Theme & System Advantages

KIRLOSKAR OIL ENGINES LIMITEDKIRLOSKAR OIL ENGINES LIMITED

‘Kirloskar Green’ Diesel Generating SetsParallel Operation

14-Feb-12 1

Page 2: Theme & System Advantages - Kirloskarkoel.kirloskar.com/sites/koel.kirloskar.com/pdfs/parallel_sets.pdfprocessor based relay e.g. Woodward or PLC e.g. Allen Bradley or Siemens

Synchronization is the process of running two or more DGsets in parallel on common bursar, while matching thecharacteristics of each system as closely as possible.

This is accomplished by minimizing the phase-angle

D G Sets Synchronizing Panels

KIRLOSKAR OIL ENGINES LIMITED

This is accomplished by minimizing the phase-angledifference, frequency difference, voltage difference &matching phase sequence between the two systems.

Page 3: Theme & System Advantages - Kirloskarkoel.kirloskar.com/sites/koel.kirloskar.com/pdfs/parallel_sets.pdfprocessor based relay e.g. Woodward or PLC e.g. Allen Bradley or Siemens

Applications of Parallel operations

• Synchronizing panels are widely used in various fieldswhere heavy power inputs are required like:

• Telecom Sector Processing plants

KIRLOSKAR OIL ENGINES LIMITED

• Engineering units Hospitals

• Hotels Offices

• Institutions Etc

14-Feb-12 3

Page 4: Theme & System Advantages - Kirloskarkoel.kirloskar.com/sites/koel.kirloskar.com/pdfs/parallel_sets.pdfprocessor based relay e.g. Woodward or PLC e.g. Allen Bradley or Siemens

• Continuous back up of power supply

• Without failure of power supply, maintenance of dg set canbe done.

Advantages of DG sets in Parallel operations

KIRLOSKAR OIL ENGINES LIMITED

• As per load condition required no. of dg sets can beoperated.

• Fuel saving

• In case, failure of one set, power can be drawnfrom other sets without any trouble.

Page 5: Theme & System Advantages - Kirloskarkoel.kirloskar.com/sites/koel.kirloskar.com/pdfs/parallel_sets.pdfprocessor based relay e.g. Woodward or PLC e.g. Allen Bradley or Siemens

• Manual synchronizing

• Automatic synchronizing

Types of Synchronizing Panels

KIRLOSKAR OIL ENGINES LIMITED14-Feb-12 5

Page 6: Theme & System Advantages - Kirloskarkoel.kirloskar.com/sites/koel.kirloskar.com/pdfs/parallel_sets.pdfprocessor based relay e.g. Woodward or PLC e.g. Allen Bradley or Siemens

• This is done by the trained operator by comparing thevalues for voltage, frequency & phase angle of bus bar &dg to be synchronized using under mentionedinstruments mounted & wired on panel board:

Manual Synchronizing- Types of Synchronizing panels

KIRLOSKAR OIL ENGINES LIMITED

Double voltmeter Double frequency meter

Syncroscope Lamps

Potentiometer Volt meter

Ampere meter Power factor meter

Killo-Watt meter

Page 7: Theme & System Advantages - Kirloskarkoel.kirloskar.com/sites/koel.kirloskar.com/pdfs/parallel_sets.pdfprocessor based relay e.g. Woodward or PLC e.g. Allen Bradley or Siemens

After synchronizing & closing of breakers, two kind of loadsharing are required :

Active load sharing : This is attained by increasing or decreasing rpm of engine using potentiometer on panel board

Manual Synchronizing- Types of Synchronizing panels

KIRLOSKAR OIL ENGINES LIMITED

Cont. …..

engine using potentiometer on panel board

Reactive load sharing : This is attained by increasing or decreasing voltage of alternator using potentiometer on panel board

Page 8: Theme & System Advantages - Kirloskarkoel.kirloskar.com/sites/koel.kirloskar.com/pdfs/parallel_sets.pdfprocessor based relay e.g. Woodward or PLC e.g. Allen Bradley or Siemens

• Check sync relay

• Reverse power relay

Protections relay

KIRLOSKAR OIL ENGINES LIMITED

• Earth fault relay

Page 9: Theme & System Advantages - Kirloskarkoel.kirloskar.com/sites/koel.kirloskar.com/pdfs/parallel_sets.pdfprocessor based relay e.g. Woodward or PLC e.g. Allen Bradley or Siemens

• For automatic synchronizing pre programmed microprocessor based relays or PLC are used and the whole process is completed step by step automatically without any manual involvement.

• Kirloskar Engines have electronic governor with the provision of manual setting of droop with simple tool. (in other make laptop with software is required on site for any

Auto Synchronizing Panels

KIRLOSKAR OIL ENGINES LIMITED

of droop with simple tool. (in other make laptop with software is required on site for any setting in governor, which may cause unnecessary delay from service point of view.)

• All synchronizing panels can be manufactured with the combination of Micro processor based relay e.g. Woodward or PLC e.g. Allen Bradley or Siemens.

• Panel for synchronization of 4-6 nos. of dg set (250kva to 600kva) with AMF logic can be supplied as per customer requirement i.e. automatic or manual.

Page 10: Theme & System Advantages - Kirloskarkoel.kirloskar.com/sites/koel.kirloskar.com/pdfs/parallel_sets.pdfprocessor based relay e.g. Woodward or PLC e.g. Allen Bradley or Siemens

PLC based DG Synchronization System

KIRLOSKAR OIL ENGINES LIMITED

Page 11: Theme & System Advantages - Kirloskarkoel.kirloskar.com/sites/koel.kirloskar.com/pdfs/parallel_sets.pdfprocessor based relay e.g. Woodward or PLC e.g. Allen Bradley or Siemens

Isochronous Load Sharing

Unit A1000 KW

Unit B800 KW

50 Hz 50 Hz

KIRLOSKAR OIL ENGINES LIMITED

0 25 50 75 100 %( 500 KW )

0 25 50 75 100 %

( 400 KW )

50 Hz 50 Hz

TOTAL LOAD 900 KW

Page 12: Theme & System Advantages - Kirloskarkoel.kirloskar.com/sites/koel.kirloskar.com/pdfs/parallel_sets.pdfprocessor based relay e.g. Woodward or PLC e.g. Allen Bradley or Siemens

Bump less Load Transfer

Gen 2

TOTAL PLANT LOAD

Gen 1

KIRLOSKAR OIL ENGINES LIMITED

ISO LOAD

SHARINGLOAD

BreakerCloses ( Gen 2 )

BreakerOpens ( Gen 1)

TIME

Unload Gen 1 Initiated

Gen 2

¶ Gen 1Gen 2

Page 13: Theme & System Advantages - Kirloskarkoel.kirloskar.com/sites/koel.kirloskar.com/pdfs/parallel_sets.pdfprocessor based relay e.g. Woodward or PLC e.g. Allen Bradley or Siemens

Kirloskar Green Offers

• Automatic DG Synchronization• Automatic Isochronous Load Sharing• Bump less Load Transfer• AMF Function• Inbuilt Engine Protections

KIRLOSKAR OIL ENGINES LIMITED

• Inbuilt Engine Protections• Inbuilt Alternator Protections• Load Management System• Auxiliary Control

Page 14: Theme & System Advantages - Kirloskarkoel.kirloskar.com/sites/koel.kirloskar.com/pdfs/parallel_sets.pdfprocessor based relay e.g. Woodward or PLC e.g. Allen Bradley or Siemens

Synchronizing

• Phase Match Synchronizing (up to 2* phase error)• Digital Signal Processing to reduce harmonics• Voltage Matching (Up to 0.1%)• Multiple Reclosing Attempts• Safe Dead Bus closing logic

KIRLOSKAR OIL ENGINES LIMITED

• Safe Dead Bus closing logic• Three Modes of operation (Run/Check/Permissive)• Capable of Grid & DG Synchronization• Manual Synchronization Capability

Page 15: Theme & System Advantages - Kirloskarkoel.kirloskar.com/sites/koel.kirloskar.com/pdfs/parallel_sets.pdfprocessor based relay e.g. Woodward or PLC e.g. Allen Bradley or Siemens

Load sharing

• Isochronous Proportional Load Sharing• Active as well as Reactive Load Sharing• Load Ramping• Adjustable Loading/Unloading ramps• Power Factor Control

KIRLOSKAR OIL ENGINES LIMITED

• Power Factor Control

Page 16: Theme & System Advantages - Kirloskarkoel.kirloskar.com/sites/koel.kirloskar.com/pdfs/parallel_sets.pdfprocessor based relay e.g. Woodward or PLC e.g. Allen Bradley or Siemens

Engine Protections

• High/Low Coolant Temperature• High/Low Lube Oil Pressure• Over Speed• Start Failure• Cool Down Timer

KIRLOSKAR OIL ENGINES LIMITED

• Cool Down Timer• Idle/Rated Control

Page 17: Theme & System Advantages - Kirloskarkoel.kirloskar.com/sites/koel.kirloskar.com/pdfs/parallel_sets.pdfprocessor based relay e.g. Woodward or PLC e.g. Allen Bradley or Siemens

Alternator Protections

• Over/Under Voltage• Over/Under Frequency• Reverse Power (Inverse Time Delay)• Reverse KVAR• Over Current (Inverse Time Delay)

KIRLOSKAR OIL ENGINES LIMITED

• Over Current (Inverse Time Delay)• Load Surge• Speed/Frequency Mismatch

Page 18: Theme & System Advantages - Kirloskarkoel.kirloskar.com/sites/koel.kirloskar.com/pdfs/parallel_sets.pdfprocessor based relay e.g. Woodward or PLC e.g. Allen Bradley or Siemens

Automatic Sequencing

• Sequencing Uses Master - Slave Configuration.

Master Slave Slave Slave

Priority 1 Priority 2 Priority 3 Priority 4

KIRLOSKAR OIL ENGINES LIMITED

• Sequencing Uses Master - Slave Configuration.• Each Unit in the system has an assigned Priority.• Master (Highest Priority) automatically sequences units on or off line as determined by system load.

• Higher priority units are sequenced on in order of their priority; taken off in reverse of priority.

• Online Changing of Priority

Page 19: Theme & System Advantages - Kirloskarkoel.kirloskar.com/sites/koel.kirloskar.com/pdfs/parallel_sets.pdfprocessor based relay e.g. Woodward or PLC e.g. Allen Bradley or Siemens

Features of PLC

• PLC has a high performance distributed architecture that reduces costs and risks.

• PLC’s powerful open communications makes it easy to share information

• PLC is a good value - large PLC power in a smaller package

KIRLOSKAR OIL ENGINES LIMITED

package• PLC is easy to maintain• PLC can save time, money, and reduce project risk with highly integrated intelligent functions.

Page 20: Theme & System Advantages - Kirloskarkoel.kirloskar.com/sites/koel.kirloskar.com/pdfs/parallel_sets.pdfprocessor based relay e.g. Woodward or PLC e.g. Allen Bradley or Siemens

Advantages

KIRLOSKAR OIL ENGINES LIMITED

Advantages

Page 21: Theme & System Advantages - Kirloskarkoel.kirloskar.com/sites/koel.kirloskar.com/pdfs/parallel_sets.pdfprocessor based relay e.g. Woodward or PLC e.g. Allen Bradley or Siemens

Memory - flexible and easy to maintain

• Easy to expand– PCMCIA cards can be easily added to the Type I

PCMCIA slot on the front of the CPU, minimizing maintenance time.

• Backup memory– Program, constants, module parameters– Easy field updates

KIRLOSKAR OIL ENGINES LIMITED

– Easy field updates

Page 22: Theme & System Advantages - Kirloskarkoel.kirloskar.com/sites/koel.kirloskar.com/pdfs/parallel_sets.pdfprocessor based relay e.g. Woodward or PLC e.g. Allen Bradley or Siemens

DIRECT INTERFACE

§ Direct interface to Electronic Governors

Electronic Governor

KIRLOSKAR OIL ENGINES LIMITED

§ Direct interface to Electronic Governors – No relay, contact, MOP in the circuit

§ Faster Response

§ High Reliability

§ Adjustable Load/Unload ramps

Page 23: Theme & System Advantages - Kirloskarkoel.kirloskar.com/sites/koel.kirloskar.com/pdfs/parallel_sets.pdfprocessor based relay e.g. Woodward or PLC e.g. Allen Bradley or Siemens

Load Sharing

• Isochronous Load Sharing• %age based Loading of DG sets• Better utilization of DG sets• No Jerks on Supply System due to Bump less Load Transfer

KIRLOSKAR OIL ENGINES LIMITED

Transfer• Smooth Loading & Unloading• Very fast & reliable synchronization• Constant frequency over the entire range

Page 24: Theme & System Advantages - Kirloskarkoel.kirloskar.com/sites/koel.kirloskar.com/pdfs/parallel_sets.pdfprocessor based relay e.g. Woodward or PLC e.g. Allen Bradley or Siemens

PLC is Easy to Maintain

plug ‘n play(no switches)

electronic keying

diagnostic LEDs

broken wire detection,terminal block detection

KIRLOSKAR OIL ENGINES LIMITED

removable terminal blocks

Hot Swap

coding ofmodules andterminal blocks

protection - short circuit,overload, preactuator voltage, surge protection

Page 25: Theme & System Advantages - Kirloskarkoel.kirloskar.com/sites/koel.kirloskar.com/pdfs/parallel_sets.pdfprocessor based relay e.g. Woodward or PLC e.g. Allen Bradley or Siemens

Other Advantages

• Specific Design for the Power Generation market • Flexibility: Easy addition & deletion of DG Sets • Modular: Each DG has a dedicated control• Standard Hardware & Software• Component Integration: Cost & space saving• Saving in space/field wiring• 24 V DC supply from engine battery

KIRLOSKAR OIL ENGINES LIMITED

• 24 V DC supply from engine battery• Inbuilt Generator Protection

A fully integrated generator control package

Page 26: Theme & System Advantages - Kirloskarkoel.kirloskar.com/sites/koel.kirloskar.com/pdfs/parallel_sets.pdfprocessor based relay e.g. Woodward or PLC e.g. Allen Bradley or Siemens

Reference Installations of Kirloskar Green

KIRLOSKAR OIL ENGINES LIMITED5 nos 600 kVA Kirloskar Green Sets in Synchronizing mode at MCA Pune

Page 27: Theme & System Advantages - Kirloskarkoel.kirloskar.com/sites/koel.kirloskar.com/pdfs/parallel_sets.pdfprocessor based relay e.g. Woodward or PLC e.g. Allen Bradley or Siemens

Reference Installations of Kirloskar Green

KIRLOSKAR OIL ENGINES LIMITED5 nos 500 kVA Kirloskar Green at Kakde Magnum, Pune

Page 28: Theme & System Advantages - Kirloskarkoel.kirloskar.com/sites/koel.kirloskar.com/pdfs/parallel_sets.pdfprocessor based relay e.g. Woodward or PLC e.g. Allen Bradley or Siemens

Thank You.

KIRLOSKAR OIL ENGINES LIMITED

Thank You.