vfd & short circuit ratings
DESCRIPTION
VFD & Short Circuit RatingsTRANSCRIPT
-
Data Bulletin8800DB1203
03/2013
Variable Frequency Drives and Short-Circuit Current Ratings
Retain for future use.
2013 Schneider Electric All Rights Reserved
Introduction Short-circuit current ratings (SCCRs) for variable frequency drives (VFDs) is a topic that has been discussed often without clarity. Some manufacturers provide SCCRs based on testing only the output section of VFDs. While this method of test may be suitable for across-the-line starters used for motor control, Schneider Electric tests VFDs following the strictest interpretation of applicable standards and conducts SCCR tests based on the most likely failure points in the VFD, which is not the output section. Also, due to the electronic nature of VFDs, their characteristics may change depending on their electrical power system connection. The level of prospective short-circuit current (PSCC) available at the point where a VFD is connected to electrical power can have a significant impact on the safety, longevity, and cost of a VFD installation. Typical VFDs use diodes to convert AC electrical power to DC power. The DC power is stored in the VFDs capacitor bank, also called the DC bus. Insulated gate bipolar transistors (IGBTs) are then used to re-create an AC sine wave to provide power to AC induction motors. The PSCC level can have a significant thermal impact on the VFDs diodes and capacitor bank.
The following should be considered when specifying and installing a VFD:
What is the level of PSCC specified? What type of overcurrent protective device (OCPD) will be used? What type of enclosure rating is required for the installation? What are the rated thermal characteristics of the VFD? Is a line reactor or DC choke required? What is the SCCR of the VFD?This data bulletin clarifies the terms and standards used in the industry, explains the thermal impact of PSCC values on VFDs, and provides VFD installation ratings information. This bulletin also includes discussion on when to specify or install line reactors or DC chokes, and the aspects of installing a VFD without using an enclosure. In addition, the reader will understand how the cost of a VFD installation is directly proportional to the SCCR level specified. Considering these topics can lead to a robust, cost effective, and energy efficient VFD installation without over specifying rating requirements and adding unnecessary components and cost.
Terminology To address these topics, an understanding is needed of the following terms: Prospective short-circuit current Overcurrent protective device, rated as ampere interrupting capacity
(AIC) or interrupting rating (IR) VFD input rating Short-circuit current rating VFD output interrupt rating
-
Variable Frequency Drives and Short-Circuit Current Ratings 8800DB1203Terminology 03/2013
2013 Schneider Electric All Rights Reserved2
Figure 1 shows a mapping of where the terms are applied in a one-line schematic of a VFD installed in an enclosure and of a VFD installed with a Type 1 conduit kit, without the use of an additional enclosure.
Prospective Short-Circuit Current The prospective short-circuit current refers to the amount of current that would flow at a given point on the electrical distribution system if a piece of bus bar were bolted across the phases and then the power was turned on. The amount of current that would flow would be limited by the impedance of the power system. The power system impedance is the result of the resistances and reactances of the transformers and the wiring. The PSCC is the symmetrical fault current that would flow, and does not include the asymmetrical component which could occur depending on the timing of the short circuit. PSCC is also referred to as the available fault current (AFC).
Instead of specifying the system resistance and inductance, many specifications reference the PSCC level in kilo amperes. Common PSCC levels specified are 5, 10, 22, 42, 65, and 100 kA.
Overcurrent Protective Device Circuit breakers and fuses are commonly used to meet code requirements for overcurrent protection. Circuit breakers have the ability to interrupt the high current that can flow in the event of a short circuit, and typically have a rating in kAIC, which stands for thousand amperes interrupting capacity. Fuses have a similar IR specification defined in rms symmetrical amperes. Although a VFD can detect a short on the output IGBTs and stop conducting very quickly, this provides no protection upstream of the IGBT output section. Therefore, the VFD cannot carry an AIC or IR rating in the same way that a fuse or circuit breaker can, nor can it be used to meet code requirements for an overcurrent protection device.
VFD Input Rating The level of PSCC can have a significant thermal impact on the VFDs input diodes and capacitor bank. The VFDs input current increases significantly as the level of PSCC rises. This is caused by the input diodes conducting only when the input voltage is higher than the DC bus. The current is then limited only by the system impedance. Applying a VFD on an electrical system with a higher PSCC than the VFD input rating may cause
Figure 1: Terms Mapped to One-Line Schematic
M
VFD
Prospective short-circuit current at point of connection
Short-circuit current rating
Overcurrent protective device(AIC or IR)
VFD input rating
VFD output interrupt rating
Line reactor (if required)
Type 1 conduit kit
M
VFD
Enclosed VFDVFD with
Type 1 conduit kit
-
8800DB1203 Variable Frequency Drives and Short-Circuit Current Ratings03/2013 Terminology
2013 Schneider Electric All Rights Reserved 3
overheating of the diodes and capacitor sections, and reduce the life expectancy of the VFD or damage the VFD. Figure 2 shows the effects of a power system with 5 kA PSCC on the input current of a 5 hp drive. The peak input current is around 30 A.
In Figure 3 the same model drive and output load are used as in Figure 2, but the input power system is modified to provide 100 kA PSCC. Note that the input current peaks now nearly reach 70 A.
Figure 2: Input Line Current on a 5 kA PSCC Power System
T ime
500ms 550ms 600msI(L1) RMS(I(R8)) RMS(I(L1))
-80A
0A
80A
Figure 3: Input Line Current on a 100 kA PSCC Power System
T ime
500ms 550ms 600msI(L1) RMS(I(R8)) RMS(I(L1))
-80A
0A
80A
-
Variable Frequency Drives and Short-Circuit Current Ratings 8800DB1203Terminology 03/2013
2013 Schneider Electric All Rights Reserved4
When the PSCC is higher, the current peaks are much higher and the rms current is also higher. This is common for AC drives using a 6-pulse diode front-end. For more information see Schneider Electric Product Data Bulletin 8800DB0801, The Effects of Available Short-Circuit Current on AC Drives.
Because the higher current peaks occur on systems with higher PSCC, there is more heating in the input diodes and the DC bus capacitors. VFDs are designed for a specific expected maximum PSCC. The power component selection and the power section layout of the VFD design determines at what level of PSCC the product will be rated. This value is the VFD input rating. Schneider Electric publishes this rating under the column heading maximum prospective line Isc in VFD ratings tables. Schneider Electric also publishes line reactor requirements to use when the PSCC exceeds the VFD input rating in documentation that ships with each VFD.
Short-Circuit Current Rating Short-circuit current rating refers to the amount of PSCC a device such as a VFD or an enclosed VFD is rated to withstand. The National Electrical Code defines the SCCR as, The prospective symmetrical fault current at a nominal voltage to which an apparatus or system is able to be connected without sustaining damage exceeding defined acceptance criteria. The VFD or the enclosed VFD must not create a shock hazard and must contain any flame, fire, or explosion hazard during a short-circuit event. For example, an enclosed VFD with a 30 kA SCCR can be applied on a power system with a PSCC of 30 kA or less.
An enclosures SCCR is calculated from the SCCRs of the various components in the enclosure. Several papers and flow charts have been published showing how to establish the proper rating for an enclosure. The SCCR may also be determined by testing the complete assembled enclosure. Schneider Electric obtains ratings for our standard enclosed family of VFDs by testing the complete assembled enclosure in which the VFD is mounted. Testing a complete assembled enclosure is often not practical in low volume or highly customized enclosed VFDs. In these instances, the rating of the VFD itself and other products in the enclosure are used in determining the maximum SCCR of the enclosure.
The Standard Technical Panel for UL 508C voted in late 2012 to clarify the wording to ensure that all VFD manufacturers conduct tests and provide consistent SCCR data across the industry. This action will benefit customers and installers by having more standardized information available when applying VFDs. These clarifications have been written into UL 61800-5-1, which is the new UL standard for VFDs. While the effectivity date for UL 61800-5-1 is three years away, Schneider Electric has tested VFDs according to the methods described in the new standard for over a decade.
Both UL 508C and UL 61800-5-1 specify product marking information. As the physical size of VFDs decreases, manufacturers are commonly supplying the product marking information in accompanying documents. For marking the SCCR, UL 508C 57.1 uses the following phrases:
General marking:Suitable For Use On A Circuit Capable Of Delivering Not More Than ___ rms Symmetrical Amperes, ___ Volts Maximum.
For protection by a fuse:When Protected By ___ Class Fuses (with a maximum rating of ___).
For protection by a circuit breaker:When Protected By A Circuit Breaker Having An Interrupting Rating Not Less Than ___ rms Symmetrical Amperes, ___ Volts Maximum.
-
8800DB1203 Variable Frequency Drives and Short-Circuit Current Ratings03/2013 When to Use a Line Reactor or a DC Choke
2013 Schneider Electric All Rights Reserved 5
UL marking requirements may also include the manufacturer's name and the part number for the OCPD. See UL 508C 57.1.1., November 9, 2010.
Schneider Electric determines the SCCR of the VFD based on containment testing. These ratings are obtained by performing containment tests that involve shorting internal components, such as the input diodes and DC bus capacitors, while connected to the specified PSCC level and using the specified OCPD. Not all manufacturers have published ratings based on containment tests. Some manufacturers have simply provided ratings based on shorting the VFDs output. This output test method is how across-the-line starters have been tested to obtain SCCRs and does not adequately test a VFD. Schneider Electric has provided SCCRs based on the VFD input rating and containment testing, following the strictest interpretation of UL 508C. This is the language that has been clarified in UL 61000-5-1, such that in the future, all VFD manufacturers will need to conduct containment tests that involve shorting internal components and not rely on obtaining ratings for the entire VFD based on testing the output section.
If the drive is mounted in an enclosure, the enclosure must contain any shock, flame, fire or explosion hazard. Refer to "Installing a VFD without an Enclosure" on page 7 for additional comments.
Most fuses clear faster than today's circuit breakers and allow less energy to enter the VFD during a short circuit. Therefore, containing the energy is easier with fuses than with circuit breakers or Type E manual motor protective devices, and typically allows a higher SCCR.
Schneider Electric publishes a document for each VFD detailing the specific SCCR depending on PSCC, VFD input rating, and what level of PSCC requires a line reactor.
VFD Output Interrupt Rating The VFD output interrupt rating has been a point of confusion in the industry as some VFD manufacturers have published a VFD output interrupt rating leading customers and installers to think that this is the SCCR of the VFD. To determine the VFD output interrupt rating, an output short-circuit test is performed by shorting the output wires from the drive to the motor. Since the drive can detect a short circuit on the output and turn off the IGBTs in microseconds, the current never gets to a high level. This test is easily passed regardless of the PSCC. Because of this, some VFD manufacturers publish a 100 kA rating, but without clearly specifying any other ratings.
A VFD should be applied on a 100 kA power system only if the SCCR and the input rating are suitable for a 100 kA system.
When to Use a Line Reactor or a DC Choke
When the PSCC value at the point of the connection of the VFD is higher than the VFD input rating, a line reactor or DC choke must be used to reduce the PSCC and limit the current spikes discussed in Figure 2. Schneider Electric VFD installation manuals contain ratings tables that show the maximum prospective line Isc where Isc stands for current short circuit as shown in Figure 4. This Isc value is the same as the VFD input rating described in this data bulletin. This value is the highest PSCC that the VFD can be connected to without adding an external impedance such as a line reactor or DC choke. Long runs of cable and transformers also add impedance. In other rating documents this may be called an input AFC rating or an input thermal rating. These values are also provided in the installation material that ships with each VFD. A list of document numbers for each VFD can be found at the end of this bulletin.
-
Variable Frequency Drives and Short-Circuit Current Ratings 8800DB1203When to Use a Line Reactor or a DC Choke 03/2013
2013 Schneider Electric All Rights Reserved6
Instead of providing an input thermal rating, some VFD manufacturers specify that if the transformer power rating is 10 times (or some other ratio) larger than the VFD power rating, then a line reactor must be used. VFD manufacturers may require a line reactor if there is low line impedance defined as less than 1% line reactance. While these methods can be applied to Schneider Electric VFDs also, we believe the information that we are providing is much clearer and easier for customers and installers to use.
Care should be taken not to simply specify a line reactor for every installation to cover the possibility of a high PSCC. Elevated available fault currentsabove 5 kAare not present in many of the pump and fan applications in commercial, educational, healthcare, or lodging buildings. This presents a significant opportunity to reduce system costs in a majority of these facilities.
When you no longer need to specify or install a line reactor, the savings in installation costs are immediate. It eliminates the cost of purchasing a line reactor and decreases the mounting space requirements in mechanical rooms. This also lightens the weight of the installation. Also, since line reactors consume energy, their elimination removes a drag on efficiency and automatically makes a system consume less energy. In addition, line reactors give off heat. System designs without line reactors will require fewer measures for heat dissipation. Lastly, eliminating line reactors does away with the voltage drops that they cause. Unless line reactors are being specified for harmonic mitigation, line reactors or other impedance should only be specified when it has been determined that the PSCC is higher than the VFD input rating.
Figure 4: Maximum Prospective Isc Column in a Typical VFD Ratings Table
-
8800DB1203 Variable Frequency Drives and Short-Circuit Current Ratings03/2013 Example of Drive Ratings Table
2013 Schneider Electric All Rights Reserved 7
Installing a VFD without an Enclosure
It is becoming more common to mount and install a VFD without placing it in an enclosure. Two installation examples are:
1. Mounting the VFD on a mechanical room wall for controlling a pump or fan motor.
2. Mounting the VFD along a material handling conveyor to control the motor of a conveyor section.
Most VFDs have an option to attach a kit that accepts conduit connections and provide a Type 1 enclosure rating. When mounted in this fashion, the VFD itself must not create a shock hazard and contain any flame, fire, or explosion hazard during a short-circuit event. This is easier to achieve when the VFD is mounted in an enclosure, and more difficult to achieve when the VFD itself is mounted on a wall. It is common for a VFD to have a lower SCCR when mounted and installed without using an enclosure. In many cases, a wall-mounted VFD may not be able to obtain a SCCR with a circuit breaker. SCCRs with fuses are more attainable as fuses have greater energy limiting capabilities than circuit breakers on the market today.
Schneider Electric publishes SCCR information for VFDs that can be mounted in this fashion with a Type 1 enclosure rating in the information shipped with the VFD.
Example of Drive Ratings Table
Table 1 on page 8 provides short-circuit current ratings and branch circuit protection information for a portion of the Altivar 61 drive family.
The combinations in the tables have been tested per UL 508C (Reference UL file E116875).
These ratings are in addition to ratings on the nameplate of the product. The values for the overcurrent protection devices are the maximum
allowable ampere size. Smaller ampere ratings may be used. Integral solid state short-circuit protection does not provide branch circuit
protection. Branch circuit protection must be provided in accordance with the National Electrical Code and any additional local codes.
The devices are provided with software integral overload and overspeed protection for the motor. Protection at 110% of the full load motor current. The motor thermal protection current (ItH) must be set to the rated current indicated on the motor nameplate. (For details see the programming manual.)
167 F (75 C) copper conductor with the AWG wire size for all products, except ATV61HC16N4 to ATV61HC63N4, ATV61HC11Y to ATV61HC80Y: 140 F (60 C) / 167 F (75 C) copper conductor with the AWG wire size.
Suitable for use on a circuit capable of delivering not more than___X___rms symmetrical kiloAmperes,___Y___Volts maximum, when protected by___Z1___with a maximum rating of___Z2___.
-
Variable Frequency Drives and Short-Circuit Current Ratings 8800DB1203Example of Drive Ratings Table 03/2013
2013 Schneider Electric All Rights Reserved8
Tabl
e1:
Shor
t-Circ
uit C
urre
nt R
atin
gs a
nd B
ranc
h C
ircui
t Pro
tect
ion
for t
he A
ltiva
r 61
Driv
e
Alti
var 6
1Sh
ort-C
ircui
t Cur
rent
Rat
ings
1
with
Circ
uit B
reak
er 2
with
GV
P 2
with
Fus
es 2
with
Fus
es a
nd T
ype
1 ki
t 3
Inpu
tvo
ltage
50/6
0H
z
YkW
HP
A
Cat
alog
nu
mbe
rIn
put
ratin
g
kA 4
Min
imum
indu
ctan
ce
mH
Line
re
acto
rre
fere
nce
Pow
erPa
ct
(Z1)
, (Z2
) 5(X
)SC
CR
kA
Min
imum
encl
osur
evo
lum
e
(in3 )
GV
PTy
pe E
6(Z
1), (
Z2)
GV
Pvo
ltage
ratin
g
V
GV
Pm
ax.
pow
er
HP
(X)
SCC
R
kA
Min
imum
en
clos
ure
volu
me
(in3 )
Fuse
ampe
rera
ting
(Z1)
, (Z2
) A
(X)
SCC
R
kA
Min
imum
en
clos
ure
volu
me
(in3 )
Fuse
ampe
rera
ting
(Z1)
, (Z2
) A
(X)
SCC
R
kA
Min
imum
en
clos
ure
volu
me
(in3 )
Thre
e-ph
ase
inpu
t, w
ithou
t lin
e re
acto
r
200/240V
Three-phase
0.75
14.
8AT
V61H
075M
35
HJL
3601
55
4017
GV
2P10
240
1.5
516
0015
7, 8
540
1715
7, 8
510
781.
52
8AT
V61H
U15
M3
5
H
JL36
025
540
17G
V2P
1424
03
516
0025
7, 8
540
1725
7, 8
510
782.
23
11AT
V61H
U22
M3
5
H
JL36
040
540
17G
V3P
1824
05
519
2040
75
4017
25 7
, 85
1550
3
13.7
ATV6
1HU
30M
35
HJL
3604
05
4017
GV
3P18
240
3/5
519
2040
75
4017
40 7
515
504
517
.5AT
V61H
U40
M3
5
H
JL36
060
565
28G
V3P
2524
07.
55
1920
60 7
565
2845
75
1550
67.
527
.5AT
V61H
U55
M3
22
H
JL36
070
2265
28G
V3P
4024
010
528
8070
722
6528
60 7
519
878
1033
ATV6
1HU
75M
322
HJL
3611
022
6528
GV
3P50
240
105
4032
110
722
6528
70 7
527
1911
1554
ATV6
1HD
11M
3X22
HJL
3612
522
6528
GV
3P50
240
105
5760
125
722
6528
90 7
540
3615
2066
ATV6
1HD
15M
3X22
JJL3
6175
2265
28G
V3P
6524
015
557
6017
5 7
2265
2811
0 7
540
3618
2575
ATV6
1HD
18M
3X22
JJL3
6200
2213
215
20
0 7
2213
215
125
75
4900
2230
88AT
V61H
D22
M3X
22
JJ
L362
5022
1321
5
250
722
1321
515
0 7
549
0030
4012
0AT
V61H
D30
M3X
22
JJ
L362
5022
1321
5
250
722
1321
520
0 7
596
4037
5014
4AT
V61H
D37
M3X
22
JJ
L362
5022
1321
5
250
722
1321
522
5 7
596
4045
6017
6AT
V61H
D45
M3X
22
300
710
9640
380/480V
Three-phase
0.75
12.
3AT
V61H
075N
45
HLL
3601
55
4017
GV
2P08
480Y
/277
25
1600
15 7
, 85
4017
6 7,
85
1078
1.50
24.
1AT
V61H
U15
N4
5
H
LL36
015
540
17G
V2P
1048
0Y/2
774
516
0015
7, 8
540
1712
7, 8
510
782.
203
5.8
ATV6
1HU
22N
45
HLL
3601
55
4017
GV
2P14
480Y
/277
55
1600
15 7
, 85
4017
15 7
, 85
1078
3
7.8
ATV6
1HU
30N
45
HLL
3601
55
4017
GV
2P14
480Y
/277
55
1920
15 7
, 85
4017
17.5
7, 8
515
504
510
.5AT
V61H
U40
N4
5
H
LL36
025
540
17G
V3P
1348
0Y/2
777.
55
1920
25 7
, 85
4017
25 7
, 85
1550
5.5
7.5
14.3
ATV6
1HU
55N
422
HLL
3603
522
6528
GV
3P25
480Y
/277
155
2880
35 7
2265
2840
75
1987
7.5
1017
.6AT
V61H
U75
N4
22
H
LL36
050
2265
28G
V3P
2548
0Y/2
7715
528
8050
722
6528
40 7
519
8711
1527
.7AT
V61H
D11
N4
22
H
LL36
060
2265
28G
V3P
4048
0Y/2
7725
540
3260
722
6528
60 7
527
1915
2033
ATV6
1HD
15N
422
HLL
3608
022
6528
GV
3P50
480Y
/277
305
5760
80 7
2265
2870
75
4036
1825
41AT
V61H
D18
N4
22
H
LL36
100
2265
28G
V3P
5048
0Y/2
7730
586
4010
0 7
2265
2870
75
4036
2230
48AT
V61H
D22
N4
22
H
LL36
125
2265
28G
V3P
5048
0Y/2
7730
586
4012
5 7
2265
2880
75
4900
3040
66AT
V61H
D30
N4
22
H
LL36
150
2265
28G
V3P
6548
0Y/2
7740
510
368
150
722
6528
90 7
572
3037
5079
ATV6
1HD
37N
422
JLL3
6175
2213
215
17
5 7
2213
215
110
75
7230
4560
94AT
V61H
D45
N4
22
JL
L362
2522
1321
5
225
722
1321
515
0 7
1012
044
5575
116
ATV6
1HD
55N
422
JLL3
6250
2213
215
25
0 7
2213
215
175
710
1204
475
100
160
ATV6
1HD
75N
422
JLL3
6250
2238
250
25
0 7
2238
250
225
710
1204
475
100
160
ATV6
1HD
75N
422
KC
L342
5022
3825
0
250
722
3825
022
5 7
1012
044
Thre
e-ph
ase
inpu
t, w
ith li
ne re
acto
r
200/240V
Three-phase
0.75
14.
8AT
V61H
075M
35
3.00
RL0
0401
HJL
3601
510
040
17G
V2P
1024
01.
565
1600
15 7
, 810
040
1715
7, 8
510
781.
52
8AT
V61H
U15
M3
51.
50R
L008
01H
JL36
025
100
4017
GV
2P14
240
365
1600
25 7
, 810
040
1725
7, 8
510
782.
23
11AT
V61H
U22
M3
51.
25R
L012
01H
JL36
040
100
4017
GV
3P18
240
565
1920
40 7
100
4017
25 7
, 85
1550
3
13.7
ATV6
1HU
30M
35
0.80
RL0
1801
HJL
3604
010
040
17G
V3P
1824
05
6519
2040
710
040
1740
75
1550
45
17.5
ATV6
1HU
40M
35
0.80
RL0
1801
HJL
3606
010
065
28G
V3P
2524
07.
565
1920
60 7
100
6528
45 7
515
506
7.5
27.5
ATV6
1HU
55M
322
0.50
RL0
2501
HJL
3607
010
065
28G
V3P
4024
010
6528
8070
710
065
2860
75
1987
810
33AT
V61H
U75
M3
220.
40R
L035
01H
JL36
110
100
6528
GV
3P50
240
1065
4032
110
710
065
2870
75
2719
1115
54AT
V61H
D11
M3X
220.
30R
L045
01H
JL36
125
100
6528
GV
3P50
240
1065
5760
125
710
065
2890
75
4036
1520
66AT
V61H
D15
M3X
220.
25R
L055
01JJ
L361
7510
065
28G
V3P
6524
015
6557
6017
5 7
100
6528
110
75
4036
1825
75AT
V61H
D18
M3X
220.
20R
L080
01JJ
L362
0010
013
215
20
0 7
100
1321
512
5 7
549
0022
3088
ATV6
1HD
22M
3X22
0.15
RL1
0001
JJL3
6250
100
1321
5
250
710
013
215
150
75
4900
3040
120
ATV6
1HD
30M
3X22
0.10
RL1
3001
JJL3
6250
100
1321
5
250
710
013
215
200
75
9640
3750
144
ATV6
1HD
37M
3X22
0.07
5R
L160
01JJ
L362
5010
013
215
25
0 7
100
1321
522
5 7
596
4045
6017
6AT
V61H
D45
M3X
220.
055
RL2
0001
LAL3
6400
2286
40
400
722
8640
300
710
9640
Con
tinue
d on
nex
t pag
e
-
8800DB1203 Variable Frequency Drives and Short-Circuit Current Ratings03/2013 Example of Drive Ratings Table
2013 Schneider Electric All Rights Reserved 9
Thre
e-ph
ase
inpu
t, w
ith li
ne re
acto
r
380/480V
Three-phase
0.75
12.
3AT
V61H
075N
45
12R
L002
01H
LL36
015
100
4017
GV2
P08
480Y
/277
265
1600
15 7
, 810
040
176
7, 8
100
1078
1.50
24.
1AT
V61H
U15
N4
56.
5R
L004
02H
LL36
015
100
4017
GV2
P10
480Y
/277
465
1600
15 7
, 810
040
1712
7, 8
100
1078
2.20
35.
8AT
V61H
U22
N4
56.
5R
L004
02H
LL36
015
100
4017
GV2
P14
480Y
/277
565
1600
15 7
, 810
040
1715
7, 8
100
1078
3-
7.8
ATV6
1HU
30N
45
3R
L008
02H
LL36
015
100
4017
GV2
P14
480Y
/277
565
1920
15 7
, 810
040
1717
.5 7
, 810
015
504
510
.5AT
V61H
U40
N4
53
RL0
0802
HLL
3602
510
040
17G
V3P
1348
0Y/2
777.
565
1920
25 7
, 810
040
1725
7, 8
100
1550
5.5
7.5
14.3
ATV6
1HU
55N
422
2.5
RL0
1202
HLL
3603
510
065
28G
V3P
2548
0Y/2
7715
6528
8035
710
065
2840
710
019
877.
510
17.6
ATV6
1HU
75N
422
1.5
RL0
1802
HLL
3605
010
065
28G
V3P
2548
0Y/2
7715
6528
8050
710
065
2840
710
019
8711
1527
.7AT
V61H
D11
N4
221.
2R
L025
02H
LL36
060
100
6528
GV3
P40
480Y
/277
2565
4032
60 7
100
6528
15
2033
ATV6
1HD
15N
422
0.8
RL0
3502
HLL
3608
010
065
28G
V3P
5048
0Y/2
7730
6557
6080
710
065
2870
710
040
3618
2541
ATV6
1HD
18N
422
0.8
RL0
3502
HLL
3610
010
065
28G
V3P
5048
0Y/2
7730
6586
4010
0 7
100
6528
70 7
100
4036
2230
48AT
V61H
D22
N4
220.
7R
L045
02H
LL36
125
100
6528
GV3
P50
480Y
/277
3065
8640
125
710
065
2880
710
049
0030
4066
ATV6
1HD
30N
422
0.5
RL0
5502
HLL
3615
010
065
28G
V3P
6548
0Y/2
7740
6510
368
150
710
065
2890
710
072
3037
5079
ATV6
1HD
37N
422
0.4
RL0
8002
JLL3
6175
100
1321
5
175
710
013
215
110
710
072
3045
6094
ATV6
1HD
45N
422
0.4
RL0
8002
JLL3
6225
100
1321
5
225
710
013
215
150
710
012
044
5575
116
ATV6
1HD
55N
422
0.3
RL1
0002
JLL3
6250
100
1321
5
250
710
013
215
175
710
012
044
7510
016
0AT
V61H
D75
N4
220.
2R
L130
02JL
L362
5010
038
250
25
0 7
100
3825
022
5 7
100
1204
475
100
160
ATV6
1HD
75N
422
0.2
RL1
3002
KCL3
4250
100
3825
0
250
710
038
250
225
710
012
044
1An
ATV
61 d
rive
outp
ut s
hort-
circ
uit t
est w
as p
erfo
rmed
for 1
00kA
. In
addi
tion
to p
rovi
ding
a ra
ting
base
d on
sho
rting
the
outp
ut o
f the
driv
e, th
ese
shor
t-circ
uit r
atin
gs h
ave
been
obt
aine
d by
sho
rting
com
pone
nts
inte
rnal
to th
e A
ltiva
r 61
driv
e.
Thes
e ra
tings
allo
w p
rope
r coo
rdin
atio
n of
sho
rt-ci
rcui
t pro
tect
ion.
The
inte
gral
sol
id s
tate
sho
rt-ci
rcui
t pro
tect
ion
in th
e dr
ive
does
not
pro
vide
bra
nch
circ
uit p
rote
ctio
n. B
ranc
h ci
rcui
t pro
tect
ion
mus
t be
prov
ided
in a
ccor
danc
e w
ith th
e N
atio
nal
Elec
trica
l Cod
e an
d an
y lo
cal c
odes
. The
list
ed li
ne re
acto
r or m
inim
um im
peda
nce
is re
quire
d to
obt
ain
ratin
gs a
bove
the
inpu
t rat
ing.
2R
atin
gs a
pply
to a
n Al
tivar
61
driv
e m
ount
ed in
a n
on-v
entil
ated
Typ
e 1,
3R
, 4(X
), or
12
rate
d en
clos
ure.
Use
not
ed ra
tings
whe
n us
ing
a Ty
pe 1
con
duit
kit.
Min
imum
enc
losu
re v
olum
e al
low
s fo
r the
spe
cifie
d SC
CR
. You
r app
licat
ion
spec
ific
ther
mal
requ
irem
ents
may
requ
ire a
larg
er e
nclo
sure
.3
The
fuse
ratin
gs in
this
col
umn
are
for a
n A
ltiva
r 61
driv
e in
stal
led
with
a V
W3A
92
T
ype
1 co
ndui
t kit.
The
se fu
se ra
tings
in th
is c
olum
n ca
n al
so a
pply
to A
ltiva
r 61
driv
e in
stal
led
in a
Typ
e 1,
3R
, 4(X
), or
12
rate
d en
clos
ure
that
has
a m
inim
um
volu
me
liste
d in
the
tabl
e.4
This
col
umn
show
s th
e m
axim
um P
SC
C v
alue
that
can
not b
e ex
ceed
ed w
ithou
t add
ing
inpu
t im
peda
nce.
Ele
ctric
al d
istri
butio
n sy
stem
s w
ith a
hig
her P
SC
C w
ill c
ause
hig
her i
nput
cur
rent
s in
the
front
end
of t
he d
rive.
It is
pos
sibl
e fo
r the
test
ed
SCC
R ra
ting
of th
e dr
ive
to b
e lo
wer
than
this
inpu
t rat
ing.
The
test
ed S
CC
R ra
ting
can
be h
ighe
r tha
n th
is in
put r
atin
g w
hen
a lin
e re
acto
r is
used
.5
Circ
uit b
reak
ers
with
low
er in
terr
upt r
atin
gs c
an b
e us
ed w
ithin
the
sam
e ci
rcui
t bre
aker
fram
e ra
ting.
For
200
/240
Vac
, rep
lace
with
HG
L or
JG
L fo
r 65
kA in
terr
upt r
atin
g. F
or 3
80/4
80Va
c, re
plac
e w
ith H
GL
or J
GL
for 3
5kA
or H
JL o
r JJL
for
65kA
inte
rrup
t rat
ing.
For
500
/600
Vac,
repl
ace
with
HJL
for 2
5kA
or H
GL
for 1
8kA
, or H
DL
for 1
4kA
inte
rrup
t rat
ing.
648
0 V
ratin
gs a
re fo
r Wye
con
nect
ed e
lect
rical
dis
tribu
tion
syst
ems
only
. G
V2P
s
elf-p
rote
cted
man
ual c
ombi
natio
n st
arte
r mus
t be
used
with
GV2
GH
7 in
sula
ting
barr
ier t
o m
eet U
L 50
8 Ty
pe E
ratin
g.G
V3P
s
elf-p
rote
cted
man
ual c
ombi
natio
n st
arte
r mus
t be
used
with
GV3
G66
+ G
VA
M11
insu
latin
g ba
rrie
r to
mee
t UL
508
Type
E ra
ting.
7U
se fa
st a
ctin
g fu
se o
r tim
e de
lay
Cla
ss J
.8
Fuse
type
Cla
ss C
C.
Tabl
e1:
Shor
t-Circ
uit C
urre
nt R
atin
gs a
nd B
ranc
h C
ircui
t Pro
tect
ion
for t
he A
ltiva
r 61
Driv
e (c
ontin
ued)
Alti
var 6
1Sh
ort-C
ircui
t Cur
rent
Rat
ings
1
with
Circ
uit B
reak
er 2
with
GV
P 2
with
Fus
es 2
with
Fus
es a
nd T
ype
1 ki
t 3
Inpu
tvo
ltage
50/6
0H
z
YkW
HP
A
Cat
alog
nu
mbe
rIn
put
ratin
g
kA 4
Min
imum
indu
ctan
ce
mH
Line
re
acto
rre
fere
nce
Pow
erPa
ct
(Z1)
, (Z2
) 5(X
)SC
CR
kA
Min
imum
encl
osur
evo
lum
e
(in3 )
GV
PTy
pe E
6(Z
1), (
Z2)
GV
Pvo
ltage
ratin
g
V
GV
Pm
ax.
pow
er
HP
(X)
SCC
R
kA
Min
imum
en
clos
ure
volu
me
(in3 )
Fuse
ampe
rera
ting
(Z1)
, (Z2
) A
(X)
SCC
R
kA
Min
imum
en
clos
ure
volu
me
(in3 )
Fuse
ampe
rera
ting
(Z1)
, (Z2
) A
(X)
SCC
R
kA
Min
imum
en
clos
ure
volu
me
(in3 )
-
Variable Frequency Drives and Short-Circuit Current Ratings 8800DB1203Conclusion 03/2013
2013 Schneider Electric All Rights Reserved10
Conclusion Matching the drive input rating to the PSCC is not enough for proper drive installation. Careful consideration of both the containment rating and the input rating, along with their related OCPD, enclosure, and line reactor or DC choke requirements are essential.
Schneider Electric's experience with electric power distribution systems and VFDs products provides a unique position to understand the dynamics and interrelationships of these systems and products. Schneider Electric is leading the industry in providing information to allow end users, control panel builders, system integrators, and OEMs to make informed decisions with regard as to how to install a VFD, select the OCPD, and what SCCR rating can be obtained using various components. This information is available for all Altivar VFDs and can be found by a web search for the documents referred to below.
Additional documents that are available from Schneider Electric:
Document No. Drive ProductS1A58684 Altivar 12S1A73476 Altivar 212S1B16328 Altivar 312S1B39941 Altivar 32S1B86981 Altivar 61S1B86988 Altivar 71
Document No. Document Title8800DB0801 The Effects of Available Short-Circuit Current on
AC Drives8536DB0901 Motor Control Solutions for the North American
MarketCPTG005 Control Panel Technical Guide
-
8800DB1203 Variable Frequency Drives and Short-Circuit Current Ratings03/2013 Conclusion
2013 Schneider Electric All Rights Reserved 11
-
Variable Frequency Drives and Short-Circuit Current Ratings 8800DB1203Data Bulletin 03/2013
Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material.
Altivar, PowerPact, and Schneider Electric are trademarks or registered trademarks of Schneider Electric. Other trademarks used herein are the property of their respective owners.
Schneider Electric USA, Inc.8001 Knightdale Blvd.Knightdale, NC 275451-888-778-2733www.schneider-electric.us
2013 Schneider Electric All Rights Reserved12
IntroductionTerminologyProspective Short-Circuit CurrentOvercurrent Protective DeviceVFD Input RatingShort-Circuit Current RatingVFD Output Interrupt Rating
When to Use a Line Reactor or a DC ChokeInstalling a VFD without an EnclosureExample of Drive Ratings TableConclusion
/ColorImageDict > /JPEG2000ColorACSImageDict > /JPEG2000ColorImageDict > /AntiAliasGrayImages false /CropGrayImages true /GrayImageMinResolution 300 /GrayImageMinResolutionPolicy /OK /DownsampleGrayImages true /GrayImageDownsampleType /Bicubic /GrayImageResolution 300 /GrayImageDepth -1 /GrayImageMinDownsampleDepth 2 /GrayImageDownsampleThreshold 1.50000 /EncodeGrayImages true /GrayImageFilter /DCTEncode /AutoFilterGrayImages true /GrayImageAutoFilterStrategy /JPEG /GrayACSImageDict > /GrayImageDict > /JPEG2000GrayACSImageDict > /JPEG2000GrayImageDict > /AntiAliasMonoImages false /CropMonoImages true /MonoImageMinResolution 1200 /MonoImageMinResolutionPolicy /OK /DownsampleMonoImages true /MonoImageDownsampleType /Bicubic /MonoImageResolution 1200 /MonoImageDepth -1 /MonoImageDownsampleThreshold 1.50000 /EncodeMonoImages true /MonoImageFilter /CCITTFaxEncode /MonoImageDict > /AllowPSXObjects false /CheckCompliance [ /None ] /PDFX1aCheck false /PDFX3Check false /PDFXCompliantPDFOnly false /PDFXNoTrimBoxError true /PDFXTrimBoxToMediaBoxOffset [ 0.00000 0.00000 0.00000 0.00000 ] /PDFXSetBleedBoxToMediaBox true /PDFXBleedBoxToTrimBoxOffset [ 0.00000 0.00000 0.00000 0.00000 ] /PDFXOutputIntentProfile () /PDFXOutputConditionIdentifier () /PDFXOutputCondition () /PDFXRegistryName () /PDFXTrapped /False
/Description > /Namespace [ (Adobe) (Common) (1.0) ] /OtherNamespaces [ > /FormElements false /GenerateStructure false /IncludeBookmarks false /IncludeHyperlinks false /IncludeInteractive false /IncludeLayers false /IncludeProfiles false /MultimediaHandling /UseObjectSettings /Namespace [ (Adobe) (CreativeSuite) (2.0) ] /PDFXOutputIntentProfileSelector /DocumentCMYK /PreserveEditing true /UntaggedCMYKHandling /LeaveUntagged /UntaggedRGBHandling /UseDocumentProfile /UseDocumentBleed false >> ]>> setdistillerparams> setpagedevice