the cooling and heating potential of an earth tube system in buildings
TRANSCRIPT
The cooling and heating potential of an earth tube system in buildings
Kwang Ho Lee *, Richard K. Strand
University of Illinois at Urbana-Champaign, Champaign, IL, United States
Received 3 September 2006; received in revised form 3 April 2007; accepted 13 April 2007
www.elsevier.com/locate/enbuild
Energy and Buildings 40 (2008) 486–494
Abstract
A new module was developed for and implemented in the EnergyPlus program for the simulation of earth tubes. The model was validated
against and showed good agreement with both theoretical and experimental data. Using the new module, a parametric analysis was carried out to
investigate the effect of pipe radius, pipe length, air flow rate and pipe depth on the overall performance of the earth tube under various conditions
during cooling season. Pipe length and pipe depth turned out to affect the overall cooling rate of the earth tube, while pipe radius and air flow rate
mainly affect earth tube inlet temperature. The cooling and heating potential of earth tubes in four different locations were also investigated.
Whether or not an earth tube is beneficial turned out to be heavily dependent on the climate of the location.
# 2007 Elsevier B.V. All rights reserved.
Keywords: Earth tube; EnergyPlus; Parametric analysis; Cooling and heating potential
1. Introduction
The utilization of geothermal energy to reduce heating and
cooling needs in buildings has received increasing attention
during the last several years. An earth tube is a long,
underground metal or plastic pipe through which air is drawn.
As air travels through the pipe, it gives up or receives some of its
heat to/from the surrounding soil and enters the room as
conditioned air during the cooling and heating period.
Due to the significance of earth tube system, numerous
research studies have been performed by Krarti et al. (1995) [1],
Puri (1986) [5] and Labs at al. (1989) [2]. Krarti (1995)
developed the model to determine the annual mean soil surface
temperature and amplitude of soil surface temperature, which is
essential to the calculation of soil surface temperature. Labs [2]
developed the model to determine the soil temperature at
various depths and elapsed time using the annual mean soil
surface temperature and the amplitude of soil surface
temperature. Recently, a sophisticated model describing the
complex mechanisms of simultaneous heat and mass transfer
occurring around the earth tube has been developed and
integrated into TRNSYS by Mihalakakou et al. (1995) [4].
* Corresponding author at: 711 W. Main Street #6, Urbana, IL 61801, United
States. Tel.: +1 217 419 6067.
E-mail address: [email protected] (K.H. Lee).
0378-7788/$ – see front matter # 2007 Elsevier B.V. All rights reserved.
doi:10.1016/j.enbuild.2007.04.003
Nevertheless, those research studies have focused either on
heat transfer to/from the surrounding soil or on the prediction of
soil temperature separately. To date, a detailed algorithm
calculating the soil temperature variation around the earth tube
directly from weather data files has not been encoded within an
existing simulation tools. Since an accurate ground temperature
prediction is also an essential factor for the simulation of an
earth tube, both the heat transfer occurring around the earth
tube and the soil temperature should be modeled together in
order to successfully simulate an earth tube. In order to
compute the soil temperature surrounding the earth tube and the
subsequent heat transfer rate, three important parameters
should be determined: annual mean ground surface tempera-
ture, amplitude of the annual soil surface temperature variation
and the phase constant of the soil surface. The existing
algorithms require users to input these three values, but finding
out these three values is another big challenge for users and it is
done by experiments in most cases. In this circumstance, the
new model is developed to calculate those three parameters
directly from the weather data file in this study.
The objective of this paper is to discuss the development and
implementation of a new module handling both the heat
transfer and soil temperature algorithms into the EnergyPlus
program for the simulation of earth tubes. The model is
validated against the data from other studies. Also, using the
new model, the effects of four parameters on the overall
performance of the earth tube is quantitatively assessed through
the parametric analysis. In addition, the cooling and heating
Nomenclature
a constant (103 Pa/8C)
As amplitude of the soil surface temperature varia-
tion (8C)
b constant (609 Pa)
Ca specific heat of air (J/kg 8C)
f fraction of evaporation rate
hc convective heat transfer coefficient at the inner
pipe surface (W/m2 8C)
hs convective heat transfer coefficient at the soil
surface (W/m2 8C)
kair thermal conductivity of the air (W/m 8C)
kp pipe thermal conductivity (W/m 8C)
ks soil thermal conductivity (W/m 8C)
L pipe length (m)
ma mass flow rate of ambient air through pipe
(kg/s)
ra relative humidity
r1 inner pipe radius (m)
r2 pipe thickness (m)
r3 distance between the pipe outer surface and
undisturbed soil (m)
Rc thermal resistance due to convection heat transfer
between the air in the pipe and the pipe inner
surface (8C/W)
Rp thermal resistance due to conduction heat tra-
nsfer between the pipe inner and outer surface
(8C/W)
Rs thermal resistance due to conduction heat transfer
between the pipe outer surface and undisturbed
soil (8C/W)
Rt total thermal resistance between pipe air and soil
(8C/W)
DR radiation constant (63 W/m2)
Sm average solar radiation (W/m2)
Sv amplitude of the solar radiation (W/m2)
t time elapsed from beginning of calendar year
(days)
t0 phase constant of the soil surface (s; days)
t0a phase constant of the air (s; days)
Ta air temperature above the ground surface (8C)
Ta(y) air temperature of the pipe at the distance y from
the pipe inlet (8C)
Tam ambient air temperature (8C)
Tm average soil surface temperature (8C)
Tma average air temperature (8C)
Tsur ground surface temperature (8C)
Tva amplitude of the air temperature (8C)
Tz,t ground temperature at time t and depth z (8C)
Ut overall heat transfer coefficient of the whole earth
tube system (W/8C)
Va average pipe air velocity (m/s)
w annual angular frequency (=1.992 � 10�7 rad/s)
z depth of the radial center of pipe below soil
surface (m)
Greek letters
as soil thermal diffusivity (m2/s; m2/days)
b soil absorption coefficient (=1– soil albedo)
e hemispherical emittance of the ground surface
wI phase angle between the insolation and the air
temperature (rad)
ws phase angle difference between the air and soil
surface temperature (rad)
K.H. Lee, R.K. Strand / Energy and Buildings 40 (2008) 486–494 487
potential of the earth tube is investigated in four representative
locations in the U.S.
2. Earth tube model description
The simulation program in which the earth tube module was
implemented is EnergyPlus, since EneryPlus is considered to be
the next-generation building performance simulation program
combining the best features of DOE-2 and BLAST. As a result,
it has the great flexibilities and capabilities for the compre-
hensive building simulation. The integrated solution manager
in EnergyPlus consists of three managers: the surface heat
balance manager, the air heat balance manager and the building
systems simulation manager. The earth tube module presented
in this paper was implemented at the air heat balance manager
level.
Due to the complex mechanisms occurring around the earth
tube, several simplifying assumptions were made:
� C
onvection flow inside the pipe is hydrodynamically andthermally developed.
� S
oil temperature in the pipe vicinity can be calculated usingthe soil model discussed below beyond a particular distance
from the center of the pipe (thickness of the annulus).
� T
he temperature profile in the pipe vicinity is not affected bythe presence of the pipe. As a result, the pipe surface
temperature is uniform in the axial direction.
� T
he soil surrounding the pipe is homogeneous and has aconstant thermal conductivity.
� P
ipe has a uniform cross sectional area in the axial direction.2.1. Soil temperature calculation
Prior to the calculation of the soil temperature around an
earth tube, the ground surface temperature directly above earth
tube should be predicted. According to Kusuda and Achenbach
(1965) [8], the ground surface temperature satisfies the
following expression:
Tsur ¼ Tð0; tÞ ¼ Tm þ As ReðeiwtÞ (1)
where T(x,t) is the soil temperature profile as a function of depth
x and time t. Tm and As are the annual mean value and the
amplitude of the ground surface temperature variation, respec-
tively, which should be calculated by considering the convec-
tive heat transfer between the air and ground, the solar radiation
K.H. Lee, R.K. Strand / Energy and Buildings 40 (2008) 486–494488
absorption by the ground, the long-wavelength radiation
emitted from the soil, and the latent heat loss due to the
moisture evaporation at the ground surface.
The model is described in depth by Krarti et al. [1], and the
derivation process will not be discussed in this paper.
According to Krarti et al. [1], the annual mean ground surface
temperature, Tm, can be estimated as follows:
Tm ¼1
he
½hrTma � eDRþ bSm � 0:0168hs fbð1� raÞ� (2)
where he ¼ hsð1þ 0:0168a f Þ; hr ¼ hsð1þ 0:0168ara f ÞMore detailed description of the algorithm is provided in
reference [7].
The amplitude of the soil surface temperature variation (8C),
As, the phase constant of the soil surface (s), t0, and phase angle
difference between the air and soil surface temperature (rad),
ws, can also be determined as follows [1]:
As ¼���� hrTva � bSv eifI
he þ dks
���� (3)
t0 ¼ t0a þfs
w(4)
fs ¼ �Arg
�hrTva � bSv eifI
he þ dks
�(5)
In Eqs. (3) and (5) the symbols jj jj and Arg are used to signify
the modulus and the argument of a complex number, respec-
tively.
The phase constant of the air (s), t0a, is the time elapsed from
the beginning of the year at which the air temperature reaches
the minimum value in the year.
The value of d is evaluated as follows:
d ¼ 1þ i
D(6)
where the dampening depth (m), D, is calculated from the
following equation:
D ¼ffiffiffiffiffiffiffi2as
w
r(7)
Assuming homogeneous soil of constant thermal diffusivity,
the temperature at any depth z and time t can be finally
estimated by the following expression (Labs et al. 1989).
Tz;t ¼ Tm � As exp
�� z
�p
365as
�1=2�
cos
�2p
365
�t � t0 �
z
2
�365
pas
�1=2�(8)
2.2. Heat transfer and earth tube inlet air temperature
calculation
In order to calculate the heat transfer between the earth tube
and the surrounding soil, the overall heat transfer coefficient
should be determined using the following three thermal
resistance values:
Rc ¼1
2pr1Lhc
(9)
Rp ¼1
2pLkp
lnr1 þ r2
r1
(10)
Rs ¼1
2pLks
lnr1 þ r2 þ r3
r1 þ r2
(11)
where Rc is thermal resistance due to convection heat transfer
between the air in the pipe and the pipe inner surface (8C/W),
Rp the thermal resistance due to conduction heat transfer
between the pipe inner and outer surface (8C/W) and
Rs is the thermal resistance due to conduction heat
transfer between the pipe outer surface and the undisturbed
soil (8C/W). The distance between the pipe outer surface and
undisturbed soil, r3, is assumed to be equal to the radius of
the pipe.
The convective heat transfer coefficient at the inner pipe
surface in Eq. (9) (W/m2 8C), hc, is a function of Nusselt
number, Nu, and thermal conductivity of air (W/m 8C), which
can be expressed by the following expression:
hc ¼Nu kair
2r1
(12)
Using the three thermal resistance values, Rc, Rp and Rs,
overall heat transfer coefficient of earth tube can be estimated
as follows:
Ut ¼1
Rt
(13)
Rt ¼ Rc þ Rp þ Rs (14)
Now, the heat transfer between the soil and the air inside the
pipe is equal to the amount of heat loss or gain as air flows along
the pipe [3]:
Ut dy½TaðyÞ � Tz;t� ¼ �maCa½dTaðyÞ� (15)
By solving for air temperature inside the pipe, Ta(y), the
following earth tube inlet air temperature (defined as the air
leaving the earth tube and entering the space in this paper) can
be finally obtained.
� I
n case Tam > Tz,tTaðLÞ ¼ Tz;t þ eA (16)
� I
n case Tam = Tz,tTaðLÞ ¼ Tz;t (17)
� I
n case Tam < Tz,tTaðLÞ ¼ Tz;t � eA (18)
where
A ¼ maCa lnjTam � Tz;tj � UtL
maCa
(19)
Fig. 1. E+ earth tube model validation (ambient air temperature 25.56 8C).
K.H. Lee, R.K. Strand / Energy and Buildings 40 (2008) 486–494 489
3. Model validation
The model developed in the previous section was validated
against both theoretical model and experimental data. The
theoretical model for the comparison was developed by Al-
Ajmi et al. [3], which was validated against relevant
experimental and theoretical studies. The experimental study
was carried out by Dhaliwal et al. [6] at North Carolina under
the configuration of a pipe diameter of 30 cm, a pipe length of
24.7 m, and a pipe depth of 1.7 m. The detailed input
parameters for the comparison to both experimental and
theoretical studies are described in Table 1. The results for both
the experimental and theoretical studies using two different
ambient air temperature conditions are presented in Tables 2
and 3, Figs. 1 and 2. As can be seen, the results show good
agreement and have the values between the two studies under
consideration. The difference in the earth tube inlet temperature
between the experimental data and the modeling results can be
seen to be a result of an obvious data error in the experimental
results (see Fig. 1). However, the discrepancies between the
EnergyPlus model and the Al-Ajmi model are insignificant,
indicating that the model can properly predict the performance
Table 1
Input parameters for comparative validation
Pipe diameter (cm) 30
Pipe length (m) 24.7
Air velocity (m/s) 1.5
Soil temperature (8C) 18.89
Pipe depth (m) 2.13
Soil thermal conductivity (W/m8C) 1.16
Soil thermal diffusivity (m2/s) 0.00232
Table 2
E+ earth tube model validation (ambient air temperature: 25.56 8C)
Axial distance
from the pipe
inlet (m)
Experimental
data of Dhaliwal
et al. (8C)
Theoretical data
of Al-Ajmi
et al. (8C)
E+ earth
tube model
(8C)
3.35 25.00 24.94 25.04
6.4 24.40 24.43 24.60
9.45 25.00 23.97 24.19
12.5 24.40 23.54 23.82
15.55 23.80 23.15 23.46
24.7 23.80 22.16 22.55
Table 3
E+ earth tube model validation (ambient air temperature: 20.55 8C)
Axial distance
from the pipe
inlet (m)
Experimental
data of Dhaliwal
et al. (8C)
Theoretical
data of Al-Ajmi
et al. (8C)
E+ earth
tube model
(8C)
3.35 20.55 20.40 20.42
6.4 20.00 20.27 20.31
9.45 20.00 20.16 20.21
12.5 20.00 20.05 20.11
15.55 20.00 19.95 20.03
24.7 20.00 19.71 19.80
of an earth tube system and the heating/cooling load reduction
due to the earth tube.
4. Description of simulation conditions and example
building
Using the newly developed earth tube model, the cooling
and heating potential of an earth tube system was predicted in
four different locations which represent four typical climatic
conditions in order to investigate the influence of soil
temperature and soil condition. Also parametric studies were
carried out to determine the effect of four important variables
influencing the earth tube inlet air temperature: pipe radius,
pipe length, air flow rate and pipe depth under the ground
surface. Simulations were performed on five different values of
each parameter while the other parameters were maintained at
the same values. 21 August is chosen as summer design day for
Key West and Spokane, and 21 July was chosen for Peoria and
Phoenix. The maximum dry bulb temperatures were set at
30.6 8C, 30.4 8C, 35.7 8C and 28.3 8C for Key West, Peoria,
Phoenix and Spokane, respectively. 21 December was chosen
as winter design day for Phoenix and Spokane, and 21 January
was chosen for Key West and Peoria. The maximum dry bulb
Fig. 2. E+ earth tube model validation (ambient air temperature 20.55 8C).
Table 4
Description of simulation conditions
Conditions
Location
Spokane, WA: mild and dry
Peoria, IL: mild and wet
Phoenix, AZ: hot and dry
Key West, FL: hot and wet
Run period
Summer design day
7/21: Peoria and Phoenix
8/21: Key West and Spokane
Winter design day
12/21: Phoenix and Spokane
1/21: Key West and Peoria
Variables
Pipe radius: 0.05 m, 0.075 m, 0.1 m, 0.15 m, 0.2 m
Pipe length: 10 m, 30 m, 50 m, 7 0m, 90 m
Air velocity: 2 m/s, 5 m/s, 8 m/s, 11 m/s, 14 m/s
Pipe depth: 1 m, 2.5 m, 4 m, 5.5 m, 7 m
K.H. Lee, R.K. Strand / Energy and Buildings 40 (2008) 486–494490
temperatures were set at 14.3 8C, �17.7 8C, 4.5 8C and
�12.3 8C for Key West, Peoria, Phoenix and Spokane,
respectively. Table 4 shows the details of the parametric studies.
The ‘‘base case’’ values for each variable were set at:
0.075 m for pipe radius, 30 m for pipe length, 5 m/s for air
velocity, and 2.5 m for pipe depth. These values were selected
for the prediction of cooling and heating potential of the
system. In addition, when changing only one variable at every
simulation process for parametric studies, the other variables
were kept at those values. Table 5 describes the inputted soil
conditions and parameters for each location. The annual
average ground surface temperature, Tm, and amplitude of the
soil surface temperature variation, As, were calculated by a
utility program that is provided with EnergyPlus.
A three-zone residential building was chosen for this study.
The building is not actually existing building, but the
constructions and thermal conditions are thoroughly based
on the real buildings. It consists of a living space, an attached
garage and attic above living space and garage having floor
areas of approximately 140 m2, 37 m2, and 177 m2, respec-
tively. In this study, the living space will be analyzed, which is
located on the northern side of the building with the ceiling
height of 3.05 m. The internal heat gains for lights and
equipment were set at 5.4 W/m2 and two people were placed in
the living space during the simulation Infiltration was set at 0.25
ACH and the earth tube was set to run constantly at the same
volumetric flow rate of 285 m3/h during the whole running
period.
Table 5
Soil related parameters
Soil condition Tm (average) (8C) As (amplitude) (8C)
Key West Heavy and moist 24.3 5.0
Peoria Heavy and moist 10.0 18.8
Phoenix Heavy and dry 25.0 9.4
Spokane Heavy and dry 9.9 18.5
5. Parametric analysis
The effects of four important parameters significantly
affecting the performance of an earth tube system were
investigated through the parametric analysis. Since the findings
discussed later in this paper showed that earth tubes have more
potential for cooling than for heating, the parametric analysis
was carried out only for cooling.
5.1. Influence of pipe length
Fig. 3 presents the effect of pipe length on the earth tube inlet
air temperature at the highest ambient air temperature. As the
pipe length increases, the inlet air temperature decreases due to
the fact that the longer pipe provides a longer path over which
heat transfer between the pipe and the surrounding soil can take
place given the same overall heat transfer coefficient of earth
tube.
However, the temperature range and decrease rate in terms
of pipe length were different among each location due to the
different soil conditions, ambient air temperature, and soil
temperature distribution. In addition, Peoria and Spokane are
appropriate locations to employ earth tubes since the earth tube
inlet air temperature is lower than the specified indoor
temperature of 23 8C. In both cases of Peoria and Spokane
after a certain point around 50–70 m increasing the length does
not result in much better performance and the improvements
begin to level off, indicating that these values can be the optimal
design values in these special cases which can be determined
using the developed earth tube model.
5.2. Influence of pipe depth
Fig. 4 shows the influence of pipe depth under the ground
surface on the earth tube inlet air temperature. As the pipe depth
increases, the inlet air temperature decreases, indicating that the
earth tube should be placed as deeply as possible. However, the
trenching cost and other economic factors should be considered
when installing earth tubes.
Similarly the temperature range and decrease rate with
regard to pipe depth were different at each location due to
Fig. 3. Influence of pipe length on inlet temperature.
Fig. 6. Influence of pipe radius on inlet temperature.Fig. 4. Influence of pipe depth on inlet temperature.
K.H. Lee, R.K. Strand / Energy and Buildings 40 (2008) 486–494 491
different soil and weather conditions. In addition like the case
of pipe depth, Peoria and Spokane are the better places for the
utilization of earth tubes than Key West and Phoenix which
have higher soil temperatures and the earth tube inlet
temperature. Moreover, after a certain point (around 4–
5.5 m) the improvements begin to level off, which can be
considered to be the optimal design values without factoring in
economic factors such as trenching and drilling costs. Based on
these results, pipe depth appears to have as large of an influence
on earth tube performance as pipe length.
6. Influence of air velocity inside pipe
Fig. 5 presents the effect of air velocity inside the pipe on the
earth tube inlet air temperature. As the air flow rate increases
the inlet air temperature increases in all locations, since the air
spends more less in the tube and thus in contact with the lower
soil temperature. This can be seen in the earth tube modeling
equations since according to Eq. (19) a higher air flow rate
causes a higher mass flow rate and higher air temperature.
Likewise, the range and rate of increase of the inlet air
temperatures as a function of air velocity were different at each
location due to different soil conditions. Like the cases of other
parameters described above, Peoria and Spokane turned out to
be more appropriate locations for earth tubes, and there is a air
Fig. 5. Influence of air velocity on inlet temperature.
velocity limit above after which the inlet temperatures become
relatively constant despite additional increases in velocity.
However, when considering the air flow rate during the
design process, simply reducing the flow rate does not
necessarily improve the earth tube performance since the
cooling heat transfer rate due to the earth tubes depends on both
air flow rate and temperature difference, not on each factor
alone (q = maCaDT). Thus, both the air flow rate and the
temperature difference should be considered simultaneously.
6.1. Influence of pipe radius
Fig. 6 illustrates the effect of pipe radius on the earth tube
inlet air temperature. As the pipe radius increases, the earth tube
inlet air temperature also increases due to the fact that higher
pipe radius results in a lower convective heat transfer
coefficient on the pipe inner surface and a lower overall heat
transfer coefficient of earth tube system.
Similarly, the temperature range and the increase in the inlet
temperature in terms of pipe radius were different at each
location. Peoria and Spokane can be considered to be better
places for earth tubes due to a lower inlet air temperature than
the specified indoor temperature of 23 8C. Compared to the
other three parameters discussed above, pipe radius did not
affect the results as much as the other parameters. Moreover,
simply reducing the pipe radius under same air flow rate will
increase the air velocity inside the pipe, resulting in an increase
in the earth tube inlet air temperature. Thus pipe radius and air
flow rate should be considered together and optimized using
simulated results.
The trends of the results in terms of the influence of design
parameters on the performance discussed above were similar to
those of other studies (Mihalakakou et al., 1995).
7. Cooling and heating potential
The simulations were carried out for the investigation of the
cooling and heating potential of an earth tube by the
comparison of the results with and without earth tubes.
Figs. 7–10 illustrate the cooling and heating rate variation under
design day conditions with and without an earth tube in four
Fig. 7. Cooling/heating rate with and without earth tube (Key West).
Fig. 8. Cooling/heating rate with and without earth tube (Peoria).
Fig. 10. Cooling/heating rate with and without earth tube (Spokane).
Table 6
K.H. Lee, R.K. Strand / Energy and Buildings 40 (2008) 486–494492
different locations. Table 6 describes the required cooling load
requirement of the building to maintain the indoor air
temperature of 23 8C during the whole summer design day
period with and without the earth tube. Similarly Table 7
describes the required heating load requirement of the building
to maintain the indoor air temperature of 20 8C during the
winter design day with and without the earth tube. As can be
Fig. 9. Cooling/heating rate with and without earth tube (Phoenix).
seen in Figs. 7–10, the cooling rate varies more than the heating
rate in all four locations since winter design days have constant
ambient air temperatures. The increases in the cooling rate
around hours 12–20 are due to the increase in the ambient air
temperature during that time period. The cooling rate around 2–
8 h reaches zero in Peoria and Spokane due to the fact that
ambient air temperature is low enough to maintain the
comfortable indoor temperature without air-conditioning and
earth tubes.
In case of cooling performance, whether or not the earth tube
is beneficial clearly depends on climatic conditions and
locations as can be seen in Table 6. The amount of reduced
total cooling load requirement due to an earth tube system were
6.6 kWh and 8.8 kWh in case of Peoria and Spokane,
respectively, an energy saving of 31% and 52%, respectively.
Therefore, large amounts of cooling energy can be saved by
employing earth tube systems. However, cooling load require-
ments with an earth tube system is even 41.8 kWh and
26.9 kWh higher than those without an earth tube in Key West
and Phoenix, respectively. This is due to the fact that the earth
tube inlet air temperatures were higher than specified indoor
temperature in the two locations, indicating that the hot weather
Total cooling load requirement of the building with and without an earth tube
Locations Cooling load requirement
without earth tube (kWh)
Cooling load requirement
with earth tube (kWh)
Key West 88.3 129.7
Peoria 20.8 14.3
Phoenix 79.7 106.6
Spokane 16.9 8.1
Table 7
Heating load requirement of the building with and without an earth tube
Locations Heating load requirement
without earth tube (kWh)
Heating load requirement
with earth tube (kWh)
Key West 20.9 21.2
Peoria 170.7 196.1
Phoenix 64.7 65.7
Spokane 142.7 161.3
Table 8
Total cooling load requirement under different earth tube air flow rates (design
day simulation)
Conditions Peoria Spokane
Cooling load requirement without
earth tube (kWh)
20.9 16.9
Cooling load requirement with
earth tube (0.75 ACH) (kWh)
14.3 8.1
Cooling load requirement with
earth tube (1.5 ACH) (kWh)
12.8 6.2
Cooling load requirement with
earth tube (3.0 ACH) (kWh)
14.2 7.0
Table 10
Heating load reduction by preheating the fresh air using an earth tube (design
day simulation)
Locations Heating load requirement
with 0.35 ACH infiltration
rate (kWh)
Heating load requirement
with 0.35 ACH earth tube
air flow rate (kWh)
Key West 22.3 14.5
Peoria 184.1 159.3
Phoenix 69.7 52.0
Spokane 153.3 132.3
K.H. Lee, R.K. Strand / Energy and Buildings 40 (2008) 486–494 493
of the two locations also increased the soil temperature
significantly and that the weather and soil conditions should be
considered in order to determine whether or not earth tubes
should be used in particular locations.
Furthermore, additional simulations were carried out to
investigate the cooling load reduction variation under different
earth tube air flow rate conditions: 0.75, 1.5 and 3.0 ACH.
Since Peoria and Spokane showed the cooling load reduction
due to an earth tube, simulations were carried out only for
these two locations. Tables 8 and 9 show the total cooling load
requirements under different earth tube air flow rates
simulated during the design day and the whole cooling season
respectively. As can be seen in the tables, large portions of the
cooling loads are reduced due to earth tubes. In case of the
whole cooling season simulation, more than 50% of cooling
loads can be saved in both locations. In both the design day and
the whole cooling season simulations, the earth tube air flow
rate of 1.5 ACH turned out to cause the largest total cooling
load reduction, even larger than 3.0 ACH. This is due to the
fact that the earth tube inlet air temperature becomes higher as
the air velocity inside the pipe also gets higher due to the
higher earth tube air flow rate under the same pipe radius
condition, which can reduce the cooling provided by the earth
tube to the zone.
Therefore, it should be noted that the higher earth tube air
flow rate does not necessarily mean the highest cooling load
reduction due to the earth tube, indicating that the optimal air
flow rate under different conditions should be determined in
advance using an earth tube model in a program such as
EnergyPlus. Although the earth tube system did not appear to
have the capacity to replace the conventional air-conditioning
Table 9
Total cooling load requirement under different earth tube air flow rates (June–
August simulation)
Conditions Peoria Spokane
Cooling load requirement without
earth tube (kWh)
1099.8 1147.8
Cooling load requirement with
earth tube (0.75 ACH) (kWh)
427.1 497.2
Cooling load requirement with
earth tube (1.5 ACH) (kWh)
336.5 394.4
Cooling load requirement with
earth tube (3.0 ACH) (kWh)
389.5 444.5
system completely, it can significantly reduce the cooling load
requirement to maintain the specified indoor conditions when
the weather and soil conditions are properly considered for each
location.
On the other hand, in case of heating performance, the
heating load requirements in all the four locations with an earth
tube were higher than those without an earth tube as can be seen
in Table 7. This is due to the fact that the earth tube inlet air
temperatures are not higher than the specified indoor
temperature within the comfort zone, indicating that an earth
tube inlet temperature high enough to provide heating cannot be
obtained. Therefore, an earth tube system has better capability
for cooling than for heating buildings given the same location.
Although an earth tube did not turned out to reduce the
heating load, additional simulations were carried out to find out
the contribution of earth tubes to the preheating of the fresh air.
According to ASHRAE Standard 62-1999, at least 0.35 ACH of
the air should be ventilated for living spaces. Therefore, two
cases were simulated: the case with the infiltration rate of 0.35
ACH without the assistance of an earth tube, and the case with
the earth tube air flow rate of 0.35 ACH. Tables 10 and 11 show
the heating load requirements of the two cases simulated during
the design day and the whole heating season, respectively. As
can be seen in the tables, a considerable amount of the heating
load can be reduced through the preheating of the fresh air using
earth tubes, though not as much as the cooling loads. In the case
of Phoenix simulated for the whole heating season, 45% of the
heating loads can be saved by preheating the fresh air. The
reason why the heating loads in Key West simulated for the
whole heating season are zero is that most ambient air
temperatures were higher than the specified indoor air
temperature of 20 8C even in the winter season and that the
indoor temperature did not fall below the 20 8C at any point
during the simulation.
Table 11
Heating load reduction by preheating the fresh air using an earth tube (Decem-
ber–February simulation)
Locations Heating load requirement
with 0.35 ACH infiltration
rate (kWh)
Heating load requirement
with 0.35 ACH earth tube
air flow rate (kWh)
Key West 0 0
Peoria 9513.6 8542.6
Phoenix 1788.0 990.1
Spokane 8283.9 7564.3
K.H. Lee, R.K. Strand / Energy and Buildings 40 (2008) 486–494494
8. Conclusion
In this paper, the algorithm for the simulation of earth tubes
is described, and validated against the data of other studies.
Parametric studies were carried out to investigate the effect of
each parameter on earth tube. The cooling and heating potential
of an earth tube was also investigated using the newly
developed model, and the following conclusions can be made
based on the data presented above:
1. A
s a result of the validation against the data from othertheoretical and experimental studies, the earth tube model
showed a good agreement with the work performed by
others. Thus it can be suitably used to predict the thermal
performance of earth tube systems.
2. A
deeply placed and longer earth tube with a lower airvelocity and smaller radius should result in lower earth tube
inlet temperatures. However, the trenching cost and other
factors should also be considered when installing earth tubes.
3. P
ipe length, air velocity inside pipe and pipe depth turned outto have more influence on earth tube performance than pipe
radius. However, pipe radius and air flow rate as well as
cooling heat transfer rate should be considered simulta-
neously.
4. W
hen properly designed, an earth tube were shown to savemore than 50% of the total cooling load in the cases
presented in this paper, depending on the weather and soil
conditions. Although the earth tube alone cannot replace
conventional air-conditioning system in these case studies, it
can significantly reduce the cooling load in buildings.
5. E
arth tubes turned out to have a larger capacity for coolingthan for heating given the same location. Even among the
case of cooling, whether or not earth tubes are beneficial is
dependent on the local climate, indicating that weather and
soil conditions should be properly considered and investi-
gated using the new model.
The availability of an earth tube model in a program such as
EnergyPlus is an important step forward when attempting to
determine whether or not earth tubes should be used for a
particular building and to determine the most optimal
combination with regard to depth, length, radius, and air
velocity. Based on this study, future work that should be done
includes the economic assessment and the environmental
effects of the earth tube since those factors affect the feasibility
of the system.
Acknowledgment
The authors of this paper wish to thank the U.S. Department
of Energy’s Lawrence Berkeley National Laboratory for
funding the work which led to this paper under Grant 6712530.
References
[1] M. Krarti, C. Lopez-Alonzo, D.E. Claridge, J.F. Kreider, Analytical model
to predict annual soil surface temperature variation, Journal of Solar Energy
Engineering 117 (1995) 91–99.
[2] K. Labs, in: J. Cook (Ed.), Passive Cooling, MIT Press, Cambridge,
Massachusetts, 1989.
[3] F. Al-Ajmi, D.L. Loveday, V.I. Hanby, The cooling potential of earth-air
heat exchangers for domestic buildings in a desert climate, Building and
Environment 41 (2005) 235–244.
[4] C.P. Jacovides, G. Mihalakakou, An underground pipe systems as an energy
source for cooling/heating purposes, Renewable Energy 6 (1995) 893–900.
[5] V.M. Puri, Heat and Mass Transfer Analysis and Modeling in Unsaturated
Ground Soils for Buried Tube Systems, Energy in Agriculture 6 (1987)
179–193.
[6] Dhaliwal, Goswami, Heat Transfer Analysis Environment Control using an
Underground Air Tunnel, ASME Solar Energy Div., Las Vegas, 1984, pp.
505–510.
[7] K.H. Lee, R.K. Strand, Implementation of an earth tube system into
EnergyPlus Program, in: Proceedings of the SimBuild 2006 Conference,
Boston MA, USA, 2006.
[8] T. Kusuda, P.R. Achenbach, Earth Temperature and Thermal diffusivity on
at Selected Stations in the United Stales, ASHRAE Trans. 71 (1965) 61–75.