va 14 21 00 electric traction elevators · be actively pursuing certified elevator mechanic status....

50
08/01/16 14 21 00-1 SECTION 14 21 00 ELECTRIC TRACTION ELEVATORS SPEC WRITER NOTE: Delete between //__// and paragraph content not applicable to project and write "not used" after title. PART 1 GENERAL 1.1 DESCRIPTION A. This section specifies the engineering, furnishing and installation of complete and ready for operation electric traction elevator systems described herein and as indicated on the Contract drawings. B. Items listed in the singular apply to each and every elevator in this specification except where noted. SPEC WRITER NOTE: Edit or delete Subparagraphs C, D and E to suit the project. Add elevator schedules as needed. C. Passenger Elevator P__ shall be // overhead // basement traction, microprocessor control system, power operated single-speed center opening car and hoistway doors with Class “A” load rated. D. Service/Passenger Elevator S__ shall be // overhead // basement traction, microprocessor control system, power operated two-speed side opening car and hoistway doors with Class “C3” load rated. E. Freight Elevator F__ shall be // overhead // basement traction, microprocessor control system, power operated vertical by-parting hoistway doors and car gate with Class “C1” load rated. ELEVATOR SCHEDULE Elevator Number Overall Platform Size Clear Inside Platform Rated Load – kg (lb) Contract Speed - m/s (fpm) Total Travel – m (ft) Floors Served Number of Openings Entrance Type & Size

Upload: vuminh

Post on 11-Apr-2018

232 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: VA 14 21 00 Electric Traction Elevators · be actively pursuing Certified Elevator Mechanic status. ... Hoisting Machine Motor, ... VA 14 21 00 Electric Traction Elevators

08/01/16

14 21 00-1

SECTION 14 21 00 ELECTRIC TRACTION ELEVATORS

SPEC WRITER NOTE: Delete between //__// and paragraph content not applicable to project and write "not used" after title.

PART 1 GENERAL

1.1 DESCRIPTION

A. This section specifies the engineering, furnishing and installation of

complete and ready for operation electric traction elevator systems

described herein and as indicated on the Contract drawings.

B. Items listed in the singular apply to each and every elevator in this

specification except where noted.

SPEC WRITER NOTE: Edit or delete Subparagraphs C, D and E to suit the project. Add elevator schedules as needed.

C. Passenger Elevator P__ shall be // overhead // basement traction,

microprocessor control system, power operated single-speed center

opening car and hoistway doors with Class “A” load rated.

D. Service/Passenger Elevator S__ shall be // overhead // basement

traction, microprocessor control system, power operated two-speed side

opening car and hoistway doors with Class “C3” load rated.

E. Freight Elevator F__ shall be // overhead // basement traction,

microprocessor control system, power operated vertical by-parting

hoistway doors and car gate with Class “C1” load rated.

ELEVATOR SCHEDULE

Elevator Number

Overall Platform Size

Clear Inside Platform

Rated Load – kg (lb)

Contract Speed - m/s (fpm)

Total Travel – m (ft)

Floors Served

Number of Openings

Entrance Type & Size

Page 2: VA 14 21 00 Electric Traction Elevators · be actively pursuing Certified Elevator Mechanic status. ... Hoisting Machine Motor, ... VA 14 21 00 Electric Traction Elevators

08/01/16

14 21 00-2

ELEVATOR SCHEDULE

Typing of Roping

1.2 RELATED WORK

A. Section 01 33 23 SPECIFICATIONS AND DRAWINGS FOR CONSTRUCTION (FAR

52.236-21) and, SPECIAL NOTES (VAAR 852.236-91), in GENERAL CONDITIONS.

B. Section 07 84 00, FIRESTOPPING: Sealing around penetrations to maintain

the integrity of fire-rated construction.

C. SECTION 09 06 00, SCHEDULE FOR FINISHES: As a master format for

construction projects, to identify interior and exterior material

finishes for type, texture, patterns, color and placement.

D. Section 13 05 41, SEISMIC RESTRAINT REQUIREMENTS FOR NON-STRUCTURAL

COMPONENTS: Requirements for seismic restraint of non-structural

components.

E. Section 26 05 11, REQUIREMENTS FOR ELECTRICAL INSTALLATIONS: General

electrical requirements that are common to more than one section.

F. Section 26 05 19, LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES

(600 VOLTS AND BELOW): Low Voltage power and lighting wiring.

G. Section 26 05 26, GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS:

Requirements for personnel safety and to provide a low impedance path

for possible ground fault currents.

H. Section 26 05 33, RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS: Conduits

for cables and wiring.

I. Section 26 05 73, OVERCURRENT PROTECTIVE DEVICE COORDINATION STUDY:

Requirements for installing the over-current protective devices to

ensure proper equipment and personnel protection.

J. Section 26 22 00, LOW-VOLTAGE TRANSFORMERS: Low voltage transformers.

K. Section 26 24 16, PANELBOARDS: Low voltage panelboards.

L. Section 26 43 13, TRANSIENT-VOLTAGE SURGE SUPPRESSION: Surge

suppressors installed in panelboards.

M. Section 26 51 00, INTERIOR LIGHTING: Fixture and ballast type for

interior lighting.

1.3 QUALIFICATIONS

A. Approval by the Contracting Officer is required for products and

services of proposed manufacturers, suppliers and installers and shall

be contingent upon submission of certificates by the Contractor stating

the following:

Page 3: VA 14 21 00 Electric Traction Elevators · be actively pursuing Certified Elevator Mechanic status. ... Hoisting Machine Motor, ... VA 14 21 00 Electric Traction Elevators

08/01/16

14 21 00-3

1. Elevator contractor is currently and regularly engaged in the

installation of elevator equipment as one of his principal products.

2. Elevator contractor shall have three years of successful experience,

trained supervisory personnel, and facilities to install elevator

equipment specified herein.

3. Elevator Mechanic (Installer) shall have passed a Mechanic

Examination approved by the U.S. Department of Labor and have

technical qualifications of at least five years of experience in the

elevator industry or 10,000 hours of field experience working in the

elevator industry with technical update training. Apprentices shall

be actively pursuing Certified Elevator Mechanic status.

Certification shall be submitted for all workers employed in this

capacity.

B. Approval of Elevator Contractor’s equipment will be contingent upon

their identifying an elevator maintenance service provider that shall

render services within // one hour // two hours // four hours // of

receipt of notification, together with certification that the quantity

and quality of replacement parts stock is sufficient to warranty

continued operation of the elevator installation.

C. Approval will not be given to elevator contractors and manufacturers

who have established on prior projects, either government, municipal,

or commercial, a record for unsatisfactory elevator installations, have

failed to complete awarded contracts within the contract period, and do

not have the requisite record of satisfactorily performing elevator

installations of similar type and magnitude.

D. Equipment within a group of electric traction elevators shall be the

product of the same manufacturer.

E. The Contractor shall provide and install safety devices that have been

subjected to tests witnessed and certified by an independent

professional testing laboratory that is not a subsidiary of the firm

that manufactures supplies or installs the equipment.

F. Welding at the project site shall be made by welders and welding

operators who have previously qualified by test as prescribed in

American Welding Society Publications AWS Dl.1 to perform the type of

work required. Certificates shall be submitted for all workers

employed in this capacity. A welding or hot work permit is required for

each day and shall be obtained from the VAMC safety department. Request

permit one day in advance.

Page 4: VA 14 21 00 Electric Traction Elevators · be actively pursuing Certified Elevator Mechanic status. ... Hoisting Machine Motor, ... VA 14 21 00 Electric Traction Elevators

08/01/16

14 21 00-4

G. Electrical work shall be performed by a Licensed Master Electrician and

Licensed Journeymen Electricians as requirements by NEC. Certificates

shall be submitted for all workers employed in this capacity.

1.4 APPLICABLE PUBLICATIONS

A. The publications listed below form a part of this specification.

Elevator installation shall meet the requirements of the latest

editions published and adopted by the United States Department of

Veterans Affairs on the date contract is signed.

B. Federal Specifications (Fed. Spec.):

J-C-30B.................Cable and Wire, Electrical (Power, Fixed

Installation)

J-C-580.................Cord, Flexible, and Wire, Fixture

W-S-610.................Splice Connectors

W-C-596F................Connector, Plug, Electrical; Connector,

Receptacle, Electrical

W-F-406E................Fittings for Cable, Power, Electrical and

Conduit, Metal, Flexible

HH-I-558C...............Insulation, Blankets, Thermal (Mineral Fiber,

Industrial Type)

W-F-408E................Fittings for Conduit, Metal, Rigid (Thick-Wall

and Thin- wall Type)

RR-W-410................Wire Rope and Strand

TT-E-489J...............Enamel, Alkyd, Gloss, Low VOC Content

QQ-S-766................Steel, Stainless and Heat Resisting, Alloys,

Plate, Sheet and Strip

C. International Building Code (IBC)

D. American Society of Mechanical Engineers (ASME):

A17.1 - Safety Code for Elevators and Escalators

A17.2 - Inspectors Manual for Electric Elevators and Escalators

E. National Fire Protection Association:

NFPA 13.................Standard for the Installation of Sprinkler

Systems

NFPA 70.................National Electrical Code (NEC)

NFPA 72.................National Fire Alarm and Signaling Code

NFPA 101................Life Safety Code

NFPA 252................Fire Test of Door Assemblies

F. American Society for Testing and Materials (ASTM):

Page 5: VA 14 21 00 Electric Traction Elevators · be actively pursuing Certified Elevator Mechanic status. ... Hoisting Machine Motor, ... VA 14 21 00 Electric Traction Elevators

08/01/16

14 21 00-5

A1008/A1008M-09.........Steel, Sheet, Cold Rolled, Carbon, Structural,

High-Strength Low-Alloy and High Strength Low-

Alloy with Improved Farability

E1042-02................Acoustically Absorptive Materials Applied by

Trowel or Spray

G. Manufacturer's Standardization Society of the Valve and Fittings

Industry (MSS):

SP-58...................Pipe Hangers and Supports

H. Society of Automotive Engineers, Inc. (SAE):

J517-91.................Hydraulic Hose, Standard

I. Gauges:

Sheet and Plate: U.S. Standard (USS)

Wire: American Wire Gauge (AWG)

J. American Welding Society (AWS):

D1.1....................Structured Welding Code Steel

K. National Electrical Manufacturers Association (NEMA):

LD-3....................High-Pressure Decorative Laminates

L. Underwriter's Laboratories (UL):

486A....................Safety Wire Connectors for Copper Conductors

797.....................Safety Electrical Metallic Tubing

M. Institute of Electrical and Electronic Engineers (IEEE)

N. Regulatory Standards:

VA Barrier Free Design Handbook H-18-13

VA Seismic Design Manual H-18-8

1.5 SUBMITTALS

A. Submit in accordance with Specification Section 01 33 23, SHOP

DRAWINGS, PRODUCT DATA, and SAMPLES.

B. Before execution of work, furnish information to evidence full

compliance with contract requirements for proposed items. Such

information shall include, as required: Manufacturer's Name, Trade

Names, Model or Catalog Number, Nameplate Data (size, capacity, and

rating) and corresponding specification reference (Federal or project

specification number and paragraph). All submitted drawings and related

elevator material shall be forwarded to the Contracting Officer.

C. Shop Drawings:

1. Complete scaled and dimensioned layout in plan and section view

showing the arrangement of equipment and all details of each and

every elevator unit specified including:

Page 6: VA 14 21 00 Electric Traction Elevators · be actively pursuing Certified Elevator Mechanic status. ... Hoisting Machine Motor, ... VA 14 21 00 Electric Traction Elevators

08/01/16

14 21 00-6

a. Hoisting machines, controllers, power conversion devices,

governors, and all other components located in machine room.

b. Car, counterweight, sheaves, supporting beams, guide rails,

brackets, buffers, and size of car platform, car frame members,

and other components located in hoistway.

c. Rail bracket spacing and maximum vertical forces on guide rails

in accordance with H 18-8 for Seismic Risk Zone 2 or greater.

d. Reaction at points of support and buffer impact loads.

e. Weight of principal parts.

f. Top and bottom clearances and over travel of car and

counterweight.

g. Location of main line switch/shunt trip circuit breaker,

switchboard panel, light switch, and feeder extension points in

the machine room.

2. Drawings of hoistway entrances and doors showing details of

construction and method of fastening to the structural members of

the building.

a. If drywall construction is used to enclose hoistway, submit

details of interface fastenings between entrance frames and

drywall.

b. Sill details including sill support.

D. Samples:

1. One each of stainless steel, 75 mm x 125 mm (3 in. x 5 in.).

2. One each of baked enamel, 75 mm x 125 mm (3 in. x 5 in.).

3. One each of color floor covering.

4. One each of protection pads, 75 mm x 125 mm (3 in. x 5 in.) if used.

5. One each car and hoistway Braille plate sample.

6. One each car and hall button sample.

7. One each car and hall lantern/position indicator sample.

8. One each wall and ceiling material finish sample.

9. One each car lighting sample.

E. Name of manufacturer, type or style designation, and applicable data of

the following equipment shall be shown on the elevator layouts:

1. Hoisting Machine.

2. Hoisting Machine Motor, HP and RPM ratings, Voltage, Starting and

Full Load Ampere, and Number of Phases.

3. Controller.

4. Starters and Overload Current Protection Devices.

Page 7: VA 14 21 00 Electric Traction Elevators · be actively pursuing Certified Elevator Mechanic status. ... Hoisting Machine Motor, ... VA 14 21 00 Electric Traction Elevators

08/01/16

14 21 00-7

5. Car Safety Device; Type “B” safeties and Governor.

6. Electric Door Operator; HP, RPM, Voltage, and Ampere rating of

motor.

7. Hoistway Door Interlocks.

8. Car and Counterweight Buffers; maximum and minimum rated loads,

maximum rated striking speed and stroke.

9. Cab Ventilation Unit; HP rating and CFM rating.

10. Hoist and Compensation Ropes; breaking strength, allowable working

load, and actual working load.

F. Complete construction drawings of elevator car enclosure showing

dimensioned details, fastenings to platform, car lighting, ventilation,

ceiling framing, top exits, and location of car equipment.

G. Complete dimensioned detail of vibration isolating foundations for

traction hoisting machines.

H. Dimensioned drawings showing details of:

1. All signal and operating fixtures.

2. Car and counterweight roller guides.

3. Hoistway door tracks, hangers, and sills.

4. Door operator, infrared curtain units.

I. Cut sheets and drawings showing details of controllers and supervisory

panels.

J. Furnish certificates as required under: Paragraph "QUALIFICATIONS".

1.6 WIRING DIAGRAMS

A. Provide three complete sets of paper and one electronic set field

wiring and straight line wiring diagrams showing all electrical

circuits in the hoistway, machine room and fixtures. Install one set

coated with an approved plastic sealer and mounted in the elevator

machine room as directed by the Resident Engineer.

B. In the event field modifications are necessary during installation,

diagrams shall be revised to include all corrections made prior to and

during the final inspection. Corrected diagrams shall be delivered to

the Resident Engineer within thirty (30) days of final acceptance.

C. Provide the following information relating to the specific type of

microprocessor controls installed:

1. Owner's information manual, containing job specific data on major

components, maintenance, and adjustment.

2. System logic description.

Page 8: VA 14 21 00 Electric Traction Elevators · be actively pursuing Certified Elevator Mechanic status. ... Hoisting Machine Motor, ... VA 14 21 00 Electric Traction Elevators

08/01/16

14 21 00-8

3. Complete wiring diagrams needed for field troubleshooting,

adjustment, repair and replacement of components. Diagrams shall be

base diagrams, containing all changes and additions made to the

equipment during the design and construction period.

4. Changes made during the warranty period shall be noted on the

drawings in adequate time to have the finalized drawings reproduced

for mounting in the machine room no later than six months prior to

the expiration of the warranty period.

1.7 ADDITIONAL EQUIPMENT

A. Additional equipment required to operate the specified equipment

manufactured and supplied for this installation shall be furnished and

installed by the contractor. The cost of the equipment shall be

included in the base bid.

B. Equipment not required by specification, which would improve the

operation, may be installed in conjunction with the specified equipment

by the contractor at his option at no additional cost to the

Government, provided prior approval is obtained from the Contracting

Officer’s Representative (COR).

1.8 TOOL CABINET

A. Provide a metal parts/tool cabinet, having two shelves and hinged

doors. Cabinet size shall be 1220 mm (48 in.) high, 762 mm (30 in.)

wide, and 457 mm (18 in.) deep.

1.9 PERFORMANCE STANDARDS

A. The elevators shall be capable of meeting the highest standards of the

industry and specifically the following:

1. Contract speed is high speed in either direction of travel with

rated capacity load in the elevator. Speed variation under all load

conditions, regardless of direction of travel, shall not vary more

than three (3) percent.

2. The controlled rate of change of acceleration and retardation of the

car shall not exceed 0.1G per ft/s/s and the maximum acceleration

and retardation shall not exceed 0.2G per ft/s/s.

3. Starting, stopping, and leveling shall be smooth and comfortable

without appreciable steps of acceleration and deceleration.

B. Passenger/ Service door operator shall open the car door and hoistway

door at 2.5-feet per second and close at 1-foot per second. Freight

door operators shall open and close at 1-foot per second.

Page 9: VA 14 21 00 Electric Traction Elevators · be actively pursuing Certified Elevator Mechanic status. ... Hoisting Machine Motor, ... VA 14 21 00 Electric Traction Elevators

08/01/16

14 21 00-9

C. Floor level stopping accuracy shall be within 3 mm (.125 in.) above or

below the floor, regardless of load condition.

D. Noise and Vibration Isolation: All elevator equipment including their

supports and fastenings to the building, shall be mechanically and

electrically isolated from the building structure to minimize

objectionable noise and vibration transmission to car, building

structure, or adjacent occupied areas of building.

E. Sound Isolation: Noise level relating to elevator equipment operation

in machine room shall not exceed 80 dBA. All dBA readings shall be

taken three (3) feet off the floor and three (3) feet from equipment.

F. Airborne Noise: Measured noise level of elevator equipment during

operation shall not exceed 50 dBA in elevator lobbies and 60 dBA inside

car under any condition including door operation and car ventilation

exhaust blower on its highest speed.

1.10 WARRANTY

A. Submit all labor and materials furnished in connection with elevator

system and installation to terms of "Warranty of Construction" articles

of FAR clause 52.246-21. The one year Warranty shall commence after

final inspection, completion of performance test, and upon full

acceptance of the installation and run concurrent with the guarantee

period of service.

B. During warranty period if a device is not functioning properly in

accordance with specification requirements, more maintenance than the

contract requires keeping device operational, device shall be removed

and a new device meeting all requirements shall be installed as part of

work until satisfactory operation of installation is obtained. Period

of warranty shall start anew for such parts from date of completion of

each new installation performed, in accordance with foregoing

requirements.

1.11 POWER SUPPLY

A. For power supply in each machine room, see Specification 26 05 19,

Electrical specifications, and Electrical drawings.

B. Main Line Disconnect Switch/Shunt Trip Circuit Breaker for each

controller shall be located inside the machine room at the strike side

of the machine room door and lockable in the “Off” position.

C. Surge Suppressors to protect the elevator equipment.

Page 10: VA 14 21 00 Electric Traction Elevators · be actively pursuing Certified Elevator Mechanic status. ... Hoisting Machine Motor, ... VA 14 21 00 Electric Traction Elevators

08/01/16

14 21 00-10

1.12 EMERGENCY POWER SUPPLY

A. Emergency power supply, its starting means, transfer switch for

transfer of elevator supply from normal to emergency power, two pair of

conductors in a conduit from an auxiliary contact on the transfer

switch (open or close contacts as required by Controller Manufacturer)

to terminals in the group elevator controller and other related work

shall be provided by the Electrical Contractor.

B. Upon loss of normal power supply there shall be a delay before

transferring to emergency power of 10 seconds minimum to 45 seconds

maximum, the delay shall be accomplished through an adjustable timing

device.

C. Prior to the return of normal power an adjustable timed circuit shall

be activated that will cause all cars to remain at a floor if already

there or stop and remain at the next floor if in flight. Actual

transfer of power from emergency power to normal building power shall

take place after all cars are stopped at a floor with their doors open.

D. Car lighting circuits shall be connected to the emergency power panel.

1.13 ELEVATOR MACHINE ROOM AND MACHINE SPACE

A. Provide a machine room that meets the requirements of ASME A17.1, IBC,

and NEC.

B. Provide stairs and landing for access to the machine room. The landing

shall be large enough to accommodate full opening of the door plus 24

in.

C. Locate the light switch on the lock side of the door inside the machine

room.

D. Locate sprinkler pipes to provide seven (7) feet head clearance. Do not

locate sprinkler heads, heat detectors, and smoke detectors directly

over elevator equipment.

1.14 HOISTWAY LIGHTING - OPTIONAL

A. Provide lighting with 3-way switches at the top and bottom of the

hoistway accessible from elevator hoistway entrance prior to entering

the pit or stepping onto the car top.

B. Lighting shall illuminate top of elevator cab when it is at the top

floor and the pit when at the bottom floor.

PART 2 – PRODUCTS

2.1 MATERIALS

A. Where stainless steel is specified, it shall be corrosion resisting

steel complying with Fed. Spec. QQ-S-766, Class 302 or 304, Condition A

Page 11: VA 14 21 00 Electric Traction Elevators · be actively pursuing Certified Elevator Mechanic status. ... Hoisting Machine Motor, ... VA 14 21 00 Electric Traction Elevators

08/01/16

14 21 00-11

with Number 4 finish on exposed surfaces. Stainless steel shall have

the grain of belting in the direction of the longest dimension and

surfaces shall be smooth and without waves. During installation all

stainless steel surfaces shall be protected with suitable material.

B. Where cold rolled steel is specified it shall be low-carbon steel

rolled to stretcher level standard flatness, complying with ASTM A109.

2.2 MANUFACTURED PRODUCTS

A. Materials, devices, and equipment furnished shall be of current

production by manufacturers regularly engaged in the manufacture of

such items. The elevator equipment, including controllers, door

operators, and supervisory system shall be the product of manufacturers

of established reputation, provided such items are capably engineered

and produced under coordinated specifications to ensure compatibility

with the total operating system.

B. Manufacturers of equipment assemblies which include components made by

others shall assume complete responsibility for the final assembled

unit. Components shall be compatible with each other and with the total

assembly for the intended service.

C. Mixing of manufactures related to a single system or group of

components shall be identified in the submittals.

D. If key operated switches are furnished in conjunction with component of

this elevator installation, furnish four (4) keys for each individual

switch or lock. Provide different key tumblers for different switch and

lock functions. Each and every key shall have a tag bearing a stamped

or etched legend identifying its purpose.

2.3 CONDUIT AND WIREWAY

A. Install electrical conductors, except traveling cable, in rigid zinc-

coated steel or aluminum conduit, electrical metallic tubing or metal

wireways. Rigid conduit smaller than .75 inch or electrical metallic

tubing smaller than .50 inch electrical trade size shall not be used.

All raceways completely embedded in concrete slabs, walls, or floor

fill shall be rigid steel conduit. Wireway (duct) shall be installed

in the hoistway and to the controller and between similar apparatus in

the elevator machine room. Fully protect self-supporting connections,

where approved, from abrasion or other mechanical injury. Flexible

metal conduit not less than .375 inch electrical trade size may be

used, not exceeding 18 inches in length unsupported, for short

Page 12: VA 14 21 00 Electric Traction Elevators · be actively pursuing Certified Elevator Mechanic status. ... Hoisting Machine Motor, ... VA 14 21 00 Electric Traction Elevators

08/01/16

14 21 00-12

connections between risers and limit switches, interlocks, and for

other applications permitted by NEC.

B. All conduit terminating in steel cabinets, junction boxes, wireways,

switch boxes, outlet boxes and similar locations shall have approved

insulation bushings. Install a steel lock nut under the bushings if

they are constructed completely of insulating materials. Protect the

conductors at ends of conduits not terminating in steel cabinets or

boxes by terminal fittings having an insulated opening for the

conductors.

C. Rigid conduit and EMT fittings using set screws or indentations as a

means of attachment shall not be used.

D. Connect motor or other items subject to movement, vibration or removal

to the conduit or EMT systems with flexible, steel conduits.

2.4 CONDUCTORS

A. Conductors shall be stranded or solid coated annealed copper in

accordance with Federal Specification J-C-30B for Type RHW or THW.

Where 16 and 18 AWG are permitted by NEC, single conductors or multiple

conductor cables in accordance with Federal Specification J-C-580 for

Type TF may be used provided the insulation of single conductor cable

and outer jacket of multiple conductor cable is flame retardant and

moisture resistant. Multiple conductor cable shall have color or number

coding for each conductor. Conductors for control boards shall be in

accordance with NEC. Joints or splices are not permitted in wiring

except at outlets. Tap connectors may be used in wireways provided

they meet all UL requirements.

B. Provide all conduit and wiring between machine room, hoistway and

fixtures.

C. All wiring must test free from short circuits or ground faults.

Insulation resistance between individual external conductors and

between conductors and ground shall be a minimum of one megohm.

D. Where size of conductor is not given, voltage and amperes shall not

exceed limits set by NEC.

E. Provide equipment grounding. Ground the conduits, supports, controller

enclosure, motor, platform and car frame, and all other non-current

conducting metal enclosures for electrical equipment in accordance with

NEC. The ground wires shall be copper, green insulated and sized as

required by NEC. Bond the grounding wires to all junction boxes,

cabinets, and wire raceways.

Page 13: VA 14 21 00 Electric Traction Elevators · be actively pursuing Certified Elevator Mechanic status. ... Hoisting Machine Motor, ... VA 14 21 00 Electric Traction Elevators

08/01/16

14 21 00-13

F. Terminal connections for all conductors used for external wiring

between various items of elevator equipment shall be solderless

pressure wire connectors in accordance with Federal Specification W-S-

610. The Elevator Contractor may, at his option, make these terminal

connections on #10 gauge or smaller conductors with approved terminal

eyelets set on the conductor with a special setting tool, or with an

approved pressure type terminal block. Terminal blocks using pierce-

through serrated washers are not acceptable.

2.5 TRAVELING CABLES

A. All conductors to the car shall consist of flexible traveling cables

conforming to the requirements of NEC. Traveling cables shall run from

the junction box on the car directly to the controller. Junction boxes

on the car shall be equipped with terminal blocks. Terminal blocks

having pressure wire connectors of the clamp type that meet UL 486A

requirements for stranded wire may be used in lieu of terminal eyelet

connections. Terminal blocks shall have permanent indelible identifying

numbers for each connection. Cables shall be securely anchored to avoid

strain on individual terminal connections. Flame and moisture resistant

outer covering must remain intact between junction boxes. Abrupt

bending, twisting and distortion of the cables shall not be permitted.

B. Provide spare conductors equal to 10 percent of the total number of

conductors furnished, but not less than 5 spare conductors in each

traveling cable.

C. Provide shielded wires for the auto dial telephone system within the

traveling cable, five (5) pair shielded wires for card reader, one (1)

RG-6 Ethernet cable for Wi-FI, and two (2) pair 14 gauge wires for

power as needed.

D. If traveling cables come into contact with the hoistway or elevator due

to sway or change in position, provide shields or pads to the elevator

and hoistway to prevent damage to the traveling cables.

E. Hardware cloth may be installed from the hoistway suspension point to

the elevator pit to prevent traveling cables from rubbing or chafing.

Hardware cloth shall be securely fastened and tensioned to prevent

buckling. Hardware cloth is not required when traveling cable is hung

against a flat wall.

2.6 CONTROLLER AND SUPERVISORY PANEL

A. UL/CSA Labeled Controller: Mount all assemblies, power supplies,

chassis switches, and relays on a steel frame in a NEMA Type 1 General

Page 14: VA 14 21 00 Electric Traction Elevators · be actively pursuing Certified Elevator Mechanic status. ... Hoisting Machine Motor, ... VA 14 21 00 Electric Traction Elevators

08/01/16

14 21 00-14

Purpose Enclosure. Cabinet shall be securely attached to the building

structure.

B. Properly identify each device on all panels by name, letter, or

standard symbol which shall be neatly stencil painted or decaled in an

indelible and legible manner. Identification markings shall be

coordinated with identical markings used on wiring diagrams. The ampere

rating shall be marked adjacent to all fuse holders. All spare

conductors to controller and supervisory panel shall be neatly formed,

laced, and identified.

C. Controller shall be provided with wiring and components for additional

future travel if required.

2.7 MICROPROCESSOR CONTROL SYSTEM

A. Provide a microprocessor control system with absolute position/speed

feedback to control dispatching, signal functions, door operation, and

VVVF Drive for hoist motor control. Complete details of the components

and printed circuit boards, together with a complete operational

description, shall be submitted for approval. Add Regenerative Drive

when economically advantages to the VA.

1. Controller manufacturer shall provide factory training, engineering

and technical support, including all manuals, wiring diagrams, and

tools necessary for adjusting, maintenance, repair, and testing of

equipment to the VA for use by the VA’s designated Elevator

Maintenance Service Provider.

2.8 EMERGENCY POWER OPERATION

A. The control system for Elevator(s) shall provide for the operation of

at least one car per elevator group on emergency power upon failure of

the normal power supply.

B. Auxiliary equipment on elevator controllers, wiring between associated

elevator controllers and wiring between elevator controllers and remote

selector panel as required to permit the elevators to operate as

detailed, shall be provided by the Elevator Contractor.

C. Upon loss of normal power supply there shall be a delay before

transferring to emergency power of 10 seconds minimum to 45 seconds

maximum, the delay shall be accomplished through an adjustable timing

device. Following this adjustable delay the associated elevators shall

function as follows:

SPEC WRITER NOTE: Selector switch is not required when Emergency Power is capable of operating all elevators in the group.

Page 15: VA 14 21 00 Electric Traction Elevators · be actively pursuing Certified Elevator Mechanic status. ... Hoisting Machine Motor, ... VA 14 21 00 Electric Traction Elevators

08/01/16

14 21 00-15

1. Selector switch, Automatic position:

a. Not more than // one elevator // two elevators // at a time in

each group shall be automatically selected and returned to the

main floor, at contract speed, cycle its car and hoistway doors

and shut down, with "Door Open" button remaining operable.

b. As each elevator reaches the designated floor and shuts down,

another elevator shall start and return to the designated floor.

c. Elevators that have been manually removed from automatic service

and are on independent service, fire service or medical emergency

shall receive an automatic return signal. Elevators on inspection

service or out of service shall not receive a signal.

d. When an elevator is given a signal to return and it is unable to

start its movement to the designated floor within 30 seconds it

shall be by-passed. When an elevator is by-passed, another

elevator shall start and return.

e. This process shall continue until all elevators have returned to

the designated floor and shut down.

f. Any elevator or elevators by-passed on initial return signal

shall be signaled again.

g. When all cars in group have returned to designated floor, //one

elevator // two elevators // all elevators // in each group shall

be designated for automatic operation. Individual cars in each

group shall restart at 5 second intervals.

h. If elevator(s) are keyed on to medical emergency service in the

car prior to transfer to emergency power operation, medical

emergency service shall be retained. This elevator shall be the

first automatically selected elevator to operate on emergency

power operation and complete its selected call demand. The

elevator will return to the designated floor after the key switch

is reset to normal position.

2. Selector switch, Manual operation:

a. Selector switch shall be mechanically and electrically

interlocked to prevent the selection of more than // one elevator

// two elevators // from operating on emergency power.

b. The selector switch shall have positions marked with the number

of each elevator controlled. It shall also have a position marked

"Automatic". When the selector switch is set to the automatic

position, the medical emergency service car shall operate on

Page 16: VA 14 21 00 Electric Traction Elevators · be actively pursuing Certified Elevator Mechanic status. ... Hoisting Machine Motor, ... VA 14 21 00 Electric Traction Elevators

08/01/16

14 21 00-16

emergency power operation, or if none, the last car arriving at

the designated floor shall operate on emergency power operation.

c. Change in selection of elevators shall be by means of the

selection switch and shall occur only when the previous selected

elevator is stopped at the designated floor.

d. The selector switch shall be locked out of operation when the

system is in the normal mode of operation.

e. Locate the selector switch above the hall push button at the

designated level. The key switch shall be a tumbler type lock

furnished with four keys. The enclosure faceplate shall be

identified "Emergency Power Control" with 13 mm (.50 in.)

engraved letters filled with black paint.

D. Prior to the return of normal power an adjustable timer circuit shall

activate that will cause all cars to remain at a floor if already there

or stop and remain at the next floor if in flight. Actual transfer of

power from emergency power to normal building power shall take place

after all cars are stopped at a floor with their doors open.

SPEC WRITER NOTE: If emergency power is not provided delete A-D and use E.

E. Emergency Rescue Operation:

Provide a power source to send the elevator to the nearest landing.

After the elevator has leveled at the nearest landing, provide power to

open the car and hoistway doors automatically. After a predetermined

time the doors shall close. Power shall stay applied to the door open

button to reopen the doors from the inside of the elevator. The

elevator shall remain shut down at the landing until normal power is

restored. Install a sign on the controller indicating that power is

applied to emergency rescue operator and door operator during loss of

normal power.

2.9 MACHINE ROOM MONITOR

A. Provide a monitor in each machine room, separate monitors for each

passenger elevator group, and each service elevator group. Provide one

keyboard for each monitor.

B. The monitor shall contain indicators to provide the following

information:

1. The floor where each elevator is currently located.

Page 17: VA 14 21 00 Electric Traction Elevators · be actively pursuing Certified Elevator Mechanic status. ... Hoisting Machine Motor, ... VA 14 21 00 Electric Traction Elevators

08/01/16

14 21 00-17

2. The direction that each elevator is currently traveling or is

scheduled to travel.

3. The location and direction of currently registered hall calls.

4. Elevators that are currently out of service.

5. Elevators that are currently bypassing hall calls.

6. Elevators that are currently engaged in passenger transfers.

7. Operations program under which entire group is currently operating.

8. Zone divisions of the entire group.

9. Door positions.

10. Status indication for cars on independent service, car top

inspection, stop switch activated, alarm activated, fire service,

and earthquake protection activated, etc.

C. The maintenance terminal shall be suitable for all troubleshooting

procedures related to the specific type microprocessor installed on

this project.

2.10 FIREFIGHTER’S SERVICE

A. Provide Firefighter’s Service.

1. Main Floor:

2. Alternate Floor:

3. Verify main and alternate floors with Contract Officer’s

Representative.

2.11 INDEPENDENT SERVICE

A. Provide a legibly and indelibly labeled "INDEPENDENT SERVICE", two-

position key operated switch on the face of the main car operating

panel that shall have its positions marked "ON" and "OFF". When the

switch is in the "ON" position, the car shall respond only to calls

registered on its car dispatch buttons and shall bypass all calls

registered on landing push buttons. The car shall start when a car call

is registered, car call button or door close button is pressed, car and

hoistway doors are closed, and interlock circuits are made. When switch

is returned to "OFF" position, normal service shall be resumed.

2.12 MEDICAL EMERGENCY SERVICE – PATEINCE CARE FACILITIES ONLY

A. Provisions shall be made for calling elevator(s) to any floor served by

the elevator on an emergency basis, operating independently from the

dispatch signals and landing call signals.

B. Install card reader/key switch in the floor landing push button fixture

above the push buttons.

Page 18: VA 14 21 00 Electric Traction Elevators · be actively pursuing Certified Elevator Mechanic status. ... Hoisting Machine Motor, ... VA 14 21 00 Electric Traction Elevators

08/01/16

14 21 00-18

C. Provide a call registered light indicator adjacent to card reader/key

switch. The card reader/key switch at the landings and in the car shall

only be operable by authorized personnel with a valid VA ID badge/key.

D. When card reader/key switch is activated at any floor, the call

register light indicator shall illuminate at the call floor and inside

the elevator only. The elevator control system shall instantly select

an elevator to respond to the medical emergency call. Immediately upon

selection, all car calls shall be cancelled. If car is traveling away

from the medical emergency call, it shall slow down and stop at the

nearest floor, maintain closed doors, reverse direction and proceed

nonstop to the medical emergency call floor. If the car is traveling

toward the medical emergency call floor, it shall proceed to that floor

nonstop. If at the time of selection it is slowing down for a stop, the

car shall stop, maintain doors closed, and start immediately toward the

medical emergency floor.

E. Arriving at the medical emergency floor, the car shall remain with

doors open for 30 seconds. After this interval has expired and the car

has not been placed on medical emergency operation inside the car, the

car shall automatically return to normal service.

F. Provide an LED illuminated indicator light next to the Medical

Emergency card reader/key switch the same size as the Fire Service

indicator.

1. Locate a “Medical Emergency” card reader/key switch above call

buttons in the main car operating panel for selecting medical

emergency service. Activation of the card reader will allow the car

to accept a car call for any floor, close doors, and proceed nonstop

to the floor desired.

2. After medical emergency call has been completed the elevator shall

return to normal operation after an adjustable time of 30 to 90

seconds has expired.

G. In the center of the rear cab panel provide a back lighted "MEDICAL

EMERGENCY" LED illuminated display that shall flash on and off

continuously when the car is assigned to this operation and until it is

restored to normal service. "MEDICAL EMERGENCY" indicator shall be a

photographic negative type 1830 mm (72 in.) to center above the floor,

152 mm (6 in.) wide X 76 mm (3 in.) high, with 12 mm (.50 in.) high

letters legible only when illuminated.

Page 19: VA 14 21 00 Electric Traction Elevators · be actively pursuing Certified Elevator Mechanic status. ... Hoisting Machine Motor, ... VA 14 21 00 Electric Traction Elevators

08/01/16

14 21 00-19

H. If the car being operated on “Independent Service”, the medical

emergency service indicator lights in the car operating panel and rear

wall shall be illuminated, buzzer shall sound, and the “Audio Voice”

system shall direct the attendant to return the car to automatic

operation.

I. If the car is out of service and unable to answer medical emergency

calls, the call register light shall not illuminate.

J. Each card reader/key switch shall have its identity legible and

indelible engraved in faceplates. All lettering shall be 6 mm (.25 in.)

high, filled with black paint.

K. When Phase I fire recall is activated it shall over-ride elevators on

medical emergency service and return them to the main or alternate fire

service recall floor. When the fire emergency floor has been identified

the attendants may complete their medical emergency run on Phase II

firefighter’s operation if life safety is not affected.

2.13 LOAD WEIGHING

A. Provide means for weighing car load for each and every elevator. When

load in a car reaches an adjustable predetermined level of the rated

capacity, that car shall bypass registered landing calls until the load

in the car drops below the predetermined level. Calls bypassed in this

manner shall remain registered for the next car. The initial adjustment

of the load weighting bypass setting shall be 60 to 100 percent.

2.14 ANTI-NUISANCE FEATURE

A. If weight in the car is not commensurate with the number of registered

car calls, cancel car calls. Systems that employ either load weighing

or door protective device for activation of this feature are

acceptable.

2.15 SEISMIC REQUIREMENTS

A. Meet the requirements of VA Seismic Design Manual H-18-8.

2.16 ELEVATOR MACHINE BEAMS

A. Overhead beams shall support machines and machinery in place to prevent

movement under any conditions imposed in service.

2.17 TRACTION HOIST MACHINE

A. Provide geared/gearless traction machine with an AC motor, brake, drive

sheave, and deflector sheave mounted in proper alignment on an isolated

bedplate.

B. Provide hoist machine mounted direct drive, digital, closed-loop

velocity encoder.

Page 20: VA 14 21 00 Electric Traction Elevators · be actively pursuing Certified Elevator Mechanic status. ... Hoisting Machine Motor, ... VA 14 21 00 Electric Traction Elevators

08/01/16

14 21 00-20

C. Drive sheaves shall be free from cracks, sand holes, and other

imperfections that would tend to injure the hoist ropes. Sheave shall

be turned smooth and true with rope grooves of proper design to insure

maximum traction and maximum life of the hoist ropes. Traction sheave

shall be mechanically coupled to the hoist motor shaft centered in a

positive manner.

D. Hoisting machine brake shall be drum or disc type and shall have the

capacity to stop and hold the elevator with 125 percent of rated load.

Arrange brake circuits so that no current shall be applied to the brake

coil prior to the establishment of the hoistway door interlock circuit,

except during leveling, re-leveling, and hoistway access operation.

2.18 SHEAVES

A. Provide deflector sheaves with a metal basket type guard mounted below

the sheave and a guard to prevent ropes from jumping out of grooves.

Securely fasten guard to sheave support beams.

B. Two-to-one idler sheaves on car and counterweight, if used, shall be

provided with metal guards that prevent foreign objects from falling

between ropes and sheave grooves and to prevent ropes from jumping out

of grooves.

SPEC WRITER NOTE: If hoisting machine is located at bottom of hoistway or offset from hoistway, include paragraph C.

C. Securely mount overhead sheaves on overhead beams in proper alignment

with basement traction sheave, car and counterweight rope hitches or

sheaves. Provide blocking beams where sheaves are installed on two or

more levels.

2.19 HOIST ROPES

A. Provide elevator with the required number and size of ropes to insure

adequate traction and required safety factor. Hoisting ropes shall be

pre-formed 8 x 19 or 8 x 25 traction steel, conforming to Federal

Specification RR-W-410 with minimum nominal diameter of 0.50 inch.

B. Securely attach a corrosion resistant metal data tag to one hoisting

rope fastening on top of the elevator.

2.20 HOIST ROPE COMPENSATION

A. Provide compensation when required by controller manufacturer.

Compensation shall consist of a necessary number and size of

encapsulated chains attached to the underside of car and counterweight

frames.

Page 21: VA 14 21 00 Electric Traction Elevators · be actively pursuing Certified Elevator Mechanic status. ... Hoisting Machine Motor, ... VA 14 21 00 Electric Traction Elevators

08/01/16

14 21 00-21

1. Provide pit guide to minimize chain sway.

2. Provide take-up to compensate for hoist rope stretch.

3. Pad areas where compensation may strike car or hoistway items.

2.21 GOVERNOR ROPE

A. Governor Rope shall be 6 x 19 or 8 x 19 wire rope, preformed traction

steel, uncoated, fiber core, conforming to Federal Specification RR-W-

410 with minimum nominal diameter of 0.375 inch having a minimum safety

factor of 5. Tiller rope construction is not acceptable.

B. Under normal operation rope shall run free and clear of governor jaws,

rope guards, and other stationary parts.

C. Securely attach governor rope tag to governor rope releasing carrier.

2.22 SPEED GOVERNOR

A. Provide Centrifugal car driven governor to operate the car safety

device // and counterweight governor to operate the counterweight

safety device //. Governor shall be complete with weighted pit tension

sheave, governor release carrier and mounting base with protected cable

sleeves.

B. Furnish overspeed switch and speed reducing switches when required.

C. The governor rope clamping device shall be designed to prevent

appreciable damage to or deformation of the governor rope that results

from the stopping action of the device operating the safety.

D. Provide metal guard over top of governor rope and sheaves.

E. Where the elevator travel does not exceed 100 feet, the weight tension

sheave may be mounted on a pivoted steel arm in lieu of operating in

steel guides.

2.23 CAR // AND COUNTERWEIGHT // SAFETY DEVICE

A. Provide “Type B Safeties” on the elevator//and counterweight//.

2.24 ASCENDING CAR OVERSPEED PROTECTION

A. Provide a device to prevent ascending over speed and unintended motion

away from the landing when the doors are not locked.

2.25 CAR AND COUNTERWEIGHT BUFFERS

A. Provide buffer(s) for each car and each counterweight. Securely fasten

buffers and supports to the pit channels and in the alignment with

striker plates on car and counterweight. Each installed buffer shall

have a permanently attached metal plate indicating its stroke and load

rating. Buffer anchorage shall not puncture pit waterproofing.

Page 22: VA 14 21 00 Electric Traction Elevators · be actively pursuing Certified Elevator Mechanic status. ... Hoisting Machine Motor, ... VA 14 21 00 Electric Traction Elevators

08/01/16

14 21 00-22

2.26 COUNTERWEIGHTS

A. Elevator shall be counterweighted with the weight of the car plus 40-50

percent of the rated capacity load as required by the controller

manufacturer.

B. Furnish two (2) tie rods with cotter pins and double nuts at top and

bottom. Install counterweight retainer plates or other approved means

on tie rods to prevent counterweight sub-weights from jumping and/or

rattling. Both ends of tie-rods shall be visible and accessible.

2.27 CAR AND COUNTERWEIGHT GUIDES

A. Install on car frame four // adjustable roller guides // flexible

sliding swivel guide shoes //, each assembled on a substantial metal

base, to permit individual alignment to the guide rails.

B. Each guide shall consisting of not less than three (3) wheels, each

with a durable, resilient oil-resistant material tire rotating on ball

bearings having sealed-in lubrication. Assemble rollers on a

substantial metal base and mount to provide continuous spring pressure

contact of all wheels with the corresponding rail surfaces under all

conditions of loading and operation. Secure the roller guides at top

and bottom on each side of car frame and counterweight frame. All

mounting bolts shall be fitted with nuts, flat washers, split lock

washers, and if required, beveled washers.

C. Provide sheet metal guards to protect rollers on top of car and

counterweight.

D. Minimum diameter of car rollers shall be 150 mm (6 in.) unless the six

wheel roller guide is used. The entire elevator car shall be properly

balanced to equalize pressure on all guide rollers. Cars shall be

balanced in post-wise and front-to-back directions. Test for this

balanced condition shall be witnessed at time of final inspection.

E. Minimum diameter of counterweight rollers shall not be less than 75 mm

(3 in.). Properly balance counterweight frame to equalize pressure on

all guide rollers. The Contractor shall have the option of furnishing,

for counterweight only, mechanically adjusted roller guide in lieu of

spring loaded roller guides as specified.

F. Alternate Guide Shoes for service and freight elevators:

1. Provide each shoe with renewable non-metallic gibs of durable

material having low coefficient of friction and long-wearing

qualities, when operated on guide rails receiving infrequent, light

Page 23: VA 14 21 00 Electric Traction Elevators · be actively pursuing Certified Elevator Mechanic status. ... Hoisting Machine Motor, ... VA 14 21 00 Electric Traction Elevators

08/01/16

14 21 00-23

applications of rail lubricant. Gibs containing graphite or other

solid lubricants are not acceptable.

2. Flexible guide shoes of approved design, other than swivel type, may

be used provided they are self-aligning on all three faces of the

guide rails.

3. Provide spring take-up in car guide shoes for side play between

rails.

G. Equip car and counterweight with an auxiliary guiding device for each

guide shoe which shall prevent the car or counterweight from leaving

the rails in the event that the normal guides are fractured. These

auxiliary guides shall not, during normal operation, touch the guiding

surfaces of the rails. Fabricate the auxiliary guides from hot rolled

steel plate and mount between the normal guide shoes and the car and

counterweight frames. The auxiliary guides may be an extension of the

normal guide shoe mounting plate if that plate is fabricated from hot

rolled steel. The portion of the auxiliary guide which shall come in

contact with the rail guiding surfaces in the event of loss of the

normal guides shall be lined with an approved bearing material to

minimize damage to the rail guiding surfaces.

2.28 GUIDE RAILS, SUPPORTS, AND FASTENINGS

A. Guide rails for car shall be planed steel T-sections and weigh // 27.5

kg/m (18.5 lb/ft) // 22.5 kg/m (15 lb/ft) //. Guide rails for

counterweight shall be planed steel T-sections and weigh // 12.0 kg/m

(8 lb/ft) // 18.0 kg/m (12 lb/ft) // 22.5 kg/m (15 lb/ft)//.

B. Securely fasten guide rails to the brackets or other supports by heavy

duty steel rail clips.

C. Provide car and counterweight rail brackets and counterweight spreader

brackets of sufficient size and design to secure substantial rigidity

to prevent spreading or distortion of rails under any condition.

D. Guide rails shall extend from channels on pit floor to within 76 mm (3

in.) of the underside of the concrete slab or grating at top of

hoistway with a maximum deviation of 3.2 mm (.125 in.) from plumb in

all directions. Provide a minimum of 19 mm (.75 in.) clearance between

bottom of rails and top of pit channels.

E. Guide rail anchorages in pit shall be made in a manner that will not

reduce effectiveness of the pit waterproofing.

F. In the event inserts or bond blocks are required for the attachment of

guide rails, the Contractor shall furnish such inserts or bond blocks

Page 24: VA 14 21 00 Electric Traction Elevators · be actively pursuing Certified Elevator Mechanic status. ... Hoisting Machine Motor, ... VA 14 21 00 Electric Traction Elevators

08/01/16

14 21 00-24

and shall install them in the forms before the concrete is poured. Use

inserts or bond blocks only in concrete or block work where steel

framing is not available for support of guide rails. Expansion-type

bolting for guide rail brackets will not be permitted.

G. Guide rails shall be clean and free of any signs of rust, grease, or

abrasion before final inspection. Paint the shank and base of the T-

section with one field coat of manufacturer’s standard enamel.

2.29 NORMAL AND FINAL TERMINAL STOPPING DEVICES

A. Mount terminal slowdown switches and direction limit switches on the

elevator or in hoistway to reduce speed and bring car to an automatic

stop at the terminal landings.

1. Switches shall function with any load up to and including 125

percent of rated elevator capacity at any speed obtained in normal

operation.

2. Switches, when opened, shall permit operation of elevator in reverse

direction of travel.

B. Mount final terminal stopping switches in the hoistway.

1. Switches shall be positively opened should the car travel beyond the

terminal direction limit switches.

2. Switches shall be independent of other stopping devices.

3. Switches, when opened, shall remove power from hoist motor, apply

hoist machine brake, and prevent operation of car in either

direction.

2.30 CROSSHEAD DATA PLATE AND CODE DATA PLATE

A. Permanently attach a non-corrosive metal Data Plate to car crosshead.

B. Permanently attach a non-corrosive Code Data Plate to the controller.

2.31 WORKMAN'S LIGHTS AND OUTLETS

A. Provide duplex GFCI protected type receptacles and lamps with guards on

top of each elevator car and beneath the platform. The receptacles

shall be in accordance with Fed. Spec. W-C-596 for Type D7, 2-pole, 3-

wire grounded type, rated for 15 amperes and 125 volts.

2.32 TOP-OF-THE CAR OPERATING DEVICE

A. Provide a cartop operating device.

B. The device shall be activated by a toggle switch mounted in the device.

The switch shall be clearly marked "INSPECTION" and "NORMAL" on the

faceplate, with 6 mm (.25 in.) letters.

C. Movement of the elevator shall be accomplished by the continuous

pressure on a direction button and a safety button.

Page 25: VA 14 21 00 Electric Traction Elevators · be actively pursuing Certified Elevator Mechanic status. ... Hoisting Machine Motor, ... VA 14 21 00 Electric Traction Elevators

08/01/16

14 21 00-25

D. Provide an emergency stop switch, push to stop/pull to run.

E. Provide permanent identification for the operation of all components in

the device.

F. The device shall be permanently attached to the elevator crosshead on

the side of the elevator nearest to the hoistway doors used for

accessing the top of the car.

2.33 CAR LEVELING DEVICE

A. Car shall be equipped with a two-way leveling device to automatically

bring the car to within 3 mm (.125 in.) of exact level with the landing

for which a stop is initiated regardless of load in car or direction.

B. If the car stops short or travels beyond the floor, the leveling

device, within its zone shall automatically correct this condition and

maintain the car within 3 mm (.125 in.) of level with the floor landing

regardless of the load carried.

C. Provide encoded steel tape or steel tape with magnets. Submit design

for approval.

2.34 EMERGENCY STOP SWITCHES

A. Provide an emergency stop switch, push to stop/pull to run, for each

top-of-car device, pit, machine spaces, service panel and firefighter’s

control panel inside the elevator. Mount stop switches in the pit

adjacent to pit access door, at top of the pit ladder 1220 mm (48 in.)

above the bottom landing sill and 1220 mm (48 in.) above the pit floor

adjacent to the pit ladder.

B. Each stop switch shall be red in color and shall have "STOP" and "RUN"

positions legibly and indelibly identified.

2.35 MAIN CAR OPERATING PANEL

A. Locate the main car operating panel in the car enclosure on the front

return panel for passenger/service elevators and the front of the side

wall for freight elevators. The top floor car call push button shall

not be more than 1220 mm (48 in.) above the finished floor. Car call

push buttons and indicator lights shall be round with a minimum

diameter of 25 mm (1 in.), LED white light illuminated.

B. One piece front faceplate with edges beveled 15 degrees or swing return

panel shall have the firefighter’s service panel recessed into the

upper section and the service operation panel recessed into the lower

section fitted with hinged doors. Doors shall have concealed hinges,

be in the same front plane as the faceplate and fitted with cylinder

Page 26: VA 14 21 00 Electric Traction Elevators · be actively pursuing Certified Elevator Mechanic status. ... Hoisting Machine Motor, ... VA 14 21 00 Electric Traction Elevators

08/01/16

14 21 00-26

type key operated locks. Secure the faceplate with stainless steel

tamperproof screws.

C. All terminology and tactile symbols on the faceplate shall be on square

or rectangular plates recessed into the faceplate with its surface

flush with the surface of the faceplate. Use 6 mm (.25 in.) letters to

identify all devices in the faceplate. The handicapped markings with

contrasting background shall be 12mm (.50 in.) high raised .030 inch on

the plate. Surface mounted plates are not acceptable.

D. The upper section shall contain the following items in order listed

from top to bottom:

1. Elevator number, 12.5 mm (.50 in.) high with black paint for

contrast.

2. Capacity plate information with black paint for contrast with

freight loading class and number of passengers allowed.

3. LED illuminated digital car position indicator with direction

arrows.

4. Emergency car lighting system consisting of a rechargeable battery,

charger, controls, and LED illuminated light fixture. The system

shall automatically provide emergency light in the car upon failure

or interruption of the normal car lighting service, and function

irrespective of the position of the light control switch in the car.

The system shall be capable of maintaining a minimum illumination of

1.0 foot-candle when measured 1220 mm (48 in.)above the car floor

and approximately 305 mm (12 in.) in front of the car operating

panel, for not less than four (4) hours.

5. Firefighter’s Emergency Operation Panel shall be 1676 mm (66 in.)

minimum to 1830 mm (72 in.) maximum to the top of the panel above

finished floor.

6. Firefighter’s Emergency Indicator Light shall be round with a

minimum diameter of 25 mm (1 in.).

7. Medical Emergency card reader/key switch marked “MEDICAL EMERGENCY”

with two positions labeled “ON” and “OFF” and Medical Emergency

Indicator Light located next to the card reader/key switch shall be

round with a minimum diameter of 25 mm (1 in.). Instruction for

Medical Emergency operation shall be engraved below the card

reader/key switch and light.

8. Key operated Independent Service Switch.

Page 27: VA 14 21 00 Electric Traction Elevators · be actively pursuing Certified Elevator Mechanic status. ... Hoisting Machine Motor, ... VA 14 21 00 Electric Traction Elevators

08/01/16

14 21 00-27

9. Provide a Door Hold Button on the faceplate next to the Independent

Service Key Switch. It shall have “DOOR HOLD” indelibly marked on

the button. Button shall light when activated. When activated, the

door shall stay open for a maximum of one minute. To override door

hold timer, push a car call button or door close button.

10. Complete set of round car call push buttons, minimum diameter of 25

mm (1 in.), and LED white light illuminated, corresponding to the

floors served. Car call buttons shall be legibly and indelibly

identified by a floor number and/or letter not less than 12mm (.50

in.) high in the face of the call button.

11. Door Open and Door Close buttons shall be located below the car call

buttons. They shall have “OPEN” and “CLOSE” legibly and indelibly

identified by letters in the face of the respective button. The

Door Open button shall be located closest to the door jamb.

a. Rear Door Open and Rear Door Close buttons shall be located below

the Front Door Open and Front Door Close buttons. They shall

have “REAR OPEN” and “REAR CLOSE” legibly and indelibly

identified by letters in the face of the respective button.

12. Red Emergency Alarm button that shall be located below the car

operating buttons. Mount the emergency alarm button not lower than

890 mm (35 in.) above the finished floor. It shall be connected to

audible signaling devices. Provide audible signaling devices

including the necessary wiring.

13. Emergency Help push button shall activate two way communications by

Auto Dial telephone system that is compatible with the VAMC’s

telephone system. Help button shall be LED white light illuminated

and flash when call is acknowledged. Legibly and indelibly label the

button “HELP” in the face of the button with 12 mm (.50 in.) high

letters.

E. The service operation panel, in the lower section shall contain the

following items:

1. Light switch labeled “LIGHTS” for controlling interior car lighting

with its two positions marked “ON” and “OFF”.

2. Inspection switch that will disconnect normal operation and activate

hoistway access switches at terminal landings. Switch shall be

labeled “ACCESS ENABLE” with its two positions marked “ON” and

“OFF”.

Page 28: VA 14 21 00 Electric Traction Elevators · be actively pursuing Certified Elevator Mechanic status. ... Hoisting Machine Motor, ... VA 14 21 00 Electric Traction Elevators

08/01/16

14 21 00-28

3. Three position switch labeled “FAN” with its positions marked

“HIGH”, “LOW” and “OFF” for controlling car ventilating blower.

4. Two position, spring return, toggle switch or push button to test

the emergency light and alarm device. It shall be labeled “TEST

EMERGENCY LIGHT AND ALARM”.

SPEC WRITER NOTE: Freight elevator, provide emergency stop switch in the face of the car operating panel. Passenger or service elevator, provide stop switch inside the service panel.

5. Two position emergency stop switch, when operated, shall interrupt

power supply and stop the elevator independently of regular

operating devices. Emergency stop switch shall be marked “PUSH TO

STOP” and “PULL TO RUN”.

2.36 AUXILIARY CAR OPERATING PANEL

A. Provide an auxiliary car operating panel in the // front return panel

opposite the main car operating panel // rear return panel // side wall

of the elevator between the handrails immediately adjacent to the front

entrance column strike jamb //. The auxiliary car operating panel shall

contain only those controls essential to passenger (public) operation.

The auxiliary car operating panel faceplate shall match the main car

operating panel faceplate in material and general design. Secure the

faceplate with stainless steel tamperproof screws.

1. Complete set of round car call push buttons, minimum diameter 25 mm

(1 in.), and LED white light illuminated, corresponding to the

floors served. Car call button shall be legibly and indelibly

identified by a floor number and/or letter not less than 12 mm (.50

in.) high in the face of the call button corresponding to the

numbers of the main car operating buttons.

2. Mount door "OPEN" and door "CLOSE" buttons closest to the door jamb

and mount the alarm button no lower than 875 mm (35 in.) above the

finished floor. The Door Open button shall be located closest to the

door.

3. Cross-connect all buttons in the auxiliary car operating panels to

their corresponding buttons in the main car operating panel.

Registration of a car call shall cause the corresponding button to

illuminate in the main and auxiliary car operating panel.

4. Emergency Help push button shall activate two way communications by

auto dial telephone that is compatible with the VAMC’s telephone

Page 29: VA 14 21 00 Electric Traction Elevators · be actively pursuing Certified Elevator Mechanic status. ... Hoisting Machine Motor, ... VA 14 21 00 Electric Traction Elevators

08/01/16

14 21 00-29

system. Help button shall be LED white light illuminated and flash

when call is acknowledged. Legibly and indelibly label the button

“HELP” in the face of the button with 12 mm (.50 in.) high letters.

5. All terminology and tactile symbols on the faceplate shall be on

square or rectangular plates recessed into the faceplate with its

surface flush with the surface of the faceplate. The handicapped

markings with contrasting background shall be 12mm (0.50 in.) high

raised .030 inch on the plate, square or rectangular in shape. Use 6

mm (.50 in.) letters to identify all other devices in the faceplate.

Surface mounted plates are not acceptable.

2.37 CAR POSITION INDICATOR

A. Provide an alpha-numeric digital car position indicator in the main car

operating panel, consisting of numerals and arrows not less than 63 mm

(2.5 in.) high, to indicate position of car and direction of car

travel. Locate position indicator at the top of the main car operating

panel, illuminated by light emitting diodes.

2.38 AUDIO VOICE SYSTEM

A. Provide digitized audio voice system. Audio voice shall announce floor

designations, direction of travel, and special announcements. The voice

announcement system shall be a natural sounding human voice that

receives messages and shall comply with ADA requirements for audible

car position indicators. The voice announcer shall have two separate

volume controls, one for the floor designations and direction of

travel, and another for special announcements. The voice announcer

shall have a full range loud speaker, located on top of the cab. The

audio voice unit shall contain the number of ports necessary to

accommodate the number of floors, direction messages, and special

announcements. Install voice announcer per manufacturer’s

recommendations and instructions. The voice system shall be the product

of a manufacturer of established reputation. Provide manufacturer

literature and list of voice messages.

2.39 AUTO DIAL TELEPHONE SYSTEM

A. Furnish and install a complete ADA compliant auto dial telephone that

is compatible with the VAMC’s telephone system.

B. Provide a two-way communication device in the car with automatic

dialing, tracking and recall features with shielded wiring to car

controller in machine room. Provide dialer with automatic rollover

capability with two numbers.

Page 30: VA 14 21 00 Electric Traction Elevators · be actively pursuing Certified Elevator Mechanic status. ... Hoisting Machine Motor, ... VA 14 21 00 Electric Traction Elevators

08/01/16

14 21 00-30

C. “HELP” button shall illuminate and flash when call is acknowledged.

Button shall match floor push button design.

D. Provide “HELP” button tactile symbol signage and Braille adjacent to

button mounted integral with car operating panels.

E. The auto dial system may be located in the main or auxiliary car

operating panel. The speaker and unit shall be mounted on the backside

of the perforated stainless steel plate cover.

F. Each elevator shall have individual phone numbers.

G. If the operator ends the call, the passenger shall be able to redial

the telephone immediately.

2.40 CORRIDOR OPERATING DEVICES

A. Fabricate faceplates for elevator operating and signal devices from not

less than 3 mm (.125 in.) thick flat stainless steel with all edges

beveled 15 degrees.

B. Corridor push button faceplates shall be sized to accommodate corridor

pictograph on faceplate. The centerline of the landing push buttons

shall be 1067 mm (42 in.) above the corridor floor.

C. Elevator Corridor Call Station Pictograph shall be engraved in the

faceplate.

D. Fasten all car and corridor operating device and signal device

faceplates with stainless steel tamperproof screws.

E. All terminology and tactile symbols on the faceplate shall be raised

.030 inch with contrasting background, on square or rectangular plates

recessed into the faceplate with its surface flush with the surface of

the faceplate. The handicapped markings with contrasting background

shall be 12mm (0.5 in.) high raised .030 inch on the plate, square or

rectangular in shape. Use 6 mm (.25 in.) letters to identify all

other devices in the faceplate. Surface mounted plates are not

acceptable.

F. Provide //one//two// risers of landing call buttons for each elevator

or group of elevators as shown on contract drawings.

G. Each button shall contain an integral registration LED white light

which shall illuminate upon registration of a call and shall extinguish

when that call is answered.

H. The direction of each button shall be legibly and indelibly identified

by arrows not less than 12 mm (.50 in.) high in the face of each

button.

Page 31: VA 14 21 00 Electric Traction Elevators · be actively pursuing Certified Elevator Mechanic status. ... Hoisting Machine Motor, ... VA 14 21 00 Electric Traction Elevators

08/01/16

14 21 00-31

I. Landing push buttons shall not re-open the doors while the car and

hoistway doors are closing at that floor, the call shall be registered

for the next available elevator. Calls registered shall be canceled if

closing doors are re-opened by means of "DOOR OPEN" button or infrared

curtain unit.

J. Provide emergency power indicator light, medical emergency card

reader/key switch and indicator light, fire service recall key switch

and indicator light, fire recall instruction, communication failure

light, audible enunciator, and reset key switch in a separate fixture

at the designated main floor.

K. Submit design of hall pushbutton fixtures for approval.

2.41 DIGITAL CORRIDOR ARRIVAL LANTERN/POSITION INDICATOR

A. Provide elevator with combination corridor lantern/position indicator

digital display mounted over the hoistway entrances at each and every

floor in healthcare facilities. For non-healthcare facilities provide

combination fixtures only at main and alternate fire recall floors.

Provide each terminal landing with "UP" or "DOWN", minimum 63 mm (2.5

in.) high digital arrow lanterns and each intermediate landing with

"UP" and "DOWN" digital arrow lanterns. Each lens shall be LED

illuminated of proper intensity, so shielded to illuminate individual

lens only. The lenses in each lantern shall be illuminated green to

indicate "UP" travel and red to indicate "DOWN" travel. Lanterns shall

signal in advance of car arrival at the landing indicating the

direction of travel. Corridor lanterns shall not be illuminated when a

car passes a floor without stopping. Each lantern shall be equipped

with an audible electronic chime which shall sound once for "UPWARD"

bound car and twice for "DOWNWARD" bound car. Audible signal shall not

sound when a car passes the floor without stopping. Provide adjustable

sound level on audible signal. Car riding lanterns are not acceptable.

B. Install alpha-numeric digital position indicator between the arrival

lanterns. Indicator faceplate shall be stainless steel. Numerals shall

be not less than 63 mm (2.5 in.) high with direction arrows. Cover

plates shall be readily removable for re-lamping. The appropriate

direction arrow shall be illuminated during entire travel of car in

corresponding direction.

2.42 HOISTWAY ACCESS

A. Provide hoistway access switches for elevator at top terminal landing

to permit access to top of car, and at bottom terminal landing to

Page 32: VA 14 21 00 Electric Traction Elevators · be actively pursuing Certified Elevator Mechanic status. ... Hoisting Machine Motor, ... VA 14 21 00 Electric Traction Elevators

08/01/16

14 21 00-32

permit access to pit. Elevators with side slide doors, mount the access

key switch 1830 mm (6 ft.) above the corridor floor in the wall next to

the strike jamb.

B. Exposed portion of each access switch or its faceplate shall have

legible, indelible legends to indicate "UP", "DOWN", and "OFF"

positions.

C. Each access switch shall be a constant pressure cylinder type lock

having not less than five pins or five stainless steel disc combination

with key removable only when switch is in the "OFF" position.

D. Lock shall not be operable by any other key which will operate any

other lock or device used for any other purpose at the VA Medical

Center.

E. Arrange the hoistway switch to initiate and maintain movement of the

car. When the elevator is operated in the down direction from the top

terminal landing, limit the zone of travel to a distance not greater

than the top of the car crosshead level with the top floor. Submit

design and location of access switches for approval.

F. Provide emergency access for all hoistway entrances, keyways for

passenger and service elevators.

2.43 HOISTWAY ENTRANCES: PASSENGER/SERVICE ELEVATORS

A. Provide complete entrances with sills, sill supports, hangers, hanger

supports, tracks, angle struts, unit frames, door panels, fascia

plates, toe guards, hardware, bumpers, sight guards, and wall anchors.

B. Provide one piece extruded // aluminum // nickel silver // stainless

steel // sills grooved for door guides and recessed for fascia plates.

Sills shall have overall height of not less than 19 mm (.75 in.) set

true, straight, and level, with hoistway edges plumb over each other,

and top surfaces flush with finished floor. Hoistway entrance frames

and sills shall be grouted solid full length after installation.

C. Construct hanger supports of not less than 4.5 mm (.1875 in.) thick

steel plate, and bolted to strut angles.

D. Structural steel angles 76 mm x 76 mm x 9 mm (3 in. x 3 in. x .375 in.)

shall extend from top of sill to bottom of floor beam above, and shall

be securely fastened at maximum 457 mm (18 in.) on center and at each

end with two bolts.

E. Provide jambs and head soffits, of not less than 14-gauge stainless

steel. Jambs and head soffits shall be bolted/welded construction and

provided with three anchors each side. Side jambs shall be curved.

Page 33: VA 14 21 00 Electric Traction Elevators · be actively pursuing Certified Elevator Mechanic status. ... Hoisting Machine Motor, ... VA 14 21 00 Electric Traction Elevators

08/01/16

14 21 00-33

Radius of curvature shall be 89 mm (3.5 in.). Head jamb shall be

square, and shall overhang corridor face of side jambs by 6 mm (.25

in.). Rigidly fasten jambs and head soffits to building structure and

grouted solid. After installation, protect jambs and head soffits to

prevent damage to finish during construction.

F. Provide raised numerals or letters on cast, rear mounted plates for all

openings. Numerals shall be a minimum of 50 mm (2 in.) high, located

on each side of entrance frame, with centerline of 1524 mm (5 ft) above

the landing sill. The number plates shall contain Braille.

G. Provide unique car number on every elevator entrance at designated main

fire service floor level, minimum 76 mm (3 in.) in height.

H. Provide passenger entrances with single speed center opening horizontal

sliding doors and service entrances with two speed side opening

horizontal sliding doors.

1. Door panels shall be flush hollow metal construction, not less than

32 mm (1.25 in.) thick, consisting of one continuous piece 16-gauge

stainless steel on corridor side wrapped around the leading edge.

Separate two plates by a sound-deadening material, and reinforce by

steel shapes welded to the plates at frequent intervals. Reinforce

panels as required for installation of hangers, power-operating and

door-opening devices. Top and bottom of door panels shall have

continuous stiffener channels welded in place. Reinforcement of the

door panels shall be a minimum of 1.0 mm (0.04 in.) in thickness and

of the hat section type.

2. Hang doors on two-point suspension hangers having sealed ball-

bearing sheaves not less than 76 mm (3 in.) in diameter, made of

non-metallic sound-reducing material. Equip hangers with adjustable

ball-bearing rollers to take upward thrust of panels. Upthrust

rollers shall be capable of being locked in position after

adjustment to a maximum of .38 mm (.015625 in.) clearance. Provide

the hanger sheaves with steel fire stops to prevent disengagement

from tracks. Do not use hangers that are constructed integrally with

the door panels.

3. Provide two removable laminated phenolic gibs or other approved

material guides and a separate fire gib at the bottom of door panel.

4. Reinforce each door panel for interlock mechanism, drive assembly,

and closer. Provide relating devices to transmit motion from one

door panel to the other.

Page 34: VA 14 21 00 Electric Traction Elevators · be actively pursuing Certified Elevator Mechanic status. ... Hoisting Machine Motor, ... VA 14 21 00 Electric Traction Elevators

08/01/16

14 21 00-34

5. One door panel for each entrance shall bear a BOCA label,

Underwriters' label or labels from other accredited test

laboratories may be furnished provided they are based on fire test

reports and factory inspection procedures acceptable to the COR.

6. Fasten sight guard of 14-gauge stainless steel, extending full

height of panel, to leading edge of // fast speed panel of two-speed

doors // each panel of center opening doors //.

I. Provide 14-gauge sheet steel fascia plates in hoistway to extend

vertically from head of hanger support housing to sill above. Plates

shall be three (3) inches wider than door opening of elevator and

reinforced to prevent waves and buckles. Below bottom terminal landing

and over upper terminal landing provide shear guards beveled back to

and fastened to the wall.

J. Equip each hoistway door with an electrical/mechanical interlock,

functioning as hoistway unit system, to prevent operation of car until

doors are locked in the closed position unless car is operating in

leveling zone or hoistway access switch is used.

K. Wiring installed from the hoistway riser to each door interlock shall

be NEC type SF-2 or equivalent.

2.44 CAR FRAME: PASSENGER/SERVICE ELEVATORS

A. Car frame shall be constructed of channel stiles, crosshead, gussets,

braces, and cable hitch plate securely bolted and/or welded. The entire

assembly shall be constructed to withstand unequal loading of platform.

Car frame members shall be constructed to relieve the car enclosure of

all strains.

2.45 CAR PLATFORM: PASSENGER/SERVICE ELEVATORS

A. Construct the car platform to meet the requirements of class loading

specified. The platform shall be designed to withstand the forces

developed under the loading conditions specified. Provide car entrances

with extruded // aluminum // nickel silver // sill or better with

machined or extruded guide grooves. Cover underside and all exposed

edges of wood filled platform with sheet metal of not less than 26-

gauge, with all exposed joints and edges folded under. Fire resistant

paint is not acceptable. Platform shall have flexible composition

flooring not less than 3 mm (.125 in.) thick. For color, see Section 09

06 00, SCHEDULE FOR FINISHES. Adhesive material shall be type

recommended by manufacturer of flooring. Lay flooring flush with

threshold plate and base.

Page 35: VA 14 21 00 Electric Traction Elevators · be actively pursuing Certified Elevator Mechanic status. ... Hoisting Machine Motor, ... VA 14 21 00 Electric Traction Elevators

08/01/16

14 21 00-35

B. Provide a platform guard (toe guard) of not less than 12-guage sheet-

steel on the entrance side, extend 76 mm (3 in.) beyond each side of

entrance jamb. Securely brace platform guard to car platform, and bevel

bottom edge at a 60-75 degree angle from horizontal. Install platform

in the hoistway, so that the clearance between front edge and landing

threshold shall not exceed 32 mm (1.25 in.).

C. Isolate the platform from the car frame by approved rubber pads or

other equally effective means.

D. Provide adjustable diagonal brace rods to hold platform firmly within

car suspension frame.

E. Balance car front to back and side to side. Provide balancing frame and

weights, properly located, to achieve the required true balance.

F. Provide a bonding wire between frame and platform.

2.46 CAR ENCLOSURE: PASSENGER/SERVICE ELEVATORS

A. Car enclosure shall have a dome height inside the cab of 2440 mm (8

ft).

B. Securely fasten car enclosure to platform by through bolts located at

intervals of not more than 457 mm (18 in.) running through an angle at

the base of panels to underside of platform.

C. Front return wall panel, entrance columns, entrance head-jamb and

transom shall be 14-gauge stainless steel. Transom shall be full width

of cab. Side and rear walls shall be constructed of 14-gauge cold

rolled steel. Coat exterior of walls with mastic sound insulation

material approximately 2.5 mm (.09375 in.) thick followed by a prime

coat of paint.

D. Side and rear walls of passenger elevators may have raised panels

covered in fire rated materials approved for use in elevator interior.

E. Side and rear walls of service elevators, up to the center line of the

top handrail, shall be covered with stainless steel. Side and rear

walls to the ceiling shall be covered with // high pressure plastic

laminate panels // stainless steel applied directly to the cab walls or

raised panels //. Submit a method of fastening panels to steel walls.

F. Construct canopy of not less than 12-gauge steel.

G. Provide car top railings.

H. Provide a hinged top emergency exit cover. Exit shall be unobstructed

when open and shall have mechanical stops on the cover. Provide a exit

switch to prevent operation of the elevator when the emergency exit is

open.

Page 36: VA 14 21 00 Electric Traction Elevators · be actively pursuing Certified Elevator Mechanic status. ... Hoisting Machine Motor, ... VA 14 21 00 Electric Traction Elevators

08/01/16

14 21 00-36

I. Provide duplex, GFCI protected receptacle in car. Locate flush-mounted

receptacle on the centerline of the main car operating panel, 150 mm (6

in.) above the car floor.

J. Lighting for passenger/service elevators:

1. Provide //stainless steel // aluminum // hanging ceiling frame.

Construct frame of .125 in. x 1.50 in. x 1.50 in. “T” and “L”

sections, divide ceiling into six panels.

2. Provide LED illuminated car light fixtures above the ceiling panels.

Maintain a minimum light level of 50-foot candles at 914 mm (36 in.)

above the finished floor.

K. Optional lighting for service elevators:

1. Provide car with indirect LED lamps mounted front to rear in

lighting coves along each side of the cab ceiling, no hanging

ceiling.

2. Equip the lighting cove with asymmetrical reflectors having specular

finish. Maintain a minimum light level of 50-foot candles 914 mm (36

in.) above finished floor at the car operating panels.

3. Enclose the entire vertical space between the light trough outer

edge and the cab canopy with approved opaque white or clear lumicite

sheeting. Lumicite sheeting shall be removable for cleaning and re-

lamping.

L. Provide a blower unit arranged to exhaust through an opening in the

canopy. Provide a stainless or chrome plated fan grill on the interior

side of the opening. Provide screening over intake and exhaust end of

blower. Provide 2-speed fan, with rated air displacement of 250 cfm and

400 cfm at respective speeds. Mount fan on top of car with rubber

isolation to prevent transmission of vibration to car structure.

Provide a 3-position switch to control the unit in the service panel.

M. Provide car enclosure with two sets of handrails with centerlines 750

mm and 1050 mm (30 in. and 42 in.) above the car floor.

1. Locate handrails 38 mm (1.50 in.) from cab wall. Install handrails

on // side and rear walls // side walls only for front and rear

openings //. Conceal all handrail fastenings. Handrails shall be

removable from inside the car enclosure.

2. Provide service elevators with flat stock handrails with the ends at

the entrance turned back to the wall.

Page 37: VA 14 21 00 Electric Traction Elevators · be actively pursuing Certified Elevator Mechanic status. ... Hoisting Machine Motor, ... VA 14 21 00 Electric Traction Elevators

08/01/16

14 21 00-37

N. Provide passenger car with single speed center opening horizontal

sliding doors and service car with two-speed side opening horizontal

sliding doors constructed the same as hoistway doors.

O. Provide one set of protective pads for service elevator of sufficient

length to completely cover two sides, rear walls and front return of

cab interior. Pads shall consist of a minimum of 6 mm (.25 in.) thick

glass fiber insulation securely sewn between flame resistant vinyl

coated coverings. Color of the covering shall be approved by the

Resident Engineer. Provide stainless steel pad buttons or hooks, spaced

at intervals of not more than 150 mm (18 in.) to adequately support

pads.

2.47 POWER DOOR OPERATORS: PASSENGER/SERVICE ELEVATORS

A. Provide a high-speed heavy duty door operator to automatically open the

car and hoistway doors simultaneously when the car is level with the

floor, and automatically close the doors simultaneously at the

expiration of the door-open time. Provide microprocessor door control

with circuitry to constantly monitor and automatically adjust door

operation based upon velocity, position, and motor current. Motor shall

be of the high-internal resistance type, capable of withstanding high

currents resulting from stall without damage to door operator/motor.

The door operator shall be capable of opening a car door and hoistway

door simultaneously, at a speed of .762 m (2.5 ft) per second. Closing

speed of the doors shall be .305 m (1 ft) per second. Reversal of

direction of the doors from the closing to opening operation, whether

initiated by obstruction of the infrared curtain or the door "OPEN"

button, shall be accomplished within 38 mm (1.50 in.) maximum of door

movement. Emphasis is placed on obtaining quiet interlock and door

operation; smooth, fast, dynamic braking for door reversals, and

stopping of the doors at extremes of travel.

B. Equip car doors with electric contact that prevents operation of car

until doors are closed unless car is operating in leveling zone or

hoistway access switch is used. Locate door contact to prevent its

being tampered with from inside of car.

C. Car and hoistway doors shall be manually operable in an emergency

without disconnecting the power door operating equipment unless the car

is outside the unlocking zone.

1. It shall not be possible for the doors to open by power unless the

elevator is within the leveling zone.

Page 38: VA 14 21 00 Electric Traction Elevators · be actively pursuing Certified Elevator Mechanic status. ... Hoisting Machine Motor, ... VA 14 21 00 Electric Traction Elevators

08/01/16

14 21 00-38

2. Provide infrared curtain unit. The device shall cause the car and

hoistway doors to reverse automatically to the fully-open position

should the unit be actuated while the doors are closing. Unit shall

function at all times when the doors are not closed, except during

firefighter’s operation.

D. Should the doors be prevented from closing for more than a

predetermined adjustable interval of 15 to 30 seconds by operation of

the curtain unit, the doors shall stay open, the audio voice message

and a buzzer located on the car shall sound only on automatic

operation. Do not provide door nudging.

1. If an obstruction of the doors should not activate the photo-

electric door control device and prevent the doors from closing for

more than a predetermined adjustable interval of 15 to 30 seconds,

the doors shall reverse to the fully open position and remain open

until the “Door Close” button re-establishes the closing cycle.

E. Provide door "OPEN" and "CLOSE" buttons. When the door "OPEN" button is

pressed and held, the doors, if in the open position, shall remain open

and if the doors are closing, they shall stop, reverse and re-open.

Momentary pressure of the door "CLOSE" button shall initiate the

closing of the doors prior to the expiration of the normal door open

time.

SPEC WRITER NOTE: Delete sections 2.48 – 2.54 if freight elevator is not required.

2.48 CORRIDOR OPERATING DEVICES FOR FREIGHT ELEVATORS

A. Provide one riser of landing call buttons located on the door lock

release side of the entrances for each and every freight elevator in

this specification.

B. Fixtures for intermediate landings shall contain "UP" and "DOWN"

buttons. Fixtures for terminal landings shall contain a single "UP" or

"DOWN" button.

C. Each button shall contain an integral registration LED white light

which shall illuminate upon registration of a call and shall extinguish

when that call is answered.

D. The direction of each button shall be legibly and indelibly identified

by arrows not less than 12 mm (.50 in.) high in the face of each

button.

Page 39: VA 14 21 00 Electric Traction Elevators · be actively pursuing Certified Elevator Mechanic status. ... Hoisting Machine Motor, ... VA 14 21 00 Electric Traction Elevators

08/01/16

14 21 00-39

E. Provide in each hall station a momentary pressure door "OPEN" button

and a continuous pressure door "CLOSE" button. These devices shall be

inoperative unless the car is at the respective landing.

2.49 HOISTWAY ENTRANCES: FREIGHT ELEVATOR

A. Entrances at landings of elevator shall be power opened and closed

vertical sliding, bi-parting doors, complete with frames, threshold,

interlocks and accessories. Door panels shall have Underwriter's label

or equal.

B. Door frames shall be structural steel channels rigidly connected to

hoistway with head members reinforced and welded at corners. Extend

side frames full floor height to provide fastenings on inside of

hoistway for door guide tracks.

C. Sills shall be metal plates of non-slip type not less than 9 mm (.375

in.) thick, same width as jamb openings, and securely anchored to floor

construction. Provide structural steel angles as fastenings required

for thresholds.

D. Construct door panels of not less than 11-gauge formed steel plates

welded to frame angles and shaped to develop a maximum strength.

Provide lower edge of upper steel plate panel with fire resistant, non-

shearing, non-crushing resilient member, minimum 50 mm (2 in.)

diameter. Rigid astragal overlapping meeting edge is prohibited.

Provide upper edge of each lower steel plate panel with a metal sill

supported at each side of door opening by adjustable stops and capable

of carrying load equal to capacity of car.

E. Provide each door panel frame with four fixed or adjustable, malleable

iron, mill-grooved, guide shoes not less than 63 mm (2.50 in.).

Securely fasten continuous, steel guide rails to hoistway construction.

F. Connect door panels to each other with adjustable rods and flexible

cable chains, running over double race, ball bearing, malleable iron,

machined sheaves secured to door guide rail. Upper door panel shall

balance the bottom panel.

G. Where pass type doors are required, attach pivoting metal lintel to the

top of upper door panel to close space between door and hoistway wall.

H. Provide upper panel of each door with one vision panel of polished

clear wired glass secured on hoistway side. Area of the vision panel

shall reject a ball 152 mm (6 in.) in diameter.

I. Provide pull straps on inside and outside faces of each manually

operated hoistway door for manual opening and closing.

Page 40: VA 14 21 00 Electric Traction Elevators · be actively pursuing Certified Elevator Mechanic status. ... Hoisting Machine Motor, ... VA 14 21 00 Electric Traction Elevators

08/01/16

14 21 00-40

J. Provide unique car number on every elevator entrance at designated

level, minimum 76mm (3 in.) in height.

2.50 ELECTRIC INTERLOCKS: BI-PARTING HOISTWAY FREIGHT DOORS

A. Equip each hoistway door with interlocks that shall prevent operating

of car until doors are locked in closed position. Interlocks shall

prevent opening of door at landing from corridor side unless car is at

rest at landing, in the leveling zone, or hoistway access switch is

used. Provide tamperproof interlocks and lock both panels of doors

together.

B. Provide retiring cams or other devices for hoistway door interlocks

securely fastened to cars and arranged to operate without objectionable

noise and vibration.

2.51 CAR FRAME: FREIGHT ELEVATOR

A. Car frame shall be constructed of steel plates and structural shapes

securely riveted, bolted, or welded together. No iron casting will be

permitted. The entire assembly shall be rugged construction, and amply

braced to withstand unequal loading of platform. Car frame members

shall be constructed to relieve the car enclosure of all strains.

Balance car front to back and side to side. Provide balancing weights

and frames, properly located, to achieve the required true balance.

2.52 CAR PLATFORM: FREIGHT ELEVATOR

A. Construct car platform of heavy steel frame with stringers, and

substantial wood or steel plate under flooring for Class “C1” loading.

Cover underside and all exposed edges of wood filled platform with

sheet metal of not less than 27-gauge with all exposed joints and edges

folded under. Top flooring shall consist of // first quality tongue-

and-groove maple not less than 19 mm (.75 in.) thick and given 2 coats

of liquid filler // steel or aluminum diamond plate not less than 4.5

mm (.1875 in.) thick //. Provide car entrance with a one piece metal

threshold with non-slip surface.

B. Provide adjustable diagonal brace rods to hold platform firmly within

car suspension frame.

C. Provide a platform guard (toe guard) of not less than 12-guage sheet-

steel on the entrance side, extend 76 mm (3 in.) beyond each side of

entrance jamb. Securely brace platform guard to car platform, and bevel

bottom edge at a 60-75 degree angle from horizontal. Clearance between

front of platform and landing threshold shall not exceed 32 mm (1.25

in.).

Page 41: VA 14 21 00 Electric Traction Elevators · be actively pursuing Certified Elevator Mechanic status. ... Hoisting Machine Motor, ... VA 14 21 00 Electric Traction Elevators

08/01/16

14 21 00-41

D. Isolate the platform from the car frame by approved rubber pads or

other equally effective means.

E. Provide a bonding wire between frame and platform.

2.53 CAR ENCLOSURE: FREIGHT ELEVATOR

A. Car enclosure walls and return panels from entrance columns to side

wall shall be sectional flush panels formed of not less than 12-gauge

steel extending from the floor to underside of ceiling. Enclose the top

with sectional flush steel panels not less than 12-gauge steel. Provide

top of car with hinged emergency exit with a mechanical stop and an

electrical contact that will prevent movement of the elevator when exit

is open. Provide recess for car operating panel.

B. Provide car entrance with power operated // one // two // section wire

mesh vertical sliding gate. Gate shall extend full width of car, and

constructed of not less than 11-gauge wire woven to 38 mm (1.50 in.)

diameter mesh set in reinforced steel frames. Expanded metal of 10-

gauge may be used in lieu of wire mesh.

C. Equip car gate with guide shoes to run on vertical steel guides

securely braced and held in rigid alignment. Connect gate to

counterweights with chains running over ball or roller bearing sheaves

set in iron housings securely fastened to guides. Counterweights shall

equally balance gate. Gate shall not project into hoistway opening when

raised. Equip car gate with electric contact.

D. Provide LED illuminated car lights mounted flush with the inside of the

ceiling. Maintain a minimum light level of 20-foot candles at the

floor.

E. Provide two permanently mounted stainless steel signs inside elevator.

One sign shall bear the Class loading and markings. The other sign

shall bear the legend "THIS IS NOT A PASSENGER ELEVATOR. NO PERSONS

OTHER THAN THE OPERATOR AND FREIGHT HANDLERS ARE PERMITTED TO RIDE ON

THIS ELEVATOR".

F. Provide car top railings.

2.54 POWER DOOR OPERATORS: BI-PARTING FREIGHT DOORS AND CAR GATE

A. Provide door and gate operators with automatic open and // automatic //

button operated // controls close the car and hoistway doors when the

car is level with a floor. Microprocessor door control shall have

circuitry to continuously monitor and automatically adjust door

operation based on velocity, position, and motor current. Motors shall

have high-internal resistance, capable of withstanding high currents

Page 42: VA 14 21 00 Electric Traction Elevators · be actively pursuing Certified Elevator Mechanic status. ... Hoisting Machine Motor, ... VA 14 21 00 Electric Traction Elevators

08/01/16

14 21 00-42

resulting from doors stalling without damage to the motor. Hoistway

doors and car gate shall open automatically when the car reaches floor

level with the landing when a stop is made. Provide a timer to hold the

car gates and hoistway doors open for an adjustable predetermined

period up to 120 seconds.

B. Operating speed for hoistway doors and car gate shall be .305 m (1 ft)

per second during high speed operation.

C. Provide re-opening devices, safety shoe and infrared sensor on the car

gate that shall, in the event the car gates meet an obstruction while

closing, immediately stop and re-open the car gate. Design this device

and adjust it to minimize the possibility of injury to persons by the

gate.

D. The hoistway door shall open two-thirds of its travel before the car

door or gate starts to open. The car gate shall close two-thirds of its

travel before the hoistway door starts to close.

E. Provide encoded speed control, time control or limit switches to

control motors as the doors and gates approach their limits of travel

in the opening and closing directions.

F. Install electric power door operators inside the hoistway rigidly

supported. Mount electric gate operator on the car on rigid framed

supported members.

G. Each door and gate shall be manually operable in an emergency without

disconnecting the power door operating equipment unless the car is

outside the unlocking zone.

PART 3 – EXECUTION

3.1 PREPARATION

A. Examine work of other trades on which the work of this Specification

depends. Report defects to the Resident Engineer in writing that may

affect the work of elevator contractor.

B. Examine elevator hoistway openings for plumb, level, in line, and that

elevator pit is proper size, waterproofed and drained with necessary

access door, and ladder.

C. Examine machine room for proper illumination, heating, ventilation,

electrical equipment, and beams are correctly located complete with

access stairs and door.

D. If the Elevator Contractor requires changes in size or location of

trolley beams or their supports and trap doors, etc., to accomplish

Page 43: VA 14 21 00 Electric Traction Elevators · be actively pursuing Certified Elevator Mechanic status. ... Hoisting Machine Motor, ... VA 14 21 00 Electric Traction Elevators

08/01/16

14 21 00-43

their work, he must make arrangements, subject to approval of the

Contracting officer, and include additional cost in their bid.

E. Work required prior to the completion of the elevator installation:

1. Supply of electric feeder wires to the terminals of the elevator

control panel, including circuit breaker.

2. Provide light and GFCI outlets in the elevator pit and machine room.

3. Furnish electric power for testing and adjusting elevator equipment.

4. Furnish circuit breaker panel in machine room for car and hoistway

lights and receptacles.

5. Supply power for cab lighting and ventilation from an emergency

power panel specified in Division 26, ELECTRICAL.

6. Machine room enclosed and protected from moisture, with self-

closing, self-locking door and access stairs.

7. Provide fire extinguisher in machine room.

F. Provide to General Contractor for installation; inserts, anchors,

bearing plates, brackets, supports and bracing including all setting

templates and diagrams for placement.

3.2 ARRANGEMENT OF EQUIPMENT

A. Arrange equipment in machine room so that major equipment components

can be removed for repair or replacement without dismantling or

removing other equipment in the same machine room. Locate controller

near and visible to its respective hoisting machine.

3.3 WORKMANSHIP, INSTALLATION, AND PROTECTION

A. Installations shall be performed by Certified Elevator Mechanics and

Apprentices to best possible industry standards. Details of the

installation shall be mechanically and electrically correct. Materials

and equipment shall be new and without imperfections.

B. Recesses, cutouts, slots, holes, patching, grouting, refinishing to

accommodate installation of equipment shall be included in the

Contractor's work. All new holes in concrete shall be core drilled.

C. Structural members shall not be cut or altered. Work in place that is

damaged or defaced shall be restored equal to original new condition.

D. Finished work shall be straight, plumb, level, and square with smooth

surfaces and lines. All machinery and equipment shall be protected

against dirt, water, or mechanical injury. At final completion, all

work shall be thoroughly cleaned and delivered in perfect unblemished

condition.

Page 44: VA 14 21 00 Electric Traction Elevators · be actively pursuing Certified Elevator Mechanic status. ... Hoisting Machine Motor, ... VA 14 21 00 Electric Traction Elevators

08/01/16

14 21 00-44

E. Sleeves for conduit and other small holes shall project 50 mm (2 in.)

above concrete slabs.

F. Hoist cables that are exposed to accidental contact in the machine room

and pit shall be completely enclosed with 16-gauge sheet metal or

expanded metal guards.

G. Exposed gears, sprockets, and sheaves shall be guarded from accidental

contact.

3.4 CLEANING

A. Upon completion of installation and prior to final inspection, all

equipment shall be thoroughly cleaned of grease, oil, cement, plaster,

dust, and other debris.

B. Clean machine room and equipment.

C. Perform hoistway clean down.

D. Prior to final acceptance remove protective coverings from finished or

ornamental surfaces. Clean and polish surfaces with regard to type of

material.

3.5 PAINTING AND FINISHING

A. All equipment, except specified as architectural finish, shall be

painted one coat of approved color, conforming to manufacturer's

standard.

B. Hoist machine, motor, shall be factory painted with manufacturer's

standard finish and color.

C. Controller, sheave, car frame and platform, counterweight, beams, rails

and buffers except their machined surfaces, cams, brackets and all

other uncoated ferrous metal items shall be painted one factory primer

coat or approved equal.

D. Stencil or apply decal floor designations not less than 100 mm (4 in.)

high on hoistway doors, fascia or walls within door restrictor areas.

The color of paint used shall contrast with the color of the surfaces

to which it is applied.

E. Elevator hoisting machine, controller, governor, main line shunt trip

circuit breaker, safety plank, and cross head of car shall be

identified by 100 mm (4 in.) high numerals and letters located as

directed. Numerals shall contrast with surrounding color and shall be

stenciled or decaled.

F. Hoistway Entrances of Passenger, and Service Elevators:

Page 45: VA 14 21 00 Electric Traction Elevators · be actively pursuing Certified Elevator Mechanic status. ... Hoisting Machine Motor, ... VA 14 21 00 Electric Traction Elevators

08/01/16

14 21 00-45

1. Door panels shall be given rust resistant treatment and a factory

finish of one coat of baked-on primer and one factory finish coat of

baked-on enamel.

2. Fascia plates, top and bottom shear guards, dust covers, hanger

covers, and other metalwork, including built-in or hidden work and

structural metal, (except stainless steel entrance frames and

surfaces to receive baked enamel finish) shall be given one approved

prime coat in the shop, and one field coat of paint of approved

color.

G. Hoistway Entrances of Freight Elevators:

1. Metal surfaces of doors and frames shall receive shop prime coat.

2. Finish painting, after installation, shall be one coat of paint of

approved color.

H. Elevator Cabs for Passenger and Service Elevators:

1. Interior and exterior steel surfaces shall be given rust resistant

treatment before finish is applied.

2. Interior steel surfaces shall be factory finished with one coat of

paint of approved color.

3. Give exterior faces of car doors one finish coat of paint of

approved color.

I. Elevator Cabs for Freight Elevators:

1. Give interior of cab one prime coat and a minimum of one coat of

paint of approved color.

2. Give exterior of cab one prime coat and one finish coat of paint of

approved color.

3. All surfaces of door frames, door panels, and cab interior surfaces

that become damaged or marred shall be restored to original

condition before final acceptance of work.

3.6 PRE-TESTS AND TESTS

A. Pre-test the elevators and related equipment in the presence of the

Resident Engineer or his authorized representative for proper operation

before requesting final inspection. Conduct final inspection at other

than normal working hours, if required by Resident Engineer.

1. Procedure outlined in the Inspectors Manual for Electric Elevators,

ASME A17.2 shall apply.

a. Final test shall be conducted in the presence of and witnessed by

a third party ASME QEI-1 Certified Elevator Inspector, contracted

by the VA.

Page 46: VA 14 21 00 Electric Traction Elevators · be actively pursuing Certified Elevator Mechanic status. ... Hoisting Machine Motor, ... VA 14 21 00 Electric Traction Elevators

08/01/16

14 21 00-46

b. Government shall furnish electric power including necessary

current for starting, testing, and operating machinery of each

elevator.

2. Contractor shall furnish the following test instruments and

materials on-site and at the designated time of inspection: properly

marked certified test weights, voltmeter, amp probe, thermometers,

direct reading tachometer, megohm meter, vibration meter, sound

meter, light meter, stop watch, and a means of two-way

communication.

B. Inspect workmanship, equipment furnished, and installation for

compliance with specification.

C. Balance Tests: The percent of counterbalance shall be checked by

placing test weights in car until the car and counterweight are equal

in weight when located at the mid-point of travel. If the actual

percent of counter balance does not conform to the specification, the

amount of counterweight shall be adjusted until conformance is reached.

D. Full-Load Run Test: Elevator shall be tested for a period of one hour

continuous run with full contract load in the car. The test run shall

consist of the elevator stopping at every floor, in either direction of

travel, for not less than five or more than ten seconds per floor.

E. Speed Test: The actual speed of the elevator shall be determined in

both directions of travel with full contract load and no load in the

elevator. Speed shall be determined by applying a certified tachometer

to the car hoisting ropes or governor rope. The actual measured speed

of the elevator with all loads in either direction shall be within

three (3) percent of specified rated speed. Full speed runs shall be

quiet and free from vibration and sway.

F. Temperature Rise Test: The temperature rise of the hoisting motor shall

be determined during the full load test run. Temperatures shall be

measured by the use of thermometers. Under these conditions, the

temperature rise of the equipment shall not exceed 50 degrees

Centigrade above ambient temperature. Test shall start when all machine

room equipment is within five (5) degrees Centigrade of the ambient

temperature. Other tests for heat runs on motors shall be performed as

prescribed by the Institute of Electrical and Electronic Engineers.

G. Car Leveling Test: Elevator car leveling devices shall be tested for

accuracy of leveling at all floors with no load in car and with

contract load in car, in both directions of travel. Accuracy of floor

Page 47: VA 14 21 00 Electric Traction Elevators · be actively pursuing Certified Elevator Mechanic status. ... Hoisting Machine Motor, ... VA 14 21 00 Electric Traction Elevators

08/01/16

14 21 00-47

level shall be within plus or minus 3 mm (.125 in.) of level with

landing floor for which the stop has been initiated regardless of load

in car or direction of travel. The car leveling device shall

automatically correct over travel as well as under travel and shall

maintain the car floor within plus or minus 3 mm (.125 in.) of level

with the landing floor regardless of change in load.

H. Brake Test: The action of the brake shall be prompt and a smooth stop

shall result in the up and down directions of travel with no load and

rated load in the elevator. Down stopping shall be tested with 125

percent of rated load in the elevator.

I. Insulation Resistance Test: The elevator's complete wiring system shall

be free from short circuits and ground faults and the insulation

resistance of the system shall be determined by use of megohm meter, at

the discretion of the Elevator Inspector conducting the test.

J. Safety Devices: Car and counterweight safety devices shall be tested.

K. Overload Devices: Test all overload current protection devices in the

system at final inspection.

L. Limit Stops:

1. The position of the car when stopped by each of the normal limit

switches with no load and with contract load in the car shall be

accurately measured.

2. Final position of the elevator relative to the terminal landings

shall be determined when the elevator has been stopped by the final

limits. The lower limit stop shall be made with contract load in the

elevator. Elevator shall be operated at inspection speed for both

tests. Normal limit stopping devices shall be inoperative for the

tests.

M. Oil Buffer Tests: These tests shall be conducted with operating device

and limit stops inoperative and with contract load in the elevator for

the car buffer and with no load in the elevator for the counterweight

buffer. Preliminary test shall be made at the lowest (leveling) speed.

Final tests shall be conducted at contract speed. Buffers shall

compress and return to the fully extended position without oil leakage.

N. Operating and Signal System: The elevator shall be operated by the

operating devices provided and the operation signals and automatic

floor leveling shall function in accordance with requirements

specified. Starting, stopping and leveling shall be smooth and

comfortable without appreciable steps of acceleration or deceleration.

Page 48: VA 14 21 00 Electric Traction Elevators · be actively pursuing Certified Elevator Mechanic status. ... Hoisting Machine Motor, ... VA 14 21 00 Electric Traction Elevators

08/01/16

14 21 00-48

O. Performance of the Elevator supervisory system shall be witnessed and

approved by the elevator inspector and a representative of the Resident

Engineer.

P. If equipment fails test requirements and a re-inspection is required,

the Contractor shall be responsible for the cost of re-inspection;

salaries, transportation expenses, and per-diem expenses incurred by

the elevator inspector and representative of the Resident Engineer.

3.7 INSTRUCTION OF VA PERSONNEL

A. Provide competent instruction to VA personnel regarding the operation

of equipment and accessories installed under this contract, for a

period equal to one eight hour day. Instruction shall commence after

completion of all work and at the time and place directed by the

Resident Engineer.

B. Written instructions in triplicate relative to care, adjustments and

operation of all equipment and accessories shall be furnished and

delivered to the Resident Engineer in independently bound folders. DVD

recordings will also be acceptable. Written instructions shall include

correct and legible wiring diagrams, nomenclature sheet of all

electrical apparatus including location of each device, complete and

comprehensive sequence of operation, complete replacement parts list of

with descriptive literature, and identification and diagrams of

equipment and parts. Information shall also include electrical

operation characteristics of all circuits, relays, timers, electronic

devices, and related characteristics for all rotating equipment.

C. Provide supplementary instruction for any new equipment that may become

necessary because of changes, modifications or replacement of equipment

or operation under requirements of paragraph entitled "Warranty of

Construction".

3.8 INSPECTION AND MAINTENANCE SERVICE: GUARANTEE PERIOD OF SERVICE

A. Furnish complete inspection and maintenance service on entire elevator

installation for a period of one (1) year after completion and

acceptance of all the elevators in this specification by the Resident

Engineer. This maintenance service shall run concurrently with the

warranty. Maintenance work shall be performed by Certified Elevator

Mechanics and Apprentices.

B. This contract will cover full maintenance including emergency call back

service, inspections, and servicing the elevators listed in the

Page 49: VA 14 21 00 Electric Traction Elevators · be actively pursuing Certified Elevator Mechanic status. ... Hoisting Machine Motor, ... VA 14 21 00 Electric Traction Elevators

08/01/16

14 21 00-49

schedule of elevators. The Elevator Contractor shall perform the

following:

1. Bi-weekly systematic examination of equipment.

2. During each maintenance visit the Elevator Contractor shall clean,

lubricate, adjust, repair and replace all parts as necessary to keep

the equipment in like new condition and proper working order.

3. Furnishing all lubricant, cleaning materials, parts and tools

necessary to perform the work required. Lubricants shall be only

those products recommended by the manufacturer of the equipment.

4. Equalizing tension, shorten or renew hoisting ropes.

5. As required, motors, controllers, selectors, leveling devices,

operating devices, switches on cars and in hoistways, hoistway doors

and car doors or gate operating device, interlock contacts, guide

shoes, guide rails, car door sills, hangers for doors, car doors or

gates, signal system, car safety device, governors, tension sheaves,

and buffers shall be cleaned, lubricated and adjusted.

6. Guide rails, overhead sheaves and beams, counterweight frames, and

bottom of platforms shall be cleaned every three months. Car tops

and machine room floors shall be cleaned monthly. Accumulated

rubbish shall be removed from the pits monthly. A general cleaning

of the entire installation including all machine room equipment and

hoistway equipment shall be accomplished quarterly. Cleaning

supplies and vacuum cleaner shall be furnished by the Contractor.

7. Maintain the performance standards set forth in this specification.

8. The operational system shall be maintained to the standards

specified hereinafter including any changes or adjustments required

to meet varying conditions of hospital occupancy.

9. Maintain smooth starting and stopping and accurate leveling at all

times.

C. Maintenance service shall not include the performance of work required

as a result of improper use, accidents, and negligence for which the

Elevator Contractor is not directly responsible.

D. Provide 24 hour emergency call-back service that shall consist of

promptly responding to calls within two hours for emergency service

should a shutdown or emergency develop between regular examinations.

Overtime emergency call-back service shall be limited to minor

adjustments and repairs required to protect the immediate safety of

persons and equipment in and about the elevator.

Page 50: VA 14 21 00 Electric Traction Elevators · be actively pursuing Certified Elevator Mechanic status. ... Hoisting Machine Motor, ... VA 14 21 00 Electric Traction Elevators

08/01/16

14 21 00-50

E. Service and emergency personnel shall report to the Resident Engineer

or his authorized representative upon arrival at the hospital and again

upon completion of the required work. A copy of the work ticket

containing a complete description of the work performed shall be given

to the Resident Engineer or his authorized representative.

F. The Elevator Contractor shall maintain a log book in the machine room.

The log shall list the date and time of all weekly examinations and all

trouble calls. Each trouble call shall be fully described including the

nature of the call, necessary correction performed or parts replaced.

G. Written “Maintenance Control Program” shall be in place to maintain the

equipment in compliance with ASME A17.1.

Spec Writer Note: Remove all spec writer notes including this one.

- - - E N D - - -