THERMAL STORAGE FOR LARGE LABORATORY LOADS, A Case Study August, 2000 Jerry Savage Mechanical Engineer, MTS Sandia is a multiprogram laboratory operated by Sandia Corporation, a Lockheed Martin Company, for the United States Department of Energy under contract DE-AC04-94AL85000.

Upload: others

Post on 15-Mar-2020

3 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: THERMAL STORAGE FOR LARGE LABORATORY LOADS, A Case … · 2006-06-26 · THERMAL STORAGE FOR LARGE LABORATORY LOADS, A Case Study August, 2000 Jerry Savage Mechanical Engineer, MTS

THERMAL STORAGE FORLARGE LABORATORY

LOADS, A Case StudyAugust, 2000

Jerry SavageMechanical Engineer, MTS

Sandia is a multiprogram laboratory operated by Sandia Corporation, a Lockheed Martin Company,for the United States Department of Energy under contract DE-AC04-94AL85000.

Page 2: THERMAL STORAGE FOR LARGE LABORATORY LOADS, A Case … · 2006-06-26 · THERMAL STORAGE FOR LARGE LABORATORY LOADS, A Case Study August, 2000 Jerry Savage Mechanical Engineer, MTS

THERMAL STORAGE SYSTEM

•Makes Chilled Water At Night When Electric Rates Are Less ForUse During The Day To Cool Ten Connected Buildings

•Stores Over One Million Gallons Or Ten Thousand Ton/Hours OfCooling Water

•Allows For The Shutoff Of Chillers During The Day When ElectricRates Are High

•Potential Energy Savings Of Over $ 200,000 Per Year

•Adds The Potential To Optimize Other Related Systems ForAdditional Savings

•No Moving Parts

•No New Pumps Required

•Will Last Over Fifty Years

•Low Maintenance

•Fast Payback

Page 3: THERMAL STORAGE FOR LARGE LABORATORY LOADS, A Case … · 2006-06-26 · THERMAL STORAGE FOR LARGE LABORATORY LOADS, A Case Study August, 2000 Jerry Savage Mechanical Engineer, MTS

Thermal Storage Theory

• Warm return water and cold supply water inthe same tank

• Thermocline forms due to densitydifferences associated with temperature

• Cold water stays at the bottom, Warm at thetop, similar to a lake

• Non Turbulent diffuser system

• Closed system, no head loss due to lowvelocity

Page 4: THERMAL STORAGE FOR LARGE LABORATORY LOADS, A Case … · 2006-06-26 · THERMAL STORAGE FOR LARGE LABORATORY LOADS, A Case Study August, 2000 Jerry Savage Mechanical Engineer, MTS

Tank Internals

Page 5: THERMAL STORAGE FOR LARGE LABORATORY LOADS, A Case … · 2006-06-26 · THERMAL STORAGE FOR LARGE LABORATORY LOADS, A Case Study August, 2000 Jerry Savage Mechanical Engineer, MTS
Page 6: THERMAL STORAGE FOR LARGE LABORATORY LOADS, A Case … · 2006-06-26 · THERMAL STORAGE FOR LARGE LABORATORY LOADS, A Case Study August, 2000 Jerry Savage Mechanical Engineer, MTS

Background and History

• We were designing a new laboratory, theProcessing and Environmental TechnologyLaboratory or PETL

• PETL would need a source of chilled waterfor cooling

• We had a nearby Campus chiller plant thatserved ten other buildings

Page 7: THERMAL STORAGE FOR LARGE LABORATORY LOADS, A Case … · 2006-06-26 · THERMAL STORAGE FOR LARGE LABORATORY LOADS, A Case Study August, 2000 Jerry Savage Mechanical Engineer, MTS

PETL Nearing Completion

Page 8: THERMAL STORAGE FOR LARGE LABORATORY LOADS, A Case … · 2006-06-26 · THERMAL STORAGE FOR LARGE LABORATORY LOADS, A Case Study August, 2000 Jerry Savage Mechanical Engineer, MTS

• We were under a normal Electrical ratestructure with Peak, Off Peak, and DemandCharges

• Thermal Storage was presented as apossible alternative to new chillers andcooling towers

• The existing chiller plant was in need of athorough design review ( known overpumping problems )

Page 9: THERMAL STORAGE FOR LARGE LABORATORY LOADS, A Case … · 2006-06-26 · THERMAL STORAGE FOR LARGE LABORATORY LOADS, A Case Study August, 2000 Jerry Savage Mechanical Engineer, MTS

Design Review of ThermalStorage

• Our A&E Firm came back to us with a lessthan optimistic life cycle cost report

• I worked with CBI and found a totallydifferent result

• A last minute decision was made to useChilled Water Thermal Storage

Page 10: THERMAL STORAGE FOR LARGE LABORATORY LOADS, A Case … · 2006-06-26 · THERMAL STORAGE FOR LARGE LABORATORY LOADS, A Case Study August, 2000 Jerry Savage Mechanical Engineer, MTS

Cost Analysis

• First cost was available from the PETLproject that would have been spent onchillers and cooling towers

• Estimated $200,000 a year in energy costsand reduced maintenance

• Simple payback of less than one year,operational before PETL for a near zeropayback period

Page 11: THERMAL STORAGE FOR LARGE LABORATORY LOADS, A Case … · 2006-06-26 · THERMAL STORAGE FOR LARGE LABORATORY LOADS, A Case Study August, 2000 Jerry Savage Mechanical Engineer, MTS

Our Plan

• Gain a complete understanding of theexisting chiller plant operation

• Create a campus wide design intent andoperating structure

• Design the Thermal Storage System tosupply PETL while correcting designdeficiencies of the entire campus system( AE’s design later replaced with Sandiadesign )

Page 12: THERMAL STORAGE FOR LARGE LABORATORY LOADS, A Case … · 2006-06-26 · THERMAL STORAGE FOR LARGE LABORATORY LOADS, A Case Study August, 2000 Jerry Savage Mechanical Engineer, MTS

Our Plan

• Perform a complete flow analysis to verifythe new design

• Implement the findings

• Keep metrics on the operation and correctthe control strategy as required

• Claim victory for our facilities group andlive happily ever after

Page 13: THERMAL STORAGE FOR LARGE LABORATORY LOADS, A Case … · 2006-06-26 · THERMAL STORAGE FOR LARGE LABORATORY LOADS, A Case Study August, 2000 Jerry Savage Mechanical Engineer, MTS
Page 14: THERMAL STORAGE FOR LARGE LABORATORY LOADS, A Case … · 2006-06-26 · THERMAL STORAGE FOR LARGE LABORATORY LOADS, A Case Study August, 2000 Jerry Savage Mechanical Engineer, MTS

System Layout

• Three 1300 ton 1000HP centrifugal chillerswith 2000 GPM circulation pumps

• Primary loop with 20 HP, 4000GPMcirculation pumps

• Decoupled secondary supply loops

Page 15: THERMAL STORAGE FOR LARGE LABORATORY LOADS, A Case … · 2006-06-26 · THERMAL STORAGE FOR LARGE LABORATORY LOADS, A Case Study August, 2000 Jerry Savage Mechanical Engineer, MTS

System Layout

• We first drew up the system and gathereddata, pump curves, etc.

• The system was sketched and reverseengineered with known operating data

• A flow model was done to verify presentoperation

• The new Storage tank was added to the flowmodel

Page 16: THERMAL STORAGE FOR LARGE LABORATORY LOADS, A Case … · 2006-06-26 · THERMAL STORAGE FOR LARGE LABORATORY LOADS, A Case Study August, 2000 Jerry Savage Mechanical Engineer, MTS

Tank Charge Cycle, Two Chillers On, Partial System Load

Page 17: THERMAL STORAGE FOR LARGE LABORATORY LOADS, A Case … · 2006-06-26 · THERMAL STORAGE FOR LARGE LABORATORY LOADS, A Case Study August, 2000 Jerry Savage Mechanical Engineer, MTS

Tank Discharge Cycle, Chillers Off, Medium System Load

Page 18: THERMAL STORAGE FOR LARGE LABORATORY LOADS, A Case … · 2006-06-26 · THERMAL STORAGE FOR LARGE LABORATORY LOADS, A Case Study August, 2000 Jerry Savage Mechanical Engineer, MTS

Final Design Analysis

• Utilized existing pumps, with new VFDdrives, increase primary flow by 50%

• Two connection points with valves for tanklines

• Self balancing

• Blending available with bypass valve

• Chiller Plant sensor upgrade with BTUmeters

Page 19: THERMAL STORAGE FOR LARGE LABORATORY LOADS, A Case … · 2006-06-26 · THERMAL STORAGE FOR LARGE LABORATORY LOADS, A Case Study August, 2000 Jerry Savage Mechanical Engineer, MTS

Design Comparison

• A&E Firm design had six new pumps withassociated VFD’s

• A complicated piping system with at leastsix connection points

• multiple operating valves and bypass lines

• It doesn’t have to be complicated if youtake the time to understand your system

Page 20: THERMAL STORAGE FOR LARGE LABORATORY LOADS, A Case … · 2006-06-26 · THERMAL STORAGE FOR LARGE LABORATORY LOADS, A Case Study August, 2000 Jerry Savage Mechanical Engineer, MTS

Lessons Learned

• Keep tank temperature sensors out of thesun

• Watch your chemical program, it can getexpensive

• Hire an A&E firm with experience inthermal storage

Page 21: THERMAL STORAGE FOR LARGE LABORATORY LOADS, A Case … · 2006-06-26 · THERMAL STORAGE FOR LARGE LABORATORY LOADS, A Case Study August, 2000 Jerry Savage Mechanical Engineer, MTS

Tank design

• One million gallon above ground (no USTregulations )

• Steel with epoxy painted interior

• Ring wall foundation with sand fill ( no oil )

• Active cathodic protection system( impressed current )

Page 22: THERMAL STORAGE FOR LARGE LABORATORY LOADS, A Case … · 2006-06-26 · THERMAL STORAGE FOR LARGE LABORATORY LOADS, A Case Study August, 2000 Jerry Savage Mechanical Engineer, MTS

Lower Difuser Cone

Page 23: THERMAL STORAGE FOR LARGE LABORATORY LOADS, A Case … · 2006-06-26 · THERMAL STORAGE FOR LARGE LABORATORY LOADS, A Case Study August, 2000 Jerry Savage Mechanical Engineer, MTS

Upper Difuser Cone and Roof Structure

Page 24: THERMAL STORAGE FOR LARGE LABORATORY LOADS, A Case … · 2006-06-26 · THERMAL STORAGE FOR LARGE LABORATORY LOADS, A Case Study August, 2000 Jerry Savage Mechanical Engineer, MTS

Insulation System and Sheething

Page 25: THERMAL STORAGE FOR LARGE LABORATORY LOADS, A Case … · 2006-06-26 · THERMAL STORAGE FOR LARGE LABORATORY LOADS, A Case Study August, 2000 Jerry Savage Mechanical Engineer, MTS

Insulation System

• Two inches of polyiso. With a bondedaluminum skin

• Very low losses due to volume vs.. surfacearea

• Losses of around one degree per week in 95degree temperatures

Page 26: THERMAL STORAGE FOR LARGE LABORATORY LOADS, A Case … · 2006-06-26 · THERMAL STORAGE FOR LARGE LABORATORY LOADS, A Case Study August, 2000 Jerry Savage Mechanical Engineer, MTS

Completed Tank

Page 27: THERMAL STORAGE FOR LARGE LABORATORY LOADS, A Case … · 2006-06-26 · THERMAL STORAGE FOR LARGE LABORATORY LOADS, A Case Study August, 2000 Jerry Savage Mechanical Engineer, MTS
Page 28: THERMAL STORAGE FOR LARGE LABORATORY LOADS, A Case … · 2006-06-26 · THERMAL STORAGE FOR LARGE LABORATORY LOADS, A Case Study August, 2000 Jerry Savage Mechanical Engineer, MTS
Page 29: THERMAL STORAGE FOR LARGE LABORATORY LOADS, A Case … · 2006-06-26 · THERMAL STORAGE FOR LARGE LABORATORY LOADS, A Case Study August, 2000 Jerry Savage Mechanical Engineer, MTS
Page 30: THERMAL STORAGE FOR LARGE LABORATORY LOADS, A Case … · 2006-06-26 · THERMAL STORAGE FOR LARGE LABORATORY LOADS, A Case Study August, 2000 Jerry Savage Mechanical Engineer, MTS