3/9/2018 1 © buildingscience.com Unvented Roofs Without Spray Foam: The Latest Building America Research Kohta Ueno NESEA BE18: Unvented Roofs Without Spray Foam 2 © buildingscience.com Background NESEA BE18: Unvented Roofs Without Spray Foam 3 © buildingscience.com Ventilated Attics—Best Choice Roof sheathing dries to ventilated attic-moisture safe Interior moisture (air leaks) ventilated away in winter Air sealing at ceiling critical for best performance (e.g., spray foam air barrier, detail with sealant) NESEA BE18: Unvented Roofs Without Spray Foam 4 © buildingscience.com Then Why Unvented Roofs? Living space built into roof Vented cathedral assemblies— often poor performance Complicated rooflines, hip geometries—how to vent? Unworkable air barrier at ceiling line Blown-in rain (coastal) Hurricane tear-off HVAC in vented attic

Upload: others

Post on 05-Jun-2020

14 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Unvented Roofs Without Spray Foam: The Latest Building ......Unvented Roofs Without Spray Foam: The Latest Building America Research Kohta Ueno NESEA BE18: Unvented Roofs Without Spray

3/9/2018

1

© buildingscience.com

Unvented Roofs Without Spray Foam:The Latest Building America Research

Kohta Ueno

NESEA BE18: Unvented Roofs Without Spray Foam2

© buildingscience.com

Background

NESEA BE18: Unvented Roofs Without Spray Foam3

© buildingscience.com

Ventilated Attics—Best Choice Roof sheathing dries to

ventilated attic-moisture safe Interior moisture (air leaks)

ventilated away in winter Air sealing at ceiling critical for

best performance (e.g., spray foam air barrier,

detail with sealant)

NESEA BE18: Unvented Roofs Without Spray Foam4

© buildingscience.com

Then Why Unvented Roofs? Living space built into roof Vented cathedral assemblies—

often poor performance Complicated rooflines, hip

geometries—how to vent? Unworkable air barrier at

ceiling line Blown-in rain (coastal) Hurricane tear-off HVAC in vented attic

Page 2: Unvented Roofs Without Spray Foam: The Latest Building ......Unvented Roofs Without Spray Foam: The Latest Building America Research Kohta Ueno NESEA BE18: Unvented Roofs Without Spray

3/9/2018

2

NESEA BE18: Unvented Roofs Without Spray Foam5

© buildingscience.com

Ducts in unconditioned attic = huge energy losses Industry reluctant to move ducts out of attic Ice dam issues due to duct losses

Solution: bring ducts into conditioned space Unvented/conditioned attic—keeps ductwork in

conditioned space, duct leak issues eliminated

Unvented Roofs & HVAC Placement

NESEA BE18: Unvented Roofs Without Spray Foam6

© buildingscience.com

Fibrous Insulation Unvented Roofs Dense pack insulation of unvented roofs common

in cold-climate retrofits Moisture risks (see BSI-043 “Don't Be Dense—

Cellulose and Dense-Pack Insulation”)—2 in 10 failure? Violates I-codes (see IRC§R806.4/R806.5) “Ridge rot”—localized problems (SIPS same problem)

NESEA BE18: Unvented Roofs Without Spray Foam7

© buildingscience.com

Why Unvented + Fibrous Risky? Different than walls? Moisture risks at sheathing Interior-sourced air leakage Vapor contributing too? Zero-perm exterior (“wrong

side perfect vapor barrier”) Night sky radiation cooling Stack effect in winter “Ridge rot” (thermal and

moisture buoyancy)

NESEA BE18: Unvented Roofs Without Spray Foam8

© buildingscience.com

Why Unvented + Loose Fill Risky? Risk reduced by: Airtightness of ceiling Dense insulations-less

airflow Solar drive

But white roofs, shading

Lower interior RH (winter) Why many of them work?

Lower permeance interior Assumes good airtightness—

vapor retarder not bypassed

Moisture accumulation: what gets in vs. gets out

Page 3: Unvented Roofs Without Spray Foam: The Latest Building ......Unvented Roofs Without Spray Foam: The Latest Building America Research Kohta Ueno NESEA BE18: Unvented Roofs Without Spray

3/9/2018

3

NESEA BE18: Unvented Roofs Without Spray Foam9

© buildingscience.com

Spray Foam/Exterior Insulation Roofs

2006 IRC: R806.4 Unvented attic assemblies Minimum R-value of “air impermeable insulation” Actually ratio of R-values (BSI-100 Hybrid Assemblies)

Nail base needed with rigid foam on roof deck

NESEA BE18: Unvented Roofs Without Spray Foam10

© buildingscience.com

Spray Foam/Exterior Insulation Roofs

2006 IRC: R806.4 Unvented attic assemblies Minimum R-value of “air impermeable insulation” Actually ratio of R-values (BSI-100 Hybrid Assemblies)

Nail base needed with rigid foam on roof deck

NESEA BE18: Unvented Roofs Without Spray Foam11

© buildingscience.com

Why Fibrous Fill Unvented Roofs? Unvented roofs without spray/board foams could

reduce costs and increase market penetration… IF moisture damage risks are addressed

Retrofit opportunities (existing uninsulated living space at roof line, without removing finishes)

NESEA BE18: Unvented Roofs Without Spray Foam12

© buildingscience.com

Previous Building America Research

Page 4: Unvented Roofs Without Spray Foam: The Latest Building ......Unvented Roofs Without Spray Foam: The Latest Building America Research Kohta Ueno NESEA BE18: Unvented Roofs Without Spray

3/9/2018

4

NESEA BE18: Unvented Roofs Without Spray Foam13

© buildingscience.com

Previous Building America Research Chicago (CZ 5A): One winter, 50% RH Unvented roofs-high risk Cellulose lower risk than FG

batt Vented compact roof (chute)

safe-but poor air leakage Houston/Orlando (CZ 2A): 2 attics, multiple seasons Diffusion vents allow greater

drying, avoid moisture problems

5 Top Vent Fiberglass-GWB

4 Top Vent Fiberglass

2 Top Vent Cellulose-GW

3 Top Vent Cellulose

7 Unvented Cellulose6 Diffusion Vent Cellulose

1 Vented

Chicagoroof disassembly

Houston roof w. diffusion ventNESEA BE18: Unvented Roofs Without Spray Foam

14© buildingscience.com

Diffusion Vent Prototype (Houston)200+ perms diffusion ventAir barrier closed

NESEA BE18: Unvented Roofs Without Spray Foam15

© buildingscience.com

Diffusion Vent Prototype (Orlando-Tile)200+ perms diffusion ventAir barrier closed

NESEA BE18: Unvented Roofs Without Spray Foam16

© buildingscience.com

Houston/Orlando Results Diffusion vent avoids wintertime ridge

accumulation problems (ridge peak RHs/MCs) No failures at low interior RH, bigger difference at

higher RH (interior humidification) Airtightness disappointing in some cases-no SPF

0

10

20

30

40

50

60

70

80

90

100

0

5

10

15

20

25

30

35

40

45

50

10/1/14 1/9/15 4/19/15 7/28/15 11/5/15 2/13/16

Relativ

e Hu

midity

 (%)

Moisture Co

nten

t (%)

DVR1 Peak Wafer UVR1 Peak WaferDVR1 Peak RH UVR1 Peak RH

Unvented

Dif. Vent.

Dif. Vent.Unvented

Summer WinterWinter

Page 5: Unvented Roofs Without Spray Foam: The Latest Building ......Unvented Roofs Without Spray Foam: The Latest Building America Research Kohta Ueno NESEA BE18: Unvented Roofs Without Spray

3/9/2018

5

NESEA BE18: Unvented Roofs Without Spray Foam17

© buildingscience.com

Orlando Decommissioning

Some bays still full Others fiberglass settling and minor mold growth

NESEA BE18: Unvented Roofs Without Spray Foam18

© buildingscience.com

“Ridge Rot” and Moisture Buoyancy

NESEA BE18: Unvented Roofs Without Spray Foam19

© buildingscience.com

Houston and Jacksonville (CZ 2A) 2001

NESEA BE18: Unvented Roofs Without Spray Foam20

© buildingscience.com

Moisture Buoyancy Moisture concentrated at highest point in

conditioned attic (ridge) Not a simple one-dimensional problem Not a straight-up air leakage problem Problem with open-cell spray foam (ocSPF)

unvented roofs (high RHs in attic)-many climates But not ccSPF—lower vapor permeance

Concentration of interior-sourced moisture Moist air is lower density (“lighter”) than dry air Others: “system in equilibrium has same dewpoint

in connected air space”

Page 6: Unvented Roofs Without Spray Foam: The Latest Building ......Unvented Roofs Without Spray Foam: The Latest Building America Research Kohta Ueno NESEA BE18: Unvented Roofs Without Spray

3/9/2018

6

NESEA BE18: Unvented Roofs Without Spray Foam21

© buildingscience.com

“Ping Pong” Water

See BSI-016: Ping Pong Water and The Chemical Engineer

NESEA BE18: Unvented Roofs Without Spray Foam22

© buildingscience.com

“Ping Pong” Water

See BSI-016: Ping Pong Water and The Chemical Engineer

NESEA BE18: Unvented Roofs Without Spray Foam23

© buildingscience.com

“Ping Pong” Water

“Gas separation process similar to pressure swing adsorption”

Solar-powered moisture concentration machine

NESEA BE18: Unvented Roofs Without Spray Foam24

© buildingscience.com

Orlando Decommissioning

Page 7: Unvented Roofs Without Spray Foam: The Latest Building ......Unvented Roofs Without Spray Foam: The Latest Building America Research Kohta Ueno NESEA BE18: Unvented Roofs Without Spray

3/9/2018

7

NESEA BE18: Unvented Roofs Without Spray Foam25

© buildingscience.com

Orlando Decommissioning

‐10

0

10

20

30

40

50

60

70

80

90

50 60 70 80 90

Height (in.)

Temperature/Dewpoint  (F)

Temperature (F)

Dewpoint (F)

‐10

0

10

20

30

40

50

60

70

80

90

50 60 70 80 90

Height (in.)

Temperature/Dewpoint  (F)

Temperature (F)

Dewpoint (F)

Temperature and dewpoint stratification directly measured

90%+ RH near ridge System is not in equilibrium

NESEA BE18: Unvented Roofs Without Spray Foam26

© buildingscience.com

Test Hut Approach & Construction

NESEA BE18: Unvented Roofs Without Spray Foam27

© buildingscience.com

Test Hut Experimental Approach Climate Zone 5A test hut Eight north-south roof bays ±R-50 (14-¾” framing, 2012 IECC) Test variables (Winter 1 2016-2017):

Vapor retarder: variable perm vs. fixed perm

Diffusion vent at ridge vs. no diffusion vent

Fiberglass vs. cellulose “Control” comparison

(§R806.4 spray foam + fibrous) Varying interior boundary conditions

Winter 1: “Normal” interior conditions Winter 2: Elevated RH (50% constant) Winter 3: Air leakage into rafter bays

Test Hut South Elevation

NESEA BE18: Unvented Roofs Without Spray Foam28

© buildingscience.com

Test Hut Construction

Walls 2x6, ccSPF, ZIP sheathing, 4” Roxul, 1x3s Roof cavity 14-¾” deep, ~R-50 (2x12 + 2x4) 8:12 roof pitch

Page 8: Unvented Roofs Without Spray Foam: The Latest Building ......Unvented Roofs Without Spray Foam: The Latest Building America Research Kohta Ueno NESEA BE18: Unvented Roofs Without Spray

3/9/2018

8

NESEA BE18: Unvented Roofs Without Spray Foam29

© buildingscience.com

Test Hut Construction

Adhered membrane connection roof-to-wall Overhangs (eave & rake) attached outboard of air

barrier layer Self-adhered membrane on entire roof

NESEA BE18: Unvented Roofs Without Spray Foam30

© buildingscience.com

Test Hut Construction

Roof bays 24” o.c. Guard bays between experimental bays

(“flash and blow” ccSPF + cellulose) Fluid-applied air and vapor barrier at guard bays

NESEA BE18: Unvented Roofs Without Spray Foam31

© buildingscience.com

Test Hut Construction

Flash and blow bays (ccSPF shown) ccSPF completes air barrier between bays, wiring holes

Insulation netted & blown (fiberglass complete in image; cellulose installation)

NESEA BE18: Unvented Roofs Without Spray Foam32

© buildingscience.com

Test Hut Construction

Interior air barrier & vapor retarder membrane Double tape seal (double-sided tape + housewrap

tape)

Page 9: Unvented Roofs Without Spray Foam: The Latest Building ......Unvented Roofs Without Spray Foam: The Latest Building America Research Kohta Ueno NESEA BE18: Unvented Roofs Without Spray

3/9/2018

9

NESEA BE18: Unvented Roofs Without Spray Foam33

© buildingscience.com

Test Hut Construction

Space conditioning with MSHP (heating & cooling) Ventilation via wall-mounted exhaust fan Solar control with roll-down shades

(all-south glazing)

NESEA BE18: Unvented Roofs Without Spray Foam34

© buildingscience.com

Test Hut Construction

Instrumentation completion

NESEA BE18: Unvented Roofs Without Spray Foam35

© buildingscience.com

Test Hut Construction

ccSPF in guard bays and walls

NESEA BE18: Unvented Roofs Without Spray Foam36

© buildingscience.com

Test Hut Construction

Fibrous insulation installed

Page 10: Unvented Roofs Without Spray Foam: The Latest Building ......Unvented Roofs Without Spray Foam: The Latest Building America Research Kohta Ueno NESEA BE18: Unvented Roofs Without Spray

3/9/2018

10

NESEA BE18: Unvented Roofs Without Spray Foam37

© buildingscience.com

Test Hut Construction

Interior air/vapor control installed

NESEA BE18: Unvented Roofs Without Spray Foam38

© buildingscience.com

Experimental Approach

NESEA BE18: Unvented Roofs Without Spray Foam39

© buildingscience.com

Experimental Approach: Insulation Mat’ls Rafter bay insulation materials Cellulose @ 3.5 PCF, ±R-52 Fiberglass @ 1.4 PCF, ±R-59

Hybrid ccSPF and cellulose roofs §R806.5 in 2012 IRC ±R-63, 40%-60% ratio

NESEA BE18: Unvented Roofs Without Spray Foam40

© buildingscience.com

Experimental Approach: Insulation Mat’ls Rafter bay insulation materials Cellulose @ 3.5 PCF, ±R-52 Fiberglass @ 1.4 PCF, ±R-59

Hybrid ccSPF and cellulose roofs §R806.5 in 2012 IRC ±R-63, 40%-60% ratio

Page 11: Unvented Roofs Without Spray Foam: The Latest Building ......Unvented Roofs Without Spray Foam: The Latest Building America Research Kohta Ueno NESEA BE18: Unvented Roofs Without Spray

3/9/2018

11

NESEA BE18: Unvented Roofs Without Spray Foam41

© buildingscience.com

0

5

10

15

20

25

30

35

40

45

50

0% 10% 20% 30% 40% 50% 60% 70% 80% 90% 100%

Perm

s

Relative Humidity (%)

Kraft Facing

CertainTeed MemBrain

DuPont AirGuard Control

DuPont AirGuard Smart (Up)

DuPont AirGuard Smart (Dn)

Owens‐Corning

Experimental Approach: Vapor Control Fixed perm: Owens Corning HPCA

(0.8 dry/1.4 wet) DuPont™ AirGuard®

Control (0.7 perm) About 1 perm (Class II)

Variable perm CertainTeed MemBrain DuPont™ AirGuard

Smart Gen2

NESEA BE18: Unvented Roofs Without Spray Foam42

© buildingscience.com

Experimental Approach: Diffusion Vent

±5 in. opening (fits under typical ridge cap) Cosella-Dörken Delta-Foxx 214 perms dry cup 550 perms wet cup

NESEA BE18: Unvented Roofs Without Spray Foam43

© buildingscience.com

Experimental Approach: Test Roof IDs

4 fiberglass bays 3 cellulose bays 1 “flash and blow” control comparison

Roof # Insulation Interior VB Diffusion Vent1 Fiberglass Fixed perm Yes2 Fiberglass Variable perm Yes3 Fiberglass Fixed perm No4 Fiberglass Variable perm No5 Dense pack cellulose Fixed perm No6 Dense pack cellulose Variable perm No7 Dense pack cellulose Variable perm Yes8 ccSPF + cellulose “flash

and blow” §R806.4 Latex paint on GWB No

NESEA BE18: Unvented Roofs Without Spray Foam44

© buildingscience.com

Experimental Approach: Roof Section

4 fiberglass bays 3 cellulose bays 1 “flash and blow” control comparison

Page 12: Unvented Roofs Without Spray Foam: The Latest Building ......Unvented Roofs Without Spray Foam: The Latest Building America Research Kohta Ueno NESEA BE18: Unvented Roofs Without Spray

3/9/2018

12

NESEA BE18: Unvented Roofs Without Spray Foam45

© buildingscience.com

Instrumentation Design

NESEA BE18: Unvented Roofs Without Spray Foam46

© buildingscience.com

Instrumentation Design: Fibrous InsulationTypical Unvented Bay

Asphalt shinglesSelf‐adhered membraneOSB 5/8” ZIP roof panel)Cavity insulation (dense pack cellulose or blown fiberglass)Interior vapor control layer (fixed or variable perm membrane)

MC/T Sheathing High

MC/T Sheathing Mid

MC/T Sheathing Low

RH/T Mid Interior

RH/T RidgeWafer at Ridge

Sensor Key:Relative humidity/temperatureMoisture content/temperatureMoisture content block “wafer”

RH/T Sheathing Mid

Notes“MC/T Sheathing High” is at top edge of sheathing at diffusion vent, or equivalent location in non‐DV roofsWafer and RH/T at ridge are directly under ridge

Wafer (South only)

NESEA BE18: Unvented Roofs Without Spray Foam47

© buildingscience.com

Instrumentation Design: Fibrous InsulationTypical Unvented Bay

Asphalt shinglesSelf‐adhered membraneOSB 5/8” ZIP roof panel)Cavity insulation (dense pack cellulose or blown fiberglass)Interior vapor control layer (fixed or variable perm membrane)

MC/T Sheathing High

MC/T Sheathing Mid

MC/T Sheathing Low

RH/T Mid Interior

RH/T RidgeWafer at Ridge

Sensor Key:Relative humidity/temperatureMoisture content/temperatureMoisture content block “wafer”

RH/T Sheathing Mid

Notes“MC/T Sheathing High” is at top edge of sheathing at diffusion vent, or equivalent location in non‐DV roofsWafer and RH/T at ridge are directly under ridge

Wafer (South only)

NESEA BE18: Unvented Roofs Without Spray Foam48

© buildingscience.com

Instrumentation Design: Fibrous InsulationTypical Unvented Bay

Asphalt shinglesSelf‐adhered membraneOSB 5/8” ZIP roof panel)Cavity insulation (dense pack cellulose or blown fiberglass)Interior vapor control layer (fixed or variable perm membrane)

MC/T Sheathing High

MC/T Sheathing Mid

MC/T Sheathing Low

RH/T Mid Interior

RH/T RidgeWafer at Ridge

Sensor Key:Relative humidity/temperatureMoisture content/temperatureMoisture content block “wafer”

RH/T Sheathing Mid

Notes“MC/T Sheathing High” is at top edge of sheathing at diffusion vent, or equivalent location in non‐DV roofsWafer and RH/T at ridge are directly under ridge

Wafer (South only)

Page 13: Unvented Roofs Without Spray Foam: The Latest Building ......Unvented Roofs Without Spray Foam: The Latest Building America Research Kohta Ueno NESEA BE18: Unvented Roofs Without Spray

3/9/2018

13

NESEA BE18: Unvented Roofs Without Spray Foam49

© buildingscience.com

Instrumentation Design: Fibrous InsulationTypical Unvented Bay

Asphalt shinglesSelf‐adhered membraneOSB 5/8” ZIP roof panel)Cavity insulation (dense pack cellulose or blown fiberglass)Interior vapor control layer (fixed or variable perm membrane)

MC/T Sheathing High

MC/T Sheathing Mid

MC/T Sheathing Low

RH/T Mid Interior

RH/T RidgeWafer at Ridge

Sensor Key:Relative humidity/temperatureMoisture content/temperatureMoisture content block “wafer”

RH/T Sheathing Mid

Notes“MC/T Sheathing High” is at top edge of sheathing at diffusion vent, or equivalent location in non‐DV roofsWafer and RH/T at ridge are directly under ridge

Wafer (South only)

NESEA BE18: Unvented Roofs Without Spray Foam50

© buildingscience.com

Instrumentation Design: Flash & Blow

“Flash and blow” roof: instruments shifted to ccSPF/cellulose interface

Control “Flash and Blow” BayAsphalt shinglesSelf‐adhered membraneOSB (5/8” ZIP roof panel)4" ccSPF insulationDense pack cellulose (±10")Interior gypsum board

MC/T Sheathing High

MC/T Sheathing Mid

MC/T Sheathing Low

RH/T Mid Interface

RH/T Ridge

Wafer at Interface

Sensor Key:Relative humidity/temperatureMoisture content/temperatureMoisture content block “wafer”

RH/T Sheathing Mid

Notes“MC/T Sheathing High” is at top edge of sheathing at diffusion vent, or equivalent location in non‐DV roofsWafer and RH/T at ridge are directly under ridge“Interface” denotes spray foam‐to‐fibrous insulation interface

RH/T Ridge Interface

Wafer Mid Interface (North only)

NESEA BE18: Unvented Roofs Without Spray Foam51

© buildingscience.com

Instrumentation Design: Interior T/RH

Interior temperature/RH measurements Low/high, east/west (4 total)

NESEA BE18: Unvented Roofs Without Spray Foam52

© buildingscience.com

Instrumentation Design: Exterior

Exterior temperature/RH (north side) Solar radiation (north and south roofs) Data collected hourly on Campbell CR1000

Page 14: Unvented Roofs Without Spray Foam: The Latest Building ......Unvented Roofs Without Spray Foam: The Latest Building America Research Kohta Ueno NESEA BE18: Unvented Roofs Without Spray

3/9/2018

14

NESEA BE18: Unvented Roofs Without Spray Foam53

© buildingscience.com

Year One Results: Boundary Conditions

NESEA BE18: Unvented Roofs Without Spray Foam54

© buildingscience.com

Boundary Conditions: Temperature

Data from December 2016-July 2017 Loss of data in January (power loss, flood),

April (GFCI tripping)

NESEA BE18: Unvented Roofs Without Spray Foam55

© buildingscience.com

Boundary Conditions: Relative Humidity

RHs in winter 25% to 45% Exhaust fan operation affects interior RH levels and

building depressurization Interior RH in summer 60-80%: MSHP cooling

NESEA BE18: Unvented Roofs Without Spray Foam56

© buildingscience.com

Boundary Conditions: Dewpoint

Dewpoint variations→exterior DP, exhaust fan Wintertime DP ~10 C/50 F during non-fan periods DP tracking exterior in summertime

Page 15: Unvented Roofs Without Spray Foam: The Latest Building ......Unvented Roofs Without Spray Foam: The Latest Building America Research Kohta Ueno NESEA BE18: Unvented Roofs Without Spray

3/9/2018

15

NESEA BE18: Unvented Roofs Without Spray Foam57

© buildingscience.com

Year One Results: Fiberglass Roofs

NESEA BE18: Unvented Roofs Without Spray Foam58

© buildingscience.com

Fiberglass Roofs: Color Codes

VB = fixed perm vapor retarder SVR = variable perm “smart” vapor retarder nDV/DV = no diffusion vent/diffusion vent

Roof # Insulation Interior VB Diffusion Vent1 Fiberglass Fixed perm Yes2 Fiberglass Variable perm Yes3 Fiberglass Fixed perm No4 Fiberglass Variable perm No5 Dense pack cellulose Fixed perm No6 Dense pack cellulose Variable perm No7 Dense pack cellulose Variable perm Yes8 ccSPF + cellulose “flash

and blow” §R806.4Latex paint on GWB No

Roof Short Name1 FG‐VB‐DV2 FG‐SVR‐DV3 FG‐VB‐nDV4 FG‐SVR‐nDV

NESEA BE18: Unvented Roofs Without Spray Foam59

© buildingscience.com

Interpreting the Data (Moisture Risks) Relative Humidity (RH) 80% RH: conservative/unrealistic threshold 90%-100% RH: mold risks, but temperature effects Condensation (liquid water): mold growth kickstarter

Wood Moisture Content (MC) Under 20% MC safe 25%-30% MC ideal for mold growth 28%+ MC decay fungi…. BUT Previous work (double stud walls): high MCs, no damage

Mold Index Combines RH, temperature, and time

NESEA BE18: Unvented Roofs Without Spray Foam60

© buildingscience.com

Roof Short Name1 FG‐VB‐DV2 FG‐SVR‐DV3 FG‐VB‐nDV4 FG‐SVR‐nDV

Roof 3 (nDV) > 90% RH most of winter Roof 4 (nDV) 100% RH, then failed Roofs 1 & 2 (DV) RHs swing, not as high DV roofs remain drier than nDV

Fiberglass Roofs: Ridge RH

Page 16: Unvented Roofs Without Spray Foam: The Latest Building ......Unvented Roofs Without Spray Foam: The Latest Building America Research Kohta Ueno NESEA BE18: Unvented Roofs Without Spray

3/9/2018

16

NESEA BE18: Unvented Roofs Without Spray Foam61

© buildingscience.com

Roof Short Name1 FG‐VB‐DV2 FG‐SVR‐DV3 FG‐VB‐nDV4 FG‐SVR‐nDV

Roof 3 (nDV) > 90% RH most of winter Roof 4 (nDV) 100% RH, then failed Roofs 1 & 2 (DV) RHs swing, not as high DV roofs remain drier than nDV

Fiberglass Roofs: Ridge RH

NESEA BE18: Unvented Roofs Without Spray Foam62

© buildingscience.com

Fiberglass Roofs: Ridge Wafers

Roofs 3 & 4 (nDV) > 40% MC Immersed wafer calibrated ~40-45% MC

Roofs 1 & 2 (DV) stay drier <25% DV: localized drying at ridge-accumulation point

Roof Short Name1 FG‐VB‐DV2 FG‐SVR‐DV3 FG‐VB‐nDV4 FG‐SVR‐nDV

NESEA BE18: Unvented Roofs Without Spray Foam63

© buildingscience.com

Fiberglass Roofs: Ridge Wafers

Roofs 3 & 4 (nDV) > 40% MC Immersed wafer calibrated ~40-45% MC

Roofs 1 & 2 (DV) stay drier <25% DV: localized drying at ridge-accumulation point

Roof Short Name1 FG‐VB‐DV2 FG‐SVR‐DV3 FG‐VB‐nDV4 FG‐SVR‐nDV

NESEA BE18: Unvented Roofs Without Spray Foam64

© buildingscience.com

Fiberglass Roofs: North Sheathing RH

All roofs 90-100% most of winter Dip in RH during warmer weather Diffusion vent-localized protection only? Interface RH falls into spring-summer

Roof Short Name1 FG‐VB‐DV2 FG‐SVR‐DV3 FG‐VB‐nDV4 FG‐SVR‐nDV

Page 17: Unvented Roofs Without Spray Foam: The Latest Building ......Unvented Roofs Without Spray Foam: The Latest Building America Research Kohta Ueno NESEA BE18: Unvented Roofs Without Spray

3/9/2018

17

NESEA BE18: Unvented Roofs Without Spray Foam65

© buildingscience.com

Fiberglass Roofs: South Sheathing RH

S roofs drier than N roofs (solar warming) Diurnal variations/swings (solar gain) Stable periods = snow cover

S drier than N into summer: 10-50% S/30-70% N

Roof Short Name1 FG‐VB‐DV2 FG‐SVR‐DV3 FG‐VB‐nDV4 FG‐SVR‐nDV

NESEA BE18: Unvented Roofs Without Spray Foam66

© buildingscience.com

Fiberglass Roofs: N Sheathing MCs

Roofs 3 & 4 (nDV) peaks over 25-30% MC SVR drier than VB, lower peak

Roofs 1 & 2 (DV) peaks below 20% MC By spring, ~5-10% vs. 20%+ at 3 & 4

Roof Short Name1 FG‐VB‐DV2 FG‐SVR‐DV3 FG‐VB‐nDV4 FG‐SVR‐nDV

NESEA BE18: Unvented Roofs Without Spray Foam67

© buildingscience.com

Fiberglass Roofs: N Sheathing MCs North sheathing MCs High-Mid-Low Gradient of MCs

(highest near ridge, lowest near eaves)

Build roofs with only lower halves?

Diffusion vent localized drying only Mid height graph Roof 2 like 3 & 4

NESEA BE18: Unvented Roofs Without Spray Foam68

© buildingscience.com

South sheathing MCs all drier than corresponding north

Only one sensor over 15% MC

Build only south-facing unvented roofs?

Roof Short Name1 FG‐VB‐DV2 FG‐SVR‐DV3 FG‐VB‐nDV4 FG‐SVR‐nDV

Fiberglass Roofs: S Sheathing MCs

Page 18: Unvented Roofs Without Spray Foam: The Latest Building ......Unvented Roofs Without Spray Foam: The Latest Building America Research Kohta Ueno NESEA BE18: Unvented Roofs Without Spray

3/9/2018

18

NESEA BE18: Unvented Roofs Without Spray Foam69

© buildingscience.com

Year One Results: Fiberglass Inward Drive

NESEA BE18: Unvented Roofs Without Spray Foam70

© buildingscience.com

Fiberglass Roofs: Inward Drive Sensors

South side wafer sensors Tracks to outdoor T-MC spikes Roofs 1 & 3 (VB) stay wetter than 2 & 4 (SVR) Peaks 25-30%, not condensation

Roof Short Name1 FG‐VB‐DV2 FG‐SVR‐DV3 FG‐VB‐nDV4 FG‐SVR‐nDV

NESEA BE18: Unvented Roofs Without Spray Foam71

© buildingscience.com

Fiberglass Roofs: Inward Drive Sensors

South side RH sensors Roofs 1 & 3 (VB) stay wetter than 2 & 4 (SVR) SVRs do what they’re supposed to do Roof Short Name

1 FG‐VB‐DV2 FG‐SVR‐DV3 FG‐VB‐nDV4 FG‐SVR‐nDV NESEA BE18: Unvented Roofs Without Spray Foam

72© buildingscience.com

Fiberglass Roofs: Inward Drive Sensors

South side RH sensors Roofs 1 & 3 (VB) stay wetter than 2 & 4 (SVR) SVRs do what they’re supposed to do Roof Short Name

1 FG‐VB‐DV2 FG‐SVR‐DV3 FG‐VB‐nDV4 FG‐SVR‐nDV

Page 19: Unvented Roofs Without Spray Foam: The Latest Building ......Unvented Roofs Without Spray Foam: The Latest Building America Research Kohta Ueno NESEA BE18: Unvented Roofs Without Spray

3/9/2018

19

NESEA BE18: Unvented Roofs Without Spray Foam73

© buildingscience.com

Fiberglass Roofs: Inward Drive Sensors

North side RH sensors Roofs 1 & 3 (VB) stay wetter than 2 & 4 (SVR) Arguably more time @ 100% RH? Roof Short Name

1 FG‐VB‐DV2 FG‐SVR‐DV3 FG‐VB‐nDV4 FG‐SVR‐nDV NESEA BE18: Unvented Roofs Without Spray Foam

74© buildingscience.com

Year One Results: Fiberglass Mold Index

NESEA BE18: Unvented Roofs Without Spray Foam75

© buildingscience.com

Fiberglass Roofs: Mold Index Calculations Viitanen Mold Index (time, temp., RH, substrate) Consistent with ASHRAE 160 Addendum e (2016) Mold index over 3.0 (visible mold growth 10%)

constitutes failure

NESEA BE18: Unvented Roofs Without Spray Foam76

© buildingscience.com

Fiberglass Roofs: Mold Index-Ridge

Roofs 3 & 4 RH ~100% most of winter Roof 4 RH sensor failed mid March 2017 Artificial decline shown

Roofs 1 & 2 (DV) boring and safeRoof Short Name

1 FG‐VB‐DV2 FG‐SVR‐DV3 FG‐VB‐nDV4 FG‐SVR‐nDV

Page 20: Unvented Roofs Without Spray Foam: The Latest Building ......Unvented Roofs Without Spray Foam: The Latest Building America Research Kohta Ueno NESEA BE18: Unvented Roofs Without Spray

3/9/2018

20

NESEA BE18: Unvented Roofs Without Spray Foam77

© buildingscience.com

Fiberglass Roofs: Mold Index-N Sheathing

All mold indices under 1 Rise occurred spring (temperatures warming) South not plotted (even less activity)

Roof Short Name1 FG‐VB‐DV2 FG‐SVR‐DV3 FG‐VB‐nDV4 FG‐SVR‐nDV NESEA BE18: Unvented Roofs Without Spray Foam

78© buildingscience.com

Fiberglass Roofs: Mold Index-Inward Drive

Roof Short Name1 FG‐VB‐DV2 FG‐SVR‐DV3 FG‐VB‐nDV4 FG‐SVR‐nDV

Roofs 1 & 3 (fixed VB) show rise

Roofs 2 & 4 (SVR) remain near 0

North shows higher peaks than south Stored moisture?

NESEA BE18: Unvented Roofs Without Spray Foam79

© buildingscience.com

Roof Short Name1 FG‐VB‐DV2 FG‐SVR‐DV3 FG‐VB‐nDV4 FG‐SVR‐nDV

Conclusions: Fiberglass All roofs show mold indices under 3.0: would pass

ASHRAE 160… BUT Ridge at Roofs 3 & 4 (no diffusion vent) Wafers indicating condensation Sheathing MCs > 25-30%

Inward drive sensors Roofs 1 & 3 (fixed VB) Extended 100% RH peaks

Roof 2 (smart vapor retarder + diffusion vent) overall safest

Winter 1 of 3 test results

NESEA BE18: Unvented Roofs Without Spray Foam80

© buildingscience.com

Year One Results: Cellulose Roofs

Page 21: Unvented Roofs Without Spray Foam: The Latest Building ......Unvented Roofs Without Spray Foam: The Latest Building America Research Kohta Ueno NESEA BE18: Unvented Roofs Without Spray

3/9/2018

21

NESEA BE18: Unvented Roofs Without Spray Foam81

© buildingscience.com

Cellulose Roofs: Color Codes

VB = fixed perm vapor retarder SVR = variable perm “smart”

vapor retarder nDV/DV = (no) diffusion vent

Roof # Insulation Interior VB Diffusion Vent1 Fiberglass Fixed perm Yes2 Fiberglass Variable perm Yes3 Fiberglass Fixed perm No4 Fiberglass Variable perm No5 Dense pack cellulose Fixed perm No6 Dense pack cellulose Variable perm No7 Dense pack cellulose Variable perm Yes8 ccSPF + cellulose “flash

and blow” §R806.4 Latex paint on GWB No

Roof Short Name

5 Cell‐VB‐nDV6 Cell‐SVR‐nDV7 Cell‐SVR‐DV8 ccSPF‐Cell

NESEA BE18: Unvented Roofs Without Spray Foam82

© buildingscience.com

Cellulose Roofs: Ridge RH

Roofs 5 & 6 (nDV) RHs 95-100% RH thru winter Roof 6 RH sensor failure 4/2017

Roof 7 (DV) RHs seldom over 90% RH Roof 8 (ccSPF + cell) 30-40% RH

Roof Short Name5 Cell‐VB‐nDV6 Cell‐SVR‐nDV7 Cell‐SVR‐DV8 ccSPF‐Cell

NESEA BE18: Unvented Roofs Without Spray Foam83

© buildingscience.com

Cellulose Roofs: Ridge RH

Roofs 5 & 6 (nDV) RHs 95-100% RH thru winter Roof 6 RH sensor failure 4/2017

Roof 7 (DV) RHs seldom over 90% RH Roof 8 (ccSPF + cell) 30-40% RH

Roof Short Name5 Cell‐VB‐nDV6 Cell‐SVR‐nDV7 Cell‐SVR‐DV8 ccSPF‐Cell

NESEA BE18: Unvented Roofs Without Spray Foam84

© buildingscience.com

Cellulose Roofs: Ridge Wafer

Roofs 5 & 6 (nDV) over 60% MC (?!?) Condensation, migration of borates, not real MC

Roof 7 (DV) wafer peak under 15% MC Roof 8 (ccSPF + cell) under 20% MC

Roof Short Name5 Cell‐VB‐nDV6 Cell‐SVR‐nDV7 Cell‐SVR‐DV8 ccSPF‐Cell

Page 22: Unvented Roofs Without Spray Foam: The Latest Building ......Unvented Roofs Without Spray Foam: The Latest Building America Research Kohta Ueno NESEA BE18: Unvented Roofs Without Spray

3/9/2018

22

NESEA BE18: Unvented Roofs Without Spray Foam85

© buildingscience.com

Cellulose Roofs: Sheathing RH North

Roofs 5, 6, 7, mostly same RHs, 90-100% peaks Lower RH peaks than fiberglass roofs Localized drying at DV, not mid-height

Roof 8 low RH, protected by ccSPF

Roof Short Name5 Cell‐VB‐nDV6 Cell‐SVR‐nDV7 Cell‐SVR‐DV8 ccSPF‐Cell

NESEA BE18: Unvented Roofs Without Spray Foam86

© buildingscience.com

Cellulose Roofs: Sheathing RH South

Drier conditions south vs. north Diurnal variations Solar gain, snow cover effects

Roof Short Name5 Cell‐VB‐nDV6 Cell‐SVR‐nDV7 Cell‐SVR‐DV8 ccSPF‐Cell

NESEA BE18: Unvented Roofs Without Spray Foam87

© buildingscience.com

Cellulose Roofs: N Sheathing MCs North sheathing MCs High-Mid-Low Upper: condensation

& borate migration Away from ridge (low,

mid) MCs in safe range (gradient)

Roof 7 (DV) and Roof 8 (ccSPF + cell) consistently dry

NESEA BE18: Unvented Roofs Without Spray Foam88

© buildingscience.com

Cellulose Roofs: S Sheathing MCs South sheathing

MCs South consistently

drier than north Upper MCs distorted

by borate migration

Page 23: Unvented Roofs Without Spray Foam: The Latest Building ......Unvented Roofs Without Spray Foam: The Latest Building America Research Kohta Ueno NESEA BE18: Unvented Roofs Without Spray

3/9/2018

23

NESEA BE18: Unvented Roofs Without Spray Foam89

© buildingscience.com

Year One Results: Cellulose Inward Drive

NESEA BE18: Unvented Roofs Without Spray Foam90

© buildingscience.com

Cellulose Roofs: Inward Drives

Inward drive wafer, south All well below 15% MC (safe)

Roof Short Name5 Cell‐VB‐nDV6 Cell‐SVR‐nDV7 Cell‐SVR‐DV8 ccSPF‐Cell

NESEA BE18: Unvented Roofs Without Spray Foam91

© buildingscience.com

Cellulose Roofs: Inward Drives

Inward drive RH, south Peaks barely over 80% RH

Roof Short Name5 Cell‐VB‐nDV6 Cell‐SVR‐nDV7 Cell‐SVR‐DV8 ccSPF‐Cell

NESEA BE18: Unvented Roofs Without Spray Foam92

© buildingscience.com

Cellulose Roofs: Inward Drives

Inward drive RH, north Peaks mostly under 90% RH Higher than south-stored moisture?

Roof Short Name5 Cell‐VB‐nDV6 Cell‐SVR‐nDV7 Cell‐SVR‐DV8 ccSPF‐Cell

Page 24: Unvented Roofs Without Spray Foam: The Latest Building ......Unvented Roofs Without Spray Foam: The Latest Building America Research Kohta Ueno NESEA BE18: Unvented Roofs Without Spray

3/9/2018

24

NESEA BE18: Unvented Roofs Without Spray Foam93

© buildingscience.com

Cellulose vs. Fiberglass Moisture Storage

ASHRAE Fundamentals data (Kumaran, Burch) Moisture buffering/storage ability of cellulose Raw data, shown by weight (not volume)

NESEA BE18: Unvented Roofs Without Spray Foam94

© buildingscience.com

Cellulose vs. Fiberglass Moisture Storage

ASHRAE Fundamentals data (Kumaran, Burch) Moisture buffering/storage ability of cellulose Raw data, shown by weight (not volume)

NESEA BE18: Unvented Roofs Without Spray Foam95

© buildingscience.com

Year One Results: Cellulose Mold Index

NESEA BE18: Unvented Roofs Without Spray Foam96

© buildingscience.com

Cellulose Roofs: Mold Index Ridge

Roofs 5 & 6 (nDV) RH 90-100% most of winter Roofs 6 RH sensor failed mid April 2017 Artificial decline shown

Roof Short Name5 Cell‐VB‐nDV6 Cell‐SVR‐nDV7 Cell‐SVR‐DV8 ccSPF‐Cell

Page 25: Unvented Roofs Without Spray Foam: The Latest Building ......Unvented Roofs Without Spray Foam: The Latest Building America Research Kohta Ueno NESEA BE18: Unvented Roofs Without Spray

3/9/2018

25

NESEA BE18: Unvented Roofs Without Spray Foam97

© buildingscience.com

Cellulose Roofs: Mold Index North Sheath.

RH peaks 90-100% much of winter Mold indices all low South even drier-lower risk

Roof Short Name5 Cell‐VB‐nDV6 Cell‐SVR‐nDV7 Cell‐SVR‐DV8 ccSPF‐Cell

NESEA BE18: Unvented Roofs Without Spray Foam98

© buildingscience.com

Cellulose Roofs: Mold Index Inward Drive

RH south side inward drive Not misplotted-max mold index 0.004

Roof Short Name5 Cell‐VB‐nDV6 Cell‐SVR‐nDV7 Cell‐SVR‐DV8 ccSPF‐Cell

NESEA BE18: Unvented Roofs Without Spray Foam99

© buildingscience.com

Conclusions: Cellulose All roofs show mold indices under 3.0: would pass

ASHRAE 160… BUT Ridge at Roofs 5 & 6 (no diffusion vent) Wafers indicating condensation Sheathing MCs high (uncertainty-borate migration)

Inward drive sensors non-issue in cellulose roofs Roof 7 (smart vapor retarder + diffusion vent)

overall safest Roof 8 (ccSPF + cell) boring and safe (did not

bother calculating Mold Index)

Roof Short Name5 Cell‐VB‐nDV6 Cell‐SVR‐nDV7 Cell‐SVR‐DV8 ccSPF‐Cell

NESEA BE18: Unvented Roofs Without Spray Foam100

© buildingscience.com

Year Two: Humidification and New Assemblies

Page 26: Unvented Roofs Without Spray Foam: The Latest Building ......Unvented Roofs Without Spray Foam: The Latest Building America Research Kohta Ueno NESEA BE18: Unvented Roofs Without Spray

3/9/2018

26

NESEA BE18: Unvented Roofs Without Spray Foam101

© buildingscience.com

New Assemblies-Replace Poor Performers

Roof Insulation Interior VB Diffusion Vent Short Name

1 Fiberglass Fixed perm (OC 1 perm) 6”/±300 perm (Yes) FG-VB-DV

2 Fiberglass Variable perm (MemBrain) 6”/±300 perm (Yes) FG-SVR-DV

3 Fiberglass Variable perm (MemBrain) Fixed perm (OC 1 perm)

2”/±25 perm No

FG-SVR-tDV FG-VB-nDV

4 Fiberglass Variable perm (MemBrain) 2”/±300 perm No FG-SVR-sDV FG-SVR-nDV

5 Dense pack cellulose Variable perm

(DuPont Variable) Fixed perm (OC 1 perm)

2”/±25 perm No

Cell-SVR-tDV Cell-VB-nDV

6 Dense pack cellulose Variable perm (DuPont Variable) 2”/±300 perm No Cell-SVR-sDV

Cell-SVR-nDV

7 Dense pack cellulose Variable perm (DuPont Variable) 6”/300 perm (Yes) Cell-SVR-DV

8 ccSPF + cellulose “flash and blow” None No ccSPF-Cell

tDV = “tight” diffusion vent (25 perms vs. 300+ perms)sDV = “small” diffusion vent (2” wide vs. 6” wide)

NESEA BE18: Unvented Roofs Without Spray Foam102

© buildingscience.com

Summertime Inward Drive

NESEA BE18: Unvented Roofs Without Spray Foam103

© buildingscience.com

Summertime Inward Drive

Inward vapor drive does matter—we were just measuring in the wrong location!

NESEA BE18: Unvented Roofs Without Spray Foam104

© buildingscience.com

Retrofit Work, Fiberglass Settling

Page 27: Unvented Roofs Without Spray Foam: The Latest Building ......Unvented Roofs Without Spray Foam: The Latest Building America Research Kohta Ueno NESEA BE18: Unvented Roofs Without Spray

3/9/2018

27

NESEA BE18: Unvented Roofs Without Spray Foam105

© buildingscience.com

Retrofit Work, Cellulose Settling

NESEA BE18: Unvented Roofs Without Spray Foam106

© buildingscience.com

Retrofit Work, Cellulose Settling

Settling along entire roof length only occurred on north side

NESEA BE18: Unvented Roofs Without Spray Foam107

© buildingscience.com

Retrofit Work, Moisture Evidence

NESEA BE18: Unvented Roofs Without Spray Foam108

© buildingscience.com

Adding Humidification (50% RH) Insulated heated “bucket” Heater & fan operate on call for humidification “Bucket” refilled by reservoir/float switch

Page 28: Unvented Roofs Without Spray Foam: The Latest Building ......Unvented Roofs Without Spray Foam: The Latest Building America Research Kohta Ueno NESEA BE18: Unvented Roofs Without Spray

3/9/2018

28

NESEA BE18: Unvented Roofs Without Spray Foam109

© buildingscience.com

Adding Humidification (50% RH)

NESEA BE18: Unvented Roofs Without Spray Foam110

© buildingscience.com

Year Two Results: Fiberglass Roofs

NESEA BE18: Unvented Roofs Without Spray Foam111

© buildingscience.com

Fiberglass Ridge RH (Full 2 Years)

Roof # Short Name1 FG‐VB‐DV2 FG‐SVR‐DV3 FG‐VB‐tDV4 FG‐SVR‐sDV

NESEA BE18: Unvented Roofs Without Spray Foam112

© buildingscience.com

Fiberglass Ridge RH (Year Two)

Roof # Short Name1 FG‐VB‐DV2 FG‐SVR‐DV3 FG‐VB‐tDV4 FG‐SVR‐sDV

Full-size diffusion ports start to dry late winter “Tight” diffusion vent stays wet “Small” diffusion vent in-between

Page 29: Unvented Roofs Without Spray Foam: The Latest Building ......Unvented Roofs Without Spray Foam: The Latest Building America Research Kohta Ueno NESEA BE18: Unvented Roofs Without Spray

3/9/2018

29

NESEA BE18: Unvented Roofs Without Spray Foam113

© buildingscience.com

Fiberglass Ridge Wafer

Roof # Short Name1 FG‐VB‐DV2 FG‐SVR‐DV3 FG‐VB‐tDV4 FG‐SVR‐sDV

“Small” diffusion vent drier than last winter (nDV) Full-size diffusion ports wetter than

Winter 1 (50% RH) “Tight” diffusion vent high MCs

NESEA BE18: Unvented Roofs Without Spray Foam114

© buildingscience.com

Fiberglass Ridge Wafer

Roof # Short Name1 FG‐VB‐DV2 FG‐SVR‐DV3 FG‐VB‐tDV4 FG‐SVR‐sDV

“Small” diffusion vent drier than last winter (nDV) Full-size diffusion ports wetter than

Winter 1 (50% RH) “Tight” diffusion vent high MCs

NESEA BE18: Unvented Roofs Without Spray Foam115

© buildingscience.com

Fiberglass Roof Sheathing North, Mid Ht.

Mid-height MC, facing north All roofs much wetter than Winter 1 (50% RH) “Tight” diffusion vent worst performer

NESEA BE18: Unvented Roofs Without Spray Foam116

© buildingscience.com

Year Two Results: Cellulose & Hybrid Roofs

Page 30: Unvented Roofs Without Spray Foam: The Latest Building ......Unvented Roofs Without Spray Foam: The Latest Building America Research Kohta Ueno NESEA BE18: Unvented Roofs Without Spray

3/9/2018

30

NESEA BE18: Unvented Roofs Without Spray Foam117

© buildingscience.com

Borate contamination of wood MCs? Hybrid ccSPF-cellulose roof > 40% MC Interior moisture through ccSPF layer? But roof sheathing only 10% MC-safe

Cellulose Ridge Wafer

Roof # Short Name5 Cell‐SVR‐tDV6 Cell‐SVR‐sDV7 Cell‐SVR‐DV8 ccSPF‐Cell

NESEA BE18: Unvented Roofs Without Spray Foam118

© buildingscience.com

Hybrid Roof Interface: RH

Effect of 50% interior RH No visible issues from interior (cellulose storage)

NESEA BE18: Unvented Roofs Without Spray Foam119

© buildingscience.com

Hybrid Roof Interface: Winter 1 DP

Interface T (greens) & interior DP (grey) DP is typically below interface temperature in

Winter 1

NESEA BE18: Unvented Roofs Without Spray Foam120

© buildingscience.com

Hybrid Roof Interface: Winter 2 DP

Interface T (greens) & interior DP (grey) DP is often greater than interface temperature in

Winter 2

Page 31: Unvented Roofs Without Spray Foam: The Latest Building ......Unvented Roofs Without Spray Foam: The Latest Building America Research Kohta Ueno NESEA BE18: Unvented Roofs Without Spray

3/9/2018

31

NESEA BE18: Unvented Roofs Without Spray Foam121

© buildingscience.com

Year Two Conclusions and Recommendations

NESEA BE18: Unvented Roofs Without Spray Foam122

© buildingscience.com

Conclusions & Further Work Roofs with diffusion vent & variable-perm vapor

consistently safest, BUT Interior at 50% RH creates much more

challenging conditions: many at risk of failure “Tight” diffusion vent (25 perms vs. 500 perms)

did not work acceptably “Small” diffusion vent: better than nothing, but

larger allows more drying 50% RH pushes limits of “flash and blow” ratios—

safe storage saves cellulose roof

NESEA BE18: Unvented Roofs Without Spray Foam123

© buildingscience.com

Conclusions & Further Work Year 2 of 3-year project Planned interior conditions: Winter 1: “Normal” interior conditions Winter 2: Elevated RH (50% constant) Winter 3: Air leakage into rafter bays

Possibly change experimental program based on Year 2 results

NESEA BE18: Unvented Roofs Without Spray Foam124

© buildingscience.com

Recommendations Code-compliant (IRC §R806.5) still safest

(spray foam or exterior rigid insulation) Mineral fiber exterior rigid insulation is an option Corson/EcoCor/PH roof assembly

Page 32: Unvented Roofs Without Spray Foam: The Latest Building ......Unvented Roofs Without Spray Foam: The Latest Building America Research Kohta Ueno NESEA BE18: Unvented Roofs Without Spray

3/9/2018

32

NESEA BE18: Unvented Roofs Without Spray Foam125

© buildingscience.com

Recommendations Code-compliant (IRC §R806.5) still safest

(spray foam or exterior rigid insulation) Mineral fiber exterior rigid insulation is an option Corson/EcoCor/PH roof assembly

NESEA BE18: Unvented Roofs Without Spray Foam126

© buildingscience.com

Recommendations Fibrous-only insulation (no exterior insulation)

roof assemblies are “off-label” (against code) Diffusion vent + variable-perm vapor retarder safest “Least bad” if choosing this option

Test airtightness of interior membrane Workmanship sensitive: project type? (e.g., public bid)

Control interior RH—for life of building 20-30% RH maximum in worst of winter?

Complete cavity fills safer Cellulose moisture storage capacity Retrofit/remediation applications?

NESEA BE18: Unvented Roofs Without Spray Foam127

© buildingscience.com

Recommendations Possible application to

retrofitting “short slope” of kneewall attic geometry

Eliminates “chute,” possible to retrofit longer runs

Higher R-value in limited cavity Not proven by this research,

but this is “lower half of roof” geometry (low risk portion)

Rafter bay has “full-size diffusion vent” to vented attic above

NESEA BE18: Unvented Roofs Without Spray Foam128

© buildingscience.com

Questions?Kohta Uenokohta [at] buildingscience [dot] com