tower smoke management

Upload: chidi-henry

Post on 02-Jun-2018

228 views

Category:

Documents


1 download

TRANSCRIPT

  • 8/10/2019 Tower Smoke Management

    1/33

    Tower Smoke Management -

    System Planning, Design &

    Testing

    Kirk Rosenbaum, CCP, PQPSenior Commissioning ManagerKEO International Consultants

  • 8/10/2019 Tower Smoke Management

    2/33

    INTRODUCTIONKirk Rosenbaum, CCP, PQP

    Senior Commissioning Manager

    30 + Years Experience in Design,

    Construction Industry

    12 + Years Experience Exclusively

    in the Area of Commissioning

    10 + Years Experience in Fire Life

    Safety Review and Inspection

    Managed the Commissioning of

    Over 2,500,000 m2 of new buildingsand 250,000 m2 of existing

    buildings

    Former Director and Treasurer of

    the Building Commissioning

    Association

  • 8/10/2019 Tower Smoke Management

    3/33

    Need for Tower Smoke Management

    Sample GCC Tower Fire Events 2012

  • 8/10/2019 Tower Smoke Management

    4/33

    Code & Standard Design Requirements

    NFPA 922012;Standard for Smoke Control Systems

    5.2.1 Pressure differential across smoke barriers shall be 12.5 Pa for fullysprinklered buildings.

    5.2.2 Pressure differential across doors shall not cause the force required to open

    the doors to exceed 133 N.

    5.3 Stairways are to be pressurized to a minimum of 12.5 Pa and a maximum levelthat causes door opening forces to be less than 133 N.

    5.4 Elevators shall be considered a separate smoke zone when smoke control isrequired.

    5.3.5.1 Vestibules shall not be required, but shall be permitted as part of a building

    smoke management system.

  • 8/10/2019 Tower Smoke Management

    5/33

    Code & Standard Design Requirements

    Qatar Civil DefenseFire Safety Standards

    FSS 2.2.13 Smoke Stop or Fire Fighting Lobby required when:(i) Stairway has no natural light or ventilation, or(ii) Stairway traverses more than 4 stories (incl. basements), or(iii) Has a habitable height more than 28 meters above Ground.

    All Fire Fighting Lifts shall be provided with a Fire Fighting Lobby.

    Mechanical Ventilation/Pressurization to be provided at 10 Air Changes per Hour(ACH).

    Mechanical equipment is to be provided with 100% stand-by power.

    Smoke Stop Lobbies shall be no less than 3 square meters in area.Fire Fighting Lobbies shall be no less than 6 square meters in area with nodimension less than 2 meters.

  • 8/10/2019 Tower Smoke Management

    6/33

    Code & Standard Design Requirements

    Qatar Civil DefenseFire Safety Standards

    FSS 2.2.13 Basements exceeding one story in depth require a Smoke Stop Lobbyadjacent to the Fire Fighting Lift and its adjacent stairway only. Other basementstairways do not require Smoke Stop Lobbies.

    FSS 6.6.3

    Fire Lift required when building habitable height exceeds 23 metersabove ground level or 9 meters below ground level.

    FSS 1.5 A high-rise building exceeding 30 storeys shall be provided with refugefloors at an interval not exceeding 20 storeys.

    A high-rise building exceeding 30 storeys shall be provided with refuge floors at aninterval not exceeding 20 storeys.

    A minimum of 50% of the gross floor area of the Refuge Floor must be a protectedHolding Area.

  • 8/10/2019 Tower Smoke Management

    7/33

    Code & Standard Design Requirements

    Qatar Civil DefenseFire Safety Standards

    FSS 1.5 The Holding Area is to be ventilated:(ii) Naturally ventilation requires the total area of the ventilation openings to not

    be less than 25% of the gross floor area of the Holding Area.(iii) Mechanical ventilation is also acceptable as long as the equipment is powered

    via 2-hour fire rated cables and 100% stand-by power is available.

  • 8/10/2019 Tower Smoke Management

    8/33

  • 8/10/2019 Tower Smoke Management

    9/33

    Low-RiseBuilding

    < 23 metersabove ground

    < 9 metersbelow ground

    No smokemgmt system

    required

  • 8/10/2019 Tower Smoke Management

    10/33

    Low-Rise Bldg

    w/ Deep

    Basement < 23 meters

    above ground

    > 9 metersbelow ground

    Fire LiftRequired

    Bsmt StairPressurizationRequired

  • 8/10/2019 Tower Smoke Management

    11/33

    Mid-RiseBuilding

    > 23 metersabove ground

    > 9 metersbelow ground

    Fire LiftRequired

    Bsmt & Tower

    Stairs RequirePressurization

  • 8/10/2019 Tower Smoke Management

    12/33

    High-Rise Bldgw/ Refuge Floor

    > 30 storeysabove ground > 9 meters

    below ground

    Fire LiftRequired

    Evacuation Liftmay be required

    Bsmt Stairs,Tower Stairs,and RefugeRequire

    Pressurization

  • 8/10/2019 Tower Smoke Management

    13/33

    High-Rise Bldgw/ Fire FloorIsolation

    Same physicalfeatures asHigh-Rise

    In addition tostandard High-Rise smokemgmt, two

    floors aboveand below thefire floor arepressurized.

  • 8/10/2019 Tower Smoke Management

    14/33

  • 8/10/2019 Tower Smoke Management

    15/33

    Typical Floor Plan (No Fire Floor Isolation)

  • 8/10/2019 Tower Smoke Management

    16/33

    Pressurized Floor (Fire Floor Isolation)

  • 8/10/2019 Tower Smoke Management

    17/33

    Typical Floor Plan (Fire Floor Isolation)

  • 8/10/2019 Tower Smoke Management

    18/33

    Code & Standard System Sizing MethodRecommendation and Test Requirements

    Document NFPA 92 - 2012 Qatar Civil Defense - FSS

    System SizingMethodRecommendation

    SFPE TR 82-4 Designing StairPressurization Systems(Similar to British StandardMethod)

    ASHRAE Chapter 52 Fire andSmoke Management

    None Provided

    System TestRequirement

    Maintain pressure differentialacross closed doors when(1) 3* Stairway Doors are

    open, or(2) Lifts parked with doors

    open.

    None Provided

    * The number of open stairway doors is determined by the local fire authority and is

    not NFPA prescribed.

  • 8/10/2019 Tower Smoke Management

    19/33

    Calculation ASHRAE 52

    QSP= 0.839 * Asb* (Delta-Psb)1/2 + 0.452 * AOD* (Delta-Psb)

    1/2

    QSP =Fan Flow Rate for Pressurization of Stairway toRequired Static Pressure (m3/s)

    HS = Total Heightof Stairway

    Asb =Total Flow Area between Stairway and Building (m2) -walls and closed doors

    AOD =Flow Area through

    Open Doors (m2)Delta -Psb =

    Primary Pressure Difference betweenStairway & Building (Pa)

  • 8/10/2019 Tower Smoke Management

    20/33

    Calculations Industry Leakage Data

    ASHRAE HANDBOOK 2007Chapter 52

    Field tests haverepeatedlyshown thatLOOSE wall

    constructionshould beutilized for

    system sizing inthe region.

  • 8/10/2019 Tower Smoke Management

    21/33

    Calculations Industry Leakage Data

    SelectDoors

    asAppropriate

    fortheProject

    (Blue

    BoxCanBeIgnored)

  • 8/10/2019 Tower Smoke Management

    22/33

    Calculations Industry Leakage Data

    Important Note: If a stairway has a door with double-leafs,BOTHleaves of the door must be open for testing and it

    only counts as One Door Open.

  • 8/10/2019 Tower Smoke Management

    23/33

    Calculations Industry Leakage Data

    Data from a Tamura and Shaw Study, 1976

  • 8/10/2019 Tower Smoke Management

    24/33

  • 8/10/2019 Tower Smoke Management

    25/33

    Typical SystemLayout

    Air InjectionPoints

    Single pointinjection OK forlifts to approx.40 storeys

    Single pointinjection OK forstairways of

    approx. 15 to 20storeys, but willnot satisfy BsmtStairways

  • 8/10/2019 Tower Smoke Management

    26/33

    RecommendedSystem Layout

    Air InjectionPoints

    Inject air to LiftShafts at top,bottom, andapproximatelyevery 40 storeys

    Inject air tostairways at topand approximatelyevery 15-20 storeys

    Inject air to allbasementstairways

  • 8/10/2019 Tower Smoke Management

    27/33

  • 8/10/2019 Tower Smoke Management

    28/33

    Lessons Learned (Page 1 of 5)

    Pressurization systems to be sized based onASHRAE 52 methodology with loose leakage rates

    and appropriate safety factors.

    Stack effect is negligible based on field test results and

    may generally be discounted in system sizing

    calculation.

    Wind effects are negligible based on field testing and

    may generally be discounted in system sizingcalculation unless stairways or lift shafts are located

    against an exterior wall.

  • 8/10/2019 Tower Smoke Management

    29/33

    Lessons Learned (Page 2 of 5)

    Pressurization system intakes and reliefs should not bedirectly exposed to wind pressure and need to have

    tightly sealing dampers. Either condition may allow

    humid outside air to enter a stairway or shaft and

    could result in mould issues.

    Masonry shafts are not appropriate as air plenums for

    pressurization systems; excessive leakage and

    excessive friction loss.

    For towers taller than 40 storeys single point air

    injection at the top of the building is generally

    insufficient for pressurizing lift shafts.

  • 8/10/2019 Tower Smoke Management

    30/33

    Lessons Learned (Page 3 of 5)

    Pressurization system fans should be equipped withVFDs for the setting of fan maximum speed.

    Pressurization systems should be equipped with

    adjustable pressure relief dampers to prevent system

    over-pressurization of stairways. Pressure sensor

    control may have excessive response time.

    Basement stairs should be equipped with stand-alone

    pressurization systems and not combined with towerpressurization systems.

  • 8/10/2019 Tower Smoke Management

    31/33

    Lessons Learned (Page 4 of 5)

    Pressurization system fans should be equipped with

    VFDs for the setting of fan maximum speed.

    Pressurization systems should be equipped with

    adjustable pressure relief dampers to prevent system

    over-pressurization of stairways. Pressure sensorcontrol may have excessive response time.

    Basement stairs should be equipped with stand-alone

    pressurization systems and not combined with tower

    pressurization systems.

    For towers taller than 15 - 20 storeys single point air

    injection at the top of the building is generally

    insufficient for pressurizing stairways.

  • 8/10/2019 Tower Smoke Management

    32/33

    Lessons Learned (Page 5 of 5)

    Construction schedules should prioritize early

    completion of pressurization systems and the executionof pressurization system testing. (Failure to validate

    the systems early could result in extensive delays

    to the approval for occupancy for the project.)

  • 8/10/2019 Tower Smoke Management

    33/33

    Questions & Answers

    Kirk Rosenbaum, CCP, PQPSenior Commissioning ManagerKEO International Consultants

    Contact Information:PO Box 27594Abu Dhabi, UAE

    +974 050 [email protected]