Series 3730 Type 3730-2 Electropneumatic Positioner Mounting and Operating Instructions EB 8384-2 EN (1300-1611) Firmware version 1.56 Edition February 2015 Fig. 1 · Type 3730-2 EB + CD

Upload: jose-libreros

Post on 12-Jul-2016

16 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Val Vu La Caldera

Series 3730Type 3730-2 Electropneumatic Positioner

Mounting andOperating Instructions

EB 8384-2 EN (1300-1611)Firmware version 1.56

Edition February 2015

Fig. 1 · Type 3730-2

EB + CD

Page 2: Val Vu La Caldera

2 EB 8384-2 EN

DANGER!indicates a hazardous situation which, if notavoided, will result in death or serious injury.

WARNING!indicates a hazardous situation which, if notavoided, could result in death or serious in-jury.

NOTICEindicates a property damage message.

Note: Supplementary explanations,information and tips

Definitions of the signal words used in these instructions

Page 3: Val Vu La Caldera

Contents Page

1 Important safety instructions . . . . . . . . . . . . . . . . . . . . . . 7

2 Article code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

3 Design and principle of operation. . . . . . . . . . . . . . . . . . . . 93.1 Additional equipment . . . . . . . . . . . . . . . . . . . . . . . . . 103.2 Configuration using TROVIS-VIEW software . . . . . . . . . . . . . . 113.3 Technical data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

4 Attachment to the control valve – Mounting parts and accessories . . . 184.1 Direct attachment . . . . . . . . . . . . . . . . . . . . . . . . . . . 204.1.1 Type 3277-5 Actuator . . . . . . . . . . . . . . . . . . . . . . . . . 204.1.2 Type 3277 Actuator . . . . . . . . . . . . . . . . . . . . . . . . . . 224.2 Attachment according to IEC 60534-6 (NAMUR) . . . . . . . . . . . . 244.3 Attachment according to VDI/VDE 3847 . . . . . . . . . . . . . . . . 264.4 Attachment to Type 3510 Micro-flow Valve. . . . . . . . . . . . . . . 324.5 Attachment to rotary actuators . . . . . . . . . . . . . . . . . . . . . 344.5.1 Heavy-duty version . . . . . . . . . . . . . . . . . . . . . . . . . . 364.6 Reversing amplifier for double-acting actuators . . . . . . . . . . . . . 384.6.1 Reversing amplifier (1079-1118 or 1079-1119) . . . . . . . . . . . . 384.7 Attaching an external position sensor. . . . . . . . . . . . . . . . . . 404.7.1 Mounting the position sensor with direct attachment. . . . . . . . . . . 404.7.2 Mounting the position sensor with attachment according to IEC 60534-6 424.7.3 Mounting the position sensor to Type 3510 Micro-flow Valve . . . . . . 434.7.4 Mounting the position sensor to rotary actuators . . . . . . . . . . . . 444.8 Mounting the leakage sensor. . . . . . . . . . . . . . . . . . . . . . 454.9 Attaching positioners with stainless steel housings . . . . . . . . . . . . 464.10 Air purging function for single-acting actuators . . . . . . . . . . . . . 464.11 Mounting parts and accessories . . . . . . . . . . . . . . . . . . . . 47

5 Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 525.1 Pneumatic connections . . . . . . . . . . . . . . . . . . . . . . . . . 525.1.1 Signal pressure gauges . . . . . . . . . . . . . . . . . . . . . . . . 525.1.2 Supply pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . 525.1.3 Signal pressure (output) . . . . . . . . . . . . . . . . . . . . . . . . 535.2 Electrical connections . . . . . . . . . . . . . . . . . . . . . . . . . 535.2.1 Switching amplifiers . . . . . . . . . . . . . . . . . . . . . . . . . . 55

6 Operator controls and readings . . . . . . . . . . . . . . . . . . . . 566.1 Serial interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57

EB 8384-2 EN 3

Contents

Page 4: Val Vu La Caldera

7 Start-up – Settings. . . . . . . . . . . . . . . . . . . . . . . . . . . 597.1 Defining the valve closed position . . . . . . . . . . . . . . . . . . . 597.2 Setting the volume restriction Q . . . . . . . . . . . . . . . . . . . . 607.3 Adapting the display. . . . . . . . . . . . . . . . . . . . . . . . . . 607.4 Limiting the signal pressure. . . . . . . . . . . . . . . . . . . . . . . 617.5 Checking the operating range of the positioner . . . . . . . . . . . . . 617.6 Initialization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 627.6.1 MAX – Initialization based on maximum range . . . . . . . . . . . . . 647.6.2 NOM – Initialization based on nominal range . . . . . . . . . . . . . 657.6.3 MAN – Initialization based on a manually selected range . . . . . . . . 667.6.4 SUb substitute calibration . . . . . . . . . . . . . . . . . . . . . . . 677.7 Zero calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . 707.8 Reset to default values . . . . . . . . . . . . . . . . . . . . . . . . . 71

8 Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 728.1 Enabling and selecting parameters . . . . . . . . . . . . . . . . . . 728.2 Operating modes . . . . . . . . . . . . . . . . . . . . . . . . . . . 738.2.1 Automatic and manual modes . . . . . . . . . . . . . . . . . . . . . 738.2.2 Fail-safe position (SAFE) . . . . . . . . . . . . . . . . . . . . . . . . 748.3 Malfunction/maintenance alarm . . . . . . . . . . . . . . . . . . . . 748.3.1 Confirming error messages . . . . . . . . . . . . . . . . . . . . . . 75

9 Adjusting the limit switch . . . . . . . . . . . . . . . . . . . . . . . 769.1 Retrofitting an inductive limit switch. . . . . . . . . . . . . . . . . . . 77

10 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79

11 Servicing explosion-protected devices . . . . . . . . . . . . . . . . . 79

12 Firmware update (serial interface) . . . . . . . . . . . . . . . . . . . 79

13 Maintenance, calibration and work on equipment . . . . . . . . . . . 80

14 Code list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81

15 Dimensions in mm . . . . . . . . . . . . . . . . . . . . . . . . . . 10015.1 Fixing levels according to VDI/VDE 3845 (September 2010) . . . . . 103

16 Valve characteristic selection . . . . . . . . . . . . . . . . . . . . . 104

4 EB 8384-2 EN

Contents

Note: The functions of EXPERTplus valve diagnostics are described in the Mounting and Op-erating Instructions EB 8389 EN

Page 5: Val Vu La Caldera

EB 8384-2 EN 5

Modifications of positioner firmware

Modifications of positioner firmware in comparison to previous versions

Previous New

1.01 1.10

The serial interface and serial interface adapter allow the positioner to be operatedand configured using TROVIS-VIEW software

The following additional status messages were implemented:Code 76 - No emergency modeCode 77 - Program loading errorDisplays number of zero calibrations performed since the last initialization.

For initialization of "AIR TO CLOSE" actuators, the direction of action (Code 7) is auto-matically set to increasing/decreasing.

Code 3, the activation period of the enabled configuration function wasextended to 120 s.

1.10 1.20

Electronics changed, no new functions added.

1.20 1.30

New EXPERTplus diagnostics functions (Code 48) addedPositioner in EXPERTplus version with extended diagnostics features.

A running initialization can be canceled by pressing the rotary pushbutton.

The position transmitter (Code 37) and solenoid valve (Code 45) options are automati-cally recognized.

1.30 1.40

All EXPERTplus functions can be used in this firmware version and higher.

The fault alarm contact is triggered by the condensed state of the positioner. It is al-ways active when condensed state = “Maintenance alarm”.

If Code 32 is set to Yes: Also active with “Function check” condensed stateIf Code 33 is set to Yes: Also active with “Maintenance required/Maintenance de-manded” condensed state

The “Function check” condensed state is additionally set for Test A1, A2, fault alarmoutput and position transmitter.

The min./max. values of the temperature monitoring can be reset.

1.40 1.41

Internal modifications

1.41 1.42

Internal modifications

Page 6: Val Vu La Caldera

EB 8384-2 EN 6

Modifications of positioner firmware

Modifications of positioner firmware in comparison to previous versions

Previous New

1.42 1.51

All EXPERTplus diagnostic functions are available in the positioner without having toactivate them first (refer to EB 8389 EN on EXPERTplus valve diagnostics)

Optional binary input with following actions:

– Transfer switching state

– Set local operation write protection

– Switch between AUTO/MAN

– Various diagnositic functions (refer to EB 8389 EN on EXPERTplus valve diagnostics)

The pressure limit (Code 16) is no longer automatically set during initialization.

1.51 1.54

Internal modifications

1.54 1.55

Code 4: The setting for 300 mm has been added to the pin position

1.55 1.56

Internal modifications

Page 7: Val Vu La Caldera

1 Important safety instructions

For your own safety, follow these instructions concerning the mounting, start-up and opera-tion of the positioner:

4 The positioner is to be mounted, started up or operated only by trained andexperienced personnel familiar with the product.According to these Mounting and Operating Instructions, trained personnel refers toindividuals who are able to judge the work they are assigned to and recognizepossible dangers due to their specialized training, their knowledge and experience aswell as their knowledge of the applicable standards.

4 Explosion-protected versions of this positioner are to be operated only by personnelwho have undergone special training or instructions or who are authorized to workon explosion-protected devices in hazardous areas. Refer to section 11.

4 Any hazards that could be caused by the process medium, the operating pressure, thesignal pressure or by moving parts of the control valve are to be prevented by meansof the appropriate measures.

4 If inadmissible motions or forces are produced in the pneumatic actuator as a result ofthe supply pressure, the supply pressure must be restricted by means of a suitablesupply pressure reducing station.

To avoid damage to any equipment, the following also applies:

4 Do not operate the positioner with the back of the positioner/vent opening facingupwards.The vent opening must not be sealed when the positioner is installed on site.

4 Proper shipping and appropriate storage are assumed.

4 Do not ground electric welding equipment near to the positioner.

Note: The device with a CE marking fulfills the requirements of the Directives 94/9/EC and2004/108/EC.The Declaration of Conformity is available on request.

EB 8384-2 EN 7

Important safety instructions

Vent opening

Page 8: Val Vu La Caldera

2 Article code

Article code

Article code Type 3730-2 x x x x x x x x 0 x 0 0 x 0 x x

With LC display, autotune

Explosion protection

Without 0

ATEX: II 2G Ex ia IIC T6 Gb; II 2D Ex tb IIIC T80°C Db IP66 1

CSA: Ex ia IIC T6, Class I Zone 0; Class I, Groups A, B, C, D;Class II, Groups E, F, G; Class III; Type 4 EnclosureClass I, Zone 2; Class I, Div. 2, Groups A, B, C, D;Class II, Div. 2, Groups E, F, G; Class III; Type 4 Enclosure

FM: Class I, Zone 0 AEx ia IIC; Class I,II,III, Div.1, Groups A, B, C, D, E, F, G;Class I, Div.2, Groups A, B, C, D; Class II, Div.2, Groups F, G

3

JIS: Ex ia IIC T6 7

ATEX: II 3G Ex nA II T6; II 3D Ex ic IIC T6; II 3D Ex tc IIIC T80°C IP66 8

Options (additional equipment)

Inductive limit switch Without

With SJ2-SN (NC contact)

With SJ2-S1N (NO contact)

0

1

2

0

Solenoid valve Without

24 V DC

0

4

Analog position transmitter WithoutWith

0

1

External position sensor WithoutWithConnection prepared

00

012

Leakage sensor WithoutWith

01

Binary input WithoutWith 0

02

Diagnostics

EXPERTplus 4

Housing material

Aluminum 0

Stainless steel 1.4581 0 1

Special applications

Without 0

Compatible with paint 1

Exhaust air with ¼ NPT connection, back of housing sealed 2

Attachment according to VDI/VDE 3847 including interface 6

Attachment according to VDI/VDE 3847 prepared for interface 7

Special versions

Without 0 0

IECEx:Ex ia IIC T4/T5/T6; IP54 and IP65 T80°C 1 1 2

GOST (EAC): 1Ex ia IIC T6/T5/T4 Gb X; Ex tb IIIC T 80°C Db X 1 1 4

GOST (EAC): 2Ex nA IIC T6/T5/T4 Gc X; 2Ex ic IIC T6/T5/T4 Gc X;Ex tc IIIC T 80°C Dc X

8 2 0

Page 9: Val Vu La Caldera

3 Design and principle ofoperation

The electropneumatic positioner is attachedto pneumatic control valves. It is used to as-sign the valve stem position (controlled vari-able x) to the control signal (reference vari-able w). The input signal received from acontrol system is compared to the travel orrotational angle of the control valve, and apneumatic signal pressure (output variabley) is produced.

The positioner basically consists of an elec-trical travel sensor system (2), an analog i/pconverter (6) with downstream air capacity

booster (7) and the electronic unit with amicrocontroller (5).

The standard positioner is fitted with threebinary contacts: A fault alarm output indi-cates a fault to a control station and twoconfigurable software limit switches areused to indicate the end positions of thevalve.

The position of the valve is transmitted aslinear travel motion or angle of rotation viapick-up lever and travel sensor (2) to an an-alog PD controller (3). Simultaneously, anA/D converter (4) transmits the position ofthe valve to the microcontroller (5). The PDcontroller compares this actual position to

EB 8384-2 EN 9

Design and principle of operation

w

x

Q

%S

mm

GG

PD

Serial Interface

162013

15

A2

A3

A1

112

4 195

3

12

6

7

8

10

1

14

14

w

xy

24V DC

9

17 18

22BE

Fig. 2 · Functional diagram

1 Control valve2 Travel sensor3 PD controller4 A/D converter5 Microcontroller6 i/p converter7 Air capacity booster8 Pressure regulator9 Flow regulator10 Volume restriction11* Inductive limit switch12* Solenoid valve13* Analog position transmitter14 Software limit switches

Alarm 1/215 Fault alarm output

Alarm 316 Display17* Solenoid valve control18* Galvanic isolation19 D/A converter20 Communication interface22 Binary input BE** Optional

Page 10: Val Vu La Caldera

the 4 to 20 mA DC control signal (referencevariable) after it has been converted by theA/D converter (4). In case of a system devi-ation, the actuator is either vented or filledwith more air. The supply air is supplied tothe air capacity booster (7) and the pressureregulator (8). An intermediate flow regulator(9) with fixed settings is used to purge thepositioner and also guarantees trouble-freeoperation of the air capacity booster. Theoutput signal pressure supplied by thebooster can be limited over the software.The volume restriction Q (10) is used to opti-mize the positioner by adapting it to the ac-tuator size.

The extended EXPERTplus diagnostics are in-tegrated into the positioner. It provides infor-mation on the positioner and generates di-agnostic and status alarms, which allowfaults to be pinpointed quickly.

The positioner is suitable for the followingtypes of attachment using the correspondingaccessories:

4 Direct attachment to SAMSONType 3277 Actuator: Section 4.1

4 Attachment to actuators acc. toIEC 60534-6 (NAMUR): Section 4.2

4 Attachment to Type 3510 Micro-flowValve: Section 4.4

4 Attachment to rotary actuators acc. toVDI/VDE 3845: Section 4.5

3.1 Additional equipment

Solenoid valve

If the operating voltage for the solenoidvalve (12) fails, the supply pressure for thebooster is vented to the atmosphere. Conse-quently, the actuator is vented and the valvemoves to the fail-safe position.

NOTICEIn manual mode (MAN), the manual setpoint is also reset to 0 %. A different manualset point must be entered again (Code 1).

Position transmitter

The position transmitter (13) is a two-wiretransmitter and issues the travel sensor sig-nal as a 4 to 20 mA signal processed by themicrocontroller. Since this signal is issued in-dependent of the positioner’s input signal(min. current 3.8 mA), the actual travel/an-gle of rotation is controlled in real-time. Ad-ditionally, the position transmitter providesthe possibility of signaling a positioner faultover a signal current of < 2.4 mA or> 21.6 mA.

Inductive limit switch

The rotary shaft of the positioner carries anadjustable tag which actuates the installedproximity switch. The optional inductive limitswitch (11) is connected to A1, while theremaining software limit switch is connectedto A2.

10 EB 8384-2 EN

Design and principle of operation

Page 11: Val Vu La Caldera

External position sensor

In this version, only the sensor is mounted tothe control valve. The positioner is locatedseparately from the valve.The connection of x and y signals to thevalve is established by cable and piping forair (only without inductive limit switch).

Leakage sensor

By upgrading the positioner with a leakagesensor, it is possible to detect seat leakagewhen the valve is in the closed position.

Binary input

The positioner has an optional binary input.The following actions can be performed overthe binary input:

4 Transfer switching state [default]The switching state of the binary input islogged.

4 Set local operation write protectionSettings cannot be changed at thepositioner while the binary input is ac-tive. The configuration enabled functionin Code 3 is not active.

4 Switch between AUTO/MANThe positioner changes from automaticmode (AUTO) mode into manualmode (MAN) and vice versa.No action is started if the positioner is inthe fail-safe position (SAFE).

4 Various diagnostic functions (refer toEB 8389 on EXPERTplus valve diagnos-tics)

Note: The optional binary input can only beconfigured using the TROVIS-VIEW software(refer to EB 8389 on EXPERTplus valve diag-nostics).The default switching state is with an openswitch.

3.2 Configuration usingTROVIS-VIEW software

Refer to Table 6 on page 50 for order num-bers.

The positioner can be configured using theTROVIS-VIEW software.The positioner is equipped for this purposewith an additional digital SERIAL INTERFACEto allow a computer to be connected over anadapter cable from the RS-232 or USB portof the computer to the positioner.The TROVIS-VIEW software enables the userto easily set parameters in the positionerand view process parameters online.

Note: The TROVIS-VIEW software is a com-mon operator interface for various smartSAMSON devices. The software togetherwith a device-specific module allow the con-figuration and parameterization of the de-vice.The device-specific module for Type 3730-2can be downloaded free of charge from theSAMSON website (Services > Software >TROVIS-VIEW).Additional information on TROVIS-VIEW(e.g. system requirements) can found on theSAMSON website and in the Data SheetT 6661.

EB 8384-2 EN 11

Design and principle of operation

Page 12: Val Vu La Caldera

3.3 Technical data

12 EB 8384-2 EN

Design and principle of operation

Type 3730-2 Positioner (the listed technical data of explosion-protected devices may be restricted by the limitsspecified in the test certificate)

Travel, adjustable

Direct attachment to Type 3277 Actuator: 3.6 to 30 mmAttachment acc. to IEC 60534-6-1: 3.6 to 300 mmAttachment acc. to VDI/VDE 3847: 3.6 to 300 mmRotary actuators: 24° to 100°

Travel rangeAdjustable within the initialized travel/angle of rotation;travel can be restricted to 1

5 at the maximum

Reference variable wSignal range 4 to 20 mA, 2-wire unit, reverse polarity protection,min. span 4 mA, static destruction limit 100 mA

Minimum current 3.6 mA for display · 3.8 mA for operation

Load impedanceVersion without explosion protection: ≤ 6 V (corresponding to 300 Ω at 20 mA)Explosion-protected version: ≤ 7 V (corresponding to 350 Ω at 20 mA)

Supply air

Supply pressure from 1.4 to 7 bar (20 to 105 psi),Air quality acc. to ISO 8573-1 (2001): Max. particle size and density: Class 4Oil content: Class 3, pressure dew point: Class 3 or at least 10 K beneath the low-est ambient temperature to be expected

Signal pressure (output)0 bar up to the capacity of supply pressure, limitable to 1.4/2.4/3.7 ±0.2 bar viasoftware

Characteristic

Linear/equal percentage/reverse equal percentageuser-definable (over operating software)butterfly valve, rotary plug valve, segmented ball valve: linear/equal percentageDeviation from terminal-based conformity ≤ 1 %

Hysteresis ≤ 0.3 %

Sensitivity ≤ 0.1 %

Transit time Venting and filling with air adjustable separately up to 240 seconds by software

Direction of action Reversible

Air consumption, steady state Independent from supply pressure approx. 110 ln/h

Air output capacityActuator filled with airActuator vented

At ∆p = 6 bar: 8.5 mn3/h, at ∆p = 1.4 bar: 3.0 mn

3/h KVmax (20 °C) = 0.09at ∆p = 6 bar: 14.0 mn

3/h, at ∆p = 1.4 bar: 4.5 mn3/h KVmax (20 °C) = 0.15

Permissible ambienttemperature

–20 to +80 °C in all versions–45 to +80 °C with metal cable gland–25 to +80 °C with inductive limit switches (SJ2-S1N) and metal cable glandThe listed technical data of explosion-protected devices may be restricted by thetemperatures specified in the test certificate

InfluencesTemperature: ≤ 0.15 %/10 K Supply air: NoneVibration: ≤ 0.25 % up to 2000 Hz and 4 g acc. to IEC 770

Page 13: Val Vu La Caldera

EB 8384-2 EN 13

Design and principle of operation

Type 3730-2 Positioner (the listed technical data of explosion-protected devices may be restricted by the limitsspecified in the test certificate)

Electrical connectionsOne M20 x 1.5 cable gland for 6 to 12 mm clamping range · Additionalsecond M20 x 1.5 threaded hole · Screw terminals for 0.2 to 2.5 mm² wirecross-section

Degree of protection IP 66/NEMA 4X

Use in safety-instrumented systems(SIL)

Emergency venting at 0 mA setpoint and on using the optional so-lenoid valve

Observing the requirements of IEC 61508, the systematic capability of thecontrol valve for emergency venting as a component in safety-instrumentedsystems is given.

Use is possible on observing the requirements of IEC 61511 and the re-quired hardware fault tolerance in safety-instrumented systems up to SIL 2(single device/HFT = 0) and SIL 3 (redundant configuration/HFT = 1).

Explosion protection See table on summary of explosion protection certificates for Type 3730-2

Communication (local) SAMSON SSP interface and serial interface adapter

Software requirements TROVIS-VIEW with database module 3730-2

Binary contacts

For connection to

- Binary input of a PLC acc. to IEC 61131-2,Pmax = 400 mW

- NAMUR switching amplifiers acc. to EN60947-5-6

NAMUR switchingamplifiers acc. toEN 60947-5-6

2 software limit switches, reverse polarity protection, floating, configurable switching characteristics,default settings as per table

Signal status:

No response:

Response:

Without explosion protection:

Non-conductingConductive (R = 348 Ω )

Exp.-protected version:

≤ 1.0 mA

≥ 2.2 mA

One fault alarm contact, floating

Signal status:

No response/No alarm

Response/Fault alarm

Without explosion protection:

Conductive (R = 348 Ω)Non-conducting

Exp.-protected version:

≥ 2.2 mA

≤ 1.0 mA

Page 14: Val Vu La Caldera

14 EB 8384-2 EN

Design and principle of operation

Type 3730-2 Positioner (the listed technical data of explosion-protected devices may be restricted by the limitsspecified in the test certificate)

Materials

HousingDie-cast aluminum EN AC-AlSi12(Fe) (EN AC-44300) acc. to DIN EN 1706,chromated and powder paint coated · Special version: Stainless steel 1.4581

External parts Stainless steel 1.4571 and 1.4301

Cable gland M20x1.5, black polyamide

Weight Approx. 1.0 kg

Compliance·

Options for Type 3730-2 Positioner

Solenoid valve · Approval acc. to IEC 61508/SIL

Input

24 V DC reverse polarity protection, static destruction limit 40 V;

Current consumption I =U 5.7 V

3840

−Ω

(corresponding to 4.8 mA at 24 V/114 mW)

Signal "0" no pick-up ≤ 12 V (emergency venting at 0 V)

Signal "1" safe pick-up > 19 V

Service life > 5 x 106 switching cycles

KV coefficient 0.15

Leakage sensor · Suitable for operation in hazardous areas

Temperature range –40 to +130 °C

Tightening torque 20 ±5 Nm

Analog position transmitter Temperature range

Supply voltage Tightening torque

Output signal 4 to 20 mA

Direction of action Reversible

Operating range –10 to +114 %

Characteristic Linear

Hysteresis andHF influence

Same as positioner

Other influences Same as positioner

Fault indication Can be issued with current signal 2.4 ±0.1 mA or 21.6 ±0.1 mA

Inductive limit switch For connection to switching amplifier acc. to EN 60947-5-6.Can be used in combination with a software limit switch.

SJ2-SN proximity switch NAMUR NC contact

SJ2-S1N proximity switch NAMUR NO contact

Page 15: Val Vu La Caldera

EB 8384-2 EN 15

Design and principle of operation

External position sensor

Travel Same as positioner

Cable10 m with M12x1 connector, designed for continuous flexing, flame retardantacc. to VDE 0472, resistant to oils, lubricants, coolants as well as other corrosivemedia

Permissible ambient temperature–60 to +105 °C · Limits specified in the EC Type Examination Certificate addi-tionally apply for explosion-protected devices.

Vibration immunity Up to 10 g in the range between 10 and 2000 Hz

Degree of protection IP 67

Binary input · Galvanically isolated · Switching behavior configured over software (e.g. TROVIS-VIEW, DTM)

Active switching behavior (default setting)

Connection For external switch (floating contact) or relay contacts

Electrical dataOpen-circuit voltage when contact is open: max. 10 V,pulsed DC current, peak value 100 mA and RMS value of 0.01 mA when contactis closed

ContactClosed, R < 20 Ω “On” switching state (default setting)

Open, R > 400 Ω “Off” switching state (default setting)

Passive switching behavior

Connection For externally applied DC voltage, reverse polarity protection

Electrical data 3 to 30 V, destruction limit 40 V, current draw 3.7 mA at 24 V

Voltage> 6 V “On” switching state (default setting)

< 1 V “Off” switching state (default setting)

Page 16: Val Vu La Caldera

Summary of explosion protection certificates for Type 3730-2

Type3730 Certification Type of protection/comments

-2Number

Date

IECEx PTB 05.0007

2005-02-21

Ex ia IIC T4/T5/T6

IP54 and IP65 T80°C

-2 STCCNumber

Valid until

972

2017-10-01

0Ex ia IIC T6X

2Ex s II T6 X

-21EC-type

examination

certificate

Number

Date PTB 00 ATEX 2158

2013-08-19

II 2G Ex ia IIC T6 Gb

II 2D Ex tb IIIC T80°C Db IP66

-21 CCoE

Number

Date

Valid until

A/P/HQ/MH/104/1339

2012-01-27

2017-01-27

Ex ia IIC T6

-21

Number

Date

Valid until

RU C-DE.08.B000697

2014-12-15

2019-12-14

1Ex ia IIC T6/T5/T4 Gb X

Ex tb IIIC T 80°C Db X

-21 INMETRO On request

-21 KCS

Number

Date

Valid until

11-KB4BO-0214

2011-10-24

2016-10-24

Ex ia IIC T6/T5/T4

-21

Number

Datum

Valid until

GYJ14.1286

2014-11-05

2019-11-04

Ex ia IIC T4...T6 Gb

-23Number

Date

1330129

2009-02-19

Ex ia IIC T6, Class I Zone 0;Class I, Groups A, B, C, D; Class II, Groups E, F, G;Class III; Type 4 Enclosure

Class I, Zone 2; Class I, Div. 2, Groups A, B, C, D;Class II, Div. 2, Groups E, F, G; Class III;Type 4 Enclosure

-23Number

Date

3012394

2011-08-11

Class I, Zone 0 AEx ia IIC;Class I,II,III, Div.1, Groups A, B, C, D, E, F, G;

Class I, Div.2, Groups A, B, C, D;Class II, Div.2, Groups F, G

-27 JISNumber

Valid until

TC18159

2016-11-25Ex ia IIC T6

-28EC-type

examination

certificate

Number

Valid until

PTB 03 ATEX 2116 X

2008-11-06

II 3G Ex nA II T6

II 3D Ex ic IIC T6

II 3D Ex tc IIIC T80°C IP66

16 EB 8384-2 EN

Design and principle of operation

Page 17: Val Vu La Caldera

Type3730 Certification Type of protection/comments

-28

Number

Date

Valid until

RU-C-DE.08.B.00697

2014-12-15

2019-12-14

2Ex nA IIC T6/T5/T4 Gc X

2Ex ic IIC T6/T5/T4 Gc X

Ex tc IIIC T 80°C Dc X

-28 INMETRO On request

-28

Number

Date

Valid until

GYJ14.1287X

2014-11-05

2019-11-04

Ex ic IIC T4...T6 Gc

Ex nA IIC T4...T6 Gc

EB 8384-2 EN 17

Design and principle of operation

Page 18: Val Vu La Caldera

4 Attachment to the controlvalve – Mounting parts andaccessories

WARNING!Attach the positioner, keeping the followingsequence:1. Mount the positioner on the control valve2. Connect the supply air3. Connect the electrical power4. Perform the start-up settings

The positioner is suitable for the followingtypes of attachment:

4 Direct attachment to SAMSONType 3277 Actuator

4 Attachment to actuators according toIEC 60534-6 (NAMUR)

4 Attachment to Type 3510 Micro-flowValve

4 Attachment to rotary actuators

NOTICEAttach the positioner to the control valve,observing the following instructions to avoiddamaging the positioner.– Use only the mounting parts/accessories

listed in the Tables 1 to 7 (pages 47 to51) to mount the positioner. Observe thetype of attachment!

– Observe the assignment between leverand pin position (see travel tables onpage 19).

Lever and pin position

The positioner is adapted to the actuatorand to the rated travel by the lever on theback of the positioner and the pin insertedinto the lever.

The travel tables on page 19 show the maxi-mum adjustment range at the positioner. Thetravel that can be implemented at the valveis additionally restricted by the selectedfail-safe position and the required compres-sion of the actuator springs.

The positioner is standard equipped with thelever M (pin position 35).

Note: If the standard mounted lever M (pinposition 35) is replaced, the newly mountedlever must be moved once all the way as faras it will go in both directions to adapt it tothe internal measuring lever.

18 EB 8384-2 EN

Attachment to the control valve – Mounting parts and accessories

Fig. 3 · Lever M with pin position 35

Page 19: Val Vu La Caldera

EB 8384-2 EN 19

Attachment to the control valve – Mounting parts and accessories

Travel tables

Note: The lever M is included in the scope of delivery.Levers S, L, XL for attachment according to IEC 60534-6 (NAMUR) are available as acces-sories (see Table 3 on page 49).

Direct attachment to Type 3277-5 and Type 3277 Actuators

Actuator size Rated travel Adjustment range at positioner 1) Requiredlever

Assignedpin position[cm²] [mm] Min. Travel Max.

120 7.5 5.0 to 25.0 M 25

120/175/240/350 15 7.0 to 35.0 M 35

355/700/750 30 10.0 to 50.0 M 50

Attachment according to IEC 60534-6 (NAMUR)

SAMSON valves/Type 3271 Actuator Adjustment range at positioner 1)

Other valves/actuators Requiredlever

Assignedpin position

Actuator size Rated travel

[cm²] [mm] min. Travel max.

60 and 120 withType 3510 Valve

7.5 3.6 to 18.0 S 17

120 7.5 5.0 to 25.0 M 25

120/175/240/350 157.0 to 35.0 M 35

700/750 7.5

355/700/750 15 and 30 10.0 to 50.0 M 50

1000/1400/2800 30 14.0 to 70.0 L 70

1000/1400/2800 60 20.0 to 100.0 L 100

1400/2800 120 40.0 to 200.0 XL 200

Attachment to rotary actuators according to VDI/VDE 3845

Rotary actuators Requiredlever

Assignedpin positionMin. Opening angle Max.

24 to 100° M 90°

1) The min./max. adjustment range is based on the NOM (nominal range) initialization mode

Page 20: Val Vu La Caldera

4.1 Direct attachment

4.1.1 Type 3277-5 Actuator

Refer to Table 1 on page 47 for the requiredmounting parts as well as the accessories.Note the travel table on page 19.

Actuator with 120 cm²

Depending on the type of positioner attach-ment, the signal pressure is routed either leftor right of the yoke through a bore to theactuator diaphragm. Depending on thefail-safe action of the actuator "Actuatorstem extends" or "Actuator stem retracts"(valve closes or opens if the supply air fails),the switchover plate (9) must first be at-tached to the actuator yoke. Align theswitchover plate with the correspondingsymbol for left or right attachment accordingto the marking (view looking onto theswitchover plate).

1. Mount connecting plate (6) or pressuregauge bracket (7) with pressure gaugesonto the positioner, making sure bothseal rings (6.1) are seated properly.

2. Remove screw plug (4) on the back ofthe positioner and close the signal pres-sure output "Output 38" on the connect-ing plate (6) or on the pressure gaugebracket (7) with the stopper (5) includedin the accessories.

3. Place follower clamp (3) on the actuatorstem, align and screw tight so that themounting screw is located in the grooveof the actuator stem.

4. Mount cover plate (10) with narrow sideof the cut-out opening (Fig. 4, left) point-ing towards the signal pressure connec-

tion. Make sure that the bonded gasket(14) points towards the actuator yoke.

5. 15 mm travel: Keep the follower pin (2)at lever M (1) on the back of thepositioner in the pin position 35 (deliv-ered state).7.5 mm travel: Remove the follower pin(2) from the pin position 35, reposition itin the bore for pin position 25 andscrew tight.

6. Insert formed seal (15) into the groove ofthe positioner housing and the seal ring(10.1) on the back of the housing.

7. Place positioner on the cover plate (10)in such a manner that the follower pin(2) rests on the top of the follower clamp(3). Adjust the lever (1) correspondinglyand open the positioner cover to holdthe positioner shaft in position at the capor the switch (Fig. 23).The lever (1) must rest on the followerclamp with spring force.Mount the positioner on the cover plate(10) using the two fixing screws.

Note for all types of attachment except fordirect attachment to Type 3277-5: The sig-nal pressure output at the back must besealed using the screw plug (4, order no.0180-1254) and the associated O-ring (or-der no. 0520-0412).

8. Mount cover (11) on the other side.Make sure that the vent plug pointsdownwards when the control valve is in-stalled to allow any condensed waterthat collects to drain off.

20 EB 8384-2 EN

Attachment to the control valve – Mounting parts and accessories

Page 21: Val Vu La Caldera

EB 8384-2 EN 21

Attachment to the control valve – Mounting parts and accessories

9 11

Supply 9 Output 38

56

4

7

6

10 10.1

3

2

1

15

6.1

1.1 1.2

14

8

Fig. 4 · Direct attachment - Signal pressure connection for Type 3277-5 Actuator with 120 cm²

Switchover plate (9) 1 Lever1.1 Nut1.2 Disk spring2 Follower pin3 Follower clamp4 Screw plug5 Stopper6 Connecting plate6.1 Seal rings7 Pressure gauge bracket8 Press. gauge mounting kit9 Switchover plate

for actuator10 Cover plate10.1 Seal ring11 Cover14 Gasket15 Formed seal

Cut-out of coverplate

Note:Always use the connecting plate (6)included in the accessories to connectsupply and output.Never screw threaded parts directlyinto the housing.

Symbols

Actuator stemextends

Attachment left Attachment right

Actuator stemretracts

Signal pressureinput for right

attachmentMarking

Signal pressureinput for leftattachment

Lever M

Page 22: Val Vu La Caldera

4.1.2 Type 3277 Actuator

Refer to Table 2 on page 48 or the requiredmounting parts as well as the accessories.Note the travel table on page 19.

Actuators with 175 to 750 cm²

Mount the positioner on the yoke as shownin Fig 5). The signal pressure is routed to theactuator over the connection block (12), foractuators with fail-safe action "Actuatorstem extends" internally through a bore inthe valve yoke and for "Actuator stem re-tracts" through external piping.

1. Place follower clamp (3) on the actuatorstem, align and screw tight so that themounting screw is located in the grooveof the actuator stem.

2. Mount cover plate (10) with narrow sideof the cut-out opening (Fig. 5, on the left)pointing towards the signal pressureconnection. Make sure that the bondedgasket (14) points towards the actuatoryoke.

3. For actuators with 355, 700 and750 cm², remove the follower pin (2) atlever M (1) on the back of the positionerfrom pin position 35, reposition it in thebore for pin position 50 and screw tight.For actuators 175, 240 and 350 cm²with 15 mm travel, the follower pin (2)remains in pin position 35.

4. Insert formed seal (15) in the groove ofthe positioner casing.

5. Place positioner on the cover plate insuch a manner that the follower pin (2)rests on the top of the follower clamp(3). Adjust the lever (1) correspondingly

and open the positioner cover to holdthe positioner shaft in position at the capor the switch (Fig. 24). The lever (1) mustrest on the follower clamp with springforce. Mount the positioner on the coverplate (10) using the two fixing screws.

6. Make sure that the tip of the gasket (16)projecting from the side of the connec-tion block (12) is positioned above theactuator symbol that corresponds withthe actuator with fail-safe action "Actua-tor stem extends" or "Actuator stem re-tracts." If necessary, remove the threefixing screws and the cover. Then reposi-tion the gasket (16) turned by 180°. Theprevious version of the connection block(Fig. 5, bottom) requires the switch plate(13) to be turned such that the corre-sponding actuator symbol points to themarking.

7. Place the connection block (12) with theassociated seal rings against thepositioner and the actuator yoke. Screwit tight using the fixing screw (12.1). Foractuators with fail-safe action "Actuatorstem retracts", additionally remove thestopper (12.2) and fit on the externalsignal pressure piping.

8. Mount cover (11) on the other side.Make sure that the vent plug pointsdownwards when the control valve is in-stalled to allow any condensed waterthat collects to drain off.

22 EB 8384-2 EN

Attachment to the control valve – Mounting parts and accessories

Page 23: Val Vu La Caldera

EB 8384-2 EN 23

Attachment to the control valve – Mounting parts and accessories

2

10 1415

1 2 3 11 11.1

SUPPLY

13

B

C

1.1 1.2

12

12.1

12

12.2

12.11216

16 16

12.2SUPPLY

Ansicht A

Ansicht B

Ansicht C

SUPPLY

G

G 3

/8

A

Fig. 5 · Direct attachment – Signal pressure connection for Type 3277 Actuator with 175 to 750 cm²

1 Lever1.1 Nut1.2 Disk spring2 Follower pin3 Follower clamp10 Cover plate11 Cover11.1 Vent plug

12 Connection block12.1 Screw12.2 Stopper or connection for

external piping13 Switch plate14 Gasket15 Formed seal16 Gasket

Lever M

Cut-out ofcover plate (10)

Connection block (old)with switch plate (13)

Stem retracts

Stem extends

Marking

View A

View C

View B

Actuator stemretracts extends

Page 24: Val Vu La Caldera

4.2 Attachment according toIEC 60534-6 (NAMUR)

Refer to Table 3 on page 49 for the requiredmounting parts as well as the accessories.Note the travel table on page 19.

The positioner is attached to the controlvalve with a NAMUR bracket (10).

1. Screw the two bolts (14) to the bracket(9.1) of the stem connector (9), place thefollower plate (3) on top and use thescrews (14.1) to tighten.Actuator size 2800 cm² and 1400 cm²(120 mm travel):– For a travel of 60 mm or smaller,

screw the longer follower plate (3.1)directly to the stem connector (9).

– For a travel exceeding 60 mm,mount the bracket (16) first and thenthe follower plate (3) to the brackettogether with the bolts (14) andscrews (14.1).

2. Mount NAMUR bracket (10) to the con-trol valve as follows:– For attachment to the NAMUR rib,

use an M8 screw (11), washer, andtoothed lock washer directly in theyoke bore.

– For attachment to valves withrod-type yokes, use two U-bolts (15)around the yoke.Align the NAMUR bracket (10) insuch a way that the slot of the fol-lower plate (3) is centrally alignedwith the NAMUR bracket at midvalve travel.

3. Mount connecting plate (6) or pressuregauge bracket (7) with pressure gauges(8) on the positioner, making sure bothseal rings (6.1) are seated properly.

4. Select required lever size (1) M, L or XLand pin position according to the actua-tor size and valve travels listed in the ta-ble on page 19.Should you require a pin position otherthan position 35 with the standard in-stalled lever M, or require a lever size Lor XL, proceed as follows:

5. Screw the follower pin (2) in the as-signed lever bore (pin position) as listedin the table. Only use the longer followerpin (2) included in the mounting kit.

6. Place lever (1) on the positioner shaftand screw tight using the disk spring(1.2) and nut (1.1).

Note: If you have mounted a new lever (1),you must move it once all the way as far asit will go in both directions.

7. Place positioner on the NAMUR bracketin such a manner that the follower pin(2) rests in the slot of the follower plate(3, 3.1). Adjust the lever (1) correspond-ingly.Screw the positioner to the NAMURbracket using both its fixing screws.

24 EB 8384-2 EN

Attachment to the control valve – Mounting parts and accessories

Page 25: Val Vu La Caldera

EB 8384-2 EN 25

Attachment to the control valve – Mounting parts and accessories

10

11

1

1 14.1

3

3.1

16

15

14

1

1.2

1.1

2

9.1

9

6.1 6 7 8

Fig. 6 · Attachment according to IEC 60534-6 (NAMUR)

1 Lever1.1 Nut1.2 Disk spring2 Follower pin3 Follower plate3.1 Follower plate6 Connecting plate6.1 Seal rings7 Pressure gauge bracket8 Pressure gauge

mounting kit9 Stem connector9.1 Bracket10 NAMUR bracket11 Screw14 Bolt14.1 Screw15 U-bolt16 Bracket

Lever L or XL

Additional bracketfor actuators with2800 cm2 travel ≥ 60 mm

Attachment to rod-type yokeRod diameter 20 to 35 mm

Attachment toNAMUR rib

Note: Always use the connecting plate (6) included in the accessories toconnect supply and output. Never screw threaded parts directly into the housing.

Page 26: Val Vu La Caldera

4.3 Attachment according toVDI/VDE 3847

Type 3730-2xxxxxxxx0x0060xx andType 3730-2xxxxxxxx0x0070xx Positionerswith optional air purging of the actuator'sspring chamber can be attached according toVDI/VDE 3847.

Type 3730-2xxxxxxxx0x0000xx Positionerwithout optional air purging of the actuator'sspring chamber can be attached according toVDI/VDE 3847.

This type of attachment allows thepositioners to be replaced quickly while theprocess is running by blocking the air in theactuator.

The signal pressure can be blocked in theactuator by unscrewing the red retainingscrew (20) and then turning the air blocker(19) on the bottom of the adapter block.

Attachment to Type 3277 Actuator (seeFig. 7)

Refer to Table 4 on page 49 for the requiredmounting parts as well as the accessories.

Mount the positioner on the yoke as shownin Fig. 7. The signal pressure is routed to theactuator over the connecting plate (12), foractuators with fail-safe action "actuator stemextends" internally through a bore in thevalve yoke and for "actuator stem retracts"through external piping.

Only the Y1 port is required for positionerattachment. The Y2 port can be used for airpurging of the spring chamber.

1. Place follower clamp (3) on the actuatorstem, align and screw tight so that themounting screw is located in the grooveof the actuator stem.

2. Place the adapter bracket (6) on thepositioner and mount using the screws(6.1). Make sure that the seals are cor-rectly seated. For positioners with airpurging, remove the stopper (5) beforemounting the positioner.For positioners without air purging, re-place the screw plug (4) with a vent plug.

3. For actuators with 355/700/750 cm²,remove the follower pin (2) at lever M(1) on the back of the positioner frompin position 35, reposition it in the borefor pin position 50 and screw tight.For actuators 175, 240 and 350 cm²with 15 mm travel, the follower pin (2)remains in pin position 35.

4. Insert formed seal (6.2) in the groove ofthe adapter bracket.

5. Insert the formed seal (17.1) into theturnboard (17) and mount the turnboardto the adapter block (13) using thescrews (17.2).

6. Mount the blank plate (18) to theturnboard (17) using the screws (18.1)Make sure that the seals are correctlyseated.

Note: A solenoid valve can also be mountedin place of the blank plate (18). The orienta-tion of the turnboard (17) determine themounting position of the solenoid valve. Al-ternatively, a restrictor plate can be mounted(see AB 11).

26 EB 8384-2 EN

Attachment to the control valve – Mounting parts and accessories

Page 27: Val Vu La Caldera

EB 8384-2 EN 27

Attachment to the control valve – Mounting parts and accessories

18.1

1

17.2 181717.1

13.1

13

12

12.1

3

11.1

11

19

20Exh.

1.11.2

1.11.2

1

2

6.2 6.16

4

6.3

5

Fig. 7 · Attachment according to VDI/VDE 3847 onto Type 3277 Actuator

1 Lever1.1 Nut1.2 Disk spring2 Follower pin3 Follower clamp4 Screw plug5 Stopper6 Adapter bracket6.1 Screws6.2 Formed seal6.3 Screws11 Cover11.1 Vent plug

12 Connecting plate12.1 Seal13 Adapter block13.1 Screws17 Turnboard17.1 Formed seal17.2 Screws18 Blank plate18.1 Screws19 Air blocker20 Retaining screw

View from below

Page 28: Val Vu La Caldera

7. Insert screws (13.1) through the middleholes of the adapter block (13).

8. Place the connecting plate (12) togetherwith the seal (12.1) onto the screws(13.1) corresponding to the fail-safe ac-tion "actuator stem extends" or "actuatorstem retracts".The fail-safe action that applies is deter-mined by aligning the groove of theadapter block (13) with the groove ofthe connecting plate (12) (Fig. 8).

9. Mount the adapter block (13) togetherwith the connecting plate (12) to the ac-tuator using the screws (13.1).

10. Insert the vent plug (11.1) into the Exh.connection.

11.For fail-safe action "actuator stem ex-tends", seal the Y1 port with a blankingplug.For fail-safe action "actuator stem re-tracts", connect the Y1 port to the signalpressure connection of the actuator.

12.Place the positioner on the adapter block(13) in such a manner that the followerpin (2) rests on the top of the followerclamp (3). Adjust the lever (1) corre-spondingly and open the positionercover to hold the positioner shaft in posi-tion at the cap or the switch (Fig. 23).The lever (1) must rest on the followerclamp with spring force.Fasten the positioner to the adapterblock (13) using the two fixing screws(6.3). Make sure the formed seal (6.2) isproperly seated.

13.Mount cover (11) on the other side.Make sure that the vent plug pointsdownwards when the control valve is in-stalled to allow any condensed waterthat collects to drain off.

28 EB 8384-2 EN

Attachment to the control valve – Mounting parts and accessories

Z

Z

1213

Fig. 8 · Fail-safe action

Actuator stemextends retracts

12 Connecting plate13 Adapter block

Page 29: Val Vu La Caldera

Attachment to NAMUR rib (see Fig. 9)

Refer to Table 4 on page 49 for the requiredmounting parts as well as the accessories.Note the travel table on page 19.

1. Series 240 Valves, actuator size up to1400-60 cm²: Screw the two bolts (14)to the bracket of the stem connector ordirectly to the stem connector (depend-ing on the version), place the followerplate (3) on top and use the screws(14.1) to fasten it.

Type 3251 Valve, 350 to 2800 cm²:Screw the longer follower plate (3.1) tothe bracket of the stem connector or di-rectly to the stem connector (dependingon the version).

Type 3254 Valve, 1400-120 to2800 cm²: Screw the two bolts (14) tothe bracket (16). Fasten the bracket (16)onto the stem connector, place the fol-lower plate (3) on top and use thescrews (14.1) to fasten it.

Mount the positioner on the NAMUR rib asshown in Fig. 9.

2. For attachment to the NAMUR rib, fas-ten the NAMUR connection block (10)directly into the existing yoke bore usingthe screw and toothed lock washer (11).Align the marking on the NAMUR valveconnection (on the side marked '1') to50 % travel.For attachment to valves with rod-typeyokes using the formed plate (15),which is placed around the yoke: screwthe four studs into the NAMUR connec-

tion block (10). Place the NAMUR con-nection block on the rod and position theformed plate (15) on the opposite side.Use the nuts and toothed lock washers tofasten the formed plate onto the studs.Align the marking on the NAMUR valveconnection (on the side marked ‘1’) to50 % travel.

3. Place the adapter bracket (6) on thepositioner and mount using the screws(6.1). Make sure that the seals are cor-rectly seated. For positioners with airpurging, remove the stopper (5) beforemounting the positioner.For positioners without air purging, re-place the screw plug (4) with a vent plug.

4. Select required lever size (1) M, L or XLand pin position according to the actua-tor size and valve travels listed in the ta-ble on page 19.

Should you require a pin position other thanposition 35 with the standard installed leverM, or require a lever size L or XL, proceedas follows:

– Screw the follower pin (2) in the as-signed lever bore (pin position) as listedin the table. Only use the longer followerpin (2) included in the mounting kit.

– Place lever (1) on the positioner shaftand screw tight using the disk spring(1.2) and nut (1.1).

– Move the lever once all the way as faras it will go in both directions.

5. Insert formed seal (6.2) in the groove ofthe adapter bracket.

6. Insert the formed seal (17.1) into theturnboard (17) and mount the turnboard

EB 8384-2 EN 29

Attachment to the control valve – Mounting parts and accessories

Page 30: Val Vu La Caldera

to the adapter block (13) using thescrews (17.2).

7. Mount the blank plate (18) to theturnboard (17) using the screws (18.1)Make sure that the seals are correctlyseated.

Note: A solenoid valve can also be mountedin place of the blank plate (18). The orienta-tion of the turnboard (17) determine themounting position of the solenoid valve. Al-ternatively, a restrictor plate can be mounted(see AB 11).

8. Mount the adapter block (13) to theNAMUR connection block using thescrews (13.1).

9. Insert the vent plug (11.1) into the Exh.connection.

10.Place the positioner on the adapter block(13) in such a manner that the followerpin (2) rests on the top of the followerclamp (3). Adjust the lever (1) corre-spondingly.Fasten the positioner to the adapterblock (13) using the two fixing screws(6.3). Make sure the formed seal (6.2) isproperly seated.

11.For single-acting actuators without airpurging connect the Y1 port of theadapter block to the signal pressure con-nection of the actuator. Seal the Y2 portwith a blanking plug.For double-acting actuators and actua-tors with air purging connect the Y2port of the adapter block to the signalpressure connection of the second actua-

tor chamber or spring chamber of theactuator.

30 EB 8384-2 EN

Attachment to the control valve – Mounting parts and accessories

Page 31: Val Vu La Caldera

EB 8384-2 EN 31

Attachment to the control valve – Mounting parts and accessories

6.2 6.16

4

6.3

5

1

2

16

3

3.1

11

18

18.1

13.113 17.21717.1

103

Exh.19

20

14

14.1

1.11.2

15

Fig. 9 · Attachment according to VDI/VDE 3847 to the NAMUR rib

View from below

1 Lever1.1 Nut1.2 Spring disk2 Follower pin3 Follower plate3.1 Follower plate4 Screw plug5 Stopper6 Adapter bracket6.1 Screws6.2 Formed seal6.3 Screws10 NAMUR

connection block11 Screw with

toothed lockwasher

13 Adapter block13.1 Screws14 Bolt14.1 Screws15 Formed plate16 Bracket17 Turnboard17.1 Formed seal17.2 Screws18 Blank plate18.1 Screws19 Air blocker20 Retaining screw

Page 32: Val Vu La Caldera

4.4 Attachment to Type 3510Micro-flow Valve

Refer to Table 3 on page 49 for the requiredmounting parts as well as the accessories.Note the travel table on page 19.

The positioner is attached to the valve yokeusing a bracket.

1. Screw bracket (9.1) to the stem connec-tor (9).

2. Fasten the two pins (9.2) to the bracket(9.1) on the stem connector. Mount thefollower plate (3) and fasten it using thescrews (9.3).

3. Mount the travel indication scale (acces-sories) to the outer side of the yoke usingthe hex screws (12.1), ensuring that thescale is aligned with the stem connector.

4. Fasten the hex bar (11) onto the outerside of yoke by screwing the M8 screws(11.1) directly into the holes on theyoke.

5. Fasten the bracket (10) to the hex bar(11) using the hex screw (10.1), washerand tooth lock washer.

6. Mount connecting plate (6) or pressuregauge bracket (7) with pressure gauges(8) on the positioner, making sure bothseal rings (6.1) are seated properly.

7. Unscrew the standard installed lever M(1) including follower pin (2) from thepositioner shaft.

8. Take lever S (1) and screw follower pin(2) in the bore for pin position 17.

9. Place lever S on the positioner shaft andscrew tight using the disk spring (1.2)and nut (1.1).

Move lever once all the way as far as itwill go in both directions.

10. Place positioner on the bracket (10) insuch a manner that the follower pinslides into the groove of the clamp (3).Adjust the lever (1) correspondingly.Screw the positioner to the bracket (10)using both its screws.

32 EB 8384-2 EN

Attachment to the control valve – Mounting parts and accessories

Page 33: Val Vu La Caldera

EB 8384-2 EN 33

Attachment to the control valve – Mounting parts and accessories

10.1

1

2

1.1

1.2

6.1

6

7

8

10

9

9.1

11 11.1

3

12.1

9.2

9.3

Fig. 10 · Attachment to Type 3510 Micro-flow Valve

Note: Always use the connecting plate(6) included in the accessories to connectsupply and output.Never screw threaded parts directly intothe housing.

1 Lever1.1 Nut1.2 Disk spring2 Follower pin3 Follower plate6 Connecting clamp6.1 Seal rings7 Pressure gauge

bracket8 Pressure gauge

mounting kit9 Stem connector9.1 Bracket9.2 Pin9.3 Screw

Lever S

10 Bracket10.1 Screw11 Hex bar11.1 Screw12.1 Screw

Page 34: Val Vu La Caldera

4.5 Attachment to rotaryactuators

Refer to Table 5 on page 50 for the requiredmounting parts as well as the accessories.Note the travel table on page 19.

The positioner is mounted to the rotary actu-ator using two pairs of double brackets.

Prior to attaching the positioner to theSAMSON Type 3278 Rotary Actuator,mount the associated adapter (5) to the freeend of the rotary actuator shaft.

Note: On attaching the positioner as de-scribed below, it is imperative that the actu-ator's direction of rotation is observed.

1. Place follower clamp (3) on the slottedactuator shaft or the adapter (5).

2. Place coupling wheel (4) with flat sidefacing the actuator on the followerclamp (3). Refer to Fig. 12 to align slotso that it matches the direction of rota-tion when the valve is in its closed posi-tion.

3. Screw coupling wheel and followerclamp tightly onto the actuator shaft us-ing screw (4.1) and disk spring (4.2).

4. Screw the bottom pair of brackets (10.1)with the bends pointing either to the in-side or to the outside (depending on theactuator size) to the actuator case. Posi-tion top pair of brackets (10) and screwtight.

5. Mount connecting plate (6) or pressuregauge bracket (7) with pressure gaugesto the positioner, making sure both

O-rings are seated properly.For double-acting, springless rotary ac-tuators, a reversing amplifier is requiredto attach the positioner to the actuator,see section 4.6.

6. Unscrew the standard follower pin (2)from the positioner's lever M (1). Use themetal follower pin (Ø5) included in themounting kit and screw tight into thebore for pin position 90°.

7. Place positioner on the top pair ofbrackets (10) and screw tight. Con-sidering the actuator's direction of rota-tion, adjust lever (1) so that it engages inthe slot of the coupling wheel (4) with itsfollower pin (see Fig. 12). It must beguaranteed that the lever (1) is parallelto the long side of the positioner whenthe actuator is at half its angle of rota-tion.

8. Stick scale plate (4.3) on the couplingwheel so that the arrow tip indicates theclosed position, and it can be easilyread when the valve is installed.

34 EB 8384-2 EN

Attachment to the control valve – Mounting parts and accessories

1.2

1.11

2

4.1

4.2

53

Fig. 11 · Mounting the coupling wheel with Type 3278

Mounting flange

Page 35: Val Vu La Caldera

EB 8384-2 EN 35

Attachment to the control valve – Mounting parts and accessories

Fig. 12 · Attachment to rotary actuators

10

10.1

6 (7, 8)

1.124.3

5

6.1

4

1.21

130 mm

80 mm

Control valve opens clockwise

Note:Always use the connectingplate (6) included in theaccessories to connectsupply and output.Never screw threadedparts directly into thehousing.

Control valve opens counterclockwise

Slot

Legends Figs. 11 + 121 Lever1.1 Nut1.2 Disk spring2 Follower pin3 Follower clamp (Fig. 11)4 Coupling wheel4.1 Screw4.2 Disk spring4.3 Scale plate4.3 Scale plate5 Actuator shaft

Adapter for Type 32786.1 Seal rings7 Pressure gauge bracket8 Pressure gauge

mounting kit10 Top pair of brackets10.1 Bottom pair of brackets Slot

Page 36: Val Vu La Caldera

4.5.1 Heavy-duty version

Refer to Table 5 on page 50 for the requiredmounting parts as well as the accessorieswith their order numbers.

Both mounting kits contain all the necessarymounting parts. First select correct actuatorsize. Prepare actuator, and mount requiredadapter supplied by the actuator manufac-turer, if necessary.

1. Mount the housing (10) onto the rotaryactuator. In case of VDI/VDE attach-ment, place spacers (11) underneath, ifnecessary.

2. For SAMSON Type 3278 and VETECS160 Rotary Actuator, screw the adapter(5) onto the free end of the shaft orplace adapter (5.1) onto the shaft of theVETEC R Actuator.Place adapter (3) onto Type 3278, VETECS160 and VETEC R Actuator. ForVDI/VDE version, this step depends onthe actuator size.

3. Stick adhesive label (4.3) onto the cou-pling wheel in such a manner that theyellow part of the sticker is visible in thewindow of the housing when the valve isOPEN. Adhesive labels with explanatorysymbols are enclosed and can be stuckon the housing, if required.

4. Screw tight coupling wheel (4) onto theslotted actuator shaft or adapter (3) us-ing screw (4.1) and disk spring (4.2).

5. Undo the standard follower pin (2) onthe lever M (1) of the positioner. Attachthe follower pin (Ø 5) included in themounting kit to pin position 90°.

6. If applicable, mount pressure gaugebracket (7) with pressure gauges or, incase G ¼ threaded connections are re-quired, the connecting plate (6), makingsure both seal rings (6.1) are seatedproperly.For double-acting, springless rotary ac-tuators, a reversing amplifier is requiredto attach the positioner to the actuator.Refer to section 4.6.

7. For actuators with a volume of less than300 cm³, fit the screw-in restriction (or-der no.1400-6964) into the signal pres-sure output of the positioner (or the out-put of the pressure gauge bracket orconnecting plate).

8. Place positioner on housing (10) andscrew it tight. Considering the actuator'sdirection of rotation, align lever (1) sothat it engages in the correct slot of thecoupling wheel with its follower pin (Fig.13).

36 EB 8384-2 EN

Attachment to the control valve – Mounting parts and accessories

1

10

4

Fig. 13 · Direction of rotation

Counterclockwise

Clockwise

Page 37: Val Vu La Caldera

EB 8384-2 EN 37

Attachment to the control valve – Mounting parts and accessories

6 6.1 7 8

1 1.1 1.2

2

4.1

3

10.1

10

11

5

4.344.2

4.1

3

5.1

5

10.1

10

4.344.2

Fig. 14 · Attachment to rotary actuators (heavy-duty version)

SAMSON Type 3278VETEC S160, VETEC R

Attachment acc. to VDE/VDI 3845(Sept .2010), level 1, size AA1 to AA4,refer to section 15.1

1 Lever1.1 Nut1.2 Disk spring2 Follower pin3 Adapter4 Coupling wheel4.1 Screw4.2 Disk spring4.3 Adhesive label5 Actuator shaft

or adapter5.1 Adapter

6 Connecting plate (only for G ¼)6.1 Seal rings7 Pressure gauge bracket8 Pressure gauge mounting kit10 Adapter housing10.1 Screws11 Spacers

Fit screw-in restriction into signal pressure outputfor actuators with < 300 cm³ volume

Page 38: Val Vu La Caldera

4.6 Reversing amplifier fordouble-acting actuators

For the use with double-acting actuators, thepositioner must be fitted with a reversingamplifier, e.g. the SAMSON Type 3710 Re-versing Amplifier (see Mounting and Oper-ating Instructions EB 8392).

If a different reversing amplifier (item no.1079-1118 or 1079-1119) is used, followthe mounting instructions described in sec-tion 4.6.1.

The following applies to all reversing am-plifiers:

The output signal pressure of the positioneris supplied at the output A1 of the reversingamplifier. An opposing pressure, whichequals the required supply pressure whenadded to the pressure at A1, is applied atoutput A2.The rule A1 + A2 = Z applies.

A1: Output A1 leading to the signal pressureconnection at the actuator which opens thevalve when the pressure increases

A2: Output A2 leading to the signal pressureconnection at the actuator which closes thevalve when the pressure increases

4 Set slide switch on positioner toAIR TO OPEN.

4.6.1 Reversing amplifier(1079-1118 or 1079-1119)

1. Mount the connecting plate (6) from theaccessories in Table 5 to the positioner.Make sure that both O-rings (6.1) areseated correctly.

2. Thread the special nuts (1.3) from theaccessories of the reversing amplifierinto the boreholes of the connectingplate.

3. Insert the gasket (1.2) into the recess ofthe reversing amplifier and push boththe hollowed special screws (1.1) intothe connecting boreholes A1 and Z.

4. Place the reversing amplifier onto theconnecting plate (6) and screw tight us-ing both the special screws (1.1).

5. Use a screwdriver (8 mm wide) to screwthe enclosed filters (1.6) into the con-necting boreholes A1 and Z.

NOTICEDo not unscrew the sealing plug (1.5) out ofthe reversing amplifier.The rubber seal (1.4) is not required andcan be removed when the sealing plug isused.

6. After the initialization is completed, setCode 16 (Pressure limit) to No.

Pressure gauge attachment

The mounting sequence shown in Fig. 15 re-mains unchanged. Screw a pressure gaugebracket onto the connections A1 and Z.

Pressure gauge G ¼ 1400-7106bracket: ¼ NPT 1400-7107

Pressure gauges for supply air Z and outputA1 as listed in Tables 1 to 7.

38 EB 8384-2 EN

Attachment to the control valve – Mounting parts and accessories

Page 39: Val Vu La Caldera

EB 8384-2 EN 39

Attachment to the control valve – Mounting parts and accessories

A1

1.5 1.6

1.3

6.266.1

1.2 1.1 1 1.6

Z

A2

1.4

A1 A2

Z

A1

Output 38 Supply 9O

utpu

t 38

Supp

ly 9

1.3 1.21.1

Fig. 15 · Mounting a reversing amplifier (1079-1118 or 1079-1119)

From the positioner

Control signals tothe actuator

6 Connecting plate6.1 O-rings6.2 Screws

1 Reversing amplifier1.1 Special screws1.2 Gasket1.3 Special nuts1.4 Rubber seal1.5 Sealing plug1.6 Filter

Page 40: Val Vu La Caldera

4.7 Attaching an externalposition sensor

Refer to Table 6 on p. 50 for the mountingparts as well as the accessories required.

In the positioner version with an external po-sition sensor, the sensor placed in a sepa-rate housing is attached over a plate orbracket to the control valve. The travelpick-off corresponds to that of a standarddevice.The positioner unit can be mounted as re-quired to a wall or a pipe.

For the pneumatic connection either a con-necting plate (6) or a pressure gaugebracket (7) must be fixed to the housing, de-pending on the accessory chosen. Makesure the seal rings (6.1) are correctly in-serted (see Fig. 6, bottom right).

For the electrical connection a 10 meterconnecting lead with M12x1 connectors isincluded in the scope of delivery.

Note:– In addition, the instructions in sections

5.1 and 5.2 apply for the pneumatic andelectrical connection.

Operation and settings are described insections 7 and 8.

– Since 2009, the back of the position sen-sor (20) is fitted with two pins acting asmechanical stops for the lever (1). If thisposition sensor is mounted using oldmounting parts, two correspondingØ8 mm holes must be drilled into themounting plate/bracket (21). A templateis available for this purpose. Refer to Ta-ble 7 on page 51.

4.7.1 Mounting the positionsensor with directattachment

Type 3277-5 Actuator with 120 cm²

The signal pressure from the positioner isrouted over the signal pressure connectionof the connecting plate (9, Fig. 17 left) to theactuator diaphragm chamber. To proceed,first screw the connecting plate (9) includedin the accessories onto the actuator yoke.

4 Turn the connecting plate (9) so that thecorrect symbol for the fail-safe position"Actuator stem extends" or "Actuatorstem retracts" is aligned with the marking(Fig. 17, below).

4 Make sure that the gasket for the con-necting plate (9) is correctly inserted.

4 The connecting plate has boreholes withNPT and G threads.Seal the threaded connection that is notused with the rubber seal and squareplug.

Type 3277 Actuator with 175 to 750 cm²:

The signal pressure is routed to the connec-tion at the side of the actuator yoke for the

40 EB 8384-2 EN

Attachment to the control valve – Mounting parts and accessories

Fig. 16 · Positioner unit with sensor mounted on amicro-flow valve

Page 41: Val Vu La Caldera

version "Actuator stem extends".For the fail-safe position "Actuator stem re-tracts" the connection on the top diaphragmcase is used. The connection at the side ofthe yoke must be fitted with a venting plug(accessories).

Mounting the position sensor

1. Place the lever (1) on the sensor inmid-position and hold it in place.Unthread the nut (1.1) and remove thelever together with the disk spring (1.2)from the sensor shaft.

2. Screw the position sensor (20) onto themounting plate (21).

3. Depending on the actuator size andrated valve travel, determine the re-quired lever and position of the follower

pin (2) from the travel table on page 19.The positioner is delivered with lever Min pin position 35 on the sensor. If nec-essary, remove the follower pin (2) fromits pin position and move it to the bore-hole for the recommended pin positionand screw tight.

4. Place the lever (1) and disk spring (1.2)on the sensor shaft.Place the lever (1) in mid-position andhold it in place. Screw on the nut (1.1).

5. Place the follower clamp (3) on the actu-ator stem, align and fasten it, makingsure that the fastening screw rests in thegroove of the actuator stem.

6. Place the mounting plate (21) togetherwith the sensor onto the actuator yoke sothat the follower pin (2) rests on the top

EB 8384-2 EN 41

Attachment to the control valve – Mounting parts and accessories

20

219

11

1.1 1.2

3

2

1

Fig. 17 · Mounting for Type 3277-5 Actuator (left) and Type 3277 Actuator (right)

Signal pressure

Vent plug

Actuator stemextends retractsSymbol

Marking

Signal pressure

1 Lever1.1 Nut1.2 Disk spring2 Follower pin3 Follower clamp9 Connecting plate11 Cover20 Position sensor21 Mounting plate

Page 42: Val Vu La Caldera

of the follower clamp (3). It must rest onit with spring force.Screw tight the mounting plate (21) ontothe actuator yoke using both fixingscrews.

7. Mount cover (11) on the other side.Make sure that the vent plug pointsdownwards when the control valve is in-stalled to allow any condensed waterthat collects to drain off.

4.7.2 Mounting the positionsensor with attachmentaccording to IEC 60534-6

For the required mounting parts and the ac-cessories, refer to Table 7 on page 51.

1. Place the lever (1) on the sensor inmid-position and hold it in place.

Unthread the nut (1.1) and remove thelever together with the disk spring (1.2)from the sensor shaft.

2. Screw the position sensor (20) onto thebracket (21).

The standard attached lever M with the fol-lower pin (2) at position 35 is designed for120, 175, 240 and 350 cm² actuators with15 mm rated travel.

For other actuator sizes or travels, select thelever and pin position from the travel tableon page 19. Lever L and XL are included inthe mounting kit.

3. Place the lever (1) and disk spring (1.2)on the sensor shaft.Place the lever (1) in mid-position andhold it in place. Screw on the nut (1.1).

4. Screw both bolts (14) to the bracket(9.1) of the stem connector (9). Attach

42 EB 8384-2 EN

Attachment to the control valve – Mounting parts and accessories

20 21

2

1.1, 1.2 14.1 3 14 99.1

Fig. 18 · Mounting according to IEC 60534-6 (NAMUR)

1 Lever1.1 Nut1.2 Disk spring2 Follower pin3 Follower plate9 Stem connector9.1 Bracket14 Bolt14.1 Screws20 Position sensor21 Bracket

Page 43: Val Vu La Caldera

the follower plate (3) and fix with thescrews (14.1).

5. Place the bracket with the sensor at theNAMUR rib in such a manner that thefollower pin (2) rests in the slot of the fol-lower plate (3), then screw the bracketusing its fixing screws onto the valve.

4.7.3 Mounting the positionsensor to Type 3510Micro-flow Valve

For the required mounting parts and the ac-cessories, refer to Table 7 on page 51.

1. Place the lever (1) in mid-position andhold it in place. Unscrew the nut (1.1)and remove the standard attached leverM (1) together with the disk spring (1.2)from the sensor shaft.

2. Screw the position sensor (20) onto thebracket (21).

3. Select the lever S (1) from the accesso-ries and screw the follower pin (2) intothe hole for pin position 17.Place the lever (1) and disk spring (1.2)on the sensor shaft.Place the lever (1) in mid-position andhold it in place. Screw on the nut (1.1).

4. Place the follower clamp (3) on the stemconnector, align it at a right angle andscrew tight.

5. Position the bracket (21) with the positi-on sensor on the valve yoke and screwtight, making sure the follower pin (2)slides into the groove of the followerclamp (3).

EB 8384-2 EN 43

Attachment to the control valve – Mounting parts and accessories

20 21

1.1 1.2

1

3

2

Fig. 19 · Mounting on a micro-flow valve

1 Lever1.1 Nut1.2 Disk spring2 Follower pin3 Follower clamp20 Position sensor21 Bracket

Page 44: Val Vu La Caldera

4.7.4 Mounting the positionsensor to rotary actuators

For the required mounting parts and the ac-cessories, refer to Table 7 on page 51.

1. Place the lever (1) in mid-position andhold it in place. Unscrew the nut (1.1)and remove the standard attached leverM (1) together with the disk spring (1.2)from the sensor shaft.

2. Screw the position sensor (20) onto themounting plate (21).

3. Replace the follower pin (2) normally at-tached to the lever (1) with the metal fol-lower pin (Ø 5) from the accessoriesand screw it into the hole for pin position90°.

4. Place the lever (1) and disk spring (1.2)on the sensor shaft.Place the lever (1) in mid-position andhold it in place. Screw on the nut (1.1).

Follow the instructions describing attachmentto the standard positioner in section 4.5Instead of the positioner, attach the positionsensor (20) with its mounting plate (21).

44 EB 8384-2 EN

Attachment to the control valve – Mounting parts and accessories

2021

2 1 1.1, 1.2

Fig. 20 · Positioner unit with sensor mounted on rotary actuators

1 Lever1.1 Nut1.2 Disk spring2 Follower pin20 Position sensor21 Mounting plate

Page 45: Val Vu La Caldera

4.8 Mounting the leakage sensor

Normally, the control valve is delivered withpositioner and leakage sensor alreadymounted.

If the leakage sensor is mounted after thevalve has been installed or it is mountedonto another control valve, proceed as de-scribed in following.

NOTICEFasten the leakage sensor using a torque of20 ±5 Nm.

The hole with M8 thread on the NAMUR ribshould preferably be used to mount the sen-sor (Fig. 21).

Note: If the positioner was mounted directlyonto the actuator (integral attachment), theNAMUR interfaces on either side of thevalve yoke can be used to mount the leak-age sensor.

The start-up of the leakage sensor is de-scribed in detail in the Operating Instruc-tions EB 8389 on EXPERTplus Valve Diag-nostics.

EB 8384-2 EN 45

Attachment to the control valve – Mounting parts and accessories

123

Fig. 21 · Mounting the leakage sensor

1 Leakage sensor2 Screw3 Plug-type connection

Page 46: Val Vu La Caldera

4.9 Attaching positioners withstainless steel housings

Positioners with stainless steel housings re-quire mounting parts that are completelymade of stainless steel or free of aluminum.

Note: The pneumatic connecting plate and apressure gauge bracket made of stainlesssteel are available (order numbers listed be-low). The Type 3710 Pneumatic ReversingAmplifier is also available in stainless steel.

Connecting plate(stainless steel):

G ¼¼ NPT

1400-74761400-7477

Pressure gaugebracket (st. steel):

G ¼¼ NPT

1402-02651400-7108

The Tables 1 to 6 (pages 47 to 50) apply forattaching positioners with stainless steelhousings with the following restrictions:

Direct attachmentAll mounting kits from Tables 1 and 2 canbe used. The connection block is not re-quired. The stainless steel version of thepneumatic connecting plate routes the air in-ternally to the actuator.

Attachment according to IEC 60534-6(NAMUR rib or attachment to rod-typeyokes)All mounting kits from Table 3 can be used.Connecting plate in stainless steel.

Attachment to rotary actuatorsAll mounting kits from Table 5 can be usedexcept for the heavy-duty version. Con-necting plate in stainless steel.

4.10 Air purging function forsingle-acting actuators

The exhaust air from the positioner is di-verted to the actuator spring chamber toprovide corrosion protection inside the actu-ator. The following must be observed:

Direct attachment to Type 3277-5 (stem ex-tends FA/stem retracts FE)The air purging function is automaticallyprovided.

Direct attachment to Type 3277, 175 to750 cm2

FA: Remove the stopper 12.2 (Fig. 5 onpage 23) at the connection block andmake a pneumatic connection to thespring chamber on the vented side.

NOTICEThe method described does not apply toold connection blocks in pow-der-paint-coated aluminum. In this case,follow the instructions for attachmentdescribed below in “Attachment acc. toIEC 60534-6 (NAMUR rib or attach-ment to rod-type yokes) and to rotaryactuators”.

FE: The air purging function is automati-cally provided.

Attachment acc. to IEC 60534-6 (NAMURrib or attachment to rod-type yokes) and torotary actuatorsThe positioner requires an additional portfor the exhaust air that can be connected

46 EB 8384-2 EN

Attachment to the control valve – Mounting parts and accessories

Page 47: Val Vu La Caldera

over piping. An adapter available as an ac-cessory is used for this purpose:

Threaded bushing(M20 x 1.5):

G ¼¼ NPT

0310-26190310-2550

NOTICEThe adapter uses one of the M20 x 1.5 con-nections in the housing which means justone cable gland can be installed.

4.11 Mounting parts andaccessories

Should other valve accessories be usedwhich vent the actuator (e.g. solenoid valve,volume booster, quick exhaust valve), thisexhaust air must also be included in thepurging function. The connection over theadapter at the positioner must be protectedwith a check valve, e.g. check valve G ¼(order no. 8502-0597) mounted in the pip-ing. Otherwise the pressure in the positionerhousing would rise above the ambient pres-sure and damage the positioner when theexhausting components respond suddenly.

EB 8384-2 EN 47

Attachment to the control valve – Mounting parts and accessories

Table 1 · Direct attachment to Type 3277-5 Actuator (Fig. 4) Order no.

Mounting parts Standard version for actuators 120 cm² or smaller 1400-7452

Version compatible with paint for actuators 120 cm² or smaller 1402-0940

Accessoriesfor theactuator

Switchover plate old for Actuator Type 3277-5xxxxxx.00 (old) 1400-6819

Switchover plate new for Actuator Type 3277-5xxxxxx.01 (new) 1) 1400-6822

Connecting plate new for Actuator Type 3277-5xxxxxx.01 (new) 1), G 18 and 1

8 NPT 1400-6823

Connecting plate old for Actuator Type 3277-5xxxxxx.00 (old): G 18 1400-6820

Connecting plate old for Actuator Type 3277-5xxxxxx.00 (old): 18 NPT 1400-6821

Accessoriesfor thepositioner

Connecting plate (6)G 1

4 1400-74611

4 NPT 1400-7462

Pressure gauge bracket (7)G 1

4 1400-74581

4 NPT 1400-7459

Pressure gauge mounting kit (8) up to max. 6 bar (output/supply)St. steel/brass 1400-6950

St. steel/St. st. 1400-69511) Only new switchover and connecting plates can be used with new actuators (Index 01).

Old and new plates are not interchangeable.

Page 48: Val Vu La Caldera

48 EB 8384-2 EN

Attachment to the control valve – Mounting parts and accessories

Table 2 · Direct attachment to Type 3277 (Fig. 5) Order no.

Mountingparts

Standard version for actuators with 175, 240, 350, 355, 700, 750 cm² 1400-7453

Version compatible with paint for actuators with 175, 240, 350, 355, 700, 750 cm² 1402-0941

Accessories

Required piping with screw fitting– for "Actuator stem retracts"– with air purging of the top diaphragmchamber

175 cm²

SteelG 1

4 / G 38 1402-0970

14 NPT / 3

8 NPT 1402-0976

Stainl.steel

G 14 / G 3

8 1402-09711

4 NPT / 38 NPT 1402-0978

240 cm²

SteelG 1

4 / G 38 1400-6444

14 NPT / 3

8 NPT 1402-0911

Stainl.steel

G 14 / G 3

8 1400-64451

4 NPT / 38 NPT 1402-0912

350 cm²

SteelG 1

4 / G 38 1400-6446

14 NPT / 3

8 NPT 1402-0913

Stainl.steel

G 14 / G 3

8 1400-64471

4 NPT / 38 NPT 1402-0914

355 cm²

SteelG 1

4 / G 38 1402-0972

14 NPT / 3

8 NPT 1402-0979

Stainl.steel

G 14 / G 3

8 1402-09731

4 NPT / 38 NPT 1402-0980

700 cm²

SteelG 1

4 / G 38 1400-6448

14 NPT / 3

8 NPT 1402-0915

Stainl.steel

G 14 / G 3

8 1400-64491

4 NPT / 38 NPT 1402-0916

750 cm²

SteelG 1

4 / G 38 1402-0974

14 NPT / 3

8 NPT 1402-0981

Stainl.steel

G 14 / G 3

8 1402-09751

4 NPT / 38 NPT 1402-0982

Connection block with seals and screwG 1

4 1400-88191

4 NPT 1400-8820

Pressure gauge mounting kit (8) up to max. 6 bar(output/supply)

Steel/brass 1400-6950

St. steel/St. steel 1400-6951

Page 49: Val Vu La Caldera

EB 8384-2 EN 49

Attachment to the control valve – Mounting parts and accessories

Table 3 · Attachment to NAMUR ribs or control valves with rod-type yokes(20 to 35 mm rod diameter) according to IEC 60534-6 (Figs. 6 and 10) Order no.

Travel in mm Lever For actuators

7.5 S Type 3271-5 Actuator with 60/120 cm² on Type 3510 Valve (Fig. 10) 1402-0478

5 to 50 M 1) Actuators from other manufacturers and Type 3271with 120 to 700 cm² 1400-7454

14 to 100 L Actuators from other manufacturers and Type 3271, 1000 and1400-60 versions

1400-7455

40 to 200 XLActuators from other manufacturers and Type 3271, versions 1400-120 and2800 cm² with 120 mm travel

1400-7456

30 or 60 L

Type 3271, versions 1400-120 and 2800 cm² (30 or 60 mm travel) 1400-7466

Mounting bracket for Emerson and Masoneilan linear actuators; a mountingkit acc. to IEC 60534-6 is necessary depending on the travel (see above)

1400-6771

Valtek Type 25/50 1400-9554

Accessories

Connecting plate (6)G ¼ 1400-7461

¼ NPT 1400-7462

Pressure gauge bracket (7)G ¼ 1400-7458

¼ NPT 1400-7459

Pressure gauge mounting kit (8) up to max. 6 bar (output/supply)St. st./Brass 1400-6950

St. steel/St. st. 1400-69511) Lever M is mounted on the standard positioner (included in the scope of delivery)

Table 4 · Attachment according to VDI/VDE 3847 (Figs. 7 and 9)

Type 3730-2xxxxxxxx0x0070xx Electropneumatic Positioner with VDI/VDE 3847 interface Order no.

Mountingparts

Interface adapter 1402-0257

Mounting kit for attachment to SAMSON Type 3277with 175 to 750 cm² 1402-0868

Mounting kit for attachment to SAMSON Type 3271 or non-SAMSON actuators 1402-0869

Travel pick-off for valve travel up to 100 mm 1402-0177

Travel pick-off for 100 to 200 mm valve travel (SAMSON Type 3271 only) 1402-0178

Page 50: Val Vu La Caldera

50 EB 8384-2 EN

Attachment to the control valve – Mounting parts and accessories

Table 5 · Attachment to rotary actuators (Figs. 11 and 12) Order no.

Mounting parts

Attachment acc. to VDI/VDE 3845 (September 2010), refer to section 15.1 fordetails

Actuator surface corresponds to level 1

Size AA1 to AA4, version with CrNiMo steel bracket

Size AA1 to AA4, heavy-duty version

Size AA5, heavy-duty version (e.g. Air Torque 10 000)

1400-7448

1400-9244

1400-9542

Bracket surface corresponds to level 2, heavy-duty version 1400-9526

Attachment for rotary actuators with max. 180° angle of rotation, level 21400-8815

and1400-9837

Attachment for SAMSON Type 3278 with 160/320 cm², CrNiMo steel bracket 1400-7614

Attachment for SAMSON Type 3278 with 160 cm² and for VETEC Type S160,Type R and Type M, heavy-duty version

1400-9245

Attachment for SAMSON Type 3278 with 320 cm² and for VETEC Type S320,heavy-duty version

1400-5891and

1400-9526

Attachment to Camflex II 1400-9120

Accessories

Connecting plate (6)G 1

4 1400-74611

4 NPT 1400-7462

Pressure gauge bracket (7)G 1

4 1400-74581

4 NPT 1400-7459

Pressure gauge mounting kit up to max. 6 bar (output/supply)St. steel/brass 1400-6950

St. steel/st. steel 1400-6951

Table 6 · General accessories Order no.

Accessories

Pneumatic reversing amplifier for double-acting actuators Type 3710

Cable glandM20 x 1.5

Black plastic (6 to 12 mm clamping range) 8808-1011

Blue plastic (6 to 12 mm clamping range) 8808-1012

Nickel-plated brass (6 to 12 mm clamping range) 1890-4875

Nickel-plated brass (10 to 14 mm clamping range) 1922-8395

Stainless steel 1.4305 (8 to 14.5 mm clamping range) 8808-0160

AdapterM20 x 1.5 to ½ NPT

Aluminum, powder paint coated 0310-2149

Stainless steel 1400-7114

Retrofit kit for inductive limit switch 1x SJ 2-SN 1400-7460

Cover plate with list of parametersand operating instructions

German/English (standard) 1990-0761

English/Spanish 1990-3100

English/French 1990-3142

Page 51: Val Vu La Caldera

EB 8384-2 EN 51

Attachment to the control valve – Mounting parts and accessories

Table 7 · Attachment of external position sensor Order no.

Template for mounting the position sensor on older mounting parts. See note on page 40. 1060-0784

Direct attachment

Mounting parts for actuators with 120 cm² see Fig. 17 left 1400-7472

Connecting plate (9, old) for ActuatorType 3277-5xxxxxx.00

G 18 1400-6820

18 NPT 1400-6821

Connecting plate (new) for Actuator Type 3277-5xxxxxx.01 (new) 1) 1400-6823

Mounting parts for actuators with 175 to 750 cm², see Fig. 17 right 1400-7471

NAMUR attachmt. Mounting parts for attachment to NAMUR rib w. lever L and XL, see Fig. 18 1400-7468

Attachment toType 3510Micro-flow Valve

Mounting parts for Type 3271 Actuator with 60 cm², see Fig. 19 1400-7469

Attachment torotary actuators

VDI/VDE 3845 (September 2010), refer to section 15.1 for details

Actuator surface area corresponds to level 1

Size AA1 to AA4 with follower clamp and coupling wheel, versionwith CrNiMo steel bracket, see Fig. 20

Size AA1 to AA4, heavy-duty version

Size AA5, heavy-duty version (e.g. Air Torque 10 000)

1400-7473

1400-9384

1400-9992

Bracket surface area corresponds to level 2, heavy-duty version 1400-9974

SAMSON Type 3278 with 160 cm² (also for VETEC Type S160 and Type R),heavy-duty version

1400-9385

SAMSON Type 3278 with 320 cm² and for VETEC Type S320, heavy-dutyversion

1400-5891and

1400-9974

Accessories forpositioner

Connecting plate (6)G 1

4 1400-7461

14 NPT 1400-7462

Pressure gauge bracket (7)G 1

4 1400-7458

14 NPT 1400-7459

Pressure gauge mounting kit up to max. 6 bar(output/supply)

St. steel/brass 1400-6950

St. steel/st. steel 1400-6951

Bracket to mount the positioner on a wall

Note: The other fastening parts are to be provided at the site of installation aswall foundations vary from site to site.

0309-0111

1) Only new switchover and connecting plates can be used with new actuators (Index 01).Old and new plates are not interchangeable.

Page 52: Val Vu La Caldera

5 Connections

WARNING!Mount the positioner, keeping the followingsequence:1. Remove the protective film from the

pneumatic connections2. Mount the positioner on the control valve3. Connect the supply air4. Connect the electrical power5. Perform the start-up settings

The connection of the electrical auxiliarypower may cause the actuator stem to move,depending on the operating mode.Do not touch the actuator stem or obstruct itto avoid risk of injury to hands or fingers.

5.1 Pneumatic connections

NOTICEFollow the instructions below to avoid dam-aging the positioner.– The threaded connections in the

positioner housing are not designed di-rect air connection!

– The screw glands must be screwed intothe connecting plate, the pressure gaugemounting block or the connection blockfrom the accessories.The air connections are optionally de-signed as a bore with ¼ NPT or G ¼thread.The customary fittings for metal and cop-per pipes or plastic hoses can be used.

– The supply air must be dry and free fromoil and dust.The maintenance instructions for up-stream pressure reducing stations must

be observed.Blow through all air pipes and hosesthoroughly prior to connecting them.

If the positioner is attached directly to theType 3277 Actuator, the connection of thepositioner's output pressure to the actuator isfixed. For attachment according toIEC 60534-6 (NAMUR), the signal pressurecan be routed to either the top or bottom di-aphragm chamber of the actuator, depend-ing on the actuator's fail-safe action"actuator stem extends" or "actuator stemretracts".For rotary actuators, the manufacturer'sspecifications for connection apply.

5.1.1 Signal pressure gauges

To monitor the supply air (Supply) and sig-nal pressure (Output), we recommend thatpressure gauges be attached (see accesso-ries in Tables 1 to 7).

5.1.2 Supply pressure

The required supply air pressure depends onthe bench range and the actuator's operat-ing direction (fail-safe action).The bench range is registered on the name-plate either as spring range or signal pres-sure range depending on the actuator. Thedirection of action is marked FA or FE, or bya symbol.

Actuator stem extends FA (air to open)

Fail-close(for globe and angle valves):

Required supply pressure = Upper benchrange value + 0.2 bar, minimum 1.4 bar.

52 EB 8384-2 EN

Connections

Page 53: Val Vu La Caldera

Actuator stem retracts FE (air to close)

Fail-open(for globe and angle valves):For tight-closing valves, the maximum signalpressure pstmax is roughly estimated as fol-lows:

pstmax = F +d p

A

2

4⋅ ⋅

⋅π ∆

[bar]

d = Seat diameter [cm]∆p = Differential pressure across the valve

[bar]A = Actuator diaphragm area [cm²]

If there are no specifications, calculate asfollows:

Required supply pressure =Upper bench range value + 1 bar.

5.1.3 Signal pressure (output)

The signal pressure at the output (Out-put 38) of the positioner can be limited to1.4, 2.4 or 3.7 bar in Code 16.

The limitation is not activated [No] by de-fault.

5.2 Electrical connections

DANGER!Risk of electric shock and/orthe formation of an explosiveatmosphere!

– For electrical installation, observe the rel-evant electrotechnical regulations andthe accident prevention regulations thatapply in the country of use.

– The following regulations apply tomounting and installation in hazardousareas: EN 60079-14: 2008 Explosiveatmospheres – Part 14: Electrical instal-lations design, selection and erection (orVDE 0165 Part 1).

NOTICE– Adhere to the terminal assignment!

Switching the assignment of the electricalterminals may cause the explosion pro-tection to become ineffective!

– Do not loosen enameled screws in or onthe housing.

– The maximum permissible values speci-fied in the national EC type examinationcertificates apply when interconnectingintrinsically safe electrical equipment (Uior Uo; Ii or Io; Pi or Po; Ci or Co, and Li orLo).

Selecting cables and wires:

Observe Clause 12 of EN 60079-14: 2008when installing intrinsically safe circuits. TheSubclause 12.2.2.7 applies when runningmulti-core cables containing more than oneintrinsically safe circuit.

EB 8384-2 EN 53

Connections

Page 54: Val Vu La Caldera

In particular, the radial thickness of the con-ductor insulation for common insulation ma-terials, such as polyethylene, must have aminimum radial thickness of 0.2 mm.

The diameter of an individual wire in afine-stranded conductor must not be smallerthan 0.1 mm. Protect the conductor endsagainst splicing, e.g. by using wire-end fer-rules.

When two separate cables are used for con-nection, an additional cable gland can beinstalled.Seal cable entries left unused with plugs.

Devices used at ambient temperatures be-low –20 °C must be fitted with metal cableglands.

Equipment for use in zone 2/zone 22

In equipment operated with type of protec-tion Ex nA II (non-sparking equipment) ac-

cording to EN 60079-15: 2003, circuitsmay be connected, interrupted or switchedwhile energized only during installation,maintenance or repair.

Equipment connected to energy-limited cir-cuits with type of protection Ex nL (en-ergy-limited equipment) according toEN 60079-15: 2003 may be switched un-der normal operating conditions.

The maximum permissible values specifiedin the Statement of Conformity or its ad-denda apply when interconnecting theequipment with energy-limited circuits intype of protection Ex nL IIC.

Cable entries

The cable entry with M20 x 1.5 cable gland,6 to 12 mm clamping range.There is a second M20 x 1.5 threaded borein the housing that can be used for addi-tional connection, when required.

54 EB 8384-2 EN

Connections

G

+81 -82 +11 -12 +83 -84 +51 -52

A2A3 A1

+41 -42 +31 -32

A

+31 -32

Fig. 22 · Electric connections

24 V DCsolenoid valve

(optional)

mAcontrol signal

A3Fault

indication

Limit switchesA2 A1

Software Softwareor optionally

inductive

Optional Optional Optional

Binary input

Notex

Binary input of PLC acc. to IEC 61131-2,

(Pmax = 400 mW) or switching

amplifier acc. to EN 60947-5-6

Ex Switching amplifier EN 60947-5-6 Two-wiretransmittersupply unit

for optionalposition

transmitter

Leakagesensor

Page 55: Val Vu La Caldera

The screw terminals are designed for wirecross-sections of 0.2 to 2.5 mm². Tighten thescrews by 0.5 to 0.6 Nm.

The wires for the reference variable must beconnected to the terminals 11 and 12 lo-cated in the housing. Only use a currentsource!

If the reference variable exceeds 22 mA,OVERLOAD appears on the LC display towarn the user.

NOTICEThe wrong connection of a voltage source ofjust around 7 V (or around 2 V whenconnected to the wrong pole) by mistake candamage the positioner.

In general, it is not necessary to connect thepositioner to a bonding conductor. Shouldthis be required, however, this conductorcan be connected inside the device.Depending on the version, the positioner isequipped with inductive limit switchesand/or a solenoid valve.

The position transmitter is operated on atwo-wire circuit. The usual supply voltage is24 V DC. Considering the resistance of thesupply leads, the voltage at the positiontransmitter terminals can be between 12 Vand 30 V DC.Refer to Fig. 22 or the label on the terminalstrip for terminal assignment.

NOTICEThe minimum permissible reference variableshould not fall below 3.8 mA for operatingthe positioner.

Accessories:

Cable gland M20 x 1.5 Order no.

Black plastic(6 to 12 mm clamping range) 8808-1011

Blue plastic(6 to 12 mm clamping range) 8808-1012

Nickel-plated brass(6 to 12 mm clamping range) 1890-4875

Nickel-plated brass(10 to 14 mm clamping range) 1922-8395

Stainless steel 1.4305(8 to 14.5 mm clamping range) 8808-0160

Adapter M20 x 1.5 to ½ NPT

Aluminum, powder paint coated 0310-2149

Stainless steel 1400-7114

5.2.1 Switching amplifiers

For operation of the limit switches, switchingamplifiers must be connected in the outputcircuit. To ensure the operating reliability ofthe positioner, the amplifiers should complywith the limit values of the output circuitsconforming to EN 60947-5-6.If the positioner is to be installed in hazar-dous areas, the relevant regulations must beobserved.

For applications in safe areas (non-hazar-dous areas), limit switches can be directlyinterconnected to the binary input of the PLCin accordance with IEC 61131. This appliesto the standard operating range for digitalinputs according to Clause 5.2.1.2 ofIEC 61131-2 with the rated voltage of24 V DC.

EB 8384-2 EN 55

Connections

Page 56: Val Vu La Caldera

6 Operator controls andreadings

Rotary pushbutton

The rotary pushbutton is located underneaththe front protective cover.The positioner is operated on site using therotary pushbutton:

Turn to select codes and values.

Press to confirm setting.

Slide switch AIR TO OPEN or AIR TO CLOSE

4 AIR TO OPEN applies when the increas-ing signal pressure opens the valve

4 AIR TO CLOSE applies when the increas-ing signal pressure closes the valve

The signal pressure is the air pressure at theoutput of the positioner which is transferredto the actuator.

For positioners with an attached reversingamplifier for double-acting rotary actuators(section 4.6): switch position AIR TO OPEN.

Volume restriction Q

The volume restriction is used to adapt theair delivery to the actuator size. Two fixedsettings are possible depending on how theair is routed at the actuator:

4 For actuators smaller than 240 cm² witha loading pressure connection at the side(Type 3271-5) → MIN SIDE.

4 For a connection at the back (Type3277-5), → MIN BACK.

4 For actuators 240 cm² and larger, →MAX SIDE for a side connection and toMAX BACK for a connection at the back.

56 EB 8384-2 EN

Operator controls and readings

AIR TOO

PEN

CLO

SE

INIT

CA

UTIO

N

VALV

E A

CTU

ATES

MIN

SIDE

MA

X BAC

K

MIN

BAC

KM

AX SID

E Q

%S

mm

SERIAL

INTERFA

CE

%mm

Fig. 23 · Operator controls

Initialization key Cap or rotary switch Metal tag of proximity switch

SSP interface

Switch forAIR TO OPENAIR TO CLOSE

Volume restriction

Rotary pushbutton

Page 57: Val Vu La Caldera

Readings on display

Icons appear on the display that are as-signed to parameters, codes and functions.

Operating modes:

4 Manual mode (MAN), section 8.2.1The positioner follows the manual setpoint (Code 1) instead of the mA signal

blinks: The positioner has not yetbeen initialized. Operation only possibleover manual set point (Code 1).

4 Automatic mode (AUTO), section 8.2.1The positioner is in closed-loop operationand follows the mA signal.

4 S – SAFE, section 8.2.2The positioner vents the output. The valvemoves to the mechanical fail-safe posi-tion.

Bar elements:

In manual and automatic modes, thebars indicate the system deviation that de-pends on the sign (+/–) and the value. Onebar element appears per 1 % system devia-tion.If the device has not yet been initialized, the

icon blinks on the display and the leverposition in degrees in relation to the longitu-dinal axis is indicated. One bar element cor-responds to approximately a 5° angle of ro-tation.If the fifth bar element blinks (reading> 30°), the permissible angle of rotation hasbeen exceeded. Lever and pin position mustbe checked.

Status messages

4 Maintenance alarm

4 Maintenance required/Maintenancedemanded

4 blinks: Outside of specification

These icons indicate that an error has oc-curred.A classified status can be assigned to eacherror. Classifications include “No message”,“Maintenance required”, “Maintenance de-manded” and “Maintenance alarm“ (seesection 8.3).

Configuration enabled

This indicates that the codes marked with anasterisk (*) in the code list (section 14) areenabled for configuration (see section 8.1).

6.1 Serial interface

The positioner must be supplied with at least4 mA.The positioner can be connected directly tothe PC via the local serial interface and theserial interface adapter.

Use the TROVIS-VIEW software with 3730-2device module installed.

EB 8384-2 EN 57

Operator controls and readings

Page 58: Val Vu La Caldera

58 EB 8384-2 EN

Operator controls and readings

%mm

%S

mm

Maintenance alarm/fault Manual mode Closed-loop operation Code

Configurationenabled Fail-safe position

active

DesignationPosition

Parameter

Limit switchAlarm 1

Bar graph forsystem deviationor lever position

Units

Limit switchAlarm 2

Maintenance required/demandedBlinking icon: Outsidespecification

Fig. 24 · Display

AUtO Automatic modeCL ClockwiseCCL CounterclockwiseErr ErrorESC EscapeHI ix ≥ 21.6 mALO ix ≤ 2.4 mALOW w too smallMAN Manual rangeMAX Maximum rangeNo Not available/not activeNOM Nominal travelOVERLOAD w > 22 mARES ResetRUN StartSAFE Fail-safe positionSUb Substitute calibrationtEStinG Test function activeTunE Initialization in progress

YES Available/ActiveZP Zero calibration

ää Increasing/increasingäæ Increasing/decreasing

blinking Emergency mode(see error code 62)

blinking Not initialized

Sblinking Valve in mechanicalfail-safe position

Displays and their meaning

Page 59: Val Vu La Caldera

7 Start-up – Settings

WARNING!Mount the positioner, keeping the followingsequence:1. Remove the protective film from the

pneumatic connections2. Mount the positioner on the control valve3. Connect the supply air4. Connect the electrical power5. Perform the start-up settings

Reading on display after connecting theelectrical auxiliary power:

4 tEStinG runs across the display and thenthe fault alarm icon appears andblinks on the display when the positionerhas not yet been initialized. The readingindicates the lever position in degrees inrelation to the longitudinal axis.

Reading when thepositioner has not yet beeninitialized

4 If Code 0 appears on the display when apositioner has been initialized. Thepositioner is in the last active operatingmode.

WARNING!The actuator stem moves while the start-upsettings are being performed.Do not touch the actuator stem or obstruct itto avoid risk of injury to hands or fingers.

NOTICEPerform the start-up settings in the same se-quence as listed (section 7.1 to section 7.6).

Note: The positioner performs a test in thestart-up phase while following its automa-tion task at the same time. During thestart-up phase, operation on site is unre-stricted, yet write access is limited.

7.1 Defining the valve closedposition

To adapt the positioner to the operating di-rection of the actuator, set slide switch to AIRTO OPEN or AIR TO CLOSE .

4 AIR TO OPEN = Signal pressure opensthe valve, for fail-safe position: actuatorstem extends/fail close

4 AIR TO CLOSE = Signal pressure closesthe valve, for fail-safe position: actuatorstem retracts/fail open.

NOTICEThe AIR TO OPEN (AtO) setting always ap-plies to double-acting actuators.

For checking purposes:After successfully completing initialization,the positioner display should read 0 % whenthe valve is closed and 100 % when thevalve is open. If this is not the case, changethe slide switch position and re-initialize thepositioner.

EB 8384-2 EN 59

Start-up – Settings

Page 60: Val Vu La Caldera

Note: The switch position is prompted priorto an initialization. After an initialization hasbeen completed, changing the switch posi-tion does not have any effect on the opera-tion of the positioner.

7.2 Setting the volume restrictionQ

The volume restriction Q is used to adapt theair delivery to the size of the actuator:

4 Actuators with a transit time < 1 s, e.g.linear actuators with an effective areasmaller than 240 cm², require a re-stricted air flow rate (MIN).

4 Actuators with a transit time ≥ 1 s do notrequire the air flow rate to be restricted(MAX).

The position of volume restriction Q also de-pends on how the signal pressure is routedat the actuator in SAMSON actuators:

4 The “SIDE“ position applies for actuatorswith a loading pressure connection at theside, e.g. Type 3271-5.

4 The “BACK“ position applies for actua-tors with a loading pressure connectionat the back, e.g. in Type 3277-5.

4 The “SIDE”restriction position always ap-plies for actuators from other manufac-turers.

Overview · Position of volume restriction Q*

Signalpressure

Transittime < 1 s ≥ 1 s

Connection at the side MIN SIDE MAX SIDE

Connection at the back MIN BACK MAX BACK

* Intermediate positions are not permitted.

NOTICEThe positioner needs to be initialized againafter the position of the restriction has beenchanged.

7.3 Adapting the display

The data representation on the positionerdisplay can be turned by 180° to adapt it tohow the positioner is mounted.

Reading direction for rightattachment of pneumaticconnections

Reading direction for leftattachment of pneumaticconnections

If the displayed data appear upside down,proceed as follows:

Turn → Code 2

Press → Code 2 blinks.

60 EB 8384-2 EN

Start-up – Settings

MAX BACK MIN SIDE

MIN BACK MAX SIDE

Q

Fig. 25 · Volume restriction QMAX BACK/MIN SIDE setting

%

Page 61: Val Vu La Caldera

Turn → Required direction

Press to confirm reading direction.

7.4 Limiting the signal pressure

If the maximum actuator force may causedamage to the valve, the signal pressuremust be limited.

Enable configuration at the positioner beforeactivating the pressure limit function:

Note: If no settings are entered within120 seconds, the enabled configurationfunction becomes invalid.

Configuration enabledDefault: No

Turn → Code 3, display: No

Press → Code 3 blinks.

Turn → YES

Press → display

Limiting the signal pressure:

Pressure limitDefault: No

Turn → Code 16

Press → Code 16 blinks.

Turn until the required pressure limit(1.4/2.4/3.7 bar) appears.

Press to confirm the pressure limit set-ting.

7.5 Checking the operatingrange of the positioner

To check the mechanical attachment and theproper functioning, the valve should bemoved through the operating range of thepositioner in the manual operating modewith the manual reference variable.

Selecting manual operating mode:

Operating modeDefault MAN

Turn → Code 0

Press → Code 0 blinks.

Turn → MAN

Press . The positioner changes to themanual operating mode.

Checking the operating range:

Manual reference variablew (current angle of rotationis indicated)

Turn → Code 1

Press → Code 1 and blink.

Turn until the pressure in the positionerbuilds up, and the control valve moves to itsfinal positions so that the travel/angle of ro-tation can be checked.

EB 8384-2 EN 61

Start-up – Settings

Page 62: Val Vu La Caldera

The angle of rotation on the back of thepositioner is indicated. A horizontal lever(mid position) is equal to 0°.

To ensure the positioner is working prop-erly, the outer bar elements may not blinkwhile the valve is moving through the oper-ating range.Exit Code 1 by pressing the rotarypushbutton ( ).

The permissible range has been exceededwhen the displayed angle is greater than30°, and the outer right or left bar elementblinks.The positioner changes to the fail-safe posi-tion (SAFE).After canceling the fail-safe position (SAFE)(see section 8.2.2) it is absolutely necessaryto check the lever and pin position as de-scribed in section 4.

WARNING!To avoid personal injury or property dam-age caused by the supply air or electricalauxiliary power, disconnect the supply airand electrical auxiliary power before ex-changing the lever or changing the pin posi-tion.

7.6 Initialization

WARNING!During initialization, the control valve movesthrough its entire travel/rotation range.Therefore, do not start the initialization pro-cedure while a process is running, but onlyduring start-up when all shut-off valves areclosed.

Before starting initialization, check the maxi-mum permissible signal pressure of the con-trol valve. During initialization, thepositioner issues an output signal pressureup to the maximum supply pressure sup-plied. If necessary, limit the signal pressureby connecting an upstream pressure reduc-ing valve.

NOTICEAfter the positioner has been mounted on toanother actuator or its mounting locationhas been changed and prior tore-initializing the positioner, the positionerneeds to be reset to its basic setting (defaultvalues). Refer to section 7.8.

During initialization the positioner adapts it-self optimally to the friction conditions andthe signal pressure demand of the controlvalve. The type and extent of self-adaptationdepends on the set initialization mode:

4 MAX maximum range (standard range)Initialization mode for simple start-up ofvalves with two clearly defined mechani-cal end positions, e.g. three-way valves(see section 7.6.1)

62 EB 8384-2 EN

Start-up – Settings

Page 63: Val Vu La Caldera

4 NOM nominal rangeInitialization mode for all globe valves(see section 7.6.2)

4 MAN manually selected rangeInitialization mode for globe valves withan unknown nominal range (see section7.6.3)

4 SUB substitute calibration (emergencymode)This mode allows a positioner to be re-placed while the plant is running, withthe least amount of disruption to theplant (see section 7.6.4)

Note: For normal operation, simply start ini-tialization by pressing the INIT key aftermounting the positioner on the valve, defin-ing the valve closed position and setting thevolume restriction. The positioner only needsto work with its default settings. If necessary,perform a reset (see section 7.8).

Alternating displays

Initialization running

Icon depending on initial-ization mode selected

Bar graph displayindicating the progress ofthe initialization

Initialization successful,positioner in automaticoperating mode

The time required for an initialization pro-cess depends on the transit time of the actu-ator and may take several minutes.

After a successful initialization, thepositioner runs in closed-loop operation in-dicated by .

A malfunctioning leads to the process beingcanceled. The initialization error appears onthe display according to how it has beenclassified by the condensed state. See sec-tion 8.3.

Note: The setting Code 48 - h0 = YEScauses the reference graphs (drive signalsteady-state d1 and hysteresis d2) to beplotted automatically after initialization hasbeen completed. tESt d1 or tESt d2 appearon the display in an alternating sequence.An error during the plotting of the referencegraphs is indicated by Code 48 - h1 andCode 81.The positioner still works properly, eventhough the reference graph plotting has notbeen completed successfully.

Valve closed position AIR TO CLOSE

If the slide switch is set to AIR TO CLOSE,the positioner automatically switches to thedirection of action increasing/decreasing(äæ) on successful completion of initializa-tion.This results in the following assignment be-tween reference variable and valve position:

EB 8384-2 EN 63

Start-up – Settings

%

Page 64: Val Vu La Caldera

Valve closedposition

Direction ofaction

ValveClosed at Open at

AIR TO OPEN ää 0 % 100 %

AIR TO CLOSE äæ 100 % 0 %

The tight-closing function is activated.

NOTICESet Code 15 (final position w>) to 99 % forthree-way valves.

Canceling an initialization process

The initialization procedure can be canceledwhile running by pressing the rotarypushbutton ( ). StOP appears three sec-onds long and the positioner then changesto the fail-safe position (SAFE).

Exit the fail-safe position again over Code 0(see section 8.2.2).

7.6.1 MAX – Initialization basedon maximum range

The positioner determines travel/angle ofrotation of the closing member from theCLOSED position to the opposite side andadopts this travel/angle of rotation as theoperating range from 0 to 100 %.

Enable configuration:

Note: If no settings are entered within120 seconds, the enabled configurationfunction becomes invalid.

Default No

Turn → Code 3, display: No

Press → Code 3 blinks

Turn → YES

Press , display

Select the initialization mode:

Initialization modeDefault MAX

Turn → Code 6

Press

Turn → MAX

Press to confirm the MAX as the initial-ization mode.

Start initialization:

4 Press INIT key to start initialization!

The nominal travel/angle of rotation is indi-cated in % after initialization. Code 5 (nomi-nal range) remains locked. The parametersfor travel/angle range start (Code 8) andtravel/angle range end (Code 9) can alsoonly be displayed and modified in %.

For a reading in mm/°, enter the pin posi-tion (Code 4).

64 EB 8384-2 EN

Start-up – Settings

Page 65: Val Vu La Caldera

Enter the pin position:

Pin positionDefault No

Turn → Code 4

Press , Code 4 blinks

Turn → Pin position on lever (see rele-vant section on attachment)

Press . The reading of the nominal rangeappears in mm/°.

7.6.2 NOM – Initialization basedon nominal range

The calibrated sensor allows the effectivevalve travel to be set very accurately. Duringthe initialization process, the positionerchecks whether the control valve can movethrough the indicated nominal range (travelor angle) without collision.If this is the case, the indicated nominalrange is adopted with the limits oftravel/angle range start (Code 8) andtravel/angle range end (Code 9) as the op-erating range.

Note: The maximum possible travel must al-ways be greater than the nominal travel en-tered. If this is not the case, initialization isinterrupted (error alarm Code 52) becausethe nominal travel is not achieved.

Enable configuration:

Note: If no settings are entered within120 seconds, the enabled configurationfunction becomes invalid.

Default No

Turn → Code 3, display: No

Press , Code 3 blinks

Turn → YES

Press , display

Enter the pin position and nominal range:

Pin positionDefault No

Nominal range(locked with Code 4 = No)

Turn → Code 4

Press , Code 4 blinks

Turn → Pin position on lever (see rele-vant section on attachment)

Press .

Turn → Code 5

Press , Code 5 blinks

EB 8384-2 EN 65

Start-up – Settings

mm

mm

mm

Page 66: Val Vu La Caldera

Turn → Nominal travel/angle

Press .

Select the initialization mode:

Initialization modeDefault MAX

Turn → Code 6

Press , Code 6 blinks

Turn → NOM

Press to confirm the NOM as the initial-ization mode.

Start initialization:

4 Press INIT key to start initialization!

Note: After initialization, check the directionof action and, if necessary, change it(Code 7).

7.6.3 MAN – Initialization basedon a manually selectedrange

Before starting initialization, move the con-trol valve manually to the OPEN position byturning in small steps. The valve mustmove to the required valve position with amonotonically increasing signal pressure.The positioner calculates the differentialtravel/angle using the OPEN and CLOSEDpositions and adopts it as the operatingrange with limits of travel/angle range start

(Code 8) and travel/angle range end(Code 9).

Enable configuration:

Note: If no settings are entered within120 seconds, the enabled configurationfunction becomes invalid.

Default No

Turn → Code 3, display: No

Press , Code 3 blinks

Turn → YES

Press , display

Enter the pin position:

Pin positionDefault No

Turn → Code 4

Press , Code 4 blinks

Turn → Pin position on lever (see rele-vant section on attachment)

Press . The reading of the nominal rangeappears in mm/°.

66 EB 8384-2 EN

Start-up – Settings

mm

Page 67: Val Vu La Caldera

Select the initialization mode:

Initialization modeDefault MAX

Turn → Code 6

Press , Code 6 blinks

Turn → MAN

Press to confirm the MAN as the initial-ization mode.

Enter OPEN position:

Manual reference variable(the current angle of rota-tion is displayed)

Turn → Code 0

Press , Code 0 blinks

Turn → MAN

Press .

Turn → Code 1

Press , Code 1 blinks

Turn until the valve reaches its OPEN po-sition.

Press to confirm the OPEN position.

Start initialization:

4 Press INIT key to start initialization!

7.6.4 SUb substitute calibration

A complete initialization procedure takesseveral minutes and requires the valve tomove through its entire travel range severaltimes. This initialization mode, however, isan emergency mode, in which the controlparameters are estimated and not deter-mined by an initialization procedure. As aresult, a high level of accuracy cannot beexpected. You should always select a differ-ent initialization mode if the plant allows it.

The SUb initialization mode is used to re-place a positioner while the process is run-ning. For this purpose, the control valve isusually fixed mechanically in a certain posi-tion, or pneumatically by means of a pres-sure signal which is routed to the actuatorexternally. The blocking position ensuresthat the plant continues to operate with thisvalve position.

By entering the blocking position (Code 35),closing direction (Code 34), pin position(Code 4), nominal range (Code 5) and di-rection of action (Code 7), the positionercan calculate the positioner configuration.

NOTICEPerform a reset before re-initializing thepositioner if the substitute positioner has al-ready been initialized. Refer to section 7.8.

Enable configuration:

Note: If no settings are entered within120 seconds, the enabled configurationfunction becomes invalid.

EB 8384-2 EN 67

Start-up – Settings

Page 68: Val Vu La Caldera

Default No

Turn → Code 3, display: No

Press , Code 3 blinks

Turn → YES

Press , display

Enter the pin position and nominal range:

Default No

Nominal range(locked with Code 4 = No)

Turn → Code 4

Press , Code 4 blinks

Turn → Pin position on lever (see rele-vant section on attachment)

Press .

Turn → Code 5

Press , Code 5 blinks

Turn → Nominal travel/angle

Press .

Select the initialization mode:

Initialization modeDefault MAX

Turn → Code 6

Press , Code 6 blinks

Turn → SUb

Press to confirm the SUb as the initializa-tion mode.

Enter the direction of action:

Default ää

Turn → Code 7

Press , Code 7 blinks

Turn → Direction of action (ää or äæ)

Press .

Deactivate travel limit:

Default 100.0

Turn → Code 11

Press , Code 11 blinks

Turn → No

Press .

68 EB 8384-2 EN

Start-up – Settings

mm

mm

Page 69: Val Vu La Caldera

Change pressure limit and control parame-ters:

Note: Do not change the pressure limit(Code 16). Only change the control param-eters KP (Code 17) and TV (Code 18) if thesettings of the replaced positioner areknown.

Pressure limitDefault No

KPDefault 7

TVDefault 2

Turn → Code 16/17/18

Press , Code 16/17/18 blinks

Turn to set the control parameter se-lected.

Press to confirm the setting.

Enter closing direction and blocking posi-tion:

Closing directionDirection of rotation caus-ing the valve to move to theCLOSED position (viewonto positioner display)Default: CCL (counterclock-wise)

Blocking positionDefault: 0

Turn → Code 34

Press , Code 34 blinks

Turn → Closing direction (CCL counter-clockwise/CL clockwise)

Press .

Turn → Code 35

Press , Code 35 blinks

Turn → Blocking position, e.g. 5 mm(read off at travel indicator scale of theblocked valve or measure with a ruler).

Press to confirm the setting.

Define the valve end position:

4 Set switch for valve end position AIR TOOPEN or AIR TO CLOSE as described insection 7.1 on page 59.

4 Set volume restriction as described insection 7.2 on page 60.

EB 8384-2 EN 69

Start-up – Settings

mm

Page 70: Val Vu La Caldera

Start initialization:

4 Press INIT key!The operating mode is changed to MAN.The blocking position is indicated.

Note: As initialization has not been carriedout completely, the error code 76 (no emer-gency mode) and possibly also error code57 (control loop) may appear on the dis-play.These alarms do not influence thepositioner’s readiness for operation.

Cancel the blocking position and change toautomatic operating mode

For the positioner to follow its referencevariable again, the blocking position mustbe canceled and the positioner must be setto automatic operating mode as follows:

Turn → Code 1

Press , Code 1 and blink

Turn in order to move the valve slightlypast the blocking position.

Press to cancel mechanical blocking.

Turn → Code 0

Press , Code 0 blinks.

Turn → AUtO

Press . The positioner switches to auto-matic operating mode. The current valve po-sition is indicated in %.

Note: If the positioner shows a tendency tooscillate in automatic operating mode, theparameters KP and TV must be slightly cor-

rected. Proceed as follows:Set TV to 4 (Code 18).If the positioner still oscillates, the gain KP(Code 17) must be decreased until thepositioner shows a stable behavior.

Zero point calibration

Finally, if process operations allow it, thezero point must be adjusted according tosection 7.7.

7.7 Zero calibration

In case of discrepancies with the closing po-sition of the valve, e.g. with soft-sealedplugs, it may become necessary torecalibrate the zero point.

NOTICEThe valve briefly moves from the currenttravel/angle of rotation position to theclosed position.

Note: The positioner must be connected tothe supply air to perform the zero calibra-tion.

Enable configuration:

Turn → Code 3, display: No

Press , Code 3 blinks

Turn → YES

Press , display

70 EB 8384-2 EN

Start-up – Settings

Page 71: Val Vu La Caldera

Perform zero calibration:

Initialization modeDefault MAX

Turn → Code 6

Press , Code 6 blinks

Turn → ZP

Press .

4 Press INIT key!

Zero calibration is started, the positionermoves the control valve to the CLOSED posi-tion and readjusts the internal electrical zeropoint.

7.8 Reset to default values

This function resets all parameters to the fac-tory default values (see code list in sec-tion 14).

Enable configuration:

Turn → Code 3, display: No

Press , Code 3 blinks

Turn → YES

Press , display

Reset start-up parameters:

ResetDefault No

Turn → Code 36, display: ••–••–

Press , Code 36 blinks

Turn → Std

Press . All start-up parameters and the di-agnosis are reset to their default values.

Note: Code 36 - diAG allows just the diag-nosis data (EXPERTplus) to be reset. Refer toEB 8389 EN on EXPERTplus valve diagnos-tics.

EB 8384-2 EN 71

Start-up – Settings

Page 72: Val Vu La Caldera

8 Operation

WARNING!The actuator stem moves while the positioneris being operated.Do not touch the actuator stem or obstruct itto avoid risk of injury to hands or fingers.

8.1 Enabling and selectingparameters

The codes which are marked with an aster-isk (*) in section 14 on page 81 onwardsmust be enabled with Code 3 before the as-sociated parameters can be configured asdescribed below.

Code 3Configurationnot enabled

Configurationenabled

Turn → Code 3, display: No

Press , Code 3 blinks.Change the setting of Code 3.

Turn → YES

Press , display:The configuration is enabled.

You can now configure codes one after theother:

Turn and select the required code.

Press to access the selected code. Thecode number starts to blink.

Turn and select the setting.

Press to confirm the selected setting.

Note: If no settings are entered within 120seconds, the enabled configuration functionbecomes invalid and the display changes toCode 0.

Cancel the setting:

Canceling the setting

To cancel a value before it is confirmed (bypressing ) proceed as follows:

Turn → ESC

Press . The entered value is not adopted.

72 EB 8384-2 EN

Operation

Page 73: Val Vu La Caldera

8.2 Operating modes

8.2.1 Automatic and manualmodes

After initialization has been completed suc-cessfully, the positioner is in automaticmode.

automatic mode

Switch to manual operating mode

Turn → Code 0

Press , display: AUtO,Code 0 blinks.

Turn → MAN

Press to switchover to manual mode.The switchover is smooth since the manualmode starts up with the set point last usedduring automatic mode. The current positionis displayed in %.

Adjust the manual reference variable

Turn → Code 1

Press , Code 1 blinks.

Turn until sufficient pressure has beenbuilt up in the positioner and the controlvalve moves to the required position.

Note: The positioner automatically returns toCode 0, but remains in manual mode ifno settings are made within 120 seconds.

Switch to automatic operating mode

Turn → Code 0

Press , Code 0 blinks.

Turn → AUtO

Press . The positioner changes to auto-matic operating mode

EB 8384-2 EN 73

Operation

%

%% %

Page 74: Val Vu La Caldera

8.2.2 Fail-safe position (SAFE)

If you want to move the valve to fail-safe po-sition determined during start-up (see sec-tion 7.1), proceed as follows:

Turn → Code 0

Press , display: current operating mode(AUtO or MAN), Code 0 blinks.

Turn → SAFE

Press , display: S.The valve moves to the fail-safe position.Once the positioner is initialized, the currentvalve position is indicated on the display in%.

Exit the fail-safe position

Turn → Code 0

Press , Code 0 blinks.

Turn and select the required operatingmode AUtO or MAN.

Press . The positioner switches to the op-erating mode selected.

8.3 Malfunction/maintenancealarm

All status and fault alarms are classifiedaccording to a status in the positioner. Thedefault settings of the status classification arelisted in the code list.

Note: The status classification can bechanged in TROVIS-VIEW. Refer toEB 8389 EN on EXPERTplus valve diagnos-tics.

To provide a better overview, the classifiedalarms are summarized in a condensedstate according to NAMUR Recommenda-tion NE 107 for the positioner. The followingstatus alarms are available:

4 Maintenance alarmThe positioner cannot perform its controltask due to a functional fault in the de-vice or in one of its peripherals or an ini-tialization has not yet been successfullycompleted.

4 Maintenance requiredThe positioner still performs its controltask (with restrictions). A maintenancerequirement or above average wear hasbeen determined. The wear tolerance willsoon be exhausted or is reducing at afaster rate than expected. Maintenance isnecessary in the medium term.

4 Maintenance demandedThe positioner still performs its controltask (with restrictions). A maintenancedemand or above average wear hasbeen determined. The wear tolerance willsoon be exhausted or is reducing at a

74 EB 8384-2 EN

Operation

Page 75: Val Vu La Caldera

faster rate than expected. Maintenance isnecessary in the short term.

4 Out of specificationThe positioner is operated outside speci-fied operating conditions.

Note: If an event is assigned to the “Nomessage” status, this event does not haveany effect on the condensed state.

The condensed state appears on the displaywith the following icons:

Condensed statePositioner

display

Maintenance alarm

Function checkText, e.g. tESting,

TunE or tESt

Maintenance required/Maintenance demanded

Out of specification blinking

If the positioner has not been initialized, themaintenance alarm icon ( ) appears onthe display as the positioner cannot followits reference variable.

If fault alarms exist, the possible source oferror is displayed in Code 49 onwards. Inthis case, Err appears on the display.

The cause and recommended action arelisted in the code list (section 14).

ExampleError caused by pinposition

Fault alarm output

The “Maintenance alarm” as the condensedstate causes the optional fault alarm outputto be switched.

4 The “Function check” condensed statecan also switch the fault alarm contact inCode 32.

4 The “Maintenance required/demanded”condensed state can also switch the faultalarm contact in Code 33.

8.3.1 Confirming error messages

Enable configuration:

Note: If no settings are entered within120 seconds, the enabled configurationfunction becomes invalid.

Turn → Code 3

Press , Code 3 blinks

Turn → ON

Press , display:

Confirm error messages:

Turn → Error code which you want toconfirm.

Press to confirm the error message.

EB 8384-2 EN 75

Operation

S

Page 76: Val Vu La Caldera

9 Adjusting the limit switch

The positioner version with inductive limitswitch has one adjustable tag (1) mountedon the shaft which operates the proximityswitch (3).

For operation of the inductive limit switch,the corresponding switching amplifier (seesection 5.2.1) must be connected to the out-put.

If the tag (1) is inside the field of the switch,the switch assumes a high resistance. If thetag is outside of the field, the switch assumesa low resistance.

Normally, the limit switch is adjusted suchthat it will provide a signal in both end posi-tions of the valve. The switch, however, canalso be adjusted to indicate intermediatevalve positions.

The desired switching function, i.e. whetherthe output relay shall be picked up or re-leased when the tag has entered the field,has to be determined, if necessary, at theswitching amplifier.

Note:The inductive limit switch replaces the soft-ware limit switch A1 with terminal assign-ment +41/–42.Each switching position can optionally be setto indicate when the tag has entered thefield, or when it has left the field.The second software limit switch remains ef-fective, the function of the software limitswitch A1 is disabled.

76 EB 8384-2 EN

Adjusting the limit switch

Fig. 26 · Adjustment of the limit switch

Adjustment screw (2) Tag (1) Proximity switch (3)

Page 77: Val Vu La Caldera

Software adaptation

Code 38 (inductive alarm is set to YES).The inductive limit switch is connected to theterminals +41/–42.The device is set up accordingly when deliv-ered ex works SAMSON.

Setting the switching point:

NOTICEDuring adjustment or testing, the switchingpoint must always be approached frommid-position (50 %).

To ensure safe switching under any ambientconditions, the switching point should be ad-justed to a value of approx. 5 % before themechanical stop (OPEN – CLOSED).

For CLOSED position:

1. Initialize positioner.2. Use the MAN function to move the

positioner to 5 % (see LC display).3. Adjust the tag using the yellow adjust-

ment screw (2) until the tag enters orleaves the field and the switching ampli-fier responds. You can measure theswitching voltage as an indicator.

Contact function:

4 Tag leaving the field > contact is made4 Tag entering the field > contact is

opened.

For OPEN position:

1. Initialize positioner.2. Use the MAN function to move the

positioner to 95 % (see LC display).3. Adjust the tag (1) using the yellow ad-

justment screw (2) until the tag enters orleaves the field of the proximity switch(3).You can measure the switching voltageas an indicator.

Contact function:

4 Tag leaving the field > Contact is made.4 Tag entering the field > Contact is

opened.

9.1 Retrofitting an inductive limitswitch

Required retrofit kit:Limit switch Order no. 1400-7460

Note: The same requirements apply toretrofitting an inductive limit switch as to ser-vicing the positioner. For explosion-pro-tected devices, the requirements in sec-tion 11 need to be kept.Check the "Limit switch, inductive" box onthe nameplate after retrofitting the limitswitch.

1. Take off the rotary pushbutton (3) andcap (1), unthread the five fixing screws(2) and lift off the plastic cover (9) to-gether with the display, taking care notto damage the ribbon cable (betweenPCB and display).

EB 8384-2 EN 77

Adjusting the limit switch

Page 78: Val Vu La Caldera

2. Use a knife to cut an opening at themarked location (4).

3. Push the connector (11) with cablethrough the opening and secure theproximity switch (7) on the cover with adot of glue.

4. Remove the jumper (8801-2267) at thesocket X7 of the top board and insert thecable connector (11).

5. Guide the cable in such a manner thatthe plastic cover can be placed backonto the positioner. Insert the fixingscrews (2) and screw tight. Attach theclamping plate (8) onto the proximityswitch.

6. Attach the rotary switch (5). Make surethe flattened side of the positioner shaftis turned so that the rotary switch (5) canbe attached with the metal tag next tothe proximity switch.

7. Note: On start-up of the positioner, setthe option "inductive alarm" under Code38 from No to YES.

78 EB 8384-2 EN

Adjusting the limit switch

Fig. 27 · Retrofitting an inductive limit switch

9 7

5

8

7

6

1

2

4

3

1 Cap2 Screws3 Rotary pushbutton4 Marking5 Rotary switch

6 Metal tag7 Proximity

switch8 Clamping plate9 Plastic cover11 Connector

Page 79: Val Vu La Caldera

10 Maintenance

The positioner does not require any mainte-nance.

There are filters with a 100 µm mesh size inthe pneumatic connections for supply andoutput which can be removed and cleaned,if required.

The maintenance instructions of any up-stream supply air pressure reducing stationsmust be observed.

11 Servicing explosion-protecteddevices

If a part of the device on which the explo-sion protection is based needs to be ser-viced, the device must not be put back intooperation until a qualified inspector has as-sessed it according to explosion protectionrequirements, has issued an inspection cer-tificate or given the device a mark of confor-mity.

Inspection by a qualified inspector is not re-quired if the manufacturer performs a rou-tine test on the device prior to putting it backinto operation. The passing of the routinetest must be documented by attaching amark of conformity to the device. Replaceexplosion-protected components only byoriginal, routine-tested components from themanufacturer.

Devices that have already been operatedoutside hazardous areas and are intendedfor future use inside hazardous areas mustcomply with the safety requirements placedon serviced devices. Before being used in-side hazardous areas, test the devices ac-cording to the specifications for servicingexplosion-protected devices.

12 Firmware update (serialinterface)

Firmware updates on positioners currently inoperation can be performed as follows:

When updates are performed by a serviceemployee appointed by SAMSON, the up-date is confirmed on the positioner by thetest mark assigned by SAMSON’s QualityAssurance.

In all other cases, only persons from theplant operator with written approval mayperform updates. This person must confirmthe update on the positioner.

Laptops and PCs connected to the powersupply must use an additional safety barrier.

This does not apply to laptops in battery op-eration. In this case, it is assumed that a bat-tery-powered laptop runs briefly for soft-ware programming or for testing purposes.

a) Updates outside the hazardous area:

Remove the positioners from the plantand update them outside the hazardousarea.

EB 8384-2 EN 79

Maintenance

Page 80: Val Vu La Caldera

b) Updates on site:

Updates on site are only permitted afterthe plant operator has presented a sig-ned hot work permit.

After updating has been completed, add thecurrent firmware to the nameplate; this canbe done using labels.

13 Maintenance, calibration andwork on equipment

The interconnection with intrinsically safecircuits to check or calibrate the apparatusmust only be performed with intrinsicallysafe current/voltage calibrators and mea-suring instruments to rule out any damageto components relevant for explosion pro-tection.

The maximum values for intrinsically safecircuits specified in the approvals must bekept.

80 EB 8384-2 EN

Maintenance, calibration and work on equipment

Page 81: Val Vu La Caldera

14 Code list

Codeno.

Parameter – Readings,values [default setting] Description

Note: Codes with marked with an asterisk (*) must be enabled with Code 3 prior to configuration.

0 Operating mode

[MAN] Manual mode

AUtO Automatic mode

SAFE Fail-safe position

ESC Escape

Switchover from automatic to manual mode is smooth.In fail-safe mode, S appears on the display.In MAN and AUtO mode, the system deviation is represented bythe bar graph elements.When the positioner is initialized, the numerical display indicatesthe valve position or the angle of rotation in %, otherwise the po-sition of the lever in relation to the central axis is displayed in de-grees °.

1 Manual w

0 to 100 [0] %of the nominal range

Adjust the manual set point with the rotary pushbutton, thecurrent travel/angle is displayed in % when the positioner is ini-tialized, otherwise the position of the lever in relation to the cen-tral axis is indicated in degrees °.

Note: Can only be selected when Code 0 = MAN

2 Reading direction

[Normal] or upside down

ESC

The reading direction of the display is turned by 180°.

3 Enable configuration

[No] YES ESC

Enables the option to modify data (automatically deactivatedwhen the rotary pushbutton has not been operated for 120 s).

EB 8384-2 EN 81

Code list

Page 82: Val Vu La Caldera

Codeno.

Parameter – Readings,values [default setting] Description

Note: Codes with marked with an asterisk (*) must be enabled with Code 3 prior to configuration.

4* Pin position

[No]

17, 25, 35, 50, 70, 100,200, 300 mm

90° with rotary actuators

ESC

Note: If you select a pinposition in Code 4 that is toosmall, the positioner switchesto SAFE mode for reasons ofsafety

The follower pin must be inserted into the correct pin position ac-cording to the valve travel/angle of rotation.

For initialization using NOM or SUb, this pin position must beentered.

Pin position Standard Adjustment range

Code 4 Code 5 Code 5

17 7.5 3.6 to 17.725 7.5 5.0 to 25.035 15.0 7.0 to 35.450 30.0 10.0 to 50.070 40.0 14.0 to 70.7100 60.0 20.0 to 100.0200 120.0 40.0 to 200.090° 90.0 24.0 to 100.0

5* Nominal range

[15.0] mm or angle °

ESC

For initialization using NOM or SUb, the nominal travel/angle ofrotation of the valve must be entered.The permissible adjustment range depends on the pin positionaccording to the table for Code 4.

After initialization has been successfully completed, the max-imum nominal travel/angle reached on initialization is dis-played.

6* Init mode

[MAX]

NOM

MAN

SUb

ZP

ESC

Select the initialization mode

MAX: Travel/angle of the closure member from the CLOSEDposition to the opposite stop in the actuator.

NOM: Travel/angle of the closure member measured from theCLOSED position to the indicated OPEN position.

MAN: Manually selected range

SUb: Substitute calibration (without initialization)

ZP: Zero calibration

82 EB 8384-2 EN

Code list

Page 83: Val Vu La Caldera

Codeno.

Parameter – Readings,values [default setting] Description

Note: Codes with marked with an asterisk (*) must be enabled with Code 3 prior to configuration.

7* w/x

[ää] increasing/increasingäæ increasing/decreasingESC

Direction of action of the reference variable w in relation to thetravel/angle of rotation x

Automatic adaptation:AIR TO OPEN:On completing initialization, the direction of action remains in-creasing/increasing (ää), a globe valve opens as the mA signalincreases.

AIR TO CLOSE:On completing initialization, the direction of action changes toincreasing/decreasing (äæ), a globe valve closes as the mAsignal increases.

8* Travel/angle range start(lower x-range value)

0.0 to 80.0 [0.0] % of thenominal range

ESC

Note: Specified in mm orangle ° provided Code 4 isset

Lower range value for the travel/angle of rotation in the nominalor operating range.The operating range is the actual travel/angle of the controlvalve and is limited by the lower x-range value (Code 8) and theupper x-range value (Code 9).Usually, the operating range and the nominal range are iden-tical. The nominal range can be limited to the operating rangeby the lower and upper x-range values.Value is displayed or must be entered.

The characteristic is adapted. See also the example in Code 9!

9* Travel/angle range end(upper x-range value)

20.0 to 100.0 [100.0] % ofthe nominal range

ESC

Note: Specified in mm orangle ° provided Code 4 isset

Upper range value for the travel/angle of rotation in the nominalor operating range.Value is displayed or must be entered.The characteristic is adapted.

Example: The operating range is modified, for example, to limitthe range of a control valve which has been sized too large. Forthis function, the entire resolution range of the reference variableis converted to the new limits. 0 % on the display corresponds tothe adjusted lower limit and 100 % to the adjusted upper limit.

10* Travel/angle lower limit(lower x-limit)

0.0 to 49.9 % of theoperating range

[No], ESC

Limitation of the travel/angle of rotation downwards to the en-tered value, the characteristic is not adapted.

The characteristic is not adapted to the reduced range. See alsoexample in Code 11.

EB 8384-2 EN 83

Code list

Page 84: Val Vu La Caldera

Codeno.

Parameter – Readings,values [default setting] Description

Note: Codes with marked with an asterisk (*) must be enabled with Code 3 prior to configuration.

11* Travel/angle upper limit(upper x-limit)

50.0 to 120.0 [100] % ofthe operating range

No, ESC

Limitation of the travel/angle of rotation upwards to the enteredvalue, the characteristic is not adapted.

Example: In some applications, it is better to limit the valvetravel, e.g. if a certain minimum medium flow is required or amaximum flow must not be reached.The lower limit must be adjusted with Code 10, and the upperlimit with Code 11.If a tight-closing function has been set up, it has priority over thetravel limitation!

When set to No, the valve can be opened past the nominal travelwith a reference variable outside of the 0 to 100 % range.

12* w-start

0.0 to 75.0 [0.0] % of thereference variable range

ESC

Lower range value of the applicable reference variable rangemust be smaller than the final value w-end, 0 % = 4 mAThe reference variable range is the difference between w-endand w-start, and must be ∆w ≥ 25 % = 4 mA.

For an adjusted reference variable range of 0 to 100 % = 4 to20 mA, the control valve must move through its entire operatingrange from 0 to 100 % travel/angle of rotation.

In split-range operation, the valves operate with smaller refer-ence variables. The control signal of the control unit to controltwo valves is divided such, for instance, that the valves movethrough their full travel/angle of rotation at only half the inputsignal (first valve set to 0 to 50 % = 4 to 12 mA and second valveset to 50 to 100 % =12 to 20 mA reference variable).

13* w-end

25.0 to 100.0 [100.0] % ofthe reference variable range

ESC

Upper range value of the applicable reference variable range,must be greater than w-start.

100 % = 20 mA

14* Set point cutoff decrease

0.0 to 49.9 [1.0] %of the span adjusted viaCode 12/13No, ESC

If w approaches the percentage adjusted at the final value thatcauses the valve to close, the actuator is immediately completelyvented (with AIR TO OPEN) or filled with air (with AIR TOCLOSE). This action always lead to maximum tight-closing of thevalve.

Codes 14/15 have priority over Codes 8/9/10/11.

Codes 21/22 have priority over Codes 14/15.

84 EB 8384-2 EN

Code list

Page 85: Val Vu La Caldera

Codeno.

Parameter – Readings,values [default setting] Description

Note: Codes with marked with an asterisk (*) must be enabled with Code 3 prior to configuration.

15* Set point cutoff increase

50.0 to 100.0 %of the span adjusted viaCode 12/13

[No], ESC

If w approaches the percentage adjusted at the final value thatcauses the valve to open, the actuator is immediately completelyfilled with air (with AIR TO OPEN) or vented (with AIR TOCLOSE). This action always lead to the valve being completelyopened.Codes 14/15 have priority over Codes 8/9/10/11.

Codes 21/22 have priority over Codes 14/15.

Example: Set the final position w > to 99 % for three-way valves.

16* Pressure limit

[No]

1.4 2.4 3.7 bar

ESC

The signal pressure to the actuator can be limited in stages.

After changing a pressure limit already set, the actuator must bevented once (e.g. by selecting the fail-safe position (SAFE) overCode 0).

NOTICEDo not activate the pressure limit for double-acting actuators withvalve closed position AIR TO OPEN (AtO).

17* Proportional-actioncoefficient KP (step)

0 to 17 [7]

ESC

Displaying or changing KP

Note on changing the KP and TV steps:During the initialization of the positioner, the KP and TV values areoptimized.Should the positioner show a tendency for impermissibly highpost-pulse oscillation due to additional interference, the KP andTV steps can be adapted after the initialization.For this, either the TV step can be increased in increments untilthe desired response behavior is reached or, when the maximumvalue of 4 is reached, the KP step can be decreased in incre-ments.

NOTICEChanging the KP step influences the system deviation.

18* Rate time TV (step)

1 [2] 3 4 No

ESC

Displaying or changing TV,see note under KP step

A change of the TV step has no effect on the system deviation.

EB 8384-2 EN 85

Code list

Page 86: Val Vu La Caldera

Codeno.

Parameter – Readings,values [default setting] Description

Note: Codes with marked with an asterisk (*) must be enabled with Code 3 prior to configuration.

19* Tolerance band

0.1 to 10.0 [5.0] % of theoperating range

ESC

Used for error monitoring

Determination of the tolerance band in relation to the operatingrange.Associated lag time [30] s is a reset criterion.If a transit time is determined during initialization which issix times > 30 s, the six-fold transit time is accepted as the lagtime.

20* Characteristic

0 to 9 [0]

ESC

Select the characteristic:

0 Linear

1 Equal percentage

2 Reverse equal percentage

3 SAMSON butterfly valve linear

4 SAMSON butterfly valve equal percentage

5 VETEC rotary plug valve linear

6 VETEC rotary plug valve equal percentage

7 Segmented ball valve linear

8 Segmented ball valve equal percentage

9 User-defined (defined over operating software)

Note: The various characteristics are listed in the Appendix(section 16).

21* Required transit time OPEN(w ramp open)

0 to 240 s [0]

ESC

The time required to pass through the operating range when thevalve opens.Limitation of the transit time (Code 21 and 22):For some applications it is recommendable to limit the transit timeof the actuator to prevent it from engaging too fast in the runningprocess.Code 21 has priority over Code 15.

NOTICEThe function is not activated when the fail-safe function or sole-noid valve is triggered nor upon failure of the auxiliary power.

22* Required transit timeCLOSED (w ramp closed)

[0] to 240 s

ESC

The time required to pass through the operating range when thevalve closes.Code 22 has priority over Code 14.

NOTICEThe function is not activated when the fail-safe function or sole-noid valve is triggered nor upon failure of the auxiliary power.

86 EB 8384-2 EN

Code list

Page 87: Val Vu La Caldera

Codeno.

Parameter – Readings,values [default setting] Description

Note: Codes with marked with an asterisk (*) must be enabled with Code 3 prior to configuration.

23* Total valve travel

0 to 99 · 107 [0]Exponential reading from 9999 travelcycles onwards

RES, ESC

Totaled double valve travel.

Can be reset to 0 over Code 36 - Std.

Note: The total valve travel is saved in a non-volatile memoryafter every 1000 double travel.

24* LV total valve travel

1000 to 99 · 107

[1 000 000]Exponential reading from 9999 travelcycles onwards

ESC

Limit value of total valve travel. If the limit is exceeded, andicons appear on the display.

25* Alarm mode

0 to 3 [2]

ESC

Switching mode of software limit switches alarm A1 and A2 inresponding state (when positioner has been initialized).

1) Explosion-protected version according to EN 60947-5-6

0: A1 ≥ 2.2 mA A2 ≤ 1.0 mA1: A1 ≤ 1.0 mA A2 ≤ 1.0 mA2: A1 ≥ 2.2 mA A2 ≥ 2.2 mA3: A1 ≤ 1.0 mA A2 ≥ 2.2 mA

2) Version without explosion protection

0: A1 R = 348 Ω A2 Non-conducting1: A1 Non-conducting A2 Non-conducting2: A1 R = 348 Ω A2 R = 348 Ω3: A1 Non-conducting A2 R = 348 ΩWhen a positioner has not been initialized, the software limitswitches always register the signal as in the state of no response.If there is no mA signal at the terminals 11/12, the software limitswitches both switch to ≤ 1.0 mA signal (Ex) or non-conducting(without explosion protection).

Note: The fault alarm output always switches to ≤ 1.0 mA/non-conducting in case of fault arises;it has ≥ 2.2 mA/R = 348 Ω when there is no fault.

EB 8384-2 EN 87

Code list

Page 88: Val Vu La Caldera

Codeno.

Parameter – Readings,values [default setting] Description

Note: Codes with marked with an asterisk (*) must be enabled with Code 3 prior to configuration.

26* Limit value A1

No0.0 to 100.0 [2.0] % of theoperating range

ESC

Alarm A1 goes into the state of response when the value exceedsthe limit.Displaying or changing the software limit value A1 in relation tothe operating range.Setting has no effect when an inductive limit switch has been in-stalled.

27* Limit value A2

No0.0 to 100.0 [98.0] % of theoperating range

ESC

Alarm A2 goes into the state of response when the value fallsbelow the limit.Displaying or changing the software limit value A2 in relation tothe operating range.

28* Alarm test

Reading direction:

Standard Turned[No] [No]RUN 1 1 RUNRUN 2 2 RUNRUN 3 3 RUN

ESC ESC

Testing the software limit switches alarm A1 and A2 in additionto the fault alarm contact A3.If the test is activated, the respective limit switches five times.

RUN1/1 RUN: Software limit switch A1 to ≥ 2.2 mARUN2/2 RUN: Software limit switch A2 to ≥ 2.2 mARUN3/3 RUN: Fault alarm contact A3 to ≤ 1.0 mA

29* Position transmitter x/ix 3)

[ää]äæ

ESC

Operating direction of the position transmitter; indicates how thetravel/angle position is assigned to the output signal i, based onthe closed position.

The operating range (see Code 8) of the valve is represented bythe 4 to 20 mA signal. Values exceeding or falling below thelimits 2.4 to 21.6 mA can be represented.When a positioner has not been initialized (reference variableless than 3.6 mA), the power consumption of the feedback signalis effective (current approx. 1.8 mA).When YES is set in Code 32, the position transmitter issues thevalue as per Code 30 during initialization or zero calibration.When No is set in Code 32, 4 mA is issued during a runningself-adaptation.

88 EB 8384-2 EN

Code list

Page 89: Val Vu La Caldera

Codeno.

Parameter – Readings,values [default setting] Description

Note: Codes with marked with an asterisk (*) must be enabled with Code 3 prior to configuration.

30* Fault alarm ix 3)

[No]

HI LO

ESC

Used to select whether faults causing the fault alarm contact toswitch should also be signaled by the position transmitter outputand how they should be signaledHI ix = 21.6 ±0.1mA or LO ix = 2.4 ±0.1mA

31* Position transmitter test 3)

–10.0 to 110.0 [defaultvalue is last indicated valueof the position transmitter]% of the operating range

ESC

Testing the position transmitter. Values can be entered in relationto the operating range.The current actual value is used in initialized positioners locallyas the start value (bumpless changeover to the test mode). Ontesting over software, the entered simulation value is issued asthe position feedback signal for 30 seconds.

3)Analog position transmitter: Code 29/30/31 can only be selected if the position transmitter (optional) is installed.

32* Fault alarm with “Functioncheck” condensed state

[YES] · No

ESC

YES: Fault alarm also with “Function check” condensed state

No: “Function check” condensed state does not cause a faultalarm to be issued

Note: Regardless of the condensed state, the fault alarm outputalways switches when error codes 57, 58, 60, 62 and 64 to 70,76 are issued.

33* Fault alarm with “Mainte-nance required” condensedstate

[YES] · NoESC

YES: Fault alarm only with “Maintenance alarm” condensed stateand with “Maintenance required” condensed state

No: Fault alarm only with “Maintenance alarm” condensed state

Note: Regardless of the condensed state, the fault alarm outputalways switches when error codes 57, 58, 60, 62 and 64 to 70,76 are issued.

34* Closing direction

CL [CCL]

ESC

CL: Clockwise, CCL: CounterclockwiseTurning direction in which the valve is moved to the CLOSED po-sition (view onto the rotary switch motion when the positionercover is open).Note: Needs only be entered in initialization mode SUb(Code 6).

35* Blocking position

[0] mm/° /%

ESC

Entering the blocking position.Distance up to the CLOSED position.

Note: Only necessary in initialization mode SUb.

EB 8384-2 EN 89

Code list

Page 90: Val Vu La Caldera

Codeno.

Parameter – Readings,values [default setting] Description

Note: Codes with marked with an asterisk (*) must be enabled with Code 3 prior to configuration.

36* Reset

[No]

Std · diAG

ESC

Std: Resets all parameters to default (factory setting) as wellas the diagnosis data. After a reset, the positioner mustbe re-initialized.

diAG: Resets diagnosis data only. Plotted reference graphs andlogs remain unaffected. The positioner does not need tobe re-initialized.

37 Position transmitter

No · YES

Display only,indicates whether the position transmitter option is installed.

38* Inductive alarm

[No], YES, ESC

Indicates whether the inductive limit switch option is installed ornot.

39 System deviation e info

–99.9 to 999.9 %

Display only,indicates the deviation from the target position (e = w – x).

40 Transit time Open info

0 to 240 s [0]

Display only,minimum opening time determined during initialization.

41 Transit time Closed info

0 to 240 s [0]

Display only,minimum closing time determined during initialization.

42 Auto-w/manual-w info

0.0 to 100.0 % of the span

4 to 20 mA

Display only,Supplied automatic reference variable according to 4 to 20 mA

43 Firmware info

Xxxx

Display only,indicates the positioner type and current firmware version inalternating sequence.

44 y info

[0] to 100 %

0 P, MAX, – – –

Display only.

Indicates the control signal y in % based on the travel range de-termined on initialization

MAX: The positioner builds up its maximum output pressure,see description in Code 14 and 15.

0 P: The positioner vents completely, see description in Code14 and 15.

– – –: The positioner is not initialized.

90 EB 8384-2 EN

Code list

Page 91: Val Vu La Caldera

Codeno.

Parameter – Readings,values [default setting] Description

Note: Codes with marked with an asterisk (*) must be enabled with Code 3 prior to configuration.

45 Solenoid valve info

YESHIGH/LOWNo

Display only,indicates whether a solenoid valve is installed or not.If a voltage supply is connected at the terminals of the installedsolenoid valve, YES and HIGH appear on the display in alter-nating sequence. If a voltage supply is not connected (actuatorvented, fail-safe position indicated on the display by the S icon),YES and LOW appear on the display in alternating sequence.

48*

49*

Diagnostics (refer to EB 8389 EN on EXPERTplus valve diagnostics)

Note: The error codes listed in following appear in the display corresponding to their statusclassification set over the condensed state (Maintenance required/Maintenance demanded:

, Out of specification: blinking, Maintenance alarm: ). If “No message” is assignedto the error code as the status classification, the error is not included in the condensed state.A status classification is assigned to every error code in the default setting. The status classifi-cation of error codes can also be changed as required using an operating software (e.g.TROVIS-VIEW).

EB 8384-2 EN 91

Code list

Page 92: Val Vu La Caldera

Initialization errors

Error codes – Recommended action Condensed state alarm active, when prompted, Err appears.When error messages exist, they are displayed here.

50 x > range The value supplied by the measuring signal is either too high ortoo low, the measuring sensor is close to its mechanical limit.• Pin positioned incorrectly.• Bracket slipped in case of NAMUR attachment or positioner is

not central.• Follower plate incorrectly attached.

Status classification [Maintenance required]

Recommended action Check attachment and pin position, set operating mode fromSAFE to MAN and re-initialize the positioner.

51 ∆x < range The measuring span of the sensor is too low.

• Pin positioned incorrectly.• Wrong lever.

A rotational angle smaller than 16° at the positioner shaft onlygenerates a message. An angle below 9° leads to the initializati-on being canceled.

Status classification [Maintenance required]

Recommended action Check attachment and re-initialize the positioner.

52 Attachment • Positioner attachment incorrect.

• Nominal travel/angle (Code 5) could not be reached duringinitialization under NOM (no tolerance downwardspermissible).

• Mechanical or pneumatic fault, e.g. wrong lever selected orsupply pressure too low to move to the required position.

Status classification [Maintenance required]

Recommended action Check attachment and supply pressure. Re-initialize thepositioner.Under certain circumstances, it may be possible to check themaximum travel/angle by entering the actual pin position andthen performing an initialization under MAX.After initialization has been completed, the Code 5 indicates themaximum achieved travel or angle.

92 EB 8384-2 EN

Code list

Page 93: Val Vu La Caldera

Error codes – Recommended action Condensed state alarm active, when prompted, Err appears.When error messages exist, they are displayed here.

53 Initialization time exceeded(Init time >)

The initialization routine lasts too long.

• No pressure on the supply line or there is a leak.• Supply air failure during initialization.

Status classification [Maintenance required]

Recommended action Check attachment and supply pressure.Re-initialize the positioner.

54 Initialization - solenoidvalve

1) A solenoid valve is installed (Code 45 = YES) and wasnot or not properly connected so that an actuator pressurecould not be built up. The message is generated when youattempt to initialize the positioner.

2) If you attempt to initialize the device from the fail-safeposition (SAFE).

Status classification [Maintenance required]

Recommended action Re. 1) Check connection and supply voltage of the forced ventingCode 45 HIGH/LOW

Re. 2) Set the MAN operating mode over Code 0. Then initializethe positioner.

55 Transit time too short(transit time <)

The actuator positioning rates determined during the initializati-on are so short that the positioner cannot adapt itself optimally.

Status classification [Maintenance required]

Recommended action Check the volume restriction setting as described in section 7.2,re-initialize the positioner.

56 Pin position Initialization was canceled because you are required to enter thepin position for the selected initialization modes NOM and SUb.

Status classification [Maintenance required]

Recommended action Enter pin position over Code 4 and nominal travel/angle overCode 5. Re-initialize the positioner.

EB 8384-2 EN 93

Code list

Page 94: Val Vu La Caldera

Operational errors

Error codes – Recommended action Condensed state alarm active, when prompted, Err appears.When error messages exist, they are displayed here.

57 Control loop Control loop error, the control valve does not react within the tol-erable times of the controlled variable (tolerance band alarmCode 19).

• Actuator mechanically blocked.• Attachment of the positioner subsequently shifted.• Supply pressure not sufficient.

Status classification [Maintenance required]

Recommended action Check attachment.

58 Zero point Zero point incorrect.Error may arise when the mounting position/linkage of the posi-tioner moves or when the valve seat trim is worn, especially withsoft-sealed plugs.

Status classification [Maintenance required]

Recommended action Check valve and mounting of the positioner. If OK, perform azero calibration over Code 6 (see section 7.7 on page 70).

We recommend re-initializing the positioner when zero point de-viations over 5 % occur.

59 Autocorrection Should an error occur in the data range of the positioner, theself-monitoring function recognizes it and automatically correctsit.

Status classification [No message]

Recommended action Automatic

60 Fatal error An error was detected in the data relevant for safety,autocorrection is not possible. This may be due to EMCdisturbances.

The positioner changes to the fail-safe position (SAFE).

Status classification Maintenance alarm (cannot be classified)

Recommended action Reset over Code 36 - Std.Re-initialize the positioner.

94 EB 8384-2 EN

Code list

Page 95: Val Vu La Caldera

Hardware errors

Error codes – Recommended action Condensed state alarm active, when prompted, Err appears.When error messages exist, they are displayed here.

62 x signal Determination of the measured data for the actuator has failed.Conductive plastic element is defective.The positioner continues to run in emergency mode, but shouldbe replaced as soon as possible.The emergency mode on the display is indicated by a blinkingclosed-loop operation icon and 4 dashes instead of the positionindication.

Note on the closed-loop operation:If the measuring system has failed, the positioner is still in a reli-able state. The positioner switches to emergency mode where theposition cannot be accurately controlled anymore. However, thepositioner continues to operate according to its reference vari-able signal so that the process remains in a safe state.

Status classification [Maintenance demanded]

Recommended action Return the positioner to SAMSON AG for repair.

63 w too small The reference variable is much smaller than 4 mA (0 %); occurs ifthe power source that drives the positioner does not comply withthe standard.This state is indicated on the positioner display by a blinkingLOW.

Recommended action [No message]

Remedy Check reference variable.If necessary, limit the current source downwards so that no valuesbelow 4 mA can be issued.

64 i/p converter The circuit of the i/p converter has been interrupted.

Status classification Maintenance alarm (cannot be classified)

Recommended action Cannot be remedied.Return the positioner to SAMSON AG for repair.

EB 8384-2 EN 95

Code list

Page 96: Val Vu La Caldera

Error codes – Recommended action Condensed state alarm active, when prompted, Err appears.When error messages exist, they are displayed here.

65 Hardware Initialization key jammed (firmware version 1.51 and higher).

A hardware error has occurred, the positioner changes to thefail-safe position (SAFE).

Status classification [Maintenance alarm]

Recommended action Check initialization key.

Confirm error and return to the automatic operating mode, orperform a reset and re-initialize the device. If this is not success-ful, return device to SAMSON AG for repair.

66 Data memory The writing of data to the data memory does not work anymore,e.g. when the written data deviate from the read data.Valve moves to the fail-safe position.

Status classification Maintenance alarm (cannot be classified)

Recommended action Return the positioner to SAMSON AG for repair.

67 Test calculation The hardware controller is monitored by means of a testcalculation.

Status classification [Maintenance alarm]

Recommended action Confirm error. If this is not possible, return the positioner toSAMSON AG for repair.

96 EB 8384-2 EN

Code list

Page 97: Val Vu La Caldera

Data errors

Error codes – Recommended action Condensed state alarm active, when prompted, Err appears.When error message exist, they are displayed here.

68 Control parameter Control parameter error

Status classification [Maintenance required]

Recommended action Confirm error, perform reset and re-initialize the positioner.

69 Poti parameter Parameter error of the digital potentiometer.

Status classification [Maintenance required]

Recommended action Confirm error, perform reset and re-initialize the positioner.

70 Calibration parameter Error in the production calibration data. Subsequently, the deviceruns on default values.

Status classification [Maintenance required]

Recommended action Return the positioner to SAMSON AG for repair.

71 General parameters Parameter errors that are not critical for the control.

Status classification [Maintenance required]

Recommended action Confirm error.Check and, if necessary, reset required parameters.

73 Internal device error 1 Internal device error

Status classification [Maintenance required]

Recommended action Return the positioner to SAMSON AG for repair.

75 Info parameter Internal positioner error

Status classification [Maintenance required]

Recommended action Confirm error.Check and, if necessary, reset required parameters.

EB 8384-2 EN 97

Code list

Page 98: Val Vu La Caldera

Error codes – Recommended action Condensed state alarm active, when prompted, Err appears.When error message exist, they are displayed here.

76 No emergency mode The travel measuring system of the positioner has aself-monitoring function (see Code 62).An emergency mode (open-loop control) is not available forcertain actuators, such as double-acting actuators. In this case,the positioner changes to the fail-safe position (SAFE) when ameasuring error occurs. During the initialization, the positionerchecks whether the actuator has such a function or not.

Status classification [No message]

Recommended action Merely information, confirm, if necessary.No further action necessary.

77 Program loading errorAdditional alarm at the faultalarm output

When the positioner starts operation for the first time after the in-put signal has been applied, it carries out a self-test (tEStinG runsacross the display).If the positioner loads the wrong program, the valve moves to thefail-safe position. It is not possible to make the valve leave thisfail-safe position again.

Status classification Maintenance alarm (cannot be classified)

Recommended action Interrupt current and restart positioner.Otherwise, return the positioner to SAMSON AG for repair.

78 Options parameter Errors in options parameters

Status classification [Maintenance required]

Recommended action Return the positioner to SAMSON AG for repair.

98 EB 8384-2 EN

Code list

Page 99: Val Vu La Caldera

Diagnosis errors

Error codes – Recommended action Condensed state alarm active, when prompted, Err appears.When error messages exist, they are displayed here.

79 Extended diagnostics Messages are generated by the extended EXPERTplus diagnostics(refer to EB 8389 on EXPERTplus valve diagnostics)

Status classification Maintenance required (cannot be classified)

80 Diagnostic parameters Errors that are not critical for control.

Status classification Maintenance required (cannot be classified)

Recommended action Confirm error.Check and, if necessary, perform a new reference test

81 Reference graphs An error occurred during plotting the reference graphs for drivesignal y steady-state or drive signal y hysteresis.

• Reference test was interrupted• Reference line for drive signal y steady-state or drive signal y

hysteresis was not adopted.

Error messages are saved in a non-volatile memory. They cannotbe reset.

Status classification [Maintenance required]

Recommended action Check and, if necessary, perform a new reference test

EB 8384-2 EN 99

Code list

Page 100: Val Vu La Caldera

15 Dimensions in mm

100 EB 8384-2 EN

Dimensions in mm

40

34

210

2814

80

164 Output (38) Supply (9)

86

70

15

46

34 70

70

28Schild

58

58

Fig. 28a · NAMUR and direct attachment

Direct attachment

Attachment acc. to IEC 60534-6

Lever mmS = 17M = 50L = 100XL = 200

Pressure gaugebracket or connecting plate

Externalposition sensor

M20 x 1.5

Page 101: Val Vu La Caldera

EB 8384-2 EN 101

Dimensions in mm

62

164

38

200

164

164

13

62

24

Fig. 28b · Attachment according to VDI/VDE 3847

Attachment according to VDI/VDE 3847to Type 3277

Attachment according toVDI/VDE 3847on NAMUR rib

Page 102: Val Vu La Caldera

102 EB 8384-2 EN

Dimensions in mm

56

86

13080

166

3086

Ø 101

80

52 Output Y1

Output Y2

Supply (9)

Output Y1

Output Y2

A1 Z

A2

Output A1

Output A2

Supply (9)

50 80

58

130

49

59

79

76

50

150

Reversing amplifier(optional)*

Connectingplate G ¼or ¼ NPT

Heavy-duty version

Light version

* Reversing amplifier

– Type 3710 (see drawing of heavy-duty version fordimensions)

– 1079-1118/1079-1119, no longer available(see drawing of light version for dimensions)

Reversing amplifier(optional)*

Fig. 28c · Attachment to rotary actuators VDI/VDE 3845 (Sept. 2010), level 1, size AA1 to AA4

Page 103: Val Vu La Caldera

15.1 Fixing levels according to VDI/VDE 3845 (September 2010)

EB 8384-2 EN 103

Dimensions in mm

A

M6

C

B

25

Mmin

Ød

ØD

Level 2 (bracket surface)

Level 1 (actuator surface)

Actuator

Dimensions in mm

Size A B C ∅ d Mmin ∅ D*

AA0 50 25 15 5.5 for M5 66 50

AA1 80 30 20 5.5 for M5 96 50

AA2 80 30 30 5.5 for M5 96 50

AA3 130 30 30 5.5 for M5 146 50

AA4 130 30 50 5.5 for M5 146 50

AA5 200 50 80 6.5 for M6 220 50

* Flange type F05 according to DIN EN ISO 5211

x

zy

Fig. 29 · Lever

1610...17

Lever x y z

S 17 mm 25 mm 33 mm

M 25 mm 50 mm 66 mm

L 70 mm 100 mm 116 mm

XL 100 mm 200 mm 216 mm

Page 104: Val Vu La Caldera

16 Valve characteristic selection

The characteristics that can be selected in Code 20 are shown in following in graph form.

Note: A characteristic can only be defined (user-defined characteristic) using a workstation/operating software (e.g. TROVIS-VIEW).

Linear (select characteristic: 0)

Equal percentage (select characteristic: 1) Rev. equal percentage (select characteristic: 2)

104 EB 8384-2 EN

Valve characteristic selection

0

50

100

0 50 100

Travel/ angle of rotation [%]

Reference variable [%]

0

50

100

0 50 100

Travel/ angle of rotation [%]

Reference variable [%]

0

50

100

0 50 100

Travel/ angle of rotation [%]

Reference variable [%]

Page 105: Val Vu La Caldera

SAMSON butterfly valve linear(select characteristic: 3)

SAMSON butterfly valve equal percentage(select characteristic: 4)

VETEC rotary plug valve linear(select characteristic: 5)

VETEC rotary plug valve equal percentage(select characteristic: 6)

Segmented valve ball linear(select characteristic: 7)

Segmented ball valve equal percentage(select characteristic: 8)

0

50

100

0 50 100

Travel/ angle of rotation [%]

Reference variable [%]

0

50

100

0 50 100

Travel/ angle of rotation [%]

Reference variable [%]0

50

100

0 50 100

Travel/ angle of rotation [%]

Reference variable [%]

0

50

100

0 50 100

Travel/ angle of rotation [%]

Reference variable [%]

0

50

100

0 50 100

Travel/ angle of rotation [%]

Reference variable [%]0

50

100

0 50 100

Travel/ angle of rotation [%]

Reference variable [%]

Page 106: Val Vu La Caldera

106 EB 8384-2 EN

Page 107: Val Vu La Caldera

EB8384-2 EN

107

,17(51$7,21$/(/(&7527(&+1,&$/&200,66,21

,(&&HUWLILFDWLRQ6FKHPHIRU([SORVLYH$WPRVSKHUHV

IRUUXOHVDQGGHWDLOVRIWKH,(&([6FKHPHYLVLWZZZLHFH[FRP

Certificate No.: ,(&([37% Issue No.:

Status: &XUUHQW

Date of Issue: Page of

Applicant: 6$0621$*0HVVXQG5HJHOWHFKQLNWeismuellerstrasse 3 D-60314 Frankfurt am Main *HUPDQ\

Electrical Apparatus: HSSRVLWLRQHUW\SH2SWLRQDODFFHVVRU\

Type of Protection: *HQHUDO5HTXLUHPHQWV,QWULQVLF6DIHW\3URWHFWLRQE\(QFORVXUH

Marking: ([LD,,&777,3DQG,37&

$SSURYHGIRULVVXHRQEHKDOIRIWKH,(&([&HUWLILFDWLRQ%RG\

Dr.-Ing. Ulrich Johannsmeyer

3RVLWLRQ Department Head "Intrinsic Safety and Safety of Systems

6LJQDWXUHIRUSULQWHGYHUVLRQ

'DWH

1. This certificate and schedule may only be reproduced in full. 2. This certificate is not transferable and remains the property of the issuing body. 3. The Status and authenticity of this certificate may be verified by visiting the Official IECEx Website.

Certificate issued by:

%XQGHVDOOHH%UDXQVFKZHLJ

*HUPDQ\

Certificate No.: ,(&([37%

Date of Issue: Issue No.:

Page of

Manufacturer: 6$0621$*0HVVXQG5HJHOWHFKQLNWeismuellerstrasse 3 D-60314 Frankfurt am Main *HUPDQ\

Manufacturing location(s):

This certificate is issued as verification that a sample(s), representative of production, was assessed and tested and found to comply with the IEC Standard list below and that the manufacture’rs quality system, relating to the Ex products covered by this certificate, was assessed and found to comply with the IECEx Quality system requirements. This certificate is granted subject to the conditions as set out in IECEx Scheme Rules, IECEx 02 and Operational Documents as amended.

67$1'$5'6The electrical apparatus and any acceptable variations to it specified in the schedule of this certificate and the identified documents, was found to comply with the following standards:

,(&Edition: 3.1

Electrical apparatus for explosive gas atmospheres - Part 0: General requirements

,(&Edition: 4

Electrical apparatus for explosive gas atmospheres - Part 11: Intrinsic safety 'i'

,(&Edition: 2

Electrical apparatus for use in the presence of combustible dust - Part 1-1: Electrical apparatus protected by enclosures and surface temperature limitation - Specification for apparatus

7KLV&HUWLILFDWHGRHVQRWLQGLFDWHFRPSOLDQFHZLWKHOHFWULFDOVDIHW\DQGSHUIRUPDQFHUHTXLUHPHQWVRWKHUWKDQWKRVHH[SUHVVO\LQFOXGHGLQWKH6WDQGDUGVOLVWHGDERYH

7(67$66(660(175(32576$VDPSOHVRIWKHHTXLSPHQWOLVWHGKDVVXFFHVVIXOO\PHWWKHH[DPLQDWLRQDQGWHVWUHTXLUHPHQWVDVUHFRUGHGLQ

IECEx ATR: File Reference:

'(37% %

Page 108: Val Vu La Caldera

108EB

8384-2 EN

Certificate No.: ,(&([37%

Date of Issue: Issue No.:

Page of

(48,30(17(TXLSPHQWDQGV\VWHPVFRYHUHGE\WKLVFHUWLILFDWHDUHDVIROORZV

General description: single- or double-acting positioner for attachment to pneumatic actuators with self-balancing automatic adjustment to valve and actuator. Reference variable: 4 to 20mA, Nominal travels 3.6 to 200 mm; angles of rotation: 24 to 100° Features: Simple attachment to current linear and rotary actuators with interface for SAMSON - direct attachment. NAMUR- rib; attachment to rod-type yoke acc. to IEC 60534-6-1. Any mounting position. Options: Position indicator, software proximity switches, inductive proximity switch, forced venting function, fault alarm output, external displacement transducer and serial interface.

&21',7,2162)&(57,),&$7,21 12

$QQH[H 3730-21_Electrical data.pdf; 3730-21_Type code.pdf

Page 109: Val Vu La Caldera

EB 8384-2 EN 109

Page 110: Val Vu La Caldera

110 EB 8384-2 EN

Page 111: Val Vu La Caldera

EB 8384-2 EN 111

Page 112: Val Vu La Caldera

112 EB 8384-2 EN

Page 113: Val Vu La Caldera

EB 8384-2 EN 113

Page 114: Val Vu La Caldera

114 EB 8384-2 EN

Page 115: Val Vu La Caldera

EB 8384-2 EN 115

Page 116: Val Vu La Caldera

116 EB 8384-2 EN

Page 117: Val Vu La Caldera

EB 8384-2 EN 117

Page 118: Val Vu La Caldera

118 EB 8384-2 EN

Page 119: Val Vu La Caldera

EB 8384-2 EN 119

Page 120: Val Vu La Caldera

120 EB 8384-2 EN

Page 121: Val Vu La Caldera

EB 8384-2 EN 121

Page 122: Val Vu La Caldera

122 EB 8384-2 EN

Page 123: Val Vu La Caldera

EB 8384-2 EN 123

Page 124: Val Vu La Caldera

124 EB 8384-2 EN

Page 125: Val Vu La Caldera

EB 8384-2 EN 125

Page 126: Val Vu La Caldera

126 EB 8384-2 EN

Page 127: Val Vu La Caldera

EB 8384-2 EN 127

Page 128: Val Vu La Caldera

128 EB 8384-2 EN

Page 129: Val Vu La Caldera

EB 8384-2 EN 129

Page 130: Val Vu La Caldera

130 EB 8384-2 EN

Page 131: Val Vu La Caldera

EB 8384-2 EN 131

Page 132: Val Vu La Caldera

132 EB 8384-2 EN

Page 133: Val Vu La Caldera

EB 8384-2 EN 133

Page 134: Val Vu La Caldera

134 EB 8384-2 EN

Page 135: Val Vu La Caldera

EB 8384-2 EN 135