UL508Afor Panel
Builders Getting Started
siemens.tld/keyword Restricted © Siemens AG 2016
Restricted © Siemens AG 20XX
XX.XX.20XX Page 2 Author / Department
Codes and Regulations for Panel Builders
Exclusion of Liability
The typical circuit diagrams and interpretations of the standard are not binding and do not claim to be complete regarding
configuration, equipment or any other eventuality. They do not represent any client-specific solutions and are only
intended to offer assistance for typical tasks.
Each person viewing this presentation is responsible for the correct operation of the products described. This
presentation does not relieve you of your responsibility regarding safe handling when using, installing, operating, and
maintaining the equipment.
By viewing this presentation you agree that Siemens cannot be made liable for possible damage beyond the above
mentioned liability clause.
We reserve the right to make changes and revisions to this informational documentation without prior announcement.
When writing these guidelines, a lot of tables and texts were lifted straight from the relevant standards. All users of this
documentation must always check whether the items quoted are still up to date or not.
The final decision about the appropriateness of applying the applicable standards must be made by the user of this
documentation.
The reproduction of this presentation and its distribution, utilization or the dissemination of its contents to third parties is
not permitted.
Restricted © Siemens AG 20XX
XX.XX.20XX Page 3 Author / Department
Codes and Regulations for Panel Builders
Speaker
Jeff Woolfolk
Bachelor of Science, Electrical Engineering Technology
System Consultant
Digital Factory
Control Products
Application consulting:
- North American Standards and Codes
- European Directives and international IEC/ISO
standards
www.usa.siemens.com/controlpaneldesign
www.usa.siemens.com/planning-efficiency
Restricted © Siemens AG 20XX
XX.XX.20XX Page 4 Author / Department
Codes and Regulations for Panel Builders
Differences between USA and everywhere else
=
Restricted © Siemens AG 20XX
XX.XX.20XX Page 5 Author / Department
Codes and Regulations for Panel Builders
Excerpts of the OSHA standards and NEC Ed. 2014
OSHA 1910.303(b)(2) Subpart S – Electrical / General requirements:
Installation and use: Listed or labeled equipment shall be installed and used in accordance with any
instructions included in the listing or labeling.
Definitions acc. NEC Art. 100:
Equipment: A general term, including fittings, devices, appliances, luminaires, apparatus, machinery, and the
like used as a part of, or in connection with, an electrical installation.
Listed: Equipment, materials, or services included in a list published by an organization that is acceptable
to the authority having jurisdiction and concerned with evaluation of products or services, that maintains
periodic inspection of production of listed equipment or materials or periodic evaluation of services, and whose
listing states that either the equipment, material, or service meets appropriate designated standards or has
been tested and found suitable for a specified purpose.
Labeled: Equipment or materials to which has been attached a label, symbol, or other identifying mark of
an organization that is acceptable to the authority having jurisdiction and concerned with product evaluation,
that maintains periodic inspection of production of labeled equipment or materials, and by whose labeling the
manufacturer indicates compliance with appropriate standards…etc.
Restricted © Siemens AG 20XX
XX.XX.20XX Page 6 Author / Department
Codes and Regulations for Panel Builders
Relevant standards for panels for the US market
Restricted © Siemens AG 20XX
XX.XX.20XX Page 7 Author / Department
Codes and Regulations for Panel Builders
Comparison between USA and IEC standards
IEC 60364-1
IEC 61439-2
IEC 60204-1
Restricted © Siemens AG 20XX
XX.XX.20XX Page 8 Author / Department
Codes and Regulations for Panel Builders
UL508A Industrial Control Panels
1893 World Exhibition in Chicago
Outbreak of a fire
1894 Start of UL
William H. Merrill opens the
“Underwriters Electrical Bureau”
Restricted © Siemens AG 20XX
XX.XX.20XX Page 9 Author / Department
Codes and Regulations for Panel Builders
National Fire Protection Association
• Foundation: 1896, due to increasing sprinkler system installations
• Headquarters: Quincy, Massachusetts
• Publication of over 300 standards to date
National Electrical Code
or
NFPA70
NFPA79
Electrical Standard for
Industrial Machinery
Standardization organization in the field of fire protection, electrical safety and building safety
Restricted © Siemens AG 20XX
XX.XX.20XX Page 10 Author / Department
Codes and Regulations for Panel Builders
NFPA (nec) and UL508A work together
Restricted © Siemens AG 20XX
XX.XX.20XX Page 11 Author / Department
Codes and Regulations for Panel Builders
NFPA (nec) and UL508A work together
When it comes to Industrial
control panels the NEC 2014
refers still to UL 508A!
Recommendation:
Industrial control Panels should
fulfill furthermore the UL 508A
Maximum voltage 600V!
UL 508A is still
limited to 600V or
less!
Restricted © Siemens AG 20XX
XX.XX.20XX Page 12 Author / Department
Most Important Network Types in Detail
Grounded wye / solidly grounded wye
Slash rating: • e.g.: 480Y/277V, solidly grounded wye
• 3 phase; 4 wire
• 3 phase; 3 wire
Possible devices
480Y/277V; 600/347V
480V; 600V
Note: • All devices having a slash rating with the indicated voltage or higher
• All devices having a delta rating with at least the higher of both voltages
3p, 4w / grounded
phase-ground
U = 277 V
across one
contact
worst case!
L1
L2
L3
Transformer
480Y/277V AC
M
Ik
Restricted © Siemens AG 20XX
XX.XX.20XX Page 13 Author / Department
Most Important Network Types in Detail
Corner grounded delta
Straight (Delta) rating:
• e.g.: 480V / 3 phase - 3 wire
Possible devices in this example: 480V; 600V
Do not use: 480Y/277V; 600Y/347V
Note:
• The devices switch full (=high) voltage at the first single pole short-circuit (phase to ground)
The following applies to this network in principle: Only devices with delta rating must be used!
Phase - Ground
U = 480 V
across one contact
worst case!!
L1
L2 L3
Transformer 480V AC
M
Ik
Restricted © Siemens AG 20XX
XX.XX.20XX Page 14 Author / Department
Most Important Network Types in Detail
Ungrounded delta - Ungrounded wye
Straight rating:
• e.g.: 480V / 3 phase - 3 wire
Possible devices in this example: 480V; 600V
Do not use: 480Y/277V; 600Y/347V
Note:
• The devices switch the full (=high) voltage at the second single-pole
short-circuit (phase to ground)
The following applies to this network in principle: Only devices with delta rating must be used!
480V AC
L1
L2 L3
Transformer
M
Δ/Y
Betrieb
Insulation
measuring
! Operation requires
Insulation monitoring! Ik
Phase - Phase
U = 480 V
across one
contact
worst case!!
Restricted © Siemens AG 20XX
XX.XX.20XX Page 15 Author / Department
Codes and Regulations for Panel Builders
UL Category Code Numbers
• The CCN represents a clear description of the respective product
• The respective CCN Guide Information clearly describes how and under which conditions the respective
product can or may be applied (www.ul.com/database)
• Every AHJ or UL inspector can thus verify whether the respective product was correctly configured and
applied
• The CCN should be additionally integrated in the parts list
Examples: DIVQ // DIVQ7 // NMTR2 // NMTR8
Restricted © Siemens AG 20XX
XX.XX.20XX Page 16 Author / Department
Codes and Regulations for Panel Builders
UL508A Table SA1.1
Restricted © Siemens AG 20XX
XX.XX.20XX Page 17 Author / Department
Codes and Regulations for Panel Builders
(www.ul.com/database)
Restricted © Siemens AG 20XX
XX.XX.20XX Page 18 Author / Department
Codes and Regulations for Panel Builders
UL508A Short Circuit Current Rating (SCCR)
• Requirement of NEC 2005 Art. 409 (mandatory since April 26, 2006)
Re-enforcement of the standards for “industrial control panels” Failures in determining the short-circuit current
rating (= SCCR) of an industrial control panel.
For the short-circuit current rating not only the short-circuit breaking capacity of, e.g. the circuit breaker is
needed, also the short-circuit current rating of every individual device is as relevant.
• SCCR-relevant components in the power circuit, such as:
• Circuit-breakers, contactors, soft starters, overload relays, but also
• Terminals, busbars,
• Supply to an control transformers,
• Frequency converters, …
• Further current limiting “effects” are not allowed to be considered
e.g.: that of wires, cables, busbars, …
Restricted © Siemens AG 20XX
XX.XX.20XX Page 19 Author / Department
Codes and Regulations for Panel Builders
UL508A Short Circuit Current Rating (SCCR)
NEC Article 409.110 Marking
An industrial control panel shall be marked with the following information that is plainly visible after installation:
….
(4) Short-circuit current rating of the industrial control panel based on one of the following:
a. Short-circuit current rating of a listed and labeled assembly
b. Short-circuit current rating established utilizing an approved method
Informational Note: ANSI/UL 508(A), Standard for Industrial Control Panels, Supplement SB, is an
example of an approved method.
Exception to (4): Short-circuit current rating markings are not required for industrial control panels containing
only control circuit components
Restricted © Siemens AG 20XX
XX.XX.20XX Page 20 Author / Department
Codes and Regulations for Panel Builders
UL508A Short Circuit Current Rating (SCCR)
Determination of the short-circuit current rating (SCCR) acc. to NEC409.110 (4):
• Step 1: necessary!
SCCR of the installed and UL-listed components
• Step 2: necessary!
Establishment of the SCCR on the basis of standard values
(UL508A suppl. SB or UL-guide; chapter 5.8.4).
• Step 3: Optional, very helpfull!
SCCR of tested industrial control equipment assemblies
(series rating = 2 circuit breakers in series or combination tests = motor branch circuits)
• Step 4: Optional, not very helpfull!
Use of current limiting devices (transformers, fuses, circuit breakers)
Restricted © Siemens AG 20XX
XX.XX.20XX Page 21 Author / Department
Codes and Regulations for Panel Builders
UL508A Short Circuit Current Rating (SCCR)
Restricted © Siemens AG 20XX
XX.XX.20XX Page 22 Author / Department
Codes and Regulations for Panel Builders
UL508A Short Circuit Current Rating (SCCR)
List the short circuit current ratings of
components, from UL 508A, Table SB 4.1, if
no values on the nameplate or on
instructions provided with the components
(see step 1)
Establishment of the SCCR value using the table in UL508A. These standard values must be used if
the technical documents do not provide SCCR values for the applied devices.
Restricted © Siemens AG 20XX
XX.XX.20XX Page 23 Author / Department
SCCR of tested industrial control equipment assemblies
Series rating tests Series connection of 2 or more devices, which are able to automatically respond in short circuit cases without delay.
SB4.3.2 in UL508A
! Current limiting cannot be used here !
Combination tests Series connection of any type of devices, e.g.:
§Motor protection circuit breaker and contactor (=fuseless load feeders as type F acc. to UL508)
§MCCB and terminal block
Codes and Regulations for Panel Builders
UL508A Short Circuit Current Rating (SCCR)
Restricted © Siemens AG 20XX
XX.XX.20XX Page 24 Author / Department
Codes and Regulations for Panel Builders
UL508A Short Circuit Current Rating (SCCR)
MCCB
3VL
MCB
5SJ4..HG4
M
MCCB
3VL
3RB
motor protection
relay
3RT
contactor
Fuse
Series rating Tested combinations
MCB
5SJ4..HG4
Series rating for Siemens Breakers www.ul.com/database
Restricted © Siemens AG 20XX
XX.XX.20XX Page 25 Author / Department
Codes and Regulations for Panel Builders
UL508A Short Circuit Current Rating (SCCR)
Main Disconnect
contactor contactor
motor heater
Overload-
relay
contactor
motor
Overload-
relay
Every Transformer is current limiting
Short circuit protection Short circuit protection Short circuit protection
Feeder circuit
Branch circuit
Current limiting
device
Transformer peak-let-through currents
can be used to protect Branch circuits!
Restricted © Siemens AG 20XX
XX.XX.20XX Page 26 Author / Department
Codes and Regulations for Panel Builders
UL508A Short Circuit Current Rating (SCCR)
Restricted © Siemens AG 20XX
XX.XX.20XX Page 27 Author / Department
Codes and Regulations for Panel Builders
UL508A Short Circuit Current Rating (SCCR)
Restricted © Siemens AG 20XX
XX.XX.20XX Page 28 Author / Department
Codes and Regulations for Panel Builders
UL508A Short Circuit Current Rating (SCCR)
1.) Single Phase Transformers:
Transformer Full-Load Current (IFL) = (Transformer kVA x 1000) / Voltage*
Short Circuit Current (ISC line-to-line) = ((Transformer Full Load Current (IFL ))
/ Transformer Impedance (Z)
2.) Three Phase Transformers:
Transformer Full-Load Current (IFL) = (Transformer kVA x 1000) / (Voltage** x
1.732)
Short Circuit Current (ISC line-to-line-to-line) = ((Transformer Full Load Current
(IFL )) / Transformer Impedance (Z)
Restricted © Siemens AG 20XX
XX.XX.20XX Page 29 Author / Department
Codes and Regulations for Panel Builders
UL508A Short Circuit Current Rating (SCCR)
Class J Fuse, 100 Amps
A.I.C: 100 kA
MCB
A.I.C: 10 kA
@480V
Compact MSP
A.I.C: 30 kA
@480V
MSP
A.I.C: 65 kA
@480V
Contactors
SCCR: 5 kA
@480V
Solid state relay
SCCR: 5 kA
@480V
Terminal Block
SCCR: 10 kA
@480V
Terminal Block
SCCR: 10 kA
@480V
Terminal Block
SCCR: 10 kA
@480V
Terminal Blocks
SCCR: 10 kA
@480V
MSP’s
A.I.C: 65 kA
@480V
Infeed system
SCCR: 65 kA
@480V
Transformer: S = 150 kVA, Z = 4%, 3 Phase, 480/277V
Available secondary Fault Current = 4.6kA @480V
Power Distribution Block
SCCR: 10 kA
@480V
Result:
Overall SCCR = 100kA = A.I.C of the
Class J Fuse on the primary side of
the Transformer since the available
secondary fault current of the
transformer (4.6kA) is less than the
SCCR and A.I.C’s of the components
on the load side of the transformer
3 Ph. 480Y/277V AC
Restricted © Siemens AG 20XX
XX.XX.20XX Page 30 Author / Department
Codes and Regulations for Panel Builders
UL508A Short Circuit Current Rating (SCCR)
• Use of current limiting fuses, when used as feeder elements SB 4.3.3
• Only fuses listed in UL508A – table SB 4.2 are applicable.
• Use let-through values from the UL508A – table SB 4.2 ONLY
(manufacturer‘s values are NOT permissible)
• Fuses are also standardized in the geometrical dimensions
manufacturer-independent replacement
• The fuse is replaced by the service staff, which shall not compare
the corresponding let-through values
(old fuse versus new fuse)
• Note:
For practical application only partially useable, as, e.g.:
• Standard contactor up to 37kW: max. 5kA
• Standard busbar: max. 10kA
• Standard terminal block: max. 10kA
Restricted © Siemens AG 20XX
XX.XX.20XX Page 31 Author / Department
Use of current limiting fuses, when used as
feeder elements SB 4.3.3
Use let-through values from the UL508A –
table SB 4.2 ONLY
(manufacturer‘s values are NOT
permissible)
Fuses are also standardized in the
geometrical dimensions
manufacturer-independent replacement
The fuse is replaced by the service staff,
which shall not compare
the corresponding let-through values
(old fuse versus new fuse)
Example: There are 7 different 30A Class R
Fuses, each. with different characteristics
Codes and Regulations for Panel Builders
UL508A Short Circuit Current Rating (SCCR)
Restricted © Siemens AG 20XX
XX.XX.20XX Page 32 Author / Department
Codes and Regulations for Panel Builders
UL508A Short Circuit Current Rating (SCCR)
• Use of current limiting circuit breakers, listed as “current limiting”, when applied as feeder element SB
4.3.2
• The circuit breaker must be listed as “current limiting”
• The circuit breaker must be marked as “current limiting” (UL508A – SB 4.3.2)
• The manufacturer has to publish the current limiting characteristics or data and provide them to the user
• When replacing the circuit breaker by a different type or manufacturer, the SCCR value must be checked again
engineering is required
• Note:
For practical applications hardly usable, as, e.g.:
• Standard contactor up to 37kW: max. 5kA
• Standard busbar: max. 10kA
• Standard terminal block: max. 10kA
Siemens “current limiting” breakers
Restricted © Siemens AG 20XX
XX.XX.20XX Page 33 Author / Department
Codes and Regulations for Panel Builders
UL508A Short Circuit Current Rating (SCCR)
Siemens SIRIUS Contactor 3RT1035
Short Circuit Current 5kA, 600V
Restricted © Siemens AG 20XX
XX.XX.20XX Page 34 Author / Department
Codes and Regulations for Panel Builders
UL508A Short Circuit Current Rating (SCCR)
Type F
Magnetic
Motor
Control
See report in the annex
Restricted © Siemens AG 20XX
XX.XX.20XX Page 35 Author / Department
Codes and Regulations for Panel Builders
UL508A Short Circuit Current Rating (SCCR)
http://www.usa.siemens.com/sccr