases. Fall of
m to 4.00 pm.
017
e inlet temperas usually ob
nt temperaturent temperature0 am is due toures Tin and T00 pm is 8.0t conditions a
rve of inlet tem°C and corre
ronment temptime of 12.00around the bloe of concrete
conductivity isobserved is 8.e in heat transf temperature
rature (Tin) onserved at time
e. A small falle of 0.9 °C. Tho same conditTout shows con0 °C as the maffect the EAH
mperature esponding perature is 0 pm. The ower. The pipes for
s less than 1 °C. The fer rate as decreases
n this day e 8.00 am. of 0.3 °C he drop of tion of air nsiderable maximum
HE system
ISSN (Print) : 2319-8613 ISSN (Online) : 0975-4024 Baljit Singh et al. / International Journal of Engineering and Technology (IJET)
DOI: 10.21817/ijet/2017/v9i5/170905188 Vol 9 No 5 Oct-Nov 2017 3962
A figureavailableincreasinenvironmtime 12.330.4°C apipes mamoisture temperatu2.00 pm.
The averof averagMarch 20temperatuThe averall other average TThe fall oon 1 Apr°C is 6.1temperatu
10 shows ate is 1.1 °C. Tng in morningment temperatu30 pm to 1.00and correspondaximizing the
through condure rises to 3
rage temperatuge fall vs. no. 017 is equal ture of 27.3 °Cage inlet tempdays. The am
Tin of 37.2 °Cof temperaturril 2017. On 2 1 °C. The aveure is 30.0 °C
Fi
t 8.00 am theThe drop tempg hours, dropure decreases
0 pm which cading maximumair to wall codensation. Th0.4°C only. T
Fig
ure fall vs. noof days provi
to is 5.5 °C wC. The fall ofperature curvemplitude of a
C on 31 marchre decreases by
April 2017 therage inlet tem
C correspondin
ig 9.Variation of t
e inlet tempeperature is 1.9p is rises to from peak ho
aused by worsm fall observe
ontact for comhe 5 April 201The drop decr
g 10.Variation of
o. of days showide more clearwhich is becauf 5.7 °C is obse extends upwaverage inlet h 2017 and coy 0.4 °C due
he average inlemperature 36ng maximum
time vs. temperat
erature (Tin) i9 °C at the ti
maximum vours of the dase climatic coned is 5.7 °C d
mplete heat exc17 is coolest reases as the e
f time vs. tempera
ws in figure 1r and concise use of averagserved on 2nd
ward after 3rd dtemperature rresponding mto decrease inet temperature
6.5 °C which fall than othe
ture on 4 April 20
s 26.2 °C at ime of 8.30 a
value in peakay. Temperatunditions. The due to the air change and, inday as compaenvironment t
ature on 5 April 2
11 from date 2picture of teme Tin temperaday caused by
day which givecurve is max
maximum dropn average Tin te is 35.8 °C anis maximum
er days is 6.5
017
this temperaam. The tempk hours and ure fall of only
maximum vacrashes arounn the summerared to other temperature d
017
29 March to 5mperature variature of 33.8 °y velocity of aes the indicati
ximum this is p of temperattemperature frnd average outhan other da°C which bec
ature the miniperature drop drop decreasy 0.1 °C obseralue of Tin at 2nd constantly r, removal of days because
decreases after
5 April 2017. iations. The d°C air and avair 2.5 m/s onion of warmer
because of mture 6.6 °C onrom 37.2 °C t
utlet temperatuays and averacause of maxi
imum fall is slowly es as the rved from 2.00 pm is inside the excess air e the inlet r the time
The plots drop on 29 erage Tout
n that day. r day from maximum n that day. to 36.1 °C ure is 29.7 age outlet imum rate
ISSN (Print) : 2319-8613 ISSN (Online) : 0975-4024 Baljit Singh et al. / International Journal of Engineering and Technology (IJET)
DOI: 10.21817/ijet/2017/v9i5/170905188 Vol 9 No 5 Oct-Nov 2017 3963
of heat tris less asis 5.4 °Ccorresponchanges i
The fitemperatumay helploss of enstate of resourcescorresponinlet temp
Authofor the reof Dr Aruthank DrBhaddal,
[1] BhogExchn
[2] Naik 2016
[3] ManjuCond
[4] TyagiMech
[5] Patel Perfor
[6] Niu Fof ear
[7] Lund [8] Kaur
Excha[9] Naili
excha
ransfer betwee compared to
C. The lines ofnding drop in in the tempera
indings from ure found map us lot in futunergy can be Punjab and ths not implemnding to inlet perature (Tin)
ors are thankfuesearch work.unKumar Asar. Rakesh Ku Roparwho he
e Dipak &Nadafnager ” IJLTET, VB. Devaraj& MuIRJET, Volume 3ul Ravi Ranjan&itions — A Reviei Vishal kumar (
hanical EngineerinRakesh D and Rrmance in Heatin
Fuxin, Yu Yuebinrth to air heat excJW, Freeston DHJagjeet, Singh Pranger System” EnNabiha, Hazam
anger forhot clima
en inlet (hot) day 2 due to f plots bend itemperature i
atures and hea
Earth air heaany benefits liure in the fielminimized wherefore the
mented at stattemperature (26.2 °C on da
ul to the IKG P The investig
ati, Associate umar, Associelped me a lot
f Sameer (2016)Volume 6, Issue undlaSubba Redd3, Issue 12.
&Bartaria V.N (2ew” MAY 2016 I(2016), “Experimng (JMSME) p-ISRamana P. V. (2ng Climate Condin, Yu Daihong, Lichanger” Applied H, Boyd TL (2005rem, Kaur Harminvironmental Sus
mi Majdi, Kooli atic condition of
temperature afewer rises inin downward is less and equat transfer rate
Fig 11. Average
V.
t exchanger bike energy savld of renewab
with the help sPunjab can bte level. The (Tin) 41.9 °C oate 5 April 20
ACKN
Punjab Technations of EartProfessor, Sh
iate professort at every step
, “A Review on4, March 2016.
dy (2016), “Resea
2016), “Earth AirIJETT, Volume 3
mental PerformanSSN: 2393-9095;2016), “Experimeition” ISSN: 2455i Haorong (2015)Energy 137 (201
5) “Direct applicander (2015), “A stainability: ConcSami, Farhat Abnorthern Tunisia”
and soil (cold)n average inletdirection on ual to 3.9 °C
e along the pip
e temperature fall
CONCLUSI
brings us that ving, money ible energy ressuch type of sbecome energ
investigationon date 31 M17.
NOWLEDGM
nical Universitth Air Heat Ex
haheed Bhagatr and Head o of my researc
REFERENCES
n performance en
arch Review on E
r Heat Exchange35, Issue 8. nce Analysis of E; e-ISSN: 2393-9ental Performanc5-3689, IJRTEM,), “Heat and mass15) 211–221. ation of geothermReview on the Ex
cepts, Principles, bdelhamid (2015” ISSN: 2455-368
) temperaturet temperature.day 8 shows as shown in f
pe are not line
l vs. No. of days.
ION
technology ois saving and sources whichsystems. The gy crisis state n shows the arch 2017, mi
MENT
ty, Kapurthalaxchanger mayt Singh State Tof Mechanicach.
S nhancement of A
Earth Pipe Air C
er Performance i
Earth Air Heat E109; Volume 2, Ice of Buried Tub, Volume 1 Issue s transfer perform
mal energy” Geothxperimental and Evidences and In5), “Energy and 89, IJRTEM, Vol
. The drop of . The drop of that it is cool
figure 11. It caear.
of varying temenvironment
h is peak demause of EAHEin few years
major tempeinor drop of 1
a for giving uy not be fulfilTechnical Camal Engineerin
Air conditioner U
Conditioning Syst
in Summer Cool
Exchanger” JournIssue 14; Octoberbe Heat Exchang1, Feb. 2016, pp
mance analysis an
hermics 2005; 34Analytical Analy
nnovations - ISBNexergy analysis
lume 1 Issue 1, F
f temperature otemperature aler than other an be observe
mperature witsaving. Thes
and of the socE is very limis; if renewabrature drop o
1.1 °C corresp
s this opportulling with the mpus, Ferozepg Departmen
Using Earth Air
tem” ISSN: 2395
ing For Various
rnal of Material r-December, 2015ger Validated by01-05.
nd cooling capacit
4(6):691–727. ysis of Earth Air TN: 978-93-83083s of horizontal g
Feb. 2016, pp 01-0
on 7th day at that day
days and ed that the
th the soil e benefits ciety. The ited in the ble energy of 8.9 °C ponding to
unity to go kind help
pur. I also nt at IET,
Tunnel heat
-0072, DEC
Supply Air
Science and 5, pp 40-44. y Simulation
ty prediction
Tunnel Heat -75-6. ground heat 05.
ISSN (Print) : 2319-8613 ISSN (Online) : 0975-4024 Baljit Singh et al. / International Journal of Engineering and Technology (IJET)
DOI: 10.21817/ijet/2017/v9i5/170905188 Vol 9 No 5 Oct-Nov 2017 3964
AUTHOR PROFILE
Baljit Singh is Ph.D Research Scholar, Department of Mechanical Engineering, IKGPTU Kapurthala, Punjab, India. He is working in the department of Mechanical Engineering in SBSSTC, Ferozepur, Punjab,India. He has 8 years of teaching experience. He has specialisation in Material, Coating and Thermal Engineering.
Dr. Arun Kumar Asati is working as Associate Professor at SBSSTC, Ferozepur, Punjab,India. He completed his Ph.D from IIT, Delhi. He has 30 years experience in the field of teaching. He has specialization in thermal engineering. He is very hard working. He has published many research publications in international journals and international conferences.His areas of interests are Heat Transfer, Refrigeration and Air Conditioning, Thermodynamics and Desiccant Cooling.
Dr. Rakesh Kumar is working as Associate Professor and Head of Mechanical Engineering Departmentat IET, Bhaddal, Ropar, Punjab. He completed his Ph.D from IKGPTU, Kapurthala in 2016. He has more than 16 year teaching experience in the field of Mechanical Engineering. His areas of interests are Heat Transfer, Refrigeration and Air Conditioning, Micro tubes and Thermal Engineering. He has published many research papers in international journals and conferences.
ISSN (Print) : 2319-8613 ISSN (Online) : 0975-4024 Baljit Singh et al. / International Journal of Engineering and Technology (IJET)
DOI: 10.21817/ijet/2017/v9i5/170905188 Vol 9 No 5 Oct-Nov 2017 3965