upatstvo termostat
TRANSCRIPT
-
7/29/2019 upatstvo termostat
1/2
RTC80.7XX(09 Weel Pro rammin thermostatExplanation of symbols
Mountin lnstructions
. lnstall the thermostat in electrical connection box with screws- i*,*FrL-
i Event indicatori Set value/time displayDav number, Plus/ririnus key, Uenu key
Cloclr-controlled ;programme mode 'manual modeActual temperatureKev lockHe-ating onOn/off switchTemperature sensorClock key
Dimension
OOoOOlnstall the housing cover and lock the external frame
llounting steps:
OOoOOOO
IIIIIiII
IIIt_=i
i
80.71 3
80.7 1 6
80.723
SENSOR
t*lSENSO
'7 6,5,4'i 3l2l1i
VYAAtjnj A, ..,L1 N1 NL3A AC230V
VYAAR tnnl Ir16A AC23OV
iI
iI
I
I
litio(r)5'>ooT'
H- ,\,L11;6'6'olJ
,\, tvNLAC230V
ttHousing cover
HVAC CONTROLS PRODUCTS 2410 E 80 1.0
-
7/29/2019 upatstvo termostat
2/2
RTC80.7XX(09) Weely Programming thermostat Mounting lnstructions
Technical data:VoltagePower consumptronSetting rangeLimitation rangeSwitch i ng d iffe rentialAmbient temperatureProtective housingHousing materialFloor sensor
: AC230V(AC 11 0V I AC24V available):2W:5t -goe:4'C -99C (factory setting: 28e-32C): t0.5K: -5*50C: lP20: anti-flammable PC: rubber-thermoplastic NTC sensor,cable length is 3m
RTC80.7XX Weely Programm i n g thermostatWeekly circulation, it is possible to set 6 periods called eventseach day with different temperatures, aiso you can select "manualmode' or "comfort mode" according to your individual requirements.The thermostat is recommended for the control of electric heatingdevices or on/off valve actuator used in water-based heating systems.Selection Table'
Daily use of the thermostat1) menu 'offi"Press the "ffi" key to select manual mode or clock-controlledprogramme mode, use the "A'or nV" key to enter into comfortmode in clock-controlled programme mode2) plus ua,' & minus "v"Press the "A" or "V" key to increase or decrease your set value3) clock "O"Press the "O" key to set the time and daypress the "O" key till the day start blinking, use the "A" or "v'l keyto set the day, press the "O" key to confirm the setting and thehours start blinking, use the "A" or "V" key to set the hours, pressthe''A" or'V" to confirm the setting and the minutes start blinking,use the "A" or "Y" key to set the minutes, press the "O" key toaccept the settings4 ) on/off 'O"Press the '(D' key to switch on or switch off the thermostat
the setted temperature and the time will be displayed on left sideof screen alternately, and the room temperature can be directlyread out on right side of screen.Programming: 6-event time and temperaturePress the "ffin key for 5 seconds to begin programming
Key Event Symbol Time AV Tem peratu reAV
m0
ooa(,l
1 + 06, 00 ao=(not@=L=3o
20"c a(D.tto(oo33oo,o3Eo0)co
2 O. 08: 00 15C3 & 11: 30 15e4 s 122 30 15C5 O. 17, 00 22.C6 ( 22t 00 15CIq)
o,I1 + 08' 00 22'C2 ( 23,. 00 15C
lba'1) the pre-programmed setpoint (15C) for event 3 & 4 is fhe same as event 2,ple.ase reset it according to you individuat requirement2) symbol 'off" will be displayed if the setpoint reachs the minimum set valueand the thermostaf is sryifched off in this eventAdvanced settings (qualified person preferred)Press the " ffi' key simultaneously switching on the thermostat toenter into the advanced setting mode(when the device is switched off)
Sensor failure:Please select the right sensor mode when operation, it will display the"Err" symbol on screen for sensor failure, thermostat must be checkedtill the fault is eliminated
Function:'g' manual modeThe scheduled event program is overridden, set the temperatureaccording to your individual requirements an d the thermostat willoperate at this temperature permanently"(Qtt clock-controlled programme modeThe day has been split into 6 events, the thermostat will operateautomatically according to the programmed temperature and time"U &"O" comfort modeThe temperature can be temporarily changed for a single event, thecomfort mode temperature is reset at the next event, and the ther-mostat will return to the scheduled event programffi wake-up, event 1ffi Leave (am), event 2reil Return (am), event 3
Leave (pm), event 4ffi Return (pl), event Offi Sleep, event 6ffi Heating onffi "Key-lock" function is activatedffi Set sensor mode: built-in/floor/both sensorsffi Set vacation operating modeffi setting Max and Min ailowed temperature!p[ Early-start adaptive functionffi Sensor calibration to ensure accurate temperature measurementffi Display with back light, stay on for 20 secondsffi LCD display for better read outffi display actual room temperature when switch-off"Key-lock" functionPress both the "A" and "v" keys for 5 secs to engageldisengage the"key-lock" function ( 'f|''symbol appear means "key-lock'function isactivated; disappear means "key-lock" function is deactivated)
ApplicatlonFor control of electric actuator or electrothermal actuatorFor control of heatinq cable or other heating equipments
Key Symbol Setting A OrV
mto0
1 ADJ Tem peratu re cal ibratior Adjust measured tem peratu re2 SEN Sensor mode
lN : built-in sensorOUT : floor sensorALL : both sensor(floor sensor is the limit sensor)3 HI Max. Temperature Max. Limitation temperaturesetpoint (99C )4 LO Min. Temperature Min. Limitation temperaturesetpoint (4C )5 ADA Adaptive function ON : preheating 30minutes earlyOFF: cancel adaptive function6 PRG Set vacation mode 512 day mode611 day mode7 day mode
2z1z0t
7 FAC Reset tofactory settingsProgramming parameters willbe reset to factory settingswhen symbol rr- - -'' appears
HVAC CONTROLS PRODUCTS 2010E80 1.0