temperature and humidity sensors - stulz | climate...

4
T e c h n o l o g y & E v o l u t i o n Temperature and humidity sensors

Upload: truongdang

Post on 26-Jun-2018

245 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Temperature and humidity sensors - STULZ | CLIMATE ...nl.stulz.com/repository/67528BE2/Sensors_Brochure_0219_en.pdf · DP series temperature & humidity sensors room, industrial and

T e c h n o l o g y & E v o l u t i o n

Temperature andhumidity sensors

Page 2: Temperature and humidity sensors - STULZ | CLIMATE ...nl.stulz.com/repository/67528BE2/Sensors_Brochure_0219_en.pdf · DP series temperature & humidity sensors room, industrial and

DP series temperature & humidity sensorsroom, industrial and duct

CAREL proposes the new DP series range of active

temperature and humidity sensors, available for rooms,

industrial applications and ducts, designed for the

residential and light industrial HVAC/R market.

The new range extends the number of models with

0 to 10 V and RS485 serial output (Modbus® and CAREL).

The RS485 version allows up to 32 sensors to be connected

to the same local network, thus optimising the use of the

I/Os on the controller, and simplifying wiring, with

signifi cant cost savings.

One important new feature is the case that houses the

sensors for industrial applications and ducts, with IP55

index of protection, and simplifi ed opening and protection

of the electronic board that is separate from the case

fastening screws.

General specifi cations

Power supply 9 to 30 Vdc / 12 to 24 Vac tol. -10%, +15%Output signal 0 to 1 V / -0.5 to 1 V / 4 to 20 mA

0 to 10 VNTC 10K @ 25 °CRS485 serial (Modbus® RTU and CAREL protocol)- up to 32 addresses;- Baud rate 9600/19200 Bit/sec;- opto-isolated output;- Dew point variable on supervisor

Operating range room -10 to 60°C / 10 to 90 rH%industrial & duct -10 to -60 °C / 10 to 90 rH%

-20 to 70 °C / 0 to 100 rH%Index of protection room IP30

industrial IP55 / (sensor IP54)duct IP55 / (sensor IP40)

For other specifi cations, see the manual.

Page 3: Temperature and humidity sensors - STULZ | CLIMATE ...nl.stulz.com/repository/67528BE2/Sensors_Brochure_0219_en.pdf · DP series temperature & humidity sensors room, industrial and

up to 32 sensors

Field-BusRS485

Field-BusRS485

Field-BusRS485

touch screengraphic display

RS485

up to 32 sensors

RS485

up to 32 sensors

BMS

70°C

-20°C

70°C

up to32 sensors

0...10 VRS485

0...10 VRS485

IP55IP55

DP series temperature & humidity sensorsroom, industrial and duct

Temperature and humidity sensors

with digital technology

Models with 0 to 10 V & RS485 output, with

Modbus® or CAREL protocol, addresses for up to 32 sensors

Simplifi ed opening of the case for industrial

and duct version

Extension of the temperature and

humidity range to -20T70°C

White plastic to better

suit the installation

environment.

For non-standard

confi gurations,

take off the

protective cover by

removing the screws.

Protection of the

electronic board.

Only the connection

terminals can be

accessed.

Fastening screws

separated from the

electronic board.

Cover opened and clo-

sed by simply twisting.

Example of connecting the RS485 serial sensors

Page 4: Temperature and humidity sensors - STULZ | CLIMATE ...nl.stulz.com/repository/67528BE2/Sensors_Brochure_0219_en.pdf · DP series temperature & humidity sensors room, industrial and

30

127

80

8322 22

4040

CAREL S.p.A.Via dell’Industria, 11 - 35020 Brugine - Padova (Italy)Tel. (+39) 0499 716611 - Fax (+39) 0499 [email protected] - www.carel.com

Dimensions (mm)

Room sensor Sensor for industrial applications

+302

2395

11 -

1.0

- 07.

02.2

008

© C

ARE

L S.

p.A

. 200

8 al

l rig

hts

rese

rved

CA

REL

rese

rves

the

right

to m

odify

or c

hang

e its

pro

duct

s w

ithou

t prio

r not

ice.

Codes and comparison to the AS* seriesROOM VERSIONCode Room version, 0 to 1 V / -0.5 to 1 Vdc/4 to 20 mA output Corresponding code in AS versionDPWT010000 Temperature (-10T60 °C) ASWT030000DPWT011000 Temperature (-10T60 °C) (output: CAREL NTC only) ASWT011000DPWC111000 Temperature (-10T60 °C) (output: CAREL NTC only) and humidity (10 to 90% rH) ASWC111000 ASWH100000** (**humidity only)DPWC110000 Temperature (-10T60 °C) and humidity (10 to 90% rH) ASWC110000

Room version, 0 to 10 Vdc outputDPWC115000 Temperature (-10T60 °C) (output: CAREL NTC only) and humidity (10 to 90% rH) ASWC115000DPWC112000 Temperature (-10T60 °C) and humidity (10 to 90% rH) ASWC112000

Room version, optically-isolated RS485 serial output DPWC114000 Temperature (-10T60 °C) and humidity (10 to 90% rH) -DPWT014000 Temperature (-10T60 °C) -

INDUSTRIAL VERSIONCode Industrial version, 0 to 1 V / -0.5 to 1 Vdc/4 to 20 mA output Corresponding code in AS versionDPPT010000 Temperature (-20T70 °C) -DPPT011000 Temperature (-20T70 °C) (output: CAREL NTC only) ASPT011000DPPC111000 Temperature (-10T60 °C) (output: CAREL NTC only) and humidity (10 to 90% rH) -DPPC110000 Temperature (-10T60 °C) and humidity (10 to 90% rH) ASPC110000DPPC210000 Temperature (-20T70 °C) and humidity (0 to 100% rH) ASPC230000/ASPC2300I0

Industrial version, 0 to 10 Vdc outputDPPC112000 Temperature (-10T60 °C) and humidity (10 to 90% rH) -DPPC212000 Temperature (-20T70 °C) and humidity (0 to 100% rH) -

Industrial version, optically-isolated RS485 serial output DPPT014000 Temperature (-20T70 °C) -DPPC114000 Temperature (-10T60 °C) and humidity (10 to 90% rH) -DPPC214000 Temperature (-20T70 °C) and humidity (0 to 100% rH) -

DUCT VERSIONCode Duct version 0 to 1 V / -0.5 to 1 Vdc/4 to 20 mA output) Corresponding code in AS version DPDT010000 Temperature (-20T70 °C) ASDT030000DPDT011000 Temperature (-20T70 °C) (output: CAREL NTC only) ASDT011000DPDC111000 Temperature (-10T60 °C) (output: CAREL NTC only) and humidity (10 to 90% rH) ASDC111000DPDC110000 Temperature (-10T60 °C) and humidity (10 to 90% rH) ASDC110000 ASDH100000** (**humidity only)DPDC210000 Temperature (-20T70 °C) and humidity (0 to 100% rH) ASDC230000 ASDH20000** (**humidity only)

Duct version 0 to 10 Vdc outputDPDC112000 Temperature (-10T60 °C) and humidity (10 to 90% rH) -DPDC212000 Temperature (-20T70 °C) and humidity (0 to 100% rH) -

Duct version optically-isolated RS485 serial outputDPDT014000 Temperature (-20T70 °C) -DPDC114000 Temperature (-10T60 °C) and humidity (10 to 90% rH) -DPDC214000 Temperature (-20T70 °C) and humidity (0 to 100% rH) -

Note: 1. Neutral versions available upon request (CAREL codes DP*******N); 2. Custom front logo available upon specific request

Duct sensor

72

72

44

170

45

mounting holes

98

105

PG9

CH19

Ø 16

272

336

20

Ø 1

6

61

120°120°

25

42

98

105

PG9

CH19

No.3 holes Ø 2,75 (non-threaded)

Ø 17

44

37,5

43,3= =