Inverter Control-Vacon driven by Profibus
ELECTRICAL AND AUTOMATION DEPARTMENT
ADDRESS: Wolffintie 30, 65200 VAASA PHONE:EMAIL: [email protected] MOBILE PHONE: +358 40 5818831URL: www.puv.fi FAX: +358 6 326 3065
2
06.11.2012
Table of contents1 General information of the exercise............................................................................................ 32 Devices used in the exercise....................................................................................................... 43 Profibus communication between the drive and the control system............................................5
3.1 Fieldbuses and drives......................................................................................................... 53.2 Profibus and drives............................................................................................................. 53.3 Hardware Configuration - Making the PLC aware of the drive........................................103.4 Profibus parameters in Vacon........................................................................................... 133.5 Testing the communication between the PLC and the drive..............................................153.6 Using analog input and output in PLC for frequency reference and actual value..............193.7 Dedicated Drive function block in the PLC......................................................................20
ELECTRICAL AND AUTOMATION DEPARTMENT
ADDRESS: Wolffintie 30, 65200 VAASA PHONE:EMAIL: [email protected] MOBILE PHONE: +358 40 5818831URL: www.puv.fi FAX: +358 6 326 3065
3
06.11.20121 General information of the exercise
The aim of this exercise is to give an idea, how inverters are controlled in systems. The steps in the exercise are:
1. Profibus communication between the drive and the control systemo How to apply the Profidrive-profile ja GSD-fileo Adding the frequency converter to PLC’s hardware configurationo How to verify the communication with PLC’s programming toolo Familiarize to profidrive state machine
2. How the control system handles the frequency controller as a componento A simple Drive-function block in the PLCo A simplified drive control application in a PLC using Profibus
communication
2 The Preliminary Exercises
2.1 Orientation
Read this document through and if necessary also the following: .Your should get a general idea, what you are about to do in this exercise.
ELECTRICAL AND AUTOMATION DEPARTMENT
ADDRESS: Wolffintie 30, 65200 VAASA PHONE:EMAIL: [email protected] MOBILE PHONE: +358 40 5818831URL: www.puv.fi FAX: +358 6 326 3065
4
06.11.2012
3 Devices used in the exercise
The training arrangements for the exercises are shown in fig. 1 and fig 2.
Fig.1. Training arrangements
Devices used in these exercises:Frequency converter: Use cases number 8 and 9,
Vacon NXP , Software package NXP 2V170Option Board Vacon OPTC5Motor Internal motor in the demo case
PLC: Siemens S7-300, Use case number 9Step 7 V5.4, Use laptop number 3.
Use the yellow cable between Laptop and Vacon. You should find the cable in EP2-area hanging at the cable tray.
Use the snipping-tool through the whole exercise to take the snapshots for documenting the exercise (foe ex. parametrization, programming and the testing results).
Use the following S7-application as the basis for this exercise.
ELECTRICAL AND AUTOMATION DEPARTMENT
ADDRESS: Wolffintie 30, 65200 VAASA PHONE:EMAIL: [email protected] MOBILE PHONE: +358 40 5818831URL: www.puv.fi FAX: +358 6 326 3065
S7-300 PLC with Profibus
Profibus
Programminginterface Ethernet
Programminginterface NCDrive RS232
I/O-Panel
5
06.11.2012
4 Profibus communication between the drive and the control system –The laboratory Exercise
4.1 Fieldbuses and drives
In industrial applications there is always a subordinate control system commanding the drives.
There are two interface possibilities between the drive and the control system – I/O and Fieldbus.
Today the fieldbus is the standard choice, because it has merely only advantages: The control system has the fieldbus interface as a standard No extra I/O cards (digital or analog) are needed at the control system or drive end – HW
savings No complicated wiring between the control system and the drive – Cabling and reliability
savings All control and supervisory information is accessible through the bus, but no through I/O –
Operational and service savings
In these exercises we use Profibus as our example for fieldbus.
4.2 Profibus and drives
Normal communication standards define strictly the communication. They enable data transfer between the devices, but do not say anything about the application. This means:
o Bits and bytes are transferred but meaning of them is not defined. o Every drive is unique from controller’s point of view o The behaviour of the drive and meaning of the exchanged data has to be defined individually
for each case.
This is why filed busses have an extra definition at application level called – Profile.This profile targeted to drives applications is called Profidrive – When profibus is used
The Profibus communication works with Master – Slave principle. o The Controller issues a command with Control Datao The Slave responses immediately with Status Data
ELECTRICAL AND AUTOMATION DEPARTMENT
ADDRESS: Wolffintie 30, 65200 VAASA PHONE:EMAIL: [email protected] MOBILE PHONE: +358 40 5818831URL: www.puv.fi FAX: +358 6 326 3065
6
06.11.2012
Fig.3. Master – Slave communication
The profile defines 5 different Control / Status –data pairs. Each pair carries a slightly different data.
The simplest of them is type number 3 called PPO3. It carries:
Command:o CW, Control Word – 2 bytes, 16 bitso REF, Reference – Frequency reference – 2 bytes, 16 bits
Response:o SW, Status Word – 2 bytes, 16 bitso ACT, Actual,– Actual Frequency – 2 bytes, 16 bits
Fig.4. Message structure in PPO3 mode
In the standard the Frequency Reference and Actual value are scaled:o -10 000 – 10 000 = - FreqMaxLimit - FreqMaxLimit
ELECTRICAL AND AUTOMATION DEPARTMENT
ADDRESS: Wolffintie 30, 65200 VAASA PHONE:EMAIL: [email protected] MOBILE PHONE: +358 40 5818831URL: www.puv.fi FAX: +358 6 326 3065
Control Data
Status DataResponse
Command
ControllerDrive
SW ACT
Controller
CW REF
Drive
7
06.11.2012The standard defines the meaning of the Control Word bits:
Fig.5. Control Word content
On the left side of the figure is presented the bits in the Control Word, when the drive is to be started. The bits form value 047F in Hex-form.
The standard defines the meaning of the Status Word bits:
Fig.6. Status Word content
On the left side of the figure is presented the bits in the Status Word, when the drive have started and reached the reference frequency. The bits form value 3337 in Hex-form.ELECTRICAL AND AUTOMATION DEPARTMENT
ADDRESS: Wolffintie 30, 65200 VAASA PHONE:EMAIL: [email protected] MOBILE PHONE: +358 40 5818831URL: www.puv.fi FAX: +358 6 326 3065
Low
Hig0
Con
trol W
ord
1
1
1
1
1
1
1
0
0
0
1
0
0
0
010
8
06.11.2012
The names of the Control Word bits describe themselves. In order to get the exact meaning of the Status Word bits the State Machine has to be investigated, but this is beyond of this exercise.
Fig.7. The State machine of the Profidrive frequency converter
ELECTRICAL AND AUTOMATION DEPARTMENT
ADDRESS: Wolffintie 30, 65200 VAASA PHONE:EMAIL: [email protected] MOBILE PHONE: +358 40 5818831URL: www.puv.fi FAX: +358 6 326 3065
9
06.11.2012
There were altogether 5 different messaging types. They are presented below in the short form.
Fig.8. Profibus messaging types
o Those two messages Control and Response are shown in the figure as one - The Message length to and from drive are equal, but with different content – see PPO3 for example. Each “box” represents one byte.
o With parameter Field – Id, Ind, Value –an individual parameter can be changed or checked. This gives the same functionality as parameter setting from the panel.
o Eight different Process Data values can be set and measured. The meanings of the PD-values are selected in the drive.
In these exercises we use type PPO3 messaging.
ELECTRICAL AND AUTOMATION DEPARTMENT
ADDRESS: Wolffintie 30, 65200 VAASA PHONE:EMAIL: [email protected] MOBILE PHONE: +358 40 5818831URL: www.puv.fi FAX: +358 6 326 3065
10
06.11.2012
4.3 Hardware Configuration - Making the PLC aware of the drive
Remark! take a screen snapshots during the exercise whenever reasonable!The application in the PLC is a piece of software. In order to interact with the physical world it needs to know the interface with the surrounding hardware. This is done with the hardware configuration.
Below is shown a typical hardware configuration of the PLC -system used in this exercise. It may vary depending on the PLC unit which is in use.
Fig.9. HW-configuration
There is a CPU with a Profibus master capability. There is also I/O-cards: Digital Input , Digital Output, Analog Input and Analog Output. One of each type. Remark that there are defined the interface addresses, where the PLC program reads and writes. For example Analog Input bytes 288…291.
Check the default parameter values of the Profibus-master:
Network address: __________
Transmission rate: __________
ELECTRICAL AND AUTOMATION DEPARTMENT
ADDRESS: Wolffintie 30, 65200 VAASA PHONE:EMAIL: [email protected] MOBILE PHONE: +358 40 5818831URL: www.puv.fi FAX: +358 6 326 3065
11
06.11.2012
Open the HW-catalogue to see the Vacon options: (If this option does not exist in the catalogue, ask your teacher to make it available)
How is it possible that in the Siemens HW-catalogue there exists Vacon NX?________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________
Add the Vacon drive to be a node on the Profibus fieldbus – Drag the Vacon NX to the bus as shown below.
Give a node address for the Vacon drive – use number 3.
ELECTRICAL AND AUTOMATION DEPARTMENT
ADDRESS: Wolffintie 30, 65200 VAASA PHONE:EMAIL: [email protected] MOBILE PHONE: +358 40 5818831URL: www.puv.fi FAX: +358 6 326 3065
12
06.11.2012
Define the messaging type to be used – here PPO3.
Drag the type to the row number 0 as shown below:
Save the configuration on the Hard disk and download to the PLC.
How the PLC application will reach the drive?Incoming data packets: ______________________________________Outgoing data packets: ______________________________________
Is there difference, how the PLC sees the drive data and the I/O-data? (Based on, what you see in the HW-configuration)_________ (Yes/No)
Fill in the addresses on the lines below.
Fig.10. How the PLC application reaches the drive
ELECTRICAL AND AUTOMATION DEPARTMENT
ADDRESS: Wolffintie 30, 65200 VAASA PHONE:EMAIL: [email protected] MOBILE PHONE: +358 40 5818831URL: www.puv.fi FAX: +358 6 326 3065
Controller
CW:________ REF:_______
Drive
SW:________ REF:_______
13
06.11.2012
4.4 Profibus parameters in Vacon
Define the parameters for the Profibus option board, based on the previously done PLC-configuration.
Fig.11. Profibus parameters in Vacon
Slave Address: ______________Baud Rate: ______________PPO Type: ______________Operate Mode: ______________
Do this part using the Panel:Monitor the fieldbus communication from the Drive panel before and after setting the parameters you defined above. Option Boards OPTC5 Monitor Profibus Status
Check the fieldbus status led on the PLC as well.
Please set the parameters on the Drive.Option Boards OPTC5 Parameters
Now monitor the filedbus status from the panel and led on the PLC.
The result? What is the actual meaning of the increasing bus monitor value on the panel?________________________________________________________________________________________________________________________________________________________
From now on you use the NCDrive for parameterization and signal monitoring. You can ask a short introduction to NCDrive from your teacher if necessary.
Set the control place to Fieldbus.
ELECTRICAL AND AUTOMATION DEPARTMENT
ADDRESS: Wolffintie 30, 65200 VAASA PHONE:EMAIL: [email protected] MOBILE PHONE: +358 40 5818831URL: www.puv.fi FAX: +358 6 326 3065
14
06.11.2012
4.5 Testing the communication between the PLC and the drive
In this exercise we will test, how the PLC operates with the drive.
We make the PLC inputs and outputs to be our human interface:o Each input switch defines a bit in the Control Wordo Each output led corresponds a status bit in the Status Word
Fig.12. The data content in the messages
The necessary PLC-program is shown below. Use M97.0 for “EN_BIT_MOVE”
Fig.13. I/O mapped directly to Vacon messages
ELECTRICAL AND AUTOMATION DEPARTMENT
ADDRESS: Wolffintie 30, 65200 VAASA PHONE:EMAIL: [email protected] MOBILE PHONE: +358 40 5818831URL: www.puv.fi FAX: +358 6 326 3065
QB5 QB 4SW ACT
Controller
IB1 IB0CW REF
Drive
15
06.11.2012Make and download the above shown testing program.
Open the Monitor window, where you can adjust the parameters in the PLC-program:
Activate the testing program by setting "EN_BIT_MOVE" = True.
Take the operating window in the NC Drive program to see the status of the drive (Stop / Running).If the operating window is not available – use the panel on the freq. converter instead.
Define below: How you will set the input switches, in order to start the drive - 0 or 1.7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0
Try to start the drive.
The result:Status of the drive___________________ (Run / Stop)
Status of the leds on the PLC7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0
Is the status what you expected it to be?ELECTRICAL AND AUTOMATION DEPARTMENT
ADDRESS: Wolffintie 30, 65200 VAASA PHONE:EMAIL: [email protected] MOBILE PHONE: +358 40 5818831URL: www.puv.fi FAX: +358 6 326 3065
16
06.11.2012________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________
Now the drive should be running, but the frequency reference is zero.What parameter in the PLC-monitor window defines the frequency reference?What value at that parameter gives 25 Hz frequency reference?
Parameter: _________________25 Hz value _________________
Set the drive first to 25 HZ and then 50 Hz at the reversing direction.
ELECTRICAL AND AUTOMATION DEPARTMENT
ADDRESS: Wolffintie 30, 65200 VAASA PHONE:EMAIL: [email protected] MOBILE PHONE: +358 40 5818831URL: www.puv.fi FAX: +358 6 326 3065
17
06.11.2012
4.6 Using analog input and output in PLC for frequency reference and actual value
We add to our human interface a feature:o Frequency Reference is read from the potentiometer on the PLCo Actual Frequency is shown on the mA meter on the PLC
The corresponding PLC program:
Fig.14. Reference from AI, Actual value from AO
Add the blocks above into the program. Do not forget to set the scaling in DB98 and DB99 at the proper values. Add M97.1 (EN_AI_AO ) to the pin named EN.
Activate this feature by setting "EN_AI_AO" = True at PLC monitoring window:
Adjust the Frequency Reference using the potentiometer on the PLC. Compare the frequency reference and actual values in PLC and Drive at monitoring window.
ELECTRICAL AND AUTOMATION DEPARTMENT
ADDRESS: Wolffintie 30, 65200 VAASA PHONE:EMAIL: [email protected] MOBILE PHONE: +358 40 5818831URL: www.puv.fi FAX: +358 6 326 3065
18
06.11.2012Comments:________________________________________________________________________________________________________________________________________________________
4.7 Dedicated Drive function block in the PLC
Now you have acquired knowledge about the technology, how Drives are interfaced to Control Systems.
In the previous exercise we were manipulating the direct HW-interface. Seen from application it is not very describing.
o It is better to connect all addresses into one block (Control and Status words, Reference and Actual values).
o At the same time the individual bits can be given meaningful names. o Also the unnecessary complexity can be hided.
This is why the Drive is shown as one function block in the application – see below.
Fig.15. “Drive” function block
ELECTRICAL AND AUTOMATION DEPARTMENT
ADDRESS: Wolffintie 30, 65200 VAASA PHONE:EMAIL: [email protected] MOBILE PHONE: +358 40 5818831URL: www.puv.fi FAX: +358 6 326 3065
19
06.11.2012
Add the block into your program. Try now the Drive Function Block with Vacon NX:Enable the feature in the PLC by setting:
o M97.2, "EN_BIT_MOVE" = Falseo M97.1, "EN_AI_AO" = Trueo M97.2, "EN_DRIVE_BLOCK" = True
o Set the inputs to proper valueso Adjust the frequency reference using the potentiometer on the PLC
Comments:____________________________________________________________________________________________________________________________________________________________________________________________________________________________________
Now you have knowledge, how industrial Drives are controlled. Based on this knowledge, make another Drive by following these steps:
o Connect the Fieldbus cable between the drive and PLC
o Set the Profibus option board parameters in the Driveo Messaging type – PPO3o Define the node number on the Fieldbus
o Set the Control Place to Fieldbus in the Drive
o Add another drive to PLC HW-configurationo Drag and dropo Define the node number on the Fieldbuso Select messaging type – PPO3o Save and download
o Add another drive to application programo Drag and drop a new Function Blocko Give name Pump2o Connect I/O
ELECTRICAL AND AUTOMATION DEPARTMENT
ADDRESS: Wolffintie 30, 65200 VAASA PHONE:EMAIL: [email protected] MOBILE PHONE: +358 40 5818831URL: www.puv.fi FAX: +358 6 326 3065
20
06.11.2012o Connect AI to Frequency Reference
Scale the reference in the AI Data Blocko Save and download
When completed the steps above, test the Drive.
Comments:____________________________________________________________________________________________________________________________________________________________________________________________________________________________________
o
Fig.16. How to make a Drive applicationELECTRICAL AND AUTOMATION DEPARTMENT
ADDRESS: Wolffintie 30, 65200 VAASA PHONE:EMAIL: [email protected] MOBILE PHONE: +358 40 5818831URL: www.puv.fi FAX: +358 6 326 3065
21
06.11.2012
4.8 Speed Profile
Make the speed profile, which is decribed below. Make the profile execution to start from input I1.6.Set the maximum frequency in inverter to 100 Hz. Then the reference range -10 000 - + 10 000 corresponds frequency range -100 Hz - +100 Hz
ELECTRICAL AND AUTOMATION DEPARTMENT
ADDRESS: Wolffintie 30, 65200 VAASA PHONE:EMAIL: [email protected] MOBILE PHONE: +358 40 5818831URL: www.puv.fi FAX: +358 6 326 3065
22
06.11.2012
5 The Post Exercises
5.1 Documenting
Document the made exercises in chapter 3:1. Present the answers to the questions in chapter 32. Add the screen snapshots to your document presenting the results
5.2 Answer the following questions
o Answer with your own words, what good is in the Profidrive-profile.o How the communication bus cable should be grounded? o What is the output frequency, when the reference is set to be 10 via the bus