VI 021

S-DIAS VARAN Control Module

Operating Manual

Date of creation: 11.06.2013 Version date: 14.02.2020 Article number: 20-003-021-E

Page 2: VI 021 - sigmatek-automation.com · VI 021 S-DIAS VARAN Control Module Operating Manual Date of creation: 11.06.2013 Version date: 14.02.2020 Article number: 20-003-021-E

Publisher: SIGMATEK GmbH & Co KG

A-5112 Lamprechtshausen

Tel.: +43/6274/4321

Fax: +43/s6274/4321-18

Email: [email protected]

WWW.SIGMATEK-AUTOMATION.COM

Copyright © 2013

SIGMATEK GmbH & Co KG

Translation from German

All rights reserved. No part of this work may be reproduced, edited using an electronic system, duplicated or

distributed in any form (print, photocopy, microfilm or in any other process) without the express permission.

We reserve the right to make changes in the content without notice. The SIGMATEK GmbH & Co KG is not

responsible for technical or printing errors in the handbook and assumes no responsibility for damages that occur

through use of this handbook.

Page 3: VI 021 - sigmatek-automation.com · VI 021 S-DIAS VARAN Control Module Operating Manual Date of creation: 11.06.2013 Version date: 14.02.2020 Article number: 20-003-021-E

S-DIAS CONTROL MODULE VARAN VI 021

14.02.2020 Page 1

S-DIAS Control Module VARAN VI 021

1x VARAN In 1x VARAN Out (optional Ethernet (VtE))

The S-DIAS VI 021 module serves as the power supply and connection for decentralized S-DIAS module groups with a CPU over the VARAN bus. A module group consists of a control module and up to 32 connected S-DIAS modules.

The VARAN Out port allows the construction of the VARAN bus in a line structure.

Page 4: VI 021 - sigmatek-automation.com · VI 021 S-DIAS VARAN Control Module Operating Manual Date of creation: 11.06.2013 Version date: 14.02.2020 Article number: 20-003-021-E

VI 021 S-DIAS CONTROL MODULE VARAN

Page 2 14.02.2020

Contents

1 Technical Data ........................................................................ 3

1.1 Performance Data ......................................................................... 3

1.2 Electrical Requirements ............................................................... 3

1.3 Miscellaneous ............................................................................... 5

1.4 Environmental Conditions ........................................................... 5

2 Mechanical Dimensions ......................................................... 6

3 Connector Layout ................................................................... 7

3.1 Status LEDs ................................................................................... 8

3.2 Connectors .................................................................................... 8

3.3 Applicable Connector Cables ...................................................... 9

3.4 Applicable Connectors ............................................................... 10

3.5 Label Field ................................................................................... 11

4 Strain Relief ............................................................................12

5 Mounting .................................................................................13

6 Recommended Shielding for VARAN ..................................15

6.1 Wiring from the Control Cabinet to an External VARAN Component .................................................................................. 16

6.2 Wiring Outside of the Control Cabinet ..................................... 17

6.3 Shielding for Wiring Within the Control Cabinet ..................... 18

6.4 Connecting Noise-Generating Components ............................ 19

6.5 Shielding Between Two Control Cabinets ............................... 20

Page 5: VI 021 - sigmatek-automation.com · VI 021 S-DIAS VARAN Control Module Operating Manual Date of creation: 11.06.2013 Version date: 14.02.2020 Article number: 20-003-021-E

S-DIAS CONTROL MODULE VARAN VI 021

14.02.2020 Page 3

1 Technical Data

1.1 Performance Data

Interfaces 1x VARAN In (Tyco Mini I/O) (maximum length: 100 m)

1x VARAN Out (since FPGA 2.0: optional Ethernet (VtE)) (Tyco Mini I/O)

(maximum length: 100 m)

1.2 Electrical Requirements

Supply voltage 18-30 V DC

Supply voltage (UL) 18-30 V DC (Class 2)

Current consumption of voltage

supply

the current consumption is dependent on the connected loads

(max. 2.75 A)

Voltage supply on the S-DIAS

bus

via the VI 021

Current capacity on the S-DIAS

bus (power supply for I/O/P

modules)

+5 V +24 V

maximum 1.6 A maximum 1.6 A

For USA and Canada: The supply must be limited to: a) max. 5 A at voltages from 0-20 V DC, or b) 100 W at voltages from 20-60 V DC The limiting component (e.g. transformer, power supply or fuse) must be certified by an NRTL (Nationally Recognized Testing Laboratory).

Pour les États-Unis et le Canada: L’alimentation doit être limitée à: a) max. 5 A pour des tensions de 0-20 V DC, ou b) 100 W pour des tensions de 20-60 V DC Le composant imposant la limite (par exemple, transformateur, alimentation électrique ou fusible) doit être certifié par un NRTL (National Recognized Testing Laboratory, par exemple, UL).

Page 6: VI 021 - sigmatek-automation.com · VI 021 S-DIAS VARAN Control Module Operating Manual Date of creation: 11.06.2013 Version date: 14.02.2020 Article number: 20-003-021-E

VI 021 S-DIAS CONTROL MODULE VARAN

Page 4 14.02.2020

Page 7: VI 021 - sigmatek-automation.com · VI 021 S-DIAS VARAN Control Module Operating Manual Date of creation: 11.06.2013 Version date: 14.02.2020 Article number: 20-003-021-E

S-DIAS CONTROL MODULE VARAN VI 021

14.02.2020 Page 5

1.3 Miscellaneous

Article number 20-003-021

Hardware version 2.x

Standard UL 508 (E247993)

Approbations UL, cUL, CE

1.4 Environmental Conditions

Storage temperature -20 ... +85 °C

Environmental temperature 0 ... +55 °C

Humidity 0-95 %, non-condensing

Operating conditions Pollution degree 2

altitude up to 2000 m

EMC resistance in accordance with EN 61000-6-2 (industrial area)

EMC noise generation in accordance with EN 61000-6-4 (industrial area)

Vibration resistance EN 60068-2-6 3.5 mm from 5-8.4 Hz

1 g from 8.4-150 Hz

Shock resistance EN 60068-2-27 15 g

Protection type EN 60529 IP20

Page 8: VI 021 - sigmatek-automation.com · VI 021 S-DIAS VARAN Control Module Operating Manual Date of creation: 11.06.2013 Version date: 14.02.2020 Article number: 20-003-021-E

VI 021 S-DIAS CONTROL MODULE VARAN

Page 6 14.02.2020

2 Mechanical Dimensions

Page 9: VI 021 - sigmatek-automation.com · VI 021 S-DIAS VARAN Control Module Operating Manual Date of creation: 11.06.2013 Version date: 14.02.2020 Article number: 20-003-021-E

S-DIAS CONTROL MODULE VARAN VI 021

14.02.2020 Page 7

3 Connector Layout

The connections of the +24 V supply (X4: pin 1 and pin 2) or the GND supply (X4: pin 3 and pin 4) are internally bridged. To supply the module, only one connection to a

+24 V pin (pin 1 or pin 2) and a GND pin (pin 3 or pin 4) is required. The bridged connections may be used for further looping of the +24 V supply and the GND supply. However, it must be taken into account that a total current of 6 A per

connection is not exceeded by the forward looping!

Page 10: VI 021 - sigmatek-automation.com · VI 021 S-DIAS VARAN Control Module Operating Manual Date of creation: 11.06.2013 Version date: 14.02.2020 Article number: 20-003-021-E

VI 021 S-DIAS CONTROL MODULE VARAN

Page 8 14.02.2020

3.1 Status LEDs

Sync green ON the module is synchronized with the VARAN manager.

Reset red ON the module is in Reset.

VARAN In Link green ON the connection between the two PHYs is established.

BLINKS the VARAN In of the primary client does not have a link.

VARAN In Active yellow ON data is exchanged over the VARAN bus.

VARAN Out Link green ON the connection between the two PHYs is established.

BLINKS there is no connection between VARAN In and the primary client.

VARAN Out Active yellow ON data is exchanged over the VARAN bus.

DC OK green ON the module is supplied with +24 V.

3.2 Connectors

X1: VARAN In, X2: VARAN Out (since FPGA 2.0: optional Ethernet (VtE)) (Tyco Mini I/O)

n.c. = do not use

Pin Function

1 Tx / Rx+ 2 Tx / Rx- 3 Rx / Tx+

4-5 n.c. 6 Rx / Tx-

7-8 n.c.

Page 11: VI 021 - sigmatek-automation.com · VI 021 S-DIAS VARAN Control Module Operating Manual Date of creation: 11.06.2013 Version date: 14.02.2020 Article number: 20-003-021-E

S-DIAS CONTROL MODULE VARAN VI 021

14.02.2020 Page 9

3.3 Applicable Connector Cables

VARAN

Cable type Length Article number

RJ45 on industrial Mini I/O Type 1, drag chain capable 0.5 m 16-911-005

1 m 16-911-010

1.5 m 16-911-015

2 m 16-911-020

3 m 16-911-030

5 m 16-911-050

10 m 16-911-100

20 m 16-911-200

50 m 16-911-500

Industrial Mini I/O Type 1 on industrial Mini I/O Type 1, drag chain capable 0.5 m 16-912-005

1 m 16-912-010

1.5 m 16-912-015

2 m 16-912-020

3 m 16-912-030

5 m 16-912-050

10 m 16-912-100

20 m 16-912-200

Page 12: VI 021 - sigmatek-automation.com · VI 021 S-DIAS VARAN Control Module Operating Manual Date of creation: 11.06.2013 Version date: 14.02.2020 Article number: 20-003-021-E

VI 021 S-DIAS CONTROL MODULE VARAN

Page 10 14.02.2020

3.4 Applicable Connectors

Connectors: X1, X2: Tyco Mini I/O Plug Type 1 Lock Extend Version (not included in delivery) X3: Connector with spring terminals (included in delivery) The spring terminals are suitable connecting ultrasonically compacted (ultrasonically welded) strands. Connections:

Stripping length/Sleeve length: 10 mm

Plug-in direction: parallel to conductor axis or to PCB

Conductor cross section, rigid: 0.2-1.5 mm2

Conductor cross section, flexible: 0.2-1.5 mm2

Conductor cross section, ultrasonically compacted: 0.2-1.5 mm2

Conductor cross section AWG/kcmil: 24-16

Conductor cross section flexible, with ferrule without plastic sleeve:

0.25-1.5 mm2

Conductor cross section flexible, with ferrule with plastic sleeve: 0.25-0.75 mm2 (ground for reducing d2 of the ferrule)

IMPORTANT: The S-DIAS module CANNOT be connected or disconnected while voltage is applied!

IMPORTANT: Le module S-Dias NE PEUT PAS être inséré ou retiré sous tension.

Page 13: VI 021 - sigmatek-automation.com · VI 021 S-DIAS VARAN Control Module Operating Manual Date of creation: 11.06.2013 Version date: 14.02.2020 Article number: 20-003-021-E

S-DIAS CONTROL MODULE VARAN VI 021

14.02.2020 Page 11

3.5 Label Field

Manufacturer Weidmüller

Type MF 10/5 CABUR MC NE WS

Weidmüller article number 1854510000

Compatible printer Weidmüller

Type Printjet Advanced 230V

Weidmüller article number 1324380000

Page 14: VI 021 - sigmatek-automation.com · VI 021 S-DIAS VARAN Control Module Operating Manual Date of creation: 11.06.2013 Version date: 14.02.2020 Article number: 20-003-021-E

VI 021 S-DIAS CONTROL MODULE VARAN

Page 12 14.02.2020

4 Strain Relief

The VARAN cable must be mounted close to the module (e.g. using a clamp)! No mechanical stress can be applied to the connection!

Le câble VARAN doit être fixé à proximité du module (par exemple avec une pince)! La connexion elle-même doit être libre d'une quelconque contrainte mécanique!

Page 15: VI 021 - sigmatek-automation.com · VI 021 S-DIAS VARAN Control Module Operating Manual Date of creation: 11.06.2013 Version date: 14.02.2020 Article number: 20-003-021-E

S-DIAS CONTROL MODULE VARAN VI 021

14.02.2020 Page 13

5 Mounting

The S-DIAS modules are designed for installation into the control cabinet. To mount the modules a DIN-rail is required. The DIN rail must establish a conductive connection with the back wall of the control cabinet. The individual S-DIAS modules are mounted on the DIN rail as a block and secured with latches. The modules must be mounted horizontally (module label up) with sufficient clearance between the ventilation slots of the S-DIAS module blocks and nearby components and/or the control cabinet wall. This is necessary for optimal cooling and air circulation, so that proper function up to the maximum operating temperature is ensured.

Page 16: VI 021 - sigmatek-automation.com · VI 021 S-DIAS VARAN Control Module Operating Manual Date of creation: 11.06.2013 Version date: 14.02.2020 Article number: 20-003-021-E

VI 021 S-DIAS CONTROL MODULE VARAN

Page 14 14.02.2020

Recommended minimum distances of the S-DIAS modules to the surrounding components or control cabinet wall:

a, b, c … distances in mm (inches)

Page 17: VI 021 - sigmatek-automation.com · VI 021 S-DIAS VARAN Control Module Operating Manual Date of creation: 11.06.2013 Version date: 14.02.2020 Article number: 20-003-021-E

S-DIAS CONTROL MODULE VARAN VI 021

14.02.2020 Page 15

6 Recommended Shielding for VARAN

The VARAN real-time Ethernet bus system exhibits a very robust quality in harsh industrial environments. Through the use of IEEE 802.3 standard Ethernet physics, the potentials between an Ethernet line and sending/receiving components are separated. In the event of an error, the VARAN Manager resends messages to a bus participant immediately. The shielding described below is principally recommended.

For applications in which the bus is run outside the control cabinet, the correct shielding is required. This is especially important, if due to physical requirements, the bus cables must be placed next to sources of strong electromagnetic noise. It is recommended to avoid placing VARAN bus lines parallel to power cables whenever possible.

SIGMATEK recommends the use of CAT5e industrial Ethernet bus cables.

For the shielding, an S-FTP cable should be used.

An S-FTP bus is a symmetric, multi-wire cable with unshielded pairs. For the total shielding, a combination of foil and braiding is used. A non-laminated variant is recommended.

The VARAN cable must be secured at a maximum distance of 20 cm from the connector to protect against vibration!

Le câble VARAN doit être protégé contre les vibrations à moins de 20 cm du connecteur (par exemple à l’aide d’une pince)!

Page 18: VI 021 - sigmatek-automation.com · VI 021 S-DIAS VARAN Control Module Operating Manual Date of creation: 11.06.2013 Version date: 14.02.2020 Article number: 20-003-021-E

VI 021 S-DIAS CONTROL MODULE VARAN

Page 16 14.02.2020

6.1 Wiring from the Control Cabinet to an External VARAN Component

If the Ethernet lines are connected from a VARAN component to a VARAN node located outside the control cabinet, the shielding should be placed at the entry point to the control cabinet housing. All noise can then be deflected from the electronic components before reaching the module.

Page 19: VI 021 - sigmatek-automation.com · VI 021 S-DIAS VARAN Control Module Operating Manual Date of creation: 11.06.2013 Version date: 14.02.2020 Article number: 20-003-021-E

S-DIAS CONTROL MODULE VARAN VI 021

14.02.2020 Page 17

6.2 Wiring Outside of the Control Cabinet

If a VARAN bus line must be connected outside of the control cabinet only, no additional shield support is required. A requirement therefore is, outside the control cabinet, only IP67 modules and connectors are used. These components are very robust and noise resistant. The shielding for all sockets in IP67 modules is electrically connected internally or over the housing, whereby voltage spikes are not deflected through the electronics.

Page 20: VI 021 - sigmatek-automation.com · VI 021 S-DIAS VARAN Control Module Operating Manual Date of creation: 11.06.2013 Version date: 14.02.2020 Article number: 20-003-021-E

VI 021 S-DIAS CONTROL MODULE VARAN

Page 18 14.02.2020

6.3 Shielding for Wiring Within the Control Cabinet

Sources of strong electromagnetic noise located within the control cabinet (drives, Transformers, etc.) can induce interference in a VARAN bus line. Spike voltages are deflected over the metallic housing of a RJ45 connector. Noise is conducted through the control cabinet housing without further action from the electronic components. To eliminate sources of noise during data transfer, it is recommended that the shielding for all electronic components be connected within the control cabinet.

Page 21: VI 021 - sigmatek-automation.com · VI 021 S-DIAS VARAN Control Module Operating Manual Date of creation: 11.06.2013 Version date: 14.02.2020 Article number: 20-003-021-E

S-DIAS CONTROL MODULE VARAN VI 021

14.02.2020 Page 19

6.4 Connecting Noise-Generating Components

With the connection of power components that generate strong electromagnetic interference, it is also critical to ensure correct shielding. The shielding should be placed before a power element (or group of power elements).

Page 22: VI 021 - sigmatek-automation.com · VI 021 S-DIAS VARAN Control Module Operating Manual Date of creation: 11.06.2013 Version date: 14.02.2020 Article number: 20-003-021-E

VI 021 S-DIAS CONTROL MODULE VARAN

Page 20 14.02.2020

6.5 Shielding Between Two Control Cabinets

If two control cabinets must be connected over a VARAN bus, it is recommended that the shielding be located at the entry points of both cabinets. Noise can be thereby stopped from reaching the electronics within the control cabinet.

Page 23: VI 021 - sigmatek-automation.com · VI 021 S-DIAS VARAN Control Module Operating Manual Date of creation: 11.06.2013 Version date: 14.02.2020 Article number: 20-003-021-E

S-DIAS CONTROL MODULE VARAN VI 021

14.02.2020 Page 21

Documentation Changes

Change date Affected

page(s)

Chapter Note

29.07.2013 9 5 Mounting Chapter Mounting added

23.10.2013 4 1.4 Environmental Cond. Added Vibration resistance

23.12.2013 7

7

3 Connector Layout

3.2 Applicable Connector

Cables

Changed image

Chapter added

09.01.2014 7, 8 3.1 Applicable Connector

Cables

3.2 Applicable Connectors

Article description more detail included, Article

numbers added

Plug description more detail included

11.02.2014 6

8

3 Connector Layout

3.2 Applicable Connectors

Changed image

Changed plug description

French notes added

01.04.2014 3

4

10

1.2 Electrical Requirements

1.3 Miscellaneous

5 Mounting

Supply voltage (UL) and notice in grey box added

UL added

Text updated

15.05.2014 10 4 Strain Relief Chapter revised

18.07.2014 6 3 Connector Layout Added wiring notice

30.01.2015 8 3.4 Applicable Connectors Added note concerning connecting the S-DIAS

module while voltage is applied

26.03.2015 9 3.4 Applicable Connectors Added connections

28.04.2016 13 5 Mounting Graphics distances

17.08.2017 5

10

1.4 Environmental Conditions

3.4 Applicable Connectors

Pollution Degrees

Sleeve length added

Added info regarding ultrasonically welded strands

03.10.2017 9 3.3 Applicable Connector

Cables

RJ45 on industrial Mini I/O Type 1, drag chain

capable: 50 m cable added

18.10.2017 11

14

3.5 Label Field

5 Mounting

Added chapter

Graphic replaced

Page 24: VI 021 - sigmatek-automation.com · VI 021 S-DIAS VARAN Control Module Operating Manual Date of creation: 11.06.2013 Version date: 14.02.2020 Article number: 20-003-021-E

VI 021 S-DIAS CONTROL MODULE VARAN

Page 22 14.02.2020

19.04.2018 1

3

8

1.1 Performance Data

3.2 Connectors

(since FPGA 1.6: optional Ethernet (VtE))

19.06.2018 3 1.2 Electrical Requirements Note UL conditions

20.09.2018 3 Connector Layout Note added

14.02.2020 3

5

8

1.1 Performance Data

1.3 Miscellaneous

3.2 Connectors

Changed to FPGA 2.0

Hardware version changed

X2 connector changed to FPGA 2.0